Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2024-07-03 12:19:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1608.31 | 332.63 | 332.63 |
Net Site Energy | 1608.31 | 332.63 | 332.63 |
Total Source Energy | 2484.63 | 513.87 | 513.87 |
Net Source Energy | 2484.63 | 513.87 | 513.87 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1252.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 111.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 62.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 29.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 12.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 355.84 | 1252.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1252.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 3.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 111.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 62.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 29.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 12.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1252.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 111.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 62.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 29.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 12.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 35.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 9.50 | 259.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 73.60 | 259.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 35.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 9.50 | 259.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 73.60 | 259.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 355.845 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 355.845 | 100.00 |
Total On-Site and Utility Electric Sources | 355.845 | 100.00 |
Total Electricity End Uses | 355.845 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 83.67 |
Time Setpoint Not Met During Occupied Cooling | 2.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3067.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| ZONE3 BULK STORAGE_DAYLCTRL | ZONE1 OFFICE_DAYLCTRL |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 17.66 | 6.51 | 0.00 | 0.00 | 11.15 |
Gross Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Above Ground Window-Wall Ratio [%] | 0.71 | 0.76 | 0.00 | 0.00 | 2.86 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 17.66 | 17.66 | 6.9682 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 0.00 | 0.00 | 7.4271 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 3.5521 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 17.66 | 17.66 | 4.8362 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 6.9682 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 7.4271 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 3.5521 | 46.45 | 2.5587 | |
Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 4.8362 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 4.8362 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-JUN-14:00 | 04-JAN-17:00 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 272873.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7744.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8207.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1691.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1379.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 29058.63 | 272873.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 272873.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 7744.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 8207.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 1691.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1379.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1357.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 11.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 352.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 196.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 94.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 39.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1126.96 | 1357.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 280.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 72.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 8.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 233.08 | 280.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 280.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 72.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 40.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 8.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 233.08 | 280.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 0.930047 |
ZONE2 FINE STORAGE DIRECT AIR | 1.55 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 3.64 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 3.64 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 142616.14 |
PSZ-OFFICE HEATING COIL | 26809.73 |
PSZ-FINE STORAGE HEATING COIL | 67573.04 |
User-Specified Heating Design Capacity [W] | |
ZONE3 BULK STORAGE HIRADIANT | 142616.15 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 0.930047 | 0.930047 | 0.930047 | 0.930047 | 0.930047 | 0.930047 | 1.00 | 1.00 | 0.930047 |
PSZ-FINE STORAGE | 1.55 | 1.55 | 1.55 | 1.55 | 1.55 | 1.55 | 1.00 | 1.00 | 1.55 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 0.930047 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 1.55 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 0.930047 | 1029.71 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 1.55 | 1653.96 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 0.930047 | 0.930047 | 0.930047 | 0.930047 | 16601.64 | 26809.73 | 40.00 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 1.55 | 1.55 | 1.55 | 1.02 | 37048.73 | 67573.04 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 0.930050 | 0.465023 | 0.620033 | 16601.64 | 8300.82 | 0.800950 | 0.800950 |
PSZ-FINE STORAGE COOLING COIL | 1.55 | 0.772842 | 1.03 | 37048.73 | 18524.37 | 0.711910 | 0.711910 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 66 | 42 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 128.00 | 17.66 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 727.17 | 0.00 | 11 | 6 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 6.968 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 15.042 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 7.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.427 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 3.552 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 6.111 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 1650.627 | 6.968 | 129.474 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 1650.627 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 10348.979 | 7.427 | 344.966 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 10348.979 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 11383.888 | 3.552 | 164.984 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 11383.888 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 2 | 2 | 0.167 | 0.1685 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
2 | SEMIHEATED_ROOF | 18 | 2 | 2 | 0.167 | 0.2163 | 0.900 | 0.900 | 0.770 | 0.700 | Smooth |
3 | NONRES_EXT_WALL_GRD | 19 | 3 | 4 | 0.167 | 0.3322 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 3 | 4 | 0.167 | 0.5089 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 2.390 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1333 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5514E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 3 | 4 | 0.167 | 0.5089 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.935 |
3 | F08 METAL ROOF SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.622 |
5 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
6 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.911 |
7 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.865 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
12 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
13 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
14 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4184 |
15 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
16 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
18 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
19 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.423 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 18.06 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
30 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
31 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
32 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
33 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
34 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
35 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.865 |
36 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
38 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 2 | 0.11213371E-07 | 0.26651818E-13 | 0.48084804E-13 | 0.0000000 |
2 | 1 | -5.2160876 | 0.60803813E-04 | -0.95086230E-04 | 0.21497930E-08 |
3 | 0 | 5.3845682 | 0.16841986 | 0.16857575 | |
4 | 2 | 0.18741198E-13 | -0.13599760E-18 | 0.18147593E-18 | 0.0000000 |
5 | 1 | -5.2160601 | 0.51384690E-04 | -0.74050972E-04 | 0.35929797E-14 |
6 | 0 | 5.4323994 | 0.21628790 | 0.21641333 | |
7 | 4 | 0.81222167E-12 | -0.60767919E-16 | 0.54071038E-14 | 0.11179850E-15 |
8 | 3 | -0.39493539E-03 | 0.23610490E-06 | -0.57388273E-04 | 0.15583693E-12 |
9 | 2 | 1.7636173 | 0.51065404E-02 | 1.1587674 | -0.75716054E-04 |
10 | 1 | -7.0971751 | 0.13140243 | -17.214859 | 0.33802748 |
11 | 0 | 5.5538614 | 0.83399502E-01 | 16.276058 | |
12 | 4 | 0.77636953E-12 | 0.13455152E-15 | -0.22334287E-14 | 0.11713399E-15 |
13 | 3 | -0.38302667E-03 | 0.35667268E-06 | -0.55544162E-04 | 0.14897333E-12 |
14 | 2 | 1.7355532 | 0.78119255E-02 | 1.1374206 | -0.73432423E-04 |
15 | 1 | -7.1339378 | 0.20261034 | -17.078806 | 0.33263302 |
16 | 0 | 5.7384608 | 0.12927054 | 16.281134 | |
17 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
18 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
19 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
20 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
21 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
22 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
23 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
24 | 0 | 2.3900722 | 2.3900722 | 2.3900722 | |
25 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
26 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
27 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
28 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
29 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
30 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
31 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
32 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
33 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
34 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
35 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
36 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
37 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
38 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
39 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
40 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
41 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
42 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
43 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
44 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
45 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
46 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
47 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
48 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
49 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
50 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
51 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
52 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
53 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
54 | 7 | -0.31875017E-08 | -0.23223167E-14 | 0.11745088E-14 | -0.42051331E-16 |
55 | 6 | 0.38616340E-05 | 0.25494915E-08 | 0.31950331E-02 | -0.26802615E-04 |
56 | 5 | -0.27022284E-03 | 0.15072689E-05 | -0.22401801 | 0.19587403E-02 |
57 | 4 | 0.61670379E-02 | 0.68550054E-04 | 4.8344327 | -0.45311958E-01 |
58 | 3 | -0.54002887E-01 | 0.54467183E-03 | -38.049021 | 0.39895888 |
59 | 2 | 0.19154071 | 0.90547994E-03 | 116.53767 | -1.4186579 |
60 | 1 | -0.27632409 | 0.27557907E-03 | -143.93893 | 2.0495597 |
61 | 0 | 0.13468807 | 0.66882102E-05 | 60.838472 | |
62 | 7 | -0.77687407E-08 | 0.22327722E-15 | -0.37072247E-14 | 0.17899991E-16 |
63 | 6 | 0.20649052E-05 | 0.10720148E-08 | 0.32011002E-02 | -0.26853511E-04 |
64 | 5 | -0.12245401E-03 | 0.62775152E-06 | -0.22436262 | 0.19617821E-02 |
65 | 4 | 0.26426329E-02 | 0.28408139E-04 | 4.8401680 | -0.45367094E-01 |
66 | 3 | -0.22645990E-01 | 0.22478354E-03 | -38.081398 | 0.39931679 |
67 | 2 | 0.79613263E-01 | 0.37221057E-03 | 116.60066 | -1.4195005 |
68 | 1 | -0.11438919 | 0.11271005E-03 | -143.97600 | 2.0501690 |
69 | 0 | 0.55641142E-01 | 0.27215667E-05 | 60.838472 | |
70 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
71 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
72 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
73 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
74 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
75 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
76 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
77 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
78 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
79 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
80 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
81 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
82 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
83 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
84 | 4 | -0.22334287E-14 | 0.13455152E-15 | 0.77636953E-12 | 0.11713399E-15 |
85 | 3 | -0.55544162E-04 | 0.35667268E-06 | -0.38302667E-03 | 0.14897333E-12 |
86 | 2 | 1.1374206 | 0.78119255E-02 | 1.7355532 | -0.73432423E-04 |
87 | 1 | -17.078806 | 0.20261034 | -7.1339378 | 0.33263302 |
88 | 0 | 16.281134 | 0.12927054 | 5.7384608 | |
89 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
90 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
91 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
92 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.292_SHGC_SOUTH_0.399 | 34 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
2 | NONRESWINDOW_U_0.292_SHGC_NORTH_0.399 | 35 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
3 | NONRESWINDOW_U_0.292_SHGC_EAST_0.399 | 36 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
4 | NONRESWINDOW_U_0.292_SHGC_WEST_0.399 | 37 | 1 | VerySmooth | 1.658 | 1.658 | 1.000 | 0.400 | ||
5 | SKYLIGHT_U_0.44_SHGC_0.55 | 38 | 1 | VerySmooth | 2.500 | 2.500 | 1.000 | 0.551 | ||
6 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | 39 | 1 | VerySmooth | 4.262 | 4.262 | 1.000 | 0.555 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 4.24832E-002 | 0.31332 | 0.48955 | 0.48955 | 0.43890 | 0.13405 | 0.17050 | 0.00000 | 0.84000 | 0.84000 | 9.91083E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.79131E-002 | 0.47116 | 0.33239 | 0.33239 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.12208 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.41263 | 0.18041 | 0.18041 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 2.99465E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | ZONE1 OFFICE | 4 | 0 |
2 | ZONE3 BULK STORAGE | 10 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | ZONE1 OFFICE | 0 | |
2 | ZONE3 BULK STORAGE | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.120 | 1.0564 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.099 | 0.553 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 3.833E-002 | 1.618E-004 | 2.498E-004 | 0.137 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.195 | 1.399E-004 | 8.913E-005 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 1.767 | 5.514E-004 | 3.602E-004 | 0.180 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone ZONE1 OFFICE | 1.2000 |
3 | Zone ZONE2 FINE STORAGE | 1.2000 |
4 | Zone ZONE3 BULK STORAGE | 1.2000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.0841E-004 |
2 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.7811E-004 |
3 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.7719E-004 |
4 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
5 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.9272E-004 |
6 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.9875E-004 |
7 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.6913E-004 |
8 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
9 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.0959E-003 |
10 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.2647E-004 |
11 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5984E-003 |
12 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4690E-003 |
13 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 6.1257E-004 |
14 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 5.2431E-004 |
15 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5371E-004 |
16 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
17 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1713E-004 |
18 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.8946E-004 |
19 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.1048E-004 |
20 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R1C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
21 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.4334E-004 |
22 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.1924E-004 |
23 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.6146E-004 |
24 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C1 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
25 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 8.3706E-004 |
26 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 7.7969E-004 |
27 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.3565E-003 |
28 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C2 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
29 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9903E-003 |
30 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.9671E-003 |
31 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.9654E-003 |
32 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C3 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.4690E-003 |
33 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.8296E-004 |
34 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 9.5084E-004 |
35 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.5174E-003 |
36 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C4 | ZONE3 BULK STORAGE_DAYLREFPT1 | 1.4373E-003 |
37 | Clear Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.8206E-004 |
38 | Clear Turbid Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 2.6317E-004 |
39 | Intermediate Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 4.1051E-004 |
40 | Overcast Sky | 01/21 | ZONE3 BULK STORAGE_DAYLCTRL | ZONE3 BULK STORAGE | SKYLIGHT_R2C5 | ZONE3 BULK STORAGE_DAYLREFPT1 | 3.2088E-004 |
41 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 6.2411E-003 |
42 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 7.4277E-004 |
43 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.6073E-003 |
44 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.6923E-004 |
