Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 17:19
Tabular Output Report in Format: HTML
Building: US+MF+CZ3C+elecres+slab+IECC_2024
Environment: ANNUAL ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2024-06-27 17:20:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 474007.73 | 15.19 | 21.93 |
Net Site Energy | 474007.73 | 15.19 | 21.93 |
Total Source Energy | 1501182.49 | 48.10 | 69.47 |
Net Source Energy | 1501182.49 | 48.10 | 69.47 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 31210.83 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 9600.87 |
Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 54864.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23182.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 13981.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 290862.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 16859.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35549.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312247.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 474007.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312247.30 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 54864.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 23182.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 13981.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 5863.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 38086.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 2437.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation | 8652.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8206.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312247.30 | |
Water Heater | 4468.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 31080.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Unassigned | 54864.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 23182.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 13981.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 290862.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 16859.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 35549.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312247.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 6.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 |
Other | 13.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 21.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 4.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 |
Other | 9.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 15.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 474007.733 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 474007.733 | 100.00 |
Total On-Site and Utility Electric Sources | 474007.733 | 100.00 |
Total Electricity End Uses | 474007.733 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 312247.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 312247.30 | 100.00 |
Total Water End Uses | 312247.30 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 213.67 |
Time Setpoint Not Met During Occupied Cooling | 1.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 519.83 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR |HEATING AND COOLING LOADS
| BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
GeneralValue | |
Program Version and Build | EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 17:19 |
RunPeriod | ANNUAL |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [ft] | 521.68 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16177.97 | 6115.58 | 1973.41 | 6115.58 | 1973.41 |
Above Ground Wall Area [ft2] | 16177.97 | 6115.58 | 1973.41 | 6115.58 | 1973.41 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.15 | 8.69 | 26.94 | 8.69 | 26.94 |
Above Ground Window-Wall Ratio [%] | 13.15 | 8.69 | 26.94 | 8.69 | 26.94 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
BREEZEWAY | 1798.16 | No | Yes | 30553.25 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.7843 |
ATTIC | 7802.71 | No | Yes | 52795.56 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.7843 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.7843 |
Total | 31210.83 | 267088.19 | 16177.97 | 0.00 | 2126.74 | 2126.74 | 0.4037 | 866.97 | 1.9278 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.5831 | 600.28 | 2.7843 | |||
Unconditioned Total | 9600.87 | 83348.81 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | Tags | |
BREEZEWAY | 1798.16 | No | Yes | 1.00 | BREEZEWAY | GENERAL | BREEZEWAY | 0.0000 | 0.00 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.7843 | |
ATTIC | 7802.71 | No | Yes | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5831 | 600.28 | 2.7843 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5831 | 600.28 | 2.7843 | |
Total | 31210.83 | 0.4037 | 866.97 | 1.9278 | |||||||
Conditioned Total | 21609.96 | 0.5831 | 600.28 | 2.7843 | |||||||
Unconditioned Total | 9600.87 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [ft2] | Conditioned Area [ft2] | Unconditioned Area [ft2] | Not Part of Total Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
GENERAL | 31210.83 | 21609.96 | 9600.87 | 0.00 | 0.4037 | 866.97 | 1.9278 |
Total | 31210.83 | 21609.96 | 9600.87 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 03-JAN-07:30 | - | - | - | - | - | - | - | - | - | - | - | 01-JAN-08:19 |
Heating | 99.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 166.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 99.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 5.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 0.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 4.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 3.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 3.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 19.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation | 0.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | |
Water Heater | 0.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Gasoline [kBtu] | Source Diesel [kBtu] | Source Coal [kBtu] | Source Fuel Oil No 1 [kBtu] | Source Fuel Oil No 2 [kBtu] | Source Propane [kBtu] | Source Other Fuel 1 [kBtu] | Source Other Fuel 2 [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 173755.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 73418.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 122590.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44279.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 921160.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 53393.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 112585.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1501182.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 8.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 42.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 69.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 5.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 29.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 48.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 280.12 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 140.14 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 192.00 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 260.74 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 127.99 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 177.61 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 326.70 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 176.80 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 231.38 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 305.29 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 162.24 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 213.25 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 241.54 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 257.52 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 367.50 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 214.85 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 217.38 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 362.21 |
Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | Sum of Air Terminal Maximum Flow Rates [ft3/min] | Adjusted Heating Design Air Flow Rate [ft3/min] | Adjusted Cooling Design Air Flow Rate [ft3/min] | Adjusted Main Design Air Flow Rate [ft3/min] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 280.12 | 280.12 | 280.12 | 280.12 | 280.12 | 280.12 | 1.00 | 1.00 | 280.12 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 140.14 | 140.14 | 140.14 | 140.14 | 140.14 | 140.14 | 1.00 | 1.00 | 140.14 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 192.00 | 192.00 | 192.00 | 192.00 | 192.00 | 192.00 | 1.00 | 1.00 | 192.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 260.74 | 260.74 | 260.74 | 260.74 | 260.74 | 260.74 | 1.00 | 1.00 | 260.74 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 127.99 | 127.99 | 127.99 | 127.99 | 127.99 | 127.99 | 1.00 | 1.00 | 127.99 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 177.61 | 177.61 | 177.61 | 177.61 | 177.61 | 177.61 | 1.00 | 1.00 | 177.61 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 326.70 | 326.70 | 326.70 | 326.70 | 326.70 | 326.70 | 1.00 | 1.00 | 326.70 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 176.80 | 176.80 | 176.80 | 176.80 | 176.80 | 176.80 | 1.00 | 1.00 | 176.80 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 231.38 | 231.38 | 231.38 | 231.38 | 231.38 | 231.38 | 1.00 | 1.00 | 231.38 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 305.29 | 305.29 | 305.29 | 305.29 | 305.29 | 305.29 | 1.00 | 1.00 | 305.29 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 162.24 | 162.24 | 162.24 | 162.24 | 162.24 | 162.24 | 1.00 | 1.00 | 162.24 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 213.25 | 213.25 | 213.25 | 213.25 | 213.25 | 213.25 | 1.00 | 1.00 | 213.25 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 367.50 | 367.50 | 367.50 | 367.50 | 367.50 | 367.50 | 1.00 | 1.00 | 367.50 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 217.38 | 217.38 | 217.38 | 217.38 | 217.38 | 217.38 | 1.00 | 1.00 | 217.38 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 257.52 | 257.52 | 257.52 | 257.52 | 257.52 | 257.52 | 1.00 | 1.00 | 257.52 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 362.21 | 362.21 | 362.21 | 362.21 | 362.21 | 362.21 | 1.00 | 1.00 | 362.21 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 214.85 | 214.85 | 214.85 | 214.85 | 214.85 | 214.85 | 1.00 | 1.00 | 214.85 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 241.54 | 241.54 | 241.54 | 241.54 | 241.54 | 241.54 | 1.00 | 1.00 | 241.54 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 280.12 | 0.846706 | 0.732215 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 140.14 | 0.450477 | 0.712093 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 192.00 | 0.580112 | 0.732328 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 260.74 | 0.791205 | 0.731161 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 127.99 | 0.410151 | 0.713887 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 177.61 | 0.530792 | 0.736306 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 326.70 | 0.967493 | 0.739810 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 176.80 | 0.545534 | 0.725705 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 231.38 | 0.692627 | 0.735856 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 305.29 | 0.910305 | 0.736922 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 162.24 | 0.505783 | 0.722005 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 213.25 | 0.633149 | 0.739099 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 367.50 | 1.08 | 0.742214 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 217.38 | 0.659050 | 0.731404 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 257.52 | 0.799243 | 0.724165 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 362.21 | 1.06 | 0.741854 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 214.85 | 0.652255 | 0.731040 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 241.54 | 0.736236 | 0.729961 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 280.12 | 280.12 | 280.12 | 5620.15 | 0.846706 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 140.14 | 140.14 | 140.14 | 4690.41 | 0.450477 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 192.00 | 192.00 | 192.00 | 5622.59 | 0.580112 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 260.74 | 260.74 | 260.74 | 5622.43 | 0.791205 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 127.99 | 127.99 | 127.99 | 4690.54 | 0.410151 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 177.61 | 177.61 | 177.61 | 5620.55 | 0.530792 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 326.70 | 326.70 | 326.70 | 5322.27 | 0.967493 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 176.80 | 176.80 | 176.80 | 4291.32 | 0.545534 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 231.38 | 231.38 | 231.38 | 5325.34 | 0.692627 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 305.29 | 305.29 | 305.29 | 5325.76 | 0.910305 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 162.24 | 162.24 | 162.24 | 4292.59 | 0.505783 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 213.25 | 213.25 | 213.25 | 5324.37 | 0.633149 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 367.50 | 367.50 | 367.50 | 6563.38 | 1.08 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 217.38 | 217.38 | 217.38 | 5511.28 | 0.659050 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 257.52 | 257.52 | 257.52 | 6566.13 | 0.799243 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 362.21 | 362.21 | 362.21 | 6565.68 | 1.06 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 214.85 | 214.85 | 214.85 | 5512.01 | 0.652255 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 241.54 | 241.54 | 241.54 | 6565.14 | 0.736236 | 1.00 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 280.12 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 140.14 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 192.00 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 260.74 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 127.99 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 177.61 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 326.70 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 176.80 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 231.38 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 305.29 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 162.24 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 213.25 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 367.50 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 217.38 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 257.52 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 362.21 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 214.85 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 241.54 |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | 160.01 |
Design Size Nominal Capacity [Btu/h] | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 6463.17 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 5393.97 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 6465.98 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 6465.80 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 5394.12 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 6463.63 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 6120.61 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 4935.02 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 6124.14 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 6124.62 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 4936.48 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 6123.03 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 7547.89 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 6337.98 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 7551.05 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 7550.53 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 6338.81 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 7549.91 |
