Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19
Tabular Output Report in Format: HTML
Building: Warehouse
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2024-07-03 12:19:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3095.47 | 640.20 | 640.20 |
Net Site Energy | 3095.47 | 640.20 | 640.20 |
Total Source Energy | 6140.05 | 1269.88 | 1269.88 |
Net Source Energy | 6140.05 | 1269.88 | 1269.88 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4835.13 |
Net Conditioned Building Area | 4835.13 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1758.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 33.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 133.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 397.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 11.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1336.80 | 1758.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1758.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 33.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 133.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 1.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 395.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 11.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1758.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 33.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 623.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 133.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 136.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 397.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 11.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.61 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 91.57 | 363.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 276.48 | 363.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 156.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 91.57 | 363.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Other | 28.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 276.48 | 363.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1336.802 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1336.802 | 100.00 |
Total On-Site and Utility Electric Sources | 1336.802 | 100.00 |
Total Electricity End Uses | 1336.802 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 51.61 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 51.61 | 100.00 |
Total Water End Uses | 51.61 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 91.33 |
Time Setpoint Not Met During Occupied Cooling | 5.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3135.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneHeatingSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ZoneElectricSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |PeakSpaceGainsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |SpaceGainComponentsAtCoolingPeakMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |ComfortReportSimple55Monthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |OccupantComfortDataSummaryMonthly
| OFFICE PEOPLE | ZONE2 FINE STORAGEPEOPLE | ZONE3 BULK STORAGEPEOPLE |DXReportMonthly
| PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |WindowReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINE STORAGE OFFICE FRONT WALL WINDOW | FINE STORAGE OFFICE LEFT WALL WINDOW | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowEnergyReportMonthly
| OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | FINE STORAGE OFFICE FRONT WALL WINDOW | FINE STORAGE OFFICE LEFT WALL WINDOW | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 |WindowZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |WindowEnergyZoneSummaryMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-OFFICE HEATING COIL | PSZ-FINE STORAGE HEATING COIL | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | PSZ-OFFICE COOLING COIL | PSZ-FINE STORAGE COOLING COIL |FanReportMonthly
| ZONE3UNITHEATER ZONE3HIRADIANT FAN | PSZ-OFFICE_ADDAQ SUPPLY FAN | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN |ZoneTemperatureOscillationReportMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentLoadsMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |AirLoopSystemComponentEnergyUseMonthly
| PSZ-OFFICE | PSZ-FINE STORAGE |MechanicalVentilationLoadsMonthly
| ZONE1 OFFICE | ZONE2 FINE STORAGE | ZONE3 BULK STORAGE |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:19 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 149.82 | 39.41 | 0.00 | 0.00 | 110.41 |
Gross Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Above Ground Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Above Ground Wall Area [m2] | 2496.99 | 858.34 | 390.15 | 858.34 | 390.15 |
Window Opening Area [m2] | 149.82 | 39.41 | 0.00 | 0.00 | 110.41 |
Gross Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Above Ground Window-Wall Ratio [%] | 6.00 | 4.59 | 0.00 | 0.00 | 28.30 |
Total | |
Gross Roof Area [m2] | 4598.25 |
Skylight Area [m2] | 21.81 |
Skylight-Roof Ratio [%] | 0.47 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1010.76 | 1.00 | 149.56 | 0.00 | 28.42 | 28.42 | 10.7186 | 18.58 | 8.0737 |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 2953.02 | 1.00 | 760.80 | 0.00 | 121.40 | 121.40 | 15.0695 | 46.45 | 0.0000 |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 35277.63 | 1.00 | 1586.63 | 0.00 | 0.00 | 0.00 | 9.6875 | 46.45 | 2.5587 |
Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 149.82 | 149.82 | 11.2890 | 43.27 | 2.0915 | |||
Conditioned Total | 4835.13 | 39241.41 | 2496.99 | 0.00 | 149.82 | 149.82 | 11.2890 | 43.27 | 2.0915 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
ZONE1 OFFICE | 236.88 | Yes | Yes | 1.00 | ZONE1 OFFICE | GENERAL | ZONE1 OFFICE | 10.7186 | 18.58 | 8.0737 | |
ZONE2 FINE STORAGE | 1393.41 | Yes | Yes | 1.00 | ZONE2 FINE STORAGE | GENERAL | ZONE2 FINE STORAGE | 15.0695 | 46.45 | 0.0000 | |
ZONE3 BULK STORAGE | 3204.84 | Yes | Yes | 1.00 | ZONE3 BULK STORAGE | GENERAL | ZONE3 BULK STORAGE | 9.6875 | 46.45 | 2.5587 | |
Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Conditioned Total | 4835.13 | 11.2890 | 21.63 | 2.0915 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4835.13 | 4835.13 | 0.00 | 0.00 | 11.2890 | 43.27 | 2.0915 |
Total | 4835.13 | 4835.13 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-14:00 | 09-DEC-08:00 | - | - | - | - | - | - | - | - | - | - | 20-JUN-11:09 |
Heating | 0.00 | 599780.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23259.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15992.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1228.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 96708.16 | 599780.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 599780.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 23259.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 13686.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 1228.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1906.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 106.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1974.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 424.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 432.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1257.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4233.65 | 1906.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 394.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 260.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 875.60 | 394.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 394.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 408.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 87.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 89.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 260.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 875.60 | 394.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
ZONE1 OFFICE DIRECT AIR | 1.58 |
ZONE2 FINE STORAGE DIRECT AIR | 6.91 |
Design Size Maximum Supply Air Flow Rate [m3/s] | |
ZONE3 BULK STORAGE UNIT HEATER | 27.46 |
Design Size Maximum Flow Rate [m3/s] | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | 27.46 |
Design Size Nominal Capacity [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | 357490.36 |
PSZ-OFFICE HEATING COIL | 25975.49 |
PSZ-FINE STORAGE HEATING COIL | 109165.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-OFFICE | 1.58 | 1.58 | 1.58 | 1.58 | 1.58 | 1.58 | 1.00 | 1.00 | 1.58 |
PSZ-FINE STORAGE | 6.91 | 6.91 | 6.91 | 6.91 | 6.91 | 6.91 | 1.00 | 1.00 | 6.91 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-OFFICE_OA_CONTROLLER | 1.58 | 0.102285 |
PSZ-FINE STORAGE_OA_CONTROLLER | 6.91 | 0.424711 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-OFFICE_ADDAQ SUPPLY FAN | 1.58 | 2626.94 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | 6.91 | 11059.77 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-OFFICE_UNITARY_PACKAGE_DX | 1.58 | 1.58 | 1.58 | 1.58 | 28517.09 | 25975.49 | 32.21 | 1.00 |
PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | 6.91 | 6.91 | 6.91 | 6.91 | 130436.47 | 109165.05 | 26.67 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-OFFICE COOLING COIL | 1.58 | 0.790295 | 1.05 | 28517.09 | 14258.55 | 0.800320 | 0.800320 |
PSZ-FINE STORAGE COOLING COIL | 6.91 | 3.46 | 4.61 | 130436.47 | 65218.24 | 0.800630 | 0.800630 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
OFFICE FRONT WALL | OFFICE FRONT DOOR | OFFICE FRONT WALL WINDOW 1 | OFFICE FRONT WALL WINDOW2 | |
OFFICE LEFT WALL | OFFICE LEFT WALL DOOR | OFFICE LEFT WALL WINDOW1 | OFFICE LEFT WALL WINDOW2 | |
FINE STORAGE FRONT WALL | FINE STORAGE OVERHEAD DOOR1 | |
FINE STORAGE RIGHT WALL | FINE STORAGE OVERHEAD DOOR2 | FINE STORAGE OVERHEAD DOOR3 | FINE STORAGE RIGHT DOOR | |
FINE STORAGE LEFT WALL | FINE STORAGE OVERHEAD DOOR4 | FINE STORAGE LEFT DOOR | |
FINE STORAGE OFFICE FRONT WALL | FINE STORAGE OFFICE FRONT WALL WINDOW | |
FINE STORAGE OFFICE LEFT WALL | FINE STORAGE OFFICE LEFT WALL WINDOW | |
BULK STORAGE RIGHT WALL | BULK STORAGE OVERHEAD DOOR8 | BULK STORAGE OVERHEAD DOOR9 | BULK STORAGE OVERHEAD DOOR10 | BULK STORAGE OVERHEAD DOOR11 | BULK STORAGE DOOR1 | BULK STORAGE DOOR2 | BULK STORAGE DOOR3 | |
BULK STORAGE REAR WALL | BULK STORAGE OVERHEAD DOOR12 | BULK STORAGE OVERHEAD DOOR13 | BULK STORAGE OVERHEAD DOOR14 | BULK STORAGE OVERHEAD DOOR15 | BULK STORAGE DOOR4 | |
BULK STORAGE LEFT WALL | BULK STORAGE OVERHEAD DOOR1 | BULK STORAGE OVERHEAD DOOR2 | BULK STORAGE OVERHEAD DOOR3 | BULK STORAGE OVERHEAD DOOR4 | BULK STORAGE OVERHEAD DOOR5 | BULK STORAGE OVERHEAD DOOR6 | BULK STORAGE OVERHEAD DOOR7 | BULK STORAGE DOOR5 | |
BULK STORAGE ROOF | SKYLIGHT_R1C1 | SKYLIGHT_R1C2 | SKYLIGHT_R1C3 | SKYLIGHT_R1C4 | SKYLIGHT_R1C5 | SKYLIGHT_R2C1 | SKYLIGHT_R2C2 | SKYLIGHT_R2C3 | SKYLIGHT_R2C4 | SKYLIGHT_R2C5 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | Warehouse | 90.000 | Urban | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.220 | 370.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 3 | 68 | 44 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | ZONE1 OFFICE | 0.0 | 0.00 | 0.00 | 0.00 | 4.57 | -12.95 | 2.13 | 1 | 1 | 1 | 0.00 | 9.14 | -25.91 | 5.60E-016 | 0.00 | 4.27 | 4.27 | 1010.76 | TARP | TARP | 236.88 | 149.56 | 117.24 | 28.42 | 6 | 6 | 0 | Yes |
2 | ZONE2 FINE STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 14.29 | -22.82 | 4.51 | 1 | 1 | 1 | 0.00 | 30.48 | -45.72 | 1.87E-015 | 0.00 | 8.53 | 7.81 | 2953.02 | TARP | TARP | 1393.41 | 760.80 | 605.78 | 121.40 | 11 | 8 | 0 | Yes |
3 | ZONE3 BULK STORAGE | 0.0 | 0.00 | 0.00 | 0.00 | 65.53 | -22.86 | 4.27 | 1 | 1 | 1 | 30.48 | 100.58 | -45.72 | 6.16E-015 | 0.00 | 8.53 | 8.53 | 35277.63 | TARP | TARP | 3204.84 | 1586.63 | 1471.35 | 14.86 | 6 | 30 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | ZONE1 OFFICE | 236.88 | 12.7 | 18.581 | 5.382E-002 | 10.719 | 8.074 | 0.000 | 0.000 | 0.000 | 0.000 | 18.792 | No |
2 | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 46.447 | 2.153E-002 | 15.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 15.069 | No |
3 | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 46.447 | 2.153E-002 | 9.688 | 2.559 | 0.000 | 0.000 | 0.000 | 0.000 | 12.246 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | OFFICE PEOPLE | BLDG_OCC_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 12.7 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | OFFICE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 13 |
2 | ZONE2 FINE STORAGEPEOPLE | BLDG_OCC_SCH | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 30.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE2 FINE STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 30 |
3 | ZONE3 BULK STORAGEPEOPLE | BLDG_OCC_SCH | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 69.0 | 2.153E-002 | 46.447 | 0.300 | 0.700 | AutoCalculate | ZONE3 BULK STORAGE ACTIVITY SCHEDULE | No | 3.8200E-008 | 0 | 69 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | OFFICE LIGHTS | LTG_SCH_OFFICE | ZONE1 OFFICE | 236.88 | 12.7 | 2539.013 | 10.719 | 199.158 | 0.000 | 0.370 | 0.180 | 0.450 | 1.000 | LightsWired | 0.000 | 2539.013 |
2 | FINE STORAGE AREA LIGHTS | LTG_SCH_FINE_STORAGE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 20997.932 | 15.069 | 699.931 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 20997.932 |
3 | BULK STORAGE AREA LIGHTS | LTG_SCH_BULK_STORAGE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 31046.942 | 9.688 | 449.956 | 0.000 | 0.420 | 0.180 | 0.400 | 1.000 | LightsWired | 0.000 | 31046.942 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | OFFICE PLUG LOAD | OFFICE_PLUG_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 1912.500 | 8.074 | 150.015 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 1912.500 |
2 | BULK STORAGE PLUG LOAD | BULK STORAGE PLUG SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 8200.120 | 2.559 | 118.842 | 0.000 | 0.000 | 0.000 | 1.000 | MiscPlug | 0.000 | 8200.120 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | NONRES_ROOF | 16 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
2 | SEMIHEATED_ROOF | 18 | 3 | 3 | 0.167 | 1.136 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | NONRES_EXT_WALL_GRD | 19 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | SEMIHEATED_EXT_WALL_GRD | 25 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | SWINGING DOOR_CON | 41 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | SWINGING DOOR_SEMI | 42 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | OVERHEAD DOOR_SEMI | 44 | 1 | 1 | 0.167 | 200.0 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
8 | OVERHEAD DOOR_CON | 45 | 1 | 1 | 0.167 | 4.938 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
9 | BULK STORAGE PRODUCTS | 46 | 1 | 18 | 0.500 | 0.5914 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
10 | INTERIOR WALL | 47 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | INSULATEDCEILING | 48 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | OFFICEFLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1926 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | FINESTORAGEFLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.7922E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BULKSTORAGEFLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.7415E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | iz-INTERIOR WALL | 52 | 5 | 5 | 2.167 | 0.7747 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
16 | iz-SEMIHEATED_EXT_WALL_GRD | 53 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
17 | iz-INSULATEDCEILING | 54 | 2 | 3 | 0.333 | 10.06 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
2 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
3 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
4 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
5 | SEMIHEATED_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8212 |
6 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
7 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
9 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
10 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
13 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
16 | OPAQUE DOOR PANEL_SEMI | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
17 | OVERHEAD DOOR_SEMI PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5000E-02 |
18 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2025 |
19 | BULK STORAGE PRODUCTS MATERIAL | 2.4384 | 1.442 | 200.231 | 836.800 | 1.691 |
20 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
21 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
22 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
23 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
26 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
27 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.116 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.55 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 13.41 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
34 | STEEL FRAME/CAVITY | 0.0889 | 0.084 | 641.379 | 502.080 | 1.057 |
35 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
36 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
37 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
38 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
39 | SEMIHEATED_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
40 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
41 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
42 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
43 | INTERIOR WALL ADDI INSUL | 0.0000 | 0.043 | 22.426 | 836.800 | 0.5871E-06 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
2 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
3 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
4 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
5 | 3 | -0.53954861E-06 | 0.47047397E-08 | -0.33276159E-05 | 0.24742089E-17 |
6 | 2 | 0.71895056 | 0.67549398E-02 | 0.98308090 | -0.63795361E-06 |
7 | 1 | -21.239987 | 0.46806363 | -6.4456230 | 0.18844773 |
8 | 0 | 21.442615 | 0.44675967 | 6.3841236 | |
9 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
10 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
11 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
12 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
13 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
14 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
15 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
16 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
17 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
18 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
19 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
20 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
21 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
22 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
23 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
24 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
25 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
26 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
27 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
28 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
29 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
30 | 0 | 200.00000 | 200.00000 | 200.00000 | |
31 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
32 | 0 | 4.9377744 | 4.9377744 | 4.9377744 | |
33 | 18 | 0.12003549E-12 | -0.36149852E-21 | 0.11999160E-12 | -0.69171859E-14 |
34 | 17 | -0.26702818E-10 | 0.22043783E-17 | -0.26702965E-10 | 0.15647703E-11 |
35 | 16 | 0.26199194E-08 | 0.46087291E-16 | 0.26199192E-08 | -0.15597178E-09 |
36 | 15 | -0.14918350E-06 | -0.27301975E-15 | -0.14918350E-06 | 0.90448703E-08 |
37 | 14 | 0.54929883E-05 | 0.10218664E-13 | 0.54929883E-05 | -0.34010628E-06 |
38 | 13 | -0.13812653E-03 | 0.13886261E-11 | -0.13812653E-03 | 0.87613853E-05 |
39 | 12 | 0.24466257E-02 | 0.76740851E-10 | 0.24466257E-02 | -0.15954016E-03 |
40 | 11 | -0.31099262E-01 | 0.20215154E-08 | -0.31099262E-01 | 0.20926433E-02 |
41 | 10 | 0.28694928 | 0.26940884E-07 | 0.28694928 | -0.20002833E-01 |
42 | 9 | -1.9353699 | 0.18750649E-06 | -1.9353699 | 0.14030665 |
43 | 8 | 9.5767226 | 0.68900696E-06 | 9.5767226 | -0.72468789 |
44 | 7 | -34.784653 | 0.13258951E-05 | -34.784653 | 2.7565275 |
45 | 6 | 92.438040 | 0.12976568E-05 | 92.438040 | -7.6923258 |
46 | 5 | -178.18614 | 0.60985027E-06 | -178.18614 | 15.604270 |
47 | 4 | 245.02895 | 0.12430126E-06 | 245.02895 | -22.615757 |
48 | 3 | -233.27712 | 0.91617964E-08 | -233.27712 | 22.714127 |
49 | 2 | 145.61910 | 0.16319500E-09 | 145.61910 | -14.964058 |
50 | 1 | -53.478849 | 0.26256209E-11 | -53.478849 | 5.7996512 |
51 | 0 | 8.7411694 | -0.39181092E-12 | 8.7411694 | |
52 | 5 | -0.68112304E-12 | 0.61645773E-13 | -0.20199983E-12 | 0.95058421E-15 |
53 | 4 | 0.71499529E-06 | 0.73238302E-07 | 0.28552134E-06 | -0.33479849E-12 |
54 | 3 | -0.58529659E-02 | 0.62218017E-03 | -0.21917430E-02 | 0.29169470E-06 |
55 | 2 | 1.2914758 | 0.88958368E-01 | 0.40042664 | -0.15953103E-02 |
56 | 1 | -8.6129398 | 0.38073474 | -3.1694576 | 0.22491773 |
57 | 0 | 7.9317533 | 0.13060792 | 3.3724149 | |
58 | 3 | -0.49407978E-15 | 0.44230608E-16 | -0.53860842E-16 | 0.0000000 |
59 | 2 | 0.54884850E-03 | 0.14309697E-03 | 0.26444340E-03 | -0.39739853E-15 |
60 | 1 | -3.9407614 | 2.0053241 | -3.6132068 | 0.31450573E-03 |
61 | 0 | 13.994357 | 8.0573072 | 13.672611 | |
62 | 7 | -0.21936956E-08 | -0.76657665E-15 | 0.52174295E-14 | -0.76362207E-16 |
63 | 6 | 0.54250385E-05 | 0.36865710E-08 | 0.31904099E-02 | -0.26763832E-04 |
64 | 5 | -0.38781740E-03 | 0.21819055E-05 | -0.22375527 | 0.19564212E-02 |
65 | 4 | 0.89061350E-02 | 0.99303795E-04 | 4.8300570 | -0.45269896E-01 |
66 | 3 | -0.78164548E-01 | 0.78949647E-03 | -38.024306 | 0.39868569 |
67 | 2 | 0.27748674 | 0.13132576E-02 | 116.48957 | -1.4180145 |
68 | 1 | -0.40047331 | 0.39992572E-03 | -143.91062 | 2.0490943 |
69 | 0 | 0.19524127 | 0.97244710E-05 | 60.838472 | |
70 | 7 | -0.53942680E-08 | -0.11156834E-13 | 0.16318657E-14 | -0.36257882E-16 |
71 | 6 | 0.25438785E-05 | 0.15223906E-08 | 0.31992327E-02 | -0.26837845E-04 |
72 | 5 | -0.16605865E-03 | 0.89659996E-06 | -0.22425660 | 0.19608463E-02 |
73 | 4 | 0.37075836E-02 | 0.40698259E-04 | 4.8384045 | -0.45350141E-01 |
74 | 3 | -0.32199378E-01 | 0.32283529E-03 | -38.071448 | 0.39920679 |
75 | 2 | 0.11382527 | 0.53586778E-03 | 116.58131 | -1.4192416 |
76 | 1 | -0.16395953 | 0.16275009E-03 | -143.96461 | 2.0499819 |
77 | 0 | 0.79856572E-01 | 0.39490086E-05 | 60.838472 | |
78 | 7 | -0.57660871E-08 | -0.13610624E-13 | 0.89936022E-15 | -0.28491615E-16 |
79 | 6 | 0.24333103E-05 | 0.14269892E-08 | 0.31996257E-02 | -0.26841142E-04 |
80 | 5 | -0.15663594E-03 | 0.83977476E-06 | -0.22427892 | 0.19610433E-02 |
81 | 4 | 0.34808858E-02 | 0.38103208E-04 | 4.8387759 | -0.45353710E-01 |
82 | 3 | -0.30176241E-01 | 0.30214868E-03 | -38.073544 | 0.39922996 |
83 | 2 | 0.10659492 | 0.50136596E-03 | 116.58539 | -1.4192962 |
84 | 1 | -0.15349297 | 0.15221123E-03 | -143.96701 | 2.0500213 |
