Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 18:23
Tabular Output Report in Format: HTML
Building: US+MF+CZ3B+gasfurnace+crawlspace+IECC_2024
Environment: ANNUAL ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2024-06-27 18:23:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 761807.72 | 19.53 | 35.25 |
Net Site Energy | 761807.72 | 19.53 | 35.25 |
Total Source Energy | 1635574.36 | 41.93 | 75.69 |
Net Source Energy | 1635574.36 | 41.93 | 75.69 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.22 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 17395.26 |
Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 33725.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 59440.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 13981.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 252763.87 | 163973.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23859.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 175355.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190015.26 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 388754.10 | 373053.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190015.26 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 0.00 | 33725.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 59440.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 13981.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 5863.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 38086.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 2437.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_dryer | 3888.48 | 79268.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_range | 0.00 | 67443.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_mels | 143183.64 | 17261.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 59304.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation | 8652.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
General | 15206.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190015.26 | |
Water Heater | 0.00 | 175355.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Unassigned | 0.00 | 33725.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 59440.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 13981.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 252763.87 | 163973.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 23859.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 175355.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190015.26 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 3.85 | 9.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 |
Other | 11.70 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 17.99 | 17.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.79 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2.14 | 5.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.87 |
Other | 6.48 | 4.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 9.97 | 9.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.87 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 388754.101 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 388754.101 | 100.00 |
Total On-Site and Utility Electric Sources | 388754.101 | 100.00 |
Total Electricity End Uses | 388754.101 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 190015.26 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 190015.26 | 100.00 |
Total Water End Uses | 190015.26 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 208.33 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DUMMY-HEAT-COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DUMMY-HEAT-COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DUMMY-HEAT-COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DUMMY-HEAT-COIL_UNIT1_BACKROW_BOTTOMFLOOR | DUMMY-HEAT-COIL_UNIT2_BACKROW_BOTTOMFLOOR | DUMMY-HEAT-COIL_UNIT3_BACKROW_BOTTOMFLOOR | DUMMY-HEAT-COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DUMMY-HEAT-COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DUMMY-HEAT-COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DUMMY-HEAT-COIL_UNIT1_BACKROW_MIDDLEFLOOR | DUMMY-HEAT-COIL_UNIT2_BACKROW_MIDDLEFLOOR | DUMMY-HEAT-COIL_UNIT3_BACKROW_MIDDLEFLOOR | DUMMY-HEAT-COIL_UNIT1_FRONTROW_TOPFLOOR | DUMMY-HEAT-COIL_UNIT2_FRONTROW_TOPFLOOR | DUMMY-HEAT-COIL_UNIT3_FRONTROW_TOPFLOOR | DUMMY-HEAT-COIL_UNIT1_BACKROW_TOPFLOOR | DUMMY-HEAT-COIL_UNIT2_BACKROW_TOPFLOOR | DUMMY-HEAT-COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |HEATING AND COOLING LOADS
| CRAWLSPACE | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
GeneralValue | |
Program Version and Build | EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 18:23 |
RunPeriod | ANNUAL |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [ft] | 3891.27 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 17103.09 | 6415.36 | 2136.19 | 6415.36 | 2136.19 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 12.43 | 8.29 | 24.89 | 8.29 | 24.89 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
CRAWLSPACE | 7794.39 | No | Yes | 19513.17 | 1.00 | 185.02 | 740.10 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.16 | No | Yes | 30553.25 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 4.3384 |
ATTIC | 7802.71 | No | Yes | 52795.56 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 4.3384 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 4.3384 |
Total | 39005.22 | 286601.37 | 16363.00 | 740.10 | 2126.74 | 2126.74 | 0.3230 | 1083.48 | 2.4036 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.5831 | 600.28 | 4.3384 | |||
Unconditioned Total | 17395.26 | 102861.98 | 1066.39 | 740.10 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | Tags | |
CRAWLSPACE | 7794.39 | No | Yes | 1.00 | CRAWLSPACE | GENERAL | CRAWLSPACE | 0.0000 | 0.00 | 0.0000 | |
BREEZEWAY | 1798.16 | No | Yes | 1.00 | BREEZEWAY | GENERAL | BREEZEWAY | 0.0000 | 0.00 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5831 | 600.28 | 4.3384 | |
ATTIC | 7802.71 | No | Yes | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5831 | 600.28 | 4.3384 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5831 | 600.28 | 4.3384 | |
Total | 39005.22 | 0.3230 | 1083.48 | 2.4036 | |||||||
Conditioned Total | 21609.96 | 0.5831 | 600.28 | 4.3384 | |||||||
Unconditioned Total | 17395.26 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [ft2] | Conditioned Area [ft2] | Unconditioned Area [ft2] | Not Part of Total Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
GENERAL | 39005.22 | 21609.96 | 17395.26 | 0.00 | 0.3230 | 1083.48 | 2.4036 |
Total | 39005.22 | 21609.96 | 17395.26 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 26-JUL-18:20 | 01-JAN-11:30 | - | - | - | - | - | - | - | - | - | - | 01-JAN-08:19 |
Heating | 0.00 | 0.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 36.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 11.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 39.43 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 159.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 95.17 | 190.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 0.00 | 0.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 36.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 11.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 3.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 1.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_dryer | 0.52 | 20.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_range | 0.00 | 9.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_mels | 22.66 | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 9.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Ventilation | 0.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
General | 3.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | |
Water Heater | 0.00 | 159.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Gasoline [kBtu] | Source Diesel [kBtu] | Source Coal [kBtu] | Source Fuel Oil No 1 [kBtu] | Source Fuel Oil No 2 [kBtu] | Source Propane [kBtu] | Source Other Fuel 1 [kBtu] | Source Other Fuel 2 [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 36558.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 188249.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 122590.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44279.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 800503.19 | 177746.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 75562.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 190084.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1231184.24 | 404390.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 1.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 8.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 37.04 | 8.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 56.97 | 18.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 0.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 20.52 | 4.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 4.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 31.56 | 10.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 491.98 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 327.43 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 379.50 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 486.89 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 326.27 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 377.10 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 472.52 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 313.77 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 367.04 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 468.18 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 312.12 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 364.68 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 434.84 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 430.48 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 536.14 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 381.86 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 377.84 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 539.54 |
Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | Sum of Air Terminal Maximum Flow Rates [ft3/min] | Adjusted Heating Design Air Flow Rate [ft3/min] | Adjusted Cooling Design Air Flow Rate [ft3/min] | Adjusted Main Design Air Flow Rate [ft3/min] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 491.98 | 491.98 | 491.98 | 491.98 | 491.98 | 491.98 | 1.00 | 1.00 | 491.98 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 327.43 | 327.43 | 327.43 | 327.43 | 327.43 | 327.43 | 1.00 | 1.00 | 327.43 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 379.50 | 379.50 | 379.50 | 379.50 | 379.50 | 379.50 | 1.00 | 1.00 | 379.50 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 486.89 | 486.89 | 486.89 | 486.89 | 486.89 | 486.89 | 1.00 | 1.00 | 486.89 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 326.27 | 326.27 | 326.27 | 326.27 | 326.27 | 326.27 | 1.00 | 1.00 | 326.27 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 377.10 | 377.10 | 377.10 | 377.10 | 377.10 | 377.10 | 1.00 | 1.00 | 377.10 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 472.52 | 472.52 | 472.52 | 472.52 | 472.52 | 472.52 | 1.00 | 1.00 | 472.52 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 313.77 | 313.77 | 313.77 | 313.77 | 313.77 | 313.77 | 1.00 | 1.00 | 313.77 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 367.04 | 367.04 | 367.04 | 367.04 | 367.04 | 367.04 | 1.00 | 1.00 | 367.04 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 468.18 | 468.18 | 468.18 | 468.18 | 468.18 | 468.18 | 1.00 | 1.00 | 468.18 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 312.12 | 312.12 | 312.12 | 312.12 | 312.12 | 312.12 | 1.00 | 1.00 | 312.12 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 364.68 | 364.68 | 364.68 | 364.68 | 364.68 | 364.68 | 1.00 | 1.00 | 364.68 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 536.14 | 536.14 | 536.14 | 536.14 | 536.14 | 536.14 | 1.00 | 1.00 | 536.14 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 377.84 | 377.84 | 377.84 | 377.84 | 377.84 | 377.84 | 1.00 | 1.00 | 377.84 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 430.48 | 430.48 | 430.48 | 430.48 | 430.48 | 430.48 | 1.00 | 1.00 | 430.48 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 539.54 | 539.54 | 539.54 | 539.54 | 539.54 | 539.54 | 1.00 | 1.00 | 539.54 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 381.86 | 381.86 | 381.86 | 381.86 | 381.86 | 381.86 | 1.00 | 1.00 | 381.86 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 434.84 | 434.84 | 434.84 | 434.84 | 434.84 | 434.84 | 1.00 | 1.00 | 434.84 |
Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | Supplemental Heating Coil Nominal Capacity [Btu/h] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 491.98 | 245.99 | 491.98 | 245.99 | 8736.72 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 327.43 | 163.71 | 327.43 | 163.71 | 7200.35 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 379.50 | 189.75 | 379.50 | 189.75 | 8737.36 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 486.89 | 243.44 | 486.89 | 243.44 | 8740.66 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 326.27 | 163.13 | 326.27 | 163.13 | 7201.66 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 377.10 | 188.55 | 377.10 | 188.55 | 8735.93 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 472.52 | 236.26 | 472.52 | 236.26 | 7210.24 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 313.77 | 156.88 | 313.77 | 156.88 | 5695.57 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 367.04 | 183.52 | 367.04 | 183.52 | 7212.27 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 468.18 | 234.09 | 468.18 | 234.09 | 7213.13 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 312.12 | 156.06 | 312.12 | 156.06 | 5695.99 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 364.68 | 182.34 | 364.68 | 182.34 | 7210.18 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 536.14 | 268.07 | 536.14 | 268.07 | 8932.95 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 377.84 | 188.92 | 377.84 | 188.92 | 7400.91 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 430.48 | 215.24 | 430.48 | 215.24 | 8935.33 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 539.54 | 269.77 | 539.54 | 269.77 | 8934.97 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 381.86 | 190.93 | 381.86 | 190.93 | 7401.10 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 434.84 | 217.42 | 434.84 | 217.42 | 8933.70 | 1.00 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 491.98 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 327.43 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 379.50 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 486.89 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 326.27 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 377.10 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 472.52 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 313.77 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 367.04 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 468.18 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 312.12 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 364.68 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 536.14 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 377.84 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 430.48 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 539.54 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 381.86 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 434.84 |
Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | Design Size Speed 2 Rated Sensible Heat Ratio | Design Size Speed 1 Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 491.98 | 245.99 | 15961.60 | 0.665067 | 0.773100 | 0.773100 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 327.43 | 163.71 | 10809.07 | 0.450378 | 0.766898 | 0.766898 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 379.50 | 189.75 | 12510.78 | 0.521282 | 0.767309 | 0.767309 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 486.89 | 243.44 | 15792.31 | 0.658013 | 0.773180 | 0.773180 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 326.27 | 163.13 | 10774.53 | 0.448939 | 0.766796 | 0.766796 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 377.10 | 188.55 | 12393.34 | 0.516389 | 0.768226 | 0.768226 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 472.52 | 236.26 | 15394.29 | 0.641429 | 0.771843 | 0.771843 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 313.77 | 156.88 | 10342.99 | 0.430958 | 0.767334 | 0.767334 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 367.04 | 183.52 | 12125.00 | 0.505208 | 0.766696 | 0.766696 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 468.18 | 234.09 | 15236.47 | 0.634853 | 0.772171 | 0.772171 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 312.12 | 156.06 | 10294.03 | 0.428918 | 0.767178 | 0.767178 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 364.68 | 182.34 | 12054.26 | 0.502261 | 0.766520 | 0.766520 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 536.14 | 268.07 | 17270.13 | 0.719589 | 0.776275 | 0.776275 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 377.84 | 188.92 | 12214.62 | 0.508942 | 0.775190 | 0.775190 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 430.48 | 215.24 | 13990.55 | 0.582939 | 0.772581 | 0.772581 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 539.54 | 269.77 | 17340.16 | 0.722507 | 0.776970 | 0.776970 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 381.86 | 190.93 | 12386.22 | 0.516092 | 0.773170 | 0.773170 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 434.84 | 217.42 | 14120.76 | 0.588365 | 0.772826 | 0.772826 |
Design Size Stage 2 Nominal Capacity [Btu/h] | Design Size Stage 1 Nominal Capacity [Btu/h] | |
DUMMY-HEAT-COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 28961.62 | 14480.81 |
DUMMY-HEAT-COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 20076.67 | 10038.34 |
DUMMY-HEAT-COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 22888.43 | 11444.22 |
DUMMY-HEAT-COIL_UNIT1_BACKROW_BOTTOMFLOOR | 28686.85 | 14343.42 |
DUMMY-HEAT-COIL_UNIT2_BACKROW_BOTTOMFLOOR | 20014.09 | 10007.05 |
DUMMY-HEAT-COIL_UNIT3_BACKROW_BOTTOMFLOOR | 22758.71 | 11379.36 |
DUMMY-HEAT-COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 27910.24 | 13955.12 |
DUMMY-HEAT-COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 19338.78 | 9669.39 |
DUMMY-HEAT-COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 22215.20 | 11107.60 |
DUMMY-HEAT-COIL_UNIT1_BACKROW_MIDDLEFLOOR | 27676.26 | 13838.13 |
DUMMY-HEAT-COIL_UNIT2_BACKROW_MIDDLEFLOOR | 19249.73 | 9624.87 |
DUMMY-HEAT-COIL_UNIT3_BACKROW_MIDDLEFLOOR | 22087.83 | 11043.92 |
DUMMY-HEAT-COIL_UNIT1_FRONTROW_TOPFLOOR | 31346.31 | 15673.15 |
DUMMY-HEAT-COIL_UNIT2_FRONTROW_TOPFLOOR | 22798.93 | 11399.47 |
DUMMY-HEAT-COIL_UNIT3_FRONTROW_TOPFLOOR | 25641.39 | 12820.69 |
DUMMY-HEAT-COIL_UNIT1_BACKROW_TOPFLOOR | 31530.04 | 15765.02 |
DUMMY-HEAT-COIL_UNIT2_BACKROW_TOPFLOOR | 23015.92 | 11507.96 |
DUMMY-HEAT-COIL_UNIT3_BACKROW_TOPFLOOR | 25876.75 | 12938.38 |
Design Size Nominal Capacity [Btu/h] | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 10047.23 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 8280.40 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 10047.97 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 10051.76 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 8281.90 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 10046.32 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 8291.78 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 6549.91 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 8294.11 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 8295.10 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 6550.39 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 8291.71 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 10272.89 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 8511.04 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 10275.63 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 10275.21 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 8511.27 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 10273.76 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 2.09 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDF | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
BGWALL_UPPER_SDR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDB | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_SDL | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
VersionVersion ID | |
1 | 23.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | No | Yes | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.200 | 0.200 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 54.59 | 48.72 | 47.12 | 48.51 | 56.43 | 65.30 | 73.65 | 79.68 | 81.45 | 78.62 | 71.78 | 63.16 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {ft} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Sensor Height Above Ground {ft} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 32.810 | 0.140 | 885.870 | 4.921 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {ft} | Standard Pressure at Elevation {psi} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 3891.27 | 13. | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{F} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} | Fixed Default Water Mains Temperature{F} | |
1 | Correlation | NA | 64.29 | 37.98 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | US+MF+CZ3B+gasfurnace+crawlspace+IECC_2024 | 0.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Algorithm {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
Space Heat Balance Sizing |
Space Heat Balance Simulation |
|
1 | ThirdOrderBackwardDifference | No | No |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Gradient Coefficient {F/ft} | |
1 | 0.220 | 1213.970 | 0.003566 |
Material Name | ThermalResistance {m2-K/w} | Roughness | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | Absorptance:Thermal | Absorptance:Solar | Absorptance:Visible | |
1 | SHEATHING_CONSOL_LAYER | 0.1351 | Rough | 0.0417 | 9.402E-002 | 42.764 | 0.280 | 0.9000 | 0.7000 | 0.7000 |
2 | CEIL_CONSOL_LAYER | 6.1981 | Rough | 1.2550 | 6.172E-002 | 2.618 | 0.185 | 0.9000 | 0.7000 | 0.7000 |
3 | FLOOR_CONSOL_LAYER | 2.8450 | Rough | 0.4584 | 4.910E-002 | 3.438 | 0.219 | 0.9000 | 0.7000 | 0.7000 |
4 | BSMTWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
5 | CRAWLWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
6 | WALL_CONSOL_LAYER | 2.4438 | Rough | 0.4584 | 5.717E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
7 | VERY HIGH REFLECTIVITY SURFACE | 2.1097E-006 | Smooth | 0.0016 | 237.000 | 168.680 | 0.216 | 0.9000 | 5.0000E-002 | 5.0000E-002 |
8 | GYPSUMBOARD-5/16IN | 5.0054E-002 | Rough | 0.0260 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
9 | COPPERPIPE | 4.7506E-005 | MediumRough | 0.0625 | 401.000 | 140.026 | 0.200 | 0.9000 | 0.6500 | 0.6500 |
10 | F08 METAL SURFACE | 1.7668E-005 | Smooth | 0.0026 | 45.280 | 488.437 | 0.119 | 0.9000 | 0.7000 | 0.7000 |
11 | CONCRETE_4IN | 7.7356E-002 | Rough | 0.3330 | 1.312 | 140.014 | 0.111 | 0.9000 | 0.7000 | 0.7000 |
12 | ASPHALT_SHINGLE | 7.7448E-002 | MediumRough | 0.0208 | 8.186E-002 | 70.000 | 0.300 | 0.9000 | 0.7500 | 0.7000 |
13 | WOOD_SHINGLE | 0.1115 | MediumSmooth | 0.0417 | 0.114 | 26.600 | 0.390 | 0.9000 | 0.7000 | 0.7000 |
14 | SLATE_SHINGLE | 8.8061E-003 | MediumSmooth | 0.0417 | 1.442 | 100.000 | 0.300 | 0.9000 | 0.7000 | 0.7000 |
15 | CEMENT_STUCCO | 2.6422E-002 | MediumSmooth | 0.0625 | 0.721 | 116.464 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
16 | SYN_STUCCO | 3.5237E-002 | MediumSmooth | 0.0100 | 8.650E-002 | 24.971 | 0.210 | 0.7000 | 0.7000 | 0.7000 |
17 | DRYWALL_1/2IN | 7.9331E-002 | MediumSmooth | 0.0417 | 0.160 | 50.000 | 0.260 | 0.9000 | 0.7000 | 0.7000 |
18 | OSB_5/8IN | 0.1365 | MediumSmooth | 0.0521 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
19 | OSB_7/16IN | 9.5550E-002 | MediumSmooth | 0.0365 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
20 | BLOWN_R30 | 5.1614 | MediumRough | 0.6975 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
21 | BLOWN_R30_TOP | 2.8489 | MediumRough | 0.3849 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
22 | PLYWOOD_3/4IN | 0.1650 | Rough | 0.0625 | 0.115 | 34.003 | 0.161 | 0.9000 | 0.7000 | 0.7000 |
23 | BATT_R19 | 7.3089 | MediumRough | 0.0833 | 3.475E-003 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
24 | LUMBER_2X4 | 0.7709 | Rough | 0.2920 | 0.115 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
25 | CARPET_N_PAD | 0.4224 | MediumSmooth | 0.0833 | 6.013E-002 | 2.000 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
26 | BATT_R13 | 2.2936 | MediumRough | 0.2917 | 3.876E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
27 | OSB_1/2IN | 0.1092 | MediumSmooth | 0.0417 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
28 | SOIL_12IN | 0.1761 | Rough | 1.0000 | 1.731 | 115.011 | 0.056 | 0.9000 | 0.7000 | 0.7000 |
29 | DOOR_CONST | 0.5870 | Smooth | 0.1387 | 7.201E-002 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
30 | GYP_BOARD_1/2IN | 8.0130E-002 | Rough | 0.0417 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
31 | STD WOOD 6INCH | 1.2500 | MediumSmooth | 0.4921 | 0.120 | 33.711 | 0.289 | 0.9000 | 0.7000 | 0.7000 |
32 | PIPE INSULATION | 1.2255 | VeryRough | 0.1334 | 3.317E-002 | 5.681 | 0.200 | 0.9000 | 0.5000 | 0.5000 |
33 | MANF_WALL_AIRGAP | 0.1200 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
34 | BLDG_PAPER_FELT | 1.0567E-002 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
35 | R_HIGH | 177.0000 | MediumRough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
36 | CLEAR ACRYLIC PLASTIC | 3.3333E-003 | VerySmooth | 0.0098 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
37 | DIFFUSING ACRYLIC PLASTIC | 2.4444E-003 | VerySmooth | 0.0072 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
38 | INT_BLIND | 0.0000 | Rough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.0000 | 0.0000 | 0.0000 |
39 | GLASS | 0.4127 | VerySmooth | 0.1373 | 0.101 | 0.000 | 0.000 | 0.8400 | 0.0000 | 0.0000 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Name | Combined convective/radiative film coefficient {Btu/h-ft2-F} | User selected Constant Temperature {F} | Coefficient modifying the constant temperature term | Coefficient modifying the external dry bulb temperature term | Coefficient modifying the ground temperature term | Coefficient modifying the wind speed term {s/m} | Coefficient modifying the zone air temperature term | Constant Temperature Schedule Name | Sinusoidal Variation | Period of Sinusoidal Variation | Previous Other Side Temperature Coefficient | Minimum Other Side Temperature {F} | Maximum Other Side Temperature {F} | |
1 | SURFPROPOTHSDCOEFSLABAVERAGE | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABAVERAGESURFACETEMP | NO | 24.000 | 0.000 | N/A | N/A |
2 | SURFPROPOTHSDCOEFSLABPERIMETER | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABPERIMETERTEMP | NO | 24.000 | 0.000 | N/A | N/A |
3 | SURFPROPOTHSDCOEFSLABCORE | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABCORETEMP | NO | 24.000 | 0.000 | N/A | N/A |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{F} |
Surface Convection Coefficient Lower Limit {Btu/h-ft2-F} |
Surface Convection Coefficient Upper Limit {Btu/h-ft2-F} |
|
1 | CTF - ConductionTransferFunction | 392. | 0.02 | 176.1 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 60 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 21 | 186 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {ft} | Origin Y-Coordinate {ft} | Origin Z-Coordinate {ft} | Centroid X-Coordinate {ft} | Centroid Y-Coordinate {ft} | Centroid Z-Coordinate {ft} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {ft} | Maximum X {ft} | Minimum Y {ft} | Maximum Y {ft} | Minimum Z {ft} | Maximum Z {ft} | Ceiling Height {ft} | Volume {ft3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {ft2} | Exterior Gross Wall Area {ft2} | Exterior Net Wall Area {ft2} | Exterior Window Area {ft2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CRAWLSPACE | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.51 | -0.8 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | -2.0 | 0.49 | 2.49 | 19513.15 | TARP | DOE-2 | 7794.37 | 185.05 | 185.05 | 0.00 | 15 | 0 | 0 | Yes |
2 | BREEZEWAY | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.55 | 13.26 | 1 | 1 | 1 | 0.00 | 119.89 | 30.05 | 35.04 | 0.49 | 25.99 | 17.00 | 30553.07 | TARP | DOE-2 | 1798.18 | 0.00 | 0.00 | 0.00 | 4 | 0 | 0 | Yes |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
15 | ATTIC | 0.0 | -134.9 | 51.61 | 0.00 | 59.94 | 32.55 | 29.56 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | 25.99 | 39.54 | 6.76 | 52795.39 | TARP | DOE-2 | 7802.66 | 881.33 | 881.33 | 0.00 | 11 | 0 | 0 | Yes |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
Zone Name | Floor Area {ft2} | # Occupants | Area per Occupant {ft2/person} | Occupant per Area {person/ft2} | Interior Lighting {Btu/h-ft2} | Electric Load {Btu/h-ft2} | Gas Load {Btu/h-ft2} | Other Load {Btu/h-ft2} | Hot Water Eq {Btu/h-ft2} | Steam Equipment {Btu/h-ft2} | Sum Loads per Area {Btu/h-ft2} | Outdoor Controlled Baseboard Heat | |
1 | CRAWLSPACE | 7794.37 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
2 | BREEZEWAY | 1798.18 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
15 | ATTIC | 7802.66 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 1.985 | 2.353 | 0.000 | 0.000 | 0.000 | 4.921 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Number of People {} | People/Floor Area {person/ft2} | Floor Area per person {ft2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
2 | PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
3 | PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
4 | PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
5 | PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
6 | PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
7 | PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
8 | PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
9 | PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
10 | PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
11 | PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
12 | PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
13 | PEOPLE_UNIT1_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
14 | PEOPLE_UNIT2_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
15 | PEOPLE_UNIT3_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
16 | PEOPLE_UNIT1_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
17 | PEOPLE_UNIT2_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
18 | PEOPLE_UNIT3_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Lighting Level {Btu/h} | Lights/Floor Area {Btu/h-ft2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {Btu/h} | Nominal Maximum Lighting Level {Btu/h} | |
1 | LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
2 | LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
3 | LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
4 | LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
5 | LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
6 | LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
7 | LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
8 | LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
9 | LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
10 | LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
11 | LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
12 | LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
13 | LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
14 | LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
15 | LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
16 | LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
17 | LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
18 | LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
19 | LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
20 | LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
21 | LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
22 | LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
23 | LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
24 | LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
25 | LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
26 | LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
27 | LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
28 | LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
29 | LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
30 | LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
31 | LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
32 | LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
33 | LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
34 | LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
35 | LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
36 | LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
1 | DISHWASHER1_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
2 | REFRIGERATOR1_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
3 | CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
4 | GAS_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
5 | GAS_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
6 | TELEVISION1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
7 | GAS_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
8 | IECC_ADJ1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
9 | DISHWASHER2_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
10 | REFRIGERATOR2_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
11 | CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
12 | GAS_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
13 | GAS_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
14 | TELEVISION2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
15 | GAS_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
16 | IECC_ADJ2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
17 | DISHWASHER3_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
18 | REFRIGERATOR3_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
19 | CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
20 | GAS_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
21 | GAS_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
22 | TELEVISION3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
23 | GAS_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
24 | IECC_ADJ3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
25 | DISHWASHER1_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
26 | REFRIGERATOR1_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
27 | CLOTHESWASHER1_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
28 | GAS_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