Evaporator air flow rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 160.01 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 2.09 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
VersionVersion ID | |
1 | 23.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | No | Yes | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.200 | 0.200 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 55.60 | 55.08 | 55.99 | 57.42 | 61.12 | 63.99 | 65.91 | 66.51 | 65.50 | 63.28 | 60.31 | 57.54 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {ft} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Sensor Height Above Ground {ft} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 32.810 | 0.140 | 885.870 | 4.921 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {ft} | Standard Pressure at Elevation {psi} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 521.68 | 14. | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{F} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} | Fixed Default Water Mains Temperature{F} | |
1 | Correlation | NA | 60.80 | 12.78 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | US+MF+CZ3C+elecres+slab+IECC_2024 | 0.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Algorithm {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
Space Heat Balance Sizing |
Space Heat Balance Simulation |
|
1 | ThirdOrderBackwardDifference | No | No |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Gradient Coefficient {F/ft} | |
1 | 0.220 | 1213.970 | 0.003566 |
Material Name | ThermalResistance {m2-K/w} | Roughness | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | Absorptance:Thermal | Absorptance:Solar | Absorptance:Visible | |
1 | SHEATHING_CONSOL_LAYER | 0.1351 | Rough | 0.0417 | 9.402E-002 | 42.764 | 0.280 | 0.9000 | 0.7000 | 0.7000 |
2 | CEIL_CONSOL_LAYER | 6.1981 | Rough | 1.2550 | 6.172E-002 | 2.618 | 0.185 | 0.9000 | 0.7000 | 0.7000 |
3 | FLOOR_CONSOL_LAYER | 1.9554E-005 | Rough | 0.0008 | 12.990 | 3.438 | 0.219 | 0.9000 | 0.7000 | 0.7000 |
4 | BSMTWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
5 | CRAWLWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
6 | WALL_CONSOL_LAYER | 2.4438 | Rough | 0.4584 | 5.717E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
7 | VERY HIGH REFLECTIVITY SURFACE | 2.1097E-006 | Smooth | 0.0016 | 237.000 | 168.680 | 0.216 | 0.9000 | 5.0000E-002 | 5.0000E-002 |
8 | GYPSUMBOARD-5/16IN | 5.0054E-002 | Rough | 0.0260 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
9 | COPPERPIPE | 4.7506E-005 | MediumRough | 0.0625 | 401.000 | 140.026 | 0.200 | 0.9000 | 0.6500 | 0.6500 |
10 | F08 METAL SURFACE | 1.7668E-005 | Smooth | 0.0026 | 45.280 | 488.437 | 0.119 | 0.9000 | 0.7000 | 0.7000 |
11 | CONCRETE_4IN | 7.7356E-002 | Rough | 0.3330 | 1.312 | 140.014 | 0.111 | 0.9000 | 0.7000 | 0.7000 |
12 | ASPHALT_SHINGLE | 7.7448E-002 | MediumRough | 0.0208 | 8.186E-002 | 70.000 | 0.300 | 0.9000 | 0.7500 | 0.7000 |
13 | WOOD_SHINGLE | 0.1115 | MediumSmooth | 0.0417 | 0.114 | 26.600 | 0.390 | 0.9000 | 0.7000 | 0.7000 |
14 | SLATE_SHINGLE | 8.8061E-003 | MediumSmooth | 0.0417 | 1.442 | 100.000 | 0.300 | 0.9000 | 0.7000 | 0.7000 |
15 | CEMENT_STUCCO | 2.6422E-002 | MediumSmooth | 0.0625 | 0.721 | 116.464 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
16 | SYN_STUCCO | 3.5237E-002 | MediumSmooth | 0.0100 | 8.650E-002 | 24.971 | 0.210 | 0.7000 | 0.7000 | 0.7000 |
17 | DRYWALL_1/2IN | 7.9331E-002 | MediumSmooth | 0.0417 | 0.160 | 50.000 | 0.260 | 0.9000 | 0.7000 | 0.7000 |
18 | OSB_5/8IN | 0.1365 | MediumSmooth | 0.0521 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
19 | OSB_7/16IN | 9.5550E-002 | MediumSmooth | 0.0365 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
20 | BLOWN_R30 | 5.1614 | MediumRough | 0.6975 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
21 | BLOWN_R30_TOP | 2.8489 | MediumRough | 0.3849 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
22 | PLYWOOD_3/4IN | 0.1650 | Rough | 0.0625 | 0.115 | 34.003 | 0.161 | 0.9000 | 0.7000 | 0.7000 |
23 | BATT_R19 | 7.3089 | MediumRough | 0.0833 | 3.475E-003 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
24 | LUMBER_2X4 | 0.7709 | Rough | 0.2920 | 0.115 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
25 | CARPET_N_PAD | 0.4224 | MediumSmooth | 0.0833 | 6.013E-002 | 2.000 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
26 | BATT_R13 | 2.2936 | MediumRough | 0.2917 | 3.876E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
27 | OSB_1/2IN | 0.1092 | MediumSmooth | 0.0417 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
28 | SOIL_12IN | 0.1761 | Rough | 1.0000 | 1.731 | 115.011 | 0.056 | 0.9000 | 0.7000 | 0.7000 |
29 | DOOR_CONST | 0.5870 | Smooth | 0.1387 | 7.201E-002 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
30 | GYP_BOARD_1/2IN | 8.0130E-002 | Rough | 0.0417 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
31 | STD WOOD 6INCH | 1.2500 | MediumSmooth | 0.4921 | 0.120 | 33.711 | 0.289 | 0.9000 | 0.7000 | 0.7000 |
32 | PIPE INSULATION | 1.2255 | VeryRough | 0.1334 | 3.317E-002 | 5.681 | 0.200 | 0.9000 | 0.5000 | 0.5000 |
33 | MANF_WALL_AIRGAP | 0.1200 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
34 | BLDG_PAPER_FELT | 1.0567E-002 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
35 | R_HIGH | 177.0000 | MediumRough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
36 | CLEAR ACRYLIC PLASTIC | 3.3333E-003 | VerySmooth | 0.0098 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
37 | DIFFUSING ACRYLIC PLASTIC | 2.4444E-003 | VerySmooth | 0.0072 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
38 | INT_BLIND | 0.0000 | Rough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.0000 | 0.0000 | 0.0000 |
39 | GLASS | 0.4127 | VerySmooth | 0.1373 | 0.101 | 0.000 | 0.000 | 0.8400 | 0.0000 | 0.0000 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Name | Combined convective/radiative film coefficient {Btu/h-ft2-F} | User selected Constant Temperature {F} | Coefficient modifying the constant temperature term | Coefficient modifying the external dry bulb temperature term | Coefficient modifying the ground temperature term | Coefficient modifying the wind speed term {s/m} | Coefficient modifying the zone air temperature term | Constant Temperature Schedule Name | Sinusoidal Variation | Period of Sinusoidal Variation | Previous Other Side Temperature Coefficient | Minimum Other Side Temperature {F} | Maximum Other Side Temperature {F} | |
1 | SURFPROPOTHSDCOEFSLABAVERAGE | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABAVERAGESURFACETEMP | NO | 24.000 | 0.000 | N/A | N/A |
2 | SURFPROPOTHSDCOEFSLABPERIMETER | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABPERIMETERTEMP | NO | 24.000 | 0.000 | N/A | N/A |
3 | SURFPROPOTHSDCOEFSLABCORE | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABCORETEMP | NO | 24.000 | 0.000 | N/A | N/A |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{F} |
Surface Convection Coefficient Lower Limit {Btu/h-ft2-F} |
Surface Convection Coefficient Upper Limit {Btu/h-ft2-F} |
|
1 | CTF - ConductionTransferFunction | 392. | 0.02 | 176.1 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 60 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 20 | 171 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {ft} | Origin Y-Coordinate {ft} | Origin Z-Coordinate {ft} | Centroid X-Coordinate {ft} | Centroid Y-Coordinate {ft} | Centroid Z-Coordinate {ft} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {ft} | Maximum X {ft} | Minimum Y {ft} | Maximum Y {ft} | Minimum Z {ft} | Maximum Z {ft} | Ceiling Height {ft} | Volume {ft3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {ft2} | Exterior Gross Wall Area {ft2} | Exterior Net Wall Area {ft2} | Exterior Window Area {ft2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BREEZEWAY | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.55 | 13.26 | 1 | 1 | 1 | 0.00 | 119.89 | 30.05 | 35.04 | 0.49 | 25.99 | 17.00 | 30553.07 | TARP | DOE-2 | 1798.18 | 0.00 | 0.00 | 0.00 | 4 | 0 | 0 | Yes |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