85 | 0 | 0.74745977E-01 | 0.36906361E-05 | 60.838472 | |
86 | 5 | -0.20199983E-12 | 0.61645773E-13 | -0.68112304E-12 | 0.95058421E-15 |
87 | 4 | 0.28552134E-06 | 0.73238302E-07 | 0.71499529E-06 | -0.33479849E-12 |
88 | 3 | -0.21917430E-02 | 0.62218017E-03 | -0.58529659E-02 | 0.29169470E-06 |
89 | 2 | 0.40042664 | 0.88958368E-01 | 1.2914758 | -0.15953103E-02 |
90 | 1 | -3.1694576 | 0.38073474 | -8.6129398 | 0.22491773 |
91 | 0 | 3.3724149 | 0.13060792 | 7.9317533 | |
92 | 7 | -0.94456721E-13 | 0.24575595E-14 | -0.29735092E-12 | 0.15324278E-15 |
93 | 6 | 0.65405332E-08 | 0.22114619E-09 | 0.28546880E-07 | -0.13451374E-12 |
94 | 5 | -0.97466953E-04 | 0.18937623E-05 | -0.18947583E-03 | 0.64660656E-08 |
95 | 4 | 0.99417931E-01 | 0.92215111E-03 | 0.29140875 | -0.33466744E-04 |
96 | 3 | -2.3345767 | 0.28579858E-01 | -7.2517161 | 0.28937395E-01 |
97 | 2 | 15.247323 | 0.10163225 | 40.822959 | -0.33280368 |
98 | 1 | -29.125752 | 0.45869584E-01 | -80.508872 | 1.0778326 |
99 | 0 | 16.291614 | 0.92288667E-03 | 46.824339 | |
100 | 3 | -0.53860842E-16 | 0.44230608E-16 | -0.49407978E-15 | 0.0000000 |
101 | 2 | 0.26444340E-03 | 0.14309697E-03 | 0.54884850E-03 | -0.39739853E-15 |
102 | 1 | -3.6132068 | 2.0053241 | -3.9407614 | 0.31450573E-03 |
103 | 0 | 13.672611 | 8.0573072 | 13.994357 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.57_SHGC_SOUTH_0.39 | 34 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
2 | NONRESWINDOW_U_0.57_SHGC_NORTH_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
3 | NONRESWINDOW_U_0.57_SHGC_EAST_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
4 | NONRESWINDOW_U_0.57_SHGC_WEST_0.39 | 37 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
5 | SKYLIGHT_U_0.69_SHGC_0.49 | 38 | 1 | VerySmooth | 3.922 | 3.922 | 1.000 | 0.493 | ||
6 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | 39 | 1 | VerySmooth | 5.799 | 5.779 | 1.004 | 0.551 | ||
7 | SKYLIGHT DOUBLE CLEAR | 43 | 3 | VerySmooth | 3.715 | 3.715 | 1.000 | 0.720 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
5 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.36905 | 0.28585 | 0.28585 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 2.30798E-002 | 1.00000 | No | |
6 | SEMIHEATED SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.39618 | 8.78068E-002 | 8.78068E-002 | 0.55000 | 0.12964 | 0.15485 | 0.00000 | 0.84000 | 0.84000 | 0.30192 | 1.00000 | No | |
7 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No | |
8 | CLEAR 2.5MM | SpectralAverage | 2.50000E-003 | 0.80000 | 7.50000E-002 | 7.50000E-002 | 0.90100 | 8.10000E-002 | 8.10000E-002 | 0.00000 | 0.84000 | 0.84000 | 0.90000 | 1.00000 | No |
Material Name | GasType | Thickness {m} | |
1 | AIR 3MM | Air | 3.200E-003 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 7.5708E-002 | 6154.7 | 1.120 | 1.0564 |
Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | CurtainWall | 5.637 | 0.467 | 0.419 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | OFFICE INFILTRATION | OFFICE INFIL SCHEDULE | ZONE1 OFFICE | 236.88 | 12.7 | 8.518E-002 | 3.596E-004 | 5.551E-004 | 0.303 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | OFFICE DOOR INFILTRATION | INFIL_DOOR_OPENING_SCH | ZONE1 OFFICE | 236.88 | 12.7 | 0.177 | 7.451E-004 | 1.150E-003 | 0.629 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | FINE STORAGE INFILTRATION | FINE SORAGE INFIL SCHEDULE | ZONE2 FINE STORAGE | 1393.41 | 30.0 | 0.433 | 3.110E-004 | 1.981E-004 | 0.528 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | BULK STORAGE INFILTRATION | BULK STORAGE INFIL_BASE SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 2.331 | 7.274E-004 | 4.751E-004 | 0.238 | 0.000 | 0.000 | 0.224 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | BULK STORAGE VENTILATION-1 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 37.760 | 1.178E-002 | 0.547 | 3.853 | Exhaust | 31.136 | 0.5 | 1.000 | 0.000 | 0.000 | 0.000 | 29.44 | 100.00 | -100.00 | -100.00 | 100.00 | 40.00 |
2 | BULK STORAGE VENTILATION-2 | ALWAYS ON SCHEDULE | ZONE3 BULK STORAGE | 3204.84 | 69.0 | 0.944 | 2.945E-004 | 1.368E-002 | 9.632E-002 | Natural | 0.000 | 1.0 | 0.000 | 0.000 | 0.224 | 0.000 | -73.33 | 29.44 | -100.00 | -100.00 | 100.00 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | ZONE1 OFFICE | Mixing/Well-Stirred |
2 | ZONE2 FINE STORAGE | Mixing/Well-Stirred |
3 | ZONE3 BULK STORAGE | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2500 |
2 | Zone ZONE1 OFFICE | 1.2500 |
3 | Zone ZONE2 FINE STORAGE | 1.2500 |
4 | Zone ZONE3 BULK STORAGE | 1.2500 |
Sizing Factor ID | Value | |
1 | Global | 1.1500 |
2 | Zone ZONE1 OFFICE | 1.1500 |
3 | Zone ZONE2 FINE STORAGE | 1.1500 |
4 | Zone ZONE3 BULK STORAGE | 1.1500 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | ZONE1 OFFICE | Cooling | 12876.68002 | 14808.18202 | 0.98978 | 1.13825 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.71600 | 1.53623E-002 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
2 | ZONE1 OFFICE | Heating | 16610.93059 | 20763.66323 | 1.26447 | 1.58059 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20000 | 3.61342E-004 | 236.87965 | 12.74874 | 0.10228 | 0.00000 |
3 | ZONE2 FINE STORAGE | Cooling | 48019.75894 | 55222.72278 | 3.69163 | 4.24538 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 30.14000 | 1.53631E-002 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
4 | ZONE2 FINE STORAGE | Heating | 72013.90445 | 90017.38056 | 5.53179 | 6.91474 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -26.20000 | 3.61342E-004 | 1393.40969 | 30.00000 | 0.42471 | 0.00000 |
5 | ZONE3 BULK STORAGE | Cooling | 0.00000 | 0.00000 | 0.00000 | 0.97684 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53651E-002 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
6 | ZONE3 BULK STORAGE | Heating | 285992.29161 | 357490.36451 | 21.97124 | 27.46405 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 3204.84228 | 69.00000 | 0.97684 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-OFFICE | Cooling | Sensible | 15279.44 | 1.13825 | 1.13825 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-OFFICE | Heating | Sensible | 25975.49 | 1.58059 | 1.58059 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
3 | PSZ-FINE STORAGE | Cooling | Sensible | 56154.49 | 4.24538 | 4.24538 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-FINE STORAGE | Heating | Sensible | 109165.05 | 6.91474 | 6.91474 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE1 OFFICE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.58059 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONE2 FINE STORAGE DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.91474 |
3 | ZoneHVAC:UnitHeater | ZONE3 BULK STORAGE UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 27.46405 |
4 | Fan:ConstantVolume | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Design Size Maximum Flow Rate [m3/s] | 27.46405 |
5 | Coil:Heating:Fuel | ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Design Size Nominal Capacity [W] | 357490.36419 |
6 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.58059 |
7 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.58059 |
8 | AirLoopHVAC | PSZ-OFFICE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.58059 |
9 | AirLoopHVAC | PSZ-OFFICE | Adjusted Heating Design Air Flow Rate [m3/s] | 1.58059 |
10 | AirLoopHVAC | PSZ-OFFICE | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.58059 |
11 | AirLoopHVAC | PSZ-OFFICE | Adjusted Main Design Air Flow Rate [m3/s] | 1.58059 |
12 | AirLoopHVAC | PSZ-OFFICE | User Heating Air Flow Ratio [] | 1.00000 |
13 | AirLoopHVAC | PSZ-OFFICE | Calculated Heating Air Flow Ratio [] | 1.00000 |
14 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.91474 |
15 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.91474 |
16 | AirLoopHVAC | PSZ-FINE STORAGE | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.91474 |
17 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Heating Design Air Flow Rate [m3/s] | 6.91474 |
18 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.91474 |
19 | AirLoopHVAC | PSZ-FINE STORAGE | Adjusted Main Design Air Flow Rate [m3/s] | 6.91474 |
20 | AirLoopHVAC | PSZ-FINE STORAGE | User Heating Air Flow Ratio [] | 1.00000 |
21 | AirLoopHVAC | PSZ-FINE STORAGE | Calculated Heating Air Flow Ratio [] | 1.00000 |
22 | AirLoopHVAC | PSZ-OFFICE | Design Supply Air Flow Rate [m3/s] | 1.58059 |
23 | AirLoopHVAC | PSZ-FINE STORAGE | Design Supply Air Flow Rate [m3/s] | 6.91474 |
24 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.58059 |
25 | Controller:OutdoorAir | PSZ-OFFICE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.10228 |
26 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.58059 |
27 | Fan:SystemModel | PSZ-OFFICE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 2626.93713 |
28 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.58059 |
29 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.58059 |
30 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.58059 |
31 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.58059 |
32 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.58059 |
33 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.79030 |
34 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.05373 |
35 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28517.09000 |
36 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14258.54500 |
37 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80032 |
38 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80032 |
39 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28517.09000 |
40 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25975.48974 |
41 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.21000 |
42 | AirLoopHVAC:UnitarySystem | PSZ-OFFICE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
43 | Coil:Heating:Fuel | PSZ-OFFICE HEATING COIL | Design Size Nominal Capacity [W] | 25975.48974 |
44 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.91474 |
45 | Controller:OutdoorAir | PSZ-FINE STORAGE_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.42471 |
46 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 6.91474 |
47 | Fan:SystemModel | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Design Electric Power Consumption [W] | 11059.77165 |
48 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 6.91474 |
49 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 6.91474 |
50 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.91474 |
51 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 6.91474 |
52 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 6.91474 |
53 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 3.45737 |
54 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 4.60983 |
55 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 130436.47000 |
56 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 65218.23500 |
57 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80063 |
58 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80063 |
59 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 130436.47000 |
60 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 109165.05318 |
61 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 26.67000 |
62 | AirLoopHVAC:UnitarySystem | PSZ-FINE STORAGE_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
63 | Coil:Heating:Fuel | PSZ-FINE STORAGE HEATING COIL | Design Size Nominal Capacity [W] | 109165.05318 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-OFFICE COOLING COIL | 27290.2 | 10.85 | 10.60 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-FINE STORAGE COOLING COIL | 125068.3 | 10.93 | 10.69 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | ZONE1 OFFICE | RunPeriod: RUNPERIOD 1 | 0.3165398642 | 0.3136977563 | Pass | Pass | 1.3445501178 | 2.1871626987 | Pass | Pass |
2 | ZONE2 FINE STORAGE | RunPeriod: RUNPERIOD 1 | 0.7130150740 | 0.7223842806 | Pass | Pass | 0.8072232486 | 0.7815344454 | Pass | Pass |
3 | ZONE3 BULK STORAGE | RunPeriod: RUNPERIOD 1 | 2.9216174911E-009 | 1.5948227769E-008 | Pass | Pass | 1.6469495320E-002 | 1.4934170760E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7900.45 | 1139.27 | 0.00 | 119.69 | 683.38 | 9842.79 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 110.54 | 88.07 | 270.00 | 90.00 | W |
OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 39.02 | 29.17 | 0.00 | 90.00 | N |
OFFICE FLOOR | OFFICEFLOOR_FFACTOR | 1.00 | 0.187 | 0.193 | 236.88 | 236.88 | 90.00 | 180.00 | |
FINE STORAGE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 169.07 | 161.64 | 270.00 | 90.00 | W |
FINE STORAGE RIGHT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 260.10 | 243.29 | 180.00 | 90.00 | S |
FINE STORAGE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 182.07 | 172.69 | 0.00 | 90.00 | N |
FINE STORAGE OFFICE FRONT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 110.54 | 20.66 | 270.00 | 90.00 | W |
FINE STORAGE OFFICE LEFT WALL | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 39.02 | 7.50 | 0.00 | 90.00 | N |
FINE STORAGE FLOOR | FINESTORAGEFLOOR_FFACTOR | 1.00 | 0.078 | 0.079 | 1156.53 | 1156.53 | 90.00 | 180.00 | |
FINE STORAGE ROOF | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 1393.41 | 1393.41 | 90.00 | 0.00 | |
BULK STORAGE RIGHT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 598.24 | 568.60 | 180.00 | 90.00 | S |
BULK STORAGE REAR WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 390.15 | 358.48 | 90.00 | 90.00 | E |
BULK STORAGE LEFT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 598.24 | 544.27 | 0.00 | 90.00 | N |
BULK STORAGE FLOOR | BULKSTORAGEFLOOR_FFACTOR | 1.00 | 0.073 | 0.074 | 3204.84 | 3204.84 | 90.00 | 180.00 | |
BULK STORAGE ROOF | SEMIHEATED_ROOF | 0.30 | 0.982 | 1.136 | 3204.84 | 3183.04 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE RIGHT WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 180.00 | 90.00 | S |
OFFICE REAR WALL | INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 90.00 | 90.00 | E |
OFFICE ROOF | INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 90.00 | 0.00 | |
iz-OFFICE RIGHT WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 39.02 | 39.02 | 0.00 | 90.00 | N |
iz-OFFICE REAR WALL | iz-INTERIOR WALL | 0.30 | 0.653 | 0.775 | 110.54 | 110.54 | 270.00 | 90.00 | W |
iz-BULK STORAGE FRONT WALL | iz-SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.662 | 0.787 | 390.15 | 390.15 | 270.00 | 90.00 | W |
iz-OFFICE ROOF | iz-INSULATEDCEILING | 0.30 | 2.711 | 10.063 | 236.88 | 236.88 | 270.00 | 180.00 | |
BULK STORAGE FRONT WALL | SEMIHEATED_EXT_WALL_GRD | 0.30 | 0.662 | 0.787 | 390.15 | 390.15 | 90.00 | 90.00 | E |
BULK STORAGE PRODUCTS SURFACE | BULK STORAGE PRODUCTS | 0.30 | 0.591 | 6028.45 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
OFFICE FRONT WALL WINDOW 1 | NONRESWINDOW_U_0.57_SHGC_WEST_0.39 | 9.73 | 0.00 | 0.00 | 9.73 | 9.73 | 3.241 | 0.391 | 0.431 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE FRONT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_WEST_0.39 | 10.79 | 0.00 | 0.00 | 10.79 | 10.79 | 3.241 | 0.391 | 0.431 | No | OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
OFFICE LEFT WALL WINDOW1 | NONRESWINDOW_U_0.57_SHGC_NORTH_0.39 | 3.95 | 0.00 | 0.00 | 3.95 | 3.95 | 3.241 | 0.391 | 0.431 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
OFFICE LEFT WALL WINDOW2 | NONRESWINDOW_U_0.57_SHGC_NORTH_0.39 | 3.95 | 0.00 | 0.00 | 3.95 | 3.95 | 3.241 | 0.391 | 0.431 | No | OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
FINE STORAGE OFFICE FRONT WALL WINDOW | NONRESWINDOW_U_0.57_SHGC_WEST_0.39 | 89.88 | 0.00 | 0.00 | 89.88 | 89.88 | 3.241 | 0.391 | 0.431 | No | FINE STORAGE OFFICE FRONT WALL | 270.00 | 90.00 | W | |||||||
FINE STORAGE OFFICE LEFT WALL WINDOW | NONRESWINDOW_U_0.57_SHGC_NORTH_0.39 | 31.51 | 0.00 | 0.00 | 31.51 | 31.51 | 3.241 | 0.391 | 0.431 | No | FINE STORAGE OFFICE LEFT WALL | 0.00 | 90.00 | N | |||||||
SKYLIGHT_R1C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R1C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C1 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C2 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C3 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C4 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
SKYLIGHT_R2C5 | SEMIHTDSKYLIGHT_U_1.02_SHGC_0.55 | SKYLIGHT_FRAME_SEMIHEATED | 1.49 | 0.69 | 0.00 | 2.18 | 2.18 | 5.799 | 0.551 | 0.552 | 283.913 | 0.000 | CurtainWall | 5.637 | 0.467 | 0.419 | No | BULK STORAGE ROOF | 0.00 | 0.00 | |
Total or Average | 171.62 | 3.566 | 0.412 | 0.446 | |||||||||||||||||
North Total or Average | 39.41 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
Non-North Total or Average | 132.21 | 3.663 | 0.418 | 0.451 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
OFFICE FRONT DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | OFFICE FRONT WALL |
OFFICE LEFT WALL DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | OFFICE LEFT WALL |
FINE STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE FRONT WALL |
FINE STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE RIGHT WALL |
FINE STORAGE RIGHT DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | FINE STORAGE RIGHT WALL |
FINE STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_CON | 2.839 | 4.938 | 7.43 | FINE STORAGE LEFT WALL |
FINE STORAGE LEFT DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | FINE STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR8 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR9 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR10 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR11 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 5.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR1 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR2 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE DOOR3 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE RIGHT WALL |
BULK STORAGE OVERHEAD DOOR12 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR13 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR14 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR15 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE REAR WALL |
BULK STORAGE DOOR4 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE REAR WALL |
BULK STORAGE OVERHEAD DOOR1 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR2 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR3 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR4 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR5 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR6 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE OVERHEAD DOOR7 | OVERHEAD DOOR_SEMI | 6.464 | 200.000 | 7.43 | BULK STORAGE LEFT WALL |
BULK STORAGE DOOR5 | SWINGING DOOR_SEMI | 3.975 | 9.815 | 1.95 | BULK STORAGE LEFT WALL |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
OFFICE FRONT WALL WINDOW 1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE FRONT WALL WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
OFFICE LEFT WALL WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
OFFICE LEFT WALL WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FINE STORAGE OFFICE FRONT WALL WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
FINE STORAGE OFFICE LEFT WALL WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SKYLIGHT_R1C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R1C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SKYLIGHT_R2C5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
OFFICE LIGHTS | ZONE1 OFFICE | ZONE1 OFFICE | GENERAL | 10.7186 | 236.88 | 2539.01 | LightsWired | LTG_SCH_OFFICE | 65.78 | 168.00 | 64.76 | 0.0000 | Y | 30.86 |
FINE STORAGE AREA LIGHTS | ZONE2 FINE STORAGE | ZONE2 FINE STORAGE | GENERAL | 15.0695 | 1393.41 | 20997.93 | LightsWired | LTG_SCH_FINE_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 239.15 |
BULK STORAGE AREA LIGHTS | ZONE3 BULK STORAGE | ZONE3 BULK STORAGE | GENERAL | 9.6875 | 3204.84 | 31046.94 | LightsWired | LTG_SCH_BULK_STORAGE | 61.98 | 168.00 | 60.67 | 0.0000 | Y | 353.60 |
Interior Lighting Total | 11.2890 | 4835.13 | 54583.89 | 623.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 8532.22 | AstronomicalClock | - | 83.63 | 83.63 | 133.94 | |
Exterior Lighting Total | 8532.22 | 133.94 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28517.09 | 22822.80 | 5694.29 | 0.80 | 3.50 | |||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | 130436.47 | 104431.35 | 26005.12 | 0.80 | 3.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-OFFICE COOLING COIL | 27290.2 | 10.85 | 10.60 | ||||
PSZ-FINE STORAGE COOLING COIL | 125068.3 | 10.93 | 10.69 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | Coil:Heating:Fuel | 357490.36 | 0.79 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | 25975.49 | 0.80 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | 109165.05 | 0.79 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 0.54 | 340.63 | 27.46 | 17453.61 | 635.51 | 1.00 | 1.18 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.58 | 966.87 | 1.58 | 2626.94 | 1662.00 | 1.00 | 1.25 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 |
PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 0.60 | 966.87 | 6.91 | 11059.77 | 1599.45 | 1.00 | 1.17 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.08 | 6154.75 | 1.00 | 1.12 | 1.06 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 12876.68 | 14808.18 | 62.51 | 0.990 | 1.138 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.90 | 23.90 | 0.00868 | 29.72 | 0.01536 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 48019.76 | 55222.72 | 39.63 | 3.692 | 4.245 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 26.70 | 26.70 | 0.00900 | 30.14 | 0.01536 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.000 | 0.977 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 0.00 | 32.37 | 0.01543 | 31.20 | 0.01537 | 0.977 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
ZONE1 OFFICE | 16610.93 | 20763.66 | 87.65 | 1.264 | 1.581 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 21.10 | 21.10 | 0.00777 | -26.20 | 0.00036 | 0.102 | 0.00 |
ZONE2 FINE STORAGE | 72013.90 | 90017.38 | 64.60 | 5.532 | 6.915 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 15.56 | 15.56 | 0.00737 | -26.20 | 0.00036 | 0.425 | 0.00 |
ZONE3 BULK STORAGE | 285992.29 | 357490.36 | 111.55 | 21.971 | 27.464 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10.00 | 10.00 | 0.00710 | -26.20 | 0.00036 | 0.977 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-OFFICE | 1.14 | 1.14 | 1.58 | 1.58 | 1.5806 | 1.5806 | 1.5806 | 1.0000 | 1.0000 |