29 | GAS_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
30 | TELEVISION1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
31 | GAS_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
32 | IECC_ADJ1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
33 | DISHWASHER2_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
34 | REFRIGERATOR2_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
35 | CLOTHESWASHER2_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
36 | GAS_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
37 | GAS_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
38 | TELEVISION2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
39 | GAS_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
40 | IECC_ADJ2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
41 | DISHWASHER3_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
42 | REFRIGERATOR3_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
43 | CLOTHESWASHER3_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
44 | GAS_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
45 | GAS_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
46 | TELEVISION3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
47 | GAS_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
48 | IECC_ADJ3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
49 | DISHWASHER1_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
50 | REFRIGERATOR1_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
51 | CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
52 | GAS_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
53 | GAS_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
54 | TELEVISION1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
55 | GAS_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
56 | IECC_ADJ1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
57 | DISHWASHER2_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
58 | REFRIGERATOR2_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
59 | CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
60 | GAS_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
61 | GAS_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
62 | TELEVISION2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
63 | GAS_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
64 | IECC_ADJ2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
65 | DISHWASHER3_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
66 | REFRIGERATOR3_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
67 | CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
68 | GAS_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
69 | GAS_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
70 | TELEVISION3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
71 | GAS_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
72 | IECC_ADJ3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
73 | DISHWASHER1_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
74 | REFRIGERATOR1_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
75 | CLOTHESWASHER1_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
76 | GAS_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
77 | GAS_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
78 | TELEVISION1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
79 | GAS_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
80 | IECC_ADJ1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
81 | DISHWASHER2_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
82 | REFRIGERATOR2_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
83 | CLOTHESWASHER2_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
84 | GAS_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
85 | GAS_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
86 | TELEVISION2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
87 | GAS_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
88 | IECC_ADJ2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
89 | DISHWASHER3_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
90 | REFRIGERATOR3_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
91 | CLOTHESWASHER3_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
92 | GAS_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
93 | GAS_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
94 | TELEVISION3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
95 | GAS_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
96 | IECC_ADJ3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
97 | DISHWASHER1_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
98 | REFRIGERATOR1_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
99 | CLOTHESWASHER1_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
100 | GAS_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
101 | GAS_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
102 | TELEVISION1_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
103 | GAS_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
104 | IECC_ADJ1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
105 | DISHWASHER2_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
106 | REFRIGERATOR2_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
107 | CLOTHESWASHER2_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
108 | GAS_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
109 | GAS_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
110 | TELEVISION2_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
111 | GAS_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
112 | IECC_ADJ2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
113 | DISHWASHER3_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
114 | REFRIGERATOR3_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
115 | CLOTHESWASHER3_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
116 | GAS_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
117 | GAS_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
118 | TELEVISION3_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
119 | GAS_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
120 | IECC_ADJ3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
121 | DISHWASHER1_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
122 | REFRIGERATOR1_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
123 | CLOTHESWASHER1_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
124 | GAS_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
125 | GAS_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
126 | TELEVISION1_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
127 | GAS_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
128 | IECC_ADJ1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
129 | DISHWASHER2_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
130 | REFRIGERATOR2_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
131 | CLOTHESWASHER2_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
132 | GAS_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
133 | GAS_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
134 | TELEVISION2_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
135 | GAS_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
136 | IECC_ADJ2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
137 | DISHWASHER3_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
138 | REFRIGERATOR3_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
139 | CLOTHESWASHER3_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
140 | GAS_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 55.199 | 0.046 | 8.089 | 0.000 | 1.000 | 0.000 | 0.000 | gas_dryer | 0.000 | 55.199 |
141 | GAS_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | gas_range | 0.000 | 0.000 |
142 | TELEVISION3_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
143 | GAS_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1343.274 | 1.119 | 196.845 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 694.502 | 1343.274 |
144 | IECC_ADJ3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 556.368 | 0.463 | 81.531 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 287.655 | 556.368 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
1 | GAS_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
2 | GAS_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
3 | GAS_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
4 | GAS_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
5 | GAS_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
6 | GAS_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
7 | GAS_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
8 | GAS_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
9 | GAS_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
10 | GAS_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
11 | GAS_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
12 | GAS_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
13 | GAS_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
14 | GAS_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
15 | GAS_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
16 | GAS_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
17 | GAS_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
18 | GAS_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
19 | GAS_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
20 | GAS_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
21 | GAS_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
22 | GAS_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
23 | GAS_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
24 | GAS_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
25 | GAS_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
26 | GAS_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
27 | GAS_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
28 | GAS_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
29 | GAS_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
30 | GAS_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
31 | GAS_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
32 | GAS_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
33 | GAS_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
34 | GAS_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
35 | GAS_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
36 | GAS_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
37 | GAS_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
38 | GAS_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
39 | GAS_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
40 | GAS_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
41 | GAS_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
42 | GAS_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
43 | GAS_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
44 | GAS_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
45 | GAS_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
46 | GAS_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
47 | GAS_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
48 | GAS_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
49 | GAS_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
50 | GAS_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
51 | GAS_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
52 | GAS_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1125.237 | 0.937 | 164.894 | 5.000E-002 | 0.100 | 0.850 | 0.000 | gas_dryer | 0.000 | 1125.237 |
53 | GAS_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1538.075 | 1.281 | 225.392 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_range | 36.215 | 1538.075 |
54 | GAS_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 161.937 | 0.135 | 23.730 | 6.000E-002 | 0.690 | 0.250 | 0.000 | gas_mels | 83.724 | 161.937 |
Construction Name | Index | #Layers | #CTFs | Time Step {Hours} | ThermalConductance {Btu/h-ft2-F} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | EXTERIOR WALL | 1 | 5 | 11 | 0.167 | 0.0631 | 0.700 | 0.900 | 0.700 | 0.700 | MediumSmooth |
2 | CEILING-FLOOR-LAYER | 3 | 1 | 5 | 0.167 | 0.228 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | EXTERIOR FLOOR | 4 | 3 | 8 | 0.167 | 0.0513 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
4 | INTERIOR FLOOR | 5 | 2 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
5 | INTERIOR CEILING | 6 | 2 | 10 | 0.167 | 0.0281 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
6 | ATTIC FLOOR | 7 | 2 | 10 | 0.167 | 0.0281 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | INTERIORWALL | 9 | 3 | 5 | 0.167 | 0.597 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | EXTERIOR ROOF | 11 | 2 | 4 | 0.167 | 0.943 | 0.900 | 0.900 | 0.750 | 0.700 | MediumRough |
9 | EXTERIOR DOOR | 14 | 1 | 5 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | GABLE_END | 16 | 5 | 6 | 0.167 | 0.428 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
11 | CRAWL WALL | 24 | 1 | 5 | 0.167 | 2.28 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
12 | iz-EXTERIOR FLOOR | 25 | 3 | 8 | 0.167 | 0.0513 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | ThermalResistance {m2-K/w} | |
1 | SYN_STUCCO | 0.0098 | 0.086 | 24.971 | 0.210 | 0.3524E-01 |
2 | SHEATHING_CONSOL_LAYER | 0.0417 | 0.094 | 42.764 | 0.280 | 0.1351 |
3 | OSB_7/16IN | 0.0364 | 0.116 | 34.000 | 0.290 | 0.9555E-01 |
4 | WALL_CONSOL_LAYER | 0.4584 | 0.057 | 7.541 | 0.248 | 2.444 |
5 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
6 | LUMBER_2X4 | 0.2920 | 0.115 | 32.003 | 0.183 | 0.7709 |
7 | FLOOR_CONSOL_LAYER | 0.4584 | 0.049 | 3.438 | 0.219 | 2.845 |
8 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
9 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
10 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
11 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
12 | CEIL_CONSOL_LAYER | 1.2550 | 0.062 | 2.618 | 0.185 | 6.198 |
13 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
14 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
15 | CEIL_CONSOL_LAYER | 1.2550 | 0.062 | 2.618 | 0.185 | 6.198 |
16 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
17 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
18 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
19 | ASPHALT_SHINGLE | 0.0207 | 0.082 | 70.000 | 0.300 | 0.7745E-01 |
20 | OSB_1/2IN | 0.0417 | 0.116 | 34.000 | 0.290 | 0.1092 |
21 | DOOR_CONST | 0.1388 | 0.072 | 32.003 | 0.183 | 0.5870 |
22 | CEMENT_STUCCO | 0.0627 | 0.721 | 116.464 | 0.210 | 0.2642E-01 |
23 | BLDG_PAPER_FELT | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1057E-01 |
24 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
25 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
26 | CONCRETE_4IN | 0.3330 | 1.312 | 140.014 | 0.111 | 0.7736E-01 |
27 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
28 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
29 | FLOOR_CONSOL_LAYER | 0.4584 | 0.049 | 3.438 | 0.219 | 2.845 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 11 | -0.54724946E-11 | -0.29353179E-14 | -0.58361936E-11 | 0.17617726E-15 |
2 | 10 | 0.24755928E-06 | 0.16971160E-13 | 0.58954555E-06 | -0.42317085E-11 |
3 | 9 | -0.21700660E-03 | 0.26282512E-10 | -0.34360792E-03 | 0.18634160E-06 |
4 | 8 | 0.10400975E-01 | 0.16063655E-07 | 0.16710006E-01 | -0.10459154E-03 |
5 | 7 | -0.18466841 | 0.14497582E-05 | -0.31678806 | 0.33996447E-02 |
6 | 6 | 1.6813335 | 0.30890211E-04 | 3.0392820 | -0.45644738E-01 |
7 | 5 | -8.8640021 | 0.19737274E-03 | -16.399456 | 0.32465800 |
8 | 4 | 28.400945 | 0.41196590E-03 | 52.185337 | -1.3315683 |
9 | 3 | -55.684303 | 0.27160336E-03 | -99.213599 | 3.2198962 |
10 | 2 | 64.740984 | 0.46773103E-04 | 110.17164 | -4.4902555 |
11 | 1 | -40.701741 | 0.11975386E-05 | -65.686261 | 3.3169381 |
12 | 0 | 10.602230 | 0.29970883E-09 | 16.204438 | |
13 | 5 | -0.10726087E-01 | 0.44268190E-05 | -0.10726087E-01 | 0.97389233E-03 |
14 | 4 | 0.31857203 | 0.80150166E-03 | 0.31857203 | -0.30727185E-01 |
15 | 3 | -2.8372473 | 0.12516450E-01 | -2.8372473 | 0.30041224 |
16 | 2 | 9.6667056 | 0.33176537E-01 | 9.6667056 | -1.1584571 |
17 | 1 | -13.322214 | 0.15207483E-01 | -13.322214 | 1.8397512 |
18 | 0 | 6.2472388 | 0.62260140E-03 | 6.2472388 | |
19 | 8 | 0.57415395E-12 | 0.13118744E-13 | 0.10972129E-06 | -0.16121901E-12 |
20 | 7 | -0.11209345E-05 | 0.79302418E-09 | -0.25702593E-04 | 0.31491488E-06 |
21 | 6 | 0.21835020E-03 | 0.55842834E-06 | 0.16732899E-02 | -0.62999473E-04 |
22 | 5 | -0.11788181E-01 | 0.43793696E-04 | -0.40973943E-01 | 0.36016799E-02 |
23 | 4 | 0.21386917 | 0.66464187E-03 | 0.43752526 | -0.72376639E-01 |
24 | 3 | -1.3884299 | 0.23440260E-02 | -2.2272953 | 0.54574706 |
25 | 2 | 3.6315139 | 0.19014595E-02 | 5.4333867 | -1.6855834 |
26 | 1 | -4.0346078 | 0.26548191E-03 | -6.0131296 | 2.1907513 |
27 | 0 | 1.5944472 | 0.16612988E-05 | 2.4140608 | |
28 | 4 | 0.50405178E-13 | 0.16668152E-13 | 0.29402090E-13 | -0.58636069E-16 |
29 | 3 | -0.78967347E-05 | 0.18486376E-05 | -0.51544008E-05 | 0.20741056E-12 |
30 | 2 | 0.37655193 | 0.34407043E-01 | 0.80677627E-01 | -0.16328896E-04 |
31 | 1 | -8.0349315 | 0.81344511 | -1.1624309 | 0.21506451 |
32 | 0 | 8.9946927 | 0.48845120 | 2.4180636 | |
33 | 10 | 0.25332408E-17 | -0.22101509E-14 | 0.15157692E-08 | 0.28211904E-17 |
34 | 9 | -0.31506112E-08 | -0.26974675E-14 | -0.81843868E-03 | 0.20118786E-08 |
35 | 8 | 0.42861811E-03 | 0.11354105E-09 | 0.39097097E-01 | -0.27370296E-03 |
36 | 7 | -0.11368907E-01 | 0.51842634E-07 | -0.64553953 | 0.74324363E-02 |
37 | 6 | 0.12484615 | 0.25047115E-05 | 5.3130581 | -0.83937451E-01 |
38 | 5 | -0.73775399 | 0.27964547E-04 | -24.889648 | 0.51283867 |
39 | 4 | 2.5553417 | 0.92755650E-04 | 70.144414 | -1.8477174 |
40 | 3 | -5.2989438 | 0.96002462E-04 | -120.51707 | 4.0111012 |
41 | 2 | 6.4233118 | 0.27752742E-04 | 123.06129 | -5.1209931 |
42 | 1 | -4.1707712 | 0.15163054E-05 | -68.409714 | 3.5199891 |
43 | 0 | 1.1151582 | 0.34288690E-08 | 15.905180 | |
44 | 10 | 0.15157692E-08 | -0.22101509E-14 | 0.25332408E-17 | 0.28211904E-17 |
45 | 9 | -0.81843868E-03 | -0.26974675E-14 | -0.31506112E-08 | 0.20118786E-08 |
46 | 8 | 0.39097097E-01 | 0.11354105E-09 | 0.42861811E-03 | -0.27370296E-03 |
47 | 7 | -0.64553953 | 0.51842634E-07 | -0.11368907E-01 | 0.74324363E-02 |
48 | 6 | 5.3130581 | 0.25047115E-05 | 0.12484615 | -0.83937451E-01 |
49 | 5 | -24.889648 | 0.27964547E-04 | -0.73775399 | 0.51283867 |
50 | 4 | 70.144414 | 0.92755650E-04 | 2.5553417 | -1.8477174 |
51 | 3 | -120.51707 | 0.96002462E-04 | -5.2989438 | 4.0111012 |
52 | 2 | 123.06129 | 0.27752742E-04 | 6.4233118 | -5.1209931 |
53 | 1 | -68.409714 | 0.15163054E-05 | -4.1707712 | 3.5199891 |
54 | 0 | 15.905180 | 0.34288690E-08 | 1.1151582 | |
55 | 5 | -0.27590492E-07 | 0.65241430E-08 | -0.27590492E-07 | 0.17331255E-13 |
56 | 4 | 0.68608714E-03 | 0.11323974E-03 | 0.68608714E-03 | -0.15705033E-07 |
57 | 3 | -0.21538511 | 0.37821720E-01 | -0.21538511 | 0.25667047E-03 |
58 | 2 | 5.0173519 | 0.62258424 | 5.0173519 | -0.50236511E-01 |
59 | 1 | -19.904252 | 0.86481321 | -19.904252 | 0.58144210 |
60 | 0 | 16.688993 | 0.62060609E-01 | 16.688993 | |
61 | 4 | 0.75441920E-10 | 0.23883683E-10 | 0.47514224E-10 | -0.69373194E-20 |
62 | 3 | -0.33730907E-03 | 0.89366797E-04 | -0.22574866E-03 | 0.77828620E-10 |
63 | 2 | 0.58624422 | 0.18542418 | 0.49024360 | -0.17301269E-03 |
64 | 1 | -11.299243 | 2.8799011 | -8.6239668 | 0.15905732 |
65 | 0 | 15.219762 | 1.4410112 | 12.640375 | |
66 | 5 | -0.32935335E-06 | 0.42931990E-07 | -0.32935335E-06 | 0.47097488E-08 |
67 | 4 | 0.68052310E-03 | 0.12823787E-03 | 0.68052310E-03 | -0.14200104E-04 |
68 | 3 | -0.11535993 | 0.17375615E-01 | -0.11535993 | 0.40770076E-02 |
69 | 2 | 2.1922172 | 0.21284128 | 2.1922172 | -0.13171357 |
70 | 1 | -7.8704965 | 0.30308566 | -7.8704965 | 0.79499401 |
71 | 0 | 6.3596665 | 0.33276539E-01 | 6.3596665 | |
72 | 6 | 0.97988530E-11 | 0.43917118E-12 | 0.24496810E-11 | -0.34892153E-15 |
73 | 5 | -0.75005310E-05 | 0.16499726E-06 | -0.28271466E-05 | 0.19166609E-11 |
74 | 4 | 0.32354224E-01 | 0.66949565E-03 | 0.10283773E-01 | -0.11111676E-05 |
75 | 3 | -1.8201547 | 0.67148336E-01 | -0.62076152 | 0.38788549E-02 |
76 | 2 | 21.173821 | 0.53241617 | 7.5279938 | -0.97325542E-01 |
77 | 1 | -64.420211 | 0.46601667 | -21.697519 | 0.64629334 |
78 | 0 | 46.121323 | 0.20873329E-01 | 15.867130 | |
79 | 5 | -0.15664505E-06 | 0.43005807E-07 | -0.15664505E-06 | 0.11899247E-09 |
80 | 4 | 0.10791049E-02 | 0.34140917E-03 | 0.10791049E-02 | -0.15677434E-05 |
81 | 3 | -0.39592122 | 0.90314630E-01 | -0.39592122 | 0.13116776E-02 |
82 | 2 | 11.651569 | 1.6702487 | 11.651569 | -0.78737360E-01 |
83 | 1 | -51.506798 | 3.1050242 | -51.506798 | 0.66829999 |
84 | 0 | 45.538973 | 0.42297268 | 45.538973 | |
85 | 8 | 0.10972129E-06 | 0.13118744E-13 | 0.57415395E-12 | -0.16121901E-12 |
86 | 7 | -0.25702593E-04 | 0.79302418E-09 | -0.11209345E-05 | 0.31491488E-06 |
87 | 6 | 0.16732899E-02 | 0.55842834E-06 | 0.21835020E-03 | -0.62999473E-04 |
88 | 5 | -0.40973943E-01 | 0.43793696E-04 | -0.11788181E-01 | 0.36016799E-02 |
89 | 4 | 0.43752526 | 0.66464187E-03 | 0.21386917 | -0.72376639E-01 |
90 | 3 | -2.2272953 | 0.23440260E-02 | -1.3884299 | 0.54574706 |
91 | 2 | 5.4333867 | 0.19014595E-02 | 3.6315139 | -1.6855834 |
92 | 1 | -6.0131296 | 0.26548191E-03 | -4.0346078 | 2.1907513 |
93 | 0 | 2.4140608 | 0.16612988E-05 | 1.5944472 |
Construction Name | Index | #Layers | Roughness | Conductance {Btu/h-ft2-F} | Conductance (Before Adjusted) {Btu/h-ft2-F} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | EXTERIOR WINDOW | 12 | 1 | VerySmooth | 0.300 | 0.300 | 1.000 | 0.217 | ||
2 | INTERIOR WINDOW | 13 | 1 | VerySmooth | 0.300 | 0.300 | 1.000 | 0.217 | ||
3 | WINDOW_W_BLINDS | 18 | 2 | VerySmooth | 0.300 | 0.300 | 1.000 | 0.208 | ||
4 | TDD DOME | 22 | 1 | VerySmooth | 1.071 | 1.071 | 1.000 | 0.929 | ||
5 | TDD DIFFUSER | 23 | 1 | VerySmooth | 1.077 | 1.077 | 1.000 | 0.906 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {ft} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLASS | SpectralAverage | 0.13728 | 0.12813 | 0.66698 | 0.66698 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
2 | GLASS | SpectralAverage | 0.13728 | 0.12813 | 0.66698 | 0.66698 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
3 | GLASS | SpectralAverage | 0.13728 | 0.12813 | 0.66698 | 0.66698 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
4 | CLEAR ACRYLIC PLASTIC | SpectralAverage | 0.00984 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No | |
5 | DIFFUSING ACRYLIC PLASTIC | SpectralAverage | 0.00722 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No |
Material Name | Slat Width {ft} | Slat Separation {ft} | Slat Thickness {ft} | Slat Angle {deg} | Slat Beam Solar Transmittance | Slat Beam Solar Front Reflectance | Blind To Glass Distance {ft} | |
1 | INT_BLIND | 0.0820 | 0.0615 | 0.0033 | 45.000 | 0.000 | 0.500 | 0.164 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000. | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {ft3} | Maximum Capacity {Btu/h} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
2 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
3 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
4 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
5 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
6 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
7 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
8 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
9 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
10 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
11 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
12 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
13 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
14 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
15 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
16 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
17 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
18 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 5.3474 | 36002.1 | 0.823 | 0.5744 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
2 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
3 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
4 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
5 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
6 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
7 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
8 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
9 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
10 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
11 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
12 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
13 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
14 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
15 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
16 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
17 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
18 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
19 | ATTICVENT | ALWAYS_AVAIL | ATTIC | 7802.66 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
20 | CRAWLVENT | ALWAYS_AVAIL | CRAWLSPACE | 7794.37 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/person Area {ft3/min-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {psi} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{F}/Schedule | Maximum Indoor Temperature{F}/Schedule | Delta Temperature{F}/Schedule | Minimum Outdoor Temperature{F}/Schedule | Maximum Outdoor Temperature{F}/Schedule | Maximum WindSpeed{ft/min} | |
1 | VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
2 | VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
3 | VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
4 | VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
5 | VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
6 | VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
7 | VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
8 | VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
9 | VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
10 | VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
11 | VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
12 | VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
13 | VENTILATION_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
14 | VENTILATION_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
15 | VENTILATION_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
16 | VENTILATION_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
17 | VENTILATION_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
18 | VENTILATION_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CRAWLSPACE | Mixing/Well-Stirred |
2 | BREEZEWAY | Mixing/Well-Stirred |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
15 | ATTIC | Mixing/Well-Stirred |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {Btu/h} | User Des Load {Btu/h} | Calc Des Air Flow Rate {ft3/min} | User Des Air Flow Rate {ft3/min} | Design Day Name | Date/Time of Peak | Temperature at Peak {F} | Humidity Ratio at Peak {lbWater/lbDryAir} | Floor Area {ft2} | # Occupants | Calc Outdoor Air Flow Rate {ft3/min} | Calc DOAS Heat Addition Rate {Btu/h} | |
1 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | 10021.93651 | 10021.93651 | 491.97028 | 491.97028 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 96.13400 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | 6750.05691 | 6750.05691 | 141.67223 | 141.67223 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | 6669.88460 | 6669.88460 | 327.41521 | 327.41521 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 92.62400 | 0.00686 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | 5190.94986 | 5190.94986 | 108.95062 | 108.95062 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | 7730.65356 | 7730.65356 | 379.49148 | 379.49148 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 94.96400 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
6 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | 6750.71205 | 6750.71205 | 141.68600 | 141.68600 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
7 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | 9918.26634 | 9918.26634 | 486.88553 | 486.88553 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 95.74399 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
8 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Heating | 6754.05325 | 6754.05325 | 141.75613 | 141.75613 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
9 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | 6646.27571 | 6646.27571 | 326.27115 | 326.27115 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 92.62400 | 0.00686 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
10 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Heating | 5192.27883 | 5192.27883 | 108.97838 | 108.97838 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
11 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | 7681.70818 | 7681.70818 | 377.09741 | 377.09741 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 94.37900 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
12 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Heating | 6749.25847 | 6749.25847 | 141.65549 | 141.65549 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
13 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | 9625.49480 | 9625.49480 | 472.52113 | 472.52113 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 95.74399 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
14 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | 5200.95541 | 5200.95541 | 109.16227 | 109.16227 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
15 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | 6391.62972 | 6391.62972 | 313.77115 | 313.77115 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 91.45400 | 0.00686 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
16 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | 3663.86944 | 3663.86944 | 76.90169 | 76.90169 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
17 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | 7476.82455 | 7476.82455 | 367.03385 | 367.03385 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 94.37900 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
18 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | 5203.01237 | 5203.01237 | 109.20549 | 109.20549 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
19 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | 9537.21298 | 9537.21298 | 468.17791 | 468.17791 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 95.35401 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
20 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Heating | 5203.88625 | 5203.88625 | 109.22393 | 109.22393 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
21 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | 6358.03210 | 6358.03210 | 312.11860 | 312.11860 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 91.45400 | 0.00686 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
22 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Heating | 3664.29317 | 3664.29317 | 76.91058 | 76.91058 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
23 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | 7428.77161 | 7428.77161 | 364.68216 | 364.68216 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 94.37900 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
24 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Heating | 5200.89799 | 5200.89799 | 109.16122 | 109.16122 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
25 | LIVING_UNIT3_BACKROW_TOPFLOOR | Cooling | 8858.05906 | 8858.05906 | 434.85164 | 434.85164 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 94.37900 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
26 | LIVING_UNIT3_BACKROW_TOPFLOOR | Heating | 6949.95306 | 6949.95306 | 145.86757 | 145.86757 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
27 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Cooling | 8769.26094 | 8769.26094 | 430.48723 | 430.48723 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 94.37900 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
28 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Heating | 6951.60559 | 6951.60559 | 145.90231 | 145.90231 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
29 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Cooling | 10921.60650 | 10921.60650 | 536.14400 | 536.14400 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 95.74399 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
30 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Heating | 6949.19014 | 6949.19014 | 145.85168 | 145.85168 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
31 | LIVING_UNIT2_BACKROW_TOPFLOOR | Cooling | 7778.78324 | 7778.78324 | 381.86436 | 381.86436 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 92.03900 | 0.00686 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
32 | LIVING_UNIT2_BACKROW_TOPFLOOR | Heating | 5394.67563 | 5394.67563 | 113.22626 | 113.22626 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
33 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Cooling | 7696.90991 | 7696.90991 | 377.83894 | 377.83894 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 91.45400 | 0.00686 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
34 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Heating | 5394.47532 | 5394.47532 | 113.22223 | 113.22223 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
35 | LIVING_UNIT1_BACKROW_TOPFLOOR | Cooling | 10990.91455 | 10990.91455 | 539.53383 | 539.53383 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 95.35401 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
36 | LIVING_UNIT1_BACKROW_TOPFLOOR | Heating | 6951.23734 | 6951.23734 | 145.89468 | 145.89468 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [ft3/min] | User Des Air Flow Rate [ft3/min] | Design Day Name | Date/Time of Peak | |
1 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 3158.79 | 491.97028 | 491.97028 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 2560.59 | 141.67223 | 141.67223 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
3 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2146.33 | 327.41521 | 327.41521 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 2110.30 | 108.95062 | 108.95062 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
5 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2481.95 | 379.49148 | 379.49148 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 2560.77 | 141.68600 | 141.68600 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
7 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 3124.00 | 486.88553 | 486.88553 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Heating | Sensible | 2561.74 | 141.75613 | 141.75613 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
9 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2139.51 | 326.27115 | 326.27115 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Heating | Sensible | 2110.68 | 108.97838 | 108.97838 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