4 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
5 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
6 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
7 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
8 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
9 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
10 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
11 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
12 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
13 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
14 | ATTIC | 0.0 | -134.9 | 51.61 | 0.00 | 59.94 | 32.55 | 29.56 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | 25.99 | 39.54 | 6.76 | 52795.39 | TARP | DOE-2 | 7802.66 | 881.33 | 881.33 | 0.00 | 11 | 0 | 0 | Yes |
15 | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
16 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
17 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
18 | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
19 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
20 | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
Zone Name | Floor Area {ft2} | # Occupants | Area per Occupant {ft2/person} | Occupant per Area {person/ft2} | Interior Lighting {Btu/h-ft2} | Electric Load {Btu/h-ft2} | Gas Load {Btu/h-ft2} | Other Load {Btu/h-ft2} | Hot Water Eq {Btu/h-ft2} | Steam Equipment {Btu/h-ft2} | Sum Loads per Area {Btu/h-ft2} | Outdoor Controlled Baseboard Heat | |
1 | BREEZEWAY | 1798.18 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
4 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
5 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
6 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
7 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
8 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
9 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
10 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
11 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
12 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
13 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
14 | ATTIC | 7802.66 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
15 | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
16 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
17 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
18 | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
19 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
20 | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.784 | 0.000 | 0.000 | 0.000 | 0.000 | 3.367 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Number of People {} | People/Floor Area {person/ft2} | Floor Area per person {ft2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
2 | PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
3 | PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
4 | PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
5 | PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
6 | PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
7 | PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
8 | PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
9 | PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
10 | PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
11 | PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
12 | PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
13 | PEOPLE_UNIT1_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
14 | PEOPLE_UNIT2_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
15 | PEOPLE_UNIT3_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
16 | PEOPLE_UNIT1_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
17 | PEOPLE_UNIT2_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
18 | PEOPLE_UNIT3_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Lighting Level {Btu/h} | Lights/Floor Area {Btu/h-ft2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {Btu/h} | Nominal Maximum Lighting Level {Btu/h} | |
1 | LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
2 | LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
3 | LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
4 | LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
5 | LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
6 | LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
7 | LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
8 | LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
9 | LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
10 | LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
11 | LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
12 | LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
13 | LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
14 | LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
15 | LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
16 | LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
17 | LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
18 | LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
19 | LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
20 | LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
21 | LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
22 | LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
23 | LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
24 | LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
25 | LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
26 | LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
27 | LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
28 | LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
29 | LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
30 | LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
31 | LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
32 | LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
33 | LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
34 | LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
35 | LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
36 | LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
1 | DISHWASHER1_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
2 | REFRIGERATOR1_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
3 | CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
4 | ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
5 | ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
6 | TELEVISION1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
7 | ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
8 | IECC_ADJ1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
9 | DISHWASHER2_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
10 | REFRIGERATOR2_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
11 | CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
12 | ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
13 | ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
14 | TELEVISION2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
15 | ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
16 | IECC_ADJ2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
17 | DISHWASHER3_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
18 | REFRIGERATOR3_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
19 | CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
20 | ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
21 | ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
22 | TELEVISION3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
23 | ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
24 | IECC_ADJ3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
25 | DISHWASHER1_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
26 | REFRIGERATOR1_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
27 | CLOTHESWASHER1_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
28 | ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
29 | ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
30 | TELEVISION1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