PSZ-FINE STORAGE | 4.25 | 4.25 | 6.91 | 6.91 | 6.9147 | 6.9147 | 6.9147 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | ZONE3 BULK STORAGE UNIT HEATER | 357490.364 | 357490.364 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 357490.36 | 357490.36 | 27.464049 | 10.00 | 9.03 | 0.00709614 | 21.11 | 14.43 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 10.00 | 0.00709614 | 88.7845 | 357490.36 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-OFFICE | 28517.090 | 22822.797 | 1.580590 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 14258.55 | 11670.42 | 1.053727 | 24.42 | 16.70 | 0.00928154 | 11.37 | 10.58 | 0.00800000 | 29.72 | 0.01536233 | 22.73 | 9.7069 | 23.90 | 0.00868116 | 44.8374 | 12876.68 | 0.00 | -999.00 | -999.00 |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-OFFICE | 25975.490 | 25975.490 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 25975.49 | 25975.49 | 1.580590 | 17.97 | 12.58 | 0.00729487 | 32.21 | 18.25 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 6.4713 | 21.10 | 0.00777460 | 47.6662 | 16610.93 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-FINE STORAGE | 130436.470 | 104431.351 | 6.914740 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 65218.24 | 52590.63 | 4.609827 | 27.05 | 17.87 | 0.00963770 | 14.23 | 11.76 | 0.00800000 | 30.28 | 0.01536338 | 22.88 | 9.2132 | 26.70 | 0.00900095 | 39.3406 | 48000.63 | 0.00 | -999.00 | -999.00 |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-FINE STORAGE | 109165.053 | 109165.053 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 109165.05 | 109165.05 | 6.914738 | 12.99 | 10.18 | 0.00694336 | 26.67 | 16.41 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 6.1421 | 15.56 | 0.00737409 | 64.0610 | 72013.90 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | ZONE3 BULK STORAGE UNIT HEATER | ZONE3 BULK STORAGE | N/A | N/A | N/A | Yes | No | unknown | No | 357490.364 | 357490.364 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ZONE3UNITHEATER ZONE3HIRADIANT FAN | Fan:ConstantVolume | 27.464049 | 31.54399361 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 357490.36 | 357490.36 | 1.0000 | 31.54399361 | 27.464049 | 10.00 | 9.03 | 0.00709614 | 27924.4 | 21.11 | 14.43 | 0.00800000 | 41534.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 357490.36 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 10.00 | 0.00709614 | 10.00 | 0.00709614 | 88.7845 | 357490.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28517.090 | 22822.797 | 1.580590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0939 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.580590 | 1.81539629 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | Sensible | 14258.55 | 11670.42 | 1.0000 | 1.21026390 | 1.053727 | 24.42 | 16.70 | 0.00928154 | 48171.9 | 11.37 | 10.58 | 0.00800000 | 31604.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14258.55 | 29.72 | 0.01536233 | 22.73 | 0.10228463 | 9.7069 | 23.90 | 0.00868116 | 23.90 | 0.00868116 | 44.8374 | 12876.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-OFFICE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-OFFICE | ZONE1 OFFICE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25975.490 | 25975.490 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-OFFICE_ADDAQ SUPPLY FAN | Fan:SystemModel | 1.580590 | 1.81539629 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | Sensible | 25975.49 | 25975.49 | 1.0000 | 1.81539629 | 1.580590 | 17.97 | 12.58 | 0.00729487 | 36545.4 | 32.21 | 18.25 | 0.00800000 | 52852.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25975.49 | -26.20 | 0.00036134 | -26.20 | 0.10228463 | 6.4713 | 21.03 | 0.00777460 | 21.10 | 0.00777460 | 47.6662 | 16610.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 130436.470 | 104431.351 | 6.914740 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.7560 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 6.914738 | 7.94196260 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | Sensible | 65218.24 | 52590.63 | 1.0000 | 5.29464328 | 4.609827 | 27.05 | 17.87 | 0.00963770 | 51773.1 | 14.23 | 11.76 | 0.00800000 | 34515.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 65218.24 | 30.28 | 0.01536338 | 22.88 | 0.42471127 | 9.2132 | 26.70 | 0.00900095 | 26.70 | 0.00900095 | 39.3406 | 48000.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-FINE STORAGE HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-FINE STORAGE | ZONE2 FINE STORAGE | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 109165.053 | 109165.053 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PSZ-FINE STORAGE_ADDAQ SUPPLY FAN | Fan:SystemModel | 6.914738 | 7.94196260 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 109165.05 | 109165.05 | 1.0000 | 7.94196260 | 6.914738 | 12.99 | 10.18 | 0.00694336 | 30586.6 | 26.67 | 16.41 | 0.00800000 | 47203.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 109165.05 | -26.20 | 0.00036134 | -26.20 | 0.42471127 | 6.1421 | 15.56 | 0.00737409 | 15.56 | 0.00737409 | 64.0610 | 72013.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-OFFICE_OA_CONTROLLER | FixedDryBulb | 0.10 | 1.58 | - | |||
PSZ-FINE STORAGE_OA_CONTROLLER | FixedDryBulb | 0.42 | 6.91 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
ZONE1 OFFICE | 2735.00 | 2563.83 | 1847.67 |
ZONE2 FINE STORAGE | 3178.00 | 3068.50 | 2666.50 |
ZONE3 BULK STORAGE | 3286.17 | 3407.67 | 3095.17 |
Facility | 3589.17 | 3440.17 | 3135.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
ZONE1 OFFICE | 329.00 | 5.83 | 74.17 | 5.33 |
ZONE2 FINE STORAGE | 536.67 | 60.50 | 29.33 | 0.00 |
ZONE3 BULK STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 805.83 | 66.33 | 91.33 | 5.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.784 | 0.366 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.42 | 30.00 | 2953.02 | 0.652 | 0.354 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.186 | 0.000 | 0.227 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
ZONE1 OFFICE | 9.53 | 12.75 | 1010.76 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE2 FINE STORAGE | 22.42 | 30.00 | 2953.02 | 0.000 | 0.000 | 0.000 | 0.000 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 9.53 | 12.75 | 1010.76 | 236.88 | 0.1023 | 0.102 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 22.42 | 30.00 | 2953.02 | 1393.41 | 0.4247 | 0.425 |
ZONE3 BULK STORAGE | 51.58 | 69.00 | 35277.63 | 3204.84 | 0.977 | ||
Total Facility | 83.53 | 111.75 | 39241.41 | 4835.13 | 0.5270 | 1.504 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
ZONE1 OFFICE | 2817353.77 | 0.00 | 2817353.77 | 2349425.27 | 5166779.04 | 3225648.14 | 5639.33 | 2319.56 | 801.12 | 0.00 |
ZONE2 FINE STORAGE | 6956149.89 | 0.00 | 6956149.89 | 9790874.37 | 16747024.26 | 13393694.68 | 5666.54 | 2585.65 | 507.80 | 11.79 |
ZONE3 BULK STORAGE | 0.00 | 46656400.78 | 46656400.78 | 48436561.36 | 95092962.14 | 30805497.77 | 6588.17 | 130.33 | 2041.50 | 5101.40 |
Total Facility | 9773503.66 | 46656400.78 | 56429904.44 | 60576861.00 | 0.12E+09 | 47424840.58 | 7757.62 | 2675.12 | 2750.07 | 5101.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
ZONE1 OFFICE | 0.2152 | 0.0000 | 0.2152 | 0.1012 | 0.3164 | 0.1023 | 515.33 | 2319.56 | 801.12 |
ZONE2 FINE STORAGE | 0.5241 | 0.0000 | 0.5241 | 0.2881 | 0.8123 | 0.4247 | 553.57 | 2585.65 | 496.78 |
ZONE3 BULK STORAGE | 0.0000 | 2.1562 | 2.1562 | 1.8313 | 3.9875 | 0.9768 | 2518.45 | 52.67 | 1064.88 |
Total Facility | 0.7394 | 2.1562 | 2.8955 | 2.2206 | 5.1161 | 1.5038 | 2633.62 | 2597.46 | 1762.67 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-OFFICE | 3716598.13 | 0.00 | 3716598.13 | 3225648.14 | 5638.36 | 0.00 | 3121.64 | 0.00 |
PSZ-FINE STORAGE | 9176417.22 | 0.00 | 9176417.22 | 13393694.68 | 5661.77 | 0.31 | 3097.93 | 11.79 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-OFFICE | 0.2839 | 0.0000 | 0.2839 | 0.1023 | 514.36 | 0.00 | 3121.64 |
PSZ-FINE STORAGE | 0.6914 | 0.0000 | 0.6914 | 0.4247 | 549.04 | 0.31 | 3086.65 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-OFFICE | 0.00 | 2528.45 | 597.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-FINE STORAGE | 0.00 | 2592.15 | 518.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-OFFICE | 0.0000 | 0.2517 | 0.6634 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-FINE STORAGE | 0.0000 | 0.5607 | 2.0721 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Surfaces by ClassTotal | Outdoors | |
Wall | 16 | 10 |
Floor | 4 | 3 |
Roof | 3 | 2 |
Internal Mass | 1 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 16 | 16 |
Door | 28 | 28 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 3 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 382 |
Defaulted Fields | 322 |
Fields with Defaults | 1019 |
Autosized Fields | 42 |
Autosizable Fields | 96 |
Autocalculated Fields | 94 |
Autocalculatable Fields | 138 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1336.80 | 6131.39 | 11-JUN-08:30 | 96708.16 | 04-AUG-15:00 |
Electricity:Building | 761.64 | 6131.39 | 01-JAN-00:10 | 58533.65 | 31-MAY-13:50 |
Electricity:Zone:ZONE1 OFFICE | 60.03 | 926.90 | 01-JAN-00:10 | 3790.09 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 760.12 | 6131.39 | 01-JAN-00:10 | 56228.36 | 02-JAN-09:10 |
InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE1 OFFICE | 30.86 | 457.02 | 01-JAN-00:10 | 1955.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 623.61 | 5661.51 | 01-JAN-00:10 | 46193.18 | 02-JAN-09:10 |
Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE2 FINE STORAGE | 239.15 | 2099.79 | 01-JAN-00:10 | 17848.24 | 02-JAN-09:10 |
Electricity:Zone:ZONE3 BULK STORAGE | 462.46 | 3104.69 | 01-JAN-00:10 | 36895.31 | 31-MAY-13:50 |
InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
LightsWired:InteriorLights:Electricity:Zone:ZONE3 BULK STORAGE | 353.60 | 3104.69 | 01-JAN-00:10 | 26389.90 | 02-JAN-09:10 |
InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE1 OFFICE | 29.16 | 469.88 | 01-JAN-00:10 | 1835.05 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 136.51 | 469.88 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:ZONE3 BULK STORAGE | 107.34 | 0.00 | 01-JAN-00:10 | 8200.12 | 02-JAN-08:10 |
Fans:Electricity | 397.19 | 0.00 | 20-FEB-14:00 | 31140.32 | 02-JAN-08:50 |
Fans:Electricity:Zone:ZONE3 BULK STORAGE | 1.52 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-JUN-15:40 |
Ventilation (simple):Fans:Electricity | 1.52 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-JUN-15:40 |
Ventilation (simple):Fans:Electricity:Zone:ZONE3 BULK STORAGE | 1.52 | 0.00 | 01-JAN-00:10 | 2305.29 | 11-JUN-15:40 |
ElectricityPurchased:Facility | 1336.80 | 6131.39 | 11-JUN-08:30 | 96708.16 | 04-AUG-15:00 |
ElectricityPurchased:Plant | 1336.80 | 6131.39 | 11-JUN-08:30 | 96708.16 | 04-AUG-15:00 |
Cogeneration:ElectricityPurchased | 1336.80 | 6131.39 | 11-JUN-08:30 | 96708.16 | 04-AUG-15:00 |
General:Cogeneration:ElectricityPurchased | 1336.80 | 6131.39 | 11-JUN-08:30 | 96708.16 | 04-AUG-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1336.80 | 6131.39 | 11-JUN-08:30 | 96708.16 | 04-AUG-15:00 |
ElectricityNet:Plant | 1336.80 | 6131.39 | 11-JUN-08:30 | 96708.16 | 04-AUG-15:00 |
Cogeneration:ElectricityNet | 1336.80 | 6131.39 | 11-JUN-08:30 | 96708.16 | 04-AUG-15:00 |
General:Cogeneration:ElectricityNet | 1336.80 | 6131.39 | 11-JUN-08:30 | 96708.16 | 04-AUG-15:00 |
Electricity:HVAC | 429.40 | 0.00 | 20-FEB-14:00 | 37855.80 | 04-AUG-15:50 |
General:Fans:Electricity | 395.67 | 0.00 | 20-FEB-14:00 | 31140.32 | 02-JAN-08:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 33.72 | 0.00 | 01-JAN-00:10 | 24169.09 | 04-AUG-15:50 |
General:Cooling:Electricity | 33.72 | 0.00 | 01-JAN-00:10 | 24169.09 | 04-AUG-15:50 |
ExteriorLights:Electricity | 133.94 | 0.00 | 01-JAN-08:00 | 8532.22 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 133.94 | 0.00 | 01-JAN-08:00 | 8532.22 | 01-JAN-00:10 |
Electricity:Plant | 11.83 | 0.00 | 02-JAN-00:20 | 1796.78 | 21-FEB-12:40 |
WaterSystems:Electricity | 11.83 | 0.00 | 02-JAN-00:20 | 1796.78 | 21-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 11.83 | 0.00 | 02-JAN-00:20 | 1796.78 | 21-FEB-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1758.67 | 4750.00 | 03-JUL-05:10 | 599780.99 | 09-DEC-09:00 |
NaturalGas:HVAC | 1758.67 | 4750.00 | 03-JUL-05:10 | 599780.99 | 09-DEC-09:00 |
Heating:NaturalGas | 1758.67 | 4750.00 | 03-JUL-05:10 | 599780.99 | 09-DEC-09:00 |
General:Heating:NaturalGas | 1758.67 | 4750.00 | 03-JUL-05:10 | 599780.99 | 09-DEC-09:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUN-11:10 |
Water:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUN-11:10 |
WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUN-11:10 |
Water Heater:WaterSystems:Water | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUN-11:10 |
MainsWater:Facility | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUN-11:10 |
MainsWater:Plant | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUN-11:10 |
WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUN-11:10 |
Water Heater:WaterSystems:MainsWater | 51.61 | 0.00 | 02-JAN-00:10 | 0.00 | 20-JUN-11:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2970.19 | 0.00 | 20-FEB-14:00 | 953952.07 | 09-DEC-09:00 |
EnergyTransfer:Building | 1587.74 | 0.00 | 20-FEB-14:00 | 482032.16 | 09-DEC-09:00 |
EnergyTransfer:Zone:ZONE1 OFFICE | 89.64 | 0.00 | 01-JAN-00:40 | 29321.87 | 19-JAN-07:10 |
Heating:EnergyTransfer | 1494.22 | 0.00 | 20-FEB-14:00 | 482032.16 | 09-DEC-09:00 |
Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 63.77 | 0.00 | 01-JAN-00:40 | 29321.87 | 19-JAN-07:10 |
General:Heating:EnergyTransfer | 1494.22 | 0.00 | 20-FEB-14:00 | 482032.16 | 09-DEC-09:00 |
General:Heating:EnergyTransfer:Zone:ZONE1 OFFICE | 63.77 | 0.00 | 01-JAN-00:40 | 29321.87 | 19-JAN-07:10 |
Cooling:EnergyTransfer | 93.53 | 0.00 | 01-JAN-00:10 | 53130.24 | 04-AUG-15:30 |
Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 25.87 | 0.00 | 01-JAN-00:10 | 11453.77 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer | 93.53 | 0.00 | 01-JAN-00:10 | 53130.24 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:ZONE1 OFFICE | 25.87 | 0.00 | 01-JAN-00:10 | 11453.77 | 04-AUG-15:30 |
EnergyTransfer:Zone:ZONE2 FINE STORAGE | 333.42 | 0.00 | 01-JAN-00:40 | 101462.33 | 09-DEC-06:50 |
Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 265.76 | 0.00 | 01-JAN-00:40 | 101462.33 | 09-DEC-06:50 |
General:Heating:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 265.76 | 0.00 | 01-JAN-00:40 | 101462.33 | 09-DEC-06:50 |
Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 67.66 | 0.00 | 01-JAN-00:10 | 44803.61 | 10-AUG-19:50 |
General:Cooling:EnergyTransfer:Zone:ZONE2 FINE STORAGE | 67.66 | 0.00 | 01-JAN-00:10 | 44803.61 | 10-AUG-19:50 |
EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1164.68 | 0.00 | 11-JAN-11:10 | 377918.60 | 09-DEC-09:00 |
Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1164.68 | 0.00 | 11-JAN-11:10 | 377918.60 | 09-DEC-09:00 |
General:Heating:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 1164.68 | 0.00 | 11-JAN-11:10 | 377918.60 | 09-DEC-09:00 |
Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ZONE3 BULK STORAGE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:HVAC | 1382.45 | 0.00 | 20-FEB-14:00 | 471919.91 | 09-DEC-09:00 |
HeatingCoils:EnergyTransfer | 1245.73 | 0.00 | 20-FEB-14:00 | 471919.91 | 09-DEC-09:00 |
CoolingCoils:EnergyTransfer | 136.72 | 0.00 | 01-JAN-00:10 | 91222.49 | 04-AUG-15:50 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
ZONE1 OFFICE | 0.000 | 0.000 | 63.774 | -25.869 | 0.000 | 0.000 | 9.943 | 30.864 | 29.165 | 17.065 | 0.000 | 0.519 | 0.000 | 0.000 | -25.599 | 0.000 | -43.231 | -56.631 |
ZONE2 FINE STORAGE | 0.000 | 0.000 | 265.758 | -67.656 | 0.000 | 0.000 | 24.428 | 239.148 | 0.000 | 72.592 | 0.000 | 0.718 | 0.002 | 0.000 | -95.683 | 0.000 | -166.020 | -273.285 |
ZONE3 BULK STORAGE | 1164.683 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 64.417 | 353.598 | 107.344 | 29.786 | 0.000 | 6.788 | 0.000 | 0.000 | -21.471 | 0.000 | -911.606 | -793.540 |
Total Facility | 1164.683 | 0.000 | 329.532 | -93.525 | 0.000 | 0.000 | 98.788 | 623.610 | 136.508 | 119.443 | 0.000 | 8.025 | 0.003 | 0.000 | -142.753 | 0.000 | -1120.857 | -1123.455 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 19-JUL-05:02 | 0.00 | 0.00 | 0.00 | -29109.62 | 0.00 | 0.00 | 88.92 | 583.97 | 550.52 | 0.00 | 0.00 | 0.00 | 29364.46 | 0.00 | -737.41 | 0.00 | -740.85 | 0.00 |
ZONE2 FINE STORAGE | 06-AUG-17:01 | 0.00 | 0.00 | 0.00 | -147707.74 | 0.00 | 0.00 | 0.00 | 2099.79 | 0.00 | 10122.81 | 0.00 | 0.00 | 138567.42 | 0.00 | -0.00 | 0.00 | -3082.29 | 0.00 |
ZONE3 BULK STORAGE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 06-AUG-17:01 | 0.00 | 0.00 | 0.00 | -147707.74 | 0.00 | 0.00 | 0.00 | 5661.51 | 469.88 | 13506.07 | 0.00 | 0.00 | 154601.33 | 0.00 | 0.00 | 0.00 | -26531.05 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
ZONE1 OFFICE | 27-JAN-06:31 | 0.00 | 0.00 | 31846.24 | 0.00 | 0.00 | 0.00 | 151.35 | 583.97 | 550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2550.86 | 0.00 | -5789.74 | -24791.48 |
ZONE2 FINE STORAGE | 09-DEC-06:41 | 0.00 | 0.00 | 133304.81 | 0.00 | 0.00 | 0.00 | 406.31 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -10520.70 | 0.00 | -33726.98 | -91563.24 |
ZONE3 BULK STORAGE | 09-DEC-09:00 | 377920.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8324.93 | 23285.21 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2462.87 | 0.00 | -299878.15 | -115389.60 |
Total Facility | 09-DEC-01:32 | 364826.46 | 0.00 | 144557.71 | 0.00 | 0.00 | 0.00 | 0.00 | 5661.51 | 2519.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16891.49 | 0.00 | -304100.93 | -196573.16 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5806 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.5806 | 0.0899 | 1.0000 | Not calculated | 0.1023 | 0.0647 | ||
PSZ-FINE STORAGE | 6.9147 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 6.9147 | 0.1000 | 1.0000 | Not calculated | 0.4247 | 0.0614 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-OFFICE | 1.5806 | 0.0000 | 12.7487 | 1.0000 | Calculated from schedules | 0.1023 | 1.5806 | 1.0000 | 1.0000 | Not calculated | 0.1023 | 0.0647 | ||
PSZ-FINE STORAGE | 6.9147 | 0.0000 | 30.0000 | 1.0000 | Calculated from schedules | 0.4247 | 6.9147 | 1.0000 | 1.0000 | Not calculated | 0.4247 | 0.0614 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
ZONE1 OFFICE | PSZ-OFFICE | 0.000000 | 12.7487 | 0.000432 | 236.88 | 0.1023 | 1.0000 | 0.1023 | 1.000 | 0.1023 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | 0.000000 | 30.0000 | 0.000305 | 1393.41 | 0.4247 | 1.0000 | 0.4247 | 1.000 | 0.4247 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-OFFICE | 0.000000 | 12.75 | 0.000432 | 236.8796 | 0.1023 | 0.1023 | 0.1023 |
PSZ-FINE STORAGE | 0.000000 | 30.00 | 0.000305 | 1393.4097 | 0.4247 | 0.4247 | 0.4247 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5806 | 1.5806 | 1.5806 | No | 0.1023 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.9147 | 6.9147 | 6.9147 | No | 0.4247 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5806 | 1.5806 | 1.5806 | 1.5806 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 6.9147 | 6.9147 | 6.9147 | 6.9147 | 0.4247 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
ZONE1 OFFICE | PSZ-OFFICE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5806 | 1.5806 | 1.5806 | No | 0.1023 | 0.0647 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ZONE2 FINE STORAGE | PSZ-FINE STORAGE | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.9147 | 6.9147 | 6.9147 | No | 0.4247 | 0.0614 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-OFFICE | 1.5806 | 1.5806 | 1.5806 | 1.5806 | 0.1023 | 1.0000 |
PSZ-FINE STORAGE | 6.9147 | 6.9147 | 6.9147 | 6.9147 | 0.4247 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4835.13 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
ZONE1 OFFICE | 236.88 | 236.88 | 0.00 | 69.73 |
ZONE2 FINE STORAGE | 1393.41 | 1393.41 | 0.00 | 69.73 |
ZONE3 BULK STORAGE | 3204.84 | 3204.84 | 0.00 | 69.73 |
Totals | 4835.13 | 4835.13 | 0.00 |
Data | |
Number of hours heating loads not met | 91.33 |
Number of hours cooling loads not met | 5.33 |
Number of hours not met | 96.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1758.67 | 599780.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 33.72 | 24169.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 623.61 | 46193.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 133.94 | 8532.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 136.51 | 10035.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 1.52 | 2305.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 395.67 | 31140.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 11.83 | 1796.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 136.51 | 1336.80 |
Natural Gas | 0.00 | 1758.67 |
Additional | 0.00 | 0.00 |
Total | 136.51 | 3095.47 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 128.97 |
Space Heating | 0.00 |
Space Cooling | 6.97 |
Fans (All) | 82.15 |
Service Water Heating | 2.45 |
Receptacle Equipment | 28.23 |
Miscellaneous (All) | 276.48 |
Subtotal | 276.48 |
Natural Gas [MJ/m2] | |
Space Heating | 363.73 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 363.73 |
Subtotal | 363.73 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 20.15 |
Space Heating | 56.81 |
Space Cooling | 1.09 |
Fans (All) | 12.83 |
Service Water Heating | 0.38 |
Receptacle Equipment | 4.41 |
Miscellaneous | 4.33 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
LTG_SCH_OFFICE | 3430. | 8760. |
LTG_SCH_BULK_STORAGE | 3232. | 8760. |
LTG_SCH_FINE_STORAGE | 3232. | 8760. |
OFFICE_PLUG_SCH | 4298. | 8760. |
BULK STORAGE PLUG SCHEDULE | 3744. | 7488. |
BLDG_OCC_SCH | 2861. | 3744. |
OFFICE PEOPLE SCHEDULE | 2861. | 3744. |
FANSCHED | 3432. | 3432. |
MINOA_MOTORIZEDDAMPER_SCHED | 3120. | 3120. |
OFFICE DHW SCHEDULE | 1825. | 5016. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 5550. | 8760. |
EXTERIOR LIGHT SCHEDULE | 5475. | 5475. |
ALWAYS OFF SCHEDULE | 0. | 0. |
OA DAMPER OFF DURING OFF HRS SCHEDULE | 2808. | 2808. |
OA DAMPER ALWAYS ON SCHEDULE | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
ALWAYS ON SCHEDULE | 8760. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
INFIL_DOOR_OPENING_SCH | 1121. | 3380. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 2600. | 2600. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6935. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
BULK STORAGE HEATING SETPOINT SCHEDULE | ZONE3 BULK STORAGE HEATING SP | January | 10.00 | 365 | 10.00 | 365 |
OFFICE HEATING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | January | 21.10 | 365 | 15.60 | 365 |
OFFICE COOLING SCHEDULE | ZONE1 OFFICE DUAL SP CONTROL | July | 23.90 | 365 | 29.40 | 365 |
FINE STORAGE HEATING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
FINE STORAGE COOLING SETPOINT SCHEDULE | ZONE2 FINE STORAGE DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 7982.83 | 777.17 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 7407.33 | 1352.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 7474.83 | 1218.00 | 65.17 | 2.00 | 0.00 |
Min | 7407.33 | 777.17 | 0.00 | 0.00 | 0.00 |
Max | 7982.83 | 1352.67 | 65.17 | 2.00 | 0.00 |
Average | 7621.67 | 1115.94 | 21.72 | 0.67 | 0.00 |
Sum | 22865.00 | 3347.83 | 65.17 | 2.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
ZONE1 OFFICE | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 62486.50 | 20232.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 151039.67 | 37621.50 | 2401.67 | 130.17 | 0.00 |