45 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 5.3203E-003 |
46 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 6.3341E-004 |
47 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT1 | 3.1365E-003 |
48 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW 1 | ZONE1 OFFICE_DAYLREFPT2 | 5.5007E-004 |
49 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.6395E-004 |
50 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 6.9722E-003 |
51 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 7.1019E-004 |
52 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.8870E-003 |
53 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.4665E-004 |
54 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 5.7703E-003 |
55 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 5.4383E-004 |
56 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE FRONT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.2177E-003 |
57 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 6.1282E-003 |
58 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 4.3684E-004 |
59 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 4.6324E-003 |
60 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.4442E-004 |
61 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.1053E-003 |
62 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 2.5528E-004 |
63 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT1 | 3.9351E-003 |
64 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW1 | ZONE1 OFFICE_DAYLREFPT2 | 3.3514E-004 |
65 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 6.3939E-003 |
66 | Clear Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 4.3777E-004 |
67 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 4.7665E-003 |
68 | Clear Turbid Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.4492E-004 |
69 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 2.8610E-003 |
70 | Intermediate Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 2.5474E-004 |
71 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT1 | 3.9350E-003 |
72 | Overcast Sky | 01/21 | ZONE1 OFFICE_DAYLCTRL | ZONE1 OFFICE | OFFICE LEFT WALL WINDOW2 | ZONE1 OFFICE_DAYLREFPT2 | 3.3514E-004 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 9027.11339 | 10832.53607 | 0.77504 | 0.93005 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36400 | 1.27228E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 10333.39961 | 12400.07954 | 0.30268 | 0.36322 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -32.70000 | 1.83376E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 19245.30688 | 23094.36826 | 1.28807 | 1.54568 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 29.85200 | 1.27254E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 30993.27858 | 37191.93430 | 0.76474 | 0.91769 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -32.70000 | 1.83376E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 29.97600 | 1.27256E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 118846.78909 | 142616.14691 | 3.03012 | 3.63615 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13379.72 | 0.93005 | 0.93005 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 14355.62 | 0.36322 | 0.36322 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 27988.12 | 1.54568 | 1.54568 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 49774.35 | 0.91769 | 0.91769 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.93005 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54568 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.63615 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 3.63615 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 142616.13831 |
6 | ZoneHVAC:HighTemperatureRadiant | ZONE3 BULK STORAGE HIRADIANT | User-Specified Heating Design Capacity [W] | 142616.14691 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.93005 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.93005 |
9 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.93005 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 0.93005 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.93005 |
12 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 0.93005 |
13 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.54568 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.54568 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.54568 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.54568 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.54568 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 1.54568 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
23 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 0.93005 |
24 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 1.54568 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.93005 |
26 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.93005 |
28 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1029.70948 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.93005 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.93005 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.93005 |
32 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.93005 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.93005 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.46502 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.62003 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16601.64000 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 8300.82000 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80095 |
39 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80095 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16601.64000 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26809.72511 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
43 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
44 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 26809.72511 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.54568 |
46 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.54568 |
48 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 1653.95576 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.54568 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.54568 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.54568 |
52 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02015 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.54568 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.77284 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.03045 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 37048.73000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18524.36500 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71191 |
59 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71191 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37048.73000 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 67573.03892 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
63 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
64 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 67573.03892 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 15879.8 | 11.64 | 11.38 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 35847.5 | 12.20 | 11.92 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.4307272729 | 0.3992049031 | Pass | Pass | 1.4287776635 | 2.9418033296 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.7862919245 | 0.7083477640 | Pass | Pass | 0.7041048922 | 0.6406840318 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 7.6051733360E-005 | 1.3610305670E-004 | Pass | Pass | 1.9215686380E-002 | 1.6215134696E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7574.25 | 648.73 | 0.00 | 107.47 | 307.39 | 8637.88 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.316 | 0.332 | 110.54 | 97.44 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.316 | 0.332 | 39.02 | 30.56 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.131 | 0.133 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.316 | 0.332 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.316 | 0.332 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.316 | 0.332 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.316 | 0.332 | 110.54 | 110.54 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.316 | 0.332 | 39.02 | 39.02 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.055 | 0.055 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.23 | 0.165 | 0.168 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.473 | 0.509 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.473 | 0.509 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.473 | 0.509 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.23 | 0.210 | 0.216 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.454 | 0.509 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.454 | 0.509 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.292_SHGC_WEST_0.399 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.658 | 0.400 | 0.440 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.292_SHGC_WEST_0.399 | 5.58 | 0.00 | 0.00 | 5.58 | 5.58 | 1.658 | 0.400 | 0.440 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.292_SHGC_NORTH_0.399 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.658 | 0.400 | 0.440 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.292_SHGC_NORTH_0.399 | 3.25 | 0.00 | 0.00 | 3.25 | 3.25 | 1.658 | 0.400 | 0.440 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.75_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.262 | 0.555 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.099 | 0.553 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 32.53 | 2.848 | 0.471 | 0.491 | |||||||||||||||||
North Total or Average | 6.51 | 1.658 | 0.400 | 0.440 | |||||||||||||||||
Non-North Total or Average | 26.02 | 3.146 | 0.488 | 0.504 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 1.760 | 2.390 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 1.760 | 2.390 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 2.101 | 3.065 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 6.9682 | 236.88 | 1650.63 | LightsWired | LTG_SCH_OFFICE | 52.33 | 168.00 | 31.78 | 0.0000 | Y | 9.85 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 7.4271 | 1393.41 | 10348.98 | LightsWired | LTG_SCH_FINE_STORAGE | 27.11 | 168.00 | 25.09 | 0.0000 | Y | 48.75 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 3.5521 | 3204.84 | 11383.89 | LightsWired | LTG_SCH_BULK_STORAGE | 27.11 | 168.00 | 24.63 | 0.0000 | Y | 52.64 |
Interior Lighting Total | 4.8362 | 4835.13 | 23383.49 | 111.24 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
ZONE3 BULK STORAGE_DAYLREFPT1 | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE_DAYLCTRL | SplitFlux | Continuous/Off | 0.12 | 11383.89 | 1320.53 |
ZONE1 OFFICE_DAYLREFPT1 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.29 | 1650.63 | 478.68 |
ZONE1 OFFICE_DAYLREFPT2 | ZONE1 OFFICE | ZONE1 OFFICE_DAYLCTRL | SplitFlux | Continuous/Off | 0.10 | 1650.63 | 165.06 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 123.84 | AstronomicalClock | - | 42.55 | 42.55 | 0.99 | |
EXTERIOR_LIGHTS_B | 4305.62 | AstronomicalClock | - | 83.52 | 63.04 | 50.95 | |
EXTERIOR_LIGHTS_C | 1091.36 | AstronomicalClock | - | 83.52 | 49.92 | 10.23 | |
Exterior Lighting Total | 5520.82 | 62.16 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16601.64 | 13297.08 | 3304.56 | 0.80 | 3.82 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 37048.73 | 26375.36 | 10673.37 | 0.71 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 15879.8 | 11.64 | 11.38 | ||||
PSZ-FINE STORAGE COOLING COIL | 35847.5 | 12.20 | 11.92 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 142616.14 | 0.80 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 26809.73 | 0.81 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 67573.04 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 49.80 | 3.64 | 337.84 | 92.91 | 1.00 | 3.27 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.56 | 622.50 | 0.93 | 1029.71 | 1107.16 | 1.00 | 1.42 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 622.50 | 1.55 | 1653.96 | 1070.05 | 1.00 | 1.36 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.12 | 1.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 9027.11 | 10832.54 | 45.73 | 0.775 | 0.930 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00845 | 28.36 | 0.01272 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 19245.31 | 23094.37 | 16.57 | 1.288 | 1.546 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 26.70 | 26.70 | 0.00901 | 29.85 | 0.01273 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 30.23 | 0.01279 | 29.98 | 0.01273 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 10333.40 | 12400.08 | 52.35 | 0.303 | 0.363 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00802 | -32.70 | 0.00018 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 30993.28 | 37191.93 | 26.69 | 0.765 | 0.918 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00713 | -32.70 | 0.00018 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 118846.79 | 142616.15 | 44.50 | 3.030 | 3.636 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00597 | -32.70 | 0.00018 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.93 | 0.93 | 0.36 | 0.36 | 0.9300 | 0.9300 | 0.9300 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 1.55 | 1.55 | 0.92 | 0.92 | 1.5457 | 1.5457 | 1.5457 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | 142616.138 | 142616.138 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 142616.14 | 142616.14 | 3.636148 | 10.00 | 7.82 | 0.00597049 | 43.33 | 21.64 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 10.00 | 0.00597049 | 75.1843 | 142616.15 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 16601.640 | 13297.084 | 0.930050 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 8300.82 | 7218.87 | 0.620033 | 25.37 | 16.78 | 0.00891810 | 12.00 | 10.89 | 0.00800000 | 28.69 | 0.01272339 | 20.72 | 16.4966 | 23.90 | 0.00844703 | 43.8441 | 9012.55 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 26809.725 | 26809.725 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 26809.73 | 26809.73 | 0.930047 | 15.14 | 11.34 | 0.00715998 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 10.9978 | 21.10 | 0.00802207 | 49.3906 | 10333.40 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 37048.730 | 26375.361 | 1.545680 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 18524.37 | 14519.07 | 1.030453 | 28.54 | 18.70 | 0.01003549 | 12.00 | 10.89 | 0.00800000 | 30.10 | 0.01272586 | 21.13 | 41.2160 | 26.70 | 0.00901457 | 39.5775 | 19223.51 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 67573.039 | 67573.039 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 67573.04 | 67573.04 | 1.545685 | 2.30 | 2.30 | 0.00521878 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 27.4772 | 15.56 | 0.00712657 | 62.2188 | 30993.28 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER or ZONEHVAC:HIGHTEMPERATURERADIANT | ZONE3 BULK STORAGE UNIT HEATER or ZONE3 BULK STORAGE HIRADIANT | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 142616.138 | 142616.138 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 3.636148 | 4.19584122 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 142616.14 | 142616.14 | 1.0000 | 4.19584122 | 3.636148 | 10.00 | 7.82 | 0.00597049 | 25088.4 | 43.33 | 21.64 | 0.00800000 | 64191.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 142616.14 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 10.00 | 0.00597049 | 10.00 | 0.00597049 | 75.1843 | 142616.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16601.640 | 13297.084 | 0.930050 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4183 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.930047 | 1.07320416 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 8300.82 | 7218.87 | 1.0000 | 0.71547188 | 0.620033 | 25.37 | 16.78 | 0.00891810 | 48213.1 | 12.00 | 10.89 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8300.82 | 28.69 | 0.01272339 | 20.72 | 0.10228463 | 16.4966 | 23.90 | 0.00844703 | 23.90 | 0.00844703 | 43.8441 | 9012.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26809.725 | 26809.725 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.930047 | 1.07320416 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 26809.73 | 26809.73 | 1.0000 | 1.07320416 | 0.930047 | 15.14 | 11.34 | 0.00715998 | 33321.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26809.73 | -32.70 | 0.00018338 | -32.70 | 0.10228463 | 10.9978 | 21.05 | 0.00802207 | 21.10 | 0.00802207 | 49.3906 | 10333.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 37048.730 | 26375.361 | 1.545680 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4955 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.545685 | 1.78360406 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 18524.37 | 14519.07 | 1.0000 | 1.18906571 | 1.030453 | 28.54 | 18.70 | 0.01003549 | 54308.5 | 12.00 | 10.89 | 0.00800000 | 32244.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18524.37 | 30.10 | 0.01272586 | 21.13 | 0.42471127 | 41.2160 | 26.70 | 0.00901457 | 26.70 | 0.00901457 | 39.5775 | 19223.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 67573.039 | 67573.039 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.545685 | 1.78360406 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 67573.04 | 67573.04 | 1.0000 | 1.78360406 | 1.545685 | 2.30 | 2.30 | 0.00521878 | 15382.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 67573.04 | -32.70 | 0.00018338 | -32.70 | 0.42471127 | 27.4772 | 15.56 | 0.00712657 | 15.56 | 0.00712657 | 62.2188 | 30993.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | DifferentialDryBulb | 0.10 | 0.93 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | DifferentialDryBulb | 0.42 | 1.55 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2792.17 | 3087.17 | 2398.67 |
ZONE2 FINE STORAGE | 3135.67 | 3267.17 | 2850.00 |
ZONE3 BULK STORAGE | 3210.00 | 3355.83 | 2973.00 |
Facility | 3328.17 | 3415.00 | 3067.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 135.50 | 2.17 | 64.50 | 2.17 |
ZONE2 FINE STORAGE | 535.17 | 0.83 | 24.50 | 0.00 |
ZONE3 BULK STORAGE | 14.83 | 0.00 | 10.33 | 0.00 |
Facility | 632.17 | 3.00 | 83.67 | 2.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.620 | 0.248 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.445 | 0.110 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.099 | 0.000 | 0.057 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.47 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.29 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.47 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.29 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.27 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.04 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2231190.36 | 0.00 | 2231190.36 | 1221616.71 | 3452807.07 | 3225648.14 | 5693.42 | 2361.75 | 704.83 | 0.00 |
ZONE2 FINE STORAGE | 4759996.01 | 0.00 | 4759996.01 | 2972779.81 | 7732775.82 | 13393694.68 | 5729.75 | 2913.83 | 116.42 | 0.25 |
ZONE3 BULK STORAGE | 0.00 | 15949858.85 | 15949858.85 | 25107799.64 | 41057658.49 | 30805497.77 | 8272.00 | 55.83 | 432.17 | 4777.50 |
Total Facility | 6991186.36 | 15949858.85 | 22941045.22 | 29302196.16 | 52243241.37 | 47424840.58 | 8505.67 | 3026.83 | 1194.00 | 4777.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.1705 | 0.0000 | 0.1705 | 0.0688 | 0.2393 | 0.1023 | 569.42 | 2361.75 | 704.83 |
ZONE2 FINE STORAGE | 0.3636 | 0.0000 | 0.3636 | 0.0901 | 0.4537 | 0.4247 | 606.00 | 2913.83 | 116.17 |
ZONE3 BULK STORAGE | 0.0000 | 0.5637 | 0.5637 | 0.9802 | 1.5439 | 0.9768 | 3366.17 | 27.83 | 242.00 |