31 | ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
32 | IECC_ADJ1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
33 | DISHWASHER2_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
34 | REFRIGERATOR2_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
35 | CLOTHESWASHER2_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
36 | ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
37 | ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
38 | TELEVISION2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
39 | ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
40 | IECC_ADJ2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
41 | DISHWASHER3_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
42 | REFRIGERATOR3_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
43 | CLOTHESWASHER3_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
44 | ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
45 | ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
46 | TELEVISION3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
47 | ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
48 | IECC_ADJ3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
49 | DISHWASHER1_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
50 | REFRIGERATOR1_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
51 | CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
52 | ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
53 | ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
54 | TELEVISION1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
55 | ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
56 | IECC_ADJ1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
57 | DISHWASHER2_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
58 | REFRIGERATOR2_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
59 | CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
60 | ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
61 | ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
62 | TELEVISION2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
63 | ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
64 | IECC_ADJ2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
65 | DISHWASHER3_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
66 | REFRIGERATOR3_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
67 | CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
68 | ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
69 | ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
70 | TELEVISION3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
71 | ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
72 | IECC_ADJ3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
73 | DISHWASHER1_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
74 | REFRIGERATOR1_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
75 | CLOTHESWASHER1_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
76 | ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
77 | ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
78 | TELEVISION1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
79 | ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
80 | IECC_ADJ1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
81 | DISHWASHER2_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
82 | REFRIGERATOR2_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
83 | CLOTHESWASHER2_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
84 | ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
85 | ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
86 | TELEVISION2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
87 | ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
88 | IECC_ADJ2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
89 | DISHWASHER3_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
90 | REFRIGERATOR3_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
91 | CLOTHESWASHER3_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
92 | ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
93 | ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
94 | TELEVISION3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
95 | ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
96 | IECC_ADJ3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
97 | DISHWASHER1_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
98 | REFRIGERATOR1_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
99 | CLOTHESWASHER1_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
100 | ELECTRIC_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
101 | ELECTRIC_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
102 | TELEVISION1_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
103 | ELECTRIC_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
104 | IECC_ADJ1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
105 | DISHWASHER2_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
106 | REFRIGERATOR2_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
107 | CLOTHESWASHER2_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
108 | ELECTRIC_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
109 | ELECTRIC_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
110 | TELEVISION2_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
111 | ELECTRIC_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
112 | IECC_ADJ2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
113 | DISHWASHER3_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
114 | REFRIGERATOR3_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
115 | CLOTHESWASHER3_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
116 | ELECTRIC_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
117 | ELECTRIC_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
118 | TELEVISION3_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
119 | ELECTRIC_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
120 | IECC_ADJ3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
121 | DISHWASHER1_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
122 | REFRIGERATOR1_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
123 | CLOTHESWASHER1_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
124 | ELECTRIC_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
125 | ELECTRIC_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
126 | TELEVISION1_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
127 | ELECTRIC_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
128 | IECC_ADJ1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
129 | DISHWASHER2_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
130 | REFRIGERATOR2_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
131 | CLOTHESWASHER2_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
132 | ELECTRIC_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
133 | ELECTRIC_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
134 | TELEVISION2_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
135 | ELECTRIC_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
136 | IECC_ADJ2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
137 | DISHWASHER3_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 103.861 | 0.087 | 15.220 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 103.861 |
138 | REFRIGERATOR3_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 287.932 | 0.240 | 42.194 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 210.592 | 287.932 |
139 | CLOTHESWASHER3_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 36.645 | 0.031 | 5.370 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 36.645 |
140 | ELECTRIC_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
141 | ELECTRIC_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
142 | TELEVISION3_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
143 | ELECTRIC_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
144 | IECC_ADJ3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
