Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2024-07-03 12:19:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3291.47 | 680.74 | 680.74 |
Net Site Energy | 3291.47 | 680.74 | 680.74 |
Total Source Energy | 6105.51 | 1262.74 | 1262.74 |
Net Source Energy | 6105.51 | 1262.74 | 1262.74 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2073.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 306.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 13.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1218.22 | 2073.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 2073.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 4.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 306.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 13.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2073.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 4.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 133.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 306.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 13.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 67.23 | 428.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 251.95 | 428.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 67.23 | 428.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 251.95 | 428.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1218.223 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1218.223 | 100.00 |
Total On-Site and Utility Electric Sources | 1218.223 | 100.00 |
Total Electricity End Uses | 1218.223 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 104.50 |
Time Setpoint Not Met During Occupied Cooling | 1.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2955.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINE STORAGE OFFICE FRONT WALL WINDOW | FINE STORAGE OFFICE LEFT WALL WINDOW | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINE STORAGE OFFICE FRONT WALL WINDOW | FINE STORAGE OFFICE LEFT WALL WINDOW | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 149.82 | 39.41 | 0.00 | 0.00 | 110.41 |
Gross Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Above Ground Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 149.82 | 39.41 | 0.00 | 0.00 | 110.41 |
Gross Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Above Ground Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 14.86 |
Skylight-Roof Ratio [%] | 0.32 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 28.42 | 28.42 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 121.40 | 121.40 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 149.82 | 149.82 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 149.82 | 149.82 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 09-JAN-15:39 | 29-JAN-00:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 377468.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 20286.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1693.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 86740.93 | 377468.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 377468.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 20286.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1693.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2247.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 15.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 421.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 971.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 42.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3858.11 | 2247.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 464.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 200.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 8.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 797.93 | 464.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 464.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 200.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 8.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 797.93 | 464.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.27 |
ZONE2 FINE STORAGE DIRECT AIR | 5.04 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 15.82 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 15.82 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 212491.56 |
PSZ-OFFICE HEATING COIL | 24633.03 |
PSZ-FINE STORAGE HEATING COIL | 95790.97 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.27 | 1.27 | 1.27 | 1.27 | 1.27 | 1.27 | 1.00 | 1.00 | 1.27 |
PSZ-FINE STORAGE | 5.04 | 5.04 | 5.04 | 5.04 | 5.04 | 5.04 | 1.00 | 1.00 | 5.04 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.27 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 5.04 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.27 | 2117.22 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 5.04 | 8115.89 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.27 | 1.27 | 1.27 | 1.27 | 21087.57 | 24633.03 | 32.21 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 5.04 | 5.04 | 5.04 | 5.04 | 83453.76 | 95790.97 | 26.67 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.27 | 0.636950 | 0.849267 | 21087.57 | 10543.78 | 0.800660 | 0.800660 |
PSZ-FINE STORAGE COOLING COIL | 5.04 | 2.52 | 3.36 | 83453.76 | 41726.88 | 0.800660 | 0.800660 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE OFFICE FRONT WALL | FINE STORAGE OFFICE FRONT WALL WINDOW | |
FINE STORAGE OFFICE LEFT WALL | FINE STORAGE OFFICE LEFT WALL WINDOW | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 68 | 44 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 117.24 | 28.42 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 605.78 | 121.40 | 11 | 8 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 3 | 3 | 0.167 | 0.2832 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
2 | SEMIHEATED_ROOF | 18 | 3 | 3 | 0.167 | 0.5694 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | NONRES_EXT_WALL_GRD | 19 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 4.938 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 200.0 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 4.938 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1413 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.5841E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
3 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
5 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.697 |
6 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
7 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2025 |
16 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
17 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5000E-02 |
18 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2025 |
19 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
20 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
21 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
22 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
23 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.998 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 17.04 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
34 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
35 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
36 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
37 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
38 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
39 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
40 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
41 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
42 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
43 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
2 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
3 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
4 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
5 | 3 | -0.59210580E-06 | 0.24981739E-08 | -0.36372244E-05 | 0.72772073E-18 |
6 | 2 | 0.75696892 | 0.34513142E-02 | 1.0299324 | -0.69732202E-06 |
7 | 1 | -21.691030 | 0.23360136 | -6.3664179 | 0.19745034 |
8 | 0 | 21.391019 | 0.21990456 | 5.7934464 | |
9 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
10 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
11 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
12 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
13 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
14 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
15 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
16 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
17 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
18 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
19 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
20 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
21 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
22 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
23 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
24 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
25 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
26 | 0 | 4.9377744 | 4.9377744 | 4.9377744 | |
27 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
28 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
29 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
30 | 0 | 200.00000 | 200.00000 | 200.00000 | |
31 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
32 | 0 | 4.9377744 | 4.9377744 | 4.9377744 | |
33 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
34 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
35 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
36 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
37 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
38 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
39 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
40 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
41 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
42 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
43 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
44 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
45 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
46 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
47 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
48 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
49 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
50 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
51 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
52 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
53 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
54 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
55 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
56 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
57 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
58 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
59 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
60 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
61 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
62 | 7 | -0.30042996E-08 | -0.19492532E-14 | 0.18571942E-14 | -0.50265421E-16 |
63 | 6 | 0.40686135E-05 | 0.27025218E-08 | 0.31944093E-02 | -0.26797382E-04 |
64 | 5 | -0.28598357E-03 | 0.15982348E-05 | -0.22398257 | 0.19584275E-02 |
65 | 4 | 0.65354345E-02 | 0.72696005E-04 | 4.8338424 | -0.45306284E-01 |
66 | 3 | -0.57256805E-01 | 0.57768437E-03 | -38.045688 | 0.39892203 |
67 | 2 | 0.20312160 | 0.96045137E-03 | 116.53119 | -1.4185711 |
68 | 1 | -0.29305691 | 0.29236276E-03 | -143.93511 | 2.0494970 |
69 | 0 | 0.14285049 | 0.70905046E-05 | 60.838472 | |
70 | 7 | -0.73310212E-08 | 0.16277859E-15 | -0.15558641E-14 | 0.17403554E-16 |
71 | 6 | 0.21213446E-05 | 0.11327280E-08 | 0.32008460E-02 | -0.26851379E-04 |
72 | 5 | -0.12816801E-03 | 0.66411688E-06 | -0.22434819 | 0.19616548E-02 |
73 | 4 | 0.27852559E-02 | 0.30072908E-04 | 4.8399282 | -0.45364789E-01 |
74 | 3 | -0.23934818E-01 | 0.23808113E-03 | -38.080046 | 0.39930184 |
75 | 2 | 0.84241938E-01 | 0.39442809E-03 | 116.59803 | -1.4194653 |
76 | 1 | -0.12110434 | 0.11951395E-03 | -143.97445 | 2.0501436 |
77 | 0 | 0.58923671E-01 | 0.28881054E-05 | 60.838472 | |
78 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
79 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
80 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
81 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
82 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
83 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
84 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
85 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
86 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
87 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
88 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
89 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
90 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
91 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
92 | 7 | -0.94456721E-13 | 0.24575595E-14 | -0.29735092E-12 | 0.15324278E-15 |
93 | 6 | 0.65405332E-08 | 0.22114619E-09 | 0.28546880E-07 | -0.13451374E-12 |
94 | 5 | -0.97466953E-04 | 0.18937623E-05 | -0.18947583E-03 | 0.64660656E-08 |
95 | 4 | 0.99417931E-01 | 0.92215111E-03 | 0.29140875 | -0.33466744E-04 |
96 | 3 | -2.3345767 | 0.28579858E-01 | -7.2517161 | 0.28937395E-01 |
97 | 2 | 15.247323 | 0.10163225 | 40.822959 | -0.33280368 |
98 | 1 | -29.125752 | 0.45869584E-01 | -80.508872 | 1.0778326 |
99 | 0 | 16.291614 | 0.92288667E-03 | 46.824339 | |
100 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
101 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
102 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
103 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.46_SHGC_SOUTH_0.4 | 34 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 | ||
2 | NONRESWINDOW_U_0.46_SHGC_NORTH_0.4 | 35 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 | ||
3 | NONRESWINDOW_U_0.46_SHGC_EAST_0.4 | 36 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 | ||
4 | NONRESWINDOW_U_0.46_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.615 | 2.615 | 1.000 | 0.401 | ||
5 | SKYLIGHT_U_0.58_SHGC_0.55 | 38 | 1 | VerySmooth | 3.298 | 3.298 | 1.000 | 0.552 | ||
6 | SEMIHTDSKYLIGHT_U_0.81_SHGC_0.55 | 39 | 1 | VerySmooth | 4.601 | 4.601 | 1.000 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.53892E-002 | 0.31435 | 0.47035 | 0.47035 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12001 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.47116 | 0.31637 | 0.31637 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 1.49357E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 0.14978 | 0.14978 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 4.00836E-002 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.120 | 1.0564 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_0.81_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 4.409 | 0.549 | 0.552 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.264 | 7.065E-004 | 4.615E-004 | 0.231 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone ZONE1 OFFICE | 1.2500 |
3 | Zone ZONE2 FINE STORAGE | 1.2500 |
4 | Zone ZONE3 BULK STORAGE | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone ZONE1 OFFICE | 1.1500 |
3 | Zone ZONE2 FINE STORAGE | 1.1500 |
4 | Zone ZONE3 BULK STORAGE | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 11523.95446 | 13252.54763 | 0.85806 | 0.98677 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 25.97200 | 7.00497E-003 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 13825.55073 | 17281.93841 | 1.01912 | 1.27390 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90000 | 6.45023E-005 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 39807.93363 | 45779.12368 | 2.96398 | 3.40857 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 25.80200 | 7.00471E-003 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 54171.29379 | 67714.11724 | 4.03315 | 5.04144 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -41.90000 | 6.45023E-005 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 27.09400 | 7.00668E-003 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 169993.24495 | 212491.55619 | 12.65609 | 15.82012 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90000 | 6.45023E-005 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 13312.06 | 0.98677 | 0.98677 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 24633.03 | 1.27390 | 1.27390 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 44739.15 | 3.40857 | 3.40857 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 95790.97 | 5.04144 | 5.04144 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.27390 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.04144 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 15.82012 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 15.82012 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 212491.55821 |
6 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.27390 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.27390 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.27390 |
9 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.27390 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.27390 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.27390 |
12 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
13 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.04144 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.04144 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.04144 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 5.04144 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.04144 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 5.04144 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.27390 |
23 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 5.04144 |
24 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.27390 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