Total Facility | 0.5340 | 0.5637 | 1.0977 | 1.1392 | 2.2369 | 1.5038 | 3381.67 | 2998.83 | 1003.58 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 2970924.95 | 0.00 | 2970924.95 | 3225648.14 | 5690.69 | 0.00 | 3069.31 | 0.00 |
PSZ-FINE STORAGE | 6338438.23 | 0.00 | 6338438.23 | 13393694.68 | 5729.75 | 0.00 | 3030.25 | 0.25 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2270 | 0.0000 | 0.2270 | 0.1023 | 566.69 | 0.00 | 3069.31 |
PSZ-FINE STORAGE | 0.4842 | 0.0000 | 0.4842 | 0.4247 | 606.00 | 0.00 | 3030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2710.14 | 367.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 3006.08 | 24.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2380 | 0.4914 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5796 | 0.7796 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 14 | 14 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 400 |
Defaulted Fields | 319 |
Fields with Defaults | 1041 |
Autosized Fields | 43 |
Autosizable Fields | 97 |
Autocalculated Fields | 92 |
Autocalculatable Fields | 134 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 355.84 | 1261.11 | 23-JUL-10:10 | 29058.63 | 30-JUN-15:00 |
Electricity:Building | 247.74 | 1261.11 | 08-JAN-11:00 | 19057.86 | 15-NOV-16:00 |
Electricity:Zone:ZONE1 OFFICE | 39.01 | 520.87 | 01-JAN-00:10 | 2846.16 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 247.74 | 1261.11 | 08-JAN-11:00 | 19057.86 | 15-NOV-16:00 |
InteriorLights:Electricity | 111.24 | 791.24 | 08-JAN-11:00 | 9022.68 | 15-NOV-16:00 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 9.85 | 51.00 | 01-JAN-00:10 | 1011.11 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 111.24 | 791.24 | 08-JAN-11:00 | 9022.68 | 15-NOV-16:00 |
LightsWired:InteriorLights:Electricity | 111.24 | 791.24 | 08-JAN-11:00 | 9022.68 | 15-NOV-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 9.85 | 51.00 | 01-JAN-00:10 | 1011.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 111.24 | 791.24 | 08-JAN-11:00 | 9022.68 | 15-NOV-16:00 |
Electricity:Zone:ZONE2 FINE STORAGE | 48.75 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 48.75 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 48.75 | 299.97 | 01-JAN-00:10 | 3848.58 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 159.99 | 440.27 | 08-JAN-11:00 | 12401.25 | 20-DEC-16:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 52.64 | 440.27 | 08-JAN-11:00 | 4201.13 | 20-DEC-16:00 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 52.64 | 440.27 | 08-JAN-11:00 | 4201.13 | 20-DEC-16:00 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 29.68 | 0.00 | 19-MAR-13:10 | 2768.34 | 04-JAN-08:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 355.84 | 1261.11 | 23-JUL-10:10 | 29058.63 | 30-JUN-15:00 |
ElectricityPurchased:Plant | 355.84 | 1261.11 | 23-JUL-10:10 | 29058.63 | 30-JUN-15:00 |
Cogeneration:ElectricityPurchased | 355.84 | 1261.11 | 23-JUL-10:10 | 29058.63 | 30-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 355.84 | 1261.11 | 23-JUL-10:10 | 29058.63 | 30-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 355.84 | 1261.11 | 23-JUL-10:10 | 29058.63 | 30-JUN-15:00 |
ElectricityNet:Plant | 355.84 | 1261.11 | 23-JUL-10:10 | 29058.63 | 30-JUN-15:00 |
Cogeneration:ElectricityNet | 355.84 | 1261.11 | 23-JUL-10:10 | 29058.63 | 30-JUN-15:00 |
General:Cogeneration:ElectricityNet | 355.84 | 1261.11 | 23-JUL-10:10 | 29058.63 | 30-JUN-15:00 |
Electricity:HVAC | 33.42 | 0.00 | 19-MAR-13:10 | 10023.20 | 29-JUN-16:00 |
General:Fans:Electricity | 29.68 | 0.00 | 19-MAR-13:10 | 2768.34 | 04-JAN-08:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 3.74 | 0.00 | 01-JAN-00:10 | 8314.35 | 29-JUN-16:00 |
General:Cooling:Electricity | 3.74 | 0.00 | 01-JAN-00:10 | 8314.35 | 29-JUN-16:00 |
ExteriorLights:Electricity | 62.16 | 0.00 | 01-JAN-08:20 | 5520.82 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 62.16 | 0.00 | 01-JAN-08:20 | 5520.82 | 01-JAN-06:10 |
Electricity:Plant | 12.52 | 0.00 | 02-JAN-00:30 | 1852.17 | 24-FEB-13:00 |
WaterSystems:Electricity | 12.52 | 0.00 | 02-JAN-00:30 | 1852.17 | 24-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 12.52 | 0.00 | 02-JAN-00:30 | 1852.17 | 24-FEB-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1252.47 | 0.00 | 19-MAR-13:10 | 272873.53 | 04-JAN-18:00 |
NaturalGas:HVAC | 1252.47 | 0.00 | 19-MAR-13:10 | 272873.53 | 04-JAN-18:00 |
Heating:NaturalGas | 1252.47 | 0.00 | 19-MAR-13:10 | 272873.53 | 04-JAN-18:00 |
General:Heating:NaturalGas | 1252.47 | 0.00 | 19-MAR-13:10 | 272873.53 | 04-JAN-18:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1919.68 | 0.00 | 19-MAR-13:10 | 405618.98 | 04-JAN-18:00 |
EnergyTransfer:Building | 938.02 | 0.00 | 19-MAR-13:10 | 200890.98 | 04-JAN-07:10 |
EnergyTransfer:Zone:ZONE1 OFFICE | 62.91 | 0.00 | 01-JAN-00:40 | 25826.85 | 14-FEB-07:10 |
Heating:EnergyTransfer | 910.93 | 0.00 | 19-MAR-13:10 | 200890.98 | 04-JAN-07:10 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 51.71 | 0.00 | 01-JAN-00:40 | 25826.85 | 14-FEB-07:10 |
General:Heating:EnergyTransfer | 910.93 | 0.00 | 19-MAR-13:10 | 200890.98 | 04-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 51.71 | 0.00 | 01-JAN-00:40 | 25826.85 | 14-FEB-07:10 |
Cooling:EnergyTransfer | 27.09 | 0.00 | 01-JAN-00:10 | 16829.45 | 30-JUN-15:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 11.20 | 0.00 | 01-JAN-00:10 | 7180.01 | 29-JUN-16:10 |
General:Cooling:EnergyTransfer | 27.09 | 0.00 | 01-JAN-00:10 | 16829.45 | 30-JUN-15:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 11.20 | 0.00 | 01-JAN-00:10 | 7180.01 | 29-JUN-16:10 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 171.09 | 0.00 | 01-JAN-00:40 | 42822.83 | 24-DEC-08:10 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 155.20 | 0.00 | 01-JAN-00:40 | 42822.83 | 24-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 155.20 | 0.00 | 01-JAN-00:40 | 42822.83 | 24-DEC-08:10 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 15.90 | 0.00 | 01-JAN-00:10 | 10200.81 | 23-JUL-16:40 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 15.90 | 0.00 | 01-JAN-00:10 | 10200.81 | 23-JUL-16:40 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 704.01 | 0.00 | 17-JAN-13:10 | 143665.80 | 04-JAN-12:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 704.01 | 0.00 | 17-JAN-13:10 | 143665.80 | 04-JAN-12:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 704.01 | 0.00 | 17-JAN-13:10 | 143665.80 | 04-JAN-12:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 981.66 | 0.00 | 19-MAR-13:10 | 215286.40 | 04-JAN-18:00 |
HeatingCoils:EnergyTransfer | 965.24 | 0.00 | 19-MAR-13:10 | 215286.40 | 04-JAN-18:00 |
CoolingCoils:EnergyTransfer | 16.42 | 0.00 | 01-JAN-00:10 | 34132.21 | 30-JUN-15:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 51.713 | -11.197 | 0.000 | 0.000 | 10.190 | 9.846 | 29.165 | 10.715 | 0.000 | 0.248 | 0.000 | 0.000 | -9.665 | 0.000 | -25.538 | -65.478 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 155.198 | -15.896 | 0.000 | 0.000 | 27.531 | 48.748 | 0.000 | 0.000 | 0.000 | 0.305 | 0.001 | 0.000 | 0.000 | 0.000 | -53.984 | -161.901 |
ZONE3 BULK STORAGE | 704.014 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 70.534 | 52.642 | 107.344 | 110.998 | 0.000 | 11.145 | 0.000 | 0.000 | -81.881 | 0.000 | -555.095 | -419.701 |
Total Facility | 704.014 | 0.000 | 206.910 | -27.093 | 0.000 | 0.000 | 108.255 | 111.236 | 136.508 | 121.713 | 0.000 | 11.698 | 0.001 | 0.000 | -91.546 | 0.000 | -634.617 | -647.079 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 01-JUL-05:02 | 0.00 | 0.00 | 0.00 | -19837.61 | 0.00 | 0.00 | 88.84 | 51.00 | 550.52 | 69.31 | 0.00 | 0.00 | 19238.60 | 0.00 | -0.00 | 0.00 | -160.65 | 0.00 |
ZONE2 FINE STORAGE | 24-JUL-17:12 | 0.00 | 0.00 | 0.00 | -28073.73 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 200.72 | 27573.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-17:12 | 0.00 | 0.00 | 0.00 | -28073.73 | 0.00 | 0.00 | 0.00 | 818.71 | 2519.91 | 14642.46 | 0.00 | 862.80 | 9229.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 30-OCT-05:32 | 0.00 | 0.00 | 28132.04 | 0.00 | 0.00 | 0.00 | 136.46 | 302.02 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -698.88 | 0.00 | -1224.29 | -27197.86 |
ZONE2 FINE STORAGE | 24-DEC-08:62 | 0.00 | 0.00 | 69989.41 | 0.00 | 0.00 | 0.00 | 0.00 | 299.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7748.45 | -62540.92 |
ZONE3 BULK STORAGE | 04-JAN-12:00 | 143665.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8518.59 | 3972.80 | 8200.12 | 268.87 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -163086.18 | -1539.56 |
Total Facility | 04-JAN-20:42 | 143226.53 | 0.00 | 97206.44 | 0.00 | 0.00 | 0.00 | 0.00 | 849.01 | 2519.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11639.98 | 0.00 | -110070.58 | -122091.32 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9300 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9300 | 0.1100 | 1.0000 | Not calculated | 0.1023 | 0.1100 | ||
PSZ-FINE STORAGE | 1.5457 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.5457 | 0.2748 | 1.0000 | Not calculated | 0.4247 | 0.2748 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 0.9300 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 0.9300 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.1100 | ||
PSZ-FINE STORAGE | 1.5457 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 1.5457 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.2748 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9300 | 0.9300 | 0.9300 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5457 | 1.5457 | 1.5457 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9300 | 0.9300 | 0.9300 | 0.9300 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.5457 | 1.5457 | 1.5457 | 1.5457 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9300 | 0.9300 | 0.9300 | No | 0.1023 | 0.2816 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5457 | 1.5457 | 1.5457 | No | 0.4247 | 0.4628 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 0.9300 | 0.9300 | 0.9300 | 0.9300 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 1.5457 | 1.5457 | 1.5457 | 1.5457 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 83.67 |
Number of hours cooling loads not met | 2.17 |
Number of hours not met | 85.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1252.47 | 272873.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3.74 | 8314.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 111.24 | 9022.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 62.16 | 5520.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 29.68 | 2768.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 12.52 | 1852.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 355.84 |
Natural Gas | 0.00 | 1252.47 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 1608.31 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 23.01 |
Space Heating | 0.00 |
Space Cooling | 0.77 |
Fans (All) | 6.14 |
Service Water Heating | 2.59 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 73.60 |
Subtotal | 73.60 |
Natural Gas [MJ/m2] | |
Space Heating | 259.03 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 259.03 |
Subtotal | 259.03 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.92 |
Space Heating | 77.87 |
Space Cooling | 0.23 |
Fans (All) | 1.85 |
Service Water Heating | 0.78 |
Receptacle Equipment | 8.49 |
Miscellaneous | 3.87 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 2729. | 8760. |
LTG_SCH_BULK_STORAGE | 1414. | 8760. |
LTG_SCH_FINE_STORAGE | 1414. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8627.17 | 132.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8471.17 | 288.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8584.00 | 176.00 | 0.00 | 0.00 | 0.00 |
Min | 8471.17 | 132.83 | 0.00 | 0.00 | 0.00 |
Max | 8627.17 | 288.83 | 0.00 | 0.00 | 0.00 |
Average | 8560.78 | 199.22 | 0.00 | 0.00 | 0.00 |
Sum | 25682.33 | 597.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 76938.00 | 5781.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 184164.00 | 7029.00 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 184164.00 | 7029.00 | 0.00 | 0.00 | 0.00 |
Average | 98043.00 | 4270.00 | 0.00 | 0.00 | 0.00 |
Sum | 294129.00 | 12810.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8110.83 | 649.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7764.33 | 995.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7957.67 | 802.33 | 0.00 | 0.00 | 0.00 |
Min | 7764.33 | 649.17 | 0.00 | 0.00 | 0.00 |
Max | 8110.83 | 995.67 | 0.00 | 0.00 | 0.00 |
Average | 7944.28 | 815.72 | 0.00 | 0.00 | 0.00 |
Sum | 23832.83 | 2447.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 31820.67 | 1206.33 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 70280.00 | 12439.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 169321.67 | 21871.33 | 0.00 | 0.00 | 0.00 |
Min | 31820.67 | 1206.33 | 0.00 | 0.00 | 0.00 |
Max | 169321.67 | 21871.33 | 0.00 | 0.00 | 0.00 |
Average | 90474.11 | 11838.89 | 0.00 | 0.00 | 0.00 |
Sum | 271422.33 | 35516.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:42
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 8760.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 8760.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 8760.00 | 8760.00 | 0.00 |
Average | 0.00 | 2920.00 | 2920.00 | 0.00 |
Sum | 0.00 | 8760.00 | 8760.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
ZONE1 OFFICE | 0.00 | 0.00 | 33027.00 | 0.00 |
ZONE2 FINE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 191193.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 191193.00 | 33027.00 | 0.00 |
Average | 0.00 | 63731.00 | 11009.00 | 0.00 |
Sum | 0.00 | 191193.00 | 33027.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2019
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -21.9 | -22.1 | 0.497043E+09 | 603.25 | 12-JAN-08:09 | -19.0 | -19.5 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -23.1 | -23.5 | 0.457282E+09 | 603.25 | 18-FEB-08:09 | -8.0 | -8.4 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 | -3.3 | 0.536828E+09 | 603.25 | 10-MAR-08:09 | -9.7 | -10.0 |
April | 1207305.90 | 238.09 | 20-APR-15:00 | 10.00 | 2.60 | 0.500605E+09 | 708.50 | 13-APR-15:00 | 10.00 | 2.60 |
May | 0.566102E+09 | 3811.95 | 25-MAY-16:00 | 29.10 | 19.63 | 0.589955E+09 | 769.00 | 26-MAY-13:00 | 21.50 | 16.64 |
June | 0.198587E+10 | 14520.93 | 28-JUN-05:03 | 15.15 | 14.73 | 0.650134E+09 | 769.01 | 29-JUN-08:09 | 23.48 | 20.03 |
July | 0.404551E+10 | 19847.87 | 01-JUL-05:02 | 9.78 | 9.47 | 0.634671E+09 | 769.02 | 25-JUL-15:30 | 20.25 | 19.33 |
August | 0.343780E+10 | 16947.17 | 07-AUG-05:03 | 13.80 | 12.30 | 0.684575E+09 | 769.02 | 07-AUG-14:50 | 21.73 | 18.87 |
September | 0.112180E+10 | 18538.08 | 02-SEP-05:03 | 13.80 | 10.55 | 0.591885E+09 | 769.02 | 01-SEP-09:00 | 13.80 | 10.55 |
October | 38476584.88 | 638.86 | 03-OCT-14:00 | 7.20 | 4.48 | 0.505737E+09 | 768.97 | 21-OCT-15:00 | 20.00 | 11.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 | 0.477605E+09 | 642.80 | 01-NOV-15:00 | 17.80 | 13.26 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.496975E+09 | 603.25 | 30-DEC-08:09 | -4.6 | -5.3 |
Annual Sum or Average | 0.111968E+11 | 0.662330E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.457282E+09 | 603.25 | -19.0 | -19.5 | ||
Maximum of Months | 0.404551E+10 | 19847.87 | 29.10 | 19.63 | 0.684575E+09 | 769.02 | 23.48 | 20.03 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -21.9 | -22.1 | 0.649190E+09 | 787.42 | 31-JAN-11:39 | -16.3 | -16.8 |
February | 0.184528E+09 | 3987.61 | 08-FEB-14:00 | 5.00 | -0.5 | 0.597326E+09 | 787.42 | 09-FEB-11:09 | -7.1 | -7.9 |
March | 0.627747E+09 | 5639.76 | 23-MAR-14:00 | 0.00 | -4.3 | 0.702285E+09 | 879.54 | 31-MAR-15:09 | 8.40 | 2.82 |
April | 0.141812E+10 | 8270.21 | 05-APR-11:20 | -3.3 | -6.6 | 0.707366E+09 | 1216.41 | 13-APR-15:00 | 20.00 | 8.11 |
May | 0.157447E+10 | 5737.86 | 20-MAY-07:10 | 6.20 | 3.46 | 0.112405E+10 | 2116.58 | 25-MAY-15:00 | 29.10 | 19.63 |
June | 0.155065E+10 | 25278.62 | 30-JUN-17:12 | 30.73 | 21.04 | 0.151165E+10 | 2246.88 | 30-JUN-12:30 | 30.73 | 21.04 |
July | 0.282383E+10 | 28073.07 | 24-JUL-17:12 | 28.70 | 19.19 | 0.176567E+10 | 2246.89 | 24-JUL-14:30 | 28.70 | 19.19 |
August | 0.222353E+10 | 5263.82 | 09-AUG-14:40 | 27.60 | 21.71 | 0.177190E+10 | 2246.81 | 11-AUG-12:30 | 23.60 | 18.33 |
September | 0.261116E+10 | 7964.64 | 06-SEP-07:05 | 4.05 | 3.63 | 0.119661E+10 | 2246.80 | 01-SEP-12:30 | 4.05 | 3.63 |
October | 0.223076E+10 | 6849.08 | 04-OCT-07:05 | 0.37 | 0.10 | 0.727149E+09 | 1302.91 | 21-OCT-15:09 | 20.00 | 11.21 |
November | 0.651420E+09 | 8795.27 | 07-NOV-10:55 | -4.4 | -6.6 | 0.631784E+09 | 1034.65 | 01-NOV-15:09 | -4.4 | -6.6 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.649265E+09 | 787.42 | 09-DEC-10:39 | -13.9 | -14.5 |
Annual Sum or Average | 0.158962E+11 | 0.120342E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -21.9 | -22.1 | 0.597326E+09 | 787.42 | -16.3 | -16.8 | ||
Maximum of Months | 0.282383E+10 | 28073.07 | 30.73 | 21.71 | 0.177190E+10 | 2246.89 | 30.73 | 21.04 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -21.9 | -22.1 | 0.640032E+09 | 793.30 | 27-JAN-14:20 | -14.4 | -15.6 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -23.1 | -23.5 | 0.595079E+09 | 879.87 | 08-FEB-14:39 | 5.00 | -0.5 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -1.3 | -3.3 | 0.711041E+09 | 1021.86 | 23-MAR-14:20 | 0.20 | -4.3 |
April | 0.00 | 0.00 | 01-APR-00:05 | 3.52 | 0.38 | 0.829361E+09 | 1701.99 | 18-APR-14:09 | 17.33 | 10.22 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -0.0 | -1.4 | 0.183346E+10 | 3640.99 | 25-MAY-15:39 | 29.03 | 19.64 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.305313E+10 | 5880.90 | 30-JUN-15:30 | 31.95 | 24.59 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 | 13.57 | 0.406861E+10 | 5987.07 | 24-JUL-15:20 | 29.23 | 19.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 | 15.36 | 0.389248E+10 | 5415.29 | 08-AUG-15:00 | 30.60 | 22.99 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 | 18.15 | 0.248403E+10 | 5105.24 | 01-SEP-15:00 | 26.10 | 17.64 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.105810E+10 | 2206.63 | 02-OCT-13:39 | 10.37 | 9.55 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 | 0.51 | 0.658858E+09 | 1358.76 | 01-NOV-14:39 | 18.13 | 13.38 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -8.8 | -9.9 | 0.642717E+09 | 780.45 | 02-DEC-16:30 | -19.1 | -19.7 |
Annual Sum or Average | 0.00 | 0.204669E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.595079E+09 | 780.45 | -19.1 | -19.7 | ||
Maximum of Months | 0.00 | 0.00 | 19.75 | 18.15 | 0.406861E+10 | 5987.07 | 31.95 | 24.59 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112325E+11 | 27542.71 | 04-JAN-06:11 | -29.1 |
February | 0.864575E+10 | 28074.47 | 08-FEB-06:32 | -4.8 |
March | 0.799163E+10 | 28089.73 | 22-MAR-05:32 | -2.6 |
April | 0.431967E+10 | 28106.59 | 27-APR-05:32 | -3.7 |
May | 0.109905E+10 | 27117.81 | 01-MAY-05:01 | -3.4 |
June | 0.116403E+09 | 16899.58 | 01-JUN-05:03 | 14.08 |
July | 23262945.18 | 1304.32 | 27-JUL-06:10 | 12.25 |
August | 54203773.40 | 1271.31 | 07-AUG-06:10 | 13.40 |
September | 0.352781E+09 | 26972.23 | 29-SEP-05:01 | 7.20 |
October | 0.271840E+10 | 28131.74 | 30-OCT-05:32 | -9.6 |
November | 0.533351E+10 | 27290.22 | 29-NOV-06:12 | -20.0 |
December | 0.982650E+10 | 27538.35 | 26-DEC-06:11 | -26.6 |
Annual Sum or Average | 0.517137E+11 | |||
Minimum of Months | 23262945.18 | 1271.31 | -29.1 | |
Maximum of Months | 0.112325E+11 | 28131.74 | 14.08 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388256E+11 | 69989.01 | 04-JAN-20:42 | -29.4 |
February | 0.279918E+11 | 69930.12 | 12-FEB-22:42 | -16.8 |
March | 0.217221E+11 | 69303.68 | 15-MAR-04:22 | -21.9 |