Min | 33027.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 151039.67 | 37621.50 | 2401.67 | 130.17 | 0.00 |
Average | 82184.39 | 19284.67 | 800.56 | 43.39 | 0.00 |
Sum | 246553.17 | 57854.00 | 2401.67 | 130.17 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 7626.17 | 1133.83 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 6837.33 | 1922.67 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 6971.50 | 1760.50 | 28.00 | 0.00 | 0.00 |
Min | 6837.33 | 1133.83 | 0.00 | 0.00 | 0.00 |
Max | 7626.17 | 1922.67 | 28.00 | 0.00 | 0.00 |
Average | 7145.00 | 1605.67 | 9.33 | 0.00 | 0.00 |
Sum | 21435.00 | 4817.00 | 28.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
ZONE1 OFFICE | 32535.33 | 491.67 | 0.00 | 0.00 | 0.00 |
ZONE2 FINE STORAGE | 59744.50 | 22974.50 | 0.00 | 0.00 | 0.00 |
ZONE3 BULK STORAGE | 144176.67 | 45844.83 | 1171.50 | 0.00 | 0.00 |
Min | 32535.33 | 491.67 | 0.00 | 0.00 | 0.00 |
Max | 144176.67 | 45844.83 | 1171.50 | 0.00 | 0.00 |
Average | 78818.83 | 23103.67 | 390.50 | 0.00 | 0.00 |
Sum | 236456.50 | 69311.00 | 1171.50 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:19:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME WAREHOUSE
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -2.8 | -3.2 | 0.496479E+09 | 603.25 | 12-JAN-16:30 | 2.25 | 0.82 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.458167E+09 | 697.36 | 24-FEB-16:10 | 8.12 | 5.76 |
March | 516753.76 | 444.34 | 25-MAR-15:00 | 18.90 | 10.43 | 0.547941E+09 | 768.97 | 28-MAR-15:39 | 16.13 | 10.43 |
April | 0.546462E+09 | 7391.08 | 18-APR-15:10 | 27.75 | 20.46 | 0.544898E+09 | 769.02 | 18-APR-12:30 | 27.75 | 20.46 |
May | 0.216941E+10 | 8651.38 | 31-MAY-16:00 | 28.30 | 18.78 | 0.644512E+09 | 769.03 | 12-MAY-14:09 | 28.30 | 18.78 |
June | 0.538953E+10 | 28501.65 | 19-JUN-05:03 | 11.78 | 10.73 | 0.658201E+09 | 769.04 | 12-JUN-08:20 | 11.78 | 10.73 |
July | 0.673458E+10 | 29120.15 | 19-JUL-05:02 | 12.48 | 11.50 | 0.634770E+09 | 769.04 | 08-JUL-12:30 | 12.48 | 11.50 |
August | 0.688092E+10 | 27817.43 | 10-AUG-05:03 | 12.38 | 11.41 | 0.685602E+09 | 769.04 | 12-AUG-15:00 | 20.60 | 18.08 |
September | 0.387474E+10 | 28589.66 | 08-SEP-05:01 | 14.32 | 13.31 | 0.624933E+09 | 769.03 | 09-SEP-08:39 | 21.30 | 16.89 |
October | 0.214667E+09 | 3419.58 | 20-OCT-15:30 | 22.30 | 13.06 | 0.569668E+09 | 768.98 | 21-OCT-15:09 | 20.67 | 14.27 |
November | 58932112.73 | 2504.01 | 04-NOV-15:00 | 14.40 | 6.81 | 0.508044E+09 | 768.97 | 06-NOV-16:40 | 11.30 | 9.94 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.3 | 0.496993E+09 | 653.37 | 02-DEC-16:10 | 4.95 | 2.78 |
Annual Sum or Average | 0.258698E+11 | 0.687021E+10 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.458167E+09 | 603.25 | 2.25 | 0.82 | ||
Maximum of Months | 0.688092E+10 | 29120.15 | 28.30 | 20.46 | 0.685602E+09 | 769.04 | 28.30 | 20.46 |
Report: ZoneCoolingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61759.39 | 83.57 | 02-JAN-15:00 | -8.3 | -9.7 | 0.658002E+09 | 1099.04 | 13-JAN-15:20 | 3.90 | 1.79 |
February | 3437192.91 | 612.57 | 17-FEB-15:30 | -6.7 | -8.6 | 0.639351E+09 | 1387.90 | 24-FEB-16:10 | 8.12 | 5.76 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -12.0 | 0.877084E+09 | 1788.90 | 25-MAR-15:09 | 18.72 | 10.45 |
April | 0.892990E+09 | 146598.35 | 17-APR-17:11 | 19.03 | 11.52 | 0.113975E+10 | 2246.99 | 18-APR-15:20 | 27.20 | 20.26 |
May | 0.220399E+10 | 63811.37 | 31-MAY-17:06 | 28.62 | 19.71 | 0.173633E+10 | 2246.97 | 30-MAY-14:30 | 28.62 | 19.71 |
June | 0.162939E+11 | 139848.88 | 22-JUN-17:41 | 20.60 | 13.29 | 0.187758E+10 | 2247.02 | 13-JUN-14:50 | 20.60 | 13.29 |
July | 0.213424E+11 | 133624.65 | 22-JUL-19:11 | 18.33 | 13.76 | 0.185011E+10 | 2247.03 | 26-JUL-13:50 | 29.22 | 24.74 |
August | 0.184491E+11 | 147709.89 | 06-AUG-17:01 | 19.03 | 11.91 | 0.199502E+10 | 2247.03 | 03-AUG-14:30 | 19.03 | 11.91 |
September | 0.846468E+10 | 138176.76 | 15-SEP-17:41 | 20.87 | 12.57 | 0.168169E+10 | 2246.98 | 11-SEP-12:09 | 20.87 | 12.57 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.39 | 0.116422E+10 | 2215.37 | 20-OCT-15:09 | 22.97 | 13.26 |
November | 654507.22 | 143.66 | 21-NOV-13:50 | -6.1 | -7.9 | 0.855829E+09 | 2005.39 | 03-NOV-15:09 | -6.1 | -7.9 |
December | 7007890.68 | 901.20 | 15-DEC-14:00 | -7.8 | -9.4 | 0.662739E+09 | 1165.68 | 02-DEC-16:10 | -7.8 | -9.4 |
Annual Sum or Average | 0.676582E+11 | 0.151377E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -11.0 | -12.0 | 0.639351E+09 | 1099.04 | -7.8 | -9.4 | ||
Maximum of Months | 0.213424E+11 | 147709.89 | 28.62 | 19.71 | 0.199502E+10 | 2247.03 | 29.22 | 24.74 |
Report: ZoneCoolingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -2.8 | -3.2 | 0.645611E+09 | 880.50 | 13-JAN-15:09 | 3.90 | 1.75 |
February | 0.00 | 0.00 | 01-FEB-00:02 | -24.1 | -24.4 | 0.608960E+09 | 1279.46 | 24-FEB-15:30 | 8.30 | 5.75 |
March | 0.00 | 0.00 | 01-MAR-00:02 | -11.0 | -12.0 | 0.850981E+09 | 2076.77 | 25-MAR-15:30 | 18.35 | 10.46 |
April | 0.00 | 0.00 | 01-APR-00:03 | -1.2 | -2.2 | 0.140974E+10 | 5240.73 | 18-APR-15:09 | 27.75 | 20.46 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.15 | 0.276008E+10 | 6415.45 | 31-MAY-15:09 | 29.72 | 19.55 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.69 | 0.436425E+10 | 7452.91 | 26-JUN-14:20 | 31.50 | 22.02 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 | 15.94 | 0.475248E+10 | 6905.99 | 03-JUL-15:20 | 29.63 | 24.33 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 | 0.500028E+10 | 8312.28 | 04-AUG-15:30 | 33.90 | 25.83 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 | 0.344136E+10 | 7320.93 | 07-SEP-14:20 | 32.03 | 18.44 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.39 | 0.125809E+10 | 2574.55 | 20-OCT-15:20 | 22.63 | 13.16 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.5 | 0.845431E+09 | 2199.23 | 03-NOV-14:50 | 16.10 | 9.74 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 | -1.3 | 0.646057E+09 | 944.01 | 02-DEC-15:50 | 5.68 | 3.15 |
Annual Sum or Average | 0.00 | 0.265833E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -24.1 | -24.4 | 0.608960E+09 | 880.50 | 3.90 | 1.75 | ||
Maximum of Months | 0.00 | 0.00 | 18.93 | 17.82 | 0.500028E+10 | 8312.28 | 33.90 | 25.83 |
Report: ZoneHeatingSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169958E+11 | 31845.87 | 27-JAN-06:31 | -17.9 |
February | 0.119590E+11 | 31811.94 | 01-FEB-06:31 | -31.5 |
March | 0.839656E+10 | 29905.78 | 06-MAR-06:22 | -13.6 |
April | 0.342840E+10 | 27997.27 | 03-APR-05:12 | -7.2 |
May | 0.588178E+09 | 27478.57 | 02-MAY-05:12 | 2.20 |
June | 0.115394E+09 | 23300.31 | 05-JUN-05:02 | 9.32 |
July | 10071303.13 | 2892.23 | 24-JUL-06:07 | 12.35 |
August | 20807145.66 | 2830.82 | 24-AUG-06:07 | 13.17 |
September | 0.374906E+09 | 27276.53 | 29-SEP-05:01 | 0.92 |
October | 0.198293E+10 | 27487.06 | 16-OCT-05:12 | 0.27 |
November | 0.714407E+10 | 28219.17 | 24-NOV-06:31 | -13.7 |
December | 0.127575E+11 | 31289.85 | 12-DEC-06:31 | -19.6 |
Annual Sum or Average | 0.637736E+11 | |||
Minimum of Months | 10071303.13 | 2830.82 | -31.5 | |
Maximum of Months | 0.169958E+11 | 31845.87 | 13.17 |
Report: ZoneHeatingSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.732703E+11 | 129979.59 | 27-JAN-06:01 | -17.4 |
February | 0.495195E+11 | 129330.30 | 01-FEB-06:01 | -31.2 |
March | 0.286625E+11 | 112635.93 | 08-MAR-06:01 | -13.0 |
April | 0.104670E+11 | 112499.63 | 06-APR-05:01 | -5.9 |
May | 0.338339E+10 | 33822.90 | 02-MAY-05:32 | 2.20 |
June | 0.101116E+10 | 10893.36 | 03-JUN-06:25 | 6.95 |
July | 0.203443E+09 | 10467.03 | 12-JUL-06:25 | 14.75 |
August | 0.422212E+09 | 10657.84 | 07-AUG-06:25 | 10.00 |
September | 0.221578E+10 | 23667.58 | 30-SEP-05:32 | 0.40 |
October | 0.730013E+10 | 90794.68 | 17-OCT-05:01 | 0.77 |
November | 0.317453E+11 | 116630.96 | 25-NOV-18:03 | -20.8 |
December | 0.575571E+11 | 133304.85 | 09-DEC-06:41 | -22.8 |
Annual Sum or Average | 0.265758E+12 | |||
Minimum of Months | 0.203443E+09 | 10467.03 | -31.2 | |
Maximum of Months | 0.732703E+11 | 133304.85 | 14.75 |
Report: ZoneHeatingSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361468E+12 | 325594.47 | 18-JAN-19:54 | -17.8 |
February | 0.238494E+12 | 308788.56 | 01-FEB-20:57 | -28.9 |
March | 0.116728E+12 | 213793.52 | 06-MAR-06:51 | -12.8 |
April | 0.247287E+11 | 121105.91 | 02-APR-24:00 | -5.6 |
May | 54164070.67 | 17285.24 | 02-MAY-05:04 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.635782E+10 | 35847.63 | 27-OCT-03:00 | 0.00 |
November | 0.136281E+12 | 229869.45 | 26-NOV-03:51 | -25.0 |
December | 0.280574E+12 | 377918.60 | 09-DEC-09:00 | -22.8 |
Annual Sum or Average | 0.116468E+13 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.361468E+12 | 377918.60 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.258145E+10 | 1955.04 | 02-JAN-08:09 | 0.244223E+10 | 1835.05 | 02-JAN-08:09 |
February | 0.235440E+10 | 1955.04 | 01-FEB-08:09 | 0.222575E+10 | 1835.05 | 01-FEB-08:09 |
March | 0.269003E+10 | 1955.04 | 01-MAR-08:09 | 0.253693E+10 | 1835.05 | 01-MAR-08:09 |
April | 0.254196E+10 | 1955.04 | 01-APR-07:10 | 0.240164E+10 | 1835.05 | 01-APR-07:10 |
May | 0.263574E+10 | 1955.04 | 01-MAY-07:10 | 0.248958E+10 | 1835.05 | 01-MAY-07:10 |
June | 0.259625E+10 | 1955.04 | 01-JUN-07:10 | 0.244899E+10 | 1835.05 | 01-JUN-07:10 |
July | 0.258145E+10 | 1955.04 | 01-JUL-07:10 | 0.244223E+10 | 1835.05 | 01-JUL-07:10 |
August | 0.269003E+10 | 1955.04 | 01-AUG-07:10 | 0.253693E+10 | 1835.05 | 01-AUG-07:10 |
September | 0.254196E+10 | 1955.04 | 01-SEP-07:10 | 0.240164E+10 | 1835.05 | 01-SEP-07:10 |
October | 0.258145E+10 | 1955.04 | 02-OCT-07:10 | 0.244223E+10 | 1835.05 | 02-OCT-07:10 |
November | 0.248766E+10 | 1955.04 | 01-NOV-07:10 | 0.235429E+10 | 1835.05 | 01-NOV-07:10 |
December | 0.258145E+10 | 1955.04 | 01-DEC-08:09 | 0.244223E+10 | 1835.05 | 01-DEC-08:09 |
Annual Sum or Average | 0.308638E+11 | 0.291647E+11 | ||||
Minimum of Months | 0.235440E+10 | 1955.04 | 0.222575E+10 | 1835.05 | ||
Maximum of Months | 0.269003E+10 | 1955.04 | 0.253693E+10 | 1835.05 |
Report: ZoneElectricSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [] | |
January | 0.198922E+11 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 |
February | 0.182065E+11 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 |
March | 0.210336E+11 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 |
April | 0.197108E+11 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 |
May | 0.204629E+11 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 |
June | 0.202815E+11 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 |
July | 0.198922E+11 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 |
August | 0.210336E+11 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 |
September | 0.197108E+11 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 |
October | 0.198922E+11 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 |
November | 0.191400E+11 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 |
December | 0.198922E+11 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 |
Annual Sum or Average | 0.239148E+12 | 0.00 | 0.00 | ||
Minimum of Months | 0.182065E+11 | 17848.24 | 0.00 | 0.00 | |
Maximum of Months | 0.210336E+11 | 17848.24 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.294120E+11 | 26389.90 | 02-JAN-09:09 | 0.885613E+10 | 8200.12 | 02-JAN-08:09 |
February | 0.269196E+11 | 26389.90 | 01-FEB-09:09 | 0.814764E+10 | 8200.12 | 01-FEB-08:09 |
March | 0.310997E+11 | 26389.90 | 01-MAR-09:09 | 0.957200E+10 | 8200.12 | 01-MAR-08:09 |
April | 0.291438E+11 | 26389.90 | 01-APR-08:09 | 0.885613E+10 | 8200.12 | 01-APR-07:10 |
May | 0.302559E+11 | 26389.90 | 01-MAY-08:09 | 0.921037E+10 | 8200.12 | 01-MAY-07:10 |
June | 0.299876E+11 | 26389.90 | 01-JUN-08:09 | 0.921037E+10 | 8200.12 | 01-JUN-07:10 |
July | 0.294120E+11 | 26389.90 | 01-JUL-08:09 | 0.885613E+10 | 8200.12 | 01-JUL-07:10 |
August | 0.310997E+11 | 26389.90 | 01-AUG-08:09 | 0.956462E+10 | 8200.12 | 01-AUG-07:10 |
September | 0.291438E+11 | 26389.90 | 01-SEP-08:09 | 0.884875E+10 | 8200.12 | 01-SEP-07:10 |
October | 0.294120E+11 | 26389.90 | 02-OCT-08:09 | 0.886351E+10 | 8200.12 | 02-OCT-07:10 |
November | 0.282999E+11 | 26389.90 | 01-NOV-08:09 | 0.850188E+10 | 8200.12 | 01-NOV-07:10 |
December | 0.294120E+11 | 26389.90 | 01-DEC-09:09 | 0.885613E+10 | 8200.12 | 01-DEC-08:09 |
Annual Sum or Average | 0.353598E+12 | 0.107344E+12 | ||||
Minimum of Months | 0.269196E+11 | 26389.90 | 0.814764E+10 | 8200.12 | ||
Maximum of Months | 0.310997E+11 | 26389.90 | 0.957200E+10 | 8200.12 |
Report: SpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817855E+10 |
February | 0.127628E+10 | 0.235440E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610642E+10 |
March | 0.149825E+10 | 0.269003E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509769E+10 |
April | 0.138726E+10 | 0.254196E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27449299.03 | 0.307418E+10 |
May | 0.144276E+10 | 0.263574E+10 | 0.248958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30497953.77 | 0.180834E+10 |
June | 0.144276E+10 | 0.259625E+10 | 0.244899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127615E+09 | 0.109974E+10 |
July | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98397131.86 | 0.757096E+09 |
August | 0.149825E+10 | 0.269003E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147034E+09 | 0.103346E+10 |
September | 0.138726E+10 | 0.254196E+10 | 0.240164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88204727.13 | 0.170758E+10 |
October | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282730E+10 |
November | 0.133177E+10 | 0.248766E+10 | 0.235429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481955E+10 |
December | 0.138726E+10 | 0.258145E+10 | 0.244223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672132E+10 |
Annual Sum or Average | 0.168137E+11 | 0.308638E+11 | 0.291647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519198E+09 | 0.432312E+11 |
Minimum of Months | 0.127628E+10 | 0.235440E+10 | 0.222575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757096E+09 |
Maximum of Months | 0.149825E+10 | 0.269003E+10 | 0.253693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147034E+09 | 0.817855E+10 |
Report: SpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309332E+11 |
February | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227752E+11 |
March | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12543.65 | 0.185064E+11 |
April | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64976149.40 | 0.113502E+11 |
May | 0.339505E+10 | 0.204629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19833495.42 | 0.756320E+10 |
June | 0.339505E+10 | 0.202815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327665E+09 | 0.490847E+10 |
July | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82099771.33 | 0.383024E+10 |
August | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128780E+09 | 0.516677E+10 |
September | 0.326447E+10 | 0.197108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94394376.85 | 0.693191E+10 |
October | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981486E+10 |
November | 0.313390E+10 | 0.191400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185046E+11 |
December | 0.326447E+10 | 0.198922E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257351E+11 |
Annual Sum or Average | 0.395654E+11 | 0.239148E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717761E+09 | 0.166020E+12 |
Minimum of Months | 0.300332E+10 | 0.182065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383024E+10 |
Maximum of Months | 0.352563E+10 | 0.210336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327665E+09 | 0.309332E+11 |
Report: SpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122319E+12 |
February | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851194E+11 |
March | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452682E+09 | 0.591177E+11 |
April | 0.750829E+10 | 0.291438E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183499E+10 | 0.317784E+11 |
May | 0.780862E+10 | 0.302559E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452140E+09 | 0.208697E+11 |
June | 0.780862E+10 | 0.299876E+11 | 0.921037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166510E+09 | 0.217934E+11 |
July | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201776E+11 |
August | 0.810895E+10 | 0.310997E+11 | 0.956462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248184E+11 |
September | 0.750829E+10 | 0.291438E+11 | 0.884875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23411956.25 | 0.249048E+11 |
October | 0.750829E+10 | 0.294120E+11 | 0.886351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466697E+09 | 0.225222E+11 |
November | 0.720796E+10 | 0.282999E+11 | 0.850188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76955808.46 | 0.602836E+11 |
December | 0.750829E+10 | 0.294120E+11 | 0.885613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.963518E+11 |
Annual Sum or Average | 0.910005E+11 | 0.353598E+12 | 0.107344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347339E+10 | 0.590056E+12 |
Minimum of Months | 0.690763E+10 | 0.269196E+11 | 0.814764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201776E+11 |
Maximum of Months | 0.810895E+10 | 0.310997E+11 | 0.957200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183499E+10 | 0.122319E+12 |
Report: PeakSpaceGainsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1680.92 | 02-JAN-08:09 | 1955.04 | 02-JAN-08:09 | 1835.05 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 18865.30 | 18-JAN-18:00 |
February | 1680.92 | 01-FEB-08:09 | 1955.04 | 01-FEB-08:09 | 1835.05 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 18439.67 | 02-FEB-08:00 |
March | 1680.92 | 01-MAR-08:09 | 1955.04 | 01-MAR-08:09 | 1835.05 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 14166.26 | 06-MAR-08:00 |
April | 1680.92 | 01-APR-07:10 | 1955.04 | 01-APR-07:10 | 1835.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1101.31 | 15-APR-17:00 | 9781.12 | 03-APR-06:10 |
May | 1680.92 | 01-MAY-07:10 | 1955.04 | 01-MAY-07:10 | 1835.05 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1372.05 | 31-MAY-17:00 | 6080.19 | 02-MAY-06:10 |
June | 1680.92 | 01-JUN-07:10 | 1955.04 | 01-JUN-07:10 | 1835.05 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2064.86 | 26-JUN-16:10 | 4397.03 | 02-JUN-06:20 |
July | 1680.92 | 01-JUL-07:10 | 1955.04 | 01-JUL-07:10 | 1835.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1820.95 | 25-JUL-16:10 | 3012.87 | 24-JUL-06:03 |
August | 1680.92 | 01-AUG-07:10 | 1955.04 | 01-AUG-07:10 | 1835.05 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2478.82 | 04-AUG-16:10 | 4123.22 | 07-AUG-06:03 |
September | 1680.92 | 01-SEP-07:10 | 1955.04 | 01-SEP-07:10 | 1835.05 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2050.48 | 06-SEP-16:10 | 6040.26 | 29-SEP-06:05 |
October | 1680.92 | 02-OCT-07:10 | 1955.04 | 02-OCT-07:10 | 1835.05 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7354.91 | 24-OCT-06:10 |
November | 1680.92 | 01-NOV-07:10 | 1955.04 | 01-NOV-07:10 | 1835.05 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 11916.77 | 24-NOV-07:10 |
December | 1680.92 | 01-DEC-08:09 | 1955.04 | 01-DEC-08:09 | 1835.05 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 18280.11 | 08-DEC-17:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3012.87 | |||||
Maximum of Months | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2478.82 | 18865.30 |
Report: PeakSpaceGainsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 3955.50 | 02-JAN-08:09 | 17848.24 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 53391.53 | 18-JAN-18:00 |
February | 3955.50 | 01-FEB-08:09 | 17848.24 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 33244.31 | 04-FEB-18:00 |
March | 3955.50 | 01-MAR-08:09 | 17848.24 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.91 | 19-MAR-14:00 | 32673.62 | 06-MAR-08:00 |
April | 3955.50 | 01-APR-07:10 | 17848.24 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3555.22 | 15-APR-17:00 | 20410.77 | 25-APR-06:10 |
May | 3955.50 | 01-MAY-07:10 | 17848.24 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1410.77 | 31-MAY-15:10 | 12305.62 | 01-MAY-15:05 |
June | 3955.50 | 01-JUN-07:10 | 17848.24 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4354.03 | 11-JUN-15:00 | 11170.92 | 02-JUN-08:00 |
July | 3955.50 | 01-JUL-07:10 | 17848.24 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2373.02 | 25-JUL-16:00 | 6804.36 | 10-JUL-15:10 |
August | 3955.50 | 01-AUG-07:10 | 17848.24 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2967.50 | 04-AUG-16:20 | 6870.56 | 30-AUG-15:10 |
September | 3955.50 | 01-SEP-07:10 | 17848.24 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2596.62 | 06-SEP-15:40 | 9770.72 | 18-SEP-16:00 |
October | 3955.50 | 02-OCT-07:10 | 17848.24 | 02-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 14218.93 | 24-OCT-06:10 |
November | 3955.50 | 01-NOV-07:10 | 17848.24 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 29671.83 | 25-NOV-16:10 |
December | 3955.50 | 01-DEC-08:09 | 17848.24 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 58989.16 | 09-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6804.36 | ||||
Maximum of Months | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4354.03 | 58989.16 |
Report: PeakSpaceGainsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 9097.65 | 02-JAN-08:09 | 26389.90 | 02-JAN-09:09 | 8200.12 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 167766.18 | 18-JAN-16:00 |
February | 9097.65 | 01-FEB-08:09 | 26389.90 | 01-FEB-09:09 | 8200.12 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 117875.81 | 28-FEB-10:00 |
March | 9097.65 | 01-MAR-08:09 | 26389.90 | 01-MAR-09:09 | 8200.12 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11085.24 | 19-MAR-14:00 | 107459.54 | 06-MAR-08:70 |
April | 9097.65 | 01-APR-07:10 | 26389.90 | 01-APR-08:09 | 8200.12 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26071.64 | 15-APR-15:00 | 51067.49 | 02-APR-24:00 |
May | 9097.65 | 01-MAY-07:10 | 26389.90 | 01-MAY-08:09 | 8200.12 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11837.98 | 04-MAY-15:00 | 45515.24 | 13-MAY-12:55 |
June | 9097.65 | 01-JUN-07:10 | 26389.90 | 01-JUN-08:09 | 8200.12 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5722.94 | 11-JUN-11:00 | 36314.07 | 02-JUN-08:00 |
July | 9097.65 | 01-JUL-07:10 | 26389.90 | 01-JUL-08:09 | 8200.12 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 31970.83 | 10-JUL-14:00 |
August | 9097.65 | 01-AUG-07:10 | 26389.90 | 01-AUG-08:09 | 8200.12 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 33088.26 | 30-AUG-15:00 |
September | 9097.65 | 01-SEP-07:10 | 26389.90 | 01-SEP-08:09 | 8200.12 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1846.44 | 06-SEP-14:00 | 35002.57 | 18-SEP-16:00 |
October | 9097.65 | 02-OCT-07:10 | 26389.90 | 02-OCT-08:09 | 8200.12 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11742.92 | 20-OCT-15:00 | 29973.71 | 24-OCT-07:10 |