26 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.27390 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2117.21882 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.27390 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.27390 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.27390 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.27390 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.27390 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.63695 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.84927 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21087.57000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 10543.78500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
39 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21087.57000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 24633.03444 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.21000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
43 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 24633.03444 |
44 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.04144 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
46 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 5.04144 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 8115.89047 |
48 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 5.04144 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 5.04144 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 5.04144 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 5.04144 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 5.04144 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 2.52072 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.36096 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 83453.76000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 41726.88000 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
59 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 83453.76000 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 95790.96532 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 26.67000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
63 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 95790.96532 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 20099.1 | 10.67 | 10.43 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 79541.8 | 10.67 | 10.43 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.5209109504 | 0.5182330244 | Pass | Pass | 0.9433446519 | 0.8226995375 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 1.0571353530 | 1.0233617164 | Pass | Pass | 0.6725661748 | 0.6896450647 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 1.1472304588E-015 | 1.0770371418E-015 | Pass | Pass | 1.7213043950E-002 | 1.5509956415E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4846.19 | 628.97 | 0.00 | 196.56 | 620.71 | 6292.45 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 110.54 | 88.07 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 39.02 | 29.17 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.138 | 0.141 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 110.54 | 20.66 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 39.02 | 7.50 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.058 | 0.058 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.30 | 0.273 | 0.283 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.30 | 0.528 | 0.569 | 3204.84 | 3189.98 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.662 | 0.787 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.662 | 0.787 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.46_SHGC_WEST_0.4 | 9.73 | 0.00 | 0.00 | 9.73 | 9.73 | 2.615 | 0.401 | 0.442 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.46_SHGC_WEST_0.4 | 10.79 | 0.00 | 0.00 | 10.79 | 10.79 | 2.615 | 0.401 | 0.442 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.46_SHGC_NORTH_0.4 | 3.95 | 0.00 | 0.00 | 3.95 | 3.95 | 2.615 | 0.401 | 0.442 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.46_SHGC_NORTH_0.4 | 3.95 | 0.00 | 0.00 | 3.95 | 3.95 | 2.615 | 0.401 | 0.442 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINE STORAGE OFFICE FRONT WALL WINDOW | NONRESWINDOW_U_0.46_SHGC_WEST_0.4 | 89.88 | 0.00 | 0.00 | 89.88 | 89.88 | 2.615 | 0.401 | 0.442 | No | FINE STORAGE OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
FINE STORAGE OFFICE LEFT WALL WINDOW | NONRESWINDOW_U_0.46_SHGC_NORTH_0.4 | 31.51 | 0.00 | 0.00 | 31.51 | 31.51 | 2.615 | 0.401 | 0.442 | No | FINE STORAGE OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_0.81_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.601 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.409 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_0.81_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.601 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.409 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_0.81_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.601 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.409 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_0.81_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.601 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.409 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_0.81_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.601 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.409 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_0.81_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.601 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.409 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_0.81_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.601 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.409 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_0.81_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.601 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.409 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_0.81_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.601 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.409 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_0.81_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 4.601 | 0.551 | 0.552 | 0.000 | 0.000 | CurtainWall | 4.409 | 0.549 | 0.552 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 164.68 | 2.794 | 0.414 | 0.452 | |||||||||||||||||
North Total or Average | 39.41 | 2.615 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 125.27 | 2.851 | 0.419 | 0.455 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 2.839 | 4.938 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINE STORAGE OFFICE FRONT WALL WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
FINE STORAGE OFFICE LEFT WALL WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.06 | 83.06 | 133.03 | |
Exterior Lighting Total | 8532.22 | 133.03 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21087.57 | 16883.97 | 4203.60 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 83453.76 | 66818.09 | 16635.67 | 0.80 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 20099.1 | 10.67 | 10.43 | ||||
PSZ-FINE STORAGE COOLING COIL | 79541.8 | 10.67 | 10.43 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 212491.56 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 24633.03 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 95790.97 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 340.63 | 15.82 | 10053.80 | 635.51 | 1.00 | 1.20 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 966.87 | 1.27 | 2117.22 | 1662.00 | 1.00 | 1.29 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.60 | 966.87 | 5.04 | 8115.89 | 1609.84 | 1.00 | 1.18 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.12 | 1.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 11523.95 | 13252.55 | 55.95 | 0.858 | 0.987 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00826 | 25.97 | 0.00700 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 39807.93 | 45779.12 | 32.85 | 2.964 | 3.409 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 26.70 | 26.70 | 0.00817 | 25.80 | 0.00700 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 0.00 | 29.72 | 0.00711 | 27.09 | 0.00701 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 13825.55 | 17281.94 | 72.96 | 1.019 | 1.274 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00816 | -41.90 | 0.00006 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 54171.29 | 67714.12 | 48.60 | 4.033 | 5.041 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00795 | -41.90 | 0.00006 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 169993.24 | 212491.56 | 66.30 | 12.656 | 15.820 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00775 | -41.90 | 0.00006 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 0.99 | 0.99 | 1.27 | 1.27 | 1.2739 | 1.2739 | 1.2739 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 3.41 | 3.41 | 5.04 | 5.04 | 5.0414 | 5.0414 | 5.0414 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3 BULK STORAGE UNIT HEATER | 212491.558 | 212491.558 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 212491.56 | 212491.56 | 15.820116 | 10.00 | 10.00 | 0.00775324 | 21.11 | 14.74 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 10.00 | 0.00775324 | 100.0000 | 212491.56 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 21087.570 | 16883.974 | 1.273900 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 10543.78 | 10304.04 | 0.849267 | 24.11 | 15.95 | 0.00812723 | 11.41 | 10.87 | 0.00800000 | 25.97 | 0.00700497 | 15.63 | 12.0439 | 23.90 | 0.00825701 | 44.0398 | 11523.95 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 24633.034 | 24633.034 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 24633.03 | 24633.03 | 1.273900 | 15.98 | 12.28 | 0.00750967 | 32.21 | 18.59 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 8.0293 | 21.10 | 0.00815965 | 51.5958 | 13825.55 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 83453.760 | 66818.087 | 5.041440 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 41726.88 | 41590.94 | 3.360960 | 26.61 | 16.74 | 0.00802110 | 14.26 | 12.06 | 0.00800000 | 25.97 | 0.00700497 | 15.63 | 12.6366 | 26.70 | 0.00816575 | 36.8761 | 39803.42 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 95790.965 | 95790.965 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 95790.97 | 95790.97 | 5.041442 | 10.72 | 9.81 | 0.00728180 | 26.67 | 16.74 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 8.4244 | 15.56 | 0.00794575 | 71.1613 | 54171.29 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3 BULK STORAGE UNIT HEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 212491.558 | 212491.558 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 15.820116 | 18.75378677 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 212491.56 | 212491.56 | 1.0000 | 18.75378677 | 15.820116 | 10.00 | 10.00 | 0.00775324 | 29582.4 | 21.11 | 14.74 | 0.00800000 | 41534.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 212491.56 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 10.00 | 0.00775324 | 10.00 | 0.00775324 | 100.0000 | 212491.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21087.570 | 16883.974 | 1.273900 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9481 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.273900 | 1.51013134 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 10543.78 | 10304.04 | 1.0000 | 1.00675408 | 0.849267 | 24.11 | 15.95 | 0.00812723 | 44920.8 | 11.41 | 10.87 | 0.00800000 | 31646.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10543.78 | 25.97 | 0.00700497 | 15.63 | 0.10228463 | 12.0439 | 23.90 | 0.00825701 | 23.90 | 0.00825701 | 44.0398 | 11523.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24633.034 | 24633.034 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.273900 | 1.51013134 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 24633.03 | 24633.03 | 1.0000 | 1.51013134 | 1.273900 | 15.98 | 12.28 | 0.00750967 | 35058.6 | 32.21 | 18.59 | 0.00800000 | 52852.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24633.03 | -41.90 | 0.00006450 | -41.90 | 0.10228463 | 8.0293 | 21.03 | 0.00815965 | 21.10 | 0.00815965 | 51.5958 | 13825.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 83453.760 | 66818.087 | 5.041440 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7508 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 5.041442 | 5.97632334 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | Sensible | 41726.88 | 41590.94 | 1.0000 | 3.98421405 | 3.360960 | 26.61 | 16.74 | 0.00802110 | 47194.7 | 14.26 | 12.06 | 0.00800000 | 34545.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41726.88 | 25.97 | 0.00700497 | 15.63 | 0.42471127 | 12.6366 | 26.70 | 0.00816575 | 26.70 | 0.00816575 | 36.8761 | 39803.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 95790.965 | 95790.965 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 5.041442 | 5.97632334 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 95790.97 | 95790.97 | 1.0000 | 5.97632334 | 5.041442 | 10.72 | 9.81 | 0.00728180 | 29127.4 | 26.67 | 16.74 | 0.00800000 | 47203.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 95790.97 | -41.90 | 0.00006450 | -41.90 | 0.42471127 | 8.4244 | 15.56 | 0.00794575 | 15.56 | 0.00794575 | 71.1613 | 54171.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | FixedDryBulb | 0.10 | 1.27 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | FixedDryBulb | 0.42 | 5.04 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2591.17 | 2863.33 | 2174.33 |
ZONE2 FINE STORAGE | 3176.67 | 2814.33 | 2447.50 |
ZONE3 BULK STORAGE | 3202.33 | 3220.67 | 2881.33 |
Facility | 3575.00 | 3295.17 | 2955.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 393.83 | 1.50 | 86.83 | 1.50 |
ZONE2 FINE STORAGE | 687.00 | 12.83 | 30.17 | 0.00 |
ZONE3 BULK STORAGE | 3.00 | 0.00 | 0.00 | 0.00 |
Facility | 995.33 | 14.33 | 104.50 | 1.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.854 | 0.270 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.764 | 0.147 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.073 | 0.000 | 0.036 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.50 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.36 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.50 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.36 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.42 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.28 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 3068256.13 | 0.00 | 3068256.13 | 1465120.67 | 4533376.79 | 3225648.14 | 5678.38 | 2032.92 | 1048.70 | 0.00 |
ZONE2 FINE STORAGE | 8157192.44 | 0.00 | 8157192.44 | 4361427.52 | 12518619.96 | 13393694.68 | 5694.41 | 2349.12 | 716.47 | 14.86 |
ZONE3 BULK STORAGE | 0.00 | 10605752.57 | 10605752.57 | 20447806.03 | 31053558.60 | 30805497.77 | 8648.52 | 10.50 | 100.98 | 4375.33 |
Total Facility | 11225448.57 | 10605752.57 | 21831201.14 | 26274354.21 | 48105555.35 | 47424840.58 | 8715.42 | 2357.37 | 1145.93 | 4375.92 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.2344 | 0.0000 | 0.2344 | 0.0746 | 0.3090 | 0.1023 | 554.38 | 2032.92 | 1048.70 |
ZONE2 FINE STORAGE | 0.6141 | 0.0000 | 0.6141 | 0.1192 | 0.7333 | 0.4247 | 583.82 | 2348.98 | 703.20 |
ZONE3 BULK STORAGE | 0.0000 | 0.3476 | 0.3476 | 0.7173 | 1.0649 | 0.9768 | 3591.42 | 3.50 | 41.08 |
Total Facility | 0.8485 | 0.3476 | 1.1960 | 0.9111 | 2.1071 | 1.5038 | 3591.42 | 2350.23 | 1073.02 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 4311716.99 | 0.00 | 4311716.99 | 3225648.14 | 5672.57 | 0.28 | 3087.15 | 0.00 |
PSZ-FINE STORAGE | 11463027.80 | 0.00 | 11463027.80 | 13393694.68 | 5686.34 | 0.54 | 3073.12 | 14.84 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.3294 | 0.0000 | 0.3294 | 0.1023 | 548.57 | 0.28 | 3087.15 |
PSZ-FINE STORAGE | 0.8629 | 0.0000 | 0.8629 | 0.4247 | 576.18 | 0.54 | 3059.28 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2368.43 | 735.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2434.00 | 659.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.3122 | 0.6235 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.7513 | 2.0199 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 16 | 16 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 382 |
Defaulted Fields | 322 |
Fields with Defaults | 1019 |
Autosized Fields | 42 |
Autosizable Fields | 96 |
Autocalculated Fields | 94 |
Autocalculatable Fields | 138 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1218.22 | 6183.75 | 23-JUL-16:00 | 86740.93 | 09-JAN-15:40 |
Electricity:Building | 760.14 | 6131.39 | 01-JAN-00:10 | 58533.65 | 29-JUL-15:00 |
Electricity:Zone:ZONE1 OFFICE | 60.03 | 926.90 | 01-JAN-00:10 | 3790.09 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 760.12 | 6131.39 | 01-JAN-00:10 | 56228.36 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 460.96 | 3104.69 | 01-JAN-00:10 | 36895.31 | 29-JUL-15:00 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 306.79 | 0.00 | 18-MAR-17:10 | 20286.91 | 02-JAN-07:10 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.02 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUL-15:00 |
Ventilation (simple):Fans:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUL-15:00 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 0.02 | 0.00 | 01-JAN-00:10 | 2305.29 | 29-JUL-15:00 |
ElectricityPurchased:Facility | 1218.22 | 6183.75 | 23-JUL-16:00 | 86740.93 | 09-JAN-15:40 |
ElectricityPurchased:Plant | 1218.22 | 6183.75 | 23-JUL-16:00 | 86740.93 | 09-JAN-15:40 |
Cogeneration:ElectricityPurchased | 1218.22 | 6183.75 | 23-JUL-16:00 | 86740.93 | 09-JAN-15:40 |
General:Cogeneration:ElectricityPurchased | 1218.22 | 6183.75 | 23-JUL-16:00 | 86740.93 | 09-JAN-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1218.22 | 6183.75 | 23-JUL-16:00 | 86740.93 | 09-JAN-15:40 |
ElectricityNet:Plant | 1218.22 | 6183.75 | 23-JUL-16:00 | 86740.93 | 09-JAN-15:40 |
Cogeneration:ElectricityNet | 1218.22 | 6183.75 | 23-JUL-16:00 | 86740.93 | 09-JAN-15:40 |
General:Cogeneration:ElectricityNet | 1218.22 | 6183.75 | 23-JUL-16:00 | 86740.93 | 09-JAN-15:40 |