April | 0.881878E+10 | 68227.52 | 05-APR-03:42 | -12.2 |
May | 0.886423E+09 | 68110.06 | 03-MAY-05:01 | 2.97 |
June | 0.130757E+09 | 1882.16 | 24-JUN-17:00 | 29.40 |
July | 51234156.28 | 662.38 | 11-JUL-16:40 | 26.30 |
August | 64292534.09 | 680.45 | 31-AUG-07:00 | 17.20 |
September | 58129654.83 | 697.65 | 30-SEP-16:10 | 20.82 |
October | 0.402529E+10 | 68596.42 | 30-OCT-05:32 | -9.6 |
November | 0.164404E+11 | 68528.14 | 25-NOV-02:42 | -16.0 |
December | 0.361829E+11 | 69989.30 | 24-DEC-08:62 | -31.1 |
Annual Sum or Average | 0.155198E+12 | |||
Minimum of Months | 51234156.28 | 662.38 | -31.1 | |
Maximum of Months | 0.388256E+11 | 69989.30 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191267E+12 | 143665.80 | 04-JAN-12:00 | -28.3 |
February | 0.140280E+12 | 143465.09 | 12-FEB-23:00 | -17.2 |
March | 0.952641E+11 | 114309.42 | 15-MAR-04:53 | -22.2 |
April | 0.276081E+11 | 69215.16 | 04-APR-18:57 | -7.2 |
May | 0.402325E+09 | 17644.43 | 01-MAY-03:57 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 19.75 |
October | 0.223337E+10 | 31204.71 | 31-OCT-20:57 | -2.2 |
November | 0.688724E+11 | 92256.02 | 25-NOV-02:00 | -15.6 |
December | 0.178087E+12 | 143281.02 | 18-DEC-15:00 | -22.8 |
Annual Sum or Average | 0.704015E+12 | |||
Minimum of Months | 0.00 | 0.00 | -28.3 | |
Maximum of Months | 0.191267E+12 | 143665.80 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.898279E+09 | 1011.11 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.759151E+09 | 982.40 | 02-FEB-16:00 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.874439E+09 | 977.50 | 13-MAR-07:10 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.791091E+09 | 965.47 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.761115E+09 | 872.18 | 19-MAY-08:30 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.764113E+09 | 933.31 | 30-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.742052E+09 | 929.28 | 08-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.819379E+09 | 964.70 | 31-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.789437E+09 | 967.63 | 19-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.844603E+09 | 1009.09 | 31-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.871183E+09 | 1011.11 | 06-NOV-16:49 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.930671E+09 | 1011.11 | 01-DEC-16:19 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.984551E+10 | 0.291647E+11 | ||||
Minimum of Months | 0.742052E+09 | 872.18 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.930671E+09 | 1011.11 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.404504E+10 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.370796E+10 | 3848.58 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.430437E+10 | 3848.58 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.401913E+10 | 3848.58 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.417471E+10 | 3848.58 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.414879E+10 | 3848.58 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.404504E+10 | 3848.58 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.430437E+10 | 3848.58 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.401913E+10 | 3848.58 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.404504E+10 | 3848.58 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.388946E+10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.404504E+10 | 3848.58 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.487481E+11 | 0.00 | 0.00 | ||
Minimum of Months | 0.370796E+10 | 3848.58 | 0.00 | 0.00 | |
Maximum of Months | 0.430437E+10 | 3848.58 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.452653E+10 | 4189.44 | 05-JAN-15:00 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.408025E+10 | 4135.57 | 08-FEB-15:00 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.463604E+10 | 4101.32 | 17-MAR-08:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.429703E+10 | 4033.50 | 06-APR-08:30 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.438885E+10 | 3955.00 | 06-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.433964E+10 | 3897.41 | 10-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.426079E+10 | 3866.66 | 31-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.452745E+10 | 4011.39 | 31-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.430604E+10 | 4081.00 | 13-SEP-08:30 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.441940E+10 | 4138.26 | 19-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.432805E+10 | 4191.28 | 29-NOV-15:00 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.453242E+10 | 4201.13 | 20-DEC-15:00 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.526425E+11 | 0.107344E+12 | ||||
Minimum of Months | 0.408025E+10 | 3866.66 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.463604E+10 | 4201.13 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.898279E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473644E+10 |
February | 0.127628E+10 | 0.759151E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369609E+10 |
March | 0.149825E+10 | 0.874439E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318168E+10 |
April | 0.138726E+10 | 0.791091E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7089572.99 | 0.190549E+10 |
May | 0.144276E+10 | 0.761115E+09 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36308554.12 | 0.864583E+09 |
June | 0.144276E+10 | 0.764113E+09 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83150888.67 | 0.491064E+09 |
July | 0.138726E+10 | 0.742052E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78571805.40 | 0.395284E+09 |
August | 0.149825E+10 | 0.819379E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41184034.76 | 0.633095E+09 |
September | 0.138726E+10 | 0.789437E+09 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1785784.46 | 0.106070E+10 |
October | 0.138726E+10 | 0.844603E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164915E+10 |
November | 0.133177E+10 | 0.871183E+09 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259628E+10 |
December | 0.138726E+10 | 0.930671E+09 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432779E+10 |
Annual Sum or Average | 0.168137E+11 | 0.984551E+10 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248091E+09 | 0.255377E+11 |
Minimum of Months | 0.127628E+10 | 0.742052E+09 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395284E+09 |
Maximum of Months | 0.149825E+10 | 0.930671E+09 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83150888.67 | 0.473644E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980530E+10 |
February | 0.300332E+10 | 0.370796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817096E+10 |
March | 0.352563E+10 | 0.430437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576514E+10 |
April | 0.326447E+10 | 0.401913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55453713.10 | 0.402693E+10 |
May | 0.339505E+10 | 0.417471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87965613.23 | 0.162370E+10 |
June | 0.339505E+10 | 0.414879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85694020.28 | 0.107400E+10 |
July | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53050020.75 | 0.118434E+10 |
August | 0.352563E+10 | 0.430437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16435478.57 | 0.157148E+10 |
September | 0.326447E+10 | 0.401913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2172851.33 | 0.218681E+10 |
October | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4035743.40 | 0.276085E+10 |
November | 0.313390E+10 | 0.388946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100522.37 | 0.586700E+10 |
December | 0.326447E+10 | 0.404504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.994773E+10 |
Annual Sum or Average | 0.395654E+11 | 0.487481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304908E+09 | 0.539842E+11 |
Minimum of Months | 0.300332E+10 | 0.370796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107400E+10 |
Maximum of Months | 0.352563E+10 | 0.430437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87965613.23 | 0.994773E+10 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.452653E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666784E+11 |
February | 0.690763E+10 | 0.408025E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537923E+11 |
March | 0.810895E+10 | 0.463604E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1250569.43 | 0.359263E+11 |
April | 0.750829E+10 | 0.429703E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147351E+10 | 0.196869E+11 |
May | 0.780862E+10 | 0.438885E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269905E+10 | 0.766481E+10 |
June | 0.780862E+10 | 0.433964E+10 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136264E+10 | 0.580124E+10 |
July | 0.750829E+10 | 0.426079E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290116E+09 | 0.897094E+10 |
August | 0.810895E+10 | 0.452745E+10 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224145E+09 | 0.116602E+11 |
September | 0.750829E+10 | 0.430604E+10 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87160433.59 | 0.153999E+11 |
October | 0.750829E+10 | 0.441940E+10 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556662E+09 | 0.145452E+11 |
November | 0.720796E+10 | 0.432805E+10 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210434E+09 | 0.326645E+11 |
December | 0.750829E+10 | 0.453242E+10 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651284E+11 |
Annual Sum or Average | 0.910005E+11 | 0.526425E+11 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690496E+10 | 0.337919E+12 |
Minimum of Months | 0.690763E+10 | 0.408025E+10 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580124E+10 |
Maximum of Months | 0.810895E+10 | 0.463604E+10 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269905E+10 | 0.666784E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1011.11 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 15016.91 | 05-JAN-08:00 |
February | 1680.92 | 01-FEB-08:09 | 982.40 | 02-FEB-16:00 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 14401.71 | 14-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 977.50 | 13-MAR-07:10 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 11988.16 | 15-MAR-07:00 |
April | 1680.92 | 01-APR-07:10 | 965.47 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.50 | 23-APR-16:00 | 8057.44 | 05-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 872.18 | 19-MAY-08:30 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.59 | 25-MAY-16:50 | 5556.87 | 01-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 933.31 | 30-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2557.46 | 29-JUN-16:10 | 2812.44 | 02-JUN-06:10 |
July | 1680.92 | 01-JUL-07:10 | 929.28 | 08-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1245.59 | 28-JUL-16:10 | 2735.91 | 18-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 964.70 | 31-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1583.05 | 08-AUG-16:10 | 3175.75 | 25-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 967.63 | 19-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.87 | 01-SEP-16:10 | 4578.98 | 06-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1009.09 | 31-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7712.46 | 30-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1011.11 | 06-NOV-16:49 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 10065.57 | 29-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1011.11 | 01-DEC-16:19 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 14229.12 | 20-DEC-08:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 872.18 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2735.91 | |||||
Maximum of Months | 1680.92 | 1011.11 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2557.46 | 15016.91 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 3848.58 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 12041.94 | 04-JAN-16:10 |
February | 3955.50 | 01-FEB-08:09 | 3848.58 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 14690.28 | 12-FEB-23:00 |
March | 3955.50 | 01-MAR-08:09 | 3848.58 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 8969.19 | 14-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 3848.58 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2516.96 | 23-APR-16:00 | 7329.30 | 26-APR-15:10 |
May | 3955.50 | 01-MAY-07:10 | 3848.58 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1284.07 | 10-MAY-15:10 | 3415.70 | 20-MAY-06:10 |
June | 3955.50 | 01-JUN-07:10 | 3848.58 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2010.41 | 29-JUN-16:00 | 3082.22 | 09-JUN-08:00 |
July | 3955.50 | 01-JUL-07:10 | 3848.58 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1374.62 | 15-JUL-15:10 | 2216.51 | 08-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 3848.58 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1037.47 | 08-AUG-16:00 | 4199.58 | 17-AUG-15:10 |
September | 3955.50 | 01-SEP-07:10 | 3848.58 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.87 | 24-SEP-15:00 | 3762.28 | 20-SEP-06:10 |
October | 3955.50 | 02-OCT-07:10 | 3848.58 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545.99 | 19-OCT-15:10 | 4821.14 | 31-OCT-17:00 |
November | 3955.50 | 01-NOV-07:10 | 3848.58 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.93 | 01-NOV-15:10 | 7253.38 | 22-NOV-01:37 |
December | 3955.50 | 01-DEC-08:09 | 3848.58 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 14787.80 | 18-DEC-16:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2216.51 | ||||
Maximum of Months | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2516.96 | 14787.80 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 4189.44 | 05-JAN-15:00 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 106307.13 | 04-JAN-12:00 |
February | 9097.65 | 01-FEB-08:09 | 4135.57 | 08-FEB-15:00 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 81486.97 | 12-FEB-22:55 |
March | 9097.65 | 01-MAR-08:09 | 4101.32 | 17-MAR-08:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 499.61 | 26-MAR-16:00 | 50264.06 | 14-MAR-15:50 |
April | 9097.65 | 01-APR-07:10 | 4033.50 | 06-APR-08:30 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24102.58 | 23-APR-16:00 | 34952.77 | 26-APR-15:00 |
May | 9097.65 | 01-MAY-07:10 | 3955.00 | 06-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16114.91 | 10-MAY-15:00 | 16191.94 | 20-MAY-07:10 |
June | 9097.65 | 01-JUN-07:10 | 3897.41 | 10-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12115.22 | 29-JUN-16:00 | 21730.99 | 09-JUN-09:00 |
July | 9097.65 | 01-JUL-07:10 | 3866.66 | 31-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7627.80 | 15-JUL-15:00 | 23539.33 | 03-JUL-11:00 |
August | 9097.65 | 01-AUG-07:10 | 4011.39 | 31-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6182.10 | 08-AUG-16:00 | 35001.63 | 17-AUG-14:00 |
September | 9097.65 | 01-SEP-07:10 | 4081.00 | 13-SEP-08:30 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3906.40 | 24-SEP-15:00 | 20206.66 | 20-SEP-07:10 |
October | 9097.65 | 02-OCT-07:10 | 4138.26 | 19-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13071.83 | 19-OCT-15:00 | 24597.58 | 05-OCT-08:00 |
November | 9097.65 | 01-NOV-07:10 | 4191.28 | 29-NOV-15:00 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6835.53 | 01-NOV-14:00 | 42313.03 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 4201.13 | 20-DEC-15:00 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 95504.91 | 18-DEC-15:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 3866.66 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16191.94 | |||||
Maximum of Months | 9097.65 | 4201.13 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 24102.58 | 106307.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 305.97 | 2819.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 707.61 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 254.98 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1125.34 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.63 |
April | 238.09 | 20-APR-15:00 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.65 |
May | 3811.95 | 25-MAY-16:00 | 1680.92 | 616.78 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 218.46 | 0.00 |
June | 14520.93 | 28-JUN-05:03 | 554.70 | 152.99 | 1651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.03 |
July | 19847.87 | 01-JUL-05:02 | 924.51 | 254.98 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.65 |
August | 16947.17 | 07-AUG-05:03 | 554.70 | 152.99 | 1651.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.67 |
September | 18538.08 | 02-SEP-05:03 | 739.61 | 203.98 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.00 |
October | 638.86 | 03-OCT-14:00 | 1680.92 | 653.66 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.64 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.09 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 152.99 | 1409.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641.99 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 51.00 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19847.87 | 1680.92 | 653.66 | 2819.25 | 0.00 | 0.00 | 0.00 | 0.00 | 218.46 | 1125.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 1799.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4217.21 |
February | 3987.61 | 08-FEB-14:00 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.63 |
March | 5639.76 | 23-MAR-14:00 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8270.21 | 05-APR-11:20 | 4192.83 | 7697.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1269.66 |
May | 5737.86 | 20-MAY-07:10 | 3955.50 | 3395.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3121.92 |
June | 25278.62 | 30-JUN-17:12 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.79 | 0.00 |
July | 28073.07 | 24-JUL-17:12 | 0.00 | 1199.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.72 | 0.00 |
August | 5263.82 | 09-AUG-14:40 | 3955.50 | 3848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.62 | 0.00 |
September | 7964.64 | 06-SEP-07:05 | 7911.00 | 6791.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.23 |
October | 6849.08 | 04-OCT-07:05 | 7911.00 | 6791.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1430.91 |
November | 8795.27 | 07-NOV-10:55 | 7911.00 | 7697.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1514.90 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3878.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 899.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28073.07 | 7911.00 | 7697.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 682.79 | 4217.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 2988.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24835.92 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2490.23 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39580.54 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 1494.14 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10490.06 |
April | 0.00 | 01-APR-00:05 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7336.94 |
May | 0.00 | 01-MAY-00:05 | 0.00 | 996.09 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1700.01 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4711.37 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2980.44 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5267.31 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2797.64 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4022.61 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 498.05 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7331.44 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1494.14 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20516.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 498.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1700.01 | |