11 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2460.56 | 377.09741 | 377.09741 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Heating | Sensible | 2560.36 | 141.65549 | 141.65549 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
13 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 3039.36 | 472.52113 | 472.52113 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 2113.20 | 109.16227 | 109.16227 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
15 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2051.41 | 313.77115 | 313.77115 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1669.28 | 76.90169 | 76.90169 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
17 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2401.33 | 367.03385 | 367.03385 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 2113.79 | 109.20549 | 109.20549 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
19 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 3009.01 | 468.17791 | 468.17791 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Heating | Sensible | 2114.05 | 109.22393 | 109.22393 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
21 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2041.70 | 312.11860 | 312.11860 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
22 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1669.40 | 76.91058 | 76.91058 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
23 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2387.44 | 364.68216 | 364.68216 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
24 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Heating | Sensible | 2113.18 | 109.16122 | 109.16122 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
25 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Cooling | Sensible | 3414.04 | 536.14400 | 536.14400 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
26 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Heating | Sensible | 2618.10 | 145.85168 | 145.85168 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
27 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Cooling | Sensible | 2428.74 | 377.83894 | 377.83894 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
28 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Heating | Sensible | 2169.08 | 113.22223 | 113.22223 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
29 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Cooling | Sensible | 2774.94 | 430.48723 | 430.48723 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
30 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Heating | Sensible | 2618.80 | 145.90231 | 145.90231 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
31 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Cooling | Sensible | 3429.25 | 539.53383 | 539.53383 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
32 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Heating | Sensible | 2618.69 | 145.89468 | 145.89468 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
33 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Cooling | Sensible | 2459.65 | 381.86436 | 381.86436 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
34 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Heating | Sensible | 2169.14 | 113.22626 | 113.22626 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
35 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Cooling | Sensible | 2800.61 | 434.85164 | 434.85164 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
36 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Heating | Sensible | 2618.32 | 145.86757 | 145.86757 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 491.97028 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 327.41521 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 379.49148 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 486.88553 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 326.27115 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 377.09741 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 472.52113 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 313.77115 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 367.03385 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 468.17791 |
11 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 312.11860 |
12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 364.68216 |
13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 434.85164 |
14 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 430.48723 |
15 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 536.14400 |
16 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 381.86436 |
17 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 377.83894 |
18 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 539.53383 |
19 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 491.97028 |
20 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 491.97028 |
21 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 491.97028 |
22 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 491.97028 |
23 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 491.97028 |
24 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 491.97028 |
25 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 327.41521 |
28 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 327.41521 |
29 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 327.41521 |
30 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 327.41521 |
31 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 327.41521 |
32 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 327.41521 |
33 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 379.49148 |
36 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 379.49148 |
37 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 379.49148 |
38 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 379.49148 |
39 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 379.49148 |
40 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 379.49148 |
41 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 486.88553 |
44 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 486.88553 |
45 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 486.88553 |
46 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 486.88553 |
47 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 486.88553 |
48 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 486.88553 |
49 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 326.27115 |
52 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 326.27115 |
53 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 326.27115 |
54 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 326.27115 |
55 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 326.27115 |
56 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 326.27115 |
57 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 377.09741 |
60 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 377.09741 |
61 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 377.09741 |
62 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 377.09741 |
63 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 377.09741 |
64 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 377.09741 |
65 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 472.52113 |
68 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 472.52113 |
69 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 472.52113 |
70 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 472.52113 |
71 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 472.52113 |
72 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 472.52113 |
73 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 313.77115 |
76 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 313.77115 |
77 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 313.77115 |
78 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 313.77115 |
79 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 313.77115 |
80 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 313.77115 |
81 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 367.03385 |
84 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 367.03385 |
85 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 367.03385 |
86 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 367.03385 |
87 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 367.03385 |
88 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 367.03385 |
89 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 468.17791 |
92 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 468.17791 |
93 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 468.17791 |
94 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 468.17791 |
95 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 468.17791 |
96 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 468.17791 |
97 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
98 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
99 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 312.11860 |
100 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 312.11860 |
101 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 312.11860 |
102 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 312.11860 |
103 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 312.11860 |
104 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 312.11860 |
105 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
106 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
107 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 364.68216 |
108 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 364.68216 |
109 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 364.68216 |
110 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 364.68216 |
111 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 364.68216 |
112 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 364.68216 |
113 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
114 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
115 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 536.14400 |
116 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 536.14400 |
117 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 536.14400 |
118 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 536.14400 |
119 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 536.14400 |
120 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 536.14400 |
121 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
122 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
123 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 377.83894 |
124 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 377.83894 |
125 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 377.83894 |
126 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 377.83894 |
127 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 377.83894 |
128 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 377.83894 |
129 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
130 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
131 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 430.48723 |
132 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 430.48723 |
133 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 430.48723 |
134 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 430.48723 |
135 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 430.48723 |
136 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 430.48723 |
137 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
138 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
139 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 539.53383 |
140 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 539.53383 |
141 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 539.53383 |
142 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 539.53383 |
143 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 539.53383 |
144 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 539.53383 |
145 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
146 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
147 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 381.86436 |
148 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 381.86436 |
149 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 381.86436 |
150 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 381.86436 |
151 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 381.86436 |
152 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 381.86436 |
153 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
154 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
155 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 434.85164 |
156 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 434.85164 |
157 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 434.85164 |
158 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 434.85164 |
159 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 434.85164 |
160 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 434.85164 |
161 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
162 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
163 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 491.97028 |
164 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 327.41521 |
165 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 379.49148 |
166 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 486.88553 |
167 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 326.27115 |
168 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 377.09741 |
169 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 472.52113 |
170 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 313.77115 |
171 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 367.03385 |
172 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 468.17791 |
173 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 312.11860 |
174 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 364.68216 |
175 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 536.14400 |
176 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 377.83894 |
177 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 430.48723 |
178 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 539.53383 |
179 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 381.86436 |
180 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 434.85164 |
181 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 491.97028 |
182 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 245.99573 |
183 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 491.97028 |
184 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 245.99573 |
185 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8736.71844 |
186 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
187 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 491.97028 |
188 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 491.97028 |
189 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 245.99573 |
190 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 15961.60169 |
191 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.66507 |
192 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.77310 |
193 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.77310 |
194 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 28961.61820 |
195 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 14480.80908 |
196 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 10047.22622 |
197 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 327.41521 |
198 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 163.71290 |
199 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 327.41521 |
200 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 163.71290 |
201 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 7200.34670 |
202 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
203 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 327.41521 |
204 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 327.41521 |
205 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 163.71290 |
206 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 10809.07311 |
207 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.45038 |
208 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.76690 |
209 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.76690 |
210 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 20076.67094 |
211 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 10038.33547 |
212 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 8280.39872 |
213 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 379.49148 |
214 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 189.74870 |
215 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 379.49148 |
216 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 189.74870 |
217 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8737.36403 |
218 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
219 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 379.49148 |
220 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 379.49148 |
221 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 189.74870 |
222 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 12510.77590 |
223 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.52128 |
224 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.76731 |
225 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.76731 |
226 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 22888.43265 |
227 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 11444.21633 |
228 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 10047.96864 |
229 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 486.88553 |
230 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 243.45336 |
231 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 486.88553 |
232 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 243.45336 |
233 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8740.65654 |
234 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
235 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 486.88553 |
236 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 486.88553 |
237 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 243.45336 |
238 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 15792.30798 |
239 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.65801 |
240 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.77318 |
241 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.77318 |
242 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 28686.84970 |
243 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 14343.42487 |
244 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 10051.75504 |
245 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 326.27115 |
246 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 163.13345 |
247 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 326.27115 |
248 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 163.13345 |
249 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 7201.65633 |
250 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
251 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 326.27115 |
252 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 326.27115 |
253 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 163.13345 |
254 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 10774.53360 |
255 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.44894 |
256 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.76680 |
257 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.76680 |
258 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 20014.09469 |
259 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 10007.04736 |
260 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 8281.90478 |
261 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 377.09741 |
262 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 188.54743 |
263 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 377.09741 |
264 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 188.54743 |
265 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8735.93164 |
266 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
267 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 377.09741 |
268 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 377.09741 |
269 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 188.54743 |
270 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 12393.33840 |
271 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.51639 |
272 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.76823 |
273 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.76823 |
274 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 22758.71397 |
275 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 11379.35700 |
276 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 10046.32139 |
277 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 472.52113 |
278 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 236.24997 |
279 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 472.52113 |
280 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 236.24997 |
281 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 7210.24034 |
282 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
283 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 472.52113 |
284 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 472.52113 |
285 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 236.24997 |
286 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 15394.29108 |
287 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.64143 |
288 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.77184 |
289 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.77184 |
290 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 27910.23902 |
291 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 13955.11951 |
292 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 8291.77641 |
293 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 313.77115 |
294 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 156.88367 |
295 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 313.77115 |
296 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 156.88367 |
297 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 5695.57138 |
298 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
299 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 313.77115 |
300 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 313.77115 |
301 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 156.88367 |
302 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 10342.99418 |
303 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.43096 |
304 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.76733 |
305 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.76733 |
306 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 19338.78073 |
307 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 9669.39035 |
308 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 6549.90708 |
309 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 367.03385 |
310 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 183.51904 |
311 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 367.03385 |
312 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 183.51904 |
313 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 7212.26731 |
314 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
315 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 367.03385 |
316 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 367.03385 |
317 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 183.51904 |
318 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 12125.00091 |
319 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.50521 |
320 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.76670 |
321 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.76670 |
322 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 22215.19861 |
323 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 11107.59929 |
324 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 8294.10742 |
325 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 468.17791 |
326 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 234.08895 |
327 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 468.17791 |
328 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 234.08895 |
329 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 7213.12847 |
330 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
331 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 468.17791 |
332 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 468.17791 |
333 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 234.08895 |
334 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 15236.47288 |
335 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.63485 |
336 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.77217 |
337 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.77217 |
338 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 27676.26375 |
339 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 13838.13189 |
340 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 8295.09776 |
341 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 312.11860 |
342 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 156.05909 |
343 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 312.11860 |
344 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 156.05909 |
345 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 5695.98891 |
346 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
347 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 312.11860 |
348 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 312.11860 |
349 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 156.05909 |
350 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 10294.02655 |
351 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.42892 |
352 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.76718 |
353 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.76718 |
354 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 19249.73064 |
355 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 9624.86532 |
356 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 6550.38725 |
357 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 364.68216 |
358 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 182.33960 |
359 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 364.68216 |
360 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 182.33960 |
361 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 7210.18377 |
362 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
363 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 364.68216 |
364 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 364.68216 |
365 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 182.33960 |
366 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 12054.25674 |
367 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.50226 |
368 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.76652 |
369 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.76652 |
370 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 22087.83445 |
371 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 11043.91724 |
372 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 8291.71135 |
373 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 536.14400 |
374 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 268.07200 |
375 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 536.14400 |
376 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 268.07200 |
377 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8932.94939 |
378 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
379 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 536.14400 |
380 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 536.14400 |
381 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 268.07200 |
382 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 17270.12949 |
383 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.71959 |
384 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.77628 |
385 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.77628 |
386 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 31346.30570 |
387 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 15673.15285 |
388 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 10272.89181 |
389 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 377.83894 |
390 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 188.92180 |
391 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 377.83894 |
392 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 188.92180 |
393 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 7400.90526 |
394 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
395 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 377.83894 |
396 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 377.83894 |
397 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 188.92180 |
398 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 12214.61993 |
399 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.50894 |
400 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.77519 |
401 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.77519 |
402 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 22798.93381 |
403 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 11399.46689 |
404 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 8511.04105 |
405 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 430.48723 |
406 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 215.23302 |
407 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 430.48723 |
408 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 215.23302 |
409 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8935.32963 |
410 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
411 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 430.48723 |
412 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 430.48723 |
413 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 215.23302 |
414 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 13990.54921 |
415 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.58294 |
416 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.77258 |
417 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.77258 |
418 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 25641.38585 |
419 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 12820.69291 |
420 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 10275.62908 |
421 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_TOPFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 539.53383 |
422 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_TOPFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 269.76692 |
423 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_TOPFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 539.53383 |
424 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_TOPFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 269.76692 |
425 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8934.96677 |
426 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT1_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
427 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 539.53383 |
428 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 539.53383 |
429 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 269.76692 |
430 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 17340.15884 |
431 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.72251 |
432 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.77697 |
433 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.77697 |
434 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 31530.03501 |
435 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 15765.01750 |
436 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 10275.21180 |
437 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_TOPFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 381.86436 |
438 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_TOPFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 190.93112 |
439 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_TOPFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 381.86436 |
440 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_TOPFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 190.93112 |
441 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 7401.10264 |
442 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT2_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
443 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 381.86436 |
444 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 381.86436 |
445 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 190.93112 |
446 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 12386.21817 |
447 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.51609 |
448 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.77317 |
449 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.77317 |
450 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 23015.92493 |
451 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 11507.96248 |
452 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 8511.26805 |
453 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_TOPFLOOR | Speed 2 Supply Air Flow Rate During Cooling Operation [ft3/min] | 434.85164 |
454 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_TOPFLOOR | Speed 1 Supply Air Flow Rate During Cooling Operation [ft3/min] | 217.41523 |
455 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_TOPFLOOR | Speed2Supply Air Flow Rate During Heating Operation [ft3/min] | 434.85164 |
456 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_TOPFLOOR | Speed1Supply Air Flow Rate During Heating Operation [ft3/min] | 217.41523 |
457 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supplemental Heating Coil Nominal Capacity [Btu/h] | 8933.70119 |
458 | AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed | ACANDF_UNIT3_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
459 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 434.85164 |
460 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Speed 2 Gross Rated Cooling COP [ft3/min] | 434.85164 |
461 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Speed 1 Rated Air Flow Rate [ft3/min] | 217.41523 |
462 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Speed 1 Rated Evaporative Condenser Pump Power Consumption [Btu/h] | 14120.76085 |