Construction Name | Index | #Layers | #CTFs | Time Step {Hours} | ThermalConductance {Btu/h-ft2-F} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | EXTERIOR WALL | 1 | 5 | 11 | 0.167 | 0.0631 | 0.700 | 0.900 | 0.700 | 0.700 | MediumSmooth |
2 | CEILING-FLOOR-LAYER | 3 | 1 | 5 | 0.167 | 0.228 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | EXTERIOR FLOOR | 4 | 3 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
4 | INTERIOR CEILING | 6 | 2 | 10 | 0.167 | 0.0281 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
5 | ATTIC FLOOR | 7 | 2 | 10 | 0.167 | 0.0281 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | INTERIORWALL | 9 | 3 | 5 | 0.167 | 0.597 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | EXTERIOR ROOF | 11 | 2 | 4 | 0.167 | 0.943 | 0.900 | 0.900 | 0.750 | 0.700 | MediumRough |
8 | EXTERIOR DOOR | 14 | 1 | 5 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | GABLE_END | 16 | 5 | 6 | 0.167 | 0.428 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | ThermalResistance {m2-K/w} | |
1 | SYN_STUCCO | 0.0098 | 0.086 | 24.971 | 0.210 | 0.3524E-01 |
2 | SHEATHING_CONSOL_LAYER | 0.0417 | 0.094 | 42.764 | 0.280 | 0.1351 |
3 | OSB_7/16IN | 0.0364 | 0.116 | 34.000 | 0.290 | 0.9555E-01 |
4 | WALL_CONSOL_LAYER | 0.4584 | 0.057 | 7.541 | 0.248 | 2.444 |
5 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
6 | LUMBER_2X4 | 0.2920 | 0.115 | 32.003 | 0.183 | 0.7709 |
7 | FLOOR_CONSOL_LAYER | 0.0010 | 12.990 | 3.438 | 0.219 | 0.1955E-04 |
8 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
9 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
10 | CEIL_CONSOL_LAYER | 1.2550 | 0.062 | 2.618 | 0.185 | 6.198 |
11 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
12 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
13 | CEIL_CONSOL_LAYER | 1.2550 | 0.062 | 2.618 | 0.185 | 6.198 |
14 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
15 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
16 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
17 | ASPHALT_SHINGLE | 0.0207 | 0.082 | 70.000 | 0.300 | 0.7745E-01 |
18 | OSB_1/2IN | 0.0417 | 0.116 | 34.000 | 0.290 | 0.1092 |
19 | DOOR_CONST | 0.1388 | 0.072 | 32.003 | 0.183 | 0.5870 |
20 | CEMENT_STUCCO | 0.0627 | 0.721 | 116.464 | 0.210 | 0.2642E-01 |
21 | BLDG_PAPER_FELT | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1057E-01 |
22 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
23 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 11 | -0.54724946E-11 | -0.29353179E-14 | -0.58361936E-11 | 0.17617726E-15 |
2 | 10 | 0.24755928E-06 | 0.16971160E-13 | 0.58954555E-06 | -0.42317085E-11 |
3 | 9 | -0.21700660E-03 | 0.26282512E-10 | -0.34360792E-03 | 0.18634160E-06 |
4 | 8 | 0.10400975E-01 | 0.16063655E-07 | 0.16710006E-01 | -0.10459154E-03 |
5 | 7 | -0.18466841 | 0.14497582E-05 | -0.31678806 | 0.33996447E-02 |
6 | 6 | 1.6813335 | 0.30890211E-04 | 3.0392820 | -0.45644738E-01 |
7 | 5 | -8.8640021 | 0.19737274E-03 | -16.399456 | 0.32465800 |
8 | 4 | 28.400945 | 0.41196590E-03 | 52.185337 | -1.3315683 |
9 | 3 | -55.684303 | 0.27160336E-03 | -99.213599 | 3.2198962 |
10 | 2 | 64.740984 | 0.46773103E-04 | 110.17164 | -4.4902555 |
11 | 1 | -40.701741 | 0.11975386E-05 | -65.686261 | 3.3169381 |
12 | 0 | 10.602230 | 0.29970883E-09 | 16.204438 | |
13 | 5 | -0.10726087E-01 | 0.44268190E-05 | -0.10726087E-01 | 0.97389233E-03 |
14 | 4 | 0.31857203 | 0.80150166E-03 | 0.31857203 | -0.30727185E-01 |
15 | 3 | -2.8372473 | 0.12516450E-01 | -2.8372473 | 0.30041224 |
16 | 2 | 9.6667056 | 0.33176537E-01 | 9.6667056 | -1.1584571 |
17 | 1 | -13.322214 | 0.15207483E-01 | -13.322214 | 1.8397512 |
18 | 0 | 6.2472388 | 0.62260140E-03 | 6.2472388 | |
19 | 4 | 0.29631924E-13 | -0.40788276E-14 | 0.60443234E-14 | -0.77798347E-16 |
20 | 3 | -0.11254351E-04 | 0.79669069E-06 | -0.23145793E-05 | 0.39394231E-13 |
21 | 2 | 0.49771861 | 0.29587917E-01 | 0.78801895E-01 | -0.76025120E-05 |
22 | 1 | -8.3915550 | 0.80192706 | -1.1535996 | 0.21114735 |
23 | 0 | 9.2367617 | 0.51139848 | 2.4177143 | |
24 | 10 | 0.25332408E-17 | -0.22101509E-14 | 0.15157692E-08 | 0.28211904E-17 |
25 | 9 | -0.31506112E-08 | -0.26974675E-14 | -0.81843868E-03 | 0.20118786E-08 |
26 | 8 | 0.42861811E-03 | 0.11354105E-09 | 0.39097097E-01 | -0.27370296E-03 |
27 | 7 | -0.11368907E-01 | 0.51842634E-07 | -0.64553953 | 0.74324363E-02 |
28 | 6 | 0.12484615 | 0.25047115E-05 | 5.3130581 | -0.83937451E-01 |
29 | 5 | -0.73775399 | 0.27964547E-04 | -24.889648 | 0.51283867 |
30 | 4 | 2.5553417 | 0.92755650E-04 | 70.144414 | -1.8477174 |
31 | 3 | -5.2989438 | 0.96002462E-04 | -120.51707 | 4.0111012 |
32 | 2 | 6.4233118 | 0.27752742E-04 | 123.06129 | -5.1209931 |
33 | 1 | -4.1707712 | 0.15163054E-05 | -68.409714 | 3.5199891 |
34 | 0 | 1.1151582 | 0.34288690E-08 | 15.905180 | |
35 | 10 | 0.15157692E-08 | -0.22101509E-14 | 0.25332408E-17 | 0.28211904E-17 |
36 | 9 | -0.81843868E-03 | -0.26974675E-14 | -0.31506112E-08 | 0.20118786E-08 |
37 | 8 | 0.39097097E-01 | 0.11354105E-09 | 0.42861811E-03 | -0.27370296E-03 |
38 | 7 | -0.64553953 | 0.51842634E-07 | -0.11368907E-01 | 0.74324363E-02 |
39 | 6 | 5.3130581 | 0.25047115E-05 | 0.12484615 | -0.83937451E-01 |
40 | 5 | -24.889648 | 0.27964547E-04 | -0.73775399 | 0.51283867 |
41 | 4 | 70.144414 | 0.92755650E-04 | 2.5553417 | -1.8477174 |
42 | 3 | -120.51707 | 0.96002462E-04 | -5.2989438 | 4.0111012 |
43 | 2 | 123.06129 | 0.27752742E-04 | 6.4233118 | -5.1209931 |
44 | 1 | -68.409714 | 0.15163054E-05 | -4.1707712 | 3.5199891 |
45 | 0 | 15.905180 | 0.34288690E-08 | 1.1151582 | |
46 | 5 | -0.27590492E-07 | 0.65241430E-08 | -0.27590492E-07 | 0.17331255E-13 |
47 | 4 | 0.68608714E-03 | 0.11323974E-03 | 0.68608714E-03 | -0.15705033E-07 |
48 | 3 | -0.21538511 | 0.37821720E-01 | -0.21538511 | 0.25667047E-03 |
49 | 2 | 5.0173519 | 0.62258424 | 5.0173519 | -0.50236511E-01 |
50 | 1 | -19.904252 | 0.86481321 | -19.904252 | 0.58144210 |
51 | 0 | 16.688993 | 0.62060609E-01 | 16.688993 | |
52 | 4 | 0.75441920E-10 | 0.23883683E-10 | 0.47514224E-10 | -0.69373194E-20 |
53 | 3 | -0.33730907E-03 | 0.89366797E-04 | -0.22574866E-03 | 0.77828620E-10 |
54 | 2 | 0.58624422 | 0.18542418 | 0.49024360 | -0.17301269E-03 |
55 | 1 | -11.299243 | 2.8799011 | -8.6239668 | 0.15905732 |
56 | 0 | 15.219762 | 1.4410112 | 12.640375 | |
57 | 5 | -0.32935335E-06 | 0.42931990E-07 | -0.32935335E-06 | 0.47097488E-08 |
58 | 4 | 0.68052310E-03 | 0.12823787E-03 | 0.68052310E-03 | -0.14200104E-04 |
59 | 3 | -0.11535993 | 0.17375615E-01 | -0.11535993 | 0.40770076E-02 |
60 | 2 | 2.1922172 | 0.21284128 | 2.1922172 | -0.13171357 |
61 | 1 | -7.8704965 | 0.30308566 | -7.8704965 | 0.79499401 |
62 | 0 | 6.3596665 | 0.33276539E-01 | 6.3596665 | |
63 | 6 | 0.97988530E-11 | 0.43917118E-12 | 0.24496810E-11 | -0.34892153E-15 |
64 | 5 | -0.75005310E-05 | 0.16499726E-06 | -0.28271466E-05 | 0.19166609E-11 |
65 | 4 | 0.32354224E-01 | 0.66949565E-03 | 0.10283773E-01 | -0.11111676E-05 |
66 | 3 | -1.8201547 | 0.67148336E-01 | -0.62076152 | 0.38788549E-02 |
67 | 2 | 21.173821 | 0.53241617 | 7.5279938 | -0.97325542E-01 |
68 | 1 | -64.420211 | 0.46601667 | -21.697519 | 0.64629334 |
69 | 0 | 46.121323 | 0.20873329E-01 | 15.867130 |
Construction Name | Index | #Layers | Roughness | Conductance {Btu/h-ft2-F} | Conductance (Before Adjusted) {Btu/h-ft2-F} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | EXTERIOR WINDOW | 12 | 1 | VerySmooth | 0.300 | 0.300 | 1.000 | 0.217 | ||
2 | INTERIOR WINDOW | 13 | 1 | VerySmooth | 0.300 | 0.300 | 1.000 | 0.217 | ||
3 | WINDOW_W_BLINDS | 18 | 2 | VerySmooth | 0.300 | 0.300 | 1.000 | 0.208 | ||
4 | TDD DOME | 22 | 1 | VerySmooth | 1.071 | 1.071 | 1.000 | 0.929 | ||
5 | TDD DIFFUSER | 23 | 1 | VerySmooth | 1.077 | 1.077 | 1.000 | 0.906 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {ft} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLASS | SpectralAverage | 0.13728 | 0.12813 | 0.66698 | 0.66698 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
2 | GLASS | SpectralAverage | 0.13728 | 0.12813 | 0.66698 | 0.66698 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
3 | GLASS | SpectralAverage | 0.13728 | 0.12813 | 0.66698 | 0.66698 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
4 | CLEAR ACRYLIC PLASTIC | SpectralAverage | 0.00984 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No | |