November | 9097.65 | 01-NOV-07:10 | 26389.90 | 01-NOV-08:09 | 8200.12 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8282.05 | 20-NOV-10:00 | 115822.08 | 25-NOV-11:00 |
December | 9097.65 | 01-DEC-08:09 | 26389.90 | 01-DEC-09:09 | 8200.12 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 213449.63 | 09-DEC-09:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29973.71 | |||||
Maximum of Months | 9097.65 | 26389.90 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 26071.64 | 213449.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 2742.13 | 2819.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1232.13 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 2742.13 | 2819.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2471.37 |
March | 444.34 | 25-MAR-15:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.21 |
April | 7391.08 | 18-APR-15:10 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 746.66 | 0.00 |
May | 8651.38 | 31-MAY-16:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 485.36 | 0.00 |
June | 28501.65 | 19-JUN-05:03 | 739.61 | 2335.89 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 994.13 |
July | 29120.15 | 19-JUL-05:02 | 924.51 | 2919.87 | 2752.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 740.85 |
August | 27817.43 | 10-AUG-05:03 | 739.61 | 2335.89 | 2202.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 938.20 |
September | 28589.66 | 08-SEP-05:01 | 1294.31 | 4087.81 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.29 |
October | 3419.58 | 20-OCT-15:30 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.36 |
November | 2504.01 | 04-NOV-15:00 | 1680.92 | 1955.04 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.42 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 1828.09 | 1879.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 1828.09 | 1835.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29120.15 | 1680.92 | 4087.81 | 3853.61 | 0.00 | 0.00 | 0.00 | 0.00 | 746.66 | 2471.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 83.57 | 02-JAN-15:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5552.00 |
February | 612.57 | 17-FEB-15:30 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6509.06 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 12598.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15917.78 |
April | 146598.35 | 17-APR-17:11 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 775.90 |
May | 63811.37 | 31-MAY-17:06 | 0.00 | 10498.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.44 | 0.00 |
June | 139848.88 | 22-JUN-17:41 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.79 |
July | 133624.65 | 22-JUL-19:11 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2151.93 |
August | 147709.89 | 06-AUG-17:01 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3082.29 |
September | 138176.76 | 15-SEP-17:41 | 0.00 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3276.05 |
November | 143.66 | 21-NOV-13:50 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6815.68 |
December | 901.20 | 15-DEC-14:00 | 3955.50 | 17848.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3184.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 2099.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 147709.89 | 3955.50 | 20997.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.44 | 15917.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 18628.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21104.27 |
February | 0.00 | 01-FEB-00:02 | 0.00 | 18628.16 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51792.97 |
March | 0.00 | 01-MAR-00:02 | 0.00 | 18628.16 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53605.73 |
April | 0.00 | 01-APR-00:03 | 0.00 | 9314.08 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9734.80 |
May | 0.00 | 01-MAY-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7145.52 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10247.87 |
July | 0.00 | 01-JUL-00:03 | 0.00 | 9314.08 | 6150.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7975.65 |
August | 0.00 | 01-AUG-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8545.70 |
September | 0.00 | 01-SEP-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11059.06 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8333.74 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 3104.69 | 2050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6474.53 |
December | 0.00 | 01-DEC-00:03 | 0.00 | 12418.78 | 8200.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21685.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 3104.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6474.53 | |
Maximum of Months | 0.00 | 0.00 | 18628.16 | 12300.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53605.73 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.144253E+12 | 91328.19 | 17-JAN-16:00 | 0.531457E+12 | 515244.85 | 18-JAN-20:10 |
February | 0.127050E+12 | 88969.69 | 18-FEB-15:39 | 0.342434E+12 | 484139.27 | 02-FEB-03:49 |
March | 0.127642E+12 | 88968.88 | 01-MAR-13:09 | 0.164700E+12 | 351594.92 | 06-MAR-06:49 |
April | 0.989384E+11 | 88887.26 | 03-APR-12:09 | 0.430437E+11 | 197738.29 | 03-APR-05:19 |
May | 0.905964E+11 | 88105.42 | 31-MAY-14:00 | 0.133094E+11 | 38682.09 | 02-MAY-05:10 |
June | 0.967045E+11 | 92438.93 | 27-JUN-14:00 | 0.123272E+11 | 10622.99 | 05-JUN-05:10 |
July | 0.983507E+11 | 93227.49 | 03-JUL-14:00 | 0.127224E+11 | 4750.00 | 01-JUL-00:10 |
August | 0.102897E+12 | 96708.16 | 04-AUG-14:00 | 0.127224E+11 | 4750.00 | 01-AUG-00:10 |
September | 0.922628E+11 | 90203.93 | 06-SEP-14:00 | 0.125705E+11 | 29904.66 | 30-SEP-05:10 |
October | 0.954612E+11 | 82863.79 | 28-OCT-07:10 | 0.189192E+11 | 66433.75 | 17-OCT-05:10 |
November | 0.119546E+12 | 91266.18 | 30-NOV-16:49 | 0.194221E+12 | 359337.46 | 26-NOV-03:49 |
December | 0.143099E+12 | 91269.33 | 30-DEC-16:00 | 0.400241E+12 | 599780.99 | 09-DEC-08:00 |
Annual Sum or Average | 0.133680E+13 | 0.175867E+13 | ||||
Minimum of Months | 0.905964E+11 | 82863.79 | 0.123272E+11 | 4750.00 | ||
Maximum of Months | 0.144253E+12 | 96708.16 | 0.531457E+12 | 599780.99 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.518856E+11 | 0.141498E+11 | 0.112984E+11 | 0.00 | 0.658346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108465E+10 | 0.00 |
February | 0.474804E+11 | 0.117898E+11 | 0.103734E+11 | 0.00 | 0.563936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101280E+10 | 0.00 |
March | 0.548234E+11 | 0.116823E+11 | 0.121089E+11 | 0.00 | 0.478605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116677E+10 | 0.00 |
April | 0.513965E+11 | 0.990079E+10 | 0.112578E+11 | 0.00 | 0.247432E+11 | 0.00 | 0.00 | 0.593870E+09 | 0.00 | 0.00 | 0.00 | 0.104629E+10 | 0.00 |
May | 0.533545E+11 | 0.900490E+10 | 0.117000E+11 | 0.00 | 0.142384E+11 | 0.00 | 0.00 | 0.127570E+10 | 0.00 | 0.00 | 0.00 | 0.102286E+10 | 0.00 |
June | 0.528654E+11 | 0.809878E+10 | 0.116594E+11 | 0.00 | 0.155015E+11 | 0.00 | 0.00 | 0.762888E+10 | 0.00 | 0.00 | 0.00 | 0.950627E+09 | 0.00 |
July | 0.518856E+11 | 0.863119E+10 | 0.112984E+11 | 0.00 | 0.151993E+11 | 0.00 | 0.00 | 0.104615E+11 | 0.00 | 0.00 | 0.00 | 0.874700E+09 | 0.00 |
August | 0.548234E+11 | 0.969090E+10 | 0.121016E+11 | 0.00 | 0.156836E+11 | 0.00 | 0.00 | 0.968534E+10 | 0.00 | 0.00 | 0.00 | 0.912641E+09 | 0.00 |
September | 0.513965E+11 | 0.106789E+11 | 0.112504E+11 | 0.00 | 0.140144E+11 | 0.00 | 0.00 | 0.405821E+10 | 0.00 | 0.00 | 0.00 | 0.864384E+09 | 0.00 |
October | 0.518856E+11 | 0.124861E+11 | 0.113057E+11 | 0.00 | 0.188485E+11 | 0.00 | 0.00 | 18793567.91 | 0.00 | 0.00 | 0.00 | 0.916485E+09 | 0.00 |
November | 0.499276E+11 | 0.133359E+11 | 0.108562E+11 | 0.00 | 0.444887E+11 | 0.00 | 0.00 | 473.07 | 0.00 | 0.00 | 0.00 | 0.937895E+09 | 0.00 |
December | 0.518856E+11 | 0.144928E+11 | 0.112984E+11 | 0.00 | 0.643859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103656E+10 | 0.00 |
Annual Sum or Average | 0.623610E+12 | 0.133942E+12 | 0.136508E+12 | 0.00 | 0.397192E+12 | 0.00 | 0.00 | 0.337223E+11 | 0.00 | 0.00 | 0.00 | 0.118267E+11 | 0.00 |
Minimum of Months | 0.474804E+11 | 0.809878E+10 | 0.103734E+11 | 0.00 | 0.140144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864384E+09 | 0.00 |
Maximum of Months | 0.548234E+11 | 0.144928E+11 | 0.121089E+11 | 0.00 | 0.658346E+11 | 0.00 | 0.00 | 0.104615E+11 | 0.00 | 0.00 | 0.00 | 0.116677E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.531457E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.342434E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.164700E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.430437E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.133094E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.123272E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.127224E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.127224E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.125705E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.189192E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.194221E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.400241E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.175867E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.123272E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.531457E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 46193.18 | 02-JAN-09:09 | 8532.22 | 01-JAN-00:10 | 10035.17 | 02-JAN-08:09 | 0.00 | 31140.32 | 02-JAN-08:50 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 46193.18 | 01-FEB-09:09 | 8532.22 | 01-FEB-00:10 | 10035.17 | 01-FEB-08:09 | 0.00 | 31140.32 | 01-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 46193.18 | 01-MAR-09:09 | 8532.22 | 01-MAR-00:10 | 10035.17 | 01-MAR-08:09 | 0.00 | 31140.32 | 01-MAR-09:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 46193.18 | 01-APR-08:09 | 8532.22 | 01-APR-00:10 | 10035.17 | 01-APR-07:10 | 0.00 | 31140.32 | 01-APR-16:19 | 0.00 | 0.00 | 01-APR-00:10 |
May | 46193.18 | 01-MAY-08:09 | 8532.22 | 01-MAY-00:10 | 10035.17 | 01-MAY-07:10 | 0.00 | 18647.04 | 02-MAY-04:40 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 46193.18 | 01-JUN-08:09 | 8532.22 | 01-JUN-00:10 | 10035.17 | 01-JUN-07:10 | 0.00 | 15992.00 | 27-JUN-15:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 46193.18 | 01-JUL-08:09 | 8532.22 | 01-JUL-00:10 | 10035.17 | 01-JUL-07:10 | 0.00 | 15992.00 | 01-JUL-13:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 46193.18 | 01-AUG-08:09 | 8532.22 | 01-AUG-00:10 | 10035.17 | 01-AUG-07:10 | 0.00 | 15992.00 | 01-AUG-14:39 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 46193.18 | 01-SEP-08:09 | 8532.22 | 01-SEP-00:10 | 10035.17 | 01-SEP-07:10 | 0.00 | 15992.00 | 06-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 46193.18 | 02-OCT-08:09 | 8532.22 | 01-OCT-00:10 | 10035.17 | 02-OCT-07:10 | 0.00 | 31140.32 | 16-OCT-06:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 46193.18 | 01-NOV-08:09 | 8532.22 | 01-NOV-00:10 | 10035.17 | 01-NOV-07:10 | 0.00 | 31140.32 | 13-NOV-08:39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 46193.18 | 01-DEC-09:09 | 8532.22 | 01-DEC-00:10 | 10035.17 | 01-DEC-08:09 | 0.00 | 31140.32 | 01-DEC-07:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 46193.18 | 8532.22 | 10035.17 | 0.00 | 15992.00 | 0.00 | 0.00 | |||||
Maximum of Months | 46193.18 | 8532.22 | 10035.17 | 0.00 | 31140.32 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 1769.02 | 31-JAN-12:00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 1796.78 | 21-FEB-12:39 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 1788.87 | 02-MAR-12:30 | 0.00 |
April | 13046.28 | 18-APR-14:00 | 0.00 | 0.00 | 0.00 | 1726.72 | 01-APR-11:50 | 0.00 |
May | 14557.61 | 31-MAY-15:09 | 0.00 | 0.00 | 0.00 | 1634.74 | 02-MAY-11:00 | 0.00 |
June | 20086.15 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 | 1534.25 | 01-JUN-11:30 | 0.00 |
July | 20399.27 | 26-JUL-15:00 | 0.00 | 0.00 | 0.00 | 1456.58 | 01-JUL-11:39 | 0.00 |
August | 24169.09 | 04-AUG-15:50 | 0.00 | 0.00 | 0.00 | 1401.80 | 01-AUG-11:00 | 0.00 |
September | 17090.38 | 06-SEP-15:20 | 0.00 | 0.00 | 0.00 | 1411.98 | 30-SEP-11:39 | 0.00 |
October | 1451.68 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 1507.08 | 31-OCT-11:00 | 0.00 |
November | 0.34 | 03-NOV-12:09 | 0.00 | 0.00 | 0.00 | 1610.89 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 1716.12 | 30-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1401.80 | 0.00 | ||
Maximum of Months | 24169.09 | 0.00 | 0.00 | 0.00 | 1796.78 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 91328.19 | 17-JAN-16:00 | 40988.70 | 10035.17 | 8532.22 | 0.00 | 31140.32 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 88969.69 | 18-FEB-15:39 | 46193.18 | 10035.17 | 0.00 | 0.00 | 31140.32 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 88968.88 | 01-MAR-13:09 | 46193.18 | 10035.17 | 0.00 | 0.00 | 31140.32 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88887.26 | 03-APR-12:09 | 46193.18 | 10035.17 | 0.00 | 0.00 | 31140.32 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88105.42 | 31-MAY-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 15992.00 | 0.00 | 0.00 | 14544.91 | 0.00 |
June | 92438.93 | 27-JUN-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 15992.00 | 0.00 | 0.00 | 18973.21 | 0.00 |
July | 93227.49 | 03-JUL-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 15992.00 | 0.00 | 0.00 | 19759.39 | 0.00 |
August | 96708.16 | 04-AUG-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 15992.00 | 0.00 | 0.00 | 23259.21 | 0.00 |
September | 90203.93 | 06-SEP-14:00 | 46193.18 | 10035.17 | 0.00 | 0.00 | 15992.00 | 0.00 | 0.00 | 16755.21 | 0.00 |
October | 82863.79 | 28-OCT-07:10 | 40988.70 | 10035.17 | 0.00 | 0.00 | 31140.32 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 91266.18 | 30-NOV-16:49 | 40988.70 | 10035.17 | 8532.22 | 0.00 | 31140.32 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 91269.33 | 30-DEC-16:00 | 40988.70 | 10035.17 | 8532.22 | 0.00 | 31140.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 82863.79 | 40988.70 | 10035.17 | 0.00 | 0.00 | 15992.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96708.16 | 46193.18 | 10035.17 | 8532.22 | 0.00 | 31140.32 | 0.00 | 0.00 | 23259.21 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 515244.85 | 18-JAN-20:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 484139.27 | 02-FEB-03:49 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 351594.92 | 06-MAR-06:49 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 197738.29 | 03-APR-05:19 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 38682.09 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 10622.99 | 05-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4750.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 4750.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 29904.66 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 66433.75 | 17-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 359337.46 | 26-NOV-03:49 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 599780.99 | 09-DEC-08:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 4750.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 599780.99 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 106.83 | 15.20 | 16.00 | 15.68 | 0.00 | 15.68 | 0.00 | 15.68 |
February | 64.83 | 15.44 | 13.00 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
March | 35.50 | 16.12 | 11.50 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
April | 11.33 | 17.46 | 6.17 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
May | 1.17 | 19.92 | 1.17 | 19.92 | 0.17 | 20.22 | 0.17 | 20.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.15 | 1.33 | 24.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.40 | 1.83 | 25.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.66 | 1.67 | 24.66 |
September | 0.67 | 20.22 | 0.67 | 20.22 | 0.33 | 21.09 | 0.33 | 21.67 |
October | 5.33 | 19.99 | 5.33 | 19.99 | 0.00 | 19.99 | 0.00 | 19.99 |
November | 33.33 | 15.67 | 7.83 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 |
December | 70.00 | 15.37 | 12.50 | 15.86 | 0.00 | 15.86 | 0.00 | 15.86 |
Annual Sum or Average | 329.00 | 15.61 | 74.17 | 16.24 | 5.83 | 16.36 | 5.33 | 16.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.68 | 0.00 | 15.68 |
Maximum of Months | 106.83 | 20.22 | 16.00 | 20.22 | 2.17 | 25.40 | 1.83 | 25.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 122.67 | 13.33 | 6.00 | 13.33 | 0.00 | 13.33 | 0.00 | 13.33 |
February | 103.83 | 13.72 | 5.17 | 13.72 | 0.00 | 13.72 | 0.00 | 13.72 |
March | 77.50 | 14.14 | 5.17 | 14.13 | 0.00 | 14.13 | 0.00 | 14.13 |
April | 28.17 | 14.50 | 2.50 | 14.50 | 0.17 | 14.57 | 0.00 | 14.57 |
May | 0.50 | 14.98 | 0.17 | 14.98 | 0.67 | 21.24 | 0.00 | 21.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.67 | 0.00 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 27.64 | 0.00 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.48 | 0.00 | 27.48 |
September | 0.17 | 15.00 | 0.00 | 15.00 | 5.50 | 27.08 | 0.00 | 27.08 |
October | 9.50 | 14.88 | 2.00 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
November | 76.33 | 13.95 | 3.17 | 13.95 | 0.00 | 13.95 | 0.00 | 13.95 |
December | 118.00 | 13.67 | 5.17 | 13.67 | 0.00 | 13.67 | 0.00 | 13.67 |
Annual Sum or Average | 536.67 | 13.78 | 29.33 | 13.78 | 60.50 | 15.12 | 0.00 | 15.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 0.00 | 13.33 |
Maximum of Months | 122.67 | 15.00 | 6.00 | 15.00 | 23.83 | 27.67 | 0.00 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 20.97 | 300.00 | 20.97 | 300.00 | 20.97 |
February | 276.00 | 21.01 | 272.00 | 21.00 | 272.00 | 21.00 |
March | 324.00 | 21.21 | 298.17 | 21.14 | 298.17 | 21.11 |
April | 277.67 | 21.80 | 201.50 | 21.59 | 189.00 | 21.46 |
May | 210.00 | 23.14 | 73.00 | 23.07 | 30.67 | 22.92 |
June | 74.00 | 23.49 | 215.83 | 23.79 | 19.33 | 23.80 |
July | 38.17 | 23.89 | 289.00 | 23.90 | 37.50 | 23.90 |
August | 47.67 | 23.91 | 298.33 | 23.91 | 44.50 | 23.91 |
September | 128.33 | 23.16 | 147.50 | 23.40 | 16.83 | 23.27 |
October | 300.00 | 22.38 | 127.00 | 22.02 | 127.00 | 21.83 |
November | 288.00 | 21.61 | 212.67 | 21.37 | 212.67 | 21.27 |
December | 300.00 | 20.99 | 300.00 | 20.99 | 300.00 | 20.99 |
Annual Sum or Average | 2563.83 | 21.79 | 2735.00 | 21.94 | 1847.67 | 21.75 |
Minimum of Months | 38.17 | 20.97 | 73.00 | 20.97 | 16.83 | 20.97 |
Maximum of Months | 324.00 | 23.91 | 300.00 | 23.91 | 300.00 | 23.91 |
Report: ComfortReportSimple55Monthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 15.61 | 300.00 | 15.61 | 300.00 | 15.61 |
February | 276.00 | 15.98 | 276.00 | 15.98 | 276.00 | 15.98 |
March | 324.00 | 17.14 | 309.67 | 17.02 | 309.67 | 16.98 |
April | 267.83 | 19.43 | 238.00 | 19.40 | 210.50 | 19.11 |
May | 135.67 | 22.77 | 216.00 | 24.35 | 58.00 | 24.08 |
June | 211.17 | 26.07 | 273.83 | 26.30 | 181.33 | 26.36 |
July | 246.67 | 26.63 | 296.50 | 26.61 | 243.83 | 26.63 |
August | 255.83 | 26.60 | 314.83 | 26.58 | 251.50 | 26.60 |
September | 175.17 | 24.01 | 219.50 | 24.86 | 106.17 | 24.80 |
October | 288.17 | 20.25 | 197.33 | 19.77 | 193.17 | 19.53 |
November | 288.00 | 17.87 | 236.33 | 17.39 | 236.33 | 17.21 |
December | 300.00 | 15.66 | 300.00 | 15.66 | 300.00 | 15.66 |
Annual Sum or Average | 3068.50 | 20.11 | 3178.00 | 20.44 | 2666.50 | 20.21 |
Minimum of Months | 135.67 | 15.61 | 197.33 | 15.61 | 58.00 | 15.61 |
Maximum of Months | 324.00 | 26.63 | 314.83 | 26.61 | 309.67 | 26.63 |
Report: ComfortReportSimple55Monthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 300.00 | 10.01 | 300.00 | 10.01 | 300.00 | 10.01 |
February | 276.00 | 10.12 | 276.00 | 10.12 | 276.00 | 10.12 |
March | 324.00 | 10.93 | 324.00 | 10.93 | 324.00 | 10.93 |
April | 300.00 | 14.31 | 280.00 | 14.03 | 280.00 | 13.93 |
May | 307.50 | 20.25 | 153.17 | 19.70 | 150.17 | 19.40 |
June | 258.00 | 26.11 | 245.67 | 26.46 | 203.83 | 26.65 |
July | 258.50 | 28.28 | 290.17 | 28.15 | 251.83 | 28.24 |
August | 266.17 | 27.96 | 298.00 | 27.88 | 250.00 | 28.00 |
September | 229.50 | 22.30 | 231.17 | 22.76 | 171.33 | 22.64 |
October | 300.00 | 13.81 | 300.00 | 13.81 | 300.00 | 13.81 |
November | 288.00 | 11.50 | 288.00 | 11.50 | 288.00 | 11.50 |
December | 300.00 | 10.01 | 300.00 | 10.01 | 300.00 | 10.01 |
Annual Sum or Average | 3407.67 | 16.70 | 3286.17 | 16.70 | 3095.17 | 16.53 |
Minimum of Months | 229.50 | 10.01 | 153.17 | 10.01 | 150.17 | 10.01 |
Maximum of Months | 324.00 | 28.28 | 324.00 | 28.15 | 324.00 | 28.24 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICE PEOPLE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE2 FINE STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ZONE3 BULK STORAGEPEOPLE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
January | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 312.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 288.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 300.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 3636.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Minimum of Months | 276.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 324.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: DXReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.688097E+09 | 0.171522E+09 | 27.00 | 0.541491E+09 | 0.146606E+09 | 0.00 | 0.85 | 18-APR-15:10 | 0.00 | 01-APR-00:03 | 13093.37 | 18-APR-15:10 | 10477.79 | 18-APR-15:10 | 3059.85 | 18-APR-08:40 | 3197.99 | 18-APR-15:10 | 0.00 | 01-APR-00:03 |
May | 0.145559E+10 | 0.358336E+09 | 66.14 | 0.118936E+10 | 0.266230E+09 | 0.00 | 0.90 | 31-MAY-15:30 | 0.00 | 01-MAY-00:10 | 13448.10 | 31-MAY-15:50 | 11808.09 | 31-MAY-15:50 | 4102.37 | 30-MAY-09:40 | 3369.02 | 31-MAY-15:10 | 0.00 | 01-MAY-00:10 |
June | 0.703403E+10 | 0.169734E+10 | 200.07 | 0.559267E+10 | 0.144136E+10 | 0.00 | 1.00 | 10-JUN-05:03 | 0.00 | 01-JUN-00:10 | 34688.03 | 26-JUN-05:01 | 20783.07 | 26-JUN-05:01 | 17976.38 | 13-JUN-05:55 | 7857.13 | 26-JUN-05:01 | 0.00 | 01-JUN-00:10 |
July | 0.988865E+10 | 0.234052E+10 | 256.57 | 0.755082E+10 | 0.233783E+10 | 0.00 | 1.00 | 01-JUL-05:01 | 0.00 | 01-JUL-00:03 | 33610.70 | 26-JUL-05:01 | 21143.56 | 26-JUL-05:01 | 19112.12 | 27-JUL-05:01 | 7697.00 | 26-JUL-05:01 | 0.00 | 01-JUL-00:03 |
August | 0.100717E+11 | 0.240773E+10 | 265.67 | 0.771216E+10 | 0.235954E+10 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:10 | 36352.62 | 04-AUG-05:01 | 19470.97 | 03-AUG-05:01 | 18074.80 | 04-AUG-05:03 | 8077.17 | 04-AUG-05:01 | 0.00 | 01-AUG-00:10 |
September | 0.407637E+10 | 0.100279E+10 | 133.77 | 0.362643E+10 | 0.449934E+09 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 30562.62 | 11-SEP-05:01 | 20144.27 | 18-SEP-05:02 | 15276.53 | 12-SEP-05:03 | 7167.49 | 11-SEP-05:01 | 0.00 | 01-SEP-00:10 |
October | 75131960.14 | 18793567.91 | 12.25 | 74443272.73 | 688687.41 | 0.00 | 0.43 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 5878.09 | 20-OCT-15:00 | 5878.09 | 20-OCT-15:00 | 209.97 | 21-OCT-15:00 | 1451.68 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 1793.58 | 473.07 | 2.83 | 1632.37 | 161.21 | 0.00 | 0.00 | 03-NOV-12:10 | 0.00 | 01-NOV-00:10 | 1.27 | 03-NOV-12:10 | 1.15 | 03-NOV-12:10 | 0.12 | 03-NOV-12:10 | 0.34 | 03-NOV-12:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.332896E+11 | 0.799703E+10 | 964.30 | 0.262874E+11 | 0.700219E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.100717E+11 | 0.240773E+10 | 265.67 | 0.771216E+10 | 0.235954E+10 | 0.00 | 1.00 | 0.00 | 36352.62 | 21143.56 | 19112.12 | 8077.17 | 0.00 |