463 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Speed 1 Gross Rated Total Cooling Capacity [ton] | 0.58836 |
464 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Speed 2 Rated Sensible Heat Ratio | 0.77283 |
465 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Speed 1 Rated Sensible Heat Ratio | 0.77283 |
466 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Stage 2 Nominal Capacity [Btu/h] | 25876.75376 |
467 | Coil:Heating:GasMultiStage | DUMMY-HEAT-COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Stage 1 Nominal Capacity [Btu/h] | 12938.37688 |
468 | Coil:Heating:Fuel | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 10273.75637 |
469 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
470 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
471 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
472 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
473 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
474 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
475 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
476 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
477 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
478 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
479 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
480 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
481 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
482 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
483 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
484 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
485 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
486 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
487 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
488 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
489 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
490 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
491 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
492 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
493 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
494 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
495 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
496 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
497 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
498 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
499 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
500 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
501 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
502 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
503 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
504 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
505 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
506 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
507 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
508 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
509 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
510 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
511 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
512 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
513 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
514 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
515 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
516 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
517 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
518 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
519 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
520 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
521 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
522 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
523 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
524 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
525 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
526 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
527 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
528 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
529 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
530 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
531 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
532 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
533 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
534 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
535 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
536 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
537 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
538 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
539 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
540 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
541 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
542 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
543 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
544 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
545 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
546 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
547 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
548 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
549 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
550 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
551 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
552 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
553 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
554 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
555 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
556 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
557 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
558 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {ton} | Standard Rated Net COP {Btuh/Btuh} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.3 | -99999. | -99999. | 19.15 | 18.46 | -99999. |
2 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.3 | -99999. | -99999. | 16.84 | 16.96 | -99999. |
3 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.9 | -99999. | -99999. | 19.19 | 18.50 | -99999. |
4 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.9 | -99999. | -99999. | 16.91 | 17.03 | -99999. |
5 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 1.0 | -99999. | -99999. | 19.19 | 18.50 | -99999. |
6 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 1.0 | -99999. | -99999. | 16.90 | 17.03 | -99999. |
7 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.3 | -99999. | -99999. | 19.15 | 18.46 | -99999. |
8 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.2 | -99999. | -99999. | 16.84 | 16.96 | -99999. |
9 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.9 | -99999. | -99999. | 19.19 | 18.50 | -99999. |
10 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.9 | -99999. | -99999. | 16.91 | 17.04 | -99999. |
11 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 1.0 | -99999. | -99999. | 19.18 | 18.49 | -99999. |
12 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 1.0 | -99999. | -99999. | 16.89 | 17.02 | -99999. |
13 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.2 | -99999. | -99999. | 19.16 | 18.47 | -99999. |
14 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.2 | -99999. | -99999. | 16.85 | 16.98 | -99999. |
15 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.8 | -99999. | -99999. | 19.19 | 18.50 | -99999. |
16 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.8 | -99999. | -99999. | 16.90 | 17.03 | -99999. |
17 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 1.0 | -99999. | -99999. | 19.20 | 18.50 | -99999. |
18 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 1.0 | -99999. | -99999. | 16.91 | 17.04 | -99999. |
19 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.2 | -99999. | -99999. | 19.16 | 18.47 | -99999. |
20 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.2 | -99999. | -99999. | 16.85 | 16.97 | -99999. |
21 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.8 | -99999. | -99999. | 19.19 | 18.50 | -99999. |
22 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.8 | -99999. | -99999. | 16.90 | 17.03 | -99999. |
23 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 1.0 | -99999. | -99999. | 19.20 | 18.51 | -99999. |
24 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 1.0 | -99999. | -99999. | 16.91 | 17.04 | -99999. |
25 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.4 | -99999. | -99999. | 19.13 | 18.44 | -99999. |
26 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.4 | -99999. | -99999. | 16.81 | 16.93 | -99999. |
27 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 1.0 | -99999. | -99999. | 19.14 | 18.45 | -99999. |
28 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 1.0 | -99999. | -99999. | 16.82 | 16.95 | -99999. |
29 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.1 | -99999. | -99999. | 19.16 | 18.47 | -99999. |
30 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.1 | -99999. | -99999. | 16.84 | 16.97 | -99999. |
31 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.4 | -99999. | -99999. | 19.13 | 18.44 | -99999. |
32 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.4 | -99999. | -99999. | 16.80 | 16.92 | -99999. |
33 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 1.0 | -99999. | -99999. | 19.15 | 18.46 | -99999. |
34 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 1.0 | -99999. | -99999. | 16.84 | 16.96 | -99999. |
35 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.1 | -99999. | -99999. | 19.15 | 18.46 | -99999. |
36 | Coil:Cooling:DX:MultiSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.1 | -99999. | -99999. | 16.84 | 16.97 | -99999. |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | SizingPeriod:DesignDay | 12/21 | 12/21 | WinterDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
2 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | SizingPeriod:DesignDay | 07/21 | 07/21 | SummerDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
3 | ANNUAL | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | No | SizingPeriod:DesignDay | ||
2 | No | SizingPeriod:DesignDay | ||
3 | No |
NumberofWarmupDays | |
1 | 6 |
2 | 6 |
3 | 6 |
Max Dry-Bulb Temp {F} | Temp Range {dC} | Temp Range Ind Type | Hum Ind Type | Hum Ind Value at Max Temp | Hum Ind Units | Pressure {psi} | Wind Direction {deg CW from N} | Wind Speed {ft/min} | Clearness | Rain | Snow | |
1 | 22.64 | 0.00 | DefaultMultipliers | Wetbulb | -5.20 | {C} | 13. | 20 | 433.1 | 0.00 | No | No |
2 | 100.58 | 13.00 | DefaultMultipliers | Wetbulb | 18.10 | {C} | 13. | 280 | 767.8 | 0.00 | No | No |
DayOfYear | ASHRAE A Coeff | ASHRAE B Coeff | ASHRAE C Coeff | Solar Constant-Annual Variation | Eq of Time {minutes} | Solar Declination Angle {deg} | Solar Model | |
1 | 355 | 1232.8 | 0.1424 | 5.7719E-002 | 1.0 | 2.45 | -24. | ASHRAEClearSky |
2 | 202 | 1084.4 | 0.2082 | 0.1365 | 1.0 | -6.23 | 20.6 | ASHRAETau |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaF} | Std Dev Warmup Temperature Difference {deltaF} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {Btu/h} | Std Dev Warmup Load Difference {Btu/h} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CRAWLSPACE | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000411943 | 0.000349620 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
2 | BREEZEWAY | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000091429 | 0.000031548 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.017196806 | 0.028894378 | Pass | Pass |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.022427039 | 0.037871234 | Pass | Pass |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.017196086 | 0.028893963 | Pass | Pass |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.017187312 | 0.028877639 | Pass | Pass |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.022422439 | 0.037865322 | Pass | Pass |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.017200538 | 0.028901300 | Pass | Pass |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.021403771 | 0.036033469 | Pass | Pass |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.030544461 | 0.052432097 | Pass | Pass |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.021395371 | 0.036018442 | Pass | Pass |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.021391684 | 0.036011960 | Pass | Pass |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.030541437 | 0.052426216 | Pass | Pass |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.021404501 | 0.036034472 | Pass | Pass |
15 | ATTIC | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000148338 | 0.000119047 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.015900761 | 0.025295344 | Pass | Pass |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.015897090 | 0.025289219 | Pass | Pass |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.015902806 | 0.025298673 | Pass | Pass |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.020589728 | 0.032967362 | Pass | Pass |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.020590677 | 0.032968930 | Pass | Pass |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.015897978 | 0.025290692 | Pass | Pass |
22 | CRAWLSPACE | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.232740660 | 0.137908607 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
23 | BREEZEWAY | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.116424636 | 0.062858752 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
24 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000102536 | 0.000244749 | Pass | Pass | 0.072496936 | 0.032359746 | Pass | Pass |
25 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000176935 | 0.000357831 | Pass | Pass | 0.054639864 | 0.037054794 | Pass | Pass |
26 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000115735 | 0.000246021 | Pass | Pass | 0.060574626 | 0.053133730 | Pass | Pass |
27 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000120583 | 0.000349176 | Pass | Pass | 0.071972828 | 0.032132609 | Pass | Pass |
28 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000132467 | 0.000284648 | Pass | Pass | 0.054328614 | 0.035379989 | Pass | Pass |
29 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000124872 | 0.000240574 | Pass | Pass | 0.060143507 | 0.054146163 | Pass | Pass |
30 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000105555 | 0.000250155 | Pass | Pass | 0.065084874 | 0.028728070 | Pass | Pass |
31 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000152716 | 0.000284658 | Pass | Pass | 0.047091628 | 0.033608181 | Pass | Pass |
32 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000130955 | 0.000262835 | Pass | Pass | 0.053985997 | 0.046892816 | Pass | Pass |
33 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000113290 | 0.000279970 | Pass | Pass | 0.064571390 | 0.028322961 | Pass | Pass |
34 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000086745 | 0.000203597 | Pass | Pass | 0.046796317 | 0.032276679 | Pass | Pass |
35 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000122994 | 0.000242460 | Pass | Pass | 0.053515502 | 0.047800835 | Pass | Pass |
36 | ATTIC | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.598847540 | 0.457828678 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
37 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000137475 | 0.000264334 | Pass | Pass | 0.057513344 | 0.045527797 | Pass | Pass |
38 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000116202 | 0.000239972 | Pass | Pass | 0.057527891 | 0.045088081 | Pass | Pass |
39 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000122550 | 0.000317225 | Pass | Pass | 0.068619135 | 0.028309427 | Pass | Pass |
40 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000129804 | 0.000278238 | Pass | Pass | 0.054039432 | 0.029139083 | Pass | Pass |
41 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000132706 | 0.000318986 | Pass | Pass | 0.053621894 | 0.031230755 | Pass | Pass |
42 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000130838 | 0.000334767 | Pass | Pass | 0.068889265 | 0.027352055 | Pass | Pass |
43 | CRAWLSPACE | RunPeriod: ANNUAL | 0.293717965 | 0.193234927 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
44 | BREEZEWAY | RunPeriod: ANNUAL | 0.073055772 | 0.042514495 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
45 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.041732705 | 0.085988898 | Pass | Pass | 0.330628508 | 0.587018493 | Pass | Pass |
46 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.041885338 | 0.081662921 | Pass | Pass | 0.330887219 | 1.148310642 | Pass | Pass |
47 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.041748829 | 0.089026754 | Pass | Pass | 0.469997082 | 1.964734922 | Pass | Pass |
48 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.041725526 | 0.080112324 | Pass | Pass | 0.771542351 | 5.274177722 | Pass | Pass |
49 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.037557644 | 0.051939209 | Pass | Pass | 0.327514850 | 1.432801309 | Pass | Pass |
50 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.028935927 | 0.042762982 | Pass | Pass | 0.363391375 | 1.456411244 | Pass | Pass |
51 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.041744460 | 0.080477773 | Pass | Pass | 0.790267057 | 6.283021338 | Pass | Pass |
52 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.041780016 | 0.072077447 | Pass | Pass | 0.251281875 | 0.764273568 | Pass | Pass |
53 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.041656414 | 0.086764803 | Pass | Pass | 0.297367903 | 0.820197831 | Pass | Pass |
54 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.041725618 | 0.069961902 | Pass | Pass | 0.395838262 | 1.756062584 | Pass | Pass |
55 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.041794477 | 0.046379323 | Pass | Pass | 0.335540331 | 0.994464604 | Pass | Pass |
56 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.042873691 | 0.045612758 | Pass | Pass | 0.322153397 | 1.239868757 | Pass | Pass |
57 | ATTIC | RunPeriod: ANNUAL | 0.542276208 | 0.465439884 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
58 | LIVING_UNIT3_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.041977815 | 0.053049139 | Pass | Pass | 0.350006555 | 1.211874766 | Pass | Pass |
59 | LIVING_UNIT3_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.041760511 | 0.081100864 | Pass | Pass | 0.263392840 | 0.492156732 | Pass | Pass |
60 | LIVING_UNIT1_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.041739041 | 0.078122217 | Pass | Pass | 0.505255390 | 2.268470014 | Pass | Pass |
61 | LIVING_UNIT2_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.041748620 | 0.052853342 | Pass | Pass | 0.250397300 | 0.597061457 | Pass | Pass |
62 | LIVING_UNIT2_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.041785023 | 0.078586207 | Pass | Pass | 0.936472254 | 5.566142072 | Pass | Pass |
63 | LIVING_UNIT1_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.041700893 | 0.079538574 | Pass | Pass | 0.340856229 | 0.845025836 | Pass | Pass |
Report: Annual Heat Emissions Report
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Annual Heat Emissions SummaryEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [kBtu] | 2872498.59 | 319653.78 | 84217.07 | 0.00 | 468685.06 | 3745069.67 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Heat Index HoursSafe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
CRAWLSPACE | 7920.33 | 839.67 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 6276.33 | 2336.50 | 147.17 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 6567.83 | 999.17 | 789.17 | 403.83 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6276.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2336.50 | 789.17 | 403.83 | 0.00 |
Average | 8497.36 | 198.83 | 44.59 | 19.23 | 0.00 |
Sum | 178444.50 | 4175.33 | 936.33 | 403.83 | 0.00 |
Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 10339.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 217122.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 7508.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 157680.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CRAWLSPACE | 7981.33 | 778.67 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 7570.17 | 1189.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8747.67 | 12.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 6698.67 | 1426.17 | 444.00 | 186.33 | 4.83 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
Min | 6698.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1426.17 | 444.00 | 186.33 | 4.83 |
Average | 8563.75 | 166.00 | 21.14 | 8.87 | 0.23 |
Sum | 179838.83 | 3486.00 | 444.00 | 186.33 | 4.83 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12034.26 | 28.13 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12045.81 | 16.58 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12040.39 | 21.99 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12037.16 | 25.23 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12046.51 | 15.87 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12041.39 | 20.99 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12056.40 | 5.98 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 12056.07 | 6.31 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12053.01 | 9.37 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12054.27 | 8.11 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 12062.38 | 28.13 | 0.00 | 0.00 | 0.00 |
Average | 10331.63 | 7.55 | 0.00 | 0.00 | 0.00 |
Sum | 216964.32 | 158.54 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8747.67 | 12.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 16.00 | 0.00 | 0.00 | 0.00 |
Average | 7504.22 | 4.35 | 0.00 | 0.00 | 0.00 |
Sum | 157588.67 | 91.33 | 0.00 | 0.00 | 0.00 |
Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
CRAWLSPACE | 0.00 | - | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Min | 0.00 | - | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Average | 7508.57 | - | 0.00 | 0.00 | 0.00 |
Sum | 157680.00 | - | 0.00 | 0.00 | 0.00 |
Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
CRAWLSPACE | 0.00 | - | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Min | 0.00 | - | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Average | 7508.57 | - | 0.00 | 0.00 | 0.00 |
Sum | 157680.00 | - | 0.00 | 0.00 | 0.00 |
Cooling Setpoint Unmet Degree-Hours [°F·hr] | Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] | Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] | Heating Setpoint Unmet Degree-Hours [°F·hr] | Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] | Heating Setpoint Unmet Occupied Degree-Hours [°C·hr] | |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.36 | 0.40 | 0.36 | 0.01 | 0.02 | 0.01 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.26 | 0.29 | 0.26 | 0.01 | 0.01 | 0.01 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.29 | 0.31 | 0.29 | 0.01 | 0.01 | 0.01 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.27 | 0.32 | 0.27 | 0.02 | 0.02 | 0.02 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.17 | 0.22 | 0.17 | 0.01 | 0.01 | 0.01 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.21 | 0.24 | 0.21 | 0.01 | 0.01 | 0.01 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.38 | 0.43 | 0.38 | 0.01 | 0.02 | 0.01 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.27 | 0.33 | 0.27 | 0.00 | 0.01 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.31 | 0.33 | 0.31 | 0.01 | 0.01 | 0.01 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.27 | 0.34 | 0.27 | 0.02 | 0.02 | 0.02 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.18 | 0.24 | 0.18 | 0.01 | 0.01 | 0.01 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.22 | 0.26 | 0.22 | 0.01 | 0.01 | 0.01 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.26 | 0.32 | 0.26 | 0.01 | 0.01 | 0.01 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.34 | 0.38 | 0.34 | 0.01 | 0.01 | 0.01 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.41 | 0.48 | 0.41 | 0.01 | 0.02 | 0.01 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.23 | 0.31 | 0.23 | 0.01 | 0.01 | 0.01 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.31 | 0.38 | 0.31 | 0.01 | 0.01 | 0.01 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.33 | 0.40 | 0.33 | 0.02 | 0.02 | 0.02 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.41 | 0.48 | 0.41 | 0.02 | 0.02 | 0.02 |
Average | 0.24 | 0.28 | 0.24 | 0.01 | 0.01 | 0.01 |
Sum | 5.07 | 5.96 | 5.07 | 0.19 | 0.23 | 0.19 |
Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 0.00 | 0.00 | 0.00 | 0.00 |
Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 22.64 | 0.00 | 22.64 | Wetbulb [F] | 433.09 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 100.58 | 23.40 | 64.58 | Wetbulb [F] | 767.75 | 280.00 |
Monthly Total Precipitation from .epw [in] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [in] | Monthly Total Roof Irrigation Depth [in] | Monthly Total Rain Collection Volume [ft3] | |
Jan | 0.12 | 6 | |||
Feb | 0.12 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.71 | 7 | |||
Jul | 1.06 | 16 | |||
Aug | 1.61 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 0.91 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 0.28 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | CRAWL WALL | 0.30 | 0.776 | 2.276 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_LOWER_LDF | CRAWL WALL | 0.30 | 0.893 | 2.276 | 239.83 | 239.83 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | CRAWL WALL | 0.30 | 0.776 | 2.276 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_LOWER_SDR | CRAWL WALL | 0.30 | 0.893 | 2.276 | 130.22 | 130.22 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | CRAWL WALL | 0.30 | 0.776 | 2.276 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_LOWER_LDB | CRAWL WALL | 0.30 | 0.893 | 2.276 | 239.83 | 239.83 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | CRAWL WALL | 0.30 | 0.776 | 2.276 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BGWALL_LOWER_SDL | CRAWL WALL | 0.30 | 0.893 | 2.276 | 130.22 | 130.22 | 270.00 | 90.00 | W |
BGFLOOR | INTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.39 | 599.39 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
BREEZEWAYROOF | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 599.39 | 599.39 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-BREEZEWAYROOF | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 599.39 | 599.39 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 |
Construction | Frame and Divider | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | NFRC Product Type | Assembly U-Factor [Btu/h-ft2-F] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | |||||||
Total or Average | 2126.74 | 0.300 | 0.217 | 0.883 | |||||||||||||||||
North Total or Average | 531.68 | 0.300 | 0.217 | 0.883 | |||||||||||||||||
Non-North Total or Average | 1595.05 | 0.300 | 0.217 | 0.883 |
Frame and Divider | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [Btu/h-ft2-F] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 0.96 | 0.00 | 0.99 | 0.93 | 0.00 | 1.00 | 0.95 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 0.96 | 0.00 | 0.99 | 0.93 | 0.00 | 1.00 | 0.95 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 0.96 | 0.00 | 0.99 | 0.93 | 0.00 | 1.00 | 0.95 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 0.96 | 0.00 | 0.99 | 0.93 | 0.00 | 1.00 | 0.95 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 0.96 | 0.00 | 0.99 | 0.93 | 0.00 | 1.00 | 0.95 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 0.96 | 0.00 | 0.99 | 0.93 | 0.00 | 1.00 | 0.95 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [Btu/h-ft2] | Space Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.2915 | 43219.92 | 12599.76 | 11336.81 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
Exterior Lighting Total | 934.89 | 4094.83 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Central PlantType | Reference Capacity [Btu/h] | Reference Efficiency [Btuh/Btuh] | Rated Capacity [Btu/h] | Rated Efficiency [Btuh/Btuh] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | 15961.60 | 12339.91 | 3621.69 | 0.77 | 4.50 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | 10809.07 | 8289.46 | 2519.62 | 0.77 | 4.50 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | 12510.78 | 9599.63 | 2911.15 | 0.77 | 4.50 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | 15792.31 | 12210.29 | 3582.01 | 0.77 | 4.50 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | 10774.53 | 8261.86 | 2512.67 | 0.77 | 4.50 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | 12393.34 | 9520.88 | 2872.45 | 0.77 | 4.50 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | 15394.29 | 11881.97 | 3512.32 | 0.77 | 4.50 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | 10342.99 | 7936.53 | 2406.46 | 0.77 | 4.50 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | 12125.00 | 9296.19 | 2828.81 | 0.77 | 4.50 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | 15236.47 | 11765.17 | 3471.31 | 0.77 | 4.50 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | 10294.03 | 7897.35 | 2396.68 | 0.77 | 4.50 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | 12054.26 | 9239.82 | 2814.43 | 0.77 | 4.50 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | 17270.13 | 13406.37 | 3863.76 | 0.78 | 4.50 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | 12214.62 | 9468.65 | 2745.97 | 0.78 | 4.50 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | 13990.55 | 10808.84 | 3181.71 | 0.77 | 4.50 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | 17340.16 | 13472.78 | 3867.38 | 0.78 | 4.50 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | 12386.22 | 9576.65 | 2809.57 | 0.77 | 4.50 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | 14120.76 | 10912.89 | 3207.87 | 0.77 | 4.50 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.3 | 19.15 | 18.46 | ||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.9 | 19.19 | 18.50 | ||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 1.0 | 19.19 | 18.50 | ||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.3 | 19.15 | 18.46 | ||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.9 | 19.19 | 18.50 | ||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 1.0 | 19.18 | 18.49 | ||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.2 | 19.16 | 18.47 | ||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.8 | 19.19 | 18.50 | ||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 1.0 | 19.20 | 18.50 | ||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.2 | 19.16 | 18.47 | ||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.8 | 19.19 | 18.50 | ||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 1.0 | 19.20 | 18.51 | ||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.4 | 19.13 | 18.44 | ||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 1.0 | 19.14 | 18.45 | ||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.1 | 19.16 | 18.47 | ||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.4 | 19.13 | 18.44 | ||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 1.0 | 19.15 | 18.46 | ||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.1 | 19.15 | 18.46 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP2 [Btuh/Btuh] | EER2 [Btu/W-h] | SEER2 User [Btu/W-h] | SEER2 Standard [Btu/W-h] | IEER2 [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | 1.3 | 16.84 | 16.96 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | 0.9 | 16.91 | 17.03 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | 1.0 | 16.90 | 17.03 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | 1.2 | 16.84 | 16.96 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | 0.9 | 16.91 | 17.04 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | 1.0 | 16.89 | 17.02 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | 1.2 | 16.85 | 16.98 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | 0.8 | 16.90 | 17.03 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | 1.0 | 16.91 | 17.04 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | 1.2 | 16.85 | 16.97 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | 0.8 | 16.90 | 17.03 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | 1.0 | 16.91 | 17.04 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | 1.4 | 16.81 | 16.93 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | 1.0 | 16.82 | 16.95 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | 1.1 | 16.84 | 16.97 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | 1.4 | 16.80 | 16.92 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | 1.0 | 16.84 | 16.96 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | 1.1 | 16.84 | 16.97 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed |
Coil Type | Rated Total Capacity [Btu/h] | Rated Sensible Capacity [Btu/h] | Rated Power[Btu/h] | Rated COP [Btuh/Btuh] | Rated Air Dry-bulb Temperature [F] | Rated Air Wet-bulb Temperature [F] | Rated Water Temperature [F] | Design Day used for Sizing | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF2 [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
DUMMY-HEAT-COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | 28961.62 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 10047.23 | 0.80 | |
DUMMY-HEAT-COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | 20076.67 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 8280.40 | 0.80 | |
DUMMY-HEAT-COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | 22888.43 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 10047.97 | 0.80 | |
DUMMY-HEAT-COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | 28686.85 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 10051.76 | 0.80 | |
DUMMY-HEAT-COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | 20014.09 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 8281.90 | 0.80 | |
DUMMY-HEAT-COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | 22758.71 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 10046.32 | 0.80 | |
DUMMY-HEAT-COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | 27910.24 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 8291.78 | 0.80 | |
DUMMY-HEAT-COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | 19338.78 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 6549.91 | 0.80 | |
DUMMY-HEAT-COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | 22215.20 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 8294.11 | 0.80 | |
DUMMY-HEAT-COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | 27676.26 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 8295.10 | 0.80 | |
DUMMY-HEAT-COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | 19249.73 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 6550.39 | 0.80 | |
DUMMY-HEAT-COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | 22087.83 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 8291.71 | 0.80 | |
DUMMY-HEAT-COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | 31346.31 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 10272.89 | 0.80 | |