Electricity:HVAC | 311.65 | 0.00 | 18-MAR-17:10 | 22275.76 | 29-JUL-16:00 |
General:Fans:Electricity | 306.76 | 0.00 | 18-MAR-17:10 | 20286.91 | 02-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 4.88 | 0.00 | 01-JAN-00:10 | 12042.65 | 29-JUL-16:00 |
General:Cooling:Electricity | 4.88 | 0.00 | 01-JAN-00:10 | 12042.65 | 29-JUL-16:00 |
ExteriorLights:Electricity | 133.03 | 0.00 | 01-JAN-11:20 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 133.03 | 0.00 | 01-JAN-11:20 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 13.41 | 0.00 | 02-JAN-00:10 | 1858.18 | 12-JAN-13:00 |
WaterSystems:Electricity | 13.41 | 0.00 | 02-JAN-00:10 | 1858.18 | 12-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 13.41 | 0.00 | 02-JAN-00:10 | 1858.18 | 12-JAN-13:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2073.25 | 5250.00 | 21-JUN-05:10 | 377468.30 | 29-JAN-00:10 |
NaturalGas:HVAC | 2073.25 | 5250.00 | 21-JUN-05:10 | 377468.30 | 29-JAN-00:10 |
Heating:NaturalGas | 2073.25 | 5250.00 | 21-JUN-05:10 | 377468.30 | 29-JAN-00:10 |
General:Heating:NaturalGas | 2073.25 | 5250.00 | 21-JUN-05:10 | 377468.30 | 29-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3165.65 | 0.00 | 18-MAR-17:10 | 603902.50 | 29-JAN-00:10 |
EnergyTransfer:Building | 1668.17 | 0.00 | 18-MAR-17:10 | 309501.92 | 29-JAN-00:20 |
EnergyTransfer:Zone:ZONE1 OFFICE | 95.47 | 0.00 | 01-JAN-00:40 | 27306.31 | 27-FEB-07:10 |
Heating:EnergyTransfer | 1622.62 | 0.00 | 18-MAR-17:10 | 309501.92 | 29-JAN-00:20 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 79.60 | 0.00 | 01-JAN-00:40 | 27306.31 | 27-FEB-07:10 |
General:Heating:EnergyTransfer | 1622.62 | 0.00 | 18-MAR-17:10 | 309501.92 | 29-JAN-00:20 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 79.60 | 0.00 | 01-JAN-00:40 | 27306.31 | 27-FEB-07:10 |
Cooling:EnergyTransfer | 45.54 | 0.00 | 01-JAN-00:10 | 40783.66 | 19-JUN-18:10 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 15.87 | 0.00 | 01-JAN-00:10 | 10598.54 | 12-AUG-05:50 |
General:Cooling:EnergyTransfer | 45.54 | 0.00 | 01-JAN-00:10 | 40783.66 | 19-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 15.87 | 0.00 | 01-JAN-00:10 | 10598.54 | 12-AUG-05:50 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 338.58 | 0.00 | 01-JAN-00:40 | 77491.57 | 29-JAN-00:20 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 308.90 | 0.00 | 01-JAN-00:40 | 77491.57 | 29-JAN-00:20 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 308.90 | 0.00 | 01-JAN-00:40 | 77491.57 | 29-JAN-00:20 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 29.67 | 0.00 | 01-JAN-00:10 | 40783.66 | 19-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 29.67 | 0.00 | 01-JAN-00:10 | 40783.66 | 19-JUN-18:10 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1234.12 | 0.00 | 09-FEB-12:00 | 223835.48 | 28-JAN-23:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1234.12 | 0.00 | 09-FEB-12:00 | 223835.48 | 28-JAN-23:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1234.12 | 0.00 | 09-FEB-12:00 | 223835.48 | 28-JAN-23:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1497.49 | 0.00 | 18-MAR-17:10 | 295417.00 | 29-JAN-00:10 |
HeatingCoils:EnergyTransfer | 1477.45 | 0.00 | 18-MAR-17:10 | 295417.00 | 29-JAN-00:10 |
CoolingCoils:EnergyTransfer | 20.03 | 0.00 | 01-JAN-00:10 | 47074.53 | 29-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 79.597 | -15.870 | 0.000 | 0.000 | 10.134 | 30.864 | 29.165 | 10.986 | 0.000 | 0.037 | 0.000 | 0.000 | -32.241 | 0.000 | -36.844 | -75.827 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 308.901 | -29.673 | 0.000 | 0.000 | 26.163 | 239.148 | 0.000 | 47.078 | 0.000 | 0.021 | 0.002 | 0.000 | -122.143 | 0.000 | -90.618 | -378.876 |
ZONE3 BULK STORAGE | 1234.122 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 70.783 | 353.598 | 107.344 | 18.183 | 0.000 | 0.177 | 0.000 | 0.000 | -23.154 | 0.000 | -474.216 | -1286.837 |
Total Facility | 1234.122 | 0.000 | 388.498 | -45.544 | 0.000 | 0.000 | 107.080 | 623.610 | 136.508 | 76.247 | 0.000 | 0.234 | 0.002 | 0.000 | -177.538 | 0.000 | -601.678 | -1741.540 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 13-JUL-05:01 | 0.00 | 0.00 | 0.00 | -30583.35 | 0.00 | 0.00 | 77.54 | 583.97 | 550.52 | 25.72 | 0.00 | 0.00 | 29753.59 | 0.00 | -0.00 | 0.00 | -408.00 | 0.00 |
ZONE2 FINE STORAGE | 07-JUN-19:51 | 0.00 | 0.00 | 0.00 | -105784.23 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 10602.31 | 0.00 | 0.00 | 94341.18 | 0.00 | -0.00 | 0.00 | -1259.04 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-JUN-19:51 | 0.00 | 0.00 | 0.00 | -105784.23 | 0.00 | 0.00 | 0.00 | 5661.51 | 2519.91 | 13144.60 | 0.00 | 0.00 | 90482.51 | 0.00 | 0.00 | 0.00 | -6024.29 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 24-FEB-06:31 | 0.00 | 0.00 | 29241.41 | 0.00 | 0.00 | 0.00 | 149.29 | 583.97 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2535.59 | 0.00 | -4004.65 | -23984.95 |
ZONE2 FINE STORAGE | 24-FEB-06:01 | 0.00 | 0.00 | 110580.78 | 0.00 | 0.00 | 0.00 | 393.69 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9595.64 | 0.00 | -15244.02 | -88234.59 |
ZONE3 BULK STORAGE | 28-JAN-23:00 | 224340.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1984.35 | 0.00 | -148667.58 | -78843.25 |
Total Facility | 29-JAN-00:13 | 222860.75 | 0.00 | 110201.47 | 0.00 | 0.00 | 0.00 | 0.00 | 5661.51 | 469.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14316.50 | 0.00 | -195818.84 | -129058.26 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2739 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2739 | 0.1037 | 1.0000 | Not calculated | 0.1023 | 0.0803 | ||
PSZ-FINE STORAGE | 5.0414 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 5.0414 | 0.1246 | 1.0000 | Not calculated | 0.4247 | 0.0842 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.2739 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.2739 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0803 | ||
PSZ-FINE STORAGE | 5.0414 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 5.0414 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.0842 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2739 | 1.2739 | 1.2739 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0414 | 5.0414 | 5.0414 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2739 | 1.2739 | 1.2739 | 1.2739 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 5.0414 | 5.0414 | 5.0414 | 5.0414 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2739 | 1.2739 | 1.2739 | No | 0.1023 | 0.0803 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0414 | 5.0414 | 5.0414 | No | 0.4247 | 0.0842 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.2739 | 1.2739 | 1.2739 | 1.2739 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 5.0414 | 5.0414 | 5.0414 | 5.0414 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 104.50 |
Number of hours cooling loads not met | 1.50 |
Number of hours not met | 106.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 2073.25 | 377468.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 4.88 | 12042.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 133.03 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.02 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 306.76 | 20286.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 13.41 | 1858.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 1218.22 |
Natural Gas | 0.00 | 2073.25 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 3291.47 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 1.01 |
Fans (All) | 63.45 |
Service Water Heating | 2.77 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 251.95 |
Subtotal | 251.95 |
Natural Gas [MJ/m2] | |
Space Heating | 428.79 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 428.79 |
Subtotal | 428.79 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 18.95 |
Space Heating | 62.99 |
Space Cooling | 0.15 |
Fans (All) | 9.32 |
Service Water Heating | 0.41 |
Receptacle Equipment | 4.15 |
Miscellaneous | 4.04 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 8568.00 | 192.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8611.17 | 148.83 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8526.00 | 234.00 | 0.00 | 0.00 | 0.00 |
Min | 8526.00 | 148.83 | 0.00 | 0.00 | 0.00 |
Max | 8611.17 | 234.00 | 0.00 | 0.00 | 0.00 |
Average | 8568.39 | 191.61 | 0.00 | 0.00 | 0.00 |
Sum | 25705.17 | 574.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 80011.00 | 2708.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 180792.50 | 10400.50 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 180792.50 | 10400.50 | 0.00 | 0.00 | 0.00 |
Average | 97943.50 | 4369.50 | 0.00 | 0.00 | 0.00 |
Sum | 293830.50 | 13108.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 8615.00 | 145.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 8557.67 | 202.33 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 8539.83 | 220.17 | 0.00 | 0.00 | 0.00 |
Min | 8539.83 | 145.00 | 0.00 | 0.00 | 0.00 |
Max | 8615.00 | 220.17 | 0.00 | 0.00 | 0.00 |
Average | 8570.83 | 189.17 | 0.00 | 0.00 | 0.00 |
Sum | 25712.50 | 567.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 79321.00 | 3398.00 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 181690.50 | 9502.50 | 0.00 | 0.00 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 181690.50 | 9502.50 | 0.00 | 0.00 | 0.00 |
Average | 98012.83 | 4300.17 | 0.00 | 0.00 | 0.00 |
Sum | 294038.50 | 12900.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:39
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.496378E+09 | 603.25 | 14-JAN-08:09 | -19.5 | -19.6 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.457007E+09 | 603.25 | 01-FEB-08:09 | -18.3 | -18.6 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.2 | 0.536530E+09 | 618.36 | 22-MAR-15:00 | 5.60 | 2.61 |
April | 67407058.27 | 2478.33 | 22-APR-16:00 | 15.00 | 6.60 | 0.522611E+09 | 768.96 | 22-APR-12:09 | 15.00 | 6.60 |
May | 0.136528E+10 | 4823.93 | 31-MAY-16:00 | 22.20 | 10.79 | 0.637182E+09 | 768.97 | 17-MAY-12:09 | 22.20 | 10.79 |
June | 0.459307E+10 | 30398.36 | 17-JUN-05:02 | 7.98 | 6.63 | 0.659685E+09 | 769.01 | 30-JUN-10:30 | 21.10 | 16.40 |
July | 0.517367E+10 | 30585.17 | 13-JUL-05:01 | 11.52 | 8.37 | 0.634673E+09 | 769.02 | 03-JUL-15:20 | 11.52 | 8.37 |
August | 0.411080E+10 | 28963.60 | 11-AUG-05:03 | 11.02 | 6.91 | 0.682758E+09 | 769.01 | 03-AUG-14:00 | 11.02 | 6.91 |
September | 0.559700E+09 | 4241.82 | 02-SEP-16:00 | 16.70 | 10.43 | 0.577126E+09 | 768.96 | 01-SEP-12:09 | 16.70 | 10.43 |
October | 678346.85 | 126.53 | 07-OCT-10:00 | 3.30 | 2.84 | 0.502058E+09 | 700.70 | 03-OCT-15:00 | 3.30 | 2.84 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 | -10.9 | 0.476877E+09 | 603.25 | 18-NOV-08:09 | -11.6 | -12.0 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -25.8 | -26.0 | 0.496554E+09 | 603.25 | 20-DEC-08:09 | -15.8 | -16.1 |
Annual Sum or Average | 0.158706E+11 | 0.667944E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.457007E+09 | 603.25 | -19.5 | -19.6 | ||
Maximum of Months | 0.517367E+10 | 30585.17 | 22.20 | 10.79 | 0.682758E+09 | 769.02 | 22.20 | 16.40 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.648921E+09 | 787.42 | 13-JAN-08:09 | -32.6 | -32.7 |
February | 4735889.64 | 755.45 | 09-FEB-12:00 | -1.7 | -2.1 | 0.597984E+09 | 857.04 | 09-FEB-16:10 | 0.13 | -0.8 |
March | 0.304510E+09 | 5017.22 | 31-MAR-15:00 | -10.0 | -12.3 | 0.722374E+09 | 1211.19 | 22-MAR-15:20 | -10.0 | -12.3 |
April | 0.307430E+09 | 3131.67 | 24-APR-08:15 | -0.9 | -4.5 | 0.925759E+09 | 1998.66 | 22-APR-15:09 | -0.9 | -4.5 |
May | 0.465645E+09 | 8728.81 | 13-MAY-15:00 | 20.00 | 9.32 | 0.160930E+10 | 2246.79 | 15-MAY-15:00 | 15.00 | 7.00 |
June | 0.961638E+10 | 105781.31 | 07-JUN-19:51 | 17.80 | 9.78 | 0.190792E+10 | 2246.87 | 30-JUN-12:09 | 25.78 | 18.15 |
July | 0.121327E+11 | 101988.76 | 30-JUL-19:31 | 17.20 | 11.89 | 0.184335E+10 | 2246.85 | 22-JUL-10:50 | 17.20 | 11.89 |
August | 0.642001E+10 | 97608.77 | 27-AUG-18:31 | 19.80 | 11.87 | 0.192909E+10 | 2246.82 | 02-AUG-14:09 | 19.80 | 11.87 |
September | 0.231668E+09 | 2528.98 | 29-SEP-08:70 | -4.4 | -4.8 | 0.121565E+10 | 2246.79 | 02-SEP-15:50 | -4.4 | -4.8 |
October | 0.190934E+09 | 2439.77 | 11-OCT-10:00 | -5.0 | -5.4 | 0.730432E+09 | 1370.12 | 03-OCT-15:09 | -5.0 | -5.4 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 | -10.9 | 0.623025E+09 | 787.42 | 28-NOV-08:09 | -28.0 | -28.2 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -25.8 | -26.0 | 0.648900E+09 | 787.42 | 11-DEC-08:09 | -19.7 | -20.0 |
Annual Sum or Average | 0.296740E+11 | 0.134027E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.597984E+09 | 787.42 | -32.6 | -32.7 | ||
Maximum of Months | 0.121327E+11 | 105781.31 | 20.00 | 11.89 | 0.192909E+10 | 2246.87 | 25.78 | 18.15 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -14.9 | -15.4 | 0.643902E+09 | 780.35 | 13-JAN-08:09 | -32.6 | -32.7 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -20.2 | -20.7 | 0.592642E+09 | 789.58 | 09-FEB-15:50 | 0.50 | -0.6 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -28.9 | -29.2 | 0.713332E+09 | 1240.82 | 22-MAR-15:30 | 5.60 | 2.42 |
April | 0.00 | 0.00 | 01-APR-00:03 | -11.7 | -13.3 | 0.917516E+09 | 2055.53 | 22-APR-14:00 | 14.40 | 6.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 | 2.18 | 0.211675E+10 | 3658.42 | 13-MAY-15:20 | 20.00 | 9.32 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 | 0.367907E+10 | 5797.39 | 30-JUN-15:09 | 27.38 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 | 13.77 | 0.417842E+10 | 6397.75 | 29-JUL-15:00 | 30.00 | 18.34 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 | 11.83 | 0.374989E+10 | 6212.14 | 04-AUG-15:09 | 22.70 | 14.61 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 | 5.90 | 0.164262E+10 | 3514.67 | 02-SEP-15:30 | 16.70 | 10.62 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 | 0.12 | 0.720703E+09 | 1424.59 | 03-OCT-15:30 | 12.25 | 6.65 |
November | 0.00 | 0.00 | 01-NOV-00:05 | -10.0 | -10.9 | 0.618263E+09 | 780.35 | 01-NOV-07:10 | -12.1 | -12.8 |
December | 0.00 | 0.00 | 01-DEC-00:02 | -25.8 | -26.0 | 0.644024E+09 | 780.35 | 15-DEC-08:09 | -33.8 | -34.0 |
Annual Sum or Average | 0.00 | 0.202171E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -28.9 | -29.2 | 0.592642E+09 | 780.35 | -33.8 | -34.0 | ||
Maximum of Months | 0.00 | 0.00 | 16.35 | 13.77 | 0.417842E+10 | 6397.75 | 30.00 | 18.34 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153108E+11 | 29225.17 | 30-JAN-06:31 | -25.6 |
February | 0.125137E+11 | 29241.30 | 24-FEB-06:31 | -25.6 |
March | 0.115999E+11 | 26536.92 | 03-MAR-07:23 | -24.7 |
April | 0.447482E+10 | 27966.38 | 01-APR-05:31 | -10.2 |
May | 0.539054E+09 | 25720.07 | 03-MAY-05:01 | 4.40 |
June | 67116671.39 | 2345.19 | 12-JUN-06:10 | 10.18 |
July | 45008490.01 | 2430.37 | 26-JUL-06:07 | 11.70 |
August | 0.149245E+09 | 5894.96 | 31-AUG-06:05 | -1.5 |
September | 0.119196E+10 | 25914.08 | 30-SEP-05:12 | -4.6 |
October | 0.678859E+10 | 26415.54 | 30-OCT-05:21 | -14.7 |
November | 0.122522E+11 | 26572.50 | 29-NOV-07:23 | -28.9 |
December | 0.146654E+11 | 26778.09 | 15-DEC-07:35 | -33.7 |
Annual Sum or Average | 0.795978E+11 | |||
Minimum of Months | 45008490.01 | 2345.19 | -33.7 | |
Maximum of Months | 0.153108E+11 | 29241.30 | 11.70 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.624078E+11 | 109967.15 | 30-JAN-06:01 | -25.6 |
February | 0.494213E+11 | 110580.81 | 24-FEB-06:01 | -25.6 |
March | 0.391432E+11 | 100502.23 | 14-MAR-17:42 | -11.9 |
April | 0.136757E+11 | 99015.26 | 01-APR-05:01 | -10.5 |
May | 0.190161E+10 | 8566.54 | 16-MAY-07:00 | 3.30 |
June | 0.422970E+09 | 8005.20 | 01-JUN-06:25 | 8.30 |
July | 0.227442E+09 | 7891.87 | 03-JUL-06:25 | 11.70 |
August | 0.643988E+09 | 7894.74 | 09-AUG-06:25 | 9.70 |
September | 0.266146E+10 | 60650.21 | 30-SEP-04:33 | -4.2 |
October | 0.238538E+11 | 99064.32 | 27-OCT-05:01 | -17.4 |
November | 0.506305E+11 | 101022.86 | 27-NOV-18:04 | -25.6 |
December | 0.639115E+11 | 101247.28 | 15-DEC-18:04 | -29.0 |
Annual Sum or Average | 0.308901E+12 | |||
Minimum of Months | 0.227442E+09 | 7891.87 | -29.0 | |
Maximum of Months | 0.639115E+11 | 110580.81 | 11.70 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255749E+12 | 224341.41 | 28-JAN-23:00 | -24.4 |
February | 0.202634E+12 | 205191.16 | 25-FEB-00:55 | -26.1 |
March | 0.167089E+12 | 168042.48 | 02-MAR-04:53 | -26.7 |
April | 0.592895E+11 | 134775.03 | 02-APR-06:54 | -16.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.191355E+10 | 36728.94 | 30-SEP-05:00 | -4.4 |
October | 0.931904E+11 | 127897.30 | 27-OCT-04:00 | -17.8 |
November | 0.197903E+12 | 146328.27 | 29-NOV-08:00 | -28.9 |
December | 0.256354E+12 | 161553.62 | 28-DEC-03:00 | -26.7 |
Annual Sum or Average | 0.123412E+13 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.256354E+12 | 224341.41 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492525E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390485E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473055E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340944E+10 |
May | 0.144276E+10 | 0.263574E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216358E+10 |
June | 0.144276E+10 | 0.259625E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10691490.93 | 0.134954E+10 |
July | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21806321.78 | 0.103096E+10 |
August | 0.149825E+10 | 0.269003E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4367066.99 | 0.156195E+10 |
September | 0.138726E+10 | 0.254196E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188577E+10 |
October | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354639E+10 |
November | 0.133177E+10 | 0.248766E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374488E+10 |
December | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459077E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36864879.70 | 0.368439E+11 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103096E+10 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21806321.78 | 0.492525E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100684E+11 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833400E+10 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120480E+11 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115166E+11 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.804727E+10 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1191203.12 | 0.547112E+10 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19418918.83 | 0.412714E+10 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540607E+10 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464794E+10 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951016E+10 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376755E+10 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767420E+10 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20610121.96 | 0.906185E+11 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376755E+10 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19418918.83 | 0.120480E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393896E+11 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317136E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435310E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4030466.71 | 0.331377E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44900403.42 | 0.203345E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1456579.99 | 0.181430E+11 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1243169.14 | 0.174235E+11 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14112744.67 | 0.204440E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142582E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21371151.79 | 0.312370E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143210E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312674E+11 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 87114515.72 | 0.315201E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142582E+11 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44900403.42 | 0.435310E+11 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 15643.90 | 12-JAN-07:10 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 15643.55 | 27-FEB-07:05 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 13792.03 | 01-MAR-07:10 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 12291.32 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 5754.29 | 16-MAY-07:00 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 552.69 | 29-JUN-16:10 | 3997.97 | 06-JUN-06:05 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1793.28 | 21-JUL-16:10 | 4033.80 | 17-JUL-06:05 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 497.93 | 11-AUG-16:10 | 6131.98 | 31-AUG-06:10 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 7124.94 | 29-SEP-07:00 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12034.51 | 31-OCT-07:00 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 14425.97 | 29-NOV-08:00 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 14705.08 | 15-DEC-12:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3997.97 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 1793.28 | 15643.90 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 34932.16 | 28-JAN-17:00 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 21109.00 | 23-FEB-17:00 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 16048.17 | 25-MAR-15:10 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 18074.52 | 01-APR-18:52 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 11567.41 | 16-MAY-07:00 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.52 | 30-JUN-15:10 | 9684.66 | 24-JUN-21:00 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2764.03 | 21-JUL-16:00 | 6279.80 | 04-JUL-17:00 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 9526.77 | 29-AUG-20:00 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 6263.07 | 21-SEP-15:10 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 11980.72 | 27-OCT-06:10 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 11731.08 | 03-NOV-19:55 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 13620.67 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6263.07 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2764.03 | 34932.16 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 127555.70 | 28-JAN-15:00 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 79581.10 | 25-FEB-12:00 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 57078.55 | 25-MAR-09:00 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 812.76 | 17-APR-18:00 | 54448.83 | 01-APR-19:00 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3617.53 | 30-MAY-18:00 | 41653.18 | 27-MAY-11:00 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.55 | 03-JUN-18:00 | 32699.19 | 24-JUN-21:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.76 | 29-JUL-16:40 | 21058.77 | 17-JUL-16:00 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1924.06 | 23-AUG-18:00 | 34732.10 | 31-AUG-09:00 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 18797.70 | 21-SEP-14:00 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2319.12 | 01-OCT-17:00 | 40573.10 | 31-OCT-09:00 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 41199.84 | 01-NOV-09:00 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 58773.85 | 22-DEC-14:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18797.70 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 3617.53 | 127555.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 3199.16 | 3289.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1102.55 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2285.11 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 843.90 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 2742.13 | 2819.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.07 |
April | 2478.33 | 22-APR-16:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 866.91 |
May | 4823.93 | 31-MAY-16:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.29 |
June | 30398.36 | 17-JUN-05:02 | 924.51 | 2919.87 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.01 |
July | 30585.17 | 13-JUL-05:01 | 1479.21 | 4671.78 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 408.00 |
August | 28963.60 | 11-AUG-05:03 | 739.61 | 2335.89 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 811.16 |
September | 4241.82 | 02-SEP-16:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.80 |
October | 126.53 | 07-OCT-10:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.67 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 914.04 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925.15 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 2285.11 | 2349.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 914.04 | 939.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30585.17 | 1680.92 | 4671.78 | 4404.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1102.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 14698.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6548.02 |
February | 755.45 | 09-FEB-12:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5017.22 | 31-MAR-15:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2088.53 |
April | 3131.67 | 24-APR-08:15 | 7911.00 | 35696.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3812.43 |
May | 8728.81 | 13-MAY-15:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 719.12 |
June | 105781.31 | 07-JUN-19:51 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1259.04 |
July | 101988.76 | 30-JUL-19:31 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1689.60 |
August | 97608.77 | 27-AUG-18:31 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2125.18 |
September | 2528.98 | 29-SEP-08:70 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.44 |
October | 2439.77 | 11-OCT-10:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 4199.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5550.12 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 4199.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 105781.31 | 7911.00 | 35696.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6548.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 21732.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21463.35 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 15523.47 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16870.79 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 18628.16 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8411.51 |
April | 0.00 | 01-APR-00:03 | 0.00 | 9314.08 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29194.10 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4852.38 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4058.75 |
July | 0.00 | 01-JUL-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5172.79 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9415.58 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5112.85 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9138.88 |
November | 0.00 | 01-NOV-00:05 | 0.00 | 6209.39 | 4100.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17154.21 |
December | 0.00 | 01-DEC-00:02 | 0.00 | 15523.47 | 10250.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 21732.86 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29194.10 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.124056E+12 | 86740.93 | 09-JAN-15:39 | 0.416318E+12 | 377468.30 | 29-JAN-00:10 |
February | 0.109795E+12 | 86110.85 | 06-FEB-09:20 | 0.326548E+12 | 346629.84 | 24-FEB-06:10 |
March | 0.118934E+12 | 80684.67 | 18-MAR-07:10 | 0.265703E+12 | 273334.53 | 02-MAR-04:49 |
April | 0.954917E+11 | 78203.95 | 01-APR-14:30 | 0.957060E+11 | 222215.97 | 03-APR-05:19 |
May | 0.823200E+11 | 68882.33 | 31-MAY-14:00 | 0.143643E+11 | 18710.19 | 03-MAY-05:10 |
June | 0.809625E+11 | 78999.10 | 30-JUN-14:50 | 0.136080E+11 | 5250.00 | 01-JUN-00:10 |
July | 0.817386E+11 | 81385.16 | 29-JUL-14:00 | 0.140616E+11 | 5250.00 | 01-JUL-00:10 |
August | 0.872906E+11 | 76444.80 | 11-AUG-14:00 | 0.140859E+11 | 10110.72 | 31-AUG-06:10 |
September | 0.852750E+11 | 77435.40 | 30-SEP-08:09 | 0.176756E+11 | 73236.22 | 30-SEP-05:19 |
October | 0.109281E+12 | 86034.01 | 31-OCT-08:39 | 0.149735E+12 | 223678.24 | 31-OCT-05:19 |
November | 0.117791E+12 | 86657.30 | 30-NOV-15:09 | 0.325186E+12 | 251372.06 | 29-NOV-07:00 |
December | 0.125287E+12 | 86739.41 | 28-DEC-15:50 | 0.420258E+12 | 275603.11 | 15-DEC-12:09 |
Annual Sum or Average | 0.121822E+13 | 0.207325E+13 | ||||
Minimum of Months | 0.809625E+11 | 68882.33 | 0.136080E+11 | 5250.00 | ||
Maximum of Months | 0.125287E+12 | 86740.93 | 0.420258E+12 | 377468.30 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.183579E+11 | 0.112984E+11 | 0.00 | 0.413529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116101E+10 | 0.00 |
February | 0.474804E+11 | 0.137352E+11 | 0.103734E+11 | 0.00 | 0.371413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106520E+10 | 0.00 |
March | 0.548234E+11 | 0.119844E+11 | 0.121089E+11 | 0.00 | 0.387775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123958E+10 | 0.00 |
April | 0.513965E+11 | 0.843666E+10 | 0.112578E+11 | 0.00 | 0.232482E+11 | 0.00 | 0.00 | 103.90 | 0.00 | 0.00 | 0.00 | 0.115261E+10 | 0.00 |
May | 0.533545E+11 | 0.551352E+10 | 0.117000E+11 | 0.00 | 0.105467E+11 | 0.00 | 0.00 | 22260114.98 | 0.00 | 0.00 | 0.00 | 0.118303E+10 | 0.00 |
June | 0.528654E+11 | 0.307160E+10 | 0.116594E+11 | 0.00 | 0.108221E+11 | 0.00 | 0.00 | 0.141235E+10 | 0.00 | 0.00 | 0.00 | 0.113171E+10 | 0.00 |
July | 0.518856E+11 | 0.426952E+10 | 0.112984E+11 | 0.00 | 0.105975E+11 | 0.00 | 0.00 | 0.262794E+10 | 0.00 | 0.00 | 0.00 | 0.105968E+10 | 0.00 |
August | 0.548234E+11 | 0.736672E+10 | 0.121016E+11 | 0.00 | 0.110694E+11 | 0.00 | 0.00 | 0.820840E+09 | 0.00 | 0.00 | 0.00 | 0.110876E+10 | 0.00 |
September | 0.513965E+11 | 0.102438E+11 | 0.112504E+11 | 0.00 | 0.113473E+11 | 0.00 | 0.00 | 653.39 | 0.00 | 0.00 | 0.00 | 0.103704E+10 | 0.00 |
October | 0.518856E+11 | 0.138171E+11 | 0.113057E+11 | 0.00 | 0.312056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106740E+10 | 0.00 |
November | 0.499276E+11 | 0.165713E+11 | 0.108562E+11 | 0.00 | 0.393763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105970E+10 | 0.00 |
December | 0.518856E+11 | 0.196582E+11 | 0.112984E+11 | 0.00 | 0.413011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114366E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.133026E+12 | 0.136508E+12 | 0.00 | 0.306786E+12 | 0.00 | 0.00 | 0.488338E+10 | 0.00 | 0.00 | 0.00 | 0.134094E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.307160E+10 | 0.103734E+11 | 0.00 | 0.105467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103704E+10 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.196582E+11 | 0.121089E+11 | 0.00 | 0.413529E+11 | 0.00 | 0.00 | 0.262794E+10 | 0.00 | 0.00 | 0.00 | 0.123958E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.416318E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.326548E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.265703E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.957060E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.143643E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.136080E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.140616E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.140859E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.176756E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.149735E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.325186E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.420258E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207325E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.136080E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.420258E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 20286.91 | 02-JAN-07:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 20286.91 | 01-FEB-07:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 20286.91 | 01-MAR-07:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10035.17 | 01-APR-07:10 | 0.00 | 20286.91 | 01-APR-06:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 10233.11 | 01-MAY-06:19 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 10233.11 | 06-JUN-11:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 12538.40 | 29-JUL-15:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 10233.11 | 02-AUG-06:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 20286.91 | 28-SEP-06:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 20286.91 | 03-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 20286.91 | 01-NOV-06:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 20286.91 | 01-DEC-07:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10035.17 | 0.00 | 10233.11 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10035.17 | 0.00 | 20286.91 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 1858.18 | 12-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 1857.72 | 27-FEB-12:39 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 1857.65 | 15-MAR-11:00 | 0.00 |
April | 0.03 | 22-APR-11:39 | 0.00 | 0.00 | 0.00 | 1857.65 | 10-APR-11:50 | 0.00 |
May | 1214.63 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 | 1857.37 | 03-MAY-11:39 | 0.00 |
June | 10976.97 | 30-JUN-14:00 | 0.00 | 0.00 | 0.00 | 1837.30 | 01-JUN-11:50 | 0.00 |
July | 12042.65 | 29-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1738.82 | 01-JUL-11:00 | 0.00 |
August | 10113.67 | 01-AUG-19:00 | 0.00 | 0.00 | 0.00 | 1714.48 | 01-AUG-11:50 | 0.00 |
September | 0.19 | 02-SEP-15:39 | 0.00 | 0.00 | 0.00 | 1711.46 | 30-SEP-11:50 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 1729.87 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 1829.60 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1857.65 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1711.46 | 0.00 | ||
Maximum of Months | 12042.65 | 0.00 | 0.00 | 0.00 | 1858.18 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 86740.93 | 09-JAN-15:39 | 46193.18 | 10035.17 | 8532.22 | 0.00 | 20286.91 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 86110.85 | 06-FEB-09:20 | 46193.18 | 10035.17 | 8532.22 | 0.00 | 20286.91 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80684.67 | 18-MAR-07:10 | 40988.70 | 10035.17 | 8532.22 | 0.00 | 20286.91 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78203.95 | 01-APR-14:30 | 46193.18 | 10035.17 | 0.00 | 0.00 | 20286.91 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 68882.33 | 31-MAY-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 10233.11 | 0.00 | 0.00 | 804.65 | 0.00 |
June | 78999.10 | 30-JUN-14:50 | 46193.18 | 10035.17 | 0.00 | 0.00 | 10233.11 | 0.00 | 0.00 | 10965.97 | 0.00 |
July | 81385.16 | 29-JUL-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 12538.40 | 0.00 | 0.00 | 11108.76 | 0.00 |
August | 76444.80 | 11-AUG-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 10233.11 | 0.00 | 0.00 | 8478.22 | 0.00 |
September | 77435.40 | 30-SEP-08:09 | 46193.18 | 10035.17 | 0.00 | 0.00 | 20286.91 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86034.01 | 31-OCT-08:39 | 46193.18 | 10035.17 | 8532.22 | 0.00 | 20286.91 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86657.30 | 30-NOV-15:09 | 46193.18 | 10035.17 | 8532.22 | 0.00 | 20286.91 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 86739.41 | 28-DEC-15:50 | 46193.18 | 10035.17 | 8532.22 | 0.00 | 20286.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 68882.33 | 40988.70 | 10035.17 | 0.00 | 0.00 | 10233.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86740.93 | 46193.18 | 10035.17 | 8532.22 | 0.00 | 20286.91 | 0.00 | 0.00 | 11108.76 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 377468.30 | 29-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 346629.84 | 24-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 273334.53 | 02-MAR-04:49 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 222215.97 | 03-APR-05:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 18710.19 | 03-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5250.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 5250.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 10110.72 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 73236.22 | 30-SEP-05:19 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 223678.24 | 31-OCT-05:19 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 251372.06 | 29-NOV-07:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 275603.11 | 15-DEC-12:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 5250.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 377468.30 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 86.83 | 15.52 | 15.67 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 |