Maximum of Months | 0.00 | 0.00 | 2988.27 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39580.54 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.329987E+11 | 27286.18 | 04-JAN-08:09 | 0.330010E+12 | 272873.53 | 04-JAN-17:00 |
February | 0.290282E+11 | 22839.19 | 02-FEB-15:00 | 0.241834E+12 | 237556.99 | 12-FEB-22:49 |
March | 0.318831E+11 | 22703.00 | 03-MAR-15:00 | 0.174200E+12 | 205494.02 | 15-MAR-05:10 |
April | 0.280325E+11 | 22204.76 | 05-APR-10:09 | 0.570038E+11 | 113967.90 | 04-APR-06:10 |
May | 0.276155E+11 | 22851.74 | 25-MAY-14:50 | 0.257985E+10 | 51242.69 | 01-MAY-05:10 |
June | 0.276810E+11 | 29058.63 | 30-JUN-14:00 | 38618875.20 | 5653.62 | 01-JUN-05:10 |
July | 0.280476E+11 | 27684.87 | 15-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.293635E+11 | 26582.84 | 08-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.278680E+11 | 24382.30 | 01-SEP-14:00 | 0.393599E+09 | 10119.68 | 29-SEP-05:10 |
October | 0.295684E+11 | 22050.60 | 30-OCT-08:09 | 0.148591E+11 | 65336.36 | 30-OCT-05:40 |
November | 0.305990E+11 | 26661.02 | 25-NOV-16:00 | 0.125359E+12 | 158906.41 | 25-NOV-06:10 |
December | 0.331594E+11 | 27103.88 | 26-DEC-08:09 | 0.306186E+12 | 268157.80 | 18-DEC-17:19 |
Annual Sum or Average | 0.355845E+12 | 0.125247E+13 | ||||
Minimum of Months | 0.276155E+11 | 22050.60 | 0.00 | 0.00 | ||
Maximum of Months | 0.331594E+11 | 29058.63 | 0.330010E+12 | 272873.53 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.946985E+10 | 0.736349E+10 | 0.112984E+11 | 0.00 | 0.373968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112733E+10 | 0.00 |
February | 0.854736E+10 | 0.587396E+10 | 0.103734E+11 | 0.00 | 0.317811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105538E+10 | 0.00 |
March | 0.981485E+10 | 0.544887E+10 | 0.121089E+11 | 0.00 | 0.328679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122365E+10 | 0.00 |
April | 0.910725E+10 | 0.421486E+10 | 0.112578E+11 | 0.00 | 0.234432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110830E+10 | 0.00 |
May | 0.932467E+10 | 0.356856E+10 | 0.117000E+11 | 0.00 | 0.178056E+10 | 0.00 | 0.00 | 0.148028E+09 | 0.00 | 0.00 | 0.00 | 0.109370E+10 | 0.00 |
June | 0.925255E+10 | 0.308102E+10 | 0.116594E+11 | 0.00 | 0.174864E+10 | 0.00 | 0.00 | 0.915265E+09 | 0.00 | 0.00 | 0.00 | 0.102416E+10 | 0.00 |
July | 0.904788E+10 | 0.332636E+10 | 0.112984E+11 | 0.00 | 0.169819E+10 | 0.00 | 0.00 | 0.173305E+10 | 0.00 | 0.00 | 0.00 | 0.943796E+09 | 0.00 |
August | 0.965120E+10 | 0.395427E+10 | 0.121016E+11 | 0.00 | 0.181806E+10 | 0.00 | 0.00 | 0.855442E+09 | 0.00 | 0.00 | 0.00 | 0.982936E+09 | 0.00 |
September | 0.911461E+10 | 0.480882E+10 | 0.112504E+11 | 0.00 | 0.167915E+10 | 0.00 | 0.00 | 89916564.59 | 0.00 | 0.00 | 0.00 | 0.925075E+09 | 0.00 |
October | 0.930904E+10 | 0.606831E+10 | 0.113057E+11 | 0.00 | 0.191582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969503E+09 | 0.00 |
November | 0.908869E+10 | 0.683606E+10 | 0.108562E+11 | 0.00 | 0.283534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982734E+09 | 0.00 |
December | 0.950813E+10 | 0.761855E+10 | 0.112984E+11 | 0.00 | 0.365559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107878E+10 | 0.00 |
Annual Sum or Average | 0.111236E+12 | 0.621631E+11 | 0.136508E+12 | 0.00 | 0.296803E+11 | 0.00 | 0.00 | 0.374170E+10 | 0.00 | 0.00 | 0.00 | 0.125154E+11 | 0.00 |
Minimum of Months | 0.854736E+10 | 0.308102E+10 | 0.103734E+11 | 0.00 | 0.167915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925075E+09 | 0.00 |
Maximum of Months | 0.981485E+10 | 0.761855E+10 | 0.121089E+11 | 0.00 | 0.373968E+10 | 0.00 | 0.00 | 0.173305E+10 | 0.00 | 0.00 | 0.00 | 0.122365E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.330010E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.241834E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.174200E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.570038E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.257985E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 38618875.20 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.393599E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.148591E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.125359E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.306186E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.125247E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.330010E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 8966.89 | 09-JAN-09:09 | 5520.82 | 01-JAN-06:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 2768.34 | 04-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 8832.38 | 27-FEB-09:09 | 5520.82 | 01-FEB-06:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 2681.83 | 14-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8857.70 | 13-MAR-08:09 | 5520.82 | 01-MAR-06:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 2587.99 | 15-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 8745.83 | 06-APR-08:30 | 5520.82 | 01-APR-05:10 | 10035.17 | 01-APR-07:10 | 0.00 | 2357.68 | 04-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 8643.95 | 06-MAY-08:09 | 4975.14 | 01-MAY-19:30 | 10035.17 | 01-MAY-07:10 | 0.00 | 2153.41 | 02-MAY-06:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 8643.56 | 10-JUN-08:09 | 4975.14 | 01-JUN-19:00 | 10035.17 | 01-JUN-07:10 | 0.00 | 1732.20 | 30-JUN-15:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 8577.03 | 22-JUL-08:30 | 4975.14 | 01-JUL-20:19 | 10035.17 | 01-JUL-07:10 | 0.00 | 1691.29 | 01-JUL-06:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 8795.34 | 31-AUG-08:09 | 5520.82 | 15-AUG-05:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 1691.29 | 01-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 8835.83 | 13-SEP-08:30 | 5520.82 | 01-SEP-05:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 1691.29 | 01-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 8907.64 | 19-OCT-08:09 | 5520.82 | 01-OCT-05:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 2326.45 | 30-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 9022.68 | 15-NOV-15:00 | 5520.82 | 01-NOV-05:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 2488.11 | 25-NOV-08:09 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 9015.30 | 13-DEC-15:00 | 5520.82 | 01-DEC-06:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 2711.64 | 20-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 8577.03 | 4975.14 | 10035.17 | 0.00 | 1691.29 | 0.00 | 0.00 | |||||
Maximum of Months | 9022.68 | 5520.82 | 10035.17 | 0.00 | 2768.34 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 1844.78 | 31-JAN-12:20 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 1852.17 | 24-FEB-12:00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 1851.99 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 1838.08 | 01-APR-11:30 | 0.00 |
May | 1528.44 | 25-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1735.37 | 01-MAY-11:09 | 0.00 |
June | 8314.35 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1660.32 | 01-JUN-11:20 | 0.00 |
July | 6392.34 | 15-JUL-14:30 | 0.00 | 0.00 | 0.00 | 1585.84 | 03-JUL-11:09 | 0.00 |
August | 5573.40 | 08-AUG-15:30 | 0.00 | 0.00 | 0.00 | 1503.79 | 01-AUG-11:30 | 0.00 |
September | 3202.55 | 01-SEP-15:30 | 0.00 | 0.00 | 0.00 | 1508.69 | 30-SEP-11:30 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 1603.54 | 31-OCT-11:00 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 1706.02 | 28-NOV-12:30 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1790.01 | 30-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1503.79 | 0.00 | ||
Maximum of Months | 8314.35 | 0.00 | 0.00 | 0.00 | 1852.17 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 27286.18 | 04-JAN-08:09 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 2768.34 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22839.19 | 02-FEB-15:00 | 8802.81 | 10035.17 | 0.00 | 0.00 | 2379.29 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22703.00 | 03-MAR-15:00 | 8819.20 | 10035.17 | 0.00 | 0.00 | 2222.32 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22204.76 | 05-APR-10:09 | 8581.24 | 10035.17 | 0.00 | 0.00 | 2177.13 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22851.74 | 25-MAY-14:50 | 8207.72 | 10035.17 | 0.00 | 0.00 | 1691.29 | 0.00 | 0.00 | 1415.79 | 0.00 |
June | 29058.63 | 30-JUN-14:00 | 8207.72 | 10035.17 | 0.00 | 0.00 | 1691.29 | 0.00 | 0.00 | 7744.70 | 0.00 |
July | 27684.87 | 15-JUL-14:30 | 8207.72 | 10035.17 | 0.00 | 0.00 | 1691.29 | 0.00 | 0.00 | 6392.34 | 0.00 |
August | 26582.84 | 08-AUG-14:00 | 8207.72 | 10035.17 | 0.00 | 0.00 | 1691.29 | 0.00 | 0.00 | 5330.07 | 0.00 |
September | 24382.30 | 01-SEP-14:00 | 8207.72 | 10035.17 | 0.00 | 0.00 | 1691.29 | 0.00 | 0.00 | 3181.74 | 0.00 |
October | 22050.60 | 30-OCT-08:09 | 8868.34 | 10035.17 | 0.00 | 0.00 | 2237.17 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26661.02 | 25-NOV-16:00 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 2391.23 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27103.88 | 26-DEC-08:09 | 8142.10 | 10035.17 | 5520.82 | 0.00 | 2631.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 22050.60 | 8142.10 | 10035.17 | 0.00 | 0.00 | 1691.29 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29058.63 | 8868.34 | 10035.17 | 5520.82 | 0.00 | 2768.34 | 0.00 | 0.00 | 7744.70 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 272873.53 | 04-JAN-17:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 237556.99 | 12-FEB-22:49 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 205494.02 | 15-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 113967.90 | 04-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 51242.69 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5653.62 | 01-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 10119.68 | 29-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 65336.36 | 30-OCT-05:40 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 158906.41 | 25-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 268157.80 | 18-DEC-17:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 272873.53 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 36.33 | 15.91 | 8.50 | 16.53 | 0.00 | 16.53 | 0.00 | 16.53 |
February | 18.17 | 16.85 | 8.17 | 17.58 | 0.00 | 17.58 | 0.00 | 17.58 |
March | 16.67 | 17.48 | 9.50 | 18.16 | 0.00 | 18.16 | 0.00 | 18.16 |
April | 9.83 | 19.03 | 8.83 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
May | 4.33 | 19.91 | 4.17 | 20.00 | 0.00 | 20.00 | 0.00 | 20.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.33 | 24.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.55 | 0.67 | 24.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.50 | 1.00 | 24.50 |
September | 0.50 | 20.45 | 0.50 | 20.45 | 0.17 | 21.03 | 0.17 | 21.46 |
October | 6.83 | 20.08 | 6.83 | 20.08 | 0.00 | 20.08 | 0.00 | 20.08 |
November | 9.83 | 18.95 | 8.50 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
December | 33.00 | 16.13 | 9.50 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
Annual Sum or Average | 135.50 | 17.08 | 64.50 | 17.85 | 2.17 | 17.92 | 2.17 | 17.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.53 | 0.00 | 16.53 |
Maximum of Months | 36.33 | 20.45 | 9.50 | 20.45 | 1.00 | 24.55 | 1.00 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 114.67 | 14.28 | 4.17 | 14.28 | 0.00 | 14.28 | 0.00 | 14.28 |
February | 100.33 | 14.46 | 4.00 | 14.45 | 0.00 | 14.45 | 0.00 | 14.45 |
March | 91.67 | 14.64 | 5.50 | 14.64 | 0.00 | 14.64 | 0.00 | 14.64 |
April | 34.50 | 14.82 | 2.67 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
May | 1.83 | 14.95 | 0.17 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.00 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.27 | 0.00 | 27.27 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6.00 | 14.94 | 0.17 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
November | 71.67 | 14.75 | 3.67 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
December | 114.50 | 14.36 | 4.17 | 14.36 | 0.00 | 14.36 | 0.00 | 14.36 |
Annual Sum or Average | 535.17 | 14.50 | 24.50 | 14.50 | 0.83 | 14.52 | 0.00 | 14.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 114.67 | 14.95 | 5.50 | 14.95 | 0.50 | 27.29 | 0.00 | 27.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.00 | 9.03 | 7.50 | 8.98 | 0.00 | 8.98 | 0.00 | 8.98 |
February | 1.00 | 9.29 | 0.00 | 9.29 | 0.00 | 9.29 | 0.00 | 9.29 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.83 | 9.18 | 2.83 | 9.18 | 0.00 | 9.18 | 0.00 | 9.18 |
Annual Sum or Average | 14.83 | 9.08 | 10.33 | 9.04 | 0.00 | 9.04 | 0.00 | 9.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.00 | 9.29 | 7.50 | 9.29 | 0.00 | 9.29 | 0.00 | 9.29 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 21.04 | 300.00 | 21.04 | 300.00 | 21.04 |
February | 276.00 | 21.04 | 276.00 | 21.04 | 276.00 | 21.04 |
March | 324.00 | 21.04 | 324.00 | 21.04 | 324.00 | 21.04 |
April | 300.00 | 21.12 | 293.50 | 21.10 | 293.50 | 21.10 |
May | 300.00 | 22.34 | 125.00 | 22.00 | 123.83 | 21.81 |
June | 252.50 | 23.46 | 115.83 | 23.55 | 68.50 | 23.56 |
July | 60.33 | 23.86 | 232.17 | 23.89 | 50.33 | 23.90 |
August | 112.17 | 23.76 | 207.17 | 23.85 | 58.33 | 23.86 |
September | 274.17 | 22.78 | 70.50 | 22.70 | 56.17 | 22.60 |
October | 300.00 | 21.23 | 262.67 | 21.16 | 262.67 | 21.14 |
November | 288.00 | 21.06 | 285.33 | 21.06 | 285.33 | 21.06 |
December | 300.00 | 21.03 | 300.00 | 21.03 | 300.00 | 21.03 |
Annual Sum or Average | 3087.17 | 21.70 | 2792.17 | 21.68 | 2398.67 | 21.56 |
Minimum of Months | 60.33 | 21.03 | 70.50 | 21.03 | 50.33 | 21.03 |
Maximum of Months | 324.00 | 23.86 | 324.00 | 23.89 | 324.00 | 23.90 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
February | 276.00 | 15.54 | 276.00 | 15.54 | 276.00 | 15.54 |
March | 324.00 | 15.55 | 324.00 | 15.55 | 324.00 | 15.55 |
April | 300.00 | 16.16 | 300.00 | 16.16 | 300.00 | 16.16 |
May | 290.83 | 19.54 | 209.83 | 19.15 | 204.33 | 18.95 |
June | 278.83 | 23.07 | 156.00 | 23.44 | 135.00 | 23.54 |
July | 145.17 | 26.13 | 275.33 | 26.09 | 136.00 | 26.15 |
August | 196.50 | 24.75 | 239.67 | 25.19 | 138.00 | 25.29 |
September | 267.83 | 20.58 | 166.83 | 20.39 | 148.67 | 20.13 |
October | 300.00 | 16.38 | 300.00 | 16.38 | 300.00 | 16.38 |
November | 288.00 | 15.64 | 288.00 | 15.64 | 288.00 | 15.64 |
December | 300.00 | 15.54 | 300.00 | 15.54 | 300.00 | 15.54 |
Annual Sum or Average | 3267.17 | 18.12 | 3135.67 | 18.18 | 2850.00 | 17.98 |
Minimum of Months | 145.17 | 15.54 | 156.00 | 15.54 | 135.00 | 15.54 |
Maximum of Months | 324.00 | 26.13 | 324.00 | 26.09 | 324.00 | 26.15 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 9.97 | 300.00 | 9.97 | 300.00 | 9.97 |
February | 276.00 | 10.02 | 276.00 | 10.02 | 276.00 | 10.02 |
March | 324.00 | 10.10 | 324.00 | 10.10 | 324.00 | 10.10 |
April | 300.00 | 11.24 | 300.00 | 11.24 | 300.00 | 11.24 |
May | 312.00 | 16.48 | 277.17 | 16.19 | 277.17 | 16.08 |
June | 301.50 | 21.62 | 200.50 | 21.65 | 190.50 | 21.62 |
July | 163.83 | 26.12 | 263.67 | 26.15 | 139.50 | 26.26 |
August | 200.17 | 23.93 | 194.83 | 24.56 | 100.50 | 24.68 |
September | 290.33 | 19.77 | 185.83 | 19.37 | 177.33 | 19.12 |
October | 300.00 | 12.75 | 300.00 | 12.75 | 300.00 | 12.75 |
November | 288.00 | 10.29 | 288.00 | 10.29 | 288.00 | 10.29 |
December | 300.00 | 9.99 | 300.00 | 9.99 | 300.00 | 9.99 |
Annual Sum or Average | 3355.83 | 14.50 | 3210.00 | 14.45 | 2973.00 | 14.16 |
Minimum of Months | 163.83 | 9.97 | 185.83 | 9.97 | 100.50 | 9.97 |
Maximum of Months | 324.00 | 26.12 | 324.00 | 26.15 | 324.00 | 26.26 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.636674E+09 | 0.148028E+09 | 60.83 | 0.554312E+09 | 82361849.22 | 0.00 | 0.74 | 25-MAY-16:00 | 0.00 | 01-MAY-00:05 | 6583.20 | 25-MAY-16:00 | 5467.36 | 25-MAY-16:00 | 1857.99 | 26-MAY-10:50 | 1528.44 | 25-MAY-16:00 | 0.00 | 01-MAY-00:05 |
June | 0.246934E+10 | 0.556704E+09 | 150.75 | 0.187645E+10 | 0.592887E+09 | 0.00 | 1.00 | 28-JUN-05:03 | 0.00 | 01-JUN-00:10 | 20299.54 | 30-JUN-05:01 | 11343.86 | 30-JUN-05:03 | 9408.98 | 30-JUN-05:01 | 4293.17 | 30-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.484641E+10 | 0.105425E+10 | 231.89 | 0.359535E+10 | 0.125106E+10 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 19038.15 | 05-JUL-05:45 | 11068.74 | 06-JUL-05:03 | 10247.13 | 05-JUL-05:45 | 4022.68 | 05-JUL-05:45 | 0.00 | 01-JUL-00:10 |
August | 0.308550E+10 | 0.674299E+09 | 183.34 | 0.226323E+10 | 0.822264E+09 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 18067.26 | 09-AUG-05:02 | 11368.49 | 14-AUG-05:03 | 9094.24 | 30-AUG-05:03 | 3866.00 | 09-AUG-05:02 | 0.00 | 01-AUG-00:10 |
September | 0.326770E+09 | 72254469.03 | 36.50 | 0.276909E+09 | 49860538.06 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 17422.43 | 01-SEP-05:03 | 11662.82 | 02-SEP-05:03 | 9036.03 | 01-SEP-05:03 | 3751.75 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.113647E+11 | 0.250554E+10 | 663.31 | 0.856626E+10 | 0.279843E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.484641E+10 | 0.105425E+10 | 231.89 | 0.359535E+10 | 0.125106E+10 | 0.00 | 1.00 | 0.00 | 20299.54 | 11662.82 | 10247.13 | 4293.17 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 |
June | 0.146239E+10 | 0.358561E+09 | 39.54 | 0.914975E+09 | 0.547415E+09 | 0.00 | 1.00 | 29-JUN-15:40 | 0.00 | 01-JUN-00:10 | 40494.66 | 30-JUN-17:12 | 28651.15 | 30-JUN-19:35 | 13298.81 | 30-JUN-17:12 | 9888.21 | 29-JUN-17:12 | 0.00 | 01-JUN-00:10 |
July | 0.278946E+10 | 0.678797E+09 | 111.60 | 0.177439E+10 | 0.101508E+10 | 0.00 | 1.00 | 22-JUL-18:05 | 0.00 | 01-JUL-00:10 | 42502.08 | 24-JUL-19:05 | 30130.51 | 24-JUL-17:12 | 17370.50 | 24-JUL-19:05 | 9259.89 | 29-JUL-18:35 | 0.00 | 01-JUL-00:10 |
August | 0.731758E+09 | 0.181143E+09 | 40.67 | 0.456020E+09 | 0.275738E+09 | 0.00 | 0.64 | 08-AUG-15:10 | 0.00 | 01-AUG-00:10 | 12954.62 | 08-AUG-15:10 | 7669.78 | 08-AUG-15:30 | 5291.03 | 08-AUG-15:10 | 3163.79 | 08-AUG-15:10 | 0.00 | 01-AUG-00:10 |
September | 70716657.09 | 17662095.56 | 5.00 | 51492077.10 | 19224579.99 | 0.00 | 0.34 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 | 5919.74 | 01-SEP-15:00 | 4467.37 | 01-SEP-15:00 | 1465.32 | 01-SEP-14:10 | 1476.71 | 01-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.505433E+10 | 0.123616E+10 | 196.81 | 0.319687E+10 | 0.185745E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.278946E+10 | 0.678797E+09 | 111.60 | 0.177439E+10 | 0.101508E+10 | 0.00 | 1.00 | 0.00 | 42502.08 | 30130.51 | 17370.50 | 9888.21 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.17 | 26.62 | 36.54 | 30.01 | 212.06 | 0.00 | 0.00 | 0.00 |
February | 102.15 | 46.68 | 55.47 | 75.08 | 165.06 | 0.00 | 0.00 | 0.00 |
March | 134.43 | 68.92 | 65.52 | 119.10 | 123.47 | 0.00 | 0.00 | 0.00 |
April | 171.31 | 86.77 | 84.55 | 185.58 | 68.81 | 0.00 | 0.00 | 0.00 |
May | 210.96 | 100.82 | 110.14 | 260.30 | 38.06 | 0.00 | 0.00 | 0.00 |
June | 203.26 | 87.96 | 115.29 | 258.41 | 29.77 | 0.00 | 0.00 | 0.00 |
July | 217.39 | 101.34 | 116.05 | 276.70 | 35.21 | 0.00 | 0.00 | 0.00 |
August | 178.03 | 80.63 | 97.39 | 220.80 | 39.70 | 0.00 | 0.00 | 0.00 |
September | 139.45 | 62.55 | 76.91 | 158.51 | 54.18 | 0.00 | 0.00 | 0.00 |
October | 88.23 | 35.45 | 52.78 | 84.58 | 72.65 | 0.00 | 0.00 | 0.00 |
November | 53.81 | 18.33 | 35.49 | 32.99 | 118.10 | 0.00 | 0.00 | 0.00 |
December | 47.52 | 16.52 | 31.00 | 16.73 | 204.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.32 | 61.14 | 73.18 | 143.62 | 96.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.52 | 16.52 | 31.00 | 16.73 | 29.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 217.39 | 101.34 | 116.05 | 276.70 | 212.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.17 | 26.62 | 36.54 | 30.01 | 212.06 | 0.00 | 0.00 | 0.00 |
February | 102.15 | 46.68 | 55.47 | 75.08 | 165.06 | 0.00 | 0.00 | 0.00 |