DUMMY-HEAT-COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | 22798.93 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 8511.04 | 0.80 | |
DUMMY-HEAT-COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | 25641.39 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 10275.63 | 0.80 | |
DUMMY-HEAT-COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | 31530.04 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 10275.21 | 0.80 | |
DUMMY-HEAT-COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | 23015.92 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 8511.27 | 0.80 | |
DUMMY-HEAT-COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | 25876.75 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 10273.76 | 0.80 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 491.98 | 185.57 | 0.38 | 1.00 | 2.16 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 327.43 | 123.50 | 0.38 | 1.00 | 2.63 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 379.50 | 143.14 | 0.38 | 1.00 | 2.44 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 486.89 | 183.65 | 0.38 | 1.00 | 2.17 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 326.27 | 123.07 | 0.38 | 1.00 | 2.64 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 377.10 | 142.24 | 0.38 | 1.00 | 2.45 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 472.52 | 178.23 | 0.38 | 1.00 | 2.20 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 313.77 | 118.35 | 0.38 | 1.00 | 2.70 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 367.04 | 138.44 | 0.38 | 1.00 | 2.48 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 468.18 | 176.59 | 0.38 | 1.00 | 2.20 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 312.12 | 117.73 | 0.38 | 1.00 | 2.70 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 364.68 | 137.55 | 0.38 | 1.00 | 2.49 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 536.14 | 202.23 | 0.38 | 1.00 | 2.08 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 377.84 | 142.52 | 0.38 | 1.00 | 2.44 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 430.48 | 162.38 | 0.38 | 1.00 | 2.29 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 539.54 | 203.51 | 0.38 | 1.00 | 2.07 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 381.86 | 144.04 | 0.38 | 1.00 | 2.43 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 434.84 | 164.02 | 0.38 | 1.00 | 2.28 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 |
Type | Control | Head [psi] | Water Flow [gal/min] | Electricity Rate [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | End Use Subcategory | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 0.82 | 0.57 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 10021.94 | 10021.94 | 8.35 | 491.976 | 491.976 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 75.00 | 75.00 | 0.00758 | 96.13 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6669.88 | 6669.88 | 5.56 | 327.426 | 327.426 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 75.00 | 75.00 | 0.00770 | 92.62 | 0.00686 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7730.65 | 7730.65 | 6.44 | 379.497 | 379.497 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 75.00 | 75.00 | 0.00763 | 94.96 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9918.27 | 9918.27 | 8.26 | 486.887 | 486.887 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 75.00 | 75.00 | 0.00760 | 95.74 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 6646.28 | 6646.28 | 5.54 | 326.267 | 326.267 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 75.00 | 75.00 | 0.00770 | 92.62 | 0.00686 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 7681.71 | 7681.71 | 6.40 | 377.095 | 377.095 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00764 | 94.38 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9625.49 | 9625.49 | 8.02 | 472.516 | 472.516 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 75.00 | 75.00 | 0.00761 | 95.74 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6391.63 | 6391.63 | 5.32 | 313.767 | 313.767 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00774 | 91.45 | 0.00686 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7476.82 | 7476.82 | 6.23 | 367.038 | 367.038 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00766 | 94.38 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9537.21 | 9537.21 | 7.94 | 468.182 | 468.182 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 75.00 | 75.00 | 0.00762 | 95.35 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6358.03 | 6358.03 | 5.30 | 312.118 | 312.118 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00775 | 91.45 | 0.00686 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7428.77 | 7428.77 | 6.19 | 364.679 | 364.679 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00766 | 94.38 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8858.06 | 8858.06 | 7.38 | 434.842 | 434.842 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00762 | 94.38 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8769.26 | 8769.26 | 7.30 | 430.483 | 430.483 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00762 | 94.38 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 10921.61 | 10921.61 | 9.10 | 536.141 | 536.141 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 75.00 | 75.00 | 0.00759 | 95.74 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 7778.78 | 7778.78 | 6.48 | 381.862 | 381.862 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 75.00 | 75.00 | 0.00769 | 92.04 | 0.00686 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 7696.91 | 7696.91 | 6.41 | 377.844 | 377.844 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00769 | 91.45 | 0.00686 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 10990.91 | 10990.91 | 9.15 | 539.544 | 539.544 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 75.00 | 75.00 | 0.00759 | 95.35 | 0.00687 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 6750.06 | 6750.06 | 5.62 | 141.672 | 141.672 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00649 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5190.95 | 5190.95 | 4.32 | 108.951 | 108.951 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00627 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6750.71 | 6750.71 | 5.62 | 141.686 | 141.686 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00649 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6754.05 | 6754.05 | 5.63 | 141.756 | 141.756 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00649 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5192.28 | 5192.28 | 4.32 | 108.978 | 108.978 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00627 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6749.26 | 6749.26 | 5.62 | 141.656 | 141.656 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00649 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5200.96 | 5200.96 | 4.33 | 109.162 | 109.162 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00649 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 3663.87 | 3663.87 | 3.05 | 76.902 | 76.902 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 72.00 | 0.00621 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5203.01 | 5203.01 | 4.33 | 109.205 | 109.205 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00649 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5203.89 | 5203.89 | 4.33 | 109.224 | 109.224 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00649 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3664.29 | 3664.29 | 3.05 | 76.910 | 76.910 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 72.00 | 0.00621 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5200.90 | 5200.90 | 4.33 | 109.161 | 109.161 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00649 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 6949.95 | 6949.95 | 5.79 | 145.868 | 145.868 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 71.99 | 0.00651 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 6951.61 | 6951.61 | 5.79 | 145.902 | 145.902 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 71.99 | 0.00651 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 6949.19 | 6949.19 | 5.79 | 145.852 | 145.852 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 71.99 | 0.00651 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 5394.68 | 5394.68 | 4.49 | 113.226 | 113.226 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 71.99 | 0.00631 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5394.48 | 5394.48 | 4.49 | 113.222 | 113.222 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 71.99 | 0.00631 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 6951.24 | 6951.24 | 5.79 | 145.895 | 145.895 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 72.00 | 71.99 | 0.00651 | 22.64 | 0.00281 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | Adjusted cooling [ft3/min] | Adjusted heating [ft3/min] | Adjusted main [ft3/min] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 491.98 | 491.98 | 141.67 | 141.67 | 491.9757 | 491.9757 | 491.9757 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 327.43 | 327.43 | 108.95 | 108.95 | 327.4257 | 327.4257 | 327.4257 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 379.50 | 379.50 | 141.69 | 141.69 | 379.4975 | 379.4975 | 379.4975 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 486.89 | 486.89 | 141.76 | 141.76 | 486.8869 | 486.8869 | 486.8869 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 326.27 | 326.27 | 108.98 | 108.98 | 326.2668 | 326.2668 | 326.2668 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 377.10 | 377.10 | 141.66 | 141.66 | 377.0950 | 377.0950 | 377.0950 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 472.52 | 472.52 | 109.16 | 109.16 | 472.5157 | 472.5157 | 472.5157 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 313.77 | 313.77 | 76.90 | 76.90 | 313.7674 | 313.7674 | 313.7674 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 367.04 | 367.04 | 109.21 | 109.21 | 367.0379 | 367.0379 | 367.0379 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 468.18 | 468.18 | 109.22 | 109.22 | 468.1822 | 468.1822 | 468.1822 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 312.12 | 312.12 | 76.91 | 76.91 | 312.1180 | 312.1180 | 312.1180 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 364.68 | 364.68 | 109.16 | 109.16 | 364.6790 | 364.6790 | 364.6790 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 536.14 | 536.14 | 145.85 | 145.85 | 536.1409 | 536.1409 | 536.1409 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 377.84 | 377.84 | 113.22 | 113.22 | 377.8436 | 377.8436 | 377.8436 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 430.48 | 430.48 | 145.90 | 145.90 | 430.4831 | 430.4831 | 430.4831 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 539.54 | 539.54 | 145.89 | 145.89 | 539.5436 | 539.5436 | 539.5436 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 381.86 | 381.86 | 113.23 | 113.23 | 381.8624 | 381.8624 | 381.8624 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 434.84 | 434.84 | 145.87 | 145.87 | 434.8423 | 434.8423 | 434.8423 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 15961.602 | 12339.909 | 491.975725 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 7980.80 | 7961.77 | 245.987862 | 78.28 | 58.46 | 0.00751726 | 53.60 | 49.11 | 0.00750000 | 96.13 | 0.00686752 | 63.35 | 18.2915 | 75.00 | 0.00756814 | 35.6219 | 10019.58 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 10047.226 | 10047.226 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 10047.23 | 10047.23 | -999. | 67.48 | 52.31 | 0.00614920 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00648550 | 33.8307 | 6750.06 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 10809.073 | 8289.457 | 327.425734 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 5404.54 | 5341.20 | 163.712867 | 78.77 | 58.73 | 0.00758693 | 53.60 | 49.11 | 0.00750000 | 92.62 | 0.00686443 | 62.24 | 27.4841 | 75.00 | 0.00765745 | 36.0373 | 6634.60 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 8280.399 | 8280.399 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 8280.40 | 8280.40 | -999. | 65.21 | 50.79 | 0.00579393 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00626957 | 32.7149 | 5190.95 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 12510.776 | 9599.628 | 379.497469 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 6255.39 | 6222.92 | 189.748734 | 78.72 | 58.64 | 0.00753818 | 53.60 | 49.11 | 0.00750000 | 94.96 | 0.00686649 | 62.98 | 23.7129 | 75.00 | 0.00753347 | 35.4606 | 7569.59 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 10047.969 | 10047.969 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 10047.97 | 10047.97 | -999. | 66.14 | 51.61 | 0.00604961 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00648560 | 33.8312 | 6750.71 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 15792.308 | 12210.294 | 486.886876 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 7896.15 | 7865.59 | 243.443438 | 78.27 | 58.47 | 0.00752806 | 53.60 | 49.11 | 0.00750000 | 95.74 | 0.00686719 | 63.23 | 18.4827 | 75.00 | 0.00758322 | 35.6921 | 9916.31 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 10051.755 | 10051.755 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 10051.76 | 10051.76 | -999. | 67.43 | 52.28 | 0.00614622 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00648609 | 33.8338 | 6754.05 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 10774.534 | 8261.865 | 326.266777 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 5387.27 | 5324.07 | 163.133388 | 78.78 | 58.74 | 0.00758704 | 53.60 | 49.11 | 0.00750000 | 92.62 | 0.00686443 | 62.24 | 27.5817 | 75.00 | 0.00767624 | 36.1247 | 6621.05 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 8281.905 | 8281.905 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 8281.90 | 8281.90 | -999. | 65.19 | 50.78 | 0.00579247 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00626983 | 32.7163 | 5192.28 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 12393.338 | 9520.885 | 377.095021 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 6196.67 | 6157.99 | 188.547510 | 78.66 | 58.63 | 0.00754590 | 53.60 | 49.11 | 0.00750000 | 94.38 | 0.00686598 | 62.80 | 23.8640 | 75.00 | 0.00762915 | 35.9057 | 7675.49 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 10046.321 | 10046.321 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 10046.32 | 10046.32 | -999. | 66.10 | 51.59 | 0.00604665 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00648539 | 33.8301 | 6749.26 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 15394.291 | 11881.972 | 472.515702 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 7697.15 | 7654.71 | 236.257851 | 78.33 | 58.51 | 0.00754010 | 53.60 | 49.11 | 0.00750000 | 95.74 | 0.00686719 | 63.23 | 19.0449 | 75.00 | 0.00759834 | 35.7625 | 9620.80 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 8291.776 | 8291.776 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 8291.78 | 8291.78 | -999. | 67.29 | 52.22 | 0.00613891 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00648944 | 33.8494 | 5200.96 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 10342.994 | 7936.531 | 313.767353 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5171.50 | 5089.27 | 156.883676 | 78.71 | 58.76 | 0.00761824 | 53.60 | 49.11 | 0.00750000 | 91.45 | 0.00686340 | 61.87 | 28.6805 | 75.00 | 0.00771939 | 36.3254 | 6353.34 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 6549.907 | 6549.907 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 6549.91 | 6549.91 | -999. | 64.92 | 50.55 | 0.00572302 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 72.00 | 0.00621096 | 32.4105 | 3663.87 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 12125.001 | 9296.194 | 367.037905 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 6062.50 | 6011.99 | 183.518953 | 78.73 | 58.68 | 0.00756151 | 53.60 | 49.11 | 0.00750000 | 94.38 | 0.00686598 | 62.80 | 24.5179 | 75.00 | 0.00755147 | 35.5444 | 7330.80 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 8294.107 | 8294.107 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 8294.11 | 8294.11 | -999. | 65.94 | 51.51 | 0.00603852 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00648982 | 33.8514 | 5203.01 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 15236.473 | 11765.166 | 468.182242 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 7618.24 | 7569.05 | 234.091121 | 78.31 | 58.51 | 0.00754698 | 53.60 | 49.11 | 0.00750000 | 95.35 | 0.00686684 | 63.10 | 19.2211 | 75.00 | 0.00761164 | 35.8243 | 9532.87 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 8295.098 | 8295.098 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 8295.10 | 8295.10 | -999. | 67.25 | 52.20 | 0.00613616 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00648998 | 33.8522 | 5203.89 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 10294.027 | 7897.350 | 312.118035 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 5147.01 | 5064.99 | 156.059017 | 78.72 | 58.76 | 0.00761855 | 53.60 | 49.11 | 0.00750000 | 91.45 | 0.00686340 | 61.87 | 28.8320 | 75.00 | 0.00772039 | 36.3300 | 6318.37 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 6550.387 | 6550.387 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 6550.39 | 6550.39 | -999. | 64.88 | 50.53 | 0.00572055 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 72.00 | 0.00621108 | 32.4111 | 3664.29 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 12054.257 | 9239.824 | 364.678998 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 6027.13 | 5976.90 | 182.339499 | 78.74 | 58.68 | 0.00756155 | 53.60 | 49.11 | 0.00750000 | 94.38 | 0.00686598 | 62.80 | 24.6765 | 75.00 | 0.00765033 | 36.0042 | 7410.89 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 8291.711 | 8291.711 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 8291.71 | 8291.71 | -999. | 65.91 | 51.49 | 0.00603525 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00648943 | 33.8494 | 5200.90 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 17270.129 | 13406.371 | 536.140860 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 8635.06 | 8600.93 | 268.070430 | 78.09 | 58.41 | 0.00752851 | 53.60 | 49.11 | 0.00750000 | 95.74 | 0.00686719 | 63.23 | 16.7848 | 75.00 | 0.00757805 | 35.6681 | 10908.15 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 10272.892 | 10272.892 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 10272.89 | 10272.89 | -999. | 67.85 | 52.54 | 0.00620233 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00651326 | 33.9740 | 6949.19 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 12214.620 | 9468.653 | 377.843554 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 6107.31 | 6029.02 | 188.921777 | 78.31 | 58.58 | 0.00759388 | 53.60 | 49.11 | 0.00750000 | 91.45 | 0.00686340 | 61.87 | 23.8167 | 75.00 | 0.00767322 | 36.1107 | 7664.31 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 8511.041 | 8511.041 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 8511.04 | 8511.04 | -999. | 66.12 | 51.32 | 0.00589133 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00630809 | 32.9139 | 5394.48 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 13990.549 | 10808.837 | 430.483140 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 6995.27 | 6951.48 | 215.241570 | 78.38 | 58.53 | 0.00754564 | 53.60 | 49.11 | 0.00750000 | 94.38 | 0.00686598 | 62.80 | 20.9044 | 75.00 | 0.00761715 | 35.8499 | 8757.71 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 10275.629 | 10275.629 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 10275.63 | 10275.63 | -999. | 66.83 | 52.02 | 0.00612632 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00651360 | 33.9758 | 6951.61 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 17340.159 | 13472.776 | 539.543606 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 8670.08 | 8629.06 | 269.771803 | 78.05 | 58.40 | 0.00753410 | 53.60 | 49.11 | 0.00750000 | 95.35 | 0.00686684 | 63.10 | 16.6789 | 75.00 | 0.00758867 | 35.7175 | 10986.38 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 10275.212 | 10275.212 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 10275.21 | 10275.21 | -999. | 67.88 | 52.56 | 0.00620456 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00651355 | 33.9755 | 6951.24 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 12386.218 | 9576.651 | 381.862376 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 6193.11 | 6117.18 | 190.931188 | 78.36 | 58.60 | 0.00758987 | 53.60 | 49.11 | 0.00750000 | 92.04 | 0.00686391 | 62.06 | 23.5661 | 75.00 | 0.00767175 | 36.1039 | 7755.57 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 8511.268 | 8511.268 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 8511.27 | 8511.27 | -999. | 66.18 | 51.36 | 0.00589575 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00630813 | 32.9141 | 5394.68 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 14120.761 | 10912.891 | 434.842264 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 7060.38 | 7016.24 | 217.421132 | 78.36 | 58.53 | 0.00754555 | 53.60 | 49.11 | 0.00750000 | 94.38 | 0.00686598 | 62.80 | 20.6949 | 75.00 | 0.00761631 | 35.8460 | 8838.18 | 0.00 | -999.0 | -999.0 |
DUMMY-HEAT-COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | 0.000 | 0.000 | -999. | -999. | -999.00 | unknown | unknown | unknown | unknown | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Fuel | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 10273.756 | 10273.756 | -999. | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | 10273.76 | 10273.76 | -999. | 66.89 | 52.04 | 0.00613000 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | -999.000 | 71.99 | 0.00651336 | 33.9746 | 6949.95 | 0.00 | -999.0 | -999.0 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [Btu/lbm-R] | Dry Air Heat Capacity [Btu/lbm-R] | Standard Air Density Adjusted for Elevation [lb/ft3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [ft3/min] | Supply Fan Maximum Air Mass Flow Rate [lb/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [Btu/lbm-R] | Plant Fluid Density [lb/ft3] | Plant Maximum Fluid Mass Flow Rate [lb/s] | Plant Design Fluid Return Temperature [F] | Plant Design Fluid Supply Temperature [F] | Plant Design Fluid Temperature Difference [deltaF] | Plant Design Capacity [Btu/h] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] | Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] | Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] | Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [F] | System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | Coil Air Mass Flow Rate at Rating Conditions [lb/s] | Coil Entering Air Drybulb at Rating Conditions [F] | Coil Entering Air Wetbulb at Rating Conditions [F] | Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] | Coil Leaving Air Drybulb at Rating Conditions [F] | Coil Leaving Air Wetbulb at Rating Conditions [F] | Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 15961.602 | 12339.909 | 491.975725 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2433 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 491.975725 | 0.53463084 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | Sensible | 7980.80 | 7961.77 | 1.0000 | 0.26731542 | 245.987862 | 78.28 | 58.46 | 0.00751726 | 10.7 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 7980.80 | 96.13 | 0.00686752 | 63.35 | 44.99498340 | 18.2915 | 75.00 | 0.00758267 | 75.00 | 0.00756814 | 35.6219 | 10019.58 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 10047.226 | 10047.226 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 491.975725 | 0.53463084 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 10047.23 | 10047.23 | 1.0000 | -0.230003E+04 | -999. | 67.48 | 52.31 | 0.00614920 | 8.5 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 10047.23 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00648550 | 71.99 | 0.00648550 | 33.8307 | 6750.06 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10809.073 | 8289.457 | 327.425734 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 327.425734 | 0.35581409 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 5404.54 | 5341.20 | 1.0000 | 0.17790704 | 163.712867 | 78.77 | 58.73 | 0.00758693 | 10.9 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5404.54 | 92.62 | 0.00686443 | 62.24 | 44.99498340 | 27.4841 | 75.00 | 0.00770204 | 75.00 | 0.00765745 | 36.0373 | 6634.60 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 8280.399 | 8280.399 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 327.425734 | 0.35581409 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 8280.40 | 8280.40 | 1.0000 | -0.230003E+04 | -999. | 65.21 | 50.79 | 0.00579393 | 7.9 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8280.40 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00626957 | 71.99 | 0.00626957 | 32.7149 | 5190.95 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 12510.776 | 9599.628 | 379.497469 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2433 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 379.497469 | 0.41240053 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | Sensible | 6255.39 | 6222.92 | 1.0000 | 0.20620026 | 189.748734 | 78.72 | 58.64 | 0.00753818 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6255.39 | 94.96 | 0.00686649 | 62.98 | 44.99498340 | 23.7129 | 75.00 | 0.00762854 | 75.00 | 0.00753347 | 35.4606 | 7569.59 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 10047.969 | 10047.969 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 379.497469 | 0.41240053 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 10047.97 | 10047.97 | 1.0000 | -0.230003E+04 | -999. | 66.14 | 51.61 | 0.00604961 | 8.2 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 10047.97 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00648560 | 71.99 | 0.00648560 | 33.8312 | 6750.71 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 15792.308 | 12210.294 | 486.886876 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2433 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 486.886876 | 0.52910078 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | Sensible | 7896.15 | 7865.59 | 1.0000 | 0.26455039 | 243.443438 | 78.27 | 58.47 | 0.00752806 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 7896.15 | 95.74 | 0.00686719 | 63.23 | 44.99498340 | 18.4827 | 75.00 | 0.00759535 | 75.00 | 0.00758322 | 35.6921 | 9916.31 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 10051.755 | 10051.755 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 486.886876 | 0.52910078 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 10051.76 | 10051.76 | 1.0000 | -0.230003E+04 | -999. | 67.43 | 52.28 | 0.00614622 | 8.4 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 10051.76 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00648609 | 71.99 | 0.00648609 | 33.8338 | 6754.05 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10774.534 | 8261.865 | 326.266777 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 326.266777 | 0.35455465 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 5387.27 | 5324.07 | 1.0000 | 0.17727732 | 163.133388 | 78.78 | 58.74 | 0.00758704 | 10.9 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5387.27 | 92.62 | 0.00686443 | 62.24 | 44.99498340 | 27.5817 | 75.00 | 0.00770264 | 75.00 | 0.00767624 | 36.1247 | 6621.05 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 8281.905 | 8281.905 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 326.266777 | 0.35455465 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 8281.90 | 8281.90 | 1.0000 | -0.230003E+04 | -999. | 65.19 | 50.78 | 0.00579247 | 7.9 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8281.90 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00626983 | 71.99 | 0.00626983 | 32.7163 | 5192.28 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 12393.338 | 9520.885 | 377.095021 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 377.095021 | 0.40978979 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 6196.67 | 6157.99 | 1.0000 | 0.20489489 | 188.547510 | 78.66 | 58.63 | 0.00754590 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6196.67 | 94.38 | 0.00686598 | 62.80 | 44.99498340 | 23.8640 | 75.00 | 0.00763802 | 75.00 | 0.00762915 | 35.9057 | 7675.49 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 10046.321 | 10046.321 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 377.095021 | 0.40978979 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 10046.32 | 10046.32 | 1.0000 | -0.230003E+04 | -999. | 66.10 | 51.59 | 0.00604665 | 8.2 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 10046.32 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00648539 | 71.99 | 0.00648539 | 33.8301 | 6749.26 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 15394.291 | 11881.972 | 472.515702 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2433 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 472.515702 | 0.51348360 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | Sensible | 7697.15 | 7654.71 | 1.0000 | 0.25674180 | 236.257851 | 78.33 | 58.51 | 0.00754010 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 7697.15 | 95.74 | 0.00686719 | 63.23 | 44.99498340 | 19.0449 | 75.00 | 0.00761092 | 75.00 | 0.00759834 | 35.7625 | 9620.80 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 8291.776 | 8291.776 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 472.515702 | 0.51348360 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 8291.78 | 8291.78 | 1.0000 | -0.230003E+04 | -999. | 67.29 | 52.22 | 0.00613891 | 8.4 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8291.78 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00648944 | 71.99 | 0.00648944 | 33.8494 | 5200.96 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10342.994 | 7936.531 | 313.767353 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 313.767353 | 0.34097150 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5171.50 | 5089.27 | 1.0000 | 0.17048575 | 156.883676 | 78.71 | 58.76 | 0.00761824 | 10.9 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5171.50 | 91.45 | 0.00686340 | 61.87 | 44.99498340 | 28.6805 | 75.00 | 0.00774460 | 75.00 | 0.00771939 | 36.3254 | 6353.34 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6549.907 | 6549.907 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 313.767353 | 0.34097150 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 6549.91 | 6549.91 | 1.0000 | -0.230003E+04 | -999. | 64.92 | 50.55 | 0.00572302 | 7.9 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6549.91 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 72.00 | 0.00621096 | 72.00 | 0.00621096 | 32.4105 | 3663.87 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 12125.001 | 9296.194 | 367.037905 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 367.037905 | 0.39886070 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 6062.50 | 6011.99 | 1.0000 | 0.19943035 | 183.518953 | 78.73 | 58.68 | 0.00756151 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6062.50 | 94.38 | 0.00686598 | 62.80 | 44.99498340 | 24.5179 | 75.00 | 0.00765869 | 75.00 | 0.00755147 | 35.5444 | 7330.80 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 8294.107 | 8294.107 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 367.037905 | 0.39886070 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 8294.11 | 8294.11 | 1.0000 | -0.230003E+04 | -999. | 65.94 | 51.51 | 0.00603852 | 8.2 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8294.11 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00648982 | 71.99 | 0.00648982 | 33.8514 | 5203.01 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 15236.473 | 11765.166 | 468.182242 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 468.182242 | 0.50877442 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | Sensible | 7618.24 | 7569.05 | 1.0000 | 0.25438721 | 234.091121 | 78.31 | 58.51 | 0.00754698 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 7618.24 | 95.35 | 0.00686684 | 63.10 | 44.99498340 | 19.2211 | 75.00 | 0.00761930 | 75.00 | 0.00761164 | 35.8243 | 9532.87 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 8295.098 | 8295.098 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 468.182242 | 0.50877442 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 8295.10 | 8295.10 | 1.0000 | -0.230003E+04 | -999. | 67.25 | 52.20 | 0.00613616 | 8.4 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8295.10 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00648998 | 71.99 | 0.00648998 | 33.8522 | 5203.89 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10294.027 | 7897.350 | 312.118035 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 312.118035 | 0.33917919 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 5147.01 | 5064.99 | 1.0000 | 0.16958959 | 156.059017 | 78.72 | 58.76 | 0.00761855 | 10.9 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5147.01 | 91.45 | 0.00686340 | 61.87 | 44.99498340 | 28.8320 | 75.00 | 0.00774575 | 75.00 | 0.00772039 | 36.3300 | 6318.37 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6550.387 | 6550.387 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 312.118035 | 0.33917919 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 6550.39 | 6550.39 | 1.0000 | -0.230003E+04 | -999. | 64.88 | 50.53 | 0.00572055 | 7.8 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6550.39 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 72.00 | 0.00621108 | 72.00 | 0.00621108 | 32.4111 | 3664.29 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 12054.257 | 9239.824 | 364.678998 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 364.678998 | 0.39629727 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 6027.13 | 5976.90 | 1.0000 | 0.19814864 | 182.339499 | 78.74 | 58.68 | 0.00756155 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6027.13 | 94.38 | 0.00686598 | 62.80 | 44.99498340 | 24.6765 | 75.00 | 0.00765945 | 75.00 | 0.00765033 | 36.0042 | 7410.89 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 8291.711 | 8291.711 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 364.678998 | 0.39629727 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | Sensible | 8291.71 | 8291.71 | 1.0000 | -0.230003E+04 | -999. | 65.91 | 51.49 | 0.00603525 | 8.2 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8291.71 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00648943 | 71.99 | 0.00648943 | 33.8494 | 5200.90 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 17270.129 | 13406.371 | 536.140860 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2433 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 536.140860 | 0.58262516 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | Sensible | 8635.06 | 8600.93 | 1.0000 | 0.29131258 | 268.070430 | 78.09 | 58.41 | 0.00752851 | 10.7 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8635.06 | 95.74 | 0.00686719 | 63.23 | 44.99498340 | 16.7848 | 75.00 | 0.00758909 | 75.00 | 0.00757805 | 35.6681 | 10908.15 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 10272.892 | 10272.892 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 536.140860 | 0.58262516 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 10272.89 | 10272.89 | 1.0000 | -0.230003E+04 | -999. | 67.85 | 52.54 | 0.00620233 | 8.5 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 10272.89 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00651326 | 71.99 | 0.00651326 | 33.9740 | 6949.19 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 12214.620 | 9468.653 | 377.843554 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 377.843554 | 0.41060322 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 6107.31 | 6029.02 | 1.0000 | 0.20530161 | 188.921777 | 78.31 | 58.58 | 0.00759388 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6107.31 | 91.45 | 0.00686340 | 61.87 | 44.99498340 | 23.8167 | 75.00 | 0.00769263 | 75.00 | 0.00767322 | 36.1107 | 7664.31 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 8511.041 | 8511.041 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 377.843554 | 0.41060322 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 8511.04 | 8511.04 | 1.0000 | -0.230003E+04 | -999. | 66.12 | 51.32 | 0.00589133 | 8.1 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8511.04 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00630809 | 71.99 | 0.00630809 | 32.9139 | 5394.48 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 13990.549 | 10808.837 | 430.483140 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 430.483140 | 0.46780674 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 6995.27 | 6951.48 | 1.0000 | 0.23390337 | 215.241570 | 78.38 | 58.53 | 0.00754564 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6995.27 | 94.38 | 0.00686598 | 62.80 | 44.99498340 | 20.9044 | 75.00 | 0.00762498 | 75.00 | 0.00761715 | 35.8499 | 8757.71 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 10275.629 | 10275.629 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 430.483140 | 0.46780674 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 10275.63 | 10275.63 | 1.0000 | -0.230003E+04 | -999. | 66.83 | 52.02 | 0.00612632 | 8.4 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 10275.63 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00651360 | 71.99 | 0.00651360 | 33.9758 | 6951.61 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 17340.159 | 13472.776 | 539.543606 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2433 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 539.543606 | 0.58632293 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | Sensible | 8670.08 | 8629.06 | 1.0000 | 0.29316147 | 269.771803 | 78.05 | 58.40 | 0.00753410 | 10.7 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8670.08 | 95.35 | 0.00686684 | 63.10 | 44.99498340 | 16.6789 | 75.00 | 0.00759480 | 75.00 | 0.00758867 | 35.7175 | 10986.38 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 10275.212 | 10275.212 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 539.543606 | 0.58632293 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 10275.21 | 10275.21 | 1.0000 | -0.230003E+04 | -999. | 67.88 | 52.56 | 0.00620456 | 8.5 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 10275.21 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00651355 | 71.99 | 0.00651355 | 33.9755 | 6951.24 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 12386.218 | 9576.651 | 381.862376 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 381.862376 | 0.41497048 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 6193.11 | 6117.18 | 1.0000 | 0.20748524 | 190.931188 | 78.36 | 58.60 | 0.00758987 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6193.11 | 92.04 | 0.00686391 | 62.06 | 44.99498340 | 23.5661 | 75.00 | 0.00768684 | 75.00 | 0.00767175 | 36.1039 | 7755.57 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 8511.268 | 8511.268 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 381.862376 | 0.41497048 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 8511.27 | 8511.27 | 1.0000 | -0.230003E+04 | -999. | 66.18 | 51.36 | 0.00589575 | 8.1 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 8511.27 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00630813 | 71.99 | 0.00630813 | 32.9141 | 5394.68 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 14120.761 | 10912.891 | 434.842264 | -999. | -999.00 | -999.0000 | 1.00000 | 0.