Report: DXReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 | 0.00 | 01-FEB-00:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 | 0.00 | 01-MAR-00:02 |
April | 0.163115E+10 | 0.422348E+09 | 22.48 | 0.133222E+10 | 0.298929E+09 | 0.00 | 1.00 | 17-APR-17:11 | 0.00 | 01-APR-00:03 | 119989.15 | 17-APR-17:11 | 119989.15 | 17-APR-17:11 | 8217.92 | 16-APR-16:05 | 28404.30 | 17-APR-17:11 | 0.00 | 01-APR-00:03 |
May | 0.360482E+10 | 0.917368E+09 | 56.37 | 0.312065E+10 | 0.484166E+09 | 0.00 | 1.00 | 31-MAY-17:06 | 0.00 | 01-MAY-00:10 | 86542.48 | 31-MAY-17:06 | 80357.06 | 31-MAY-17:06 | 6654.22 | 30-MAY-11:00 | 21130.20 | 31-MAY-17:06 | 0.00 | 01-MAY-00:10 |
June | 0.236695E+11 | 0.593154E+10 | 212.13 | 0.199482E+11 | 0.372135E+10 | 0.00 | 1.00 | 09-JUN-18:01 | 0.00 | 01-JUN-00:10 | 146214.82 | 11-JUN-20:11 | 133171.51 | 19-JUN-17:08 | 69017.07 | 11-JUN-20:11 | 35163.51 | 26-JUN-17:05 | 0.00 | 01-JUN-00:10 |
July | 0.331415E+11 | 0.812098E+10 | 290.73 | 0.273769E+11 | 0.576467E+10 | 0.00 | 1.00 | 01-JUL-17:06 | 0.00 | 01-JUL-00:03 | 149365.36 | 04-JUL-02:31 | 131484.80 | 22-JUL-17:08 | 80768.08 | 04-JUL-02:31 | 35519.50 | 03-JUL-17:05 | 0.00 | 01-JUL-00:03 |
August | 0.294421E+11 | 0.727761E+10 | 255.77 | 0.241824E+11 | 0.525969E+10 | 0.00 | 1.00 | 01-AUG-17:06 | 0.00 | 01-AUG-00:10 | 151429.68 | 04-AUG-19:10 | 122732.50 | 10-AUG-19:50 | 80438.55 | 04-AUG-18:21 | 34841.33 | 04-AUG-19:10 | 0.00 | 01-AUG-00:10 |
September | 0.119423E+11 | 0.305542E+10 | 130.22 | 0.111944E+11 | 0.747891E+09 | 0.00 | 1.00 | 01-SEP-18:21 | 0.00 | 01-SEP-00:10 | 143364.84 | 11-SEP-19:50 | 122197.95 | 15-SEP-17:41 | 35529.54 | 08-SEP-19:41 | 33454.34 | 11-SEP-19:50 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.103431E+12 | 0.257253E+11 | 967.70 | 0.871547E+11 | 0.162767E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.331415E+11 | 0.812098E+10 | 290.73 | 0.273769E+11 | 0.576467E+10 | 0.00 | 1.00 | 0.00 | 151429.68 | 133171.51 | 80768.08 | 35519.50 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 119.88 | 48.63 | 71.25 | 39.57 | 599.35 | 0.00 | 0.00 | 0.00 |
February | 174.38 | 85.53 | 88.84 | 95.41 | 468.15 | 0.00 | 0.00 | 0.00 |
March | 209.38 | 78.00 | 131.38 | 143.24 | 286.50 | 0.00 | 0.00 | 0.00 |
April | 305.23 | 150.83 | 154.40 | 305.53 | 204.01 | 0.00 | 0.00 | 0.00 |
May | 306.06 | 122.28 | 183.78 | 330.08 | 135.06 | 0.00 | 0.00 | 0.00 |
June | 358.58 | 155.11 | 203.47 | 433.28 | 116.65 | 0.00 | 0.00 | 0.00 |
July | 385.82 | 183.36 | 202.46 | 478.19 | 110.28 | 0.00 | 0.00 | 0.00 |
August | 336.26 | 153.79 | 182.47 | 419.60 | 125.29 | 0.00 | 0.00 | 0.00 |
September | 272.86 | 129.36 | 143.50 | 305.33 | 185.79 | 0.00 | 0.00 | 0.00 |
October | 190.99 | 85.13 | 105.85 | 164.38 | 224.71 | 0.00 | 0.00 | 0.00 |
November | 114.25 | 42.43 | 71.81 | 59.98 | 355.85 | 0.00 | 0.00 | 0.00 |
December | 88.24 | 41.97 | 46.27 | 39.35 | 525.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 238.75 | 106.40 | 132.36 | 235.18 | 277.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.24 | 41.97 | 46.27 | 39.35 | 110.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 385.82 | 183.36 | 203.47 | 478.19 | 599.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.95 | 53.94 | 79.02 | 43.89 | 664.73 | 0.00 | 0.00 | 0.00 |
February | 193.40 | 94.87 | 98.54 | 105.82 | 519.22 | 0.00 | 0.00 | 0.00 |
March | 232.22 | 86.51 | 145.71 | 158.87 | 317.75 | 0.00 | 0.00 | 0.00 |
April | 338.53 | 167.29 | 171.24 | 338.86 | 226.27 | 0.00 | 0.00 | 0.00 |
May | 339.45 | 135.62 | 203.83 | 366.10 | 149.80 | 0.00 | 0.00 | 0.00 |
June | 397.69 | 172.03 | 225.67 | 480.55 | 129.38 | 0.00 | 0.00 | 0.00 |
July | 427.91 | 203.36 | 224.55 | 530.36 | 122.31 | 0.00 | 0.00 | 0.00 |
August | 372.94 | 170.57 | 202.38 | 465.37 | 138.96 | 0.00 | 0.00 | 0.00 |
September | 302.63 | 143.47 | 159.16 | 338.64 | 206.06 | 0.00 | 0.00 | 0.00 |
October | 211.82 | 94.42 | 117.40 | 182.31 | 249.23 | 0.00 | 0.00 | 0.00 |
November | 126.71 | 47.06 | 79.65 | 66.52 | 394.67 | 0.00 | 0.00 | 0.00 |
December | 97.86 | 46.54 | 51.32 | 43.65 | 582.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 264.80 | 118.00 | 146.80 | 260.84 | 307.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.86 | 46.54 | 51.32 | 43.65 | 122.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 427.91 | 203.36 | 225.67 | 530.36 | 664.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.82 | 0.00 | 22.82 | 0.00 | 266.73 | 0.00 | 0.00 | 0.00 |
February | 28.94 | 0.00 | 28.94 | 0.49 | 211.27 | 0.00 | 0.00 | 0.00 |
March | 43.38 | 0.00 | 43.37 | 9.46 | 126.77 | 0.00 | 0.00 | 0.00 |
April | 50.18 | 0.34 | 49.84 | 23.53 | 86.93 | 0.00 | 0.00 | 0.00 |
May | 65.39 | 2.53 | 62.86 | 48.50 | 53.02 | 0.00 | 0.00 | 0.00 |
June | 76.26 | 6.89 | 69.37 | 75.86 | 44.22 | 0.00 | 0.00 | 0.00 |
July | 71.54 | 4.80 | 66.74 | 72.38 | 42.31 | 0.00 | 0.00 | 0.00 |
August | 60.13 | 1.25 | 58.88 | 61.34 | 49.61 | 0.00 | 0.00 | 0.00 |
September | 45.98 | 0.03 | 45.95 | 34.18 | 77.47 | 0.00 | 0.00 | 0.00 |
October | 34.16 | 0.00 | 34.16 | 10.89 | 96.44 | 0.00 | 0.00 | 0.00 |
November | 23.89 | 0.00 | 23.89 | 1.95 | 154.36 | 0.00 | 0.00 | 0.00 |
December | 15.50 | 0.00 | 15.50 | 0.00 | 228.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.93 | 1.33 | 43.61 | 28.38 | 119.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.50 | 0.00 | 15.50 | 0.00 | 42.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 76.26 | 6.89 | 69.37 | 75.86 | 266.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 22.82 | 0.00 | 22.82 | 0.00 | 266.73 | 0.00 | 0.00 | 0.00 |
February | 28.94 | 0.00 | 28.94 | 0.49 | 211.27 | 0.00 | 0.00 | 0.00 |
March | 43.38 | 0.00 | 43.37 | 9.46 | 126.77 | 0.00 | 0.00 | 0.00 |
April | 50.18 | 0.34 | 49.84 | 23.53 | 86.93 | 0.00 | 0.00 | 0.00 |
May | 65.39 | 2.53 | 62.86 | 48.50 | 53.02 | 0.00 | 0.00 | 0.00 |
June | 76.26 | 6.89 | 69.37 | 75.86 | 44.22 | 0.00 | 0.00 | 0.00 |
July | 71.54 | 4.80 | 66.74 | 72.38 | 42.31 | 0.00 | 0.00 | 0.00 |
August | 60.13 | 1.25 | 58.88 | 61.34 | 49.61 | 0.00 | 0.00 | 0.00 |
September | 45.98 | 0.03 | 45.95 | 34.18 | 77.47 | 0.00 | 0.00 | 0.00 |
October | 34.16 | 0.00 | 34.16 | 10.89 | 96.44 | 0.00 | 0.00 | 0.00 |
November | 23.89 | 0.00 | 23.89 | 1.95 | 154.36 | 0.00 | 0.00 | 0.00 |
December | 15.50 | 0.00 | 15.50 | 0.00 | 228.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.93 | 1.33 | 43.61 | 28.38 | 119.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.50 | 0.00 | 15.50 | 0.00 | 42.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 76.26 | 6.89 | 69.37 | 75.86 | 266.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINE STORAGE OFFICE FRONT WALL WINDOW
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1107.25 | 449.17 | 658.08 | 426.71 | 4794.09 | 0.00 | 0.00 | 0.00 |
February | 1610.67 | 790.05 | 820.62 | 963.92 | 3725.84 | 0.00 | 0.00 | 0.00 |
March | 1933.96 | 720.44 | 1213.52 | 1419.04 | 2257.90 | 0.00 | 0.00 | 0.00 |
April | 2819.29 | 1393.19 | 1426.10 | 2805.32 | 1652.44 | 0.00 | 0.00 | 0.00 |
May | 2826.94 | 1129.45 | 1697.49 | 2915.95 | 1185.47 | 0.00 | 0.00 | 0.00 |
June | 3312.01 | 1432.66 | 1879.35 | 3801.17 | 1045.66 | 0.00 | 0.00 | 0.00 |
July | 3563.63 | 1693.58 | 1870.05 | 4207.48 | 980.99 | 0.00 | 0.00 | 0.00 |
August | 3105.87 | 1420.47 | 1685.39 | 3668.32 | 1117.52 | 0.00 | 0.00 | 0.00 |
September | 2520.33 | 1194.84 | 1325.49 | 2717.95 | 1573.21 | 0.00 | 0.00 | 0.00 |
October | 1764.05 | 786.34 | 977.71 | 1575.18 | 1739.76 | 0.00 | 0.00 | 0.00 |
November | 1055.24 | 391.94 | 663.29 | 611.75 | 2788.27 | 0.00 | 0.00 | 0.00 |
December | 815.01 | 387.62 | 427.40 | 412.72 | 4149.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2205.27 | 982.74 | 1222.53 | 2132.78 | 2244.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 815.01 | 387.62 | 427.40 | 412.72 | 980.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3563.63 | 1693.58 | 1879.35 | 4207.48 | 4794.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: FINE STORAGE OFFICE LEFT WALL WINDOW
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 182.14 | 0.00 | 182.14 | 0.31 | 1846.62 | 0.00 | 0.00 | 0.00 |
February | 230.92 | 0.00 | 230.92 | 7.85 | 1449.00 | 0.00 | 0.00 | 0.00 |
March | 346.14 | 0.01 | 346.13 | 98.41 | 852.84 | 0.00 | 0.00 | 0.00 |
April | 400.46 | 2.73 | 397.73 | 188.29 | 604.85 | 0.00 | 0.00 | 0.00 |
May | 521.83 | 20.21 | 501.62 | 351.33 | 403.24 | 0.00 | 0.00 | 0.00 |
June | 608.52 | 54.97 | 553.55 | 544.81 | 342.14 | 0.00 | 0.00 | 0.00 |
July | 570.87 | 38.30 | 532.57 | 514.47 | 324.21 | 0.00 | 0.00 | 0.00 |
August | 479.85 | 10.00 | 469.85 | 428.07 | 382.18 | 0.00 | 0.00 | 0.00 |
September | 366.96 | 0.25 | 366.71 | 246.36 | 567.74 | 0.00 | 0.00 | 0.00 |
October | 272.58 | 0.00 | 272.58 | 105.32 | 642.88 | 0.00 | 0.00 | 0.00 |
November | 190.67 | 0.00 | 190.67 | 24.99 | 1040.22 | 0.00 | 0.00 | 0.00 |
December | 123.68 | 0.00 | 123.68 | 0.09 | 1554.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 358.56 | 10.58 | 347.98 | 210.39 | 831.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 123.68 | 0.00 | 123.68 | 0.09 | 324.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 608.52 | 54.97 | 553.55 | 544.81 | 1846.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 13.64 | 146.47 | 3.33 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 33.80 | 109.72 | 1.50 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 81.54 | 61.00 | 17.17 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.90 | 42.52 | 34.33 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 156.99 | 33.84 | 17.67 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 175.73 | 39.91 | 23.50 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 175.60 | 43.02 | 22.50 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.45 | 43.54 | 30.17 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 110.01 | 56.14 | 10.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 69.25 | 46.35 | 14.00 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 29.39 | 75.62 | 0.67 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 11.21 | 121.02 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 94.45 | 68.08 | 175.83 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 11.21 | 33.84 | 0.50 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 175.73 | 146.47 | 34.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 13.64 | 146.47 | 3.33 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 33.80 | 109.72 | 1.50 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 81.54 | 61.00 | 17.17 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.90 | 42.52 | 34.33 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 156.99 | 33.84 | 17.67 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 175.73 | 39.91 | 23.50 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 175.60 | 43.02 | 22.50 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.45 | 43.54 | 30.17 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 110.01 | 56.14 | 10.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 69.25 | 46.35 | 14.00 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 29.39 | 75.62 | 0.67 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 11.21 | 121.02 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 94.45 | 68.08 | 175.83 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 11.21 | 33.84 | 0.50 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 175.73 | 146.47 | 34.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 13.64 | 146.47 | 3.33 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 33.80 | 109.72 | 1.50 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 81.54 | 61.00 | 17.17 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.90 | 42.52 | 34.33 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 156.99 | 33.84 | 17.67 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 175.73 | 39.91 | 23.50 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 175.60 | 43.02 | 22.50 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.45 | 43.54 | 30.17 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 110.01 | 56.14 | 10.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 69.25 | 46.35 | 14.00 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 29.39 | 75.62 | 0.67 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 11.21 | 121.02 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 94.45 | 68.08 | 175.83 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 11.21 | 33.84 | 0.50 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 175.73 | 146.47 | 34.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 13.64 | 146.47 | 3.33 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 33.80 | 109.72 | 1.50 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 81.54 | 61.00 | 17.17 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.90 | 42.52 | 34.33 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 156.99 | 33.84 | 17.67 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 175.73 | 39.91 | 23.50 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 175.60 | 43.02 | 22.50 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.45 | 43.54 | 30.17 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 110.01 | 56.14 | 10.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 69.25 | 46.35 | 14.00 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 29.39 | 75.62 | 0.67 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 11.21 | 121.02 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 94.45 | 68.08 | 175.83 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 11.21 | 33.84 | 0.50 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 175.73 | 146.47 | 34.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 13.64 | 146.47 | 3.33 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 33.80 | 109.72 | 1.50 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 81.54 | 61.00 | 17.17 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.90 | 42.52 | 34.33 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 156.99 | 33.84 | 17.67 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 175.73 | 39.91 | 23.50 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 175.60 | 43.02 | 22.50 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.45 | 43.54 | 30.17 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 110.01 | 56.14 | 10.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 69.25 | 46.35 | 14.00 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 29.39 | 75.62 | 0.67 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 11.21 | 121.02 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 94.45 | 68.08 | 175.83 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 11.21 | 33.84 | 0.50 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 175.73 | 146.47 | 34.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 13.64 | 146.47 | 3.33 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 33.80 | 109.72 | 1.50 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 81.54 | 61.00 | 17.17 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.90 | 42.52 | 34.33 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 156.99 | 33.84 | 17.67 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 175.73 | 39.91 | 23.50 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 175.60 | 43.02 | 22.50 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.45 | 43.54 | 30.17 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 110.01 | 56.14 | 10.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 69.25 | 46.35 | 14.00 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 29.39 | 75.62 | 0.67 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 11.21 | 121.02 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 94.45 | 68.08 | 175.83 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 11.21 | 33.84 | 0.50 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 175.73 | 146.47 | 34.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 13.64 | 146.47 | 3.33 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 33.80 | 109.72 | 1.50 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 81.54 | 61.00 | 17.17 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.90 | 42.52 | 34.33 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 156.99 | 33.84 | 17.67 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 175.73 | 39.91 | 23.50 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 175.60 | 43.02 | 22.50 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.45 | 43.54 | 30.17 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 110.01 | 56.14 | 10.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 69.25 | 46.35 | 14.00 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 29.39 | 75.62 | 0.67 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 11.21 | 121.02 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 94.45 | 68.08 | 175.83 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 11.21 | 33.84 | 0.50 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 175.73 | 146.47 | 34.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 13.64 | 146.47 | 3.33 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 33.80 | 109.72 | 1.50 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 81.54 | 61.00 | 17.17 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.90 | 42.52 | 34.33 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 156.99 | 33.84 | 17.67 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 175.73 | 39.91 | 23.50 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 175.60 | 43.02 | 22.50 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.45 | 43.54 | 30.17 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 110.01 | 56.14 | 10.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 69.25 | 46.35 | 14.00 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 29.39 | 75.62 | 0.67 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 11.21 | 121.02 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 94.45 | 68.08 | 175.83 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 11.21 | 33.84 | 0.50 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 175.73 | 146.47 | 34.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 13.64 | 146.47 | 3.33 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 33.80 | 109.72 | 1.50 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 81.54 | 61.00 | 17.17 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.90 | 42.52 | 34.33 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 156.99 | 33.84 | 17.67 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 175.73 | 39.91 | 23.50 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 175.60 | 43.02 | 22.50 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.45 | 43.54 | 30.17 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 110.01 | 56.14 | 10.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 69.25 | 46.35 | 14.00 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 29.39 | 75.62 | 0.67 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 11.21 | 121.02 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 94.45 | 68.08 | 175.83 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 11.21 | 33.84 | 0.50 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 175.73 | 146.47 | 34.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.03 | 14.83 | 19.19 | 13.64 | 146.47 | 3.33 | 0.00 | 0.00 |
February | 46.61 | 23.32 | 23.29 | 33.80 | 109.72 | 1.50 | 0.00 | 0.00 |
March | 73.17 | 34.99 | 38.18 | 81.54 | 61.00 | 17.17 | 0.00 | 0.00 |
April | 99.35 | 59.69 | 39.66 | 123.90 | 42.52 | 34.33 | 0.00 | 0.00 |
May | 119.41 | 67.09 | 52.31 | 156.99 | 33.84 | 17.67 | 0.00 | 0.00 |
June | 135.78 | 79.42 | 56.37 | 175.73 | 39.91 | 23.50 | 0.00 | 0.00 |
July | 136.82 | 84.18 | 52.65 | 175.60 | 43.02 | 22.50 | 0.00 | 0.00 |
August | 113.92 | 64.87 | 49.06 | 148.45 | 43.54 | 30.17 | 0.00 | 0.00 |
September | 88.50 | 51.35 | 37.15 | 110.01 | 56.14 | 10.50 | 0.00 | 0.00 |
October | 56.25 | 27.88 | 28.37 | 69.25 | 46.35 | 14.00 | 0.00 | 0.00 |
November | 33.57 | 12.43 | 21.14 | 29.39 | 75.62 | 0.67 | 0.00 | 0.00 |
December | 23.10 | 11.36 | 11.74 | 11.21 | 121.02 | 0.50 | 0.00 | 0.00 |
Annual Sum or Average | 80.22 | 44.39 | 35.83 | 94.45 | 68.08 | 175.83 | 0.00 | 0.00 |
Minimum of Months | 23.10 | 11.36 | 11.74 | 11.21 | 33.84 | 0.50 | 0.00 | 0.00 |
Maximum of Months | 136.82 | 84.18 | 56.37 | 175.73 | 146.47 | 34.33 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW 1
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321077E+09 | 0.130250E+09 | 0.190827E+09 | 0.105981E+09 | 0.160529E+10 |
February | 0.421859E+09 | 0.206926E+09 | 0.214933E+09 | 0.230823E+09 | 0.113255E+10 |
March | 0.560804E+09 | 0.208912E+09 | 0.351892E+09 | 0.383660E+09 | 0.767359E+09 |
April | 0.791159E+09 | 0.390962E+09 | 0.400197E+09 | 0.791927E+09 | 0.528807E+09 |
May | 0.819750E+09 | 0.327517E+09 | 0.492233E+09 | 0.884098E+09 | 0.361748E+09 |
June | 0.929428E+09 | 0.402039E+09 | 0.527389E+09 | 0.112305E+10 | 0.302355E+09 |
July | 0.103337E+10 | 0.491100E+09 | 0.542272E+09 | 0.128079E+10 | 0.295364E+09 |
August | 0.900632E+09 | 0.411906E+09 | 0.488726E+09 | 0.112385E+10 | 0.335581E+09 |
September | 0.707262E+09 | 0.335301E+09 | 0.371962E+09 | 0.791404E+09 | 0.481570E+09 |
October | 0.511535E+09 | 0.228022E+09 | 0.283513E+09 | 0.440270E+09 | 0.601864E+09 |
November | 0.296124E+09 | 0.109989E+09 | 0.186135E+09 | 0.155462E+09 | 0.922370E+09 |
December | 0.236336E+09 | 0.112401E+09 | 0.123935E+09 | 0.105407E+09 | 0.140676E+10 |
Annual Sum or Average | 0.752934E+10 | 0.335532E+10 | 0.417401E+10 | 0.741673E+10 | 0.874161E+10 |
Minimum of Months | 0.236336E+09 | 0.109989E+09 | 0.123935E+09 | 0.105407E+09 | 0.295364E+09 |
Maximum of Months | 0.103337E+10 | 0.491100E+09 | 0.542272E+09 | 0.128079E+10 | 0.160529E+10 |
Report: WindowEnergyReportMonthly
For: OFFICE FRONT WALL WINDOW2
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.356105E+09 | 0.144460E+09 | 0.211646E+09 | 0.117543E+09 | 0.178042E+10 |
February | 0.467882E+09 | 0.229501E+09 | 0.238381E+09 | 0.256005E+09 | 0.125611E+10 |
March | 0.621986E+09 | 0.231704E+09 | 0.390282E+09 | 0.425516E+09 | 0.851075E+09 |
April | 0.877472E+09 | 0.433614E+09 | 0.443857E+09 | 0.878323E+09 | 0.586498E+09 |
May | 0.909181E+09 | 0.363247E+09 | 0.545934E+09 | 0.980550E+09 | 0.401213E+09 |
June | 0.103082E+10 | 0.445900E+09 | 0.584925E+09 | 0.124557E+10 | 0.335340E+09 |
July | 0.114611E+10 | 0.544677E+09 | 0.601432E+09 | 0.142052E+10 | 0.327587E+09 |
August | 0.998887E+09 | 0.456843E+09 | 0.542044E+09 | 0.124646E+10 | 0.372192E+09 |
September | 0.784422E+09 | 0.371881E+09 | 0.412541E+09 | 0.877743E+09 | 0.534107E+09 |
October | 0.567342E+09 | 0.252898E+09 | 0.314443E+09 | 0.488301E+09 | 0.667525E+09 |
November | 0.328430E+09 | 0.121988E+09 | 0.206442E+09 | 0.172422E+09 | 0.102300E+10 |