February | 71.50 | 15.37 | 11.17 | 15.84 | 0.00 | 15.84 | 0.00 | 15.84 |
March | 54.33 | 15.76 | 12.83 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 |
April | 18.50 | 16.86 | 8.67 | 17.58 | 0.00 | 17.58 | 0.00 | 17.58 |
May | 1.33 | 20.38 | 1.33 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.55 | 0.50 | 24.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.53 | 0.83 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.52 | 0.17 | 24.52 |
September | 2.33 | 19.93 | 2.33 | 19.93 | 0.00 | 19.93 | 0.00 | 19.93 |
October | 22.50 | 16.62 | 9.17 | 17.32 | 0.00 | 17.32 | 0.00 | 17.32 |
November | 51.00 | 15.86 | 12.00 | 16.44 | 0.00 | 16.44 | 0.00 | 16.44 |
December | 85.50 | 15.47 | 13.67 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
Annual Sum or Average | 393.83 | 15.73 | 86.83 | 16.31 | 1.50 | 16.34 | 1.50 | 16.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 0.00 | 15.84 |
Maximum of Months | 86.83 | 20.38 | 15.67 | 20.38 | 0.83 | 24.55 | 0.83 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 116.00 | 13.59 | 4.33 | 13.59 | 0.00 | 13.59 | 0.00 | 13.59 |
February | 103.33 | 13.70 | 4.33 | 13.70 | 0.00 | 13.70 | 0.00 | 13.70 |
March | 104.33 | 14.02 | 5.33 | 14.01 | 0.00 | 14.01 | 0.00 | 14.01 |
April | 45.17 | 14.38 | 3.17 | 14.38 | 0.00 | 14.38 | 0.00 | 14.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.40 | 0.00 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.41 | 0.00 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.31 | 0.00 | 27.31 |
September | 5.67 | 14.88 | 1.00 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
October | 85.17 | 14.39 | 3.67 | 14.38 | 0.00 | 14.38 | 0.00 | 14.38 |
November | 112.17 | 13.83 | 4.17 | 13.83 | 0.00 | 13.83 | 0.00 | 13.83 |
December | 115.17 | 13.62 | 4.17 | 13.62 | 0.00 | 13.62 | 0.00 | 13.62 |
Annual Sum or Average | 687.00 | 13.88 | 30.17 | 13.88 | 12.83 | 14.12 | 0.00 | 14.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 116.00 | 14.88 | 5.33 | 14.87 | 7.17 | 27.41 | 0.00 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 8.93 | 0.00 | 8.93 | 0.00 | 8.93 | 0.00 | 8.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.00 | 8.93 | 0.00 | 8.93 | 0.00 | 8.93 | 0.00 | 8.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 8.93 | 0.00 | 8.93 | 0.00 | 8.93 | 0.00 | 8.93 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.98 | 300.00 | 20.98 | 300.00 | 20.98 |
February | 276.00 | 21.00 | 276.00 | 21.00 | 276.00 | 21.00 |
March | 324.00 | 21.00 | 324.00 | 21.00 | 324.00 | 21.00 |
April | 300.00 | 21.51 | 247.50 | 21.34 | 247.50 | 21.27 |
May | 310.83 | 23.21 | 40.50 | 22.98 | 40.50 | 22.80 |
June | 60.67 | 23.73 | 97.17 | 23.84 | 0.00 | 23.84 |
July | 15.67 | 23.59 | 218.50 | 23.88 | 0.00 | 23.88 |
August | 90.17 | 23.57 | 103.33 | 23.72 | 2.17 | 23.69 |
September | 298.00 | 22.53 | 109.00 | 22.15 | 109.00 | 21.93 |
October | 300.00 | 21.12 | 287.17 | 21.09 | 287.17 | 21.08 |
November | 288.00 | 21.00 | 288.00 | 21.00 | 288.00 | 21.00 |
December | 300.00 | 20.98 | 300.00 | 20.98 | 300.00 | 20.98 |
Annual Sum or Average | 2863.33 | 21.61 | 2591.17 | 21.56 | 2174.33 | 21.40 |
Minimum of Months | 15.67 | 20.98 | 40.50 | 20.98 | 0.00 | 20.98 |
Maximum of Months | 324.00 | 23.73 | 324.00 | 23.88 | 324.00 | 23.88 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.53 | 300.00 | 15.53 | 300.00 | 15.53 |
February | 276.00 | 15.54 | 276.00 | 15.54 | 276.00 | 15.54 |
March | 324.00 | 15.74 | 324.00 | 15.74 | 324.00 | 15.74 |
April | 300.00 | 18.27 | 260.00 | 17.93 | 260.00 | 17.80 |
May | 189.83 | 22.26 | 141.00 | 22.92 | 55.83 | 22.46 |
June | 56.83 | 25.79 | 279.17 | 26.47 | 40.33 | 26.50 |
July | 113.17 | 26.53 | 287.83 | 26.57 | 106.83 | 26.60 |
August | 85.50 | 24.67 | 257.67 | 25.99 | 42.17 | 25.99 |
September | 281.00 | 20.72 | 163.00 | 20.12 | 154.33 | 19.75 |
October | 300.00 | 16.36 | 300.00 | 16.36 | 300.00 | 16.36 |
November | 288.00 | 15.53 | 288.00 | 15.53 | 288.00 | 15.53 |
December | 300.00 | 15.53 | 300.00 | 15.53 | 300.00 | 15.53 |
Annual Sum or Average | 2814.33 | 17.83 | 3176.67 | 18.56 | 2447.50 | 18.11 |
Minimum of Months | 56.83 | 15.53 | 141.00 | 15.53 | 40.33 | 15.53 |
Maximum of Months | 324.00 | 26.53 | 324.00 | 26.57 | 324.00 | 26.60 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
February | 276.00 | 10.00 | 276.00 | 10.00 | 276.00 | 10.00 |
March | 324.00 | 10.11 | 324.00 | 10.11 | 324.00 | 10.11 |
April | 300.00 | 11.75 | 300.00 | 11.75 | 300.00 | 11.75 |
May | 312.00 | 17.80 | 302.00 | 17.73 | 302.00 | 17.71 |
June | 177.17 | 22.60 | 142.83 | 23.47 | 48.33 | 23.25 |
July | 127.00 | 26.47 | 234.17 | 26.72 | 85.83 | 27.01 |
August | 216.50 | 22.71 | 143.50 | 23.49 | 65.33 | 23.44 |
September | 300.00 | 15.90 | 291.83 | 15.83 | 291.83 | 15.80 |
October | 300.00 | 10.52 | 300.00 | 10.52 | 300.00 | 10.52 |
November | 288.00 | 10.00 | 288.00 | 10.00 | 288.00 | 10.00 |
December | 300.00 | 10.00 | 300.00 | 10.00 | 300.00 | 10.00 |
Annual Sum or Average | 3220.67 | 13.72 | 3202.33 | 13.87 | 2881.33 | 13.50 |
Minimum of Months | 127.00 | 10.00 | 142.83 | 10.00 | 48.33 | 10.00 |
Maximum of Months | 324.00 | 26.47 | 324.00 | 26.72 | 324.00 | 27.01 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 394.13 | 103.90 | 2.17 | 394.13 | 0.00 | 0.00 | 0.00 | 22-APR-11:40 | 0.00 | 01-APR-00:03 | 0.10 | 22-APR-11:40 | 0.10 | 22-APR-11:40 | 0.00 | 22-APR-11:50 | 0.03 | 22-APR-11:40 | 0.00 | 01-APR-00:03 |
May | 87762320.64 | 22257646.26 | 27.67 | 87762320.64 | -0.0 | 0.00 | 0.51 | 31-MAY-16:00 | 0.00 | 01-MAY-00:10 | 4990.83 | 31-MAY-16:00 | 4990.83 | 31-MAY-16:00 | 0.00 | 31-MAY-16:20 | 1214.63 | 31-MAY-16:00 | 0.00 | 01-MAY-00:10 |
June | 0.202607E+10 | 0.488164E+09 | 134.75 | 0.194593E+10 | 80146499.65 | 0.00 | 1.00 | 08-JUN-05:03 | 0.00 | 01-JUN-00:10 | 20157.28 | 30-JUN-05:01 | 17494.31 | 14-JUN-05:02 | 7679.19 | 28-JUN-05:03 | 4777.25 | 30-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.360328E+10 | 0.862494E+09 | 181.19 | 0.332327E+10 | 0.280013E+09 | 0.00 | 1.00 | 01-JUL-05:02 | 0.00 | 01-JUL-00:10 | 20590.71 | 25-JUL-05:02 | 17251.38 | 12-JUL-05:01 | 8967.30 | 26-JUL-05:03 | 4877.95 | 25-JUL-05:02 | 0.00 | 01-JUL-00:10 |
August | 0.159758E+10 | 0.385210E+09 | 101.40 | 0.147814E+10 | 0.119438E+09 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 20061.91 | 03-AUG-05:01 | 17843.33 | 11-AUG-05:03 | 8102.64 | 04-AUG-05:02 | 4754.61 | 03-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 663.12 | 174.95 | 1.50 | 663.12 | 0.00 | 0.00 | 0.00 | 02-SEP-07:10 | 0.00 | 01-SEP-00:10 | 0.19 | 02-SEP-07:10 | 0.19 | 02-SEP-07:10 | 0.00 | 01-SEP-16:20 | 0.05 | 02-SEP-07:10 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.731470E+10 | 0.175813E+10 | 448.67 | 0.683510E+10 | 0.479597E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.360328E+10 | 0.862494E+09 | 181.19 | 0.332327E+10 | 0.280013E+09 | 0.00 | 1.00 | 0.00 | 20590.71 | 17843.33 | 8967.30 | 4877.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 | 0.00 | 01-APR-00:03 |
May | 9362.32 | 2468.72 | 9.83 | 9362.32 | -0.0 | 0.00 | 0.00 | 17-MAY-17:00 | 0.00 | 01-MAY-00:10 | 1.17 | 17-MAY-17:00 | 1.17 | 17-MAY-17:00 | 0.00 | 31-MAY-12:40 | 0.31 | 17-MAY-17:00 | 0.00 | 01-MAY-00:10 |
June | 0.377467E+10 | 0.924182E+09 | 62.80 | 0.370633E+10 | 68340124.08 | 0.00 | 1.00 | 07-JUN-17:10 | 0.00 | 01-JUN-00:10 | 90019.38 | 30-JUN-18:00 | 86249.95 | 28-JUN-19:40 | 34317.38 | 30-JUN-17:51 | 21086.15 | 30-JUN-18:00 | 0.00 | 01-JUN-00:10 |
July | 0.717575E+10 | 0.176544E+10 | 115.74 | 0.706124E+10 | 0.114513E+09 | 0.00 | 1.00 | 06-JUL-20:05 | 0.00 | 01-JUL-00:10 | 91078.83 | 08-JUL-17:27 | 86329.73 | 14-JUL-17:50 | 29454.58 | 08-JUL-17:11 | 21285.13 | 08-JUL-17:27 | 0.00 | 01-JUL-00:10 |
August | 0.176623E+10 | 0.435631E+09 | 46.96 | 0.174834E+10 | 17893920.83 | 0.00 | 1.00 | 01-AUG-17:11 | 0.00 | 01-AUG-00:10 | 88365.46 | 03-AUG-17:17 | 86001.13 | 04-AUG-18:40 | 13867.47 | 01-AUG-20:51 | 20765.89 | 03-AUG-17:17 | 0.00 | 01-AUG-00:10 |
September | 1814.90 | 478.44 | 1.17 | 1814.90 | -0.0 | 0.00 | 0.00 | 02-SEP-15:40 | 0.00 | 01-SEP-00:10 | 0.73 | 02-SEP-15:40 | 0.73 | 02-SEP-15:40 | 0.00 | 02-SEP-15:20 | 0.19 | 02-SEP-15:40 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.127167E+11 | 0.312526E+10 | 236.50 | 0.125159E+11 | 0.200747E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.717575E+10 | 0.176544E+10 | 115.74 | 0.706124E+10 | 0.114513E+09 | 0.00 | 1.00 | 0.00 | 91078.83 | 86329.73 | 34317.38 | 21285.13 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 8.32 | 1.45 | 6.87 | 0.00 | 668.95 | 0.00 | 0.00 | 0.00 |
February | 49.52 | 17.35 | 32.17 | 4.58 | 575.45 | 0.00 | 0.00 | 0.00 |
March | 148.84 | 64.46 | 84.39 | 70.65 | 419.18 | 0.00 | 0.00 | 0.00 |
April | 351.14 | 182.04 | 169.10 | 324.11 | 225.44 | 0.00 | 0.00 | 0.00 |
May | 341.01 | 155.35 | 185.65 | 328.87 | 124.43 | 0.00 | 0.00 | 0.00 |
June | 373.90 | 159.59 | 214.31 | 385.37 | 85.12 | 0.00 | 0.00 | 0.00 |
July | 312.47 | 118.12 | 194.36 | 322.39 | 94.50 | 0.00 | 0.00 | 0.00 |
August | 257.60 | 109.46 | 148.13 | 245.03 | 133.49 | 0.00 | 0.00 | 0.00 |
September | 155.23 | 64.79 | 90.43 | 110.58 | 203.36 | 0.00 | 0.00 | 0.00 |
October | 60.79 | 18.20 | 42.59 | 17.48 | 357.69 | 0.00 | 0.00 | 0.00 |
November | 24.37 | 8.83 | 15.54 | 0.89 | 642.15 | 0.00 | 0.00 | 0.00 |
December | 2.19 | 0.24 | 1.96 | 0.00 | 710.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 174.23 | 75.15 | 99.08 | 151.44 | 352.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2.19 | 0.24 | 1.96 | 0.00 | 85.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 373.90 | 182.04 | 214.31 | 385.37 | 710.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.23 | 1.61 | 7.62 | 0.00 | 741.93 | 0.00 | 0.00 | 0.00 |
February | 54.92 | 19.24 | 35.68 | 5.08 | 638.23 | 0.00 | 0.00 | 0.00 |
March | 165.08 | 71.49 | 93.59 | 78.36 | 464.91 | 0.00 | 0.00 | 0.00 |
April | 389.44 | 201.90 | 187.55 | 359.47 | 250.04 | 0.00 | 0.00 | 0.00 |
May | 378.21 | 172.30 | 205.91 | 364.75 | 138.00 | 0.00 | 0.00 | 0.00 |
June | 414.70 | 177.00 | 237.69 | 427.41 | 94.41 | 0.00 | 0.00 | 0.00 |
July | 346.56 | 131.00 | 215.56 | 357.57 | 104.81 | 0.00 | 0.00 | 0.00 |
August | 285.70 | 121.41 | 164.30 | 271.77 | 148.05 | 0.00 | 0.00 | 0.00 |
September | 172.16 | 71.86 | 100.30 | 122.65 | 225.55 | 0.00 | 0.00 | 0.00 |
October | 67.42 | 20.19 | 47.23 | 19.38 | 396.71 | 0.00 | 0.00 | 0.00 |
November | 27.03 | 9.79 | 17.24 | 0.99 | 712.20 | 0.00 | 0.00 | 0.00 |
December | 2.43 | 0.26 | 2.17 | 0.00 | 788.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 193.24 | 83.35 | 109.89 | 167.96 | 390.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2.43 | 0.26 | 2.17 | 0.00 | 94.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 414.70 | 201.90 | 237.69 | 427.41 | 788.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.00 | 2.44 | 0.00 | 274.62 | 0.00 | 0.00 | 0.00 |
February | 10.80 | 0.00 | 10.80 | 0.00 | 248.25 | 0.00 | 0.00 | 0.00 |
March | 28.96 | 0.01 | 28.95 | 0.82 | 188.93 | 0.00 | 0.00 | 0.00 |
April | 52.68 | 1.47 | 51.21 | 13.75 | 98.87 | 0.00 | 0.00 | 0.00 |
May | 80.76 | 13.04 | 67.71 | 48.40 | 44.09 | 0.00 | 0.00 | 0.00 |
June | 104.12 | 22.85 | 81.27 | 82.87 | 24.96 | 0.00 | 0.00 | 0.00 |
July | 87.87 | 14.46 | 73.41 | 71.56 | 31.87 | 0.00 | 0.00 | 0.00 |
August | 56.45 | 3.05 | 53.40 | 31.00 | 51.86 | 0.00 | 0.00 | 0.00 |
September | 31.40 | 0.09 | 31.31 | 5.48 | 88.38 | 0.00 | 0.00 | 0.00 |
October | 15.20 | 0.00 | 15.20 | 0.47 | 153.95 | 0.00 | 0.00 | 0.00 |
November | 4.72 | 0.00 | 4.72 | 0.00 | 269.55 | 0.00 | 0.00 | 0.00 |
December | 0.74 | 0.00 | 0.74 | 0.00 | 289.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.82 | 4.60 | 35.22 | 21.32 | 146.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.74 | 0.00 | 0.74 | 0.00 | 24.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.12 | 22.85 | 81.27 | 82.87 | 289.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.44 | 0.00 | 2.44 | 0.00 | 274.62 | 0.00 | 0.00 | 0.00 |
February | 10.80 | 0.00 | 10.80 | 0.00 | 248.25 | 0.00 | 0.00 | 0.00 |
March | 28.96 | 0.01 | 28.95 | 0.82 | 188.93 | 0.00 | 0.00 | 0.00 |
April | 52.68 | 1.47 | 51.21 | 13.75 | 98.87 | 0.00 | 0.00 | 0.00 |
May | 80.76 | 13.04 | 67.71 | 48.40 | 44.09 | 0.00 | 0.00 | 0.00 |
June | 104.12 | 22.85 | 81.27 | 82.87 | 24.96 | 0.00 | 0.00 | 0.00 |
July | 87.87 | 14.46 | 73.41 | 71.56 | 31.87 | 0.00 | 0.00 | 0.00 |
August | 56.45 | 3.05 | 53.40 | 31.00 | 51.86 | 0.00 | 0.00 | 0.00 |
September | 31.40 | 0.09 | 31.31 | 5.48 | 88.38 | 0.00 | 0.00 | 0.00 |
October | 15.20 | 0.00 | 15.20 | 0.47 | 153.95 | 0.00 | 0.00 | 0.00 |
November | 4.72 | 0.00 | 4.72 | 0.00 | 269.55 | 0.00 | 0.00 | 0.00 |
December | 0.74 | 0.00 | 0.74 | 0.00 | 289.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 39.82 | 4.60 | 35.22 | 21.32 | 146.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.74 | 0.00 | 0.74 | 0.00 | 24.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 104.12 | 22.85 | 81.27 | 82.87 | 289.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINE STORAGE OFFICE FRONT WALL WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 76.87 | 13.39 | 63.48 | 0.00 | 5496.47 | 0.00 | 0.00 | 0.00 |
February | 457.39 | 160.24 | 297.15 | 62.95 | 4700.12 | 0.00 | 0.00 | 0.00 |
March | 1374.82 | 595.37 | 779.45 | 723.83 | 3385.67 | 0.00 | 0.00 | 0.00 |
April | 3243.29 | 1681.38 | 1561.91 | 3068.60 | 1825.19 | 0.00 | 0.00 | 0.00 |
May | 3149.74 | 1434.92 | 1714.81 | 2990.26 | 1065.72 | 0.00 | 0.00 | 0.00 |
June | 3453.60 | 1474.08 | 1979.52 | 3412.19 | 766.96 | 0.00 | 0.00 | 0.00 |
July | 2886.18 | 1091.00 | 1795.18 | 2843.98 | 851.35 | 0.00 | 0.00 | 0.00 |
August | 2379.33 | 1011.07 | 1368.26 | 2171.26 | 1175.25 | 0.00 | 0.00 | 0.00 |
September | 1433.75 | 598.48 | 835.27 | 1052.30 | 1619.14 | 0.00 | 0.00 | 0.00 |
October | 561.48 | 168.14 | 393.34 | 194.79 | 2821.23 | 0.00 | 0.00 | 0.00 |
November | 225.08 | 81.53 | 143.54 | 13.09 | 5242.30 | 0.00 | 0.00 | 0.00 |
December | 20.25 | 2.17 | 18.08 | 0.00 | 5845.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1609.28 | 694.11 | 915.17 | 1383.00 | 2890.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.25 | 2.17 | 18.08 | 0.00 | 766.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3453.60 | 1681.38 | 1979.52 | 3412.19 | 5845.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINE STORAGE OFFICE LEFT WALL WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.49 | 0.00 | 19.49 | 0.00 | 1952.66 | 0.00 | 0.00 | 0.00 |
February | 86.15 | 0.00 | 86.15 | 0.00 | 1755.46 | 0.00 | 0.00 | 0.00 |
March | 231.09 | 0.08 | 231.01 | 12.35 | 1309.69 | 0.00 | 0.00 | 0.00 |
April | 420.41 | 11.75 | 408.66 | 130.74 | 679.39 | 0.00 | 0.00 | 0.00 |
May | 644.44 | 104.09 | 540.36 | 382.33 | 328.63 | 0.00 | 0.00 | 0.00 |
June | 830.85 | 182.34 | 648.51 | 618.34 | 195.52 | 0.00 | 0.00 | 0.00 |
July | 701.20 | 115.38 | 585.82 | 529.39 | 248.12 | 0.00 | 0.00 | 0.00 |
August | 450.49 | 24.36 | 426.13 | 222.13 | 394.85 | 0.00 | 0.00 | 0.00 |
September | 250.59 | 0.72 | 249.87 | 51.13 | 605.19 | 0.00 | 0.00 | 0.00 |
October | 121.27 | 0.00 | 121.27 | 7.49 | 1044.81 | 0.00 | 0.00 | 0.00 |
November | 37.64 | 0.00 | 37.64 | 0.00 | 1905.56 | 0.00 | 0.00 | 0.00 |