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 434.842264 | 0.47254381 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 7060.38 | 7016.24 | 1.0000 | 0.23627191 | 217.421132 | 78.36 | 58.53 | 0.00754555 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 7060.38 | 94.38 | 0.00686598 | 62.80 | 44.99498340 | 20.6949 | 75.00 | 0.00762399 | 75.00 | 0.00761631 | 35.8460 | 8838.18 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DUMMY-HEAT-COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Gas:MultiStage | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 0.000 | 0.000 | -999. | -999. | -999.00 | -999.0000 | -999.00000 | -999.00000 | -999.000 | 0.2400 | 0.0652 | unknown | unknown | -999. | -999. | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | -999.0 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | -999.00 | 0.00 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 10273.756 | 10273.756 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 434.842264 | 0.47254381 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:10:00 | Sensible | 10273.76 | 10273.76 | 1.0000 | -0.230003E+04 | -999. | 66.89 | 52.04 | 0.00613000 | 8.4 | 122.00 | 72.00 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 10273.76 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | -999.000 | 71.99 | 0.00651336 | 71.99 | 0.00651336 | 33.9746 | 6949.95 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. |
Report: System Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2748.83 | 4145.50 | 184.50 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2195.50 | 4263.00 | 136.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2687.17 | 4049.50 | 148.50 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2585.33 | 4737.33 | 194.50 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2025.50 | 4880.50 | 145.17 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2536.17 | 4611.33 | 155.67 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2899.83 | 3583.00 | 59.83 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2334.83 | 3487.83 | 42.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2851.50 | 3467.83 | 47.83 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2717.67 | 4234.50 | 63.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2134.17 | 4356.67 | 42.17 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2656.00 | 4190.17 | 48.67 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 2888.50 | 4241.33 | 84.33 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 3019.67 | 3796.33 | 80.33 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 2991.00 | 3885.33 | 100.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2510.33 | 4408.00 | 69.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 2638.33 | 3893.50 | 67.17 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 2886.67 | 4333.17 | 107.83 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 3309.83 | 5085.17 | 208.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.107 | 0.000 | 0.270 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.094 | 0.000 | 0.270 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.107 | 0.000 | 0.270 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.106 | 0.000 | 0.270 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.094 | 0.000 | 0.270 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.106 | 0.000 | 0.270 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.047 | 0.000 | 0.270 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.034 | 0.000 | 0.270 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.047 | 0.000 | 0.270 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.047 | 0.000 | 0.270 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.034 | 0.000 | 0.270 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.047 | 0.000 | 0.270 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.106 | 0.000 | 0.270 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.107 | 0.000 | 0.270 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.107 | 0.000 | 0.270 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.094 | 0.000 | 0.270 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.094 | 0.000 | 0.270 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.106 | 0.000 | 0.270 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Zone Area [ft2] | Design Zone Outdoor Airflow - Voz [ft3/min] | Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
Total Facility | 24.79 | 36.00 | 183739.38 | 21609.96 | 0.0000 | 0.000 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Infiltration [ft3] | Total Ventilation and Infiltration [ft3] | Dynamic Target Ventilation - Voz-dyn [ft3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 9428051.74 | 33269545.26 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 8314227.00 | 32155720.53 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 9436421.90 | 33277915.43 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 9403384.92 | 33244878.45 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 8282245.57 | 32123739.09 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 9403947.89 | 33245441.42 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 4139575.49 | 27982450.35 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 3016567.33 | 26859442.18 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 4143178.94 | 27986053.79 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 4129507.94 | 27972382.79 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 3005904.12 | 26848778.98 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 4130216.01 | 27973090.87 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 9419930.35 | 33264187.99 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 9445533.11 | 33289790.75 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 9437756.70 | 33282014.34 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 8298660.16 | 32142917.80 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 8323193.69 | 32167451.33 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 9418946.93 | 33263204.57 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
Total Facility | 0.00 | 0.429172E+09 | 0.429172E+09 | 0.131177E+09 | 0.560349E+09 | 0.428131E+09 | 3814.50 | 1362.50 | 3646.00 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Infiltration [ft3/min] | Total Ventilation and Infiltration [ft3/min] | Dynamic Target Ventilation - Voz-dyn [ft3/min] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 17.8353 | 62.9370 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 15.7283 | 60.8300 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 17.8512 | 62.9529 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 17.7887 | 62.8904 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 15.6678 | 60.7695 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 17.7897 | 62.8914 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 7.8310 | 52.9353 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 5.7065 | 50.8108 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 7.8378 | 52.9421 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 7.8119 | 52.9162 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 5.6864 | 50.7907 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 7.8133 | 52.9176 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 17.8200 | 62.9269 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 17.8684 | 62.9753 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 17.8537 | 62.9606 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 15.6988 | 60.8058 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 15.7452 | 60.8522 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 17.8181 | 62.9250 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
Total Facility | 0.0000 | 811.8776 | 811.8776 | 248.1521 | 1060.0298 | 809.9097 | 3814.50 | 1362.50 | 3646.00 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [ft3/min] | Limits and Scheduled Limits [ft3/min] | Economizer [ft3/min] | Exhaust Flow [ft3/min] | Mixed Air Flow [ft3/min] | High Humidity [ft3/min] | Demand Controlled Ventilation [ft3/min] | Night Ventilation [ft3/min] | Demand Limiting [ft3/min] | Energy Management System [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 58 |
Floor | 29 | 4 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 60 | 60 |
Overhang | 30 | 30 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1994 |
Defaulted Fields | 1933 |
Fields with Defaults | 7099 |
Autosized Fields | 468 |
Autosizable Fields | 954 |
Autocalculated Fields | 161 |
Autocalculatable Fields | 349 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 113856.65 | 7786.08 | 27-FEB-12:40 | 27871.69 | 26-JUL-18:10 |
Electricity:Building | 85365.22 | 6873.11 | 02-JAN-03:10 | 15890.03 | 01-JAN-20:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
Electricity:SpaceType:GENERAL | 85365.22 | 6873.11 | 02-JAN-03:10 | 15890.03 | 01-JAN-20:10 |
InteriorLights:Electricity | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
General:InteriorLights:Electricity | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:SpaceType:GENERAL | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4742.51 | 381.84 | 02-JAN-03:10 | 882.78 | 01-JAN-20:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
InteriorEquipment:Electricity | 74028.41 | 6408.15 | 02-JAN-04:10 | 12197.25 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 74028.41 | 6408.15 | 02-JAN-04:10 | 12197.25 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity | 1717.21 | 15.72 | 02-JAN-03:10 | 547.93 | 01-JAN-19:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL | 1717.21 | 15.72 | 02-JAN-03:10 | 547.93 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity | 11154.55 | 1110.97 | 01-JAN-04:10 | 1518.99 | 01-JAN-18:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 11154.55 | 1110.97 | 01-JAN-04:10 | 1518.99 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity | 713.84 | 6.86 | 02-JAN-02:10 | 193.33 | 01-JAN-09:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL | 713.84 | 6.86 | 02-JAN-02:10 | 193.33 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity | 1138.84 | 5.81 | 02-JAN-03:10 | 291.20 | 01-JAN-11:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL | 1138.84 | 5.81 | 02-JAN-03:10 | 291.20 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_range:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity | 41935.01 | 3663.85 | 01-JAN-09:10 | 7086.44 | 01-JAN-20:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
gas_mels:InteriorEquipment:Electricity:SpaceType:GENERAL | 41935.01 | 3663.85 | 01-JAN-09:10 | 7086.44 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity | 17368.96 | 1517.52 | 01-JAN-09:10 | 2935.11 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL | 17368.96 | 1517.52 | 01-JAN-09:10 | 2935.11 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4112.69 | 356.01 | 02-JAN-04:10 | 677.62 | 01-JAN-20:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 63.27 | 0.32 | 02-JAN-03:10 | 16.18 | 01-JAN-11:10 |
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 2329.72 | 203.55 | 01-JAN-09:10 | 393.69 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 964.94 | 84.31 | 01-JAN-09:10 | 163.06 | 01-JAN-20:10 |
Fans:Electricity | 6987.82 | 289.29 | 08-FEB-06:00 | 3076.13 | 02-JAN-05:30 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 113856.65 | 7786.08 | 27-FEB-12:40 | 27871.69 | 26-JUL-18:10 |
ElectricityPurchased:Plant | 113856.65 | 7786.08 | 27-FEB-12:40 | 27871.69 | 26-JUL-18:10 |
Cogeneration:ElectricityPurchased | 113856.65 | 7786.08 | 27-FEB-12:40 | 27871.69 | 26-JUL-18:10 |
General:Cogeneration:ElectricityPurchased | 113856.65 | 7786.08 | 27-FEB-12:40 | 27871.69 | 26-JUL-18:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 113856.65 | 7786.08 | 27-FEB-12:40 | 27871.69 | 26-JUL-18:10 |
ElectricityNet:Plant | 113856.65 | 7786.08 | 27-FEB-12:40 | 27871.69 | 26-JUL-18:10 |
Cogeneration:ElectricityNet | 113856.65 | 7786.08 | 27-FEB-12:40 | 27871.69 | 26-JUL-18:10 |
General:Cogeneration:ElectricityNet | 113856.65 | 7786.08 | 27-FEB-12:40 | 27871.69 | 26-JUL-18:10 |
Electricity:HVAC | 24396.59 | 289.29 | 08-FEB-06:00 | 12153.10 | 26-JUL-17:40 |
Ventilation:Fans:Electricity | 2534.14 | 289.29 | 01-JAN-00:10 | 289.29 | 01-JAN-00:10 |
General:Fans:Electricity | 4453.67 | 0.00 | 08-FEB-06:00 | 2786.84 | 02-JAN-05:30 |
ExteriorLights:Electricity | 4094.83 | 0.00 | 01-JAN-06:10 | 934.89 | 01-JAN-00:10 |
Exterior-Lights:ExteriorLights:Electricity | 4094.83 | 0.00 | 01-JAN-06:10 | 934.89 | 01-JAN-00:10 |
Garage-Lights:ExteriorLights:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 17408.78 | 0.00 | 01-JAN-00:30 | 10913.00 | 26-JUL-17:30 |
General:Cooling:Electricity | 17408.78 | 0.00 | 01-JAN-00:30 | 10913.00 | 26-JUL-17:30 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Natural Gas Annual Value [therm] | Natural Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3730.54 | 2644.47 | 07-FEB-04:00 | 190285.22 | 01-JAN-11:20 |
NaturalGas:Building | 1639.73 | 2644.47 | 02-JAN-03:10 | 43735.22 | 01-JAN-17:10 |
NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
NaturalGas:SpaceType:GENERAL | 1639.73 | 2644.47 | 02-JAN-03:10 | 43735.22 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas | 1639.73 | 2644.47 | 02-JAN-03:10 | 43735.22 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:SpaceType:GENERAL | 1639.73 | 2644.47 | 02-JAN-03:10 | 43735.22 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas | 792.69 | 403.80 | 02-JAN-03:10 | 20254.25 | 01-JAN-11:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_dryer:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 792.69 | 403.80 | 02-JAN-03:10 | 20254.25 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas | 674.43 | 651.88 | 01-JAN-02:10 | 27685.38 | 01-JAN-17:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_range:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 674.43 | 651.88 | 01-JAN-02:10 | 27685.38 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas | 172.61 | 1507.04 | 01-JAN-09:10 | 2914.85 | 01-JAN-20:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
gas_mels:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 172.61 | 1507.04 | 01-JAN-09:10 | 2914.85 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:10 | 2429.73 | 01-JAN-17:10 |
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 44.04 | 22.43 | 02-JAN-03:10 | 1125.24 | 01-JAN-11:10 |
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 37.47 | 36.22 | 01-JAN-02:10 | 1538.08 | 01-JAN-17:10 |
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 9.59 | 83.72 | 01-JAN-09:10 | 161.94 | 01-JAN-20:10 |
NaturalGas:HVAC | 337.25 | 0.00 | 01-JAN-11:40 | 92428.72 | 27-DEC-07:10 |
Heating:NaturalGas | 337.25 | 0.00 | 01-JAN-11:40 | 92428.72 | 27-DEC-07:10 |
General:Heating:NaturalGas | 337.25 | 0.00 | 01-JAN-11:40 | 92428.72 | 27-DEC-07:10 |
NaturalGas:Plant | 1753.55 | 0.00 | 01-JAN-00:10 | 162664.19 | 01-JAN-02:10 |
WaterSystems:NaturalGas | 1753.55 | 0.00 | 01-JAN-00:10 | 162664.19 | 01-JAN-02:10 |
Water Heater:WaterSystems:NaturalGas | 1753.55 | 0.00 | 01-JAN-00:10 | 162664.19 | 01-JAN-02:10 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 25405.07 | 0.00 | 02-JAN-02:10 | 0.09 | 01-JAN-08:10 |
Water:Plant | 25405.07 | 0.00 | 02-JAN-02:10 | 0.09 | 01-JAN-08:10 |
WaterSystems:Water | 25405.07 | 0.00 | 02-JAN-02:10 | 0.09 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:Water | 25405.07 | 0.00 | 02-JAN-02:10 | 0.09 | 01-JAN-08:10 |
MainsWater:Facility | 25405.07 | 0.00 | 02-JAN-02:10 | 0.09 | 01-JAN-08:10 |
MainsWater:Plant | 25405.07 | 0.00 | 02-JAN-02:10 | 0.09 | 01-JAN-08:10 |
WaterSystems:MainsWater | 25405.07 | 0.00 | 02-JAN-02:10 | 0.09 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:MainsWater | 25405.07 | 0.00 | 02-JAN-02:10 | 0.09 | 01-JAN-08:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 883505.43 | 530.95 | 11-OCT-03:00 | 331432.93 | 26-JUL-18:10 |
EnergyTransfer:Building | 398013.70 | 0.00 | 08-FEB-06:00 | 159143.39 | 15-JUN-18:10 |
EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer | 39572.53 | 0.00 | 01-JAN-13:30 | 83451.69 | 27-DEC-07:10 |
Heating:EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 39572.53 | 0.00 | 01-JAN-13:30 | 83451.69 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 358441.17 | 0.00 | 01-JAN-00:30 | 159143.39 | 15-JUN-18:10 |
Cooling:EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer | 358441.17 | 0.00 | 01-JAN-00:30 | 159143.39 | 15-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 24008.79 | 0.00 | 01-JAN-00:10 | 11264.22 | 15-JUN-17:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2806.65 | 0.00 | 01-JAN-00:10 | 5513.27 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2806.65 | 0.00 | 01-JAN-00:10 | 5513.27 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 21202.14 | 0.00 | 01-JAN-00:10 | 11264.22 | 15-JUN-17:20 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 21202.14 | 0.00 | 01-JAN-00:10 | 11264.22 | 15-JUN-17:20 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 18496.94 | 0.00 | 01-JAN-00:10 | 7079.82 | 14-JUN-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1559.33 | 0.00 | 01-JAN-00:10 | 4078.76 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1559.33 | 0.00 | 01-JAN-00:10 | 4078.76 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 16937.61 | 0.00 | 01-JAN-00:10 | 7079.82 | 14-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 16937.61 | 0.00 | 01-JAN-00:10 | 7079.82 | 14-JUN-18:10 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 23371.59 | 0.00 | 01-JAN-00:10 | 8084.41 | 14-JUN-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2485.16 | 0.00 | 01-JAN-00:10 | 5528.08 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2485.16 | 0.00 | 01-JAN-00:10 | 5528.08 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 20886.43 | 0.00 | 01-JAN-00:10 | 8084.41 | 14-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 20886.43 | 0.00 | 01-JAN-00:10 | 8084.41 | 14-JUN-18:10 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 21909.79 | 0.00 | 01-JAN-13:20 | 11436.17 | 15-JUN-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 3795.08 | 0.00 | 01-JAN-13:20 | 5534.79 | 03-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 3795.08 | 0.00 | 01-JAN-13:20 | 5534.79 | 03-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 18114.70 | 0.00 | 01-JAN-00:10 | 11436.17 | 15-JUN-17:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 18114.70 | 0.00 | 01-JAN-00:10 | 11436.17 | 15-JUN-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 16492.80 | 0.00 | 01-JAN-00:10 | 7251.48 | 14-JUN-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2523.42 | 0.00 | 01-JAN-00:10 | 4195.65 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2523.42 | 0.00 | 01-JAN-00:10 | 4195.65 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 13969.38 | 0.00 | 01-JAN-00:10 | 7251.48 | 14-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 13969.38 | 0.00 | 01-JAN-00:10 | 7251.48 | 14-JUN-18:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 21270.87 | 0.00 | 01-JAN-11:00 | 8276.98 | 14-JUN-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 3408.80 | 0.00 | 01-JAN-11:00 | 5623.26 | 03-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 3408.80 | 0.00 | 01-JAN-11:00 | 5623.26 | 03-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 17862.07 | 0.00 | 01-JAN-00:10 | 8276.98 | 14-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 17862.07 | 0.00 | 01-JAN-00:10 | 8276.98 | 14-JUN-18:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 24739.46 | 0.00 | 01-JAN-00:10 | 10564.78 | 15-JUN-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1353.38 | 0.00 | 01-JAN-00:10 | 4113.99 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1353.38 | 0.00 | 01-JAN-00:10 | 4113.99 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 23386.08 | 0.00 | 01-JAN-00:10 | 10564.78 | 15-JUN-17:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 23386.08 | 0.00 | 01-JAN-00:10 | 10564.78 | 15-JUN-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 19936.81 | 0.00 | 01-JAN-00:30 | 6587.96 | 02-JUL-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 495.46 | 0.00 | 01-JAN-00:10 | 2698.50 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 495.46 | 0.00 | 01-JAN-00:10 | 2698.50 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 19441.35 | 0.00 | 01-JAN-00:30 | 6587.96 | 02-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 19441.35 | 0.00 | 01-JAN-00:30 | 6587.96 | 02-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 24500.14 | 0.00 | 01-JAN-00:10 | 7733.62 | 02-JUL-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1179.80 | 0.00 | 01-JAN-00:10 | 4139.85 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1179.80 | 0.00 | 01-JAN-00:10 | 4139.85 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 23320.33 | 0.00 | 01-JAN-00:10 | 7733.62 | 02-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 23320.33 | 0.00 | 01-JAN-00:10 | 7733.62 | 02-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 21893.71 | 0.00 | 01-JAN-00:10 | 10757.22 | 15-JUN-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2011.63 | 0.00 | 01-JAN-00:10 | 4171.39 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2011.63 | 0.00 | 01-JAN-00:10 | 4171.39 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 19882.08 | 0.00 | 01-JAN-00:10 | 10757.22 | 15-JUN-17:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 19882.08 | 0.00 | 01-JAN-00:10 | 10757.22 | 15-JUN-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 16833.65 | 0.00 | 01-JAN-00:10 | 6752.91 | 15-JUN-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1012.50 | 0.00 | 01-JAN-00:10 | 2861.17 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1012.50 | 0.00 | 01-JAN-00:10 | 2861.17 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 15821.15 | 0.00 | 01-JAN-00:10 | 6752.91 | 15-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 15821.15 | 0.00 | 01-JAN-00:10 | 6752.91 | 15-JUN-18:30 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 21514.76 | 0.00 | 01-JAN-00:10 | 7845.95 | 14-JUN-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1746.05 | 0.00 | 01-JAN-00:10 | 4132.89 | 03-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1746.05 | 0.00 | 01-JAN-00:10 | 4132.89 | 03-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 19768.71 | 0.00 | 01-JAN-00:10 | 7845.95 | 14-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 19768.71 | 0.00 | 01-JAN-00:10 | 7845.95 | 14-JUN-18:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 24451.54 | 0.00 | 01-JAN-00:10 | 9374.29 | 02-JUL-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 3101.01 | 0.00 | 01-JAN-00:10 | 5748.09 | 03-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 3101.01 | 0.00 | 01-JAN-00:10 | 5748.09 | 03-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 21350.52 | 0.00 | 01-JAN-00:10 | 9374.29 | 02-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 21350.52 | 0.00 | 01-JAN-00:10 | 9374.29 | 02-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 25955.11 | 0.00 | 01-JAN-00:10 | 9245.34 | 02-JUL-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 2324.16 | 0.00 | 01-JAN-00:10 | 5690.79 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 2324.16 | 0.00 | 01-JAN-00:10 | 5690.79 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 23630.95 | 0.00 | 01-JAN-00:10 | 9245.34 | 02-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 23630.95 | 0.00 | 01-JAN-00:10 | 9245.34 | 02-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 26565.09 | 0.00 | 01-JAN-00:10 | 11893.40 | 15-JUN-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 2656.92 | 0.00 | 01-JAN-00:10 | 5661.08 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 2656.92 | 0.00 | 01-JAN-00:10 | 5661.08 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 23908.17 | 0.00 | 01-JAN-00:10 | 11893.40 | 15-JUN-17:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 23908.17 | 0.00 | 01-JAN-00:10 | 11893.40 | 15-JUN-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 19732.90 | 0.00 | 01-JAN-00:10 | 8243.29 | 02-JUL-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 2206.55 | 0.00 | 01-JAN-00:10 | 4352.64 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 2206.55 | 0.00 | 01-JAN-00:10 | 4352.64 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 17526.35 | 0.00 | 01-JAN-00:10 | 8243.29 | 02-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 17526.35 | 0.00 | 01-JAN-00:10 | 8243.29 | 02-JUL-18:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 21245.06 | 0.00 | 01-JAN-00:10 | 8103.92 | 02-JUL-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 1409.86 | 0.00 | 01-JAN-00:10 | 4247.36 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 1409.86 | 0.00 | 01-JAN-00:10 | 4247.36 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 19835.20 | 0.00 | 01-JAN-00:10 | 8103.92 | 02-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 19835.20 | 0.00 | 01-JAN-00:10 | 8103.92 | 02-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 25094.70 | 0.00 | 01-JAN-00:10 | 12104.74 | 15-JUN-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 3496.75 | 0.00 | 01-JAN-00:10 | 5700.87 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 3496.75 | 0.00 | 01-JAN-00:10 | 5700.87 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 21597.95 | 0.00 | 01-JAN-00:10 | 12104.74 | 15-JUN-17:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 21597.95 | 0.00 | 01-JAN-00:10 | 12104.74 | 15-JUN-17:30 |
PlantLoopHeatingDemand:Facility | 56012.32 | 400.03 | 01-AUG-03:00 | 16116.70 | 29-JAN-09:00 |
PlantLoopHeatingDemand:Plant | 56012.32 | 400.03 | 01-AUG-03:00 | 16116.70 | 29-JAN-09:00 |
WaterSystems:PlantLoopHeatingDemand | 56012.32 | 400.03 | 01-AUG-03:00 | 16116.70 | 29-JAN-09:00 |
General:WaterSystems:PlantLoopHeatingDemand | 56012.32 | 400.03 | 01-AUG-03:00 | 16116.70 | 29-JAN-09:00 |
EnergyTransfer:HVAC | 429479.40 | 0.00 | 04-JAN-02:20 | 172893.19 | 26-JUL-18:10 |
HeatingCoils:EnergyTransfer | 26980.23 | 0.00 | 01-JAN-11:40 | 73942.98 | 27-DEC-07:10 |
CoolingCoils:EnergyTransfer | 402499.17 | 0.00 | 01-JAN-00:30 | 172893.19 | 26-JUL-18:10 |
EnergyTransfer:Plant | 56012.32 | 400.03 | 01-AUG-03:00 | 16116.70 | 29-JAN-09:00 |
WaterSystems:EnergyTransfer | 56012.32 | 400.03 | 01-AUG-03:00 | 16116.70 | 29-JAN-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 56012.32 | 400.03 | 01-AUG-03:00 | 16116.70 | 29-JAN-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 2806.623 | -1765.66 | 0.000 | 0.000 | 2954.395 | 2150.478 | 14073.672 | 10625.196 | 0.000 | 1335.873 | 0.175 | 0.000 | -3490.03 | 0.000 | -6905.60 | -2348.52 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 1559.318 | -1410.53 | 0.000 | 0.000 | 2941.083 | 2150.478 | 14073.672 | 4668.414 | 0.000 | 1289.322 | 0.030 | 0.000 | -1405.57 | 0.000 | -6720.39 | -1618.71 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 2485.132 | -1739.38 | 0.000 | 0.000 | 2953.177 | 2150.478 | 14073.672 | 10656.532 | 0.000 | 1335.894 | 0.041 | 0.000 | -3378.76 | 0.000 | -6941.90 | -2447.77 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 3795.054 | -1508.55 | 0.000 | 0.000 | 2967.977 | 2150.478 | 14073.672 | 7511.915 | 0.000 | 1335.865 | 0.079 | 0.000 | -3578.76 | 0.000 | -6797.26 | -3344.26 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 2523.400 | -1163.34 | 0.000 | 0.000 | 2962.031 | 2150.478 | 14073.672 | 1445.406 | 0.000 | 1289.307 | 0.072 | 0.000 | -1476.35 | 0.000 | -6564.96 | -2433.57 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 3408.778 | -1487.51 | 0.000 | 0.000 | 2971.895 | 2150.478 | 14073.672 | 7468.400 | 0.000 | 1335.880 | 0.033 | 0.000 | -3371.00 | 0.000 | -6795.67 | -3380.32 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 1353.366 | -1947.54 | 0.000 | 0.000 | 2933.172 | 2150.478 | 14073.672 | 10550.592 | 0.000 | 1113.006 | 659.484 | 0.000 | -3606.70 | 0.000 | -5841.01 | -0.24 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 495.457 | -1619.03 | 0.000 | 0.000 | 2915.585 | 2150.478 | 14073.672 | 4632.247 | 0.000 | 1066.622 | 1219.394 | 0.000 | -1452.67 | 0.000 | -5659.40 | -0.26 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 1179.792 | -1942.07 | 0.000 | 0.000 | 2931.766 | 2150.478 | 14073.672 | 10576.950 | 0.000 | 1113.023 | 654.999 | 0.000 | -3488.99 | 0.000 | -5871.32 | -0.22 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 2011.612 | -1655.73 | 0.000 | 0.000 | 2945.715 | 2150.478 | 14073.672 | 7456.581 | 0.000 | 1112.999 | 0.057 | 0.000 | -3705.04 | 0.000 | -5758.51 | -405.42 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 1012.489 | -1317.55 | 0.000 | 0.000 | 2934.716 | 2150.478 | 14073.672 | 1429.463 | 0.000 | 1066.611 | 228.767 | 0.000 | -1532.32 | 0.000 | -5542.66 | -0.03 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 1746.037 | -1646.30 | 0.000 | 0.000 | 2950.068 | 2150.478 | 14073.672 | 7401.537 | 0.000 | 1113.015 | 0.006 | 0.000 | -3486.35 | 0.000 | -5761.46 | -418.23 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 3100.987 | -1778.03 | 0.000 | 0.000 | 2961.078 | 2150.478 | 14073.672 | 7392.972 | 0.000 | 1326.770 | 688.213 | 0.000 | -3470.98 | 0.000 | -6872.62 | -0.09 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 2324.137 | -1967.93 | 0.000 | 0.000 | 2946.336 | 2150.478 | 14073.672 | 10579.190 | 0.000 | 1326.776 | 674.386 | 0.000 | -3454.78 | 0.000 | -6989.20 | -0.43 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 2656.897 | -1991.01 | 0.000 | 0.000 | 2947.349 | 2150.478 | 14073.672 | 10547.868 | 0.000 | 1326.758 | 728.230 | 0.000 | -3567.11 | 0.000 | -6955.99 | -0.32 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 2206.534 | -1459.56 | 0.000 | 0.000 | 2949.356 | 2150.478 | 14073.672 | 1424.325 | 0.000 | 1280.527 | 1613.092 | 0.000 | -1520.18 | 0.000 | -6651.41 | -0.04 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 1409.844 | -1651.83 | 0.000 | 0.000 | 2933.536 | 2150.478 | 14073.672 | 4631.572 | 0.000 | 1280.533 | 1563.862 | 0.000 | -1435.87 | 0.000 | -6772.40 | -0.21 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 3496.721 | -1798.63 | 0.000 | 0.000 | 2957.406 | 2150.478 | 14073.672 | 7434.920 | 0.000 | 1326.752 | 706.248 | 0.000 | -3675.22 | 0.000 | -6873.04 | -0.42 |
CRAWLSPACE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 68979.270 | 23439.370 | 0.000 | 0.000 | 0.000 | -92418.64 | -3.11 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26379.417 | 188675.725 | 0.000 | 0.000 | 0.000 | -215055.14 | -2.69 |