December | 0.262119E+09 | 0.124664E+09 | 0.137456E+09 | 0.116907E+09 | 0.156023E+10 |
Annual Sum or Average | 0.835076E+10 | 0.372138E+10 | 0.462938E+10 | 0.822586E+10 | 0.969529E+10 |
Minimum of Months | 0.262119E+09 | 0.121988E+09 | 0.137456E+09 | 0.116907E+09 | 0.327587E+09 |
Maximum of Months | 0.114611E+10 | 0.544677E+09 | 0.601432E+09 | 0.142052E+10 | 0.178042E+10 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW1
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61133653.05 | 0.00 | 61133653.05 | 0.00 | 0.714403E+09 |
February | 70004980.87 | 0.00 | 70004980.87 | 1176654.39 | 0.511098E+09 |
March | 0.116178E+09 | 3151.44 | 0.116175E+09 | 25327905.17 | 0.339542E+09 |
April | 0.130072E+09 | 885193.38 | 0.129187E+09 | 60984867.62 | 0.225316E+09 |
May | 0.175146E+09 | 6782558.59 | 0.168363E+09 | 0.129904E+09 | 0.142004E+09 |
June | 0.197654E+09 | 17855202.44 | 0.179799E+09 | 0.196640E+09 | 0.114618E+09 |
July | 0.191606E+09 | 12855895.14 | 0.178750E+09 | 0.193857E+09 | 0.113324E+09 |
August | 0.161054E+09 | 3355321.61 | 0.157698E+09 | 0.164300E+09 | 0.132880E+09 |
September | 0.119191E+09 | 79634.19 | 0.119111E+09 | 88583879.97 | 0.200795E+09 |
October | 91486996.33 | 0.00 | 91486996.33 | 29178920.82 | 0.258293E+09 |
November | 61931706.49 | 0.00 | 61931706.49 | 5045291.67 | 0.400094E+09 |
December | 41511702.95 | 0.00 | 41511702.95 | 0.00 | 0.612480E+09 |
Annual Sum or Average | 0.141697E+10 | 41816956.81 | 0.137515E+10 | 0.894997E+09 | 0.376485E+10 |
Minimum of Months | 41511702.95 | 0.00 | 41511702.95 | 0.00 | 0.113324E+09 |
Maximum of Months | 0.197654E+09 | 17855202.44 | 0.179799E+09 | 0.196640E+09 | 0.714403E+09 |
Report: WindowEnergyReportMonthly
For: OFFICE LEFT WALL WINDOW2
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 61133653.05 | 0.00 | 61133653.05 | 0.00 | 0.714403E+09 |
February | 70004980.88 | 0.00 | 70004980.88 | 1176654.39 | 0.511098E+09 |
March | 0.116178E+09 | 3151.44 | 0.116175E+09 | 25327905.17 | 0.339542E+09 |
April | 0.130072E+09 | 885193.38 | 0.129187E+09 | 60984867.62 | 0.225316E+09 |
May | 0.175146E+09 | 6782558.59 | 0.168363E+09 | 0.129904E+09 | 0.142004E+09 |
June | 0.197654E+09 | 17855202.44 | 0.179799E+09 | 0.196640E+09 | 0.114618E+09 |
July | 0.191606E+09 | 12855895.14 | 0.178750E+09 | 0.193857E+09 | 0.113324E+09 |
August | 0.161054E+09 | 3355321.61 | 0.157698E+09 | 0.164300E+09 | 0.132880E+09 |
September | 0.119191E+09 | 79634.19 | 0.119111E+09 | 88583879.97 | 0.200795E+09 |
October | 91486996.33 | 0.00 | 91486996.33 | 29178920.82 | 0.258293E+09 |
November | 61931706.49 | 0.00 | 61931706.49 | 5045291.67 | 0.400094E+09 |
December | 41511702.96 | 0.00 | 41511702.96 | 0.00 | 0.612480E+09 |
Annual Sum or Average | 0.141697E+10 | 41816956.81 | 0.137515E+10 | 0.894997E+09 | 0.376485E+10 |
Minimum of Months | 41511702.96 | 0.00 | 41511702.96 | 0.00 | 0.113324E+09 |
Maximum of Months | 0.197654E+09 | 17855202.44 | 0.179799E+09 | 0.196640E+09 | 0.714403E+09 |
Report: WindowEnergyReportMonthly
For: FINE STORAGE OFFICE FRONT WALL WINDOW
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.296565E+10 | 0.120306E+10 | 0.176259E+10 | 0.114290E+10 | 0.128405E+11 |
February | 0.389653E+10 | 0.191129E+10 | 0.198525E+10 | 0.233192E+10 | 0.901355E+10 |
March | 0.517991E+10 | 0.192963E+10 | 0.325028E+10 | 0.380076E+10 | 0.604755E+10 |
April | 0.730760E+10 | 0.361114E+10 | 0.369646E+10 | 0.727139E+10 | 0.428313E+10 |
May | 0.757168E+10 | 0.302513E+10 | 0.454656E+10 | 0.781008E+10 | 0.317518E+10 |
June | 0.858474E+10 | 0.371346E+10 | 0.487128E+10 | 0.985263E+10 | 0.271035E+10 |
July | 0.954483E+10 | 0.453608E+10 | 0.500875E+10 | 0.112693E+11 | 0.262749E+10 |
August | 0.831876E+10 | 0.380459E+10 | 0.451416E+10 | 0.982523E+10 | 0.299316E+10 |
September | 0.653268E+10 | 0.309702E+10 | 0.343566E+10 | 0.704493E+10 | 0.407775E+10 |
October | 0.472483E+10 | 0.210614E+10 | 0.261869E+10 | 0.421897E+10 | 0.465976E+10 |
November | 0.273517E+10 | 0.101592E+10 | 0.171925E+10 | 0.158566E+10 | 0.722720E+10 |
December | 0.218293E+10 | 0.103820E+10 | 0.114474E+10 | 0.110544E+10 | 0.111152E+11 |
Annual Sum or Average | 0.695453E+11 | 0.309917E+11 | 0.385537E+11 | 0.672592E+11 | 0.707708E+11 |
Minimum of Months | 0.218293E+10 | 0.101592E+10 | 0.114474E+10 | 0.110544E+10 | 0.262749E+10 |
Maximum of Months | 0.954483E+10 | 0.453608E+10 | 0.500875E+10 | 0.112693E+11 | 0.128405E+11 |
Report: WindowEnergyReportMonthly
For: FINE STORAGE OFFICE LEFT WALL WINDOW
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.487851E+09 | 0.00 | 0.487851E+09 | 818983.68 | 0.494599E+10 |
February | 0.558645E+09 | 0.00 | 0.558645E+09 | 18988768.95 | 0.350542E+10 |
March | 0.927106E+09 | 25148.74 | 0.927081E+09 | 0.263585E+09 | 0.228424E+10 |
April | 0.103798E+10 | 7063905.37 | 0.103092E+10 | 0.488041E+09 | 0.156776E+10 |
May | 0.139768E+10 | 54125293.85 | 0.134355E+10 | 0.941006E+09 | 0.108004E+10 |
June | 0.157729E+10 | 0.142486E+09 | 0.143481E+10 | 0.141215E+10 | 0.886823E+09 |
July | 0.152903E+10 | 0.102591E+09 | 0.142644E+10 | 0.137796E+10 | 0.868360E+09 |
August | 0.128522E+10 | 26775702.06 | 0.125844E+10 | 0.114654E+10 | 0.102363E+10 |
September | 0.951153E+09 | 635486.44 | 0.950517E+09 | 0.638563E+09 | 0.147159E+10 |
October | 0.730073E+09 | 0.00 | 0.730073E+09 | 0.282096E+09 | 0.172190E+10 |
November | 0.494219E+09 | 0.00 | 0.494219E+09 | 64782644.93 | 0.269626E+10 |
December | 0.331266E+09 | 0.00 | 0.331266E+09 | 235378.33 | 0.416277E+10 |
Annual Sum or Average | 0.113075E+11 | 0.333702E+09 | 0.109738E+11 | 0.663477E+10 | 0.262148E+11 |
Minimum of Months | 0.331266E+09 | 0.00 | 0.331266E+09 | 235378.33 | 0.868360E+09 |
Maximum of Months | 0.157729E+10 | 0.142486E+09 | 0.143481E+10 | 0.141215E+10 | 0.494599E+10 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C1
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 36528729.79 | 0.392308E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 81779314.21 | 0.265437E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.218401E+09 | 0.163385E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.321153E+09 | 0.110203E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.420494E+09 | 90637540.20 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.455496E+09 | 0.103453E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.470316E+09 | 0.115232E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397606E+09 | 0.116621E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.285153E+09 | 0.145509E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.185485E+09 | 0.124148E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 76185847.18 | 0.196011E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 0.324143E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.297862E+10 | 0.214709E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 90637540.20 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.470316E+09 | 0.392308E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C2
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 36528729.79 | 0.392308E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 81779314.21 | 0.265437E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.218401E+09 | 0.163385E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.321153E+09 | 0.110203E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.420494E+09 | 90637540.20 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.455496E+09 | 0.103453E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.470316E+09 | 0.115232E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397606E+09 | 0.116621E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.285153E+09 | 0.145509E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.185485E+09 | 0.124148E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 76185847.18 | 0.196011E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 0.324143E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.297862E+10 | 0.214709E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 90637540.20 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.470316E+09 | 0.392308E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C3
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 36528729.79 | 0.392308E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 81779314.21 | 0.265437E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.218401E+09 | 0.163385E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.321153E+09 | 0.110203E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.420494E+09 | 90637540.20 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.455496E+09 | 0.103453E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.470316E+09 | 0.115232E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397606E+09 | 0.116621E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.285153E+09 | 0.145509E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.185485E+09 | 0.124148E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 76185847.18 | 0.196011E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 0.324143E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.297862E+10 | 0.214709E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 90637540.20 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.470316E+09 | 0.392308E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C4
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 36528729.79 | 0.392308E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 81779314.21 | 0.265437E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.218401E+09 | 0.163385E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.321153E+09 | 0.110203E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.420494E+09 | 90637540.20 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.455496E+09 | 0.103453E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.470316E+09 | 0.115232E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397606E+09 | 0.116621E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.285153E+09 | 0.145509E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.185485E+09 | 0.124148E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 76185847.18 | 0.196011E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 0.324143E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.297862E+10 | 0.214709E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 90637540.20 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.470316E+09 | 0.392308E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R1C5
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 36528729.79 | 0.392308E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 81779314.21 | 0.265437E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.218401E+09 | 0.163385E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.321153E+09 | 0.110203E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.420494E+09 | 90637540.20 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.455496E+09 | 0.103453E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.470316E+09 | 0.115232E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397606E+09 | 0.116621E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.285153E+09 | 0.145509E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.185485E+09 | 0.124148E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 76185847.18 | 0.196011E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 0.324143E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.297862E+10 | 0.214709E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 90637540.20 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.470316E+09 | 0.392308E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C1
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 36528729.79 | 0.392308E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 81779314.21 | 0.265437E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.218401E+09 | 0.163385E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.321153E+09 | 0.110203E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.420494E+09 | 90637540.20 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.455496E+09 | 0.103453E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.470316E+09 | 0.115232E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397606E+09 | 0.116621E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.285153E+09 | 0.145509E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.185485E+09 | 0.124148E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 76185847.18 | 0.196011E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 0.324143E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.297862E+10 | 0.214709E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 90637540.20 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.470316E+09 | 0.392308E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C2
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 36528729.79 | 0.392308E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 81779314.21 | 0.265437E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.218401E+09 | 0.163385E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.321153E+09 | 0.110203E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.420494E+09 | 90637540.20 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.455496E+09 | 0.103453E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.470316E+09 | 0.115232E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397606E+09 | 0.116621E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.285153E+09 | 0.145509E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.185485E+09 | 0.124148E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 76185847.18 | 0.196011E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 0.324143E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.297862E+10 | 0.214709E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 90637540.20 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.470316E+09 | 0.392308E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C3
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 36528729.79 | 0.392308E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 81779314.21 | 0.265437E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.218401E+09 | 0.163385E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.321153E+09 | 0.110203E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.420494E+09 | 90637540.20 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.455496E+09 | 0.103453E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.470316E+09 | 0.115232E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397606E+09 | 0.116621E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.285153E+09 | 0.145509E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.185485E+09 | 0.124148E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 76185847.18 | 0.196011E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 0.324143E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.297862E+10 | 0.214709E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 90637540.20 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.470316E+09 | 0.392308E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C4
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 36528729.79 | 0.392308E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 81779314.21 | 0.265437E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.218401E+09 | 0.163385E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.321153E+09 | 0.110203E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.420494E+09 | 90637540.20 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.455496E+09 | 0.103453E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.470316E+09 | 0.115232E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397606E+09 | 0.116621E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.285153E+09 | 0.145509E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.185485E+09 | 0.124148E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 76185847.18 | 0.196011E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 0.324143E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.297862E+10 | 0.214709E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 90637540.20 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.470316E+09 | 0.392308E+09 |
Report: WindowEnergyReportMonthly
For: SKYLIGHT_R2C5
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 91140116.50 | 39731200.19 | 51408916.32 | 36528729.79 | 0.392308E+09 |
February | 0.112763E+09 | 56409773.14 | 56353277.23 | 81779314.21 | 0.265437E+09 |
March | 0.195982E+09 | 93715522.13 | 0.102266E+09 | 0.218401E+09 | 0.163385E+09 |
April | 0.257527E+09 | 0.154725E+09 | 0.102802E+09 | 0.321153E+09 | 0.110203E+09 |
May | 0.319817E+09 | 0.179706E+09 | 0.140112E+09 | 0.420494E+09 | 90637540.20 |
June | 0.351953E+09 | 0.205848E+09 | 0.146105E+09 | 0.455496E+09 | 0.103453E+09 |
July | 0.366470E+09 | 0.225455E+09 | 0.141015E+09 | 0.470316E+09 | 0.115232E+09 |
August | 0.305134E+09 | 0.173736E+09 | 0.131398E+09 | 0.397606E+09 | 0.116621E+09 |
September | 0.229385E+09 | 0.133104E+09 | 96280418.45 | 0.285153E+09 | 0.145509E+09 |
October | 0.150654E+09 | 74673752.66 | 75980173.28 | 0.185485E+09 | 0.124148E+09 |
November | 87018582.94 | 32228773.78 | 54789809.15 | 76185847.18 | 0.196011E+09 |
December | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 0.324143E+09 |
Annual Sum or Average | 0.252971E+10 | 0.139975E+10 | 0.112996E+10 | 0.297862E+10 | 0.214709E+10 |
Minimum of Months | 61863407.88 | 30418138.13 | 31445269.75 | 30023787.50 | 90637540.20 |
Maximum of Months | 0.366470E+09 | 0.225455E+09 | 0.146105E+09 | 0.470316E+09 | 0.392308E+09 |
Report: WindowZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 57.64 | 1771.72 | 298.48 | 102.56 | 195.92 | 0.00 | 0.00 |
February | 170.19 | 1377.89 | 425.66 | 180.40 | 245.26 | 0.00 | 0.00 |
March | 304.94 | 841.71 | 528.35 | 164.51 | 363.85 | 0.00 | 0.00 |
April | 684.28 | 596.98 | 744.13 | 318.81 | 425.32 | 0.00 | 0.00 |
May | 790.84 | 388.55 | 776.29 | 262.97 | 513.33 | 0.00 | 0.00 |
June | 1060.48 | 329.40 | 908.78 | 340.91 | 567.87 | 0.00 | 0.00 |
July | 1149.38 | 313.27 | 956.80 | 396.31 | 560.49 | 0.00 | 0.00 |
August | 1006.12 | 361.94 | 829.46 | 326.86 | 502.60 | 0.00 | 0.00 |
September | 708.07 | 542.54 | 667.46 | 272.89 | 394.57 | 0.00 | 0.00 |
October | 359.02 | 657.35 | 471.12 | 179.56 | 291.57 | 0.00 | 0.00 |
November | 117.17 | 1046.02 | 288.74 | 89.50 | 199.24 | 0.00 | 0.00 |
December | 62.47 | 1544.56 | 217.10 | 88.51 | 128.59 | 0.00 | 0.00 |
Annual Sum or Average | 541.12 | 811.73 | 593.42 | 227.05 | 366.37 | 0.00 | 0.00 |
Minimum of Months | 57.64 | 313.27 | 217.10 | 88.51 | 128.59 | 0.00 | 0.00 |
Maximum of Months | 1149.38 | 1771.72 | 956.80 | 396.31 | 567.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 332.34 | 6546.03 | 1289.39 | 449.17 | 840.22 | 0.00 | 0.00 |
February | 859.54 | 5062.61 | 1841.59 | 790.05 | 1051.54 | 0.00 | 0.00 |
March | 1466.48 | 3059.76 | 2280.10 | 720.45 | 1559.65 | 0.00 | 0.00 |
April | 2970.01 | 2233.69 | 3219.75 | 1395.91 | 1823.83 | 0.00 | 0.00 |
May | 3256.89 | 1578.33 | 3348.78 | 1149.66 | 2199.11 | 0.00 | 0.00 |
June | 4324.01 | 1365.83 | 3920.54 | 1487.63 | 2432.90 | 0.00 | 0.00 |
July | 4704.81 | 1288.06 | 4134.50 | 1731.88 | 2402.62 | 0.00 | 0.00 |
August | 4089.97 | 1493.27 | 3585.71 | 1430.47 | 2155.24 | 0.00 | 0.00 |
September | 2947.46 | 2124.09 | 2887.28 | 1195.08 | 1692.20 | 0.00 | 0.00 |
October | 1649.67 | 2351.80 | 2036.63 | 786.34 | 1250.29 | 0.00 | 0.00 |
November | 591.50 | 3783.25 | 1245.91 | 391.94 | 853.96 | 0.00 | 0.00 |
December | 342.61 | 5633.94 | 938.70 | 387.62 | 551.08 | 0.00 | 0.00 |
Annual Sum or Average | 2301.87 | 3034.10 | 2563.83 | 993.32 | 1570.51 | 0.00 | 0.00 |
Minimum of Months | 332.34 | 1288.06 | 938.70 | 387.62 | 551.08 | 0.00 | 0.00 |
Maximum of Months | 4704.81 | 6546.03 | 4134.50 | 1731.88 | 2432.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 136.38 | 1464.71 | 340.28 | 148.34 | 191.94 | 0.00 | 0.00 |
February | 338.04 | 1097.21 | 466.12 | 233.18 | 232.94 | 0.00 | 0.00 |
March | 815.42 | 610.01 | 731.71 | 349.89 | 381.82 | 0.00 | 0.00 |
April | 1239.02 | 425.17 | 993.55 | 596.93 | 396.61 | 0.00 | 0.00 |
May | 1569.94 | 338.40 | 1194.06 | 670.94 | 523.12 | 0.00 | 0.00 |
June | 1757.31 | 399.13 | 1357.84 | 794.17 | 563.68 | 0.00 | 0.00 |
July | 1755.96 | 430.23 | 1368.24 | 841.75 | 526.49 | 0.00 | 0.00 |
August | 1484.49 | 435.41 | 1139.24 | 648.65 | 490.58 | 0.00 | 0.00 |
September | 1100.13 | 561.38 | 884.97 | 513.52 | 371.45 | 0.00 | 0.00 |
October | 692.52 | 463.51 | 562.48 | 278.80 | 283.68 | 0.00 | 0.00 |
November | 293.93 | 756.22 | 335.72 | 124.34 | 211.38 | 0.00 | 0.00 |
December | 112.10 | 1210.21 | 230.97 | 113.57 | 117.40 | 0.00 | 0.00 |
Annual Sum or Average | 944.51 | 680.84 | 802.16 | 443.86 | 358.31 | 0.00 | 0.00 |
Minimum of Months | 112.10 | 338.40 | 230.97 | 113.57 | 117.40 | 0.00 | 0.00 |
Maximum of Months | 1757.31 | 1464.71 | 1368.24 | 841.75 | 563.68 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.154370E+09 | 0.474537E+10 | 0.799450E+09 | 0.274709E+09 | 0.524740E+09 | 0.00 | 0.00 |
February | 0.411717E+09 | 0.333339E+10 | 0.102975E+10 | 0.436427E+09 | 0.593324E+09 | 0.00 | 0.00 |
March | 0.816754E+09 | 0.225444E+10 | 0.141515E+10 | 0.440622E+09 | 0.974523E+09 | 0.00 | 0.00 |
April | 0.177365E+10 | 0.154737E+10 | 0.192877E+10 | 0.826347E+09 | 0.110243E+10 | 0.00 | 0.00 |
May | 0.211817E+10 | 0.104069E+10 | 0.207922E+10 | 0.704329E+09 | 0.137489E+10 | 0.00 | 0.00 |
June | 0.274877E+10 | 0.853795E+09 | 0.235556E+10 | 0.883649E+09 | 0.147191E+10 | 0.00 | 0.00 |
July | 0.307850E+10 | 0.839071E+09 | 0.256269E+10 | 0.106149E+10 | 0.150120E+10 | 0.00 | 0.00 |
August | 0.269479E+10 | 0.969420E+09 | 0.222163E+10 | 0.875460E+09 | 0.134617E+10 | 0.00 | 0.00 |
September | 0.183532E+10 | 0.140627E+10 | 0.173007E+10 | 0.707340E+09 | 0.102273E+10 | 0.00 | 0.00 |
October | 0.961599E+09 | 0.176064E+10 | 0.126185E+10 | 0.480921E+09 | 0.780930E+09 | 0.00 | 0.00 |
November | 0.303704E+09 | 0.271128E+10 | 0.748417E+09 | 0.231978E+09 | 0.516440E+09 | 0.00 | 0.00 |
December | 0.167330E+09 | 0.413696E+10 | 0.581479E+09 | 0.237065E+09 | 0.344414E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170647E+11 | 0.255987E+11 | 0.187140E+11 | 0.716034E+10 | 0.115537E+11 | 0.00 | 0.00 |
Minimum of Months | 0.154370E+09 | 0.839071E+09 | 0.581479E+09 | 0.231978E+09 | 0.344414E+09 | 0.00 | 0.00 |
Maximum of Months | 0.307850E+10 | 0.474537E+10 | 0.256269E+10 | 0.106149E+10 | 0.150120E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.890144E+09 | 0.175329E+11 | 0.345350E+10 | 0.120306E+10 | 0.225044E+10 | 0.00 | 0.00 |
February | 0.207940E+10 | 0.122475E+11 | 0.445518E+10 | 0.191129E+10 | 0.254389E+10 | 0.00 | 0.00 |
March | 0.392782E+10 | 0.819526E+10 | 0.610702E+10 | 0.192966E+10 | 0.417736E+10 | 0.00 | 0.00 |
April | 0.769826E+10 | 0.578973E+10 | 0.834558E+10 | 0.361821E+10 | 0.472738E+10 | 0.00 | 0.00 |
May | 0.872325E+10 | 0.422739E+10 | 0.896936E+10 | 0.307925E+10 | 0.589011E+10 | 0.00 | 0.00 |