March | 134.43 | 68.92 | 65.52 | 119.10 | 123.47 | 0.00 | 0.00 | 0.00 |
April | 171.31 | 86.77 | 84.55 | 185.58 | 68.81 | 0.00 | 0.00 | 0.00 |
May | 210.96 | 100.82 | 110.14 | 260.30 | 38.06 | 0.00 | 0.00 | 0.00 |
June | 203.26 | 87.96 | 115.29 | 258.41 | 29.77 | 0.00 | 0.00 | 0.00 |
July | 217.39 | 101.34 | 116.05 | 276.70 | 35.21 | 0.00 | 0.00 | 0.00 |
August | 178.03 | 80.63 | 97.39 | 220.80 | 39.70 | 0.00 | 0.00 | 0.00 |
September | 139.45 | 62.55 | 76.91 | 158.51 | 54.18 | 0.00 | 0.00 | 0.00 |
October | 88.23 | 35.45 | 52.78 | 84.58 | 72.65 | 0.00 | 0.00 | 0.00 |
November | 53.81 | 18.33 | 35.49 | 32.99 | 118.10 | 0.00 | 0.00 | 0.00 |
December | 47.52 | 16.52 | 31.00 | 16.73 | 204.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 134.32 | 61.14 | 73.18 | 143.62 | 96.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 47.52 | 16.52 | 31.00 | 16.73 | 29.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 217.39 | 101.34 | 116.05 | 276.70 | 212.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.46 | 0.00 | 16.46 | 0.36 | 135.65 | 0.00 | 0.00 | 0.00 |
February | 25.29 | 0.00 | 25.29 | 3.29 | 104.10 | 0.00 | 0.00 | 0.00 |
March | 31.12 | 0.00 | 31.12 | 8.03 | 76.42 | 0.00 | 0.00 | 0.00 |
April | 40.87 | 0.40 | 40.48 | 27.59 | 40.38 | 0.00 | 0.00 | 0.00 |
May | 57.39 | 3.07 | 54.33 | 61.43 | 20.85 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 6.97 | 56.99 | 76.62 | 16.47 | 0.00 | 0.00 | 0.00 |
July | 61.05 | 5.13 | 55.92 | 71.31 | 19.45 | 0.00 | 0.00 | 0.00 |
August | 46.60 | 0.93 | 45.67 | 49.71 | 22.57 | 0.00 | 0.00 | 0.00 |
September | 36.23 | 0.03 | 36.20 | 30.91 | 32.09 | 0.00 | 0.00 | 0.00 |
October | 25.13 | 0.00 | 25.13 | 13.74 | 43.65 | 0.00 | 0.00 | 0.00 |
November | 16.64 | 0.00 | 16.64 | 2.46 | 73.02 | 0.00 | 0.00 | 0.00 |
December | 13.95 | 0.00 | 13.95 | 0.07 | 129.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.28 | 1.38 | 34.90 | 28.94 | 59.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.95 | 0.00 | 13.95 | 0.07 | 16.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.96 | 6.97 | 56.99 | 76.62 | 135.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.46 | 0.00 | 16.46 | 0.36 | 135.65 | 0.00 | 0.00 | 0.00 |
February | 25.29 | 0.00 | 25.29 | 3.29 | 104.10 | 0.00 | 0.00 | 0.00 |
March | 31.12 | 0.00 | 31.12 | 8.03 | 76.42 | 0.00 | 0.00 | 0.00 |
April | 40.87 | 0.40 | 40.48 | 27.59 | 40.38 | 0.00 | 0.00 | 0.00 |
May | 57.39 | 3.07 | 54.32 | 61.43 | 20.85 | 0.00 | 0.00 | 0.00 |
June | 63.96 | 6.97 | 56.99 | 76.61 | 16.47 | 0.00 | 0.00 | 0.00 |
July | 61.05 | 5.13 | 55.92 | 71.31 | 19.45 | 0.00 | 0.00 | 0.00 |
August | 46.60 | 0.93 | 45.67 | 49.71 | 22.57 | 0.00 | 0.00 | 0.00 |
September | 36.23 | 0.03 | 36.20 | 30.91 | 32.09 | 0.00 | 0.00 | 0.00 |
October | 25.13 | 0.00 | 25.13 | 13.73 | 43.65 | 0.00 | 0.00 | 0.00 |
November | 16.64 | 0.00 | 16.64 | 2.46 | 73.02 | 0.00 | 0.00 | 0.00 |
December | 13.95 | 0.00 | 13.95 | 0.07 | 129.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 36.28 | 1.38 | 34.90 | 28.94 | 59.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.95 | 0.00 | 13.95 | 0.07 | 16.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 63.96 | 6.97 | 56.99 | 76.61 | 135.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.13 | 9.48 | 17.66 | 9.59 | 108.52 | 0.00 | 0.00 | 0.00 |
February | 48.08 | 22.12 | 25.96 | 38.53 | 84.29 | 0.00 | 0.00 | 0.00 |
March | 69.29 | 39.19 | 30.10 | 70.09 | 59.59 | 0.00 | 0.00 | 0.00 |
April | 100.98 | 63.59 | 37.38 | 124.72 | 33.27 | 3.50 | 0.00 | 0.00 |
May | 123.85 | 69.54 | 54.31 | 165.39 | 21.28 | 0.00 | 0.00 | 0.00 |
June | 130.69 | 75.28 | 55.41 | 173.09 | 20.29 | 28.83 | 0.00 | 0.00 |
July | 133.60 | 79.61 | 53.99 | 170.89 | 27.66 | 14.67 | 0.00 | 0.00 |
August | 106.45 | 60.05 | 46.40 | 134.17 | 27.66 | 12.50 | 0.00 | 0.00 |
September | 77.35 | 40.04 | 37.31 | 92.90 | 32.79 | 4.17 | 0.00 | 0.00 |
October | 44.44 | 16.97 | 27.47 | 49.61 | 34.74 | 15.00 | 0.00 | 0.00 |
November | 26.54 | 8.13 | 18.41 | 20.64 | 54.63 | 13.17 | 0.00 | 0.00 |
December | 21.06 | 5.36 | 15.71 | 4.69 | 102.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.93 | 40.87 | 35.06 | 88.10 | 50.46 | 91.83 | 0.00 | 0.00 |
Minimum of Months | 21.06 | 5.36 | 15.71 | 4.69 | 20.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.60 | 79.61 | 55.41 | 173.09 | 108.52 | 28.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.13 | 9.48 | 17.66 | 9.59 | 108.52 | 0.00 | 0.00 | 0.00 |
February | 48.08 | 22.12 | 25.96 | 38.53 | 84.29 | 0.00 | 0.00 | 0.00 |
March | 69.29 | 39.19 | 30.10 | 70.09 | 59.59 | 0.00 | 0.00 | 0.00 |
April | 100.98 | 63.59 | 37.38 | 124.72 | 33.27 | 3.50 | 0.00 | 0.00 |
May | 123.85 | 69.54 | 54.31 | 165.39 | 21.28 | 0.00 | 0.00 | 0.00 |
June | 130.69 | 75.28 | 55.41 | 173.09 | 20.29 | 28.83 | 0.00 | 0.00 |
July | 133.60 | 79.61 | 53.99 | 170.89 | 27.66 | 14.67 | 0.00 | 0.00 |
August | 106.45 | 60.05 | 46.40 | 134.17 | 27.66 | 12.50 | 0.00 | 0.00 |
September | 77.35 | 40.04 | 37.31 | 92.90 | 32.79 | 4.17 | 0.00 | 0.00 |
October | 44.44 | 16.97 | 27.47 | 49.61 | 34.74 | 15.00 | 0.00 | 0.00 |
November | 26.54 | 8.13 | 18.41 | 20.64 | 54.63 | 13.17 | 0.00 | 0.00 |
December | 21.06 | 5.36 | 15.71 | 4.69 | 102.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.93 | 40.87 | 35.06 | 88.10 | 50.46 | 91.83 | 0.00 | 0.00 |
Minimum of Months | 21.06 | 5.36 | 15.71 | 4.69 | 20.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.60 | 79.61 | 55.41 | 173.09 | 108.52 | 28.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.13 | 9.48 | 17.66 | 9.59 | 108.52 | 0.00 | 0.00 | 0.00 |
February | 48.08 | 22.12 | 25.96 | 38.53 | 84.29 | 0.00 | 0.00 | 0.00 |
March | 69.29 | 39.19 | 30.10 | 70.09 | 59.59 | 0.00 | 0.00 | 0.00 |
April | 100.98 | 63.59 | 37.38 | 124.72 | 33.27 | 3.50 | 0.00 | 0.00 |
May | 123.85 | 69.54 | 54.31 | 165.39 | 21.28 | 0.00 | 0.00 | 0.00 |
June | 130.69 | 75.28 | 55.41 | 173.09 | 20.29 | 28.83 | 0.00 | 0.00 |
July | 133.60 | 79.61 | 53.99 | 170.89 | 27.66 | 14.67 | 0.00 | 0.00 |
August | 106.45 | 60.05 | 46.40 | 134.17 | 27.66 | 12.50 | 0.00 | 0.00 |
September | 77.35 | 40.04 | 37.31 | 92.90 | 32.79 | 4.17 | 0.00 | 0.00 |
October | 44.44 | 16.97 | 27.47 | 49.61 | 34.74 | 15.00 | 0.00 | 0.00 |
November | 26.54 | 8.13 | 18.41 | 20.64 | 54.63 | 13.17 | 0.00 | 0.00 |
December | 21.06 | 5.36 | 15.71 | 4.69 | 102.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.93 | 40.87 | 35.06 | 88.10 | 50.46 | 91.83 | 0.00 | 0.00 |
Minimum of Months | 21.06 | 5.36 | 15.71 | 4.69 | 20.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.60 | 79.61 | 55.41 | 173.09 | 108.52 | 28.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.13 | 9.48 | 17.66 | 9.59 | 108.52 | 0.00 | 0.00 | 0.00 |
February | 48.08 | 22.12 | 25.96 | 38.53 | 84.29 | 0.00 | 0.00 | 0.00 |
March | 69.29 | 39.19 | 30.10 | 70.09 | 59.59 | 0.00 | 0.00 | 0.00 |
April | 100.98 | 63.59 | 37.38 | 124.72 | 33.27 | 3.50 | 0.00 | 0.00 |
May | 123.85 | 69.54 | 54.31 | 165.39 | 21.28 | 0.00 | 0.00 | 0.00 |
June | 130.69 | 75.28 | 55.41 | 173.09 | 20.29 | 28.83 | 0.00 | 0.00 |
July | 133.60 | 79.61 | 53.99 | 170.89 | 27.66 | 14.67 | 0.00 | 0.00 |
August | 106.45 | 60.05 | 46.40 | 134.17 | 27.66 | 12.50 | 0.00 | 0.00 |
September | 77.35 | 40.04 | 37.31 | 92.90 | 32.79 | 4.17 | 0.00 | 0.00 |
October | 44.44 | 16.97 | 27.47 | 49.61 | 34.74 | 15.00 | 0.00 | 0.00 |
November | 26.54 | 8.13 | 18.41 | 20.64 | 54.63 | 13.17 | 0.00 | 0.00 |
December | 21.06 | 5.36 | 15.71 | 4.69 | 102.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.93 | 40.87 | 35.06 | 88.10 | 50.46 | 91.83 | 0.00 | 0.00 |
Minimum of Months | 21.06 | 5.36 | 15.71 | 4.69 | 20.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.60 | 79.61 | 55.41 | 173.09 | 108.52 | 28.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.13 | 9.48 | 17.66 | 9.59 | 108.52 | 0.00 | 0.00 | 0.00 |
February | 48.08 | 22.12 | 25.96 | 38.53 | 84.29 | 0.00 | 0.00 | 0.00 |
March | 69.29 | 39.19 | 30.10 | 70.09 | 59.59 | 0.00 | 0.00 | 0.00 |
April | 100.98 | 63.59 | 37.38 | 124.72 | 33.27 | 3.50 | 0.00 | 0.00 |
May | 123.85 | 69.54 | 54.31 | 165.39 | 21.28 | 0.00 | 0.00 | 0.00 |
June | 130.69 | 75.28 | 55.41 | 173.09 | 20.29 | 28.83 | 0.00 | 0.00 |
July | 133.60 | 79.61 | 53.99 | 170.89 | 27.66 | 14.67 | 0.00 | 0.00 |
August | 106.45 | 60.05 | 46.40 | 134.17 | 27.66 | 12.50 | 0.00 | 0.00 |
September | 77.35 | 40.04 | 37.31 | 92.90 | 32.79 | 4.17 | 0.00 | 0.00 |
October | 44.44 | 16.97 | 27.47 | 49.61 | 34.74 | 15.00 | 0.00 | 0.00 |
November | 26.54 | 8.13 | 18.41 | 20.64 | 54.63 | 13.17 | 0.00 | 0.00 |
December | 21.06 | 5.36 | 15.71 | 4.69 | 102.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.93 | 40.87 | 35.06 | 88.10 | 50.46 | 91.83 | 0.00 | 0.00 |
Minimum of Months | 21.06 | 5.36 | 15.71 | 4.69 | 20.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.60 | 79.61 | 55.41 | 173.09 | 108.52 | 28.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.13 | 9.48 | 17.66 | 9.59 | 108.52 | 0.00 | 0.00 | 0.00 |
February | 48.08 | 22.12 | 25.96 | 38.53 | 84.29 | 0.00 | 0.00 | 0.00 |
March | 69.29 | 39.19 | 30.10 | 70.09 | 59.59 | 0.00 | 0.00 | 0.00 |
April | 100.98 | 63.59 | 37.38 | 124.72 | 33.27 | 3.50 | 0.00 | 0.00 |
May | 123.85 | 69.54 | 54.31 | 165.39 | 21.28 | 0.00 | 0.00 | 0.00 |
June | 130.69 | 75.28 | 55.41 | 173.09 | 20.29 | 28.83 | 0.00 | 0.00 |
July | 133.60 | 79.61 | 53.99 | 170.89 | 27.66 | 14.67 | 0.00 | 0.00 |
August | 106.45 | 60.05 | 46.40 | 134.17 | 27.66 | 12.50 | 0.00 | 0.00 |
September | 77.35 | 40.04 | 37.31 | 92.90 | 32.79 | 4.17 | 0.00 | 0.00 |
October | 44.44 | 16.97 | 27.47 | 49.61 | 34.74 | 15.00 | 0.00 | 0.00 |
November | 26.54 | 8.13 | 18.41 | 20.64 | 54.63 | 13.17 | 0.00 | 0.00 |
December | 21.06 | 5.36 | 15.71 | 4.69 | 102.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.93 | 40.87 | 35.06 | 88.10 | 50.46 | 91.83 | 0.00 | 0.00 |
Minimum of Months | 21.06 | 5.36 | 15.71 | 4.69 | 20.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.60 | 79.61 | 55.41 | 173.09 | 108.52 | 28.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.13 | 9.48 | 17.66 | 9.59 | 108.52 | 0.00 | 0.00 | 0.00 |
February | 48.08 | 22.12 | 25.96 | 38.53 | 84.29 | 0.00 | 0.00 | 0.00 |
March | 69.29 | 39.19 | 30.10 | 70.09 | 59.59 | 0.00 | 0.00 | 0.00 |
April | 100.98 | 63.59 | 37.38 | 124.72 | 33.27 | 3.50 | 0.00 | 0.00 |
May | 123.85 | 69.54 | 54.31 | 165.39 | 21.28 | 0.00 | 0.00 | 0.00 |
June | 130.69 | 75.28 | 55.41 | 173.09 | 20.29 | 28.83 | 0.00 | 0.00 |
July | 133.60 | 79.61 | 53.99 | 170.89 | 27.66 | 14.67 | 0.00 | 0.00 |
August | 106.45 | 60.05 | 46.40 | 134.17 | 27.66 | 12.50 | 0.00 | 0.00 |
September | 77.35 | 40.04 | 37.31 | 92.90 | 32.79 | 4.17 | 0.00 | 0.00 |
October | 44.44 | 16.97 | 27.47 | 49.61 | 34.74 | 15.00 | 0.00 | 0.00 |
November | 26.54 | 8.13 | 18.41 | 20.64 | 54.63 | 13.17 | 0.00 | 0.00 |
December | 21.06 | 5.36 | 15.71 | 4.69 | 102.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.93 | 40.87 | 35.06 | 88.10 | 50.46 | 91.83 | 0.00 | 0.00 |
Minimum of Months | 21.06 | 5.36 | 15.71 | 4.69 | 20.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.60 | 79.61 | 55.41 | 173.09 | 108.52 | 28.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.13 | 9.48 | 17.66 | 9.59 | 108.52 | 0.00 | 0.00 | 0.00 |
February | 48.08 | 22.12 | 25.96 | 38.53 | 84.29 | 0.00 | 0.00 | 0.00 |
March | 69.29 | 39.19 | 30.10 | 70.09 | 59.59 | 0.00 | 0.00 | 0.00 |
April | 100.98 | 63.59 | 37.38 | 124.72 | 33.27 | 3.50 | 0.00 | 0.00 |
May | 123.85 | 69.54 | 54.31 | 165.39 | 21.28 | 0.00 | 0.00 | 0.00 |
June | 130.69 | 75.28 | 55.41 | 173.09 | 20.29 | 28.83 | 0.00 | 0.00 |
July | 133.60 | 79.61 | 53.99 | 170.89 | 27.66 | 14.67 | 0.00 | 0.00 |
August | 106.45 | 60.05 | 46.40 | 134.17 | 27.66 | 12.50 | 0.00 | 0.00 |
September | 77.35 | 40.04 | 37.31 | 92.90 | 32.79 | 4.17 | 0.00 | 0.00 |
October | 44.44 | 16.97 | 27.47 | 49.61 | 34.74 | 15.00 | 0.00 | 0.00 |
November | 26.54 | 8.13 | 18.41 | 20.64 | 54.63 | 13.17 | 0.00 | 0.00 |
December | 21.06 | 5.36 | 15.71 | 4.69 | 102.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.93 | 40.87 | 35.06 | 88.10 | 50.46 | 91.83 | 0.00 | 0.00 |
Minimum of Months | 21.06 | 5.36 | 15.71 | 4.69 | 20.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.60 | 79.61 | 55.41 | 173.09 | 108.52 | 28.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.13 | 9.48 | 17.66 | 9.59 | 108.52 | 0.00 | 0.00 | 0.00 |
February | 48.08 | 22.12 | 25.96 | 38.53 | 84.29 | 0.00 | 0.00 | 0.00 |
March | 69.29 | 39.19 | 30.10 | 70.09 | 59.59 | 0.00 | 0.00 | 0.00 |
April | 100.98 | 63.59 | 37.38 | 124.72 | 33.27 | 3.50 | 0.00 | 0.00 |
May | 123.85 | 69.54 | 54.31 | 165.39 | 21.28 | 0.00 | 0.00 | 0.00 |
June | 130.69 | 75.28 | 55.41 | 173.09 | 20.29 | 28.83 | 0.00 | 0.00 |
July | 133.60 | 79.61 | 53.99 | 170.89 | 27.66 | 14.67 | 0.00 | 0.00 |
August | 106.45 | 60.05 | 46.40 | 134.17 | 27.66 | 12.50 | 0.00 | 0.00 |
September | 77.35 | 40.04 | 37.31 | 92.90 | 32.79 | 4.17 | 0.00 | 0.00 |
October | 44.44 | 16.97 | 27.47 | 49.61 | 34.74 | 15.00 | 0.00 | 0.00 |
November | 26.54 | 8.13 | 18.41 | 20.64 | 54.63 | 13.17 | 0.00 | 0.00 |
December | 21.06 | 5.36 | 15.71 | 4.69 | 102.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.93 | 40.87 | 35.06 | 88.10 | 50.46 | 91.83 | 0.00 | 0.00 |
Minimum of Months | 21.06 | 5.36 | 15.71 | 4.69 | 20.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.60 | 79.61 | 55.41 | 173.09 | 108.52 | 28.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.13 | 9.48 | 17.66 | 9.59 | 108.52 | 0.00 | 0.00 | 0.00 |
February | 48.08 | 22.12 | 25.96 | 38.53 | 84.29 | 0.00 | 0.00 | 0.00 |
March | 69.29 | 39.19 | 30.10 | 70.09 | 59.59 | 0.00 | 0.00 | 0.00 |
April | 100.98 | 63.59 | 37.38 | 124.72 | 33.27 | 3.50 | 0.00 | 0.00 |
May | 123.85 | 69.54 | 54.31 | 165.39 | 21.28 | 0.00 | 0.00 | 0.00 |
June | 130.69 | 75.28 | 55.41 | 173.09 | 20.29 | 28.83 | 0.00 | 0.00 |
July | 133.60 | 79.61 | 53.99 | 170.89 | 27.66 | 14.67 | 0.00 | 0.00 |
August | 106.45 | 60.05 | 46.40 | 134.17 | 27.66 | 12.50 | 0.00 | 0.00 |
September | 77.35 | 40.04 | 37.31 | 92.90 | 32.79 | 4.17 | 0.00 | 0.00 |
October | 44.44 | 16.97 | 27.47 | 49.61 | 34.74 | 15.00 | 0.00 | 0.00 |
November | 26.54 | 8.13 | 18.41 | 20.64 | 54.63 | 13.17 | 0.00 | 0.00 |
December | 21.06 | 5.36 | 15.71 | 4.69 | 102.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.93 | 40.87 | 35.06 | 88.10 | 50.46 | 91.83 | 0.00 | 0.00 |
Minimum of Months | 21.06 | 5.36 | 15.71 | 4.69 | 20.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 133.60 | 79.61 | 55.41 | 173.09 | 108.52 | 28.83 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169188E+09 | 71310039.14 | 97877819.02 | 80369747.45 | 0.567978E+09 |
February | 0.247115E+09 | 0.112927E+09 | 0.134189E+09 | 0.181626E+09 | 0.399305E+09 |
March | 0.360063E+09 | 0.184588E+09 | 0.175476E+09 | 0.319004E+09 | 0.330711E+09 |
April | 0.444048E+09 | 0.224903E+09 | 0.219145E+09 | 0.481015E+09 | 0.178347E+09 |
May | 0.565046E+09 | 0.270036E+09 | 0.295010E+09 | 0.697190E+09 | 0.101950E+09 |
June | 0.526839E+09 | 0.227995E+09 | 0.298844E+09 | 0.669792E+09 | 77175067.98 |
July | 0.582261E+09 | 0.271431E+09 | 0.310830E+09 | 0.741126E+09 | 94314737.51 |
August | 0.476826E+09 | 0.215967E+09 | 0.260859E+09 | 0.591388E+09 | 0.106341E+09 |
September | 0.361461E+09 | 0.162122E+09 | 0.199339E+09 | 0.410847E+09 | 0.140446E+09 |
October | 0.236305E+09 | 94946522.70 | 0.141359E+09 | 0.226535E+09 | 0.194578E+09 |
November | 0.139483E+09 | 47502805.60 | 91980385.34 | 85518120.39 | 0.306106E+09 |
December | 0.127272E+09 | 44245023.89 | 83027461.39 | 44807408.10 | 0.548021E+09 |
Annual Sum or Average | 0.423591E+10 | 0.192797E+10 | 0.230794E+10 | 0.452922E+10 | 0.304527E+10 |
Minimum of Months | 0.127272E+09 | 44245023.89 | 83027461.39 | 44807408.10 | 77175067.98 |
Maximum of Months | 0.582261E+09 | 0.271431E+09 | 0.310830E+09 | 0.741126E+09 | 0.567978E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.169188E+09 | 71310039.14 | 97877819.02 | 80369747.45 | 0.567978E+09 |
February | 0.247115E+09 | 0.112927E+09 | 0.134189E+09 | 0.181626E+09 | 0.399305E+09 |
March | 0.360063E+09 | 0.184588E+09 | 0.175476E+09 | 0.319004E+09 | 0.330711E+09 |
April | 0.444048E+09 | 0.224903E+09 | 0.219145E+09 | 0.481015E+09 | 0.178347E+09 |
May | 0.565046E+09 | 0.270036E+09 | 0.295010E+09 | 0.697190E+09 | 0.101950E+09 |
June | 0.526839E+09 | 0.227995E+09 | 0.298844E+09 | 0.669792E+09 | 77175067.98 |
July | 0.582261E+09 | 0.271431E+09 | 0.310830E+09 | 0.741126E+09 | 94314737.51 |
August | 0.476826E+09 | 0.215967E+09 | 0.260859E+09 | 0.591388E+09 | 0.106341E+09 |
September | 0.361461E+09 | 0.162122E+09 | 0.199339E+09 | 0.410847E+09 | 0.140446E+09 |
October | 0.236305E+09 | 94946522.70 | 0.141359E+09 | 0.226535E+09 | 0.194578E+09 |
November | 0.139483E+09 | 47502805.60 | 91980385.34 | 85518120.39 | 0.306106E+09 |
December | 0.127272E+09 | 44245023.89 | 83027461.39 | 44807408.10 | 0.548021E+09 |
Annual Sum or Average | 0.423591E+10 | 0.192797E+10 | 0.230794E+10 | 0.452922E+10 | 0.304527E+10 |
Minimum of Months | 0.127272E+09 | 44245023.89 | 83027461.39 | 44807408.10 | 77175067.98 |
Maximum of Months | 0.582261E+09 | 0.271431E+09 | 0.310830E+09 | 0.741126E+09 | 0.567978E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44094952.87 | 0.00 | 44094952.87 | 973668.92 | 0.363316E+09 |
February | 61178459.21 | 0.00 | 61178459.21 | 7967810.82 | 0.251831E+09 |
March | 83356067.63 | 5803.67 | 83350263.96 | 21499896.91 | 0.204693E+09 |
April | 0.105941E+09 | 1024676.05 | 0.104916E+09 | 71511061.96 | 0.104663E+09 |
May | 0.153727E+09 | 8219746.63 | 0.145507E+09 | 0.164537E+09 | 55853578.77 |
June | 0.165784E+09 | 18057648.23 | 0.147727E+09 | 0.198586E+09 | 42683595.44 |
July | 0.163520E+09 | 13751546.81 | 0.149769E+09 | 0.191002E+09 | 52095098.48 |
August | 0.124826E+09 | 2498136.87 | 0.122328E+09 | 0.133142E+09 | 60450229.97 |
September | 93909122.30 | 66224.69 | 93842897.61 | 80123003.54 | 83185829.95 |
October | 67311536.44 | 0.00 | 67311536.44 | 36789726.72 | 0.116915E+09 |
November | 43131065.87 | 0.00 | 43131065.87 | 6386922.73 | 0.189274E+09 |
December | 37360749.73 | 0.00 | 37360749.73 | 178770.31 | 0.346526E+09 |
Annual Sum or Average | 0.114414E+10 | 43623782.94 | 0.110052E+10 | 0.912698E+09 | 0.187149E+10 |
Minimum of Months | 37360749.73 | 0.00 | 37360749.73 | 178770.31 | 42683595.44 |
Maximum of Months | 0.165784E+09 | 18057648.23 | 0.149769E+09 | 0.198586E+09 | 0.363316E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44093496.95 | 0.00 | 44093496.95 | 973469.17 | 0.363317E+09 |
February | 61176534.27 | 0.00 | 61176534.27 | 7966985.36 | 0.251832E+09 |
March | 83353555.62 | 5803.40 | 83347752.23 | 21498145.76 | 0.204694E+09 |
April | 0.105938E+09 | 1024628.02 | 0.104913E+09 | 71507885.70 | 0.104663E+09 |
May | 0.153722E+09 | 8219361.36 | 0.145502E+09 | 0.164531E+09 | 55853185.18 |
June | 0.165779E+09 | 18056801.84 | 0.147722E+09 | 0.198579E+09 | 42683247.37 |
July | 0.163515E+09 | 13750902.26 | 0.149764E+09 | 0.190996E+09 | 52094671.05 |
August | 0.124822E+09 | 2498019.78 | 0.122324E+09 | 0.133137E+09 | 60449900.13 |
September | 93906202.37 | 66221.58 | 93839980.79 | 80119618.98 | 83185583.57 |
October | 67309291.58 | 0.00 | 67309291.58 | 36787411.87 | 0.116915E+09 |
November | 43129596.33 | 0.00 | 43129596.33 | 6386227.14 | 0.189274E+09 |
December | 37359475.66 | 0.00 | 37359475.66 | 178699.15 | 0.346526E+09 |
Annual Sum or Average | 0.114410E+10 | 43621738.24 | 0.110048E+10 | 0.912661E+09 | 0.187149E+10 |
Minimum of Months | 37359475.66 | 0.00 | 37359475.66 | 178699.15 | 42683247.37 |
Maximum of Months | 0.165779E+09 | 18056801.84 | 0.149764E+09 | 0.198579E+09 | 0.363317E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72671252.93 | 25379022.92 | 47292230.02 | 25681415.69 | 0.290671E+09 |
February | 0.116325E+09 | 53524211.52 | 62800646.02 | 93203596.63 | 0.203909E+09 |