December | 5.91 | 0.00 | 5.91 | 0.00 | 2061.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 317.77 | 36.73 | 281.05 | 163.76 | 1036.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.91 | 0.00 | 5.91 | 0.00 | 195.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 830.85 | 182.34 | 648.51 | 618.34 | 2061.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 144.84 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.18 | 120.88 | 0.00 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 31.97 | 80.30 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 98.72 | 42.55 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 137.15 | 24.51 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 145.47 | 18.68 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 127.68 | 23.79 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 92.28 | 31.30 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 44.46 | 38.25 | 0.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 10.30 | 62.90 | 10.17 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 141.11 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 154.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 57.66 | 73.42 | 10.17 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 18.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 145.47 | 154.82 | 10.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 144.84 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.18 | 120.88 | 0.00 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 31.97 | 80.30 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 98.72 | 42.55 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 137.15 | 24.51 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 145.47 | 18.68 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 127.68 | 23.79 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 92.28 | 31.30 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 44.46 | 38.25 | 0.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 10.30 | 62.90 | 10.17 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 141.11 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 154.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 57.66 | 73.42 | 10.17 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 18.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 145.47 | 154.82 | 10.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 144.84 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.18 | 120.88 | 0.00 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 31.97 | 80.30 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 98.72 | 42.55 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 137.15 | 24.51 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 145.47 | 18.68 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 127.68 | 23.79 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 92.28 | 31.30 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 44.46 | 38.25 | 0.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 10.30 | 62.90 | 10.17 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 141.11 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 154.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 57.66 | 73.42 | 10.17 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 18.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 145.47 | 154.82 | 10.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 144.84 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.18 | 120.88 | 0.00 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 31.97 | 80.30 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 98.72 | 42.55 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 137.15 | 24.51 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 145.47 | 18.68 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 127.68 | 23.79 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 92.28 | 31.30 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 44.46 | 38.25 | 0.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 10.30 | 62.90 | 10.17 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 141.11 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 154.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 57.66 | 73.42 | 10.17 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 18.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 145.47 | 154.82 | 10.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 144.84 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.18 | 120.88 | 0.00 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 31.97 | 80.30 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 98.72 | 42.55 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 137.15 | 24.51 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 145.47 | 18.68 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 127.68 | 23.79 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 92.28 | 31.30 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 44.46 | 38.25 | 0.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 10.30 | 62.90 | 10.17 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 141.11 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 154.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 57.66 | 73.42 | 10.17 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 18.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 145.47 | 154.82 | 10.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 144.84 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.18 | 120.88 | 0.00 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 31.97 | 80.30 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 98.72 | 42.55 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 137.15 | 24.51 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 145.47 | 18.68 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 127.68 | 23.79 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 92.28 | 31.30 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 44.46 | 38.25 | 0.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 10.30 | 62.90 | 10.17 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 141.11 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 154.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 57.66 | 73.42 | 10.17 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 18.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 145.47 | 154.82 | 10.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 144.84 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.18 | 120.88 | 0.00 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 31.97 | 80.30 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 98.72 | 42.55 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 137.15 | 24.51 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 145.47 | 18.68 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 127.68 | 23.79 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 92.28 | 31.30 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 44.46 | 38.25 | 0.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 10.30 | 62.90 | 10.17 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 141.11 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 154.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 57.66 | 73.42 | 10.17 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 18.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 145.47 | 154.82 | 10.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 144.84 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.18 | 120.88 | 0.00 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 31.97 | 80.30 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 98.72 | 42.55 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 137.15 | 24.51 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 145.47 | 18.68 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 127.68 | 23.79 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 92.28 | 31.30 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 44.46 | 38.25 | 0.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 10.30 | 62.90 | 10.17 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 141.11 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 154.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 57.66 | 73.42 | 10.17 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 18.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 145.47 | 154.82 | 10.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 144.84 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.18 | 120.88 | 0.00 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 31.97 | 80.30 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 98.72 | 42.55 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 137.15 | 24.51 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 145.47 | 18.68 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 127.68 | 23.79 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 92.28 | 31.30 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 44.46 | 38.25 | 0.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 10.30 | 62.90 | 10.17 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 141.11 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 154.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 57.66 | 73.42 | 10.17 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 18.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 145.47 | 154.82 | 10.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.37 | 0.23 | 2.14 | 0.00 | 144.84 | 0.00 | 0.00 | 0.00 |
February | 12.07 | 3.07 | 9.00 | 0.18 | 120.88 | 0.00 | 0.00 | 0.00 |
March | 42.17 | 18.13 | 24.04 | 31.97 | 80.30 | 0.00 | 0.00 | 0.00 |
April | 84.36 | 45.62 | 38.74 | 98.72 | 42.55 | 0.00 | 0.00 | 0.00 |
May | 109.71 | 62.40 | 47.30 | 137.15 | 24.51 | 0.00 | 0.00 | 0.00 |
June | 118.93 | 59.23 | 59.70 | 145.47 | 18.68 | 0.00 | 0.00 | 0.00 |
July | 106.72 | 51.56 | 55.16 | 127.68 | 23.79 | 0.00 | 0.00 | 0.00 |
August | 80.47 | 39.07 | 41.40 | 92.28 | 31.30 | 0.00 | 0.00 | 0.00 |
September | 43.65 | 17.41 | 26.24 | 44.46 | 38.25 | 0.00 | 0.00 | 0.00 |
October | 17.99 | 4.48 | 13.51 | 10.30 | 62.90 | 10.17 | 0.00 | 0.00 |
November | 4.50 | 0.40 | 4.10 | 0.00 | 141.11 | 0.00 | 0.00 | 0.00 |
December | 0.66 | 0.01 | 0.65 | 0.00 | 154.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.17 | 25.26 | 26.92 | 57.66 | 73.42 | 10.17 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.01 | 0.65 | 0.00 | 18.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.93 | 62.40 | 59.70 | 145.47 | 154.82 | 10.17 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 22290705.67 | 3882028.10 | 18408677.57 | 0.00 | 0.179173E+10 |
February | 0.119797E+09 | 41968586.06 | 77828619.52 | 11084098.52 | 0.139212E+10 |
March | 0.398666E+09 | 0.172643E+09 | 0.226023E+09 | 0.189241E+09 | 0.112273E+10 |
April | 0.910144E+09 | 0.471836E+09 | 0.438307E+09 | 0.840096E+09 | 0.584350E+09 |
May | 0.913353E+09 | 0.416096E+09 | 0.497257E+09 | 0.880847E+09 | 0.333262E+09 |
June | 0.969160E+09 | 0.413663E+09 | 0.555498E+09 | 0.998878E+09 | 0.220630E+09 |
July | 0.836927E+09 | 0.316367E+09 | 0.520561E+09 | 0.863500E+09 | 0.253109E+09 |
August | 0.689951E+09 | 0.293187E+09 | 0.396764E+09 | 0.656296E+09 | 0.357535E+09 |
September | 0.402345E+09 | 0.167948E+09 | 0.234397E+09 | 0.286627E+09 | 0.527121E+09 |
October | 0.162817E+09 | 48756966.85 | 0.114060E+09 | 46809901.93 | 0.958024E+09 |
November | 63161489.47 | 22880523.91 | 40280965.56 | 2302224.41 | 0.166445E+10 |
December | 5872298.20 | 629619.57 | 5242678.64 | 0.00 | 0.190389E+10 |
Annual Sum or Average | 0.549449E+10 | 0.236986E+10 | 0.312463E+10 | 0.477568E+10 | 0.111089E+11 |
Minimum of Months | 5872298.20 | 629619.57 | 5242678.64 | 0.00 | 0.220630E+09 |
Maximum of Months | 0.969160E+09 | 0.471836E+09 | 0.555498E+09 | 0.998878E+09 | 0.190389E+10 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 24722537.34 | 4305542.68 | 20416994.65 | 0.00 | 0.198720E+10 |
February | 0.132867E+09 | 46547200.03 | 86319427.48 | 12293331.73 | 0.154399E+10 |
March | 0.442159E+09 | 0.191478E+09 | 0.250681E+09 | 0.209887E+09 | 0.124521E+10 |
April | 0.100944E+10 | 0.523312E+09 | 0.486125E+09 | 0.931748E+09 | 0.648100E+09 |
May | 0.101300E+10 | 0.461491E+09 | 0.551506E+09 | 0.976944E+09 | 0.369620E+09 |
June | 0.107489E+10 | 0.458792E+09 | 0.616101E+09 | 0.110785E+10 | 0.244700E+09 |
July | 0.928233E+09 | 0.350881E+09 | 0.577352E+09 | 0.957705E+09 | 0.280722E+09 |
August | 0.765223E+09 | 0.325173E+09 | 0.440050E+09 | 0.727896E+09 | 0.396541E+09 |
September | 0.446239E+09 | 0.186270E+09 | 0.259968E+09 | 0.317897E+09 | 0.584627E+09 |
October | 0.180580E+09 | 54076167.49 | 0.126504E+09 | 51916685.15 | 0.106254E+10 |
November | 70052169.03 | 25376702.51 | 44675466.51 | 2553388.38 | 0.184603E+10 |
December | 6512943.72 | 698308.68 | 5814635.04 | 0.00 | 0.211160E+10 |
Annual Sum or Average | 0.609391E+10 | 0.262840E+10 | 0.346551E+10 | 0.529669E+10 | 0.123209E+11 |
Minimum of Months | 6512943.72 | 698308.68 | 5814635.04 | 0.00 | 0.244700E+09 |
Maximum of Months | 0.107489E+10 | 0.523312E+09 | 0.616101E+09 | 0.110785E+10 | 0.211160E+10 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6540797.67 | 0.00 | 6540797.67 | 0.00 | 0.735548E+09 |
February | 26115379.02 | 0.00 | 26115379.02 | 0.00 | 0.600562E+09 |
March | 77561597.88 | 25922.78 | 77535675.10 | 2196731.95 | 0.506028E+09 |
April | 0.136552E+09 | 3815027.76 | 0.132737E+09 | 35645640.16 | 0.256284E+09 |
May | 0.216298E+09 | 34935042.94 | 0.181363E+09 | 0.129646E+09 | 0.118078E+09 |
June | 0.269867E+09 | 59225935.84 | 0.210641E+09 | 0.214792E+09 | 64705448.09 |
July | 0.235348E+09 | 38725245.78 | 0.196623E+09 | 0.191676E+09 | 85372667.22 |
August | 0.151199E+09 | 8176244.97 | 0.143023E+09 | 83038171.84 | 0.138907E+09 |
September | 81395184.68 | 234846.81 | 81160337.87 | 14213563.27 | 0.229081E+09 |
October | 40703541.04 | 0.00 | 40703541.04 | 1251034.69 | 0.412339E+09 |
November | 12224284.69 | 0.00 | 12224284.69 | 0.00 | 0.698670E+09 |
December | 1984136.48 | 0.00 | 1984136.48 | 0.00 | 0.775909E+09 |
Annual Sum or Average | 0.125579E+10 | 0.145138E+09 | 0.111065E+10 | 0.672459E+09 | 0.462148E+10 |
Minimum of Months | 1984136.48 | 0.00 | 1984136.48 | 0.00 | 64705448.09 |
Maximum of Months | 0.269867E+09 | 59225935.84 | 0.210641E+09 | 0.214792E+09 | 0.775909E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6540797.67 | 0.00 | 6540797.67 | 0.00 | 0.735548E+09 |
February | 26115379.02 | 0.00 | 26115379.02 | 0.00 | 0.600562E+09 |
March | 77561597.88 | 25922.78 | 77535675.10 | 2196731.95 | 0.506028E+09 |
April | 0.136552E+09 | 3815027.76 | 0.132737E+09 | 35645640.16 | 0.256284E+09 |
May | 0.216298E+09 | 34935042.94 | 0.181363E+09 | 0.129646E+09 | 0.118078E+09 |
June | 0.269867E+09 | 59225935.84 | 0.210641E+09 | 0.214792E+09 | 64705448.10 |
July | 0.235348E+09 | 38725245.78 | 0.196623E+09 | 0.191676E+09 | 85372667.23 |
August | 0.151199E+09 | 8176244.97 | 0.143023E+09 | 83038171.84 | 0.138907E+09 |
September | 81395184.68 | 234846.81 | 81160337.87 | 14213563.27 | 0.229081E+09 |
October | 40703541.04 | 0.00 | 40703541.04 | 1251034.69 | 0.412339E+09 |
November | 12224284.69 | 0.00 | 12224284.69 | 0.00 | 0.698670E+09 |
December | 1984136.48 | 0.00 | 1984136.48 | 0.00 | 0.775909E+09 |
Annual Sum or Average | 0.125579E+10 | 0.145138E+09 | 0.111065E+10 | 0.672459E+09 | 0.462148E+10 |
Minimum of Months | 1984136.48 | 0.00 | 1984136.48 | 0.00 | 64705448.10 |
Maximum of Months | 0.269867E+09 | 59225935.84 | 0.210641E+09 | 0.214792E+09 | 0.775909E+09 |
Report: WindowEnergyReportMonthly
For: FINE STORAGE OFFICE FRONT WALL WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.205890E+09 | 35856595.00 | 0.170033E+09 | 0.00 | 0.147218E+11 |
February | 0.110652E+10 | 0.387645E+09 | 0.718871E+09 | 0.152290E+09 | 0.113705E+11 |
March | 0.368231E+10 | 0.159463E+10 | 0.208768E+10 | 0.193869E+10 | 0.906818E+10 |
April | 0.840661E+10 | 0.435815E+10 | 0.404847E+10 | 0.795382E+10 | 0.473090E+10 |
May | 0.843626E+10 | 0.384330E+10 | 0.459296E+10 | 0.800912E+10 | 0.285443E+10 |
June | 0.895173E+10 | 0.382082E+10 | 0.513091E+10 | 0.884439E+10 | 0.198796E+10 |
July | 0.773035E+10 | 0.292214E+10 | 0.480821E+10 | 0.761732E+10 | 0.228024E+10 |
August | 0.637279E+10 | 0.270804E+10 | 0.366475E+10 | 0.581549E+10 | 0.314778E+10 |
September | 0.371629E+10 | 0.155126E+10 | 0.216502E+10 | 0.272756E+10 | 0.419680E+10 |
October | 0.150388E+10 | 0.450347E+09 | 0.105353E+10 | 0.521720E+09 | 0.755639E+10 |
November | 0.583396E+09 | 0.211337E+09 | 0.372058E+09 | 33934653.38 | 0.135880E+11 |
December | 54239950.55 | 5815520.47 | 48424430.08 | 0.00 | 0.156573E+11 |
Annual Sum or Average | 0.507502E+11 | 0.218893E+11 | 0.288609E+11 | 0.436143E+11 | 0.911603E+11 |
Minimum of Months | 54239950.55 | 5815520.47 | 48424430.08 | 0.00 | 0.198796E+10 |
Maximum of Months | 0.895173E+10 | 0.435815E+10 | 0.513091E+10 | 0.884439E+10 | 0.156573E+11 |
Report: WindowEnergyReportMonthly
For: FINE STORAGE OFFICE LEFT WALL WINDOW
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52196017.29 | 0.00 | 52196017.29 | 0.00 | 0.523001E+10 |
February | 0.208403E+09 | 0.00 | 0.208403E+09 | 0.00 | 0.424680E+10 |
March | 0.618947E+09 | 206865.61 | 0.618740E+09 | 33076725.65 | 0.350786E+10 |
April | 0.108969E+10 | 30444189.45 | 0.105925E+10 | 0.338889E+09 | 0.176097E+10 |
May | 0.172608E+10 | 0.278784E+09 | 0.144729E+10 | 0.102402E+10 | 0.880198E+09 |
June | 0.215355E+10 | 0.472627E+09 | 0.168093E+10 | 0.160273E+10 | 0.506790E+09 |
July | 0.187809E+10 | 0.309030E+09 | 0.156906E+10 | 0.141791E+10 | 0.664552E+09 |
August | 0.120658E+10 | 65247008.99 | 0.114133E+10 | 0.594958E+09 | 0.105757E+10 |
September | 0.649539E+09 | 1874094.07 | 0.647665E+09 | 0.132541E+09 | 0.156865E+10 |
October | 0.324817E+09 | 0.00 | 0.324817E+09 | 20067943.82 | 0.279841E+10 |
November | 97550636.32 | 0.00 | 97550636.32 | 0.00 | 0.493920E+10 |
December | 15833546.55 | 0.00 | 15833546.55 | 0.00 | 0.552179E+10 |
Annual Sum or Average | 0.100213E+11 | 0.115821E+10 | 0.886307E+10 | 0.516420E+10 | 0.326828E+11 |
Minimum of Months | 15833546.55 | 0.00 | 15833546.55 | 0.00 | 0.506790E+09 |