June | 0.112078E+11 | 0.354023E+10 | 0.101620E+11 | 0.385594E+10 | 0.630609E+10 | 0.00 | 0.00 |
July | 0.126014E+11 | 0.344993E+10 | 0.110739E+11 | 0.463867E+10 | 0.643519E+10 | 0.00 | 0.00 |
August | 0.109546E+11 | 0.399959E+10 | 0.960397E+10 | 0.383137E+10 | 0.577260E+10 | 0.00 | 0.00 |
September | 0.763981E+10 | 0.550565E+10 | 0.748384E+10 | 0.309766E+10 | 0.438618E+10 | 0.00 | 0.00 |
October | 0.441848E+10 | 0.629907E+10 | 0.545491E+10 | 0.210614E+10 | 0.334877E+10 | 0.00 | 0.00 |
November | 0.153317E+10 | 0.980618E+10 | 0.322939E+10 | 0.101592E+10 | 0.221347E+10 | 0.00 | 0.00 |
December | 0.917659E+09 | 0.150899E+11 | 0.251420E+10 | 0.103820E+10 | 0.147600E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.725918E+11 | 0.956833E+11 | 0.808528E+11 | 0.313254E+11 | 0.495275E+11 | 0.00 | 0.00 |
Minimum of Months | 0.890144E+09 | 0.344993E+10 | 0.251420E+10 | 0.101592E+10 | 0.147600E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126014E+11 | 0.175329E+11 | 0.110739E+11 | 0.463867E+10 | 0.643519E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.365287E+09 | 0.392308E+10 | 0.911401E+09 | 0.397312E+09 | 0.514089E+09 | 0.00 | 0.00 |
February | 0.817793E+09 | 0.265437E+10 | 0.112763E+10 | 0.564098E+09 | 0.563533E+09 | 0.00 | 0.00 |
March | 0.218401E+10 | 0.163385E+10 | 0.195982E+10 | 0.937155E+09 | 0.102266E+10 | 0.00 | 0.00 |
April | 0.321153E+10 | 0.110203E+10 | 0.257527E+10 | 0.154725E+10 | 0.102802E+10 | 0.00 | 0.00 |
May | 0.420494E+10 | 0.906375E+09 | 0.319817E+10 | 0.179706E+10 | 0.140112E+10 | 0.00 | 0.00 |
June | 0.455496E+10 | 0.103453E+10 | 0.351953E+10 | 0.205848E+10 | 0.146105E+10 | 0.00 | 0.00 |
July | 0.470316E+10 | 0.115232E+10 | 0.366470E+10 | 0.225455E+10 | 0.141015E+10 | 0.00 | 0.00 |
August | 0.397606E+10 | 0.116621E+10 | 0.305134E+10 | 0.173736E+10 | 0.131398E+10 | 0.00 | 0.00 |
September | 0.285153E+10 | 0.145509E+10 | 0.229385E+10 | 0.133104E+10 | 0.962804E+09 | 0.00 | 0.00 |
October | 0.185485E+10 | 0.124148E+10 | 0.150654E+10 | 0.746738E+09 | 0.759802E+09 | 0.00 | 0.00 |
November | 0.761858E+09 | 0.196011E+10 | 0.870186E+09 | 0.322288E+09 | 0.547898E+09 | 0.00 | 0.00 |
December | 0.300238E+09 | 0.324143E+10 | 0.618634E+09 | 0.304181E+09 | 0.314453E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.297862E+11 | 0.214709E+11 | 0.252971E+11 | 0.139975E+11 | 0.112996E+11 | 0.00 | 0.00 |
Minimum of Months | 0.300238E+09 | 0.906375E+09 | 0.618634E+09 | 0.304181E+09 | 0.314453E+09 | 0.00 | 0.00 |
Maximum of Months | 0.470316E+10 | 0.392308E+10 | 0.366470E+10 | 0.225455E+10 | 0.146105E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.108465E+10 | -994289018.5 | 0.00 | 0.00 | 744.00 | 0.00 | -90365373.7 | 59.95 | 0.00 | 0.00 |
February | 0.101281E+10 | -931397035.2 | 0.00 | 0.00 | 672.00 | 0.00 | -81412327.2 | 59.95 | 0.00 | 0.00 |
March | 0.116679E+10 | -0.107787E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -88914170.1 | 59.95 | 0.00 | 0.00 |
April | 0.104629E+10 | -963506106.6 | 0.00 | 0.00 | 720.00 | 0.00 | -82779775.1 | 59.95 | 0.00 | 0.00 |
May | 0.102286E+10 | -944010832.6 | 0.00 | 0.00 | 744.00 | 0.00 | -78851193.0 | 59.95 | 0.00 | 0.00 |
June | 0.950626E+09 | -878259306.5 | 0.00 | 0.00 | 720.00 | 0.00 | -72367072.6 | 59.95 | 0.00 | 0.00 |
July | 0.874682E+09 | -801847191.7 | 0.00 | 0.00 | 744.00 | 0.00 | -72834957.5 | 59.95 | 0.00 | 0.00 |
August | 0.912630E+09 | -838910103.9 | 0.00 | 0.00 | 744.00 | 0.00 | -73719402.9 | 59.95 | 0.00 | 0.00 |
September | 0.864388E+09 | -790319438.8 | 0.00 | 0.00 | 720.00 | 0.00 | -74068398.6 | 59.95 | 0.00 | 0.00 |
October | 0.916490E+09 | -831284930.7 | 0.00 | 0.00 | 744.00 | 0.00 | -85205261.4 | 59.95 | 0.00 | 0.00 |
November | 0.937900E+09 | -852415893.0 | 0.00 | 0.00 | 720.00 | 0.00 | -85483824.2 | 59.95 | 0.00 | 0.00 |
December | 0.103655E+10 | -946293805.6 | 0.00 | 0.00 | 744.00 | 0.00 | -90255809.2 | 59.95 | 0.00 | 0.00 |
Annual Sum or Average | 0.118267E+11 | -0.108504E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -976257565.5 | 59.95 | 0.00 | 0.00 |
Minimum of Months | 0.864388E+09 | -0.107787E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -90365373.7 | 59.95 | 0.00 | 0.00 |
Maximum of Months | 0.116679E+10 | -790319438.8 | 0.00 | 0.00 | 744.00 | 0.00 | -72367072.6 | 59.95 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 214.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 334.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 285.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 400.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 414.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 410.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 326.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 254.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3807.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 428.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE HEATING COIL
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173647E+11 | 25975.49 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119381E+11 | 25975.49 | 01-FEB-00:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.763065E+10 | 25975.49 | 01-MAR-00:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.267424E+10 | 25975.49 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.227816E+09 | 25975.49 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 10538306.44 | 22943.54 | 05-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.124326E+09 | 25975.49 | 27-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109743E+10 | 25975.49 | 02-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.654465E+10 | 25975.49 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127038E+11 | 25975.49 | 01-DEC-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.603162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.173647E+11 | 25975.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE HEATING COIL
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.705891E+11 | 109165.05 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.460107E+11 | 109165.05 | 01-FEB-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228032E+11 | 109165.05 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.594902E+10 | 109165.05 | 02-APR-23:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168845E+09 | 31416.20 | 02-MAY-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49901183.99 | 21650.53 | 30-SEP-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185085E+10 | 86645.96 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262949E+11 | 109165.05 | 14-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.531056E+11 | 109165.05 | 01-DEC-06:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226822E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.705891E+11 | 109165.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT HEATING COIL
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.315386E+12 | 308140.86 | 18-JAN-19:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198887E+12 | 291334.95 | 01-FEB-20:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.861463E+11 | 196339.91 | 06-MAR-06:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144087E+11 | 103652.30 | 02-APR-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143575E+10 | 18394.02 | 27-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107612E+12 | 212415.84 | 26-NOV-03:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234713E+12 | 357490.36 | 09-DEC-01:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.958589E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.315386E+12 | 357490.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-OFFICE COOLING COIL
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.688097E+09 | 0.541491E+09 | 13093.37 | 18-APR-15:10 | 10477.79 | 0.00 |
May | 0.00 | 0.00 | 0.145559E+10 | 0.118936E+10 | 13448.10 | 31-MAY-15:50 | 11808.09 | 0.00 |
June | 0.00 | 0.00 | 0.703403E+10 | 0.559267E+10 | 34688.03 | 26-JUN-05:01 | 20783.07 | 0.00 |
July | 0.00 | 0.00 | 0.988865E+10 | 0.755082E+10 | 33610.70 | 26-JUL-05:01 | 21143.56 | 0.00 |
August | 0.00 | 0.00 | 0.100717E+11 | 0.771216E+10 | 36352.62 | 04-AUG-05:01 | 18355.59 | 0.00 |
September | 0.00 | 0.00 | 0.407637E+10 | 0.362643E+10 | 30562.62 | 11-SEP-05:01 | 17840.22 | 0.00 |
October | 0.00 | 0.00 | 75131960.14 | 74443272.73 | 5878.09 | 20-OCT-15:00 | 5878.09 | 0.00 |
November | 0.00 | 0.00 | 1793.58 | 1632.37 | 1.27 | 03-NOV-12:10 | 1.15 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.332896E+11 | 0.262874E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100717E+11 | 0.771216E+10 | 36352.62 | 21143.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-FINE STORAGE COOLING COIL
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:02 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.163115E+10 | 0.133222E+10 | 119989.15 | 17-APR-17:11 | 119989.15 | 0.00 |
May | 0.00 | 0.00 | 0.360482E+10 | 0.312065E+10 | 86542.48 | 31-MAY-17:06 | 80357.06 | 0.00 |
June | 0.00 | 0.00 | 0.236695E+11 | 0.199482E+11 | 146214.82 | 11-JUN-20:11 | 77197.75 | 0.00 |
July | 0.00 | 0.00 | 0.331415E+11 | 0.273769E+11 | 149365.36 | 04-JUL-02:31 | 68597.28 | 0.00 |
August | 0.00 | 0.00 | 0.294421E+11 | 0.241824E+11 | 151429.68 | 04-AUG-19:10 | 101438.98 | 0.00 |
September | 0.00 | 0.00 | 0.119423E+11 | 0.111944E+11 | 143364.84 | 11-SEP-19:50 | 116258.95 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.103431E+12 | 0.871547E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.331415E+11 | 0.273769E+11 | 151429.68 | 119989.15 | 0.00 |
Report: FanReportMonthly
For: ZONE3UNITHEATER ZONE3HIRADIANT FAN
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.460880E+11 | 0.54 | 17453.61 | 01-JAN-00:02 | 0.55 |
February | 0.396406E+11 | 0.51 | 17453.61 | 01-FEB-00:02 | 0.55 |
March | 0.306721E+11 | 0.36 | 17453.61 | 01-MAR-00:02 | 0.55 |
April | 0.103971E+11 | 0.13 | 17453.61 | 01-APR-00:03 | 0.55 |
May | 60040411.99 | 0.00 | 17453.61 | 02-MAY-03:10 | 0.55 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.502053E+10 | 0.06 | 17453.61 | 08-OCT-02:20 | 0.55 |
November | 0.287140E+11 | 0.35 | 17453.61 | 01-NOV-00:10 | 0.55 |
December | 0.458803E+11 | 0.54 | 17453.61 | 01-DEC-00:03 | 0.55 |
Annual Sum or Average | 0.206473E+12 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.460880E+11 | 0.54 | 17453.61 | 0.55 |
Report: FanReportMonthly
For: PSZ-OFFICE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.336161E+10 | 1.22 | 2626.94 | 02-JAN-08:70 | 1.43 |
February | 0.288943E+10 | 1.15 | 2626.94 | 01-FEB-08:70 | 1.44 |
March | 0.311072E+10 | 0.96 | 2626.94 | 01-MAR-07:20 | 1.44 |
April | 0.271293E+10 | 0.68 | 2626.94 | 01-APR-06:40 | 1.43 |
May | 0.271669E+10 | 0.56 | 2626.94 | 01-MAY-06:10 | 1.43 |
June | 0.275621E+10 | 0.59 | 2626.94 | 05-JUN-06:25 | 1.42 |
July | 0.268574E+10 | 0.56 | 2626.94 | 01-JUL-06:40 | 1.41 |
August | 0.286474E+10 | 0.59 | 2626.94 | 01-AUG-07:20 | 1.41 |
September | 0.262618E+10 | 0.56 | 2626.94 | 01-SEP-10:10 | 1.42 |
October | 0.265336E+10 | 0.57 | 2626.94 | 02-OCT-06:13 | 1.42 |
November | 0.279826E+10 | 0.92 | 2626.94 | 01-NOV-06:50 | 1.43 |
December | 0.312321E+10 | 1.20 | 2626.94 | 01-DEC-07:30 | 1.43 |
Annual Sum or Average | 0.342991E+11 | 0.79 | |||
Minimum of Months | 0.262618E+10 | 0.56 | 2626.94 | 1.41 | |
Maximum of Months | 0.336161E+10 | 1.22 | 2626.94 | 1.44 |
Report: FanReportMonthly
For: PSZ-FINE STORAGE_ADDAQ SUPPLY FAN
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163850E+11 | 1.24 | 11059.77 | 05-JAN-11:50 | 1.38 |
February | 0.138636E+11 | 1.22 | 11059.77 | 02-FEB-12:00 | 1.38 |
March | 0.140777E+11 | 1.07 | 11059.77 | 01-MAR-07:40 | 1.38 |
April | 0.116331E+11 | 0.78 | 11059.77 | 18-APR-09:50 | 1.36 |
May | 0.114451E+11 | 0.55 | 11059.77 | 04-MAY-13:30 | 1.36 |
June | 0.122367E+11 | 0.69 | 11059.77 | 10-JUN-11:30 | 1.36 |
July | 0.120599E+11 | 0.70 | 11059.77 | 21-JUL-11:30 | 1.36 |
August | 0.124642E+11 | 0.66 | 11059.77 | 01-AUG-07:50 | 1.35 |
September | 0.112044E+11 | 0.58 | 11059.77 | 01-SEP-11:00 | 1.37 |
October | 0.111746E+11 | 0.64 | 11059.77 | 19-OCT-06:05 | 1.38 |
November | 0.129765E+11 | 1.01 | 11059.77 | 10-NOV-07:20 | 1.38 |
December | 0.153824E+11 | 1.22 | 11059.77 | 29-DEC-07:40 | 1.38 |
Annual Sum or Average | 0.154903E+12 | 0.86 | |||
Minimum of Months | 0.111746E+11 | 0.55 | 11059.77 | 1.35 | |
Maximum of Months | 0.163850E+11 | 1.24 | 11059.77 | 1.38 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.336161E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.288943E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.311072E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.288445E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.307503E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.445354E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.502626E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.527247E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.362897E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.267215E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.279826E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.312321E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.422961E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.267215E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.527247E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.163850E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.138636E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.140777E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.120555E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.123625E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.181682E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.201809E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.197418E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.142598E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.111746E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.129765E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.153824E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.180628E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.111746E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.201809E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.336161E+10 | 0.00 | 0.173647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288943E+10 | 0.00 | 0.119381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311072E+10 | 0.00 | 0.763065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.271293E+10 | 0.688097E+09 | 0.267424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271669E+10 | 0.145559E+10 | 0.227816E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.275621E+10 | 0.703403E+10 | 10538306.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.268574E+10 | 0.988865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.286474E+10 | 0.100717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262618E+10 | 0.407637E+10 | 0.124326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.265336E+10 | 75131960.14 | 0.109743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279826E+10 | 1793.58 | 0.654465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.312321E+10 | 0.00 | 0.127038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342991E+11 | 0.332896E+11 | 0.603162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.262618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.336161E+10 | 0.100717E+11 | 0.173647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.163850E+11 | 0.00 | 0.705891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138636E+11 | 0.00 | 0.460107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140777E+11 | 0.00 | 0.228032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116331E+11 | 0.163115E+10 | 0.594902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114451E+11 | 0.360482E+10 | 0.168845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122367E+11 | 0.236695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120599E+11 | 0.331415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124642E+11 | 0.294421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112044E+11 | 0.119423E+11 | 49901183.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111746E+11 | 0.00 | 0.185085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129765E+11 | 0.00 | 0.262949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153824E+11 | 0.00 | 0.531056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154903E+12 | 0.103431E+12 | 0.226822E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163850E+11 | 0.331415E+11 | 0.705891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.336161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.271293E+10 | 0.00 | 0.00 | 0.00 | 0.171522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271669E+10 | 0.00 | 0.00 | 0.00 | 0.358336E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.275621E+10 | 0.00 | 0.00 | 0.00 | 0.169734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.268574E+10 | 0.00 | 0.00 | 0.00 | 0.234052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.286474E+10 | 0.00 | 0.00 | 0.00 | 0.240773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262618E+10 | 0.00 | 0.00 | 0.00 | 0.100279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.265336E+10 | 0.00 | 0.00 | 0.00 | 18793567.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279826E+10 | 0.00 | 0.00 | 0.00 | 473.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.312321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342991E+11 | 0.00 | 0.00 | 0.00 | 0.799703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.262618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.336161E+10 | 0.00 | 0.00 | 0.00 | 0.240773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.163850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116331E+11 | 0.00 | 0.00 | 0.00 | 0.422348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114451E+11 | 0.00 | 0.00 | 0.00 | 0.917368E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.122367E+11 | 0.00 | 0.00 | 0.00 | 0.593154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.120599E+11 | 0.00 | 0.00 | 0.00 | 0.812098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.124642E+11 | 0.00 | 0.00 | 0.00 | 0.727761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112044E+11 | 0.00 | 0.00 | 0.00 | 0.305542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154903E+12 | 0.00 | 0.00 | 0.00 | 0.257253E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.163850E+11 | 0.00 | 0.00 | 0.00 | 0.812098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE1 OFFICE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379035E+10 | 0.00 | 0.00 | 0.12 |
February | 54397740.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289860E+10 | 0.00 | 0.00 | 0.13 |
March | 0.253473E+09 | 0.00 | 0.00 | 858.72 | 0.00 | 0.219323E+10 | 6454576.96 | 0.00 | 0.14 |
April | 0.545534E+09 | 55559502.62 | 0.00 | 473128.02 | 5054.73 | 0.101868E+10 | 0.575646E+09 | 0.00 | 0.20 |
May | 0.281685E+09 | 69058726.10 | 0.00 | 2704757.65 | 0.00 | 62247989.15 | 0.325605E+10 | 0.00 | 0.59 |
June | 0.117853E+09 | 0.510236E+09 | 0.00 | 4870560.67 | 249577.18 | 0.00 | 0.247142E+10 | 0.00 | 0.60 |
July | 15587399.71 | 0.739314E+09 | 0.00 | 4846640.00 | 1298411.40 | 0.00 | 0.164774E+10 | 0.00 | 0.55 |
August | 39034382.67 | 0.759563E+09 | 0.00 | 4747256.00 | 32913.77 | 0.00 | 0.175990E+10 | 0.00 | 0.59 |
September | 0.303384E+09 | 0.166419E+09 | 0.00 | 4130672.68 | 117939.33 | 23536855.44 | 0.262735E+10 | 0.00 | 0.50 |
October | 0.105916E+10 | 0.00 | 0.00 | 358218.05 | 0.00 | 0.400155E+09 | 0.666304E+09 | 0.00 | 0.21 |
November | 0.457469E+09 | 0.00 | 0.00 | 97785.80 | 0.00 | 0.170899E+10 | 0.265539E+09 | 0.00 | 0.15 |
December | 19835337.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314917E+10 | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.314741E+10 | 0.230015E+10 | 0.00 | 22229877.60 | 1703896.41 | 0.152450E+11 | 0.132764E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Maximum of Months | 0.105916E+10 | 0.759563E+09 | 0.00 | 4870560.67 | 1298411.40 | 0.379035E+10 | 0.325605E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE2 FINE STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.638651E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121294E+11 | 0.00 | 0.00 | 0.17 |
February | 0.221065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749058E+10 | 0.00 | 0.00 | 0.18 |
March | 0.462737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306297E+10 | 0.00 | 0.00 | 0.19 |
April | 0.531970E+10 | 83613810.85 | 0.00 | 452741.97 | 5575678.20 | 0.489622E+09 | 0.667142E+09 | 0.00 | 0.20 |
May | 0.467129E+10 | 80380888.09 | 0.00 | 1787912.43 | 0.00 | 0.00 | 0.267559E+10 | 0.00 | 0.32 |
June | 0.178541E+10 | 0.105986E+10 | 0.00 | 12234649.39 | 0.00 | 0.00 | 0.619914E+10 | 0.00 | 0.48 |
July | 0.461177E+09 | 0.149086E+10 | 0.00 | 15593827.73 | 0.00 | 0.00 | 0.527090E+10 | 0.00 | 0.43 |
August | 0.684988E+09 | 0.147356E+10 | 0.00 | 15786402.45 | 0.00 | 0.00 | 0.544727E+10 | 0.00 | 0.46 |
September | 0.305869E+10 | 0.230430E+09 | 0.00 | 8051613.38 | 0.00 | 0.00 | 0.393411E+10 | 0.00 | 0.33 |
October | 0.547072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31706967.59 | 0.00 | 0.00 | 0.18 |
November | 0.372347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350195E+10 | 0.00 | 0.00 | 0.17 |
December | 0.139305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.881692E+10 | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.340452E+11 | 0.441871E+10 | 0.00 | 53907147.36 | 5575678.20 | 0.355232E+11 | 0.241942E+11 | 0.00 | 0.27 |
Minimum of Months | 0.461177E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.547072E+10 | 0.149086E+10 | 0.00 | 15786402.45 | 5575678.20 | 0.121294E+11 | 0.619914E+10 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ZONE3 BULK STORAGE
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:19:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.409765E+12 | 0.223013E+12 | 0.00 | 0.165584E+11 | 0.128114E+12 |
February | 0.442393E+12 | 0.156666E+12 | 0.00 | 0.126542E+11 | 0.855980E+11 |
March | 0.686175E+12 | 0.112737E+12 | 0.00 | 0.100817E+11 | 0.481198E+11 |
April | 0.824666E+12 | 0.607331E+11 | 0.00 | 0.847726E+10 | 0.229249E+11 |
May | 0.978389E+12 | 0.424120E+11 | 0.00 | 0.108135E+11 | 0.192488E+11 |
June | 0.104075E+13 | 0.473874E+11 | 0.00 | 0.920586E+10 | 0.506491E+11 |
July | 0.105415E+13 | 0.520799E+11 | 0.00 | 0.548459E+10 | 0.662141E+11 |
August | 0.918458E+12 | 0.532099E+11 | 0.00 | 0.604172E+10 | 0.619215E+11 |
September | 0.633820E+12 | 0.514106E+11 | 0.00 | 0.970310E+10 | 0.324731E+11 |
October | 0.439100E+12 | 0.476693E+11 | 0.00 | 0.762840E+10 | 0.146291E+11 |
November | 0.262480E+12 | 0.114671E+12 | 0.00 | 0.965752E+10 | 0.537697E+11 |
December | 0.210297E+12 | 0.177277E+12 | 0.00 | 0.133790E+11 | 0.997188E+11 |
Annual Sum or Average | 0.790045E+13 | 0.113927E+13 | 0.00 | 0.119685E+12 | 0.683381E+12 |
Minimum of Months | 0.210297E+12 | 0.424120E+11 | 0.00 | 0.548459E+10 | 0.146291E+11 |
Maximum of Months | 0.105415E+13 | 0.223013E+12 | 0.00 | 0.165584E+11 | 0.128114E+12 |