March | 0.185586E+09 | 0.104976E+09 | 80609916.19 | 0.187721E+09 | 0.159612E+09 |
April | 0.261737E+09 | 0.164836E+09 | 96901852.08 | 0.323262E+09 | 86244986.20 |
May | 0.331716E+09 | 0.186263E+09 | 0.145454E+09 | 0.442985E+09 | 57004480.16 |
June | 0.338747E+09 | 0.195119E+09 | 0.143628E+09 | 0.448651E+09 | 52596313.71 |
July | 0.357824E+09 | 0.213221E+09 | 0.144603E+09 | 0.457703E+09 | 74086724.94 |
August | 0.285117E+09 | 0.160831E+09 | 0.124287E+09 | 0.359350E+09 | 74074161.27 |
September | 0.200495E+09 | 0.103794E+09 | 96700571.39 | 0.240807E+09 | 84985637.10 |
October | 0.119026E+09 | 45459104.88 | 73566654.93 | 0.132871E+09 | 93056298.97 |
November | 68786201.39 | 21065930.38 | 47720271.01 | 53489003.83 | 0.141607E+09 |
December | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 0.273489E+09 |
Annual Sum or Average | 0.239444E+10 | 0.128881E+10 | 0.110563E+10 | 0.277828E+10 | 0.159134E+10 |
Minimum of Months | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 52596313.71 |
Maximum of Months | 0.357824E+09 | 0.213221E+09 | 0.145454E+09 | 0.457703E+09 | 0.290671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72671252.93 | 25379022.92 | 47292230.02 | 25681415.69 | 0.290671E+09 |
February | 0.116325E+09 | 53524211.52 | 62800646.02 | 93203596.63 | 0.203909E+09 |
March | 0.185586E+09 | 0.104976E+09 | 80609916.19 | 0.187721E+09 | 0.159612E+09 |
April | 0.261737E+09 | 0.164836E+09 | 96901852.08 | 0.323262E+09 | 86244986.20 |
May | 0.331716E+09 | 0.186263E+09 | 0.145454E+09 | 0.442985E+09 | 57004480.16 |
June | 0.338747E+09 | 0.195119E+09 | 0.143628E+09 | 0.448651E+09 | 52596313.71 |
July | 0.357824E+09 | 0.213221E+09 | 0.144603E+09 | 0.457703E+09 | 74086724.94 |
August | 0.285117E+09 | 0.160831E+09 | 0.124287E+09 | 0.359350E+09 | 74074161.27 |
September | 0.200495E+09 | 0.103794E+09 | 96700571.39 | 0.240807E+09 | 84985637.10 |
October | 0.119026E+09 | 45459104.88 | 73566654.93 | 0.132871E+09 | 93056298.97 |
November | 68786201.39 | 21065930.38 | 47720271.01 | 53489003.83 | 0.141607E+09 |
December | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 0.273489E+09 |
Annual Sum or Average | 0.239444E+10 | 0.128881E+10 | 0.110563E+10 | 0.277828E+10 | 0.159134E+10 |
Minimum of Months | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 52596313.71 |
Maximum of Months | 0.357824E+09 | 0.213221E+09 | 0.145454E+09 | 0.457703E+09 | 0.290671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72671252.93 | 25379022.92 | 47292230.02 | 25681415.69 | 0.290671E+09 |
February | 0.116325E+09 | 53524211.52 | 62800646.02 | 93203596.63 | 0.203909E+09 |
March | 0.185586E+09 | 0.104976E+09 | 80609916.19 | 0.187721E+09 | 0.159612E+09 |
April | 0.261737E+09 | 0.164836E+09 | 96901852.08 | 0.323262E+09 | 86244986.20 |
May | 0.331716E+09 | 0.186263E+09 | 0.145454E+09 | 0.442985E+09 | 57004480.16 |
June | 0.338747E+09 | 0.195119E+09 | 0.143628E+09 | 0.448651E+09 | 52596313.71 |
July | 0.357824E+09 | 0.213221E+09 | 0.144603E+09 | 0.457703E+09 | 74086724.94 |
August | 0.285117E+09 | 0.160831E+09 | 0.124287E+09 | 0.359350E+09 | 74074161.27 |
September | 0.200495E+09 | 0.103794E+09 | 96700571.39 | 0.240807E+09 | 84985637.10 |
October | 0.119026E+09 | 45459104.88 | 73566654.93 | 0.132871E+09 | 93056298.97 |
November | 68786201.39 | 21065930.38 | 47720271.01 | 53489003.83 | 0.141607E+09 |
December | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 0.273489E+09 |
Annual Sum or Average | 0.239444E+10 | 0.128881E+10 | 0.110563E+10 | 0.277828E+10 | 0.159134E+10 |
Minimum of Months | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 52596313.71 |
Maximum of Months | 0.357824E+09 | 0.213221E+09 | 0.145454E+09 | 0.457703E+09 | 0.290671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72671252.93 | 25379022.92 | 47292230.02 | 25681415.69 | 0.290671E+09 |
February | 0.116325E+09 | 53524211.52 | 62800646.02 | 93203596.63 | 0.203909E+09 |
March | 0.185586E+09 | 0.104976E+09 | 80609916.19 | 0.187721E+09 | 0.159612E+09 |
April | 0.261737E+09 | 0.164836E+09 | 96901852.08 | 0.323262E+09 | 86244986.20 |
May | 0.331716E+09 | 0.186263E+09 | 0.145454E+09 | 0.442985E+09 | 57004480.16 |
June | 0.338747E+09 | 0.195119E+09 | 0.143628E+09 | 0.448651E+09 | 52596313.71 |
July | 0.357824E+09 | 0.213221E+09 | 0.144603E+09 | 0.457703E+09 | 74086724.94 |
August | 0.285117E+09 | 0.160831E+09 | 0.124287E+09 | 0.359350E+09 | 74074161.27 |
September | 0.200495E+09 | 0.103794E+09 | 96700571.39 | 0.240807E+09 | 84985637.10 |
October | 0.119026E+09 | 45459104.88 | 73566654.93 | 0.132871E+09 | 93056298.97 |
November | 68786201.39 | 21065930.38 | 47720271.01 | 53489003.83 | 0.141607E+09 |
December | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 0.273489E+09 |
Annual Sum or Average | 0.239444E+10 | 0.128881E+10 | 0.110563E+10 | 0.277828E+10 | 0.159134E+10 |
Minimum of Months | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 52596313.71 |
Maximum of Months | 0.357824E+09 | 0.213221E+09 | 0.145454E+09 | 0.457703E+09 | 0.290671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72671252.93 | 25379022.92 | 47292230.02 | 25681415.69 | 0.290671E+09 |
February | 0.116325E+09 | 53524211.52 | 62800646.02 | 93203596.63 | 0.203909E+09 |
March | 0.185586E+09 | 0.104976E+09 | 80609916.19 | 0.187721E+09 | 0.159612E+09 |
April | 0.261737E+09 | 0.164836E+09 | 96901852.08 | 0.323262E+09 | 86244986.20 |
May | 0.331716E+09 | 0.186263E+09 | 0.145454E+09 | 0.442985E+09 | 57004480.16 |
June | 0.338747E+09 | 0.195119E+09 | 0.143628E+09 | 0.448651E+09 | 52596313.71 |
July | 0.357824E+09 | 0.213221E+09 | 0.144603E+09 | 0.457703E+09 | 74086724.94 |
August | 0.285117E+09 | 0.160831E+09 | 0.124287E+09 | 0.359350E+09 | 74074161.27 |
September | 0.200495E+09 | 0.103794E+09 | 96700571.39 | 0.240807E+09 | 84985637.10 |
October | 0.119026E+09 | 45459104.88 | 73566654.93 | 0.132871E+09 | 93056298.97 |
November | 68786201.39 | 21065930.38 | 47720271.01 | 53489003.83 | 0.141607E+09 |
December | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 0.273489E+09 |
Annual Sum or Average | 0.239444E+10 | 0.128881E+10 | 0.110563E+10 | 0.277828E+10 | 0.159134E+10 |
Minimum of Months | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 52596313.71 |
Maximum of Months | 0.357824E+09 | 0.213221E+09 | 0.145454E+09 | 0.457703E+09 | 0.290671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72671252.93 | 25379022.92 | 47292230.02 | 25681415.69 | 0.290671E+09 |
February | 0.116325E+09 | 53524211.52 | 62800646.02 | 93203596.63 | 0.203909E+09 |
March | 0.185586E+09 | 0.104976E+09 | 80609916.19 | 0.187721E+09 | 0.159612E+09 |
April | 0.261737E+09 | 0.164836E+09 | 96901852.08 | 0.323262E+09 | 86244986.20 |
May | 0.331716E+09 | 0.186263E+09 | 0.145454E+09 | 0.442985E+09 | 57004480.16 |
June | 0.338747E+09 | 0.195119E+09 | 0.143628E+09 | 0.448651E+09 | 52596313.71 |
July | 0.357824E+09 | 0.213221E+09 | 0.144603E+09 | 0.457703E+09 | 74086724.94 |
August | 0.285117E+09 | 0.160831E+09 | 0.124287E+09 | 0.359350E+09 | 74074161.27 |
September | 0.200495E+09 | 0.103794E+09 | 96700571.39 | 0.240807E+09 | 84985637.10 |
October | 0.119026E+09 | 45459104.88 | 73566654.93 | 0.132871E+09 | 93056298.97 |
November | 68786201.39 | 21065930.38 | 47720271.01 | 53489003.83 | 0.141607E+09 |
December | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 0.273489E+09 |
Annual Sum or Average | 0.239444E+10 | 0.128881E+10 | 0.110563E+10 | 0.277828E+10 | 0.159134E+10 |
Minimum of Months | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 52596313.71 |
Maximum of Months | 0.357824E+09 | 0.213221E+09 | 0.145454E+09 | 0.457703E+09 | 0.290671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72671252.93 | 25379022.92 | 47292230.02 | 25681415.69 | 0.290671E+09 |
February | 0.116325E+09 | 53524211.52 | 62800646.02 | 93203596.63 | 0.203909E+09 |
March | 0.185586E+09 | 0.104976E+09 | 80609916.19 | 0.187721E+09 | 0.159612E+09 |
April | 0.261737E+09 | 0.164836E+09 | 96901852.08 | 0.323262E+09 | 86244986.20 |
May | 0.331716E+09 | 0.186263E+09 | 0.145454E+09 | 0.442985E+09 | 57004480.16 |
June | 0.338747E+09 | 0.195119E+09 | 0.143628E+09 | 0.448651E+09 | 52596313.71 |
July | 0.357824E+09 | 0.213221E+09 | 0.144603E+09 | 0.457703E+09 | 74086724.94 |
August | 0.285117E+09 | 0.160831E+09 | 0.124287E+09 | 0.359350E+09 | 74074161.27 |
September | 0.200495E+09 | 0.103794E+09 | 96700571.39 | 0.240807E+09 | 84985637.10 |
October | 0.119026E+09 | 45459104.88 | 73566654.93 | 0.132871E+09 | 93056298.97 |
November | 68786201.39 | 21065930.38 | 47720271.01 | 53489003.83 | 0.141607E+09 |
December | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 0.273489E+09 |
Annual Sum or Average | 0.239444E+10 | 0.128881E+10 | 0.110563E+10 | 0.277828E+10 | 0.159134E+10 |
Minimum of Months | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 52596313.71 |
Maximum of Months | 0.357824E+09 | 0.213221E+09 | 0.145454E+09 | 0.457703E+09 | 0.290671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72671252.93 | 25379022.92 | 47292230.02 | 25681415.69 | 0.290671E+09 |
February | 0.116325E+09 | 53524211.52 | 62800646.02 | 93203596.63 | 0.203909E+09 |
March | 0.185586E+09 | 0.104976E+09 | 80609916.19 | 0.187721E+09 | 0.159612E+09 |
April | 0.261737E+09 | 0.164836E+09 | 96901852.08 | 0.323262E+09 | 86244986.20 |
May | 0.331716E+09 | 0.186263E+09 | 0.145454E+09 | 0.442985E+09 | 57004480.16 |
June | 0.338747E+09 | 0.195119E+09 | 0.143628E+09 | 0.448651E+09 | 52596313.71 |
July | 0.357824E+09 | 0.213221E+09 | 0.144603E+09 | 0.457703E+09 | 74086724.94 |
August | 0.285117E+09 | 0.160831E+09 | 0.124287E+09 | 0.359350E+09 | 74074161.27 |
September | 0.200495E+09 | 0.103794E+09 | 96700571.39 | 0.240807E+09 | 84985637.10 |
October | 0.119026E+09 | 45459104.88 | 73566654.93 | 0.132871E+09 | 93056298.97 |
November | 68786201.39 | 21065930.38 | 47720271.01 | 53489003.83 | 0.141607E+09 |
December | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 0.273489E+09 |
Annual Sum or Average | 0.239444E+10 | 0.128881E+10 | 0.110563E+10 | 0.277828E+10 | 0.159134E+10 |
Minimum of Months | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 52596313.71 |
Maximum of Months | 0.357824E+09 | 0.213221E+09 | 0.145454E+09 | 0.457703E+09 | 0.290671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72671252.93 | 25379022.92 | 47292230.02 | 25681415.69 | 0.290671E+09 |
February | 0.116325E+09 | 53524211.52 | 62800646.02 | 93203596.63 | 0.203909E+09 |
March | 0.185586E+09 | 0.104976E+09 | 80609916.19 | 0.187721E+09 | 0.159612E+09 |
April | 0.261737E+09 | 0.164836E+09 | 96901852.08 | 0.323262E+09 | 86244986.20 |
May | 0.331716E+09 | 0.186263E+09 | 0.145454E+09 | 0.442985E+09 | 57004480.16 |
June | 0.338747E+09 | 0.195119E+09 | 0.143628E+09 | 0.448651E+09 | 52596313.71 |
July | 0.357824E+09 | 0.213221E+09 | 0.144603E+09 | 0.457703E+09 | 74086724.94 |
August | 0.285117E+09 | 0.160831E+09 | 0.124287E+09 | 0.359350E+09 | 74074161.27 |
September | 0.200495E+09 | 0.103794E+09 | 96700571.39 | 0.240807E+09 | 84985637.10 |
October | 0.119026E+09 | 45459104.88 | 73566654.93 | 0.132871E+09 | 93056298.97 |
November | 68786201.39 | 21065930.38 | 47720271.01 | 53489003.83 | 0.141607E+09 |
December | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 0.273489E+09 |
Annual Sum or Average | 0.239444E+10 | 0.128881E+10 | 0.110563E+10 | 0.277828E+10 | 0.159134E+10 |
Minimum of Months | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 52596313.71 |
Maximum of Months | 0.357824E+09 | 0.213221E+09 | 0.145454E+09 | 0.457703E+09 | 0.290671E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 72671252.93 | 25379022.92 | 47292230.02 | 25681415.69 | 0.290671E+09 |
February | 0.116325E+09 | 53524211.52 | 62800646.02 | 93203596.63 | 0.203909E+09 |
March | 0.185586E+09 | 0.104976E+09 | 80609916.19 | 0.187721E+09 | 0.159612E+09 |
April | 0.261737E+09 | 0.164836E+09 | 96901852.08 | 0.323262E+09 | 86244986.20 |
May | 0.331716E+09 | 0.186263E+09 | 0.145454E+09 | 0.442985E+09 | 57004480.16 |
June | 0.338747E+09 | 0.195119E+09 | 0.143628E+09 | 0.448651E+09 | 52596313.71 |
July | 0.357824E+09 | 0.213221E+09 | 0.144603E+09 | 0.457703E+09 | 74086724.94 |
August | 0.285117E+09 | 0.160831E+09 | 0.124287E+09 | 0.359350E+09 | 74074161.27 |
September | 0.200495E+09 | 0.103794E+09 | 96700571.39 | 0.240807E+09 | 84985637.10 |
October | 0.119026E+09 | 45459104.88 | 73566654.93 | 0.132871E+09 | 93056298.97 |
November | 68786201.39 | 21065930.38 | 47720271.01 | 53489003.83 | 0.141607E+09 |
December | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 0.273489E+09 |
Annual Sum or Average | 0.239444E+10 | 0.128881E+10 | 0.110563E+10 | 0.277828E+10 | 0.159134E+10 |
Minimum of Months | 56411319.97 | 14346283.14 | 42065036.83 | 12557331.13 | 52596313.71 |
Maximum of Months | 0.357824E+09 | 0.213221E+09 | 0.145454E+09 | 0.457703E+09 | 0.290671E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 44.23 | 678.91 | 159.26 | 53.25 | 106.01 | 0.00 | 0.00 |
February | 144.68 | 526.24 | 254.87 | 93.36 | 161.51 | 0.00 | 0.00 |
March | 247.26 | 392.80 | 331.11 | 137.84 | 193.27 | 0.00 | 0.00 |
April | 425.03 | 217.07 | 424.37 | 174.33 | 250.05 | 0.00 | 0.00 |
May | 641.20 | 115.57 | 536.72 | 207.78 | 328.94 | 0.00 | 0.00 |
June | 667.94 | 90.38 | 534.43 | 189.86 | 344.57 | 0.00 | 0.00 |
July | 693.65 | 106.94 | 556.88 | 212.95 | 343.93 | 0.00 | 0.00 |
August | 540.44 | 123.97 | 449.26 | 163.13 | 286.13 | 0.00 | 0.00 |
September | 377.95 | 171.67 | 351.36 | 125.15 | 226.22 | 0.00 | 0.00 |
October | 194.91 | 230.88 | 226.71 | 70.90 | 155.82 | 0.00 | 0.00 |
November | 65.26 | 376.59 | 140.91 | 36.65 | 104.25 | 0.00 | 0.00 |
December | 21.59 | 655.97 | 122.93 | 33.04 | 89.90 | 0.00 | 0.00 |
Annual Sum or Average | 339.78 | 306.47 | 341.20 | 125.04 | 216.16 | 0.00 | 0.00 |
Minimum of Months | 21.59 | 90.38 | 122.93 | 33.04 | 89.90 | 0.00 | 0.00 |
Maximum of Months | 693.65 | 678.91 | 556.88 | 212.95 | 344.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 514.71 | 8550.22 | 271.32 | 94.75 | 176.57 | 0.00 | 0.00 |
February | 2011.93 | 6591.57 | 480.84 | 221.25 | 259.59 | 0.00 | 0.00 |
March | 3361.15 | 4199.30 | 692.90 | 391.94 | 300.96 | 0.00 | 0.00 |
April | 5273.96 | 1872.88 | 1009.79 | 635.94 | 373.85 | 0.00 | 0.00 |
May | 6529.00 | 728.10 | 1238.49 | 695.43 | 543.06 | 0.00 | 0.00 |
June | 6831.85 | 611.51 | 1306.89 | 752.77 | 554.12 | 0.00 | 0.00 |
July | 6340.69 | 859.66 | 1335.96 | 796.08 | 539.89 | 0.00 | 0.00 |
August | 5020.47 | 860.61 | 1064.51 | 600.47 | 464.03 | 0.00 | 0.00 |
September | 3641.63 | 1024.26 | 773.51 | 400.44 | 373.07 | 0.00 | 0.00 |
October | 1972.70 | 1593.77 | 444.39 | 169.72 | 274.67 | 0.00 | 0.00 |
November | 985.70 | 3450.99 | 265.38 | 81.27 | 184.11 | 0.00 | 0.00 |
December | 254.39 | 7923.97 | 210.62 | 53.56 | 157.05 | 0.00 | 0.00 |
Annual Sum or Average | 3567.44 | 3176.82 | 759.27 | 408.68 | 350.59 | 0.00 | 0.00 |
Minimum of Months | 254.39 | 611.51 | 210.62 | 53.56 | 157.05 | 0.00 | 0.00 |
Maximum of Months | 6831.85 | 8550.22 | 1335.96 | 796.08 | 554.12 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118478E+09 | 0.181838E+10 | 0.426564E+09 | 0.142620E+09 | 0.283944E+09 | 0.00 | 0.00 |
February | 0.350001E+09 | 0.127309E+10 | 0.616586E+09 | 0.225853E+09 | 0.390733E+09 | 0.00 | 0.00 |
March | 0.662265E+09 | 0.105207E+10 | 0.886836E+09 | 0.369187E+09 | 0.517650E+09 | 0.00 | 0.00 |
April | 0.110167E+10 | 0.562637E+09 | 0.109997E+10 | 0.451856E+09 | 0.648119E+09 | 0.00 | 0.00 |
May | 0.171739E+10 | 0.309548E+09 | 0.143754E+10 | 0.556511E+09 | 0.881029E+09 | 0.00 | 0.00 |
June | 0.173130E+10 | 0.234266E+09 | 0.138524E+10 | 0.492105E+09 | 0.893137E+09 | 0.00 | 0.00 |
July | 0.185787E+10 | 0.286436E+09 | 0.149156E+10 | 0.570364E+09 | 0.921194E+09 | 0.00 | 0.00 |
August | 0.144751E+10 | 0.332034E+09 | 0.120330E+10 | 0.436929E+09 | 0.766370E+09 | 0.00 | 0.00 |
September | 0.979650E+09 | 0.444976E+09 | 0.910737E+09 | 0.324377E+09 | 0.586360E+09 | 0.00 | 0.00 |
October | 0.522049E+09 | 0.618387E+09 | 0.607231E+09 | 0.189893E+09 | 0.417338E+09 | 0.00 | 0.00 |
November | 0.169161E+09 | 0.976111E+09 | 0.365227E+09 | 95005611.21 | 0.270221E+09 | 0.00 | 0.00 |
December | 57834543.81 | 0.175696E+10 | 0.329265E+09 | 88490047.79 | 0.240775E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107152E+11 | 0.966488E+10 | 0.107601E+11 | 0.394319E+10 | 0.681687E+10 | 0.00 | 0.00 |
Minimum of Months | 57834543.81 | 0.234266E+09 | 0.329265E+09 | 88490047.79 | 0.240775E+09 | 0.00 | 0.00 |
Maximum of Months | 0.185787E+10 | 0.181838E+10 | 0.149156E+10 | 0.570364E+09 | 0.921194E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.137859E+10 | 0.229009E+11 | 0.726713E+09 | 0.253790E+09 | 0.472922E+09 | 0.00 | 0.00 |
February | 0.486727E+10 | 0.159463E+11 | 0.116325E+10 | 0.535242E+09 | 0.628006E+09 | 0.00 | 0.00 |
March | 0.900249E+10 | 0.112474E+11 | 0.185586E+10 | 0.104976E+10 | 0.806099E+09 | 0.00 | 0.00 |
April | 0.136701E+11 | 0.485452E+10 | 0.261737E+10 | 0.164836E+10 | 0.969019E+09 | 0.00 | 0.00 |
May | 0.174873E+11 | 0.195014E+10 | 0.331716E+10 | 0.186263E+10 | 0.145454E+10 | 0.00 | 0.00 |
June | 0.177082E+11 | 0.158503E+10 | 0.338747E+10 | 0.195119E+10 | 0.143628E+10 | 0.00 | 0.00 |
July | 0.169829E+11 | 0.230251E+10 | 0.357824E+10 | 0.213221E+10 | 0.144603E+10 | 0.00 | 0.00 |
August | 0.134468E+11 | 0.230505E+10 | 0.285117E+10 | 0.160831E+10 | 0.124287E+10 | 0.00 | 0.00 |
September | 0.943910E+10 | 0.265489E+10 | 0.200495E+10 | 0.103794E+10 | 0.967006E+09 | 0.00 | 0.00 |
October | 0.528367E+10 | 0.426876E+10 | 0.119026E+10 | 0.454591E+09 | 0.735667E+09 | 0.00 | 0.00 |
November | 0.255492E+10 | 0.894496E+10 | 0.687862E+09 | 0.210659E+09 | 0.477203E+09 | 0.00 | 0.00 |
December | 0.681351E+09 | 0.212236E+11 | 0.564113E+09 | 0.143463E+09 | 0.420650E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.112503E+12 | 0.100184E+12 | 0.239444E+11 | 0.128881E+11 | 0.110563E+11 | 0.00 | 0.00 |
Minimum of Months | 0.681351E+09 | 0.158503E+10 | 0.564113E+09 | 0.143463E+09 | 0.420650E+09 | 0.00 | 0.00 |
Maximum of Months | 0.177082E+11 | 0.229009E+11 | 0.357824E+10 | 0.213221E+10 | 0.145454E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.112733E+10 | -0.103720E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -90124321.1 | 59.95 | 0.00 | 0.00 |
February | 0.105537E+10 | -974108928.3 | 0.00 | 0.00 | 672.00 | 0.00 | -81265964.3 | 59.95 | 0.00 | 0.00 |
March | 0.122367E+10 | -0.113414E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -89532807.2 | 59.95 | 0.00 | 0.00 |
April | 0.110829E+10 | -0.102243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -85856854.6 | 59.95 | 0.00 | 0.00 |
May | 0.109372E+10 | -0.101101E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -82712533.8 | 59.95 | 0.00 | 0.00 |
June | 0.102416E+10 | -948346208.2 | 0.00 | 0.00 | 720.00 | 0.00 | -75817575.9 | 59.95 | 0.00 | 0.00 |
July | 0.943773E+09 | -869180335.3 | 0.00 | 0.00 | 744.00 | 0.00 | -74592949.0 | 59.95 | 0.00 | 0.00 |
August | 0.982940E+09 | -907200430.5 | 0.00 | 0.00 | 744.00 | 0.00 | -75739204.8 | 59.95 | 0.00 | 0.00 |
September | 0.925077E+09 | -847581051.8 | 0.00 | 0.00 | 720.00 | 0.00 | -77495844.9 | 59.95 | 0.00 | 0.00 |
October | 0.969519E+09 | -882041088.7 | 0.00 | 0.00 | 744.00 | 0.00 | -87477889.8 | 59.95 | 0.00 | 0.00 |
November | 0.982714E+09 | -895941924.3 | 0.00 | 0.00 | 720.00 | 0.00 | -86771786.2 | 59.95 | 0.00 | 0.00 |
December | 0.107878E+10 | -988674471.1 | 0.00 | 0.00 | 744.00 | 0.00 | -90109188.7 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.125154E+11 | -0.115179E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -997496920.3 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.925077E+09 | -0.113414E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -90124321.1 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.122367E+10 | -847581051.8 | 0.00 | 0.00 | 744.00 | 0.00 | -74592949.0 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE3 BULK STORAGE_DAYLCTRL