Maximum of Months | 0.215355E+10 | 0.472627E+09 | 0.168093E+10 | 0.160273E+10 | 0.552179E+10 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.387949E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 431028.54 | 0.292445E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 85622481.47 | 0.215070E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.255872E+09 | 0.110281E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.367336E+09 | 65655899.53 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.377054E+09 | 48406437.55 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.341979E+09 | 63708088.67 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.247169E+09 | 83841927.56 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.115251E+09 | 99131999.82 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 27583825.52 | 0.168463E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.365769E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.414673E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.181830E+10 | 0.231539E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 48406437.55 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.377054E+09 | 0.414673E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.387949E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 431028.54 | 0.292445E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 85622481.47 | 0.215070E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.255872E+09 | 0.110281E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.367336E+09 | 65655899.53 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.377054E+09 | 48406437.55 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.341979E+09 | 63708088.67 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.247169E+09 | 83841927.56 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.115251E+09 | 99131999.82 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 27583825.52 | 0.168463E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.365769E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.414673E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.181830E+10 | 0.231539E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 48406437.55 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.377054E+09 | 0.414673E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.387949E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 431028.54 | 0.292445E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 85622481.47 | 0.215070E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.255872E+09 | 0.110281E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.367336E+09 | 65655899.53 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.377054E+09 | 48406437.55 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.341979E+09 | 63708088.67 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.247169E+09 | 83841927.56 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.115251E+09 | 99131999.82 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 27583825.52 | 0.168463E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.365769E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.414673E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.181830E+10 | 0.231539E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 48406437.55 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.377054E+09 | 0.414673E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.387949E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 431028.54 | 0.292445E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 85622481.47 | 0.215070E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.255872E+09 | 0.110281E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.367336E+09 | 65655899.53 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.377054E+09 | 48406437.55 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.341979E+09 | 63708088.67 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.247169E+09 | 83841927.56 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.115251E+09 | 99131999.82 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 27583825.52 | 0.168463E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.365769E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.414673E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.181830E+10 | 0.231539E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 48406437.55 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.377054E+09 | 0.414673E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.387949E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 431028.54 | 0.292445E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 85622481.47 | 0.215070E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.255872E+09 | 0.110281E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.367336E+09 | 65655899.53 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.377054E+09 | 48406437.55 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.341979E+09 | 63708088.67 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.247169E+09 | 83841927.56 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.115251E+09 | 99131999.82 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 27583825.52 | 0.168463E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.365769E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.414673E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.181830E+10 | 0.231539E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 48406437.55 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.377054E+09 | 0.414673E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.387949E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 431028.54 | 0.292445E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 85622481.47 | 0.215070E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.255872E+09 | 0.110281E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.367336E+09 | 65655899.53 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.377054E+09 | 48406437.55 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.341979E+09 | 63708088.67 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.247169E+09 | 83841927.56 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.115251E+09 | 99131999.82 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 27583825.52 | 0.168463E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.365769E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.414673E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.181830E+10 | 0.231539E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 48406437.55 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.377054E+09 | 0.414673E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.387949E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 431028.54 | 0.292445E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 85622481.47 | 0.215070E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.255872E+09 | 0.110281E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.367336E+09 | 65655899.53 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.377054E+09 | 48406437.55 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.341979E+09 | 63708088.67 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.247169E+09 | 83841927.56 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.115251E+09 | 99131999.82 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 27583825.52 | 0.168463E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.365769E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.414673E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.181830E+10 | 0.231539E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 48406437.55 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.377054E+09 | 0.414673E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.387949E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 431028.54 | 0.292445E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 85622481.47 | 0.215070E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.255872E+09 | 0.110281E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.367336E+09 | 65655899.53 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.377054E+09 | 48406437.55 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.341979E+09 | 63708088.67 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.247169E+09 | 83841927.56 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.115251E+09 | 99131999.82 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 27583825.52 | 0.168463E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.365769E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.414673E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.181830E+10 | 0.231539E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 48406437.55 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.377054E+09 | 0.414673E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.387949E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 431028.54 | 0.292445E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 85622481.47 | 0.215070E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.255872E+09 | 0.110281E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.367336E+09 | 65655899.53 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.377054E+09 | 48406437.55 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.341979E+09 | 63708088.67 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.247169E+09 | 83841927.56 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.115251E+09 | 99131999.82 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 27583825.52 | 0.168463E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.365769E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.414673E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.181830E+10 | 0.231539E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 48406437.55 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.377054E+09 | 0.414673E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6348617.64 | 621089.23 | 5727528.41 | 0.00 | 0.387949E+09 |
February | 29196265.26 | 7428725.85 | 21767539.41 | 431028.54 | 0.292445E+09 |
March | 0.112951E+09 | 48564302.36 | 64386624.33 | 85622481.47 | 0.215070E+09 |
April | 0.218659E+09 | 0.118236E+09 | 0.100422E+09 | 0.255872E+09 | 0.110281E+09 |
May | 0.293835E+09 | 0.167145E+09 | 0.126690E+09 | 0.367336E+09 | 65655899.53 |
June | 0.308263E+09 | 0.153533E+09 | 0.154731E+09 | 0.377054E+09 | 48406437.55 |
July | 0.285843E+09 | 0.138096E+09 | 0.147747E+09 | 0.341979E+09 | 63708088.67 |
August | 0.215518E+09 | 0.104640E+09 | 0.110877E+09 | 0.247169E+09 | 83841927.56 |
September | 0.113141E+09 | 45118305.63 | 68023086.89 | 0.115251E+09 | 99131999.82 |
October | 48180346.56 | 12004834.37 | 36175512.19 | 27583825.52 | 0.168463E+09 |
November | 11662255.45 | 1036583.65 | 10625671.80 | 0.00 | 0.365769E+09 |
December | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 0.414673E+09 |
Annual Sum or Average | 0.164537E+10 | 0.796462E+09 | 0.848906E+09 | 0.181830E+10 | 0.231539E+10 |
Minimum of Months | 1769623.80 | 36985.30 | 1732638.50 | 0.00 | 48406437.55 |
Maximum of Months | 0.308263E+09 | 0.167145E+09 | 0.154731E+09 | 0.377054E+09 | 0.414673E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1960.13 | 22.44 | 3.06 | 19.38 | 0.00 | 0.00 |
February | 2.65 | 1703.15 | 126.03 | 36.59 | 89.44 | 0.00 | 0.00 |
March | 126.52 | 1237.81 | 371.84 | 135.97 | 235.88 | 0.00 | 0.00 |
April | 695.69 | 657.83 | 845.94 | 386.87 | 459.07 | 0.00 | 0.00 |
May | 760.85 | 321.02 | 880.73 | 353.74 | 526.99 | 0.00 | 0.00 |
June | 942.65 | 193.58 | 996.83 | 382.29 | 614.54 | 0.00 | 0.00 |
July | 798.85 | 238.82 | 834.77 | 278.04 | 556.73 | 0.00 | 0.00 |
August | 568.14 | 374.60 | 656.20 | 236.97 | 419.23 | 0.00 | 0.00 |
September | 235.72 | 597.20 | 390.19 | 136.84 | 253.35 | 0.00 | 0.00 |
October | 30.74 | 1055.23 | 158.60 | 38.39 | 120.21 | 0.00 | 0.00 |
November | 0.50 | 1892.08 | 60.83 | 18.62 | 42.21 | 0.00 | 0.00 |
December | 0.00 | 2078.59 | 6.11 | 0.50 | 5.61 | 0.00 | 0.00 |
Annual Sum or Average | 348.35 | 1022.36 | 447.11 | 167.70 | 279.41 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 193.58 | 6.11 | 0.50 | 5.61 | 0.00 | 0.00 |
Maximum of Months | 942.65 | 2078.59 | 996.83 | 386.87 | 614.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 7449.13 | 96.36 | 13.39 | 82.97 | 0.00 | 0.00 |
February | 27.69 | 6420.31 | 543.53 | 160.24 | 383.30 | 0.00 | 0.00 |
March | 653.89 | 4613.07 | 1605.91 | 595.44 | 1010.46 | 0.00 | 0.00 |
April | 3152.57 | 2457.81 | 3663.70 | 1693.13 | 1970.57 | 0.00 | 0.00 |
May | 3252.79 | 1274.55 | 3794.18 | 1539.01 | 2255.17 | 0.00 | 0.00 |
June | 3881.12 | 813.07 | 4284.44 | 1656.42 | 2628.02 | 0.00 | 0.00 |
July | 3271.15 | 997.24 | 3587.38 | 1206.38 | 2381.00 | 0.00 | 0.00 |
August | 2348.86 | 1525.57 | 2829.81 | 1035.43 | 1794.39 | 0.00 | 0.00 |
September | 1072.97 | 2193.86 | 1684.35 | 599.20 | 1085.14 | 0.00 | 0.00 |
October | 174.92 | 3838.68 | 682.76 | 168.14 | 514.62 | 0.00 | 0.00 |
November | 5.50 | 7140.26 | 262.71 | 81.53 | 181.18 | 0.00 | 0.00 |
December | 0.00 | 7907.35 | 26.16 | 2.17 | 23.99 | 0.00 | 0.00 |
Annual Sum or Average | 1492.85 | 3873.13 | 1927.05 | 730.83 | 1196.22 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 813.07 | 26.16 | 2.17 | 23.99 | 0.00 | 0.00 |
Maximum of Months | 3881.12 | 7907.35 | 4284.44 | 1693.13 | 2628.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1448.43 | 23.70 | 2.32 | 21.38 | 0.00 | 0.00 |
February | 1.78 | 1208.85 | 120.69 | 30.71 | 89.98 | 0.00 | 0.00 |
March | 319.68 | 802.98 | 421.71 | 181.32 | 240.39 | 0.00 | 0.00 |
April | 987.16 | 425.47 | 843.59 | 456.16 | 387.43 | 0.00 | 0.00 |
May | 1371.48 | 245.13 | 1097.05 | 624.05 | 473.01 | 0.00 | 0.00 |
June | 1454.68 | 186.75 | 1189.29 | 592.33 | 596.95 | 0.00 | 0.00 |
July | 1276.80 | 237.86 | 1067.22 | 515.59 | 551.62 | 0.00 | 0.00 |
August | 922.82 | 313.03 | 804.65 | 390.68 | 413.97 | 0.00 | 0.00 |
September | 444.64 | 382.45 | 436.50 | 174.07 | 262.43 | 0.00 | 0.00 |
October | 102.99 | 628.97 | 179.88 | 44.82 | 135.06 | 0.00 | 0.00 |
November | 0.00 | 1411.14 | 44.99 | 4.00 | 40.99 | 0.00 | 0.00 |
December | 0.00 | 1548.21 | 6.61 | 0.14 | 6.47 | 0.00 | 0.00 |
Annual Sum or Average | 576.58 | 734.21 | 521.74 | 252.56 | 269.19 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 186.75 | 6.61 | 0.14 | 6.47 | 0.00 | 0.00 |
Maximum of Months | 1454.68 | 1548.21 | 1189.29 | 624.05 | 596.95 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.525002E+10 | 60094838.35 | 8187570.78 | 51907267.57 | 0.00 | 0.00 |
February | 6401709.09 | 0.412026E+10 | 0.304895E+09 | 88515786.10 | 0.216379E+09 | 0.00 | 0.00 |
March | 0.338877E+09 | 0.331535E+10 | 0.995948E+09 | 0.364173E+09 | 0.631775E+09 | 0.00 | 0.00 |
April | 0.180322E+10 | 0.170510E+10 | 0.219268E+10 | 0.100278E+10 | 0.118991E+10 | 0.00 | 0.00 |
May | 0.203787E+10 | 0.859829E+09 | 0.235895E+10 | 0.947457E+09 | 0.141149E+10 | 0.00 | 0.00 |
June | 0.244334E+10 | 0.501771E+09 | 0.258379E+10 | 0.990906E+09 | 0.159288E+10 | 0.00 | 0.00 |
July | 0.213964E+10 | 0.639659E+09 | 0.223586E+10 | 0.744698E+09 | 0.149116E+10 | 0.00 | 0.00 |
August | 0.152171E+10 | 0.100333E+10 | 0.175757E+10 | 0.634712E+09 | 0.112286E+10 | 0.00 | 0.00 |
September | 0.610985E+09 | 0.154794E+10 | 0.101137E+10 | 0.354688E+09 | 0.656686E+09 | 0.00 | 0.00 |
October | 82327305.24 | 0.282634E+10 | 0.424804E+09 | 0.102833E+09 | 0.321971E+09 | 0.00 | 0.00 |
November | 1305185.97 | 0.490427E+10 | 0.157662E+09 | 48257226.43 | 0.109405E+09 | 0.00 | 0.00 |
December | 0.00 | 0.556730E+10 | 16353514.89 | 1327928.25 | 15025586.64 | 0.00 | 0.00 |
Annual Sum or Average | 0.109857E+11 | 0.322412E+11 | 0.141000E+11 | 0.528854E+10 | 0.881144E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.501771E+09 | 16353514.89 | 1327928.25 | 15025586.64 | 0.00 | 0.00 |
Maximum of Months | 0.244334E+10 | 0.556730E+10 | 0.258379E+10 | 0.100278E+10 | 0.159288E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.199518E+11 | 0.258086E+09 | 35856595.00 | 0.222229E+09 | 0.00 | 0.00 |
February | 66988037.43 | 0.155320E+11 | 0.131492E+10 | 0.387645E+09 | 0.927273E+09 | 0.00 | 0.00 |
March | 0.175138E+10 | 0.123557E+11 | 0.430126E+10 | 0.159484E+10 | 0.270642E+10 | 0.00 | 0.00 |
April | 0.817147E+10 | 0.637064E+10 | 0.949630E+10 | 0.438859E+10 | 0.510771E+10 | 0.00 | 0.00 |
May | 0.871227E+10 | 0.341376E+10 | 0.101623E+11 | 0.412208E+10 | 0.604025E+10 | 0.00 | 0.00 |
June | 0.100599E+11 | 0.210747E+10 | 0.111053E+11 | 0.429345E+10 | 0.681183E+10 | 0.00 | 0.00 |
July | 0.876144E+10 | 0.267101E+10 | 0.960844E+10 | 0.323117E+10 | 0.637727E+10 | 0.00 | 0.00 |
August | 0.629118E+10 | 0.408607E+10 | 0.757937E+10 | 0.277329E+10 | 0.480608E+10 | 0.00 | 0.00 |
September | 0.278113E+10 | 0.568648E+10 | 0.436583E+10 | 0.155314E+10 | 0.281269E+10 | 0.00 | 0.00 |
October | 0.468504E+09 | 0.102815E+11 | 0.182869E+10 | 0.450347E+09 | 0.137835E+10 | 0.00 | 0.00 |
November | 14243921.02 | 0.185076E+11 | 0.680946E+09 | 0.211337E+09 | 0.469609E+09 | 0.00 | 0.00 |
December | 0.00 | 0.211790E+11 | 70073497.09 | 5815520.47 | 64257976.63 | 0.00 | 0.00 |
Annual Sum or Average | 0.470785E+11 | 0.122143E+12 | 0.607715E+11 | 0.230476E+11 | 0.377240E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.210747E+10 | 70073497.09 | 5815520.47 | 64257976.63 | 0.00 | 0.00 |
Maximum of Months | 0.100599E+11 | 0.211790E+11 | 0.111053E+11 | 0.438859E+10 | 0.681183E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.387949E+10 | 63486176.40 | 6210892.33 | 57275284.06 | 0.00 | 0.00 |
February | 4310285.39 | 0.292445E+10 | 0.291963E+09 | 74287258.49 | 0.217675E+09 | 0.00 | 0.00 |
March | 0.856225E+09 | 0.215070E+10 | 0.112951E+10 | 0.485643E+09 | 0.643866E+09 | 0.00 | 0.00 |
April | 0.255872E+10 | 0.110281E+10 | 0.218659E+10 | 0.118236E+10 | 0.100422E+10 | 0.00 | 0.00 |
May | 0.367336E+10 | 0.656559E+09 | 0.293835E+10 | 0.167145E+10 | 0.126690E+10 | 0.00 | 0.00 |
June | 0.377054E+10 | 0.484064E+09 | 0.308263E+10 | 0.153533E+10 | 0.154731E+10 | 0.00 | 0.00 |
July | 0.341979E+10 | 0.637081E+09 | 0.285843E+10 | 0.138096E+10 | 0.147747E+10 | 0.00 | 0.00 |
August | 0.247169E+10 | 0.838419E+09 | 0.215518E+10 | 0.104640E+10 | 0.110877E+10 | 0.00 | 0.00 |
September | 0.115251E+10 | 0.991320E+09 | 0.113141E+10 | 0.451183E+09 | 0.680231E+09 | 0.00 | 0.00 |
October | 0.275838E+09 | 0.168463E+10 | 0.481803E+09 | 0.120048E+09 | 0.361755E+09 | 0.00 | 0.00 |
November | 0.00 | 0.365769E+10 | 0.116623E+09 | 10365836.48 | 0.106257E+09 | 0.00 | 0.00 |
December | 0.00 | 0.414673E+10 | 17696238.01 | 369852.99 | 17326385.03 | 0.00 | 0.00 |
Annual Sum or Average | 0.181830E+11 | 0.231539E+11 | 0.164537E+11 | 0.796462E+10 | 0.848906E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.484064E+09 | 17696238.01 | 369852.99 | 17326385.03 | 0.00 | 0.00 |
Maximum of Months | 0.377054E+10 | 0.414673E+10 | 0.308263E+10 | 0.167145E+10 | 0.154731E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.116104E+10 | -0.107077E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -90266633.8 | 59.95 | 0.00 | 0.00 |
February | 0.106518E+10 | -983743375.2 | 0.00 | 0.00 | 672.00 | 0.00 | -81439040.4 | 59.95 | 0.00 | 0.00 |
March | 0.123957E+10 | -0.114981E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -89761906.7 | 59.95 | 0.00 | 0.00 |
April | 0.115262E+10 | -0.106814E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -84470745.9 | 59.95 | 0.00 | 0.00 |
May | 0.118303E+10 | -0.110281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -80219955.7 | 59.95 | 0.00 | 0.00 |
June | 0.113170E+10 | -0.105913E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -72567384.5 | 59.95 | 0.00 | 0.00 |
July | 0.105967E+10 | -985661048.0 | 0.00 | 0.00 | 744.00 | 0.00 | -74004773.2 | 59.95 | 0.00 | 0.00 |
August | 0.110877E+10 | -0.103339E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -75383194.6 | 59.95 | 0.00 | 0.00 |
September | 0.103704E+10 | -957154144.9 | 0.00 | 0.00 | 720.00 | 0.00 | -79882763.0 | 59.95 | 0.00 | 0.00 |
October | 0.106741E+10 | -977972690.4 | 0.00 | 0.00 | 744.00 | 0.00 | -89435351.6 | 59.95 | 0.00 | 0.00 |