5 | DIFFUSING ACRYLIC PLASTIC | SpectralAverage | 0.00722 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No |
Material Name | Slat Width {ft} | Slat Separation {ft} | Slat Thickness {ft} | Slat Angle {deg} | Slat Beam Solar Transmittance | Slat Beam Solar Front Reflectance | Blind To Glass Distance {ft} | |
1 | INT_BLIND | 0.0820 | 0.0615 | 0.0033 | 45.000 | 0.000 | 0.500 | 0.164 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000. | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {ft3} | Maximum Capacity {Btu/h} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
2 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
3 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
4 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
5 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
6 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
7 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
8 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
9 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
10 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
11 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
12 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
13 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
14 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
15 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
16 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
17 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 | |
18 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 6.6825 | 4477.6 | 0.000 | 0.0000 | 926 |
Node Number | Height {ft} | Volume {ft3} | Maximum Capacity {Btu/h} | Off-Cycle UA {Btu/h-F} | On-Cycle UA {Btu/h-F} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
2 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
3 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
4 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
5 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
6 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
7 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
8 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
9 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
10 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
11 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
12 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
13 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
14 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
15 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
16 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
17 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
18 | 1 | 5.2299 | 6.6825 | 0.000 | 0.9104 | 0.9104 | 1 | 1 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
2 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
3 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
4 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
5 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
6 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
7 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
8 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
9 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
10 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
11 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
12 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
13 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
14 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
15 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
16 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
17 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
18 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
19 | ATTICVENT | ALWAYS_AVAIL | ATTIC | 7802.66 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/person Area {ft3/min-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {psi} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{F}/Schedule | Maximum Indoor Temperature{F}/Schedule | Delta Temperature{F}/Schedule | Minimum Outdoor Temperature{F}/Schedule | Maximum Outdoor Temperature{F}/Schedule | Maximum WindSpeed{ft/min} | |
1 | VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
2 | VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
3 | VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
4 | VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
5 | VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
6 | VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
7 | VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
8 | VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
9 | VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
10 | VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
11 | VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
12 | VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
13 | VENTILATION_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
14 | VENTILATION_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
15 | VENTILATION_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
16 | VENTILATION_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
17 | VENTILATION_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
18 | VENTILATION_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BREEZEWAY | Mixing/Well-Stirred |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
4 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
5 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
6 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
7 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
8 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
9 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
10 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
11 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
12 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
13 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
14 | ATTIC | Mixing/Well-Stirred |
15 | LIVING_UNIT3_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
16 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
17 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
18 | LIVING_UNIT2_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
19 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
20 | LIVING_UNIT1_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {Btu/h} | User Des Load {Btu/h} | Calc Des Air Flow Rate {ft3/min} | User Des Air Flow Rate {ft3/min} | Design Day Name | Date/Time of Peak | Temperature at Peak {F} | Humidity Ratio at Peak {lbWater/lbDryAir} | Floor Area {ft2} | # Occupants | Calc Outdoor Air Flow Rate {ft3/min} | Calc DOAS Heat Addition Rate {Btu/h} | |
1 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | 6457.07574 | 6457.07574 | 280.12708 | 280.12708 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 86.31081 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | 4094.67392 | 4094.67392 | 75.95084 | 75.95084 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | 3230.40507 | 3230.40507 | 140.14045 | 140.14045 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 83.29370 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | 3151.17734 | 3151.17734 | 58.45063 | 58.45063 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | 4425.86157 | 4425.86157 | 191.99955 | 191.99955 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 83.05340 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
6 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | 4097.15311 | 4097.15311 | 75.99681 | 75.99681 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
7 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | 6010.28362 | 6010.28362 | 260.74149 | 260.74149 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 85.83021 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
8 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Heating | 4096.99435 | 4096.99435 | 75.99385 | 75.99385 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