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.94 | 0.88 | 03-JAN-12:20 | 114.25 | 8.47 | 0.00 | 29.17 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.93 | 0.88 | 02-FEB-10:39 | 142.23 | 9.76 | 0.00 | 64.67 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.93 | 0.88 | 02-MAR-10:39 | 153.92 | 10.04 | 0.00 | 99.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.92 | 0.88 | 01-APR-08:20 | 181.44 | 10.58 | 0.00 | 143.17 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.91 | 0.88 | 01-MAY-09:20 | 886.50 | 12.13 | 0.00 | 258.83 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.91 | 0.88 | 01-JUN-07:30 | 372.81 | 12.48 | 1.83 | 266.17 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.90 | 0.88 | 01-JUL-07:30 | 965.73 | 13.65 | 27.67 | 272.67 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.90 | 0.88 | 01-AUG-07:49 | 261.06 | 12.27 | 0.00 | 222.83 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.91 | 0.88 | 01-SEP-14:20 | 195.45 | 11.13 | 0.00 | 140.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.92 | 0.88 | 01-OCT-08:39 | 159.49 | 10.12 | 0.00 | 94.83 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.93 | 0.88 | 01-NOV-09:20 | 119.44 | 8.86 | 0.00 | 22.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.94 | 0.88 | 01-DEC-11:20 | 110.74 | 8.37 | 0.00 | 8.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.92 | 357.65 | 10.99 | 29.50 | 1621.83 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 226.33 | 0.90 | 0.88 | 110.74 | 8.37 | 0.00 | 8.50 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 437.50 | 0.94 | 0.88 | 965.73 | 13.65 | 27.67 | 272.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: ZONE1 OFFICE_DAYLCTRL
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.81 | 0.64 | 31-JAN-15:09 | 269.00 | 23.09 | 132.00 | 19.67 | 109.85 | 20.75 | 105.83 | 0.00 |
February | 265.33 | 0.76 | 0.61 | 06-FEB-15:20 | 544.50 | 25.12 | 169.33 | 64.67 | 151.18 | 21.86 | 160.50 | 1.67 |
March | 254.17 | 0.74 | 0.61 | 02-MAR-14:20 | 564.26 | 24.56 | 178.33 | 85.00 | 478.05 | 25.22 | 199.50 | 45.00 |
April | 296.33 | 0.73 | 0.61 | 01-APR-12:20 | 407.35 | 22.61 | 190.67 | 102.50 | 439.75 | 23.86 | 237.50 | 70.17 |
May | 437.50 | 0.71 | 0.61 | 01-MAY-14:30 | 343.75 | 21.98 | 258.00 | 174.50 | 460.44 | 23.08 | 305.67 | 91.83 |
June | 401.83 | 0.70 | 0.61 | 01-JUN-13:30 | 374.51 | 22.18 | 249.00 | 167.33 | 455.75 | 23.39 | 316.17 | 97.33 |
July | 409.17 | 0.69 | 0.61 | 01-JUL-13:30 | 390.02 | 22.51 | 250.83 | 187.50 | 531.18 | 23.67 | 329.50 | 115.67 |
August | 352.83 | 0.70 | 0.61 | 01-AUG-13:30 | 384.55 | 22.79 | 226.33 | 150.17 | 436.01 | 23.74 | 281.17 | 92.67 |
September | 344.17 | 0.74 | 0.61 | 01-SEP-14:20 | 489.09 | 23.88 | 212.00 | 107.00 | 415.02 | 24.35 | 236.33 | 56.00 |
October | 299.00 | 0.78 | 0.61 | 01-OCT-13:50 | 346.85 | 23.35 | 167.50 | 48.33 | 147.16 | 22.03 | 167.33 | 5.00 |
November | 255.50 | 0.83 | 0.64 | 09-NOV-14:39 | 197.61 | 21.45 | 108.50 | 8.67 | 100.47 | 20.27 | 96.83 | 0.00 |
December | 226.33 | 0.84 | 0.66 | 16-DEC-14:30 | 170.95 | 20.24 | 81.00 | 0.00 | 94.99 | 20.28 | 78.17 | 0.00 |
Annual Sum or Average | 3785.50 | 0.74 | 378.13 | 22.79 | 2223.50 | 1115.33 | 345.64 | 22.88 | 2514.50 | 575.33 | ||
Minimum of Months | 226.33 | 0.69 | 0.61 | 170.95 | 20.24 | 81.00 | 0.00 | 94.99 | 20.27 | 78.17 | 0.00 | |
Maximum of Months | 437.50 | 0.84 | 0.66 | 564.26 | 25.12 | 258.00 | 187.50 | 531.18 | 25.22 | 329.50 | 115.67 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141191E+11 | 26809.73 | 01-JAN-03:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106688E+11 | 26809.73 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.974766E+10 | 26809.73 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.484652E+10 | 26809.73 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.967895E+09 | 26809.73 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26471590.48 | 16973.62 | 01-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.267033E+09 | 26809.73 | 23-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.314073E+10 | 26809.73 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.644569E+10 | 26809.73 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124129E+11 | 26809.73 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.626428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141191E+11 | 26809.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.515310E+11 | 67573.04 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.369565E+11 | 67573.04 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.293350E+11 | 67573.04 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109141E+11 | 67573.04 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.470235E+09 | 67573.04 | 03-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.510675E+10 | 67573.04 | 30-OCT-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.212997E+11 | 67573.04 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.476321E+11 | 67573.04 | 01-DEC-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203245E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.515310E+11 | 67573.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190366E+12 | 142616.14 | 03-JAN-20:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139491E+12 | 142616.14 | 12-FEB-21:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.944534E+11 | 113971.58 | 15-MAR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.272117E+11 | 68877.31 | 04-APR-18:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.386242E+09 | 17306.59 | 01-MAY-03:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212352E+10 | 30866.87 | 31-OCT-20:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.681380E+11 | 91918.19 | 25-NOV-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177182E+12 | 142616.14 | 18-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.699353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.190366E+12 | 142616.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.636674E+09 | 0.554312E+09 | 6583.20 | 25-MAY-16:00 | 5467.36 | 0.00 |
June | 0.00 | 0.00 | 0.246934E+10 | 0.187645E+10 | 20299.54 | 30-JUN-05:01 | 10890.56 | 0.00 |
July | 0.00 | 0.00 | 0.484641E+10 | 0.359535E+10 | 19038.15 | 05-JUL-05:45 | 8791.02 | 0.00 |
August | 0.00 | 0.00 | 0.308550E+10 | 0.226323E+10 | 18067.26 | 09-AUG-05:02 | 9375.13 | 0.00 |
September | 0.00 | 0.00 | 0.326770E+09 | 0.276909E+09 | 17422.43 | 01-SEP-05:03 | 8386.40 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.113647E+11 | 0.856626E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.484641E+10 | 0.359535E+10 | 20299.54 | 10890.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.146239E+10 | 0.914975E+09 | 40494.66 | 30-JUN-17:12 | 27195.85 | 0.00 |
July | 0.00 | 0.00 | 0.278946E+10 | 0.177439E+10 | 42502.08 | 24-JUL-19:05 | 25131.59 | 0.00 |
August | 0.00 | 0.00 | 0.731758E+09 | 0.456020E+09 | 12954.62 | 08-AUG-15:10 | 7663.59 | 0.00 |
September | 0.00 | 0.00 | 70716657.09 | 51492077.10 | 5919.74 | 01-SEP-15:00 | 4467.37 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.505433E+10 | 0.319687E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.278946E+10 | 0.177439E+10 | 42502.08 | 27195.85 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.901212E+09 | 0.08 | 337.84 | 01-JAN-00:02 | 0.08 |
February | 0.788104E+09 | 0.08 | 337.84 | 01-FEB-00:02 | 0.08 |
March | 0.809134E+09 | 0.07 | 337.84 | 01-MAR-00:03 | 0.08 |
April | 0.395826E+09 | 0.04 | 337.84 | 01-APR-00:05 | 0.08 |
May | 16013431.70 | 0.00 | 337.84 | 01-MAY-00:05 | 0.08 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.109121E+09 | 0.01 | 337.84 | 12-OCT-04:30 | 0.08 |
November | 0.732935E+09 | 0.07 | 337.84 | 01-NOV-00:10 | 0.08 |
December | 0.904860E+09 | 0.08 | 337.84 | 01-DEC-00:03 | 0.08 |
Annual Sum or Average | 0.465721E+10 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.904860E+09 | 0.08 | 337.84 | 0.08 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116462E+10 | 0.70 | 1029.71 | 02-JAN-10:40 | 0.95 |
February | 0.104555E+10 | 0.65 | 1029.71 | 01-FEB-07:10 | 0.95 |
March | 0.118039E+10 | 0.57 | 1029.71 | 01-MAR-18:00 | 0.95 |
April | 0.106019E+10 | 0.44 | 1029.71 | 01-APR-07:10 | 0.95 |
May | 0.107267E+10 | 0.38 | 1029.71 | 01-MAY-07:10 | 0.95 |
June | 0.106465E+10 | 0.38 | 1029.71 | 01-JUN-10:40 | 0.94 |
July | 0.103575E+10 | 0.36 | 1029.71 | 01-JUL-08:30 | 0.94 |
August | 0.111069E+10 | 0.38 | 1029.71 | 01-AUG-06:10 | 0.94 |
September | 0.102418E+10 | 0.37 | 1029.71 | 01-SEP-06:40 | 0.93 |
October | 0.104221E+10 | 0.38 | 1029.71 | 02-OCT-06:10 | 0.94 |
November | 0.103012E+10 | 0.47 | 1029.71 | 01-NOV-06:30 | 0.95 |
December | 0.114440E+10 | 0.68 | 1029.71 | 01-DEC-11:30 | 0.95 |
Annual Sum or Average | 0.129754E+11 | 0.48 | |||
Minimum of Months | 0.102418E+10 | 0.36 | 1029.71 | 0.93 | |
Maximum of Months | 0.118039E+10 | 0.70 | 1029.71 | 0.95 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.167384E+10 | 0.67 | 1653.96 | 01-JAN-00:05 | 0.92 |
February | 0.134446E+10 | 0.64 | 1653.96 | 01-FEB-00:02 | 0.92 |
March | 0.129727E+10 | 0.60 | 1653.96 | 01-MAR-06:01 | 0.92 |
April | 0.888310E+09 | 0.46 | 1653.96 | 03-APR-05:01 | 0.92 |
May | 0.691874E+09 | 0.23 | 1653.96 | 03-MAY-05:01 | 0.92 |
June | 0.683982E+09 | 0.22 | 1653.96 | 29-JUN-17:12 | 0.90 |
July | 0.662447E+09 | 0.21 | 1566.20 | 24-JUL-17:12 | 0.88 |
August | 0.707364E+09 | 0.22 | 661.58 | 24-AUG-15:00 | 0.55 |
September | 0.654966E+09 | 0.21 | 661.58 | 01-SEP-12:30 | 0.55 |
October | 0.764497E+09 | 0.36 | 1653.96 | 30-OCT-05:32 | 0.92 |
November | 0.107228E+10 | 0.58 | 1653.96 | 04-NOV-05:01 | 0.92 |
December | 0.160633E+10 | 0.66 | 1653.96 | 01-DEC-02:62 | 0.92 |
Annual Sum or Average | 0.120476E+11 | 0.42 | |||
Minimum of Months | 0.654966E+09 | 0.21 | 661.58 | 0.55 | |
Maximum of Months | 0.167384E+10 | 0.67 | 1653.96 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.116462E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.104555E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.118039E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.106019E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.122070E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.162136E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.209000E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.178499E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.109644E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.104221E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.103012E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.114440E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.154810E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.103012E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.209000E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.167384E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134446E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.129727E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.888310E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.691874E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.104254E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.134124E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.888507E+09 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.672629E+09 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.764497E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.107228E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.160633E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.132838E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.672629E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.167384E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.116462E+10 | 0.00 | 0.141191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104555E+10 | 0.00 | 0.106688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118039E+10 | 0.00 | 0.974766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106019E+10 | 0.00 | 0.484652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107267E+10 | 0.636674E+09 | 0.967895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106465E+10 | 0.246934E+10 | 26471590.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103575E+10 | 0.484641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111069E+10 | 0.308550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102418E+10 | 0.326770E+09 | 0.267033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104221E+10 | 0.00 | 0.314073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103012E+10 | 0.00 | 0.644569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114440E+10 | 0.00 | 0.124129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129754E+11 | 0.113647E+11 | 0.626428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118039E+10 | 0.484641E+10 | 0.141191E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.167384E+10 | 0.00 | 0.515310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134446E+10 | 0.00 | 0.369565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129727E+10 | 0.00 | 0.293350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.888310E+09 | 0.00 | 0.109141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.691874E+09 | 0.00 | 0.470235E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.683982E+09 | 0.145828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.662447E+09 | 0.278086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.707364E+09 | 0.731758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.654966E+09 | 70716657.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.764497E+09 | 0.00 | 0.510675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107228E+10 | 0.00 | 0.212997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160633E+10 | 0.00 | 0.476321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120476E+11 | 0.504161E+10 | 0.203245E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.654966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167384E+10 | 0.278086E+10 | 0.515310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.116462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107267E+10 | 0.00 | 0.00 | 0.00 | 0.148028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.106465E+10 | 0.00 | 0.00 | 0.00 | 0.556704E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103575E+10 | 0.00 | 0.00 | 0.00 | 0.105425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111069E+10 | 0.00 | 0.00 | 0.00 | 0.674299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102418E+10 | 0.00 | 0.00 | 0.00 | 72254469.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.114440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129754E+11 | 0.00 | 0.00 | 0.00 | 0.250554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118039E+10 | 0.00 | 0.00 | 0.00 | 0.105425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.167384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.129727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.888310E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.691874E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.683982E+09 | 0.00 | 0.00 | 0.00 | 0.358561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.662447E+09 | 0.00 | 0.00 | 0.00 | 0.678797E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.707364E+09 | 0.00 | 0.00 | 0.00 | 0.181143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.654966E+09 | 0.00 | 0.00 | 0.00 | 17662095.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.764497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120476E+11 | 0.00 | 0.00 | 0.00 | 0.123616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.654966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167384E+10 | 0.00 | 0.00 | 0.00 | 0.678797E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427938E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327463E+10 | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318956E+10 | 0.00 | 0.00 | 0.13 |
April | 99905632.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173468E+10 | 0.00 | 0.00 | 0.13 |
May | 0.500601E+09 | 26234061.34 | 0.00 | 460815.19 | 0.00 | 0.343059E+09 | 0.375970E+09 | 0.00 | 0.22 |
June | 0.217945E+09 | 0.315962E+09 | 0.00 | 1554927.12 | 0.00 | 0.00 | 0.127477E+10 | 0.00 | 0.48 |
July | 6962545.94 | 0.541812E+09 | 0.00 | 3611773.98 | 452725.79 | 0.00 | 0.156395E+10 | 0.00 | 0.54 |
August | 40354612.15 | 0.231963E+09 | 0.00 | 4023325.36 | 70261.06 | 0.00 | 0.234215E+10 | 0.00 | 0.64 |
September | 0.654303E+09 | 7076972.19 | 0.00 | 1470086.50 | 0.00 | 71676827.40 | 0.142883E+10 | 0.00 | 0.32 |
October | 0.325394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142260E+10 | 0.00 | 0.00 | 0.12 |
November | 9357336.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236125E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395999E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.185482E+10 | 0.112305E+10 | 0.00 | 11120928.15 | 522986.85 | 0.206368E+11 | 0.698566E+10 | 0.00 | 0.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.654303E+09 | 0.541812E+09 | 0.00 | 4023325.36 | 452725.79 | 0.427938E+10 | 0.234215E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147016E+11 | 0.00 | 0.00 | 0.17 |
February | 0.750638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100196E+11 | 0.00 | 0.00 | 0.17 |
March | 0.198092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.794052E+10 | 0.00 | 0.00 | 0.19 |
April | 0.306126E+10 | 0.00 | 0.00 | 0.00 | 3203461.70 | 0.178228E+10 | 0.00 | 0.00 | 0.18 |
May | 0.252467E+10 | 0.00 | 0.00 | 0.00 | 55240093.40 | 22573987.65 | 0.00 | 0.00 | 0.18 |
June | 0.216972E+10 | 0.375115E+09 | 0.00 | 64143.92 | 4551735.75 | 0.00 | 51581068.89 | 0.00 | 0.20 |
July | 0.168205E+10 | 0.389936E+09 | 0.00 | 1298362.87 | 1444150.45 | 0.00 | 0.955253E+09 | 0.00 | 0.22 |
August | 0.302567E+10 | 76356308.37 | 0.00 | 520804.98 | 1623243.76 | 0.00 | 0.462320E+09 | 0.00 | 0.21 |
September | 0.392293E+10 | 0.00 | 0.00 | 112231.94 | 0.00 | 0.00 | 78284396.29 | 0.00 | 0.19 |
October | 0.396835E+10 | 0.00 | 0.00 | 0.00 | 3820053.05 | 0.577063E+09 | 0.00 | 0.00 | 0.17 |
November | 0.218035E+10 | 0.00 | 0.00 | 0.00 | 4842255.44 | 0.475526E+10 | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133573E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.252666E+11 | 0.841407E+09 | 0.00 | 1995543.71 | 74724993.55 | 0.531562E+11 | 0.154744E+10 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.396835E+10 | 0.389936E+09 | 0.00 | 1298362.87 | 55240093.40 | 0.147016E+11 | 0.955253E+09 | 0.00 | 0.22 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:42
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.246545E+12 | 0.125202E+12 | 0.00 | 0.189810E+11 | 0.739915E+11 |
February | 0.429791E+12 | 0.100956E+12 | 0.00 | 0.140449E+11 | 0.547175E+11 |
March | 0.652606E+12 | 0.688717E+11 | 0.00 | 0.131110E+11 | 0.406643E+11 |
April | 0.850363E+12 | 0.371510E+11 | 0.00 | 0.667492E+10 | 0.140315E+11 |
May | 0.103141E+13 | 0.127999E+11 | 0.00 | 0.368586E+10 | 0.154018E+10 |
June | 0.105966E+13 | 0.111172E+11 | 0.00 | 0.302229E+10 | 0.485914E+10 |
July | 0.109985E+13 | 0.204490E+11 | 0.00 | 0.328989E+10 | 0.936892E+10 |
August | 0.916827E+12 | 0.245522E+11 | 0.00 | 0.559763E+10 | 0.467270E+10 |
September | 0.657861E+12 | 0.320163E+11 | 0.00 | 0.615686E+10 | 0.613969E+09 |
October | 0.339499E+12 | 0.296123E+11 | 0.00 | 0.628959E+10 | 0.448812E+10 |
November | 0.144060E+12 | 0.631419E+11 | 0.00 | 0.930138E+10 | 0.294757E+11 |
December | 0.145777E+12 | 0.122864E+12 | 0.00 | 0.173173E+11 | 0.689594E+11 |
Annual Sum or Average | 0.757425E+13 | 0.648733E+12 | 0.00 | 0.107473E+12 | 0.307383E+12 |
Minimum of Months | 0.144060E+12 | 0.111172E+11 | 0.00 | 0.302229E+10 | 0.613969E+09 |
Maximum of Months | 0.109985E+13 | 0.125202E+12 | 0.00 | 0.189810E+11 | 0.739915E+11 |