November | 0.105969E+10 | -972405046.4 | 0.00 | 0.00 | 720.00 | 0.00 | -87289369.1 | 59.95 | 0.00 | 0.00 |
December | 0.114364E+10 | -0.105339E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -90250380.0 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.134094E+11 | -0.124144E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -994971498.4 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.103704E+10 | -0.114981E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -90266633.8 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.123957E+10 | -957154144.9 | 0.00 | 0.00 | 744.00 | 0.00 | -72567384.5 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 108.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 205.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 329.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 421.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 545.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 562.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 467.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 356.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 135.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 71.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 583.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.170687E+11 | 24633.03 | 01-JAN-00:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136790E+11 | 24633.03 | 01-FEB-03:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125304E+11 | 24633.03 | 01-MAR-00:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.434388E+10 | 24633.03 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.207927E+09 | 24633.03 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15945692.41 | 4114.71 | 31-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.966615E+09 | 24633.03 | 06-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.715312E+10 | 24633.03 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139977E+11 | 24633.03 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167290E+11 | 24633.03 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.866922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.170687E+11 | 24633.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.666521E+11 | 95790.97 | 01-JAN-00:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.514338E+11 | 95790.97 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398193E+11 | 95790.97 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118161E+11 | 95790.97 | 01-APR-00:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.107705E+10 | 58185.92 | 30-SEP-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229992E+11 | 95790.97 | 12-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.547925E+11 | 95790.97 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.691186E+11 | 95790.97 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317709E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.691186E+11 | 95790.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.228820E+12 | 212491.56 | 28-JAN-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178443E+12 | 195137.36 | 25-FEB-00:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142349E+12 | 157988.68 | 02-MAR-04:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.473009E+11 | 124721.23 | 02-APR-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.828953E+09 | 26675.13 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.740424E+11 | 117843.50 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171843E+12 | 136274.47 | 29-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229426E+12 | 151499.82 | 28-DEC-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107305E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.229426E+12 | 212491.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 394.13 | 394.13 | 0.10 | 22-APR-11:40 | 0.10 | 0.00 |
May | 0.00 | 0.00 | 87762320.64 | 87762320.64 | 4990.83 | 31-MAY-16:00 | 4990.83 | 0.00 |
June | 0.00 | 0.00 | 0.202607E+10 | 0.194593E+10 | 20157.28 | 30-JUN-05:01 | 13179.90 | 0.00 |
July | 0.00 | 0.00 | 0.360328E+10 | 0.332327E+10 | 20590.71 | 25-JUL-05:02 | 11871.04 | 0.00 |
August | 0.00 | 0.00 | 0.159758E+10 | 0.147814E+10 | 20061.91 | 03-AUG-05:01 | 13745.67 | 0.00 |
September | 0.00 | 0.00 | 663.12 | 663.12 | 0.19 | 02-SEP-07:10 | 0.19 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.731470E+10 | 0.683510E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.360328E+10 | 0.332327E+10 | 20590.71 | 13745.67 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 9362.32 | 9362.32 | 1.17 | 17-MAY-17:00 | 1.17 | 0.00 |
June | 0.00 | 0.00 | 0.377467E+10 | 0.370633E+10 | 90019.38 | 30-JUN-18:00 | 79171.95 | 0.00 |
July | 0.00 | 0.00 | 0.717575E+10 | 0.706124E+10 | 91078.83 | 08-JUL-17:27 | 77046.72 | 0.00 |
August | 0.00 | 0.00 | 0.176623E+10 | 0.174834E+10 | 88365.46 | 03-AUG-17:17 | 82514.97 | 0.00 |
September | 0.00 | 0.00 | 1814.90 | 1814.90 | 0.73 | 02-SEP-15:40 | 0.73 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.127167E+11 | 0.125159E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.717575E+10 | 0.706124E+10 | 91078.83 | 82514.97 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.269281E+11 | 0.53 | 10053.80 | 01-JAN-00:01 | 0.53 |
February | 0.241955E+11 | 0.53 | 10053.80 | 01-FEB-00:02 | 0.53 |
March | 0.247499E+11 | 0.49 | 10053.80 | 01-MAR-00:02 | 0.53 |
April | 0.120015E+11 | 0.25 | 10053.80 | 01-APR-00:03 | 0.53 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.108682E+10 | 0.02 | 10053.80 | 28-SEP-01:00 | 0.53 |
October | 0.191784E+11 | 0.38 | 10053.80 | 01-OCT-00:10 | 0.53 |
November | 0.260595E+11 | 0.53 | 10053.80 | 01-NOV-00:05 | 0.53 |
December | 0.269281E+11 | 0.53 | 10053.80 | 01-DEC-00:02 | 0.53 |
Annual Sum or Average | 0.161128E+12 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.269281E+11 | 0.53 | 10053.80 | 0.53 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.261047E+10 | 1.17 | 2117.22 | 06-JAN-12:50 | 1.39 |
February | 0.234613E+10 | 1.15 | 2117.22 | 02-FEB-07:06 | 1.39 |
March | 0.261434E+10 | 1.10 | 2117.22 | 03-MAR-11:30 | 1.39 |
April | 0.222772E+10 | 0.75 | 2117.22 | 04-APR-10:30 | 1.39 |
May | 0.219062E+10 | 0.55 | 2117.22 | 01-MAY-06:13 | 1.39 |
June | 0.220550E+10 | 0.56 | 2117.22 | 01-JUN-07:15 | 1.38 |
July | 0.213637E+10 | 0.53 | 2117.22 | 08-JUL-09:40 | 1.38 |
August | 0.228035E+10 | 0.56 | 2117.22 | 01-AUG-06:03 | 1.38 |
September | 0.212000E+10 | 0.55 | 2117.22 | 01-SEP-16:40 | 1.38 |
October | 0.227481E+10 | 0.80 | 2117.22 | 02-OCT-08:40 | 1.38 |
November | 0.238159E+10 | 1.13 | 2117.22 | 02-NOV-12:40 | 1.39 |
December | 0.254869E+10 | 1.17 | 2117.22 | 01-DEC-12:20 | 1.39 |
Annual Sum or Average | 0.279366E+11 | 0.83 | |||
Minimum of Months | 0.212000E+10 | 0.53 | 2117.22 | 1.38 | |
Maximum of Months | 0.261434E+10 | 1.17 | 2117.22 | 1.39 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.118144E+11 | 1.20 | 8115.89 | 04-JAN-17:40 | 1.35 |
February | 0.105997E+11 | 1.20 | 8115.89 | 02-FEB-13:50 | 1.35 |
March | 0.114132E+11 | 1.19 | 8115.89 | 01-MAR-10:50 | 1.35 |
April | 0.901895E+10 | 0.85 | 8115.89 | 01-APR-10:30 | 1.35 |
May | 0.835612E+10 | 0.52 | 8115.89 | 15-MAY-15:50 | 1.34 |
June | 0.861664E+10 | 0.57 | 8115.89 | 06-JUN-11:20 | 1.34 |
July | 0.843910E+10 | 0.56 | 8115.89 | 07-JUL-15:50 | 1.33 |
August | 0.878904E+10 | 0.55 | 8115.89 | 10-AUG-16:30 | 1.34 |
September | 0.814045E+10 | 0.58 | 8115.89 | 30-SEP-08:50 | 1.34 |
October | 0.975234E+10 | 1.07 | 8115.89 | 11-OCT-08:40 | 1.34 |
November | 0.109353E+11 | 1.20 | 8115.89 | 01-NOV-06:50 | 1.35 |
December | 0.118243E+11 | 1.21 | 8115.89 | 27-DEC-07:20 | 1.35 |
Annual Sum or Average | 0.117699E+12 | 0.89 | |||
Minimum of Months | 0.814045E+10 | 0.52 | 8115.89 | 1.33 | |
Maximum of Months | 0.118243E+11 | 1.21 | 8115.89 | 1.35 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.261047E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.234613E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.261434E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.222772E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.221288E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.269366E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.299887E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.266556E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.212000E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.227481E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.238159E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.254869E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.296947E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.212000E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.299887E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.118144E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.105997E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.114132E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.901895E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.835612E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.954082E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.102045E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.922467E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.814045E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.975234E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.109353E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.118243E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.120825E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.814045E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.118243E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.261047E+10 | 0.00 | 0.170687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.234613E+10 | 0.00 | 0.136790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261434E+10 | 0.00 | 0.125304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222772E+10 | 394.13 | 0.434388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.219062E+10 | 87762320.64 | 0.207927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220550E+10 | 0.202607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.213637E+10 | 0.360328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.228035E+10 | 0.159758E+10 | 15945692.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212000E+10 | 663.12 | 0.966615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.227481E+10 | 0.00 | 0.715312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238159E+10 | 0.00 | 0.139977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254869E+10 | 0.00 | 0.167290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279366E+11 | 0.731470E+10 | 0.866922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.212000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261434E+10 | 0.360328E+10 | 0.170687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.118144E+11 | 0.00 | 0.666521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105997E+11 | 0.00 | 0.514338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114132E+11 | 0.00 | 0.398193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.901895E+10 | 0.00 | 0.118161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.835612E+10 | 9362.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.861664E+10 | 0.377467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.843910E+10 | 0.717575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.878904E+10 | 0.176623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.814045E+10 | 1814.90 | 0.107705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.975234E+10 | 0.00 | 0.229992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109353E+11 | 0.00 | 0.547925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118243E+11 | 0.00 | 0.691186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117699E+12 | 0.127167E+11 | 0.317709E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.814045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118243E+11 | 0.717575E+10 | 0.691186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.261047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.234613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.261434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.222772E+10 | 0.00 | 0.00 | 0.00 | 103.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.219062E+10 | 0.00 | 0.00 | 0.00 | 22257646.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.220550E+10 | 0.00 | 0.00 | 0.00 | 0.488164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.213637E+10 | 0.00 | 0.00 | 0.00 | 0.862494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.228035E+10 | 0.00 | 0.00 | 0.00 | 0.385210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.212000E+10 | 0.00 | 0.00 | 0.00 | 174.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.227481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279366E+11 | 0.00 | 0.00 | 0.00 | 0.175813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.212000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.261434E+10 | 0.00 | 0.00 | 0.00 | 0.862494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.118144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.901895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.835612E+10 | 0.00 | 0.00 | 0.00 | 2468.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.861664E+10 | 0.00 | 0.00 | 0.00 | 0.924182E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.843910E+10 | 0.00 | 0.00 | 0.00 | 0.176544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.878904E+10 | 0.00 | 0.00 | 0.00 | 0.435631E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.814045E+10 | 0.00 | 0.00 | 0.00 | 478.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.975234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117699E+12 | 0.00 | 0.00 | 0.00 | 0.312526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.814045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118243E+11 | 0.00 | 0.00 | 0.00 | 0.176544E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455035E+10 | 0.00 | 0.00 | 0.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367684E+10 | 0.00 | 0.00 | 0.13 |
March | 10749841.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371206E+10 | 0.00 | 0.00 | 0.13 |
April | 0.554137E+09 | 0.00 | 0.00 | 102891.10 | 0.00 | 0.156724E+10 | 0.246551E+09 | 0.00 | 0.14 |
May | 0.552029E+09 | 0.00 | 0.00 | 2268320.83 | 0.00 | 25984289.60 | 0.296625E+10 | 0.00 | 0.43 |
June | 36685707.96 | 7591806.01 | 0.00 | 7940316.58 | 0.00 | 0.00 | 0.532261E+10 | 0.00 | 0.96 |
July | 42288531.33 | 23674765.01 | 0.00 | 8920909.16 | 0.00 | 0.00 | 0.420602E+10 | 0.00 | 0.91 |
August | 0.117646E+09 | 156702.19 | 0.00 | 7167353.95 | 0.00 | 0.00 | 0.513468E+10 | 0.00 | 0.82 |
September | 0.917938E+09 | 0.00 | 0.00 | 859964.10 | 0.00 | 0.494196E+09 | 0.136710E+10 | 0.00 | 0.22 |
October | 0.205192E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263460E+10 | 0.00 | 0.00 | 0.12 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432580E+10 | 0.00 | 0.00 | 0.12 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479425E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.243667E+10 | 31423273.22 | 0.00 | 27259755.72 | 0.00 | 0.257813E+11 | 0.192432E+11 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.917938E+09 | 23674765.01 | 0.00 | 8920909.16 | 0.00 | 0.479425E+10 | 0.532261E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157567E+11 | 0.00 | 0.00 | 0.17 |
February | 0.307295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120377E+11 | 0.00 | 0.00 | 0.18 |
March | 0.298506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918090E+10 | 0.00 | 0.00 | 0.19 |
April | 0.587293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150088E+10 | 0.00 | 0.00 | 0.18 |
May | 0.572264E+10 | 0.00 | 0.00 | 686103.76 | 0.00 | 0.00 | 0.172623E+10 | 0.00 | 0.24 |
June | 0.996805E+09 | 97535.94 | 0.00 | 17111984.13 | 0.00 | 0.00 | 0.148673E+11 | 0.00 | 0.76 |
July | 0.751702E+09 | 14665329.99 | 0.00 | 20691638.33 | 0.00 | 0.00 | 0.140585E+11 | 0.00 | 0.81 |
August | 0.269648E+10 | 0.00 | 0.00 | 11464688.43 | 0.00 | 0.00 | 0.115329E+11 | 0.00 | 0.62 |
September | 0.696188E+10 | 0.00 | 0.00 | 5705.13 | 0.00 | 91127953.05 | 57455137.88 | 0.00 | 0.18 |
October | 0.388497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516623E+10 | 0.00 | 0.00 | 0.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149550E+11 | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167388E+11 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.301798E+11 | 14762865.93 | 0.00 | 49960119.77 | 0.00 | 0.754273E+11 | 0.422424E+11 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.696188E+10 | 14665329.99 | 0.00 | 20691638.33 | 0.00 | 0.167388E+11 | 0.148673E+11 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:39
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.726428E+11 | 0.754287E+11 | 0.00 | 0.203070E+11 | 0.103774E+12 |
February | 0.477907E+11 | 0.612722E+11 | 0.00 | 0.160218E+11 | 0.829928E+11 |
March | 0.399584E+12 | 0.839421E+11 | 0.00 | 0.158888E+11 | 0.710034E+11 |
April | 0.718639E+12 | 0.664471E+11 | 0.00 | 0.974185E+10 | 0.322451E+11 |
May | 0.932982E+12 | 0.432377E+11 | 0.00 | 0.109975E+11 | 0.142664E+11 |
June | 0.988169E+12 | 0.375740E+11 | 0.00 | 0.216736E+11 | 0.208211E+11 |
July | 0.908754E+12 | 0.362944E+11 | 0.00 | 0.195612E+11 | 0.274686E+11 |
August | 0.672154E+12 | 0.423944E+11 | 0.00 | 0.197689E+11 | 0.182546E+11 |
September | 0.296355E+12 | 0.302173E+11 | 0.00 | 0.989056E+10 | 0.148030E+11 |
October | 0.818542E+11 | 0.618412E+11 | 0.00 | 0.118910E+11 | 0.455404E+11 |
November | -0.343443E+11 | 0.300267E+11 | 0.00 | 0.192808E+11 | 0.845527E+11 |
December | -0.931048E+11 | 0.602951E+11 | 0.00 | 0.215331E+11 | 0.104984E+12 |
Annual Sum or Average | 0.484619E+13 | 0.628971E+12 | 0.00 | 0.196556E+12 | 0.620706E+12 |
Minimum of Months | -0.931048E+11 | 0.300267E+11 | 0.00 | 0.974185E+10 | 0.142664E+11 |
Maximum of Months | 0.988169E+12 | 0.839421E+11 | 0.00 | 0.216736E+11 | 0.104984E+12 |