Total Facility | 0.000 | 0.000 | 39572.176 | -29850.17 | 0.000 | 0.000 | 53056.643 | 38708.604 | 253326.094 | 126434.079 | 0.000 | 117734.220 | 220852.264 | 0.000 | -51096.66 | 0.000 | -423748.58 | -16404.87 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 15-JUN-17:24 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 263.18 | 469.21 | 2697.56 | 5445.48 | 0.00 | 1529.33 | 859.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 14-JUN-18:15 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 426.77 | 631.63 | 2590.59 | 463.50 | 0.00 | 1439.45 | 1528.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 14-JUN-18:15 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 426.77 | 631.63 | 2590.59 | 1121.86 | 0.00 | 1506.26 | 1807.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 15-JUN-17:34 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 263.18 | 469.21 | 2697.56 | 5780.37 | 0.00 | 1483.36 | 742.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 14-JUN-18:15 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 426.77 | 631.63 | 2590.59 | 821.68 | 0.00 | 1439.44 | 1341.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 14-JUN-18:15 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 426.77 | 631.63 | 2590.59 | 1478.32 | 0.00 | 1506.27 | 1643.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 15-JUN-17:34 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 263.18 | 469.21 | 2697.56 | 5284.24 | 0.00 | 1163.97 | 686.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 02-JUL-18:13 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 426.79 | 631.63 | 2616.29 | 465.05 | 0.00 | 1036.47 | 1415.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 02-JUL-18:13 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 426.79 | 631.63 | 2616.29 | 1138.74 | 0.00 | 1095.44 | 1828.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 15-JUN-17:34 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 263.18 | 469.21 | 2697.56 | 5774.30 | 0.00 | 1163.98 | 389.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 15-JUN-18:34 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 426.77 | 631.63 | 2590.59 | 927.50 | 0.00 | 966.52 | 1210.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 14-JUN-18:15 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 426.77 | 631.63 | 2590.59 | 1492.46 | 0.00 | 1190.29 | 1514.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 02-JUL-18:13 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 426.77 | 631.63 | 2616.29 | 1398.69 | 0.00 | 1371.03 | 2930.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 02-JUL-18:13 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 426.77 | 631.63 | 2616.29 | 1117.42 | 0.00 | 1371.03 | 3082.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 15-JUN-17:34 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 263.18 | 469.21 | 2697.56 | 5259.39 | 0.00 | 1479.41 | 1724.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 02-JUL-18:34 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 426.78 | 631.63 | 2616.29 | 817.16 | 0.00 | 1243.78 | 2508.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 02-JUL-18:13 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 426.77 | 631.63 | 2616.29 | 455.94 | 0.00 | 1312.14 | 2661.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 15-JUN-17:34 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 263.18 | 469.21 | 2697.56 | 5746.57 | 0.00 | 1479.41 | 1449.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-JUN-18:15 | 0.00 | 0.00 | 0.00 | -13.3 | 0.00 | 0.00 | 7681.95 | 11369.32 | 46630.56 | 37411.77 | 0.00 | 64149.33 | 11316.11 | 0.00 | 0.00 | 0.00 | -19407.2 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 27-DEC-07:10 | 0.00 | 0.00 | 5513.24 | 0.00 | 0.00 | 0.00 | 464.72 | 300.78 | 1634.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1825.0 | 0.00 | -3270.0 | -2818.4 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 27-DEC-07:10 | 0.00 | 0.00 | 4078.73 | 0.00 | 0.00 | 0.00 | 464.72 | 300.78 | 1634.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -740.6 | 0.00 | -3144.4 | -2593.9 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27-DEC-07:10 | 0.00 | 0.00 | 5528.04 | 0.00 | 0.00 | 0.00 | 464.72 | 300.78 | 1634.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1821.7 | 0.00 | -3270.0 | -2836.5 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 03-FEB-06:00 | 0.00 | 0.00 | 5535.64 | 0.00 | 0.00 | 0.00 | 526.24 | 336.87 | 1398.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1932.9 | 0.00 | -3414.3 | -2449.9 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 27-DEC-08:09 | 0.00 | 0.00 | 4196.56 | 0.00 | 0.00 | 0.00 | 215.03 | 132.34 | 1555.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -549.6 | 0.00 | -3019.3 | -2530.9 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 03-FEB-06:00 | 0.00 | 0.00 | 5624.12 | 0.00 | 0.00 | 0.00 | 526.24 | 336.87 | 1398.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1924.6 | 0.00 | -3414.3 | -2546.7 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 27-DEC-07:10 | 0.00 | 0.00 | 4113.97 | 0.00 | 0.00 | 0.00 | 464.72 | 300.78 | 1634.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1858.8 | 0.00 | -2680.9 | -1974.4 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 27-DEC-07:10 | 0.00 | 0.00 | 2698.48 | 0.00 | 0.00 | 0.00 | 464.72 | 300.78 | 1634.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -755.2 | 0.00 | -2555.1 | -1788.2 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 27-DEC-07:10 | 0.00 | 0.00 | 4139.82 | 0.00 | 0.00 | 0.00 | 464.72 | 300.78 | 1634.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1858.0 | 0.00 | -2680.9 | -2001.0 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 27-DEC-08:15 | 0.00 | 0.00 | 4179.24 | 0.00 | 0.00 | 0.00 | 215.03 | 132.34 | 1555.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1388.3 | 0.00 | -2579.2 | -2114.9 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 27-DEC-08:09 | 0.00 | 0.00 | 2862.07 | 0.00 | 0.00 | 0.00 | 215.03 | 132.34 | 1555.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -566.3 | 0.00 | -2459.8 | -1739.2 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 03-FEB-06:04 | 0.00 | 0.00 | 4134.94 | 0.00 | 0.00 | 0.00 | 526.24 | 336.87 | 1398.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1959.9 | 0.00 | -2804.2 | -1632.4 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 03-FEB-06:00 | 0.00 | 0.00 | 5748.96 | 0.00 | 0.00 | 0.00 | 526.24 | 336.87 | 1398.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1945.6 | 0.00 | -3419.5 | -2645.3 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 27-DEC-07:10 | 0.00 | 0.00 | 5690.75 | 0.00 | 0.00 | 0.00 | 464.72 | 300.78 | 1634.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1845.2 | 0.00 | -3275.1 | -2970.6 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 27-DEC-07:10 | 0.00 | 0.00 | 5661.04 | 0.00 | 0.00 | 0.00 | 464.72 | 300.78 | 1634.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1844.4 | 0.00 | -3275.1 | -2941.6 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 27-DEC-08:09 | 0.00 | 0.00 | 4353.36 | 0.00 | 0.00 | 0.00 | 215.03 | 132.34 | 1555.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -560.5 | 0.00 | -3024.1 | -2672.0 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 27-DEC-07:10 | 0.00 | 0.00 | 4247.33 | 0.00 | 0.00 | 0.00 | 464.72 | 300.78 | 1634.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -748.4 | 0.00 | -3149.3 | -2749.8 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 27-DEC-08:09 | 0.00 | 0.00 | 5701.75 | 0.00 | 0.00 | 0.00 | 215.03 | 132.34 | 1555.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1374.5 | 0.00 | -3143.7 | -3086.8 |
CRAWLSPACE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-DEC-07:10 | 0.00 | 0.00 | 83451.12 | 0.00 | 0.00 | 0.00 | 8365.04 | 5413.96 | 29422.49 | 0.00 | 0.00 | 6942.95 | 8831.20 | 0.00 | -26585.1 | 0.00 | -115841.7 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 491.9757 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 491.9757 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 327.4257 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 327.4257 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 379.4975 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 379.4975 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 486.8869 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 486.8869 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 326.2668 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 326.2668 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 377.0950 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 377.0950 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 472.5157 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 472.5157 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 313.7674 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 313.7674 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 367.0379 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 367.0379 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 468.1822 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 468.1822 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 312.1180 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 312.1180 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 364.6790 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 364.6790 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 536.1409 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 536.1409 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 377.8436 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 377.8436 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 430.4831 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 430.4831 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 539.5436 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 539.5436 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 381.8624 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 381.8624 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 434.8423 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 434.8423 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 491.9757 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 491.9757 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 327.4257 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 327.4257 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 379.4975 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 379.4975 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 486.8869 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 486.8869 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 326.2668 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 326.2668 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 377.0950 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 377.0950 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 472.5157 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 472.5157 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 313.7674 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 313.7674 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 367.0379 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 367.0379 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 468.1822 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 468.1822 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 312.1180 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 312.1180 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 364.6790 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 364.6790 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 536.1409 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 536.1409 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 377.8436 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 377.8436 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 430.4831 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 430.4831 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 539.5436 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 539.5436 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 381.8624 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 381.8624 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 434.8423 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 434.8423 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 491.9757 | 491.9757 | 491.9757 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 327.4257 | 327.4257 | 327.4257 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 379.4975 | 379.4975 | 379.4975 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 486.8869 | 486.8869 | 486.8869 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 326.2668 | 326.2668 | 326.2668 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 377.0950 | 377.0950 | 377.0950 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 472.5157 | 472.5157 | 472.5157 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 313.7674 | 313.7674 | 313.7674 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 367.0379 | 367.0379 | 367.0379 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 468.1822 | 468.1822 | 468.1822 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 312.1180 | 312.1180 | 312.1180 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 364.6790 | 364.6790 | 364.6790 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 434.8423 | 434.8423 | 434.8423 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 430.4831 | 430.4831 | 430.4831 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 536.1409 | 536.1409 | 536.1409 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 381.8624 | 381.8624 | 381.8624 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 377.8436 | 377.8436 | 377.8436 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 539.5436 | 539.5436 | 539.5436 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 491.9757 | 491.9757 | 491.9757 | 491.9757 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 327.4257 | 327.4257 | 327.4257 | 327.4257 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 379.4975 | 379.4975 | 379.4975 | 379.4975 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 486.8869 | 486.8869 | 486.8869 | 486.8869 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 326.2668 | 326.2668 | 326.2668 | 326.2668 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 377.0950 | 377.0950 | 377.0950 | 377.0950 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 472.5157 | 472.5157 | 472.5157 | 472.5157 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 313.7674 | 313.7674 | 313.7674 | 313.7674 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 367.0379 | 367.0379 | 367.0379 | 367.0379 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 468.1822 | 468.1822 | 468.1822 | 468.1822 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 312.1180 | 312.1180 | 312.1180 | 312.1180 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 364.6790 | 364.6790 | 364.6790 | 364.6790 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 536.1409 | 536.1409 | 536.1409 | 536.1409 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 377.8436 | 377.8436 | 377.8436 | 377.8436 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 430.4831 | 430.4831 | 430.4831 | 430.4831 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 539.5436 | 539.5436 | 539.5436 | 539.5436 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 381.8624 | 381.8624 | 381.8624 | 381.8624 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 434.8423 | 434.8423 | 434.8423 | 434.8423 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 491.9757 | 491.9757 | 491.9757 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 327.4257 | 327.4257 | 327.4257 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 379.4975 | 379.4975 | 379.4975 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 486.8869 | 486.8869 | 486.8869 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 326.2668 | 326.2668 | 326.2668 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 377.0950 | 377.0950 | 377.0950 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 472.5157 | 472.5157 | 472.5157 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 313.7674 | 313.7674 | 313.7674 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 367.0379 | 367.0379 | 367.0379 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 468.1822 | 468.1822 | 468.1822 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 312.1180 | 312.1180 | 312.1180 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 364.6790 | 364.6790 | 364.6790 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 434.8423 | 434.8423 | 434.8423 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 430.4831 | 430.4831 | 430.4831 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 536.1409 | 536.1409 | 536.1409 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 381.8624 | 381.8624 | 381.8624 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 377.8436 | 377.8436 | 377.8436 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 539.5436 | 539.5436 | 539.5436 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 491.9757 | 491.9757 | 491.9757 | 491.9757 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 327.4257 | 327.4257 | 327.4257 | 327.4257 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 379.4975 | 379.4975 | 379.4975 | 379.4975 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 486.8869 | 486.8869 | 486.8869 | 486.8869 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 326.2668 | 326.2668 | 326.2668 | 326.2668 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 377.0950 | 377.0950 | 377.0950 | 377.0950 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 472.5157 | 472.5157 | 472.5157 | 472.5157 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 313.7674 | 313.7674 | 313.7674 | 313.7674 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 367.0379 | 367.0379 | 367.0379 | 367.0379 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 468.1822 | 468.1822 | 468.1822 | 468.1822 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 312.1180 | 312.1180 | 312.1180 | 312.1180 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 364.6790 | 364.6790 | 364.6790 | 364.6790 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 536.1409 | 536.1409 | 536.1409 | 536.1409 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 377.8436 | 377.8436 | 377.8436 | 377.8436 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 430.4831 | 430.4831 | 430.4831 | 430.4831 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 539.5436 | 539.5436 | 539.5436 | 539.5436 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 381.8624 | 381.8624 | 381.8624 | 381.8624 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 434.8423 | 434.8423 | 434.8423 | 434.8423 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [ft2] | 39005.22 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
CRAWLSPACE | 7794.39 | 0.00 | 7794.39 | 0.00 |
BREEZEWAY | 1798.16 | 0.00 | 1798.16 | 0.00 |
ATTIC | 7802.71 | 0.00 | 7802.71 | 0.00 |
Totals | 39005.22 | 21609.96 | 17395.26 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Gasoline Use [therm] | Gasoline Demand [Btu/h] | Diesel Use [kBtu] | Diesel Demand [Btu/h] | Coal Use [kBtu] | Coal Demand [Btu/h] | Fuel Oil No 1 Use [kBtu] | Fuel Oil No 1 Demand [Btu/h] | Fuel Oil No 2 Use [kBtu] | Fuel Oil No 2 Demand [Btu/h] | Propane Use [kBtu] | Propane Demand [Btu/h] | Other Fuel 1 Use [kBtu] | Other Fuel 1 Demand [Btu/h] | Other Fuel 2 Use [kBtu] | Other Fuel 2 Demand [Btu/h] | District Cooling Use [ton-hrs] | District Cooling Demand [ton] | District Heating Use [kBtu] | District Heating Demand [Btu/h] | |
Heating -- General | 0.00 | 0.00 | 337.25 | 92428.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 17408.78 | 10913.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- General | 11336.81 | 3692.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Exterior-Lights | 4094.83 | 934.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- dishwasher | 1717.21 | 547.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- refrigerator | 11154.55 | 1518.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- clotheswasher | 713.84 | 193.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- gas_dryer | 1138.84 | 291.20 | 792.69 | 20254.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- gas_range | 0.00 | 0.00 | 674.43 | 27685.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- gas_mels | 41935.01 | 7086.44 | 172.61 | 2914.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- IECC_adj | 17368.96 | 2935.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation | 2534.14 | 289.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 4453.67 | 2786.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 1753.55 | 162664.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 252763.87 | 388754.10 |
Natural Gas | 163973.19 | 373053.62 |
Additional | 0.00 | 0.00 |
Total | 416737.07 | 761807.72 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting (All) | 0.29 |
Space Heating | 0.00 |
Space Cooling | 0.45 |
Fans (All) | 0.18 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1.90 |
Miscellaneous (All) | 2.92 |
Subtotal | 2.92 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.25 |
Service Water Heating | 1.32 |
Miscellaneous (All) | 2.80 |
Subtotal | 2.80 |
Additional [kBtu/ft2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 5.08 |
Space Heating | 4.43 |
Space Cooling | 7.80 |
Fans (All) | 3.13 |
Service Water Heating | 23.02 |
Receptacle Equipment | 54.70 |
Miscellaneous | 1.84 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OCCUPANCY | 6031. | 8760. |
INTERIORLIGHTING | 2852. | 8760. |
INTERIORLIGHTINGHE | 3070. | 8760. |
INTERIORLIGHTINGHE_OS | 2910. | 8760. |
INTERIORLIGHTINGHE_VS | 2149. | 8760. |
EXTERIORLIGHTING | 4380. | 4380. |
REFRIGERATOR | 7343. | 8760. |
MISCPLUGLOAD | 5918. | 8760. |
COOKINGRANGE | 2434. | 8760. |
DISHWASHER_FLOW_SCH | 1608. | 8760. |
CLOTHESWASHER_FLOW_SCH | 1894. | 8760. |
DISHWASHER_EQUIP_SCH | 3134. | 8760. |
CLOTHESWASHER_EQUIP_SCH | 3692. | 8760. |
CLOTHESDRYER | 3911. | 8760. |
SHADING_2012IECC | 0. | 0. |
SHADING_2012IECC_HERS | 7007. | 8760. |
SINKSENSSCHEDULE | 6025. | 8760. |
SINKLATSCHEDULE | 2735. | 8760. |
SHOWERSENSSCHEDULE | 4492. | 8760. |
SHOWERLATSCHEDULE | 4268. | 8760. |
BATHSENSSCHEDULE | 8760. | 8760. |
BATHLATSCHEDULE | 0. | 0. |
First Object Used | Month Assumed | 11am First Wednesday [F] | Days with Same 11am Value | 11pm First Wednesday [F] | Days with Same 11pm Value | |
HEATING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | January | 72.00 | 365 | 72.00 | 365 |
COOLING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | July | 75.00 | 365 | 75.00 | 365 |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 18:23:07
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 186.833 | 0.552 | 325.944 | 61.039 | 66.734 |
February | 236.403 | 0.829 | 214.667 | 40.666 | 45.202 |
March | 324.097 | 1.312 | 163.833 | 31.716 | 37.986 |
April | 540.264 | 2.963 | 29.750 | 8.484 | 10.495 |
May | 707.567 | 4.907 | 0.000 | 4.907 | 4.907 |
June | 720.000 | 7.475 | 0.000 | 7.475 | 7.475 |
July | 744.000 | 8.535 | 0.000 | 8.535 | 8.535 |
August | 744.000 | 7.241 | 0.000 | 7.241 | 7.241 |
September | 689.667 | 5.847 | 0.000 | 5.847 | 5.856 |
October | 533.808 | 3.371 | 8.500 | 4.949 | 6.672 |
November | 286.183 | 1.247 | 206.458 | 39.560 | 44.363 |
December | 171.722 | 0.429 | 345.333 | 64.514 | 69.057 |
Annual Sum or Average | 5884.544 | 44.708 | 1294.486 | 284.933 | 314.525 |
Minimum of Months | 171.722 | 0.429 | 0.000 | 4.907 | 4.907 |
Maximum of Months | 744.000 | 8.535 | 345.333 | 64.514 | 69.057 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 213.806 | 0.419 | 265.361 | 33.192 | 36.791 |
February | 257.703 | 0.660 | 156.306 | 19.964 | 23.136 |
March | 341.625 | 0.927 | 118.889 | 15.610 | 18.004 |
April | 577.412 | 2.226 | 17.500 | 4.387 | 5.175 |
May | 729.417 | 3.649 | 0.000 | 3.649 | 3.649 |
June | 720.000 | 5.708 | 0.000 | 5.708 | 5.708 |
July | 744.000 | 7.152 | 0.000 | 7.152 | 7.152 |
August | 744.000 | 5.860 | 0.000 | 5.860 | 5.860 |
September | 703.306 | 4.728 | 0.000 | 4.728 | 4.728 |
October | 600.800 | 2.805 | 0.333 | 2.846 | 3.180 |
November | 327.514 | 1.019 | 162.431 | 21.080 | 23.527 |
December | 192.444 | 0.330 | 297.444 | 37.067 | 39.054 |
Annual Sum or Average | 6152.026 | 35.484 | 1018.264 | 161.246 | 175.966 |
Minimum of Months | 192.444 | 0.330 | 0.000 | 2.846 | 3.180 |
Maximum of Months | 744.000 | 7.152 | 297.444 | 37.067 | 39.054 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 196.833 | 0.387 | 309.361 | 44.671 | 47.929 |
February | 257.750 | 0.739 | 188.583 | 27.735 | 30.385 |
March | 361.179 | 1.164 | 142.750 | 21.599 | 24.387 |
April | 580.754 | 2.875 | 22.167 | 6.048 | 6.730 |
May | 718.722 | 4.671 | 0.000 | 4.671 | 4.671 |
June | 720.000 | 7.603 | 0.000 | 7.603 | 7.603 |
July | 744.000 | 9.505 | 0.000 | 9.505 | 9.505 |
August | 744.000 | 7.589 | 0.000 | 7.589 | 7.589 |
September | 694.944 | 6.009 | 0.000 | 6.009 | 6.035 |
October | 558.919 | 3.214 | 11.500 | 4.860 | 5.910 |
November | 311.642 | 1.106 | 199.250 | 29.628 | 32.464 |
December | 167.486 | 0.296 | 330.792 | 47.648 | 49.975 |
Annual Sum or Average | 6056.230 | 45.158 | 1204.403 | 217.566 | 233.183 |
Minimum of Months | 167.486 | 0.296 | 0.000 | 4.671 | 4.671 |
Maximum of Months | 744.000 | 9.505 | 330.792 | 47.648 | 49.975 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 56.889 | 0.054 | 431.750 | 79.348 | 86.339 |
February | 132.167 | 0.314 | 272.278 | 50.319 | 55.661 |
March | 264.750 | 0.804 | 200.583 | 37.643 | 44.609 |
April | 525.455 | 2.558 | 32.500 | 8.527 | 10.702 |
May | 710.625 | 4.807 | 0.000 | 4.807 | 4.807 |
June | 720.000 | 7.663 | 0.000 | 7.663 | 7.663 |
July | 744.000 | 8.515 | 0.000 | 8.515 | 8.515 |
August | 744.000 | 6.682 | 0.000 | 6.682 | 6.682 |
September | 686.028 | 4.637 | 0.000 | 4.637 | 4.660 |
October | 489.353 | 2.319 | 11.500 | 4.431 | 6.403 |
November | 196.167 | 0.453 | 262.431 | 48.650 | 54.980 |
December | 27.806 | 0.014 | 459.583 | 84.419 | 90.928 |
Annual Sum or Average | 5297.238 | 38.821 | 1670.625 | 345.641 | 381.950 |
Minimum of Months | 27.806 | 0.014 | 0.000 | 4.431 | 4.660 |
Maximum of Months | 744.000 | 8.515 | 459.583 | 84.419 | 90.928 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 23.250 | 0.017 | 423.000 | 52.075 | 57.961 |
February | 126.194 | 0.185 | 251.472 | 31.134 | 35.373 |
March | 251.708 | 0.448 | 164.431 | 20.684 | 23.978 |
April | 559.611 | 1.855 | 20.000 | 4.316 | 5.202 |
May | 730.056 | 3.556 | 0.000 | 3.556 | 3.556 |
June | 720.000 | 5.813 | 0.000 | 5.813 | 5.813 |
July | 744.000 | 7.038 | 0.000 | 7.038 | 7.038 |
August | 744.000 | 5.224 | 0.000 | 5.224 | 5.224 |
September | 700.438 | 3.506 | 0.000 | 3.506 | 3.506 |
October | 554.253 | 1.727 | 1.667 | 1.932 | 2.460 |
November | 177.056 | 0.243 | 237.675 | 29.494 | 32.878 |
December | 9.583 | 0.004 | 472.083 | 58.103 | 62.933 |
Annual Sum or Average | 5340.150 | 29.615 | 1570.328 | 222.874 | 245.921 |
Minimum of Months | 9.583 | 0.004 | 0.000 | 1.932 | 2.460 |
Maximum of Months | 744.000 | 7.038 | 472.083 | 58.103 | 62.933 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 17.000 | 0.013 | 455.472 | 64.800 | 71.306 |
February | 138.736 | 0.233 | 263.250 | 37.678 | 42.021 |
March | 298.647 | 0.632 | 169.917 | 24.801 | 27.993 |
April | 573.948 | 2.497 | 23.000 | 5.769 | 6.441 |
May | 719.375 | 4.564 | 0.000 | 4.564 | 4.564 |
June | 720.000 | 7.723 | 0.000 | 7.723 | 7.723 |
July | 744.000 | 9.357 | 0.000 | 9.357 | 9.357 |
August | 744.000 | 6.691 | 0.000 | 6.691 | 6.691 |
September | 693.875 | 4.395 | 0.000 | 4.395 | 4.446 |
October | 537.658 | 2.111 | 12.833 | 3.936 | 5.134 |
November | 179.194 | 0.302 | 242.306 | 34.768 | 39.345 |
December | 6.000 | 0.002 | 504.417 | 71.751 | 76.571 |
Annual Sum or Average | 5372.435 | 38.518 | 1671.194 | 276.232 | 301.590 |
Minimum of Months | 6.000 | 0.002 | 0.000 | 3.936 | 4.446 |
Maximum of Months | 744.000 | 9.357 | 504.417 | 71.751 | 76.571 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 257.333 | 0.783 | 216.833 | 39.430 | 45.553 |
February | 299.325 | 1.078 | 119.458 | 22.369 | 27.297 |
March | 392.078 | 1.614 | 66.167 | 13.407 | 18.974 |
April | 607.876 | 3.366 | 8.750 | 4.926 | 5.771 |
May | 734.444 | 5.282 | 0.000 | 5.282 | 5.282 |
June | 720.000 | 7.653 | 0.000 | 7.653 | 7.653 |
July | 744.000 | 8.830 | 0.000 | 8.830 | 8.830 |
August | 744.000 | 7.651 | 0.000 | 7.651 | 7.651 |
September | 707.150 | 6.473 | 0.000 | 6.473 | 6.473 |
October | 629.178 | 3.894 | 0.000 | 3.894 | 3.983 |
November | 352.458 | 1.540 | 113.500 | 21.770 | 27.642 |
December | 237.278 | 0.639 | 254.583 | 46.015 | 51.052 |
Annual Sum or Average | 6425.120 | 48.803 | 779.292 | 187.700 | 216.161 |
Minimum of Months | 237.278 | 0.639 | 0.000 | 3.894 | 3.983 |
Maximum of Months | 744.000 | 8.830 | 254.583 | 46.015 | 51.052 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 307.958 | 0.721 | 112.306 | 14.013 | 17.955 |
February | 360.056 | 0.979 | 63.000 | 8.435 | 9.852 |
March | 458.967 | 1.303 | 30.667 | 4.933 | 5.857 |
April | 653.064 | 2.661 | 0.833 | 2.760 | 3.101 |
May | 741.611 | 4.042 | 0.000 | 4.042 | 4.042 |
June | 720.000 | 5.944 | 0.000 | 5.944 | 5.944 |
July | 744.000 | 7.649 | 0.000 | 7.649 | 7.649 |
August | 744.000 | 6.478 | 0.000 | 6.478 | 6.478 |
September | 716.528 | 5.587 | 0.000 | 5.587 | 5.587 |
October | 700.947 | 3.522 | 0.000 | 3.522 | 3.522 |
November | 412.067 | 1.398 | 48.125 | 7.094 | 9.203 |
December | 290.111 | 0.610 | 164.083 | 20.030 | 23.144 |
Annual Sum or Average | 6849.308 | 40.895 | 419.014 | 90.487 | 102.334 |
Minimum of Months | 290.111 | 0.610 | 0.000 | 2.760 | 3.101 |
Maximum of Months | 744.000 | 7.649 | 164.083 | 20.030 | 23.144 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 274.167 | 0.645 | 206.417 | 29.223 | 32.238 |
February | 335.273 | 1.037 | 104.333 | 15.481 | 17.920 |
March | 442.985 | 1.543 | 63.278 | 10.304 | 12.568 |
April | 639.092 | 3.310 | 6.333 | 4.186 | 4.584 |
May | 738.278 | 5.091 | 0.000 | 5.091 | 5.091 |
June | 720.000 | 8.080 | 0.000 | 8.080 | 8.080 |
July | 744.000 | 10.340 | 0.000 | 10.340 | 10.340 |
August | 744.000 | 8.504 | 0.000 | 8.504 | 8.504 |
September | 708.972 | 7.038 | 0.000 | 7.038 | 7.038 |
October | 641.797 | 3.842 | 0.000 | 3.842 | 3.951 |
November | 380.331 | 1.440 | 114.000 | 17.224 | 20.272 |
December | 251.431 | 0.522 | 240.167 | 33.773 | 36.244 |
Annual Sum or Average | 6620.325 | 51.393 | 734.528 | 153.087 | 166.831 |
Minimum of Months | 251.431 | 0.522 | 0.000 | 3.842 | 3.951 |
Maximum of Months | 744.000 | 10.340 | 240.167 | 33.773 | 36.244 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 121.667 | 0.128 | 308.667 | 54.639 | 62.643 |
February | 193.389 | 0.439 | 171.000 | 30.637 | 37.191 |
March | 331.236 | 1.052 | 88.903 | 16.752 | 23.687 |
April | 598.039 | 2.940 | 9.333 | 4.588 | 5.604 |
May | 734.622 | 5.190 | 0.000 | 5.190 | 5.190 |
June | 720.000 | 7.854 | 0.000 | 7.854 | 7.854 |
July | 744.000 | 8.823 | 0.000 | 8.823 | 8.823 |
August | 744.000 | 7.066 | 0.000 | 7.066 | 7.066 |
September | 704.405 | 5.126 | 0.000 | 5.126 | 5.126 |
October | 600.619 | 2.757 | 0.000 | 2.757 | 3.013 |
November | 262.583 | 0.648 | 168.500 | 30.405 | 37.264 |
December | 72.722 | 0.057 | 362.967 | 64.157 | 69.692 |
Annual Sum or Average | 5827.283 | 42.079 | 1109.369 | 237.994 | 273.151 |
Minimum of Months | 72.722 | 0.057 | 0.000 | 2.757 | 3.013 |
Maximum of Months | 744.000 | 8.823 | 362.967 | 64.157 | 69.692 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 72.375 | 0.060 | 238.194 | 28.103 | 33.550 |
February | 204.111 | 0.328 | 127.750 | 15.368 | 17.665 |
March | 370.194 | 0.723 | 47.167 | 6.276 | 8.185 |
April | 642.197 | 2.275 | 1.667 | 2.471 | 2.803 |
May | 742.000 | 3.961 | 0.000 | 3.961 | 3.961 |
June | 720.000 | 6.086 | 0.000 | 6.086 | 6.086 |
July | 744.000 | 7.544 | 0.000 | 7.544 | 7.544 |
August | 744.000 | 5.739 | 0.000 | 5.739 | 5.739 |
September | 715.861 | 4.035 | 0.000 | 4.035 | 4.035 |
October | 684.806 | 2.272 | 0.000 | 2.272 | 2.272 |
November | 273.292 | 0.453 | 102.778 | 12.553 | 15.942 |
December | 45.056 | 0.030 | 321.056 | 37.829 | 41.915 |
Annual Sum or Average | 5957.892 | 33.506 | 838.611 | 132.238 | 149.698 |
Minimum of Months | 45.056 | 0.030 | 0.000 | 2.272 | 2.272 |
Maximum of Months | 744.000 | 7.544 | 321.056 | 37.829 | 41.915 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 44.722 | 0.039 | 303.417 | 41.777 | 47.810 |
February | 203.111 | 0.376 | 148.639 | 20.823 | 24.824 |
March | 390.488 | 0.944 | 79.861 | 11.930 | 14.425 |
April | 634.011 | 2.922 | 6.500 | 3.816 | 4.250 |
May | 738.500 | 4.956 | 0.000 | 4.956 | 4.956 |
June | 720.000 | 8.153 | 0.000 | 8.153 | 8.153 |
July | 744.000 | 10.105 | 0.000 | 10.105 | 10.105 |
August | 744.000 | 7.353 | 0.000 | 7.353 | 7.353 |
September | 707.833 | 4.931 | 0.000 | 4.931 | 4.931 |
October | 629.756 | 2.594 | 0.667 | 2.686 | 2.831 |
November | 255.889 | 0.496 | 155.667 | 21.910 | 24.925 |
December | 25.000 | 0.015 | 380.750 | 52.391 | 57.709 |
Annual Sum or Average | 5837.310 | 42.886 | 1075.500 | 190.830 | 212.274 |
Minimum of Months | 25.000 | 0.015 | 0.000 | 2.686 | 2.831 |
Maximum of Months | 744.000 | 10.105 | 380.750 | 52.391 | 57.709 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 195.083 | 0.574 | 303.611 | 61.975 | 68.125 |
February | 248.056 | 0.901 | 190.417 | 39.410 | 44.941 |
March | 338.944 | 1.461 | 140.417 | 29.858 | 35.892 |
April | 561.751 | 3.391 | 22.667 | 7.975 | 9.713 |
May | 722.406 | 5.556 | 0.000 | 5.556 | 5.556 |
June | 720.000 | 8.605 | 0.000 | 8.605 | 8.605 |
July | 744.000 | 9.925 | 0.000 | 9.925 | 9.925 |
August | 744.000 | 8.333 | 0.000 | 8.333 | 8.333 |
September | 693.828 | 6.639 | 0.000 | 6.639 | 6.639 |
October | 563.081 | 3.742 | 2.583 | 4.264 | 5.830 |
November | 301.386 | 1.347 | 185.958 | 38.954 | 44.064 |
December | 177.750 | 0.438 | 326.917 | 66.552 | 72.012 |
Annual Sum or Average | 6010.285 | 50.913 | 1172.569 | 288.047 | 319.637 |
Minimum of Months | 177.750 | 0.438 | 0.000 | 4.264 | 5.556 |
Maximum of Months | 744.000 | 9.925 | 326.917 | 66.552 | 72.012 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 223.556 | 0.477 | 234.194 | 33.856 | 37.761 |
February | 272.361 | 0.773 | 127.611 | 18.960 | 22.477 |
March | 367.011 | 1.128 | 79.125 | 12.406 | 15.965 |
April | 604.649 | 2.700 | 10.167 | 4.149 | 4.710 |
May | 734.294 | 4.386 | 0.000 | 4.386 | 4.386 |
June | 720.000 | 6.971 | 0.000 | 6.971 | 6.971 |
July | 744.000 | 8.803 | 0.000 | 8.803 | 8.803 |
August | 744.000 | 7.158 | 0.000 | 7.158 | 7.158 |
September | 708.211 | 5.678 | 0.000 | 5.678 | 5.678 |
October | 629.756 | 3.274 | 0.000 | 3.274 | 3.316 |
November | 343.347 | 1.169 | 131.569 | 19.921 | 23.197 |
December | 202.611 | 0.370 | 273.722 | 39.382 | 42.171 |
Annual Sum or Average | 6293.796 | 42.886 | 856.389 | 164.942 | 182.591 |
Minimum of Months | 202.611 | 0.370 | 0.000 | 3.274 | 3.316 |
Maximum of Months | 744.000 | 8.803 | 273.722 | 39.382 | 42.171 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 201.306 | 0.417 | 283.922 | 46.520 | 50.761 |
February | 269.497 | 0.824 | 165.389 | 27.680 | 31.125 |
March | 378.039 | 1.333 | 114.883 | 19.988 | 22.930 |
April | 601.085 | 3.315 | 16.167 | 5.940 | 6.468 |
May | 729.819 | 5.372 | 0.000 | 5.372 | 5.372 |
June | 720.000 | 8.657 | 0.000 | 8.657 | 8.657 |
July | 744.000 | 10.761 | 0.000 | 10.761 | 10.761 |
August | 744.000 | 8.618 | 0.000 | 8.618 | 8.618 |
September | 699.472 | 6.688 | 0.000 | 6.688 | 6.688 |
October | 587.219 | 3.587 | 5.333 | 4.453 | 5.374 |
November | 321.694 | 1.216 | 173.833 | 29.443 | 33.225 |
December | 171.194 | 0.311 | 311.550 | 50.900 | 53.983 |
Annual Sum or Average | 6167.327 | 51.099 | 1071.078 | 225.021 | 243.963 |
Minimum of Months | 171.194 | 0.311 | 0.000 | 4.453 | 5.372 |
Maximum of Months | 744.000 | 10.761 | 311.550 | 50.900 | 53.983 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 96.639 | 0.117 | 383.833 | 78.234 | 86.126 |
February | 167.167 | 0.456 | 238.083 | 48.910 | 54.872 |
March | 298.250 | 1.100 | 163.488 | 34.373 | 41.552 |
April | 554.129 | 3.161 | 23.833 | 8.012 | 9.999 |
May | 724.528 | 5.537 | 0.000 | 5.537 | 5.537 |
June | 720.000 | 8.766 | 0.000 | 8.766 | 8.766 |
July | 744.000 | 9.981 | 0.000 | 9.981 | 9.981 |
August | 744.000 | 8.059 | 0.000 | 8.059 | 8.059 |
September | 691.539 | 5.886 | 0.000 | 5.886 | 5.886 |
October | 528.256 | 2.949 | 4.167 | 3.797 | 5.693 |
November | 230.208 | 0.669 | 233.000 | 48.089 | 54.481 |
December | 58.222 | 0.043 | 420.417 | 85.605 | 91.895 |
Annual Sum or Average | 5556.937 | 46.723 | 1466.821 | 345.248 | 382.845 |
Minimum of Months | 58.222 | 0.043 | 0.000 | 3.797 | 5.537 |
Maximum of Months | 744.000 | 9.981 | 420.417 | 85.605 | 91.895 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 54.694 | 0.050 | 351.667 | 50.704 | 56.388 |
February | 169.556 | 0.334 | 190.889 | 27.830 | 32.678 |
March | 308.511 | 0.760 | 107.500 | 16.244 | 20.854 |
April | 595.489 | 2.467 | 11.167 | 4.076 | 4.756 |
May | 734.675 | 4.334 | 0.000 | 4.334 | 4.334 |
June | 720.000 | 6.992 | 0.000 | 6.992 | 6.992 |
July | 744.000 | 8.682 | 0.000 | 8.682 | 8.682 |
August | 744.000 | 6.743 | 0.000 | 6.743 | 6.743 |
September | 706.548 | 4.824 | 0.000 | 4.824 | 4.824 |
October | 596.000 | 2.433 | 0.000 | 2.433 | 2.601 |
November | 227.361 | 0.457 | 190.167 | 27.848 | 32.117 |
December | 30.778 | 0.017 | 402.781 | 58.033 | 63.165 |
Annual Sum or Average | 5631.612 | 38.094 | 1254.169 | 218.745 | 244.136 |
Minimum of Months | 30.778 | 0.017 | 0.000 | 2.433 | 2.601 |
Maximum of Months | 744.000 | 8.682 | 402.781 | 58.033 | 63.165 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 36.528 | 0.036 | 394.500 | 64.743 | 71.626 |
February | 167.911 | 0.375 | 217.883 | 36.113 | 40.695 |
March | 336.597 | 0.946 | 128.917 | 22.091 | 26.055 |
April | 598.554 | 3.093 | 16.333 | 5.772 | 6.308 |
May | 730.014 | 5.320 | 0.000 | 5.320 | 5.320 |
June | 720.000 | 8.622 | 0.000 | 8.622 | 8.622 |
July | 744.000 | 10.523 | 0.000 | 10.523 | 10.523 |
August | 744.000 | 8.029 | 0.000 | 8.029 | 8.029 |
September | 699.167 | 5.669 | 0.000 | 5.669 | 5.669 |
October | 573.131 | 2.751 | 6.833 | 3.872 | 4.807 |
November | 223.167 | 0.506 | 213.556 | 35.534 | 39.695 |
December | 13.667 | 0.007 | 450.778 | 73.945 | 79.565 |
Annual Sum or Average | 5586.734 | 45.876 | 1428.800 | 280.233 | 306.915 |
Minimum of Months | 13.667 | 0.007 | 0.000 | 3.872 | 4.807 |
Maximum of Months | 744.000 | 10.523 | 450.778 | 73.945 | 79.565 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 629.07 | 0.00 | 0.00 |
February | 468.05 | 0.00 | 0.00 |
March | 244.06 | 0.00 | 0.00 |
April | 31.26 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 2.15 | 0.00 | 0.00 |
November | 340.21 | 0.00 | 0.00 |
December | 874.05 | 0.00 | 0.00 |
Annual Sum or Average | 215.01 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 874.05 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 354.86 | 0.00 | 0.00 |
February | 267.72 | 0.00 | 0.00 |
March | 125.36 | 0.00 | 0.00 |
April | 12.97 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.01 | 0.00 | 0.00 |
November | 183.30 | 0.00 | 0.00 |
December | 537.76 | 0.00 | 0.00 |
Annual Sum or Average | 123.13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 537.76 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 623.68 | 0.00 | 0.00 |
February | 432.80 | 0.00 | 0.00 |
March | 231.03 | 0.00 | 0.00 |
April | 26.43 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 4.19 | 0.00 | 0.00 |
November | 347.15 | 0.00 | 0.00 |
December | 863.72 | 0.00 | 0.00 |
Annual Sum or Average | 210.21 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 863.72 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 902.88 | 0.00 | 0.00 |
February | 653.98 | 0.00 | 0.00 |
March | 305.88 | 0.00 | 0.00 |
April | 33.59 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 3.46 | 0.00 | 0.00 |
November | 470.50 | 0.00 | 0.00 |
December | 1232.37 | 0.00 | 0.00 |
Annual Sum or Average | 299.22 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1232.37 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 621.10 | 0.00 | 0.00 |
February | 445.33 | 0.00 | 0.00 |
March | 182.79 | 0.00 | 0.00 |
April | 14.34 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.15 | 0.00 | 0.00 |
November | 291.24 | 0.00 | 0.00 |
December | 895.01 | 0.00 | 0.00 |
Annual Sum or Average | 203.58 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 895.01 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 884.80 | 0.00 | 0.00 |
February | 580.37 | 0.00 | 0.00 |
March | 280.04 | 0.00 | 0.00 |
April | 27.31 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 5.69 | 0.00 | 0.00 |
November | 441.57 | 0.00 | 0.00 |
December | 1223.15 | 0.00 | 0.00 |
Annual Sum or Average | 286.36 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1223.15 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 256.31 | 0.00 | 0.00 |
February | 192.71 | 0.00 | 0.00 |
March | 77.33 | 0.00 | 0.00 |
April | 4.73 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 119.90 | 0.00 | 0.00 |
December | 421.44 | 0.00 | 0.00 |
Annual Sum or Average | 89.16 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 421.44 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 79.06 | 0.00 | 0.00 |
February | 71.93 | 0.00 | 0.00 |
March | 27.02 | 0.00 | 0.00 |
April | 0.05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 36.76 | 0.00 | 0.00 |
December | 176.81 | 0.00 | 0.00 |
Annual Sum or Average | 32.57 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 176.81 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 262.63 | 0.00 | 0.00 |
February | 178.34 | 0.00 | 0.00 |
March | 77.96 | 0.00 | 0.00 |
April | 3.74 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 128.16 | 0.00 | 0.00 |
December | 425.48 | 0.00 | 0.00 |
Annual Sum or Average | 89.59 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 425.48 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 421.38 | 0.00 | 0.00 |
February | 300.92 | 0.00 | 0.00 |
March | 104.09 | 0.00 | 0.00 |
April | 5.24 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 186.21 | 0.00 | 0.00 |
December | 659.16 | 0.00 | 0.00 |
Annual Sum or Average | 139.43 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 659.16 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 202.10 | 0.00 | 0.00 |
February | 155.67 | 0.00 | 0.00 |
March | 45.76 | 0.00 | 0.00 |
April | 0.13 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 74.81 | 0.00 | 0.00 |
December | 365.90 | 0.00 | 0.00 |
Annual Sum or Average | 70.23 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 365.90 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 409.80 | 0.00 | 0.00 |
February | 257.88 | 0.00 | 0.00 |
March | 101.82 | 0.00 | 0.00 |
April | 3.96 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.04 | 0.00 | 0.00 |
November | 182.69 | 0.00 | 0.00 |
December | 642.85 | 0.00 | 0.00 |
Annual Sum or Average | 133.18 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 642.85 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 585.46 | 0.00 | 0.00 |
February | 422.25 | 0.00 | 0.00 |
March | 206.16 | 0.00 | 0.00 |
April | 21.57 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.92 | 0.00 | 0.00 |
November | 309.32 | 0.00 | 0.00 |
December | 841.44 | 0.00 | 0.00 |
Annual Sum or Average | 198.36 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 841.44 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 306.29 | 0.00 | 0.00 |
February | 223.08 | 0.00 | 0.00 |
March | 95.64 | 0.00 | 0.00 |
April | 6.74 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 152.05 | 0.00 | 0.00 |
December | 495.48 | 0.00 | 0.00 |
Annual Sum or Average | 106.38 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 495.48 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 569.47 | 0.00 | 0.00 |
February | 378.39 | 0.00 | 0.00 |
March | 189.88 | 0.00 | 0.00 |
April | 16.86 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 1.56 | 0.00 | 0.00 |
November | 307.73 | 0.00 | 0.00 |
December | 819.78 | 0.00 | 0.00 |
Annual Sum or Average | 189.96 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 819.78 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 814.11 | 0.00 | 0.00 |
February | 570.64 | 0.00 | 0.00 |
March | 248.21 | 0.00 | 0.00 |
April | 22.70 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 1.47 | 0.00 | 0.00 |
November | 417.39 | 0.00 | 0.00 |
December | 1149.40 | 0.00 | 0.00 |
Annual Sum or Average | 267.92 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1149.40 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 524.17 | 0.00 | 0.00 |
February | 361.79 | 0.00 | 0.00 |
March | 131.47 | 0.00 | 0.00 |
April | 7.40 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 240.95 | 0.00 | 0.00 |
December | 795.70 | 0.00 | 0.00 |
Annual Sum or Average | 171.43 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 795.70 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 784.83 | 0.00 | 0.00 |
February | 496.02 | 0.00 | 0.00 |
March | 220.36 | 0.00 | 0.00 |
April | 17.05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 2.22 | 0.00 | 0.00 |
November | 385.67 | 0.00 | 0.00 |
December | 1122.34 | 0.00 | 0.00 |
Annual Sum or Average | 252.03 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1122.34 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DUMMY-HEAT-COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.09 |
April | 0.00 | 0.00 | 0.21 |
May | 0.00 | 0.00 | 0.31 |
June | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.00 | 0.36 |
October | 0.00 | 0.00 | 0.22 |
November | 0.00 | 0.00 | 0.09 |
December | 0.00 | 0.00 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.00 | 0.03 |
Maximum of Months | 0.00 | 0.00 | 0.45 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.03 |
February | 0.00 | 0.00 | 0.05 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.24 |
June | 0.00 | 0.00 | 0.33 |
July | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.00 | 0.30 |
October | 0.00 | 0.00 | 0.19 |
November | 0.00 | 0.00 | 0.08 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.38 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.03 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.08 |
April | 0.00 | 0.00 | 0.21 |
May | 0.00 | 0.00 | 0.31 |
June | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.00 | 0.36 |
October | 0.00 | 0.00 | 0.21 |
November | 0.00 | 0.00 | 0.08 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.18 |
May | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.00 | 0.31 |
October | 0.00 | 0.00 | 0.16 |
November | 0.00 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.45 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.13 |
May | 0.00 | 0.00 | 0.24 |
June | 0.00 | 0.00 | 0.33 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.00 | 0.25 |
October | 0.00 | 0.00 | 0.12 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.18 |
May | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.00 | 0.31 |
October | 0.00 | 0.00 | 0.15 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.09 |
March | 0.00 | 0.00 | 0.12 |
April | 0.00 | 0.00 | 0.23 |
May | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.00 | 0.25 |
November | 0.00 | 0.00 | 0.11 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.47 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.08 |
March | 0.00 | 0.00 | 0.09 |
April | 0.00 | 0.00 | 0.19 |
May | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.00 | 0.33 |
October | 0.00 | 0.00 | 0.23 |
November | 0.00 | 0.00 | 0.11 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.08 |
March | 0.00 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.34 |
June | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.00 | 0.25 |
November | 0.00 | 0.00 | 0.11 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.48 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.21 |
May | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.00 | 0.34 |
October | 0.00 | 0.00 | 0.19 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.47 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.16 |
November | 0.00 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.21 |
May | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.00 | 0.34 |
October | 0.00 | 0.00 | 0.18 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.47 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.10 |
April | 0.00 | 0.00 | 0.23 |
May | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.00 | 0.40 |
October | 0.00 | 0.00 | 0.25 |
November | 0.00 | 0.00 | 0.10 |
December | 0.00 | 0.00 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.03 |
Maximum of Months | 0.00 | 0.00 | 0.51 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.03 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.08 |
April | 0.00 | 0.00 | 0.19 |
May | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.00 | 0.35 |
October | 0.00 | 0.00 | 0.22 |
November | 0.00 | 0.00 | 0.09 |
December | 0.00 | 0.00 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.03 |
Maximum of Months | 0.00 | 0.00 | 0.43 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.03 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.09 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.00 | 0.41 |
October | 0.00 | 0.00 | 0.24 |
November | 0.00 | 0.00 | 0.09 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.52 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.08 |
April | 0.00 | 0.00 | 0.22 |
May | 0.00 | 0.00 | 0.34 |
June | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.00 | 0.37 |
October | 0.00 | 0.00 | 0.20 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.51 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.18 |
May | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.17 |
November | 0.00 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.43 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.22 |
May | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.00 | 0.38 |
October | 0.00 | 0.00 | 0.19 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.52 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1014.14 | 755.05 |
February | 0.00 | 0.00 | 1009.63 | 678.95 |
March | 0.00 | 0.00 | 976.58 | 727.09 |
April | 0.00 | 0.00 | 915.74 | 659.80 |
May | 0.00 | 0.00 | 851.42 | 633.91 |
June | 0.00 | 0.00 | 800.52 | 576.78 |
July | 0.00 | 0.00 | 770.70 | 573.81 |
August | 0.00 | 0.00 | 770.62 | 573.75 |
September | 0.00 | 0.00 | 800.55 | 576.81 |
October | 0.00 | 0.00 | 855.41 | 636.87 |
November | 0.00 | 0.00 | 927.26 | 668.10 |
December | 0.00 | 0.00 | 986.73 | 734.65 |
Annual Sum or Average | 0.00 | 0.00 | 889.27 | 7795.57 |
Minimum of Months | 0.00 | 0.00 | 770.62 | 573.75 |
Maximum of Months | 0.00 | 0.00 | 1014.14 | 755.05 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1012.54 | 753.87 |
February | 0.00 | 0.00 | 1005.95 | 676.48 |
March | 0.00 | 0.00 | 975.03 | 725.94 |
April | 0.00 | 0.00 | 915.60 | 659.70 |
May | 0.00 | 0.00 | 851.45 | 633.93 |
June | 0.00 | 0.00 | 800.56 | 576.82 |
July | 0.00 | 0.00 | 770.60 | 573.73 |
August | 0.00 | 0.00 | 769.16 | 572.66 |
September | 0.00 | 0.00 | 800.56 | 576.81 |
October | 0.00 | 0.00 | 854.74 | 636.38 |
November | 0.00 | 0.00 | 924.38 | 666.03 |
December | 0.00 | 0.00 | 985.17 | 733.49 |
Annual Sum or Average | 0.00 | 0.00 | 888.16 | 7785.82 |
Minimum of Months | 0.00 | 0.00 | 769.16 | 572.66 |
Maximum of Months | 0.00 | 0.00 | 1012.54 | 753.87 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1012.39 | 753.75 |
February | 0.00 | 0.00 | 1007.81 | 677.73 |
March | 0.00 | 0.00 | 974.93 | 725.86 |
April | 0.00 | 0.00 | 915.55 | 659.67 |
May | 0.00 | 0.00 | 851.44 | 633.92 |
June | 0.00 | 0.00 | 800.51 | 576.78 |
July | 0.00 | 0.00 | 770.71 | 573.81 |
August | 0.00 | 0.00 | 769.02 | 572.56 |
September | 0.00 | 0.00 | 800.57 | 576.82 |
October | 0.00 | 0.00 | 856.41 | 637.62 |
November | 0.00 | 0.00 | 926.01 | 667.20 |
December | 0.00 | 0.00 | 986.79 | 734.70 |
Annual Sum or Average | 0.00 | 0.00 | 888.69 | 7790.41 |
Minimum of Months | 0.00 | 0.00 | 769.02 | 572.56 |
Maximum of Months | 0.00 | 0.00 | 1012.39 | 753.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1019.24 | 758.85 |
February | 0.00 | 0.00 | 1013.50 | 681.56 |
March | 0.00 | 0.00 | 980.21 | 729.79 |
April | 0.00 | 0.00 | 915.71 | 659.78 |
May | 0.00 | 0.00 | 853.01 | 635.09 |
June | 0.00 | 0.00 | 798.88 | 575.60 |
July | 0.00 | 0.00 | 770.69 | 573.80 |
August | 0.00 | 0.00 | 770.61 | 573.74 |
September | 0.00 | 0.00 | 800.58 | 576.83 |
October | 0.00 | 0.00 | 856.49 | 637.68 |
November | 0.00 | 0.00 | 931.20 | 670.94 |
December | 0.00 | 0.00 | 993.69 | 739.83 |
Annual Sum or Average | 0.00 | 0.00 | 891.32 | 7813.49 |
Minimum of Months | 0.00 | 0.00 | 770.61 | 573.74 |
Maximum of Months | 0.00 | 0.00 | 1019.24 | 758.85 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1020.87 | 760.07 |
February | 0.00 | 0.00 | 1013.39 | 681.48 |
March | 0.00 | 0.00 | 978.36 | 728.41 |
April | 0.00 | 0.00 | 915.67 | 659.75 |
May | 0.00 | 0.00 | 851.40 | 633.89 |
June | 0.00 | 0.00 | 800.53 | 576.79 |
July | 0.00 | 0.00 | 770.69 | 573.80 |
August | 0.00 | 0.00 | 769.04 | 572.57 |
September | 0.00 | 0.00 | 800.57 | 576.82 |
October | 0.00 | 0.00 | 854.82 | 636.44 |
November | 0.00 | 0.00 | 931.25 | 670.98 |
December | 0.00 | 0.00 | 995.21 | 740.96 |
Annual Sum or Average | 0.00 | 0.00 | 891.15 | 7811.97 |
Minimum of Months | 0.00 | 0.00 | 769.04 | 572.57 |
Maximum of Months | 0.00 | 0.00 | 1020.87 | 760.07 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1022.52 | 761.29 |
February | 0.00 | 0.00 | 1013.42 | 681.50 |
March | 0.00 | 0.00 | 976.65 | 727.14 |
April | 0.00 | 0.00 | 915.60 | 659.70 |
May | 0.00 | 0.00 | 851.45 | 633.93 |
June | 0.00 | 0.00 | 800.50 | 576.77 |
July | 0.00 | 0.00 | 770.69 | 573.80 |
August | 0.00 | 0.00 | 769.11 | 572.63 |
September | 0.00 | 0.00 | 800.60 | 576.84 |
October | 0.00 | 0.00 | 856.37 | 637.59 |
November | 0.00 | 0.00 | 931.33 | 671.03 |
December | 0.00 | 0.00 | 995.29 | 741.02 |
Annual Sum or Average | 0.00 | 0.00 | 891.29 | 7813.25 |
Minimum of Months | 0.00 | 0.00 | 769.11 | 572.63 |
Maximum of Months | 0.00 | 0.00 | 1022.52 | 761.29 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1010.86 | 752.62 |
February | 0.00 | 0.00 | 1005.92 | 676.46 |
March | 0.00 | 0.00 | 971.63 | 723.40 |
April | 0.00 | 0.00 | 915.55 | 659.66 |
May | 0.00 | 0.00 | 851.45 | 633.93 |
June | 0.00 | 0.00 | 798.89 | 575.61 |
July | 0.00 | 0.00 | 770.70 | 573.81 |
August | 0.00 | 0.00 | 770.64 | 573.76 |
September | 0.00 | 0.00 | 800.53 | 576.79 |
October | 0.00 | 0.00 | 853.13 | 635.18 |
November | 0.00 | 0.00 | 924.34 | 665.99 |
December | 0.00 | 0.00 | 983.50 | 732.24 |
Annual Sum or Average | 0.00 | 0.00 | 887.44 | 7779.45 |
Minimum of Months | 0.00 | 0.00 | 770.64 | 573.76 |
Maximum of Months | 0.00 | 0.00 | 1010.86 | 752.62 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1007.51 | 750.12 |
February | 0.00 | 0.00 | 1002.21 | 673.96 |
March | 0.00 | 0.00 | 968.35 | 720.96 |
April | 0.00 | 0.00 | 913.89 | 658.47 |
May | 0.00 | 0.00 | 851.44 | 633.92 |
June | 0.00 | 0.00 | 798.90 | 575.62 |
July | 0.00 | 0.00 | 770.69 | 573.80 |
August | 0.00 | 0.00 | 770.63 | 573.76 |
September | 0.00 | 0.00 | 800.54 | 576.79 |
October | 0.00 | 0.00 | 851.78 | 634.17 |
November | 0.00 | 0.00 | 922.25 | 664.49 |
December | 0.00 | 0.00 | 980.16 | 729.76 |
Annual Sum or Average | 0.00 | 0.00 | 885.88 | 7765.82 |
Minimum of Months | 0.00 | 0.00 | 770.63 | 573.76 |
Maximum of Months | 0.00 | 0.00 | 1007.51 | 750.12 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1009.04 | 751.26 |
February | 0.00 | 0.00 | 1003.98 | 675.16 |
March | 0.00 | 0.00 | 971.60 | 723.38 |
April | 0.00 | 0.00 | 912.21 | 657.26 |
May | 0.00 | 0.00 | 851.38 | 633.87 |
June | 0.00 | 0.00 | 800.53 | 576.79 |
July | 0.00 | 0.00 | 770.70 | 573.81 |
August | 0.00 | 0.00 | 770.57 | 573.71 |
September | 0.00 | 0.00 | 800.55 | 576.80 |
October | 0.00 | 0.00 | 853.11 | 635.16 |
November | 0.00 | 0.00 | 922.63 | 664.77 |
December | 0.00 | 0.00 | 983.35 | 732.13 |
Annual Sum or Average | 0.00 | 0.00 | 886.83 | 7774.10 |
Minimum of Months | 0.00 | 0.00 | 770.57 | 573.71 |
Maximum of Months | 0.00 | 0.00 | 1009.04 | 751.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1015.83 | 756.31 |
February | 0.00 | 0.00 | 1009.74 | 679.03 |
March | 0.00 | 0.00 | 975.07 | 725.97 |
April | 0.00 | 0.00 | 915.66 | 659.74 |
May | 0.00 | 0.00 | 851.38 | 633.87 |
June | 0.00 | 0.00 | 798.89 | 575.61 |
July | 0.00 | 0.00 | 770.67 | 573.79 |
August | 0.00 | 0.00 | 770.64 | 573.76 |
September | 0.00 | 0.00 | 800.55 | 576.81 |
October | 0.00 | 0.00 | 853.12 | 635.17 |
November | 0.00 | 0.00 | 927.76 | 668.46 |
December | 0.00 | 0.00 | 990.23 | 737.25 |
Annual Sum or Average | 0.00 | 0.00 | 889.30 | 7795.77 |
Minimum of Months | 0.00 | 0.00 | 770.64 | 573.76 |
Maximum of Months | 0.00 | 0.00 | 1015.83 | 756.31 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1015.83 | 756.31 |
February | 0.00 | 0.00 | 1007.84 | 677.75 |
March | 0.00 | 0.00 | 971.77 | 723.51 |
April | 0.00 | 0.00 | 913.91 | 658.48 |
May | 0.00 | 0.00 | 851.41 | 633.90 |
June | 0.00 | 0.00 | 800.52 | 576.78 |
July | 0.00 | 0.00 | 770.67 | 573.79 |
August | 0.00 | 0.00 | 769.05 | 572.58 |
September | 0.00 | 0.00 | 800.59 | 576.84 |
October | 0.00 | 0.00 | 853.05 | 635.12 |
November | 0.00 | 0.00 | 926.06 | 667.24 |
December | 0.00 | 0.00 | 990.18 | 737.22 |
Annual Sum or Average | 0.00 | 0.00 | 888.58 | 7789.51 |
Minimum of Months | 0.00 | 0.00 | 769.05 | 572.58 |
Maximum of Months | 0.00 | 0.00 | 1015.83 | 756.31 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1017.60 | 757.63 |
February | 0.00 | 0.00 | 1009.73 | 679.02 |
March | 0.00 | 0.00 | 971.74 | 723.49 |
April | 0.00 | 0.00 | 913.89 | 658.47 |
May | 0.00 | 0.00 | 851.42 | 633.91 |
June | 0.00 | 0.00 | 800.51 | 576.78 |
July | 0.00 | 0.00 | 770.66 | 573.77 |
August | 0.00 | 0.00 | 769.04 | 572.57 |
September | 0.00 | 0.00 | 800.58 | 576.83 |
October | 0.00 | 0.00 | 854.77 | 636.40 |
November | 0.00 | 0.00 | 926.07 | 667.25 |
December | 0.00 | 0.00 | 991.94 | 738.52 |
Annual Sum or Average | 0.00 | 0.00 | 889.17 | 7794.63 |
Minimum of Months | 0.00 | 0.00 | 769.04 | 572.57 |
Maximum of Months | 0.00 | 0.00 | 1017.60 | 757.63 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1012.41 | 753.77 |
February | 0.00 | 0.00 | 1009.66 | 678.97 |
March | 0.00 | 0.00 | 975.06 | 725.96 |
April | 0.00 | 0.00 | 917.06 | 660.75 |
May | 0.00 | 0.00 | 851.66 | 634.08 |
June | 0.00 | 0.00 | 798.90 | 575.61 |
July | 0.00 | 0.00 | 770.68 | 573.79 |
August | 0.00 | 0.00 | 770.63 | 573.75 |
September | 0.00 | 0.00 | 800.59 | 576.83 |
October | 0.00 | 0.00 | 854.84 | 636.45 |
November | 0.00 | 0.00 | 927.87 | 668.54 |
December | 0.00 | 0.00 | 985.11 | 733.44 |
Annual Sum or Average | 0.00 | 0.00 | 888.86 | 7791.95 |
Minimum of Months | 0.00 | 0.00 | 770.63 | 573.75 |
Maximum of Months | 0.00 | 0.00 | 1012.41 | 753.77 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1010.73 | 752.51 |
February | 0.00 | 0.00 | 1005.96 | 676.49 |
March | 0.00 | 0.00 | 973.24 | 724.60 |
April | 0.00 | 0.00 | 915.62 | 659.71 |
May | 0.00 | 0.00 | 851.46 | 633.93 |
June | 0.00 | 0.00 | 798.90 | 575.62 |
July | 0.00 | 0.00 | 770.70 | 573.81 |
August | 0.00 | 0.00 | 770.64 | 573.76 |
September | 0.00 | 0.00 | 800.53 | 576.79 |
October | 0.00 | 0.00 | 853.15 | 635.20 |
November | 0.00 | 0.00 | 924.38 | 666.02 |
December | 0.00 | 0.00 | 985.13 | 733.46 |
Annual Sum or Average | 0.00 | 0.00 | 887.72 | 7781.92 |
Minimum of Months | 0.00 | 0.00 | 770.64 | 573.76 |
Maximum of Months | 0.00 | 0.00 | 1010.73 | 752.51 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1012.54 | 753.86 |
February | 0.00 | 0.00 | 1007.71 | 677.66 |
March | 0.00 | 0.00 | 973.40 | 724.72 |
April | 0.00 | 0.00 | 913.90 | 658.47 |
May | 0.00 | 0.00 | 851.41 | 633.90 |
June | 0.00 | 0.00 | 800.51 | 576.77 |
July | 0.00 | 0.00 | 770.65 | 573.77 |
August | 0.00 | 0.00 | 769.04 | 572.57 |
September | 0.00 | 0.00 | 800.56 | 576.81 |
October | 0.00 | 0.00 | 856.37 | 637.59 |
November | 0.00 | 0.00 | 926.07 | 667.25 |
December | 0.00 | 0.00 | 985.12 | 733.45 |
Annual Sum or Average | 0.00 | 0.00 | 888.28 | 7786.83 |
Minimum of Months | 0.00 | 0.00 | 769.04 | 572.57 |
Maximum of Months | 0.00 | 0.00 | 1012.54 | 753.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1017.58 | 757.62 |
February | 0.00 | 0.00 | 1011.70 | 680.35 |
March | 0.00 | 0.00 | 978.29 | 728.36 |
April | 0.00 | 0.00 | 915.71 | 659.78 |
May | 0.00 | 0.00 | 851.45 | 633.93 |
June | 0.00 | 0.00 | 798.90 | 575.62 |
July | 0.00 | 0.00 | 770.70 | 573.81 |
August | 0.00 | 0.00 | 770.64 | 573.76 |
September | 0.00 | 0.00 | 800.56 | 576.81 |
October | 0.00 | 0.00 | 856.48 | 637.67 |
November | 0.00 | 0.00 | 929.59 | 669.78 |
December | 0.00 | 0.00 | 991.79 | 738.42 |
Annual Sum or Average | 0.00 | 0.00 | 890.45 | 7805.90 |
Minimum of Months | 0.00 | 0.00 | 770.64 | 573.76 |
Maximum of Months | 0.00 | 0.00 | 1017.58 | 757.62 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1017.94 | 757.88 |
February | 0.00 | 0.00 | 1011.04 | 679.90 |
March | 0.00 | 0.00 | 976.74 | 727.21 |
April | 0.00 | 0.00 | 913.92 | 658.49 |
May | 0.00 | 0.00 | 851.42 | 633.91 |
June | 0.00 | 0.00 | 800.51 | 576.77 |
July | 0.00 | 0.00 | 770.64 | 573.77 |
August | 0.00 | 0.00 | 769.05 | 572.58 |
September | 0.00 | 0.00 | 800.61 | 576.85 |
October | 0.00 | 0.00 | 854.78 | 636.41 |
November | 0.00 | 0.00 | 928.11 | 668.71 |
December | 0.00 | 0.00 | 993.44 | 739.64 |
Annual Sum or Average | 0.00 | 0.00 | 890.02 | 7802.11 |
Minimum of Months | 0.00 | 0.00 | 769.05 | 572.58 |
Maximum of Months | 0.00 | 0.00 | 1017.94 | 757.88 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1019.29 | 758.89 |
February | 0.00 | 0.00 | 1013.19 | 681.35 |
March | 0.00 | 0.00 | 974.98 | 725.90 |
April | 0.00 | 0.00 | 913.91 | 658.48 |
May | 0.00 | 0.00 | 851.40 | 633.89 |
June | 0.00 | 0.00 | 800.51 | 576.78 |
July | 0.00 | 0.00 | 770.67 | 573.78 |
August | 0.00 | 0.00 | 769.06 | 572.58 |
September | 0.00 | 0.00 | 800.59 | 576.84 |
October | 0.00 | 0.00 | 856.42 | 637.63 |
November | 0.00 | 0.00 | 929.60 | 669.79 |
December | 0.00 | 0.00 | 993.52 | 739.70 |
Annual Sum or Average | 0.00 | 0.00 | 890.42 | 7805.61 |
Minimum of Months | 0.00 | 0.00 | 769.06 | 572.58 |
Maximum of Months | 0.00 | 0.00 | 1019.29 | 758.89 |
Report: HEATING AND COOLING LOADS
For: CRAWLSPACE
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: BREEZEWAY
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 29.08 | 694.46 |
February | 43.50 | 466.36 |
March | 68.50 | 307.00 |
April | 146.18 | 48.27 |
May | 216.85 | 0.00 |
June | 276.43 | 0.00 |
July | 275.22 | 0.00 |
August | 256.98 | 0.00 |
September | 219.40 | 0.03 |
October | 146.79 | 12.89 |
November | 63.97 | 392.43 |
December | 22.75 | 885.22 |
Annual Sum or Average | 1765.67 | 2806.65 |
Minimum of Months | 22.75 | 0.00 |
Maximum of Months | 276.43 | 885.22 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 22.31 | 388.46 |
February | 35.20 | 256.82 |
March | 49.19 | 151.70 |
April | 113.29 | 19.42 |
May | 169.32 | 0.00 |
June | 218.38 | 0.00 |
July | 220.93 | 0.00 |
August | 208.86 | 0.00 |
September | 179.25 | 0.00 |
October | 122.89 | 1.29 |
November | 53.09 | 208.98 |
December | 17.83 | 532.67 |
Annual Sum or Average | 1410.52 | 1559.33 |
Minimum of Months | 17.83 | 0.00 |
Maximum of Months | 220.93 | 532.67 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 20.50 | 626.76 |
February | 39.27 | 392.34 |
March | 61.69 | 251.37 |
April | 146.61 | 32.23 |
May | 218.81 | 0.00 |
June | 280.17 | 0.00 |
July | 279.00 | 0.00 |
August | 259.87 | 0.00 |
September | 219.44 | 0.09 |
October | 140.59 | 12.33 |
November | 57.56 | 357.25 |
December | 15.86 | 812.78 |
Annual Sum or Average | 1739.37 | 2485.16 |
Minimum of Months | 15.86 | 0.00 |
Maximum of Months | 280.17 | 812.78 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 2.77 | 966.93 |
February | 16.21 | 628.83 |
March | 41.63 | 377.36 |
April | 126.92 | 52.04 |
May | 212.24 | 0.00 |
June | 277.71 | 0.00 |
July | 273.62 | 0.00 |
August | 244.23 | 0.00 |
September | 187.42 | 0.08 |
October | 102.56 | 16.54 |
November | 22.51 | 525.25 |
December | 0.75 | 1228.05 |
Annual Sum or Average | 1508.55 | 3795.08 |
Minimum of Months | 0.75 | 0.00 |
Maximum of Months | 277.71 | 1228.05 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.87 | 660.32 |
February | 9.77 | 419.65 |
March | 23.60 | 216.48 |
April | 93.90 | 21.77 |
May | 164.93 | 0.00 |
June | 219.94 | 0.00 |
July | 219.51 | 0.00 |
August | 195.91 | 0.00 |
September | 146.22 | 0.00 |
October | 76.35 | 2.62 |
November | 12.12 | 321.31 |
December | 0.22 | 881.27 |
Annual Sum or Average | 1163.34 | 2523.42 |
Minimum of Months | 0.22 | 0.00 |
Maximum of Months | 219.94 | 881.27 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.67 | 902.24 |
February | 12.12 | 533.00 |
March | 32.96 | 301.99 |
April | 126.41 | 33.16 |
May | 214.06 | 0.00 |
June | 281.18 | 0.00 |
July | 277.07 | 0.00 |
August | 246.82 | 0.00 |
September | 186.88 | 0.17 |
October | 94.25 | 14.57 |
November | 15.01 | 451.51 |
December | 0.09 | 1172.15 |
Annual Sum or Average | 1487.51 | 3408.80 |
Minimum of Months | 0.09 | 0.00 |
Maximum of Months | 281.18 | 1172.15 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 41.42 | 343.79 |
February | 56.92 | 219.18 |
March | 84.90 | 116.92 |
April | 165.43 | 11.63 |
May | 233.80 | 0.00 |
June | 285.09 | 0.00 |
July | 286.60 | 0.00 |
August | 271.37 | 0.00 |
September | 238.86 | 0.00 |
October | 169.35 | 0.31 |
November | 79.59 | 175.57 |
December | 34.21 | 485.98 |
Annual Sum or Average | 1947.54 | 1353.38 |
Minimum of Months | 34.21 | 0.00 |
Maximum of Months | 286.60 | 485.98 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 38.53 | 117.75 |
February | 52.43 | 78.70 |
March | 69.45 | 35.68 |
April | 135.56 | 1.54 |
May | 186.76 | 0.00 |
June | 226.34 | 0.00 |
July | 231.53 | 0.00 |
August | 222.74 | 0.00 |
September | 199.35 | 0.00 |
October | 150.06 | 0.00 |
November | 73.20 | 53.16 |
December | 33.09 | 208.64 |
Annual Sum or Average | 1619.03 | 495.46 |
Minimum of Months | 33.09 | 0.00 |
Maximum of Months | 231.53 | 208.64 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 34.41 | 303.49 |
February | 55.44 | 177.63 |
March | 82.36 | 95.72 |
April | 169.52 | 7.06 |
May | 237.10 | 0.00 |
June | 289.44 | 0.00 |
July | 290.78 | 0.00 |
August | 274.80 | 0.00 |
September | 239.78 | 0.00 |
October | 164.70 | 0.37 |
November | 75.55 | 156.70 |
December | 28.17 | 438.84 |
Annual Sum or Average | 1942.06 | 1179.80 |
Minimum of Months | 28.17 | 0.00 |
Maximum of Months | 290.78 | 438.84 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 6.60 | 527.26 |
February | 22.81 | 327.91 |
March | 54.80 | 154.85 |
April | 145.93 | 12.88 |
May | 229.50 | 0.00 |
June | 286.46 | 0.00 |
July | 285.19 | 0.00 |
August | 258.94 | 0.00 |
September | 207.13 | 0.00 |
October | 122.97 | 0.88 |
November | 32.42 | 259.24 |
December | 2.99 | 728.61 |
Annual Sum or Average | 1655.73 | 2011.63 |
Minimum of Months | 2.99 | 0.00 |
Maximum of Months | 286.46 | 728.61 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 3.11 | 264.85 |
February | 17.28 | 163.91 |
March | 38.21 | 59.56 |
April | 115.60 | 1.89 |
May | 182.66 | 0.00 |
June | 227.99 | 0.00 |
July | 230.29 | 0.00 |
August | 210.13 | 0.00 |
September | 166.62 | 0.00 |
October | 101.29 | 0.00 |
November | 22.76 | 106.81 |
December | 1.61 | 415.47 |
Annual Sum or Average | 1317.55 | 1012.50 |
Minimum of Months | 1.61 | 0.00 |
Maximum of Months | 230.29 | 415.47 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 2.03 | 468.27 |
February | 19.77 | 256.93 |
March | 49.82 | 121.88 |
April | 149.45 | 7.40 |
May | 232.62 | 0.00 |
June | 290.52 | 0.00 |
July | 289.02 | 0.00 |
August | 262.10 | 0.00 |
September | 207.70 | 0.00 |
October | 117.46 | 0.84 |
November | 24.99 | 215.08 |
December | 0.81 | 675.66 |
Annual Sum or Average | 1646.29 | 1746.05 |
Minimum of Months | 0.81 | 0.00 |
Maximum of Months | 290.52 | 675.66 |
Report: HEATING AND COOLING LOADS
For: ATTIC
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 1.82 | 828.82 |
February | 19.40 | 471.30 |
March | 49.03 | 249.86 |
April | 155.33 | 23.27 |
May | 246.39 | 0.00 |
June | 319.07 | 0.00 |
July | 318.27 | 0.00 |
August | 289.47 | 0.00 |
September | 230.43 | 0.00 |
October | 123.28 | 8.68 |
November | 25.16 | 411.76 |
December | 0.36 | 1107.31 |
Annual Sum or Average | 1778.02 | 3101.01 |
Minimum of Months | 0.36 | 0.00 |
Maximum of Months | 319.07 | 1107.31 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 21.79 | 595.96 |
February | 43.13 | 358.00 |
March | 69.60 | 215.19 |
April | 167.16 | 22.93 |
May | 248.27 | 0.00 |
June | 317.33 | 0.00 |
July | 318.05 | 0.00 |
August | 295.95 | 0.00 |
September | 249.55 | 0.00 |
October | 158.32 | 7.27 |
November | 62.37 | 331.08 |
December | 16.41 | 793.72 |
Annual Sum or Average | 1967.93 | 2324.16 |
Minimum of Months | 16.41 | 0.00 |
Maximum of Months | 318.05 | 793.72 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 30.01 | 666.64 |
February | 46.89 | 434.41 |
March | 75.77 | 271.12 |
April | 165.91 | 37.15 |
May | 245.94 | 0.00 |
June | 313.66 | 0.00 |
July | 314.50 | 0.00 |
August | 292.95 | 0.00 |
September | 249.41 | 0.00 |
October | 164.32 | 7.82 |
November | 68.61 | 368.79 |
December | 23.05 | 870.98 |
Annual Sum or Average | 1991.02 | 2656.92 |
Minimum of Months | 23.05 | 0.00 |
Maximum of Months | 314.50 | 870.98 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 2.53 | 582.67 |
February | 17.38 | 353.77 |
March | 39.55 | 166.54 |
April | 123.49 | 13.16 |
May | 197.82 | 0.00 |
June | 257.73 | 0.00 |
July | 260.66 | 0.00 |
August | 238.66 | 0.00 |
September | 190.77 | 0.00 |
October | 107.32 | 0.57 |
November | 22.76 | 281.76 |
December | 0.88 | 808.08 |
Annual Sum or Average | 1459.55 | 2206.55 |
Minimum of Months | 0.88 | 0.00 |
Maximum of Months | 260.66 | 808.08 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 24.97 | 355.41 |
February | 40.39 | 224.17 |
March | 58.75 | 121.91 |
April | 134.96 | 11.73 |
May | 199.53 | 0.00 |
June | 255.75 | 0.00 |
July | 260.17 | 0.00 |
August | 245.06 | 0.00 |
September | 210.11 | 0.00 |
October | 142.80 | 0.14 |
November | 59.76 | 184.82 |
December | 19.58 | 511.68 |
Annual Sum or Average | 1651.83 | 1409.86 |
Minimum of Months | 19.58 | 0.00 |
Maximum of Months | 260.17 | 511.68 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 18:23:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 5.94 | 899.88 |
February | 23.47 | 569.63 |
March | 56.69 | 323.01 |
April | 154.61 | 39.72 |
May | 244.13 | 0.00 |
June | 315.49 | 0.00 |
July | 314.88 | 0.00 |
August | 286.64 | 0.00 |
September | 230.53 | 0.00 |
October | 130.76 | 10.47 |
November | 33.26 | 484.55 |
December | 2.21 | 1169.48 |
Annual Sum or Average | 1798.63 | 3496.75 |