9 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | 2950.40615 | 2950.40615 | 127.99405 | 127.99405 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 82.09220 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
10 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Heating | 3151.31177 | 3151.31177 | 58.45317 | 58.45317 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
11 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | 4094.20268 | 4094.20268 | 177.61142 | 177.61142 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 81.34461 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
12 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Heating | 4095.07769 | 4095.07769 | 75.95825 | 75.95825 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
13 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | 7530.97063 | 7530.97063 | 326.69487 | 326.69487 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 85.83021 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
14 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | 3792.37068 | 3792.37068 | 70.34427 | 70.34427 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
15 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | 4075.42382 | 4075.42382 | 176.79998 | 176.79998 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 82.09220 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
16 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | 2746.16772 | 2746.16772 | 50.93876 | 50.93876 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
17 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | 5333.70354 | 5333.70354 | 231.37709 | 231.37709 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 | 84.25490 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
18 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | 3795.48198 | 3795.48198 | 70.40190 | 70.40190 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
19 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | 7037.31299 | 7037.31299 | 305.29657 | 305.29657 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 85.56319 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
20 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Heating | 3795.90613 | 3795.90613 | 70.40974 | 70.40974 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
21 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | 3739.91906 | 3739.91906 | 162.24489 | 162.24489 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 82.09220 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
22 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Heating | 2747.45496 | 2747.45496 | 50.96249 | 50.96249 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
23 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | 4915.77049 | 4915.77049 | 213.24150 | 213.24150 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 82.65290 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
24 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Heating | 3794.50308 | 3794.50308 | 70.38389 | 70.38389 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
25 | LIVING_UNIT3_BACKROW_TOPFLOOR | Cooling | 5567.73865 | 5567.73865 | 241.54658 | 241.54658 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 84.49520 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
26 | LIVING_UNIT3_BACKROW_TOPFLOOR | Heating | 5053.63787 | 5053.63787 | 93.73812 | 93.73812 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
27 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Cooling | 5935.99660 | 5935.99660 | 257.52115 | 257.52115 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 88.34000 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
28 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Heating | 5054.64745 | 5054.64745 | 93.75677 | 93.75677 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
29 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Cooling | 8471.34516 | 8471.34516 | 367.49995 | 367.49995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 85.56319 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
30 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Heating | 5051.85790 | 5051.85790 | 93.70507 | 93.70507 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
31 | LIVING_UNIT2_BACKROW_TOPFLOOR | Cooling | 4952.48289 | 4952.48289 | 214.85167 | 214.85167 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 82.49270 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
32 | LIVING_UNIT2_BACKROW_TOPFLOOR | Heating | 3984.92912 | 3984.92912 | 73.91546 | 73.91546 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
33 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Cooling | 5010.84580 | 5010.84580 | 217.37285 | 217.37285 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 82.49270 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
34 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Heating | 3984.19376 | 3984.19376 | 73.90169 | 73.90169 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
35 | LIVING_UNIT1_BACKROW_TOPFLOOR | Cooling | 8349.40291 | 8349.40291 | 362.20334 | 362.20334 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 85.56319 | 0.00823 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
36 | LIVING_UNIT1_BACKROW_TOPFLOOR | Heating | 5054.19140 | 5054.19140 | 93.74829 | 93.74829 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 38.84000 | 0.00506 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [ft3/min] | User Des Air Flow Rate [ft3/min] | Design Day Name | Date/Time of Peak | |
1 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2025.08 | 280.12708 | 280.12708 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 1647.17 | 75.95084 | 75.95084 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 |
3 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1050.05 | 140.14045 | 140.14045 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 1374.68 | 58.45063 | 58.45063 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 |
5 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1392.26 | 191.99955 | 191.99955 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 1647.89 | 75.99681 | 75.99681 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 |
7 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1889.19 | 260.74149 | 260.74149 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Heating | Sensible | 1647.84 | 75.99385 | 75.99385 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 |
9 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 952.28 | 127.99405 | 127.99405 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Heating | Sensible | 1374.72 | 58.45317 | 58.45317 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 |
11 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1272.45 | 177.61142 | 177.61142 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Heating | Sensible | 1647.29 | 75.95825 | 75.95825 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 |
13 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2328.79 | 326.69487 | 326.69487 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1559.87 | 70.34427 | 70.34427 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
15 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 1277.50 | 176.79998 | 176.79998 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1257.72 | 50.93876 | 50.93876 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
17 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 1671.54 | 231.37709 | 231.37709 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1560.77 | 70.40190 | 70.40190 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
19 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2182.34 | 305.29657 | 305.29657 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1560.89 | 70.40974 | 70.40974 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
21 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1180.51 | 162.24489 | 162.24489 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
22 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1258.09 | 50.96249 | 50.96249 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
23 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1528.27 | 213.24150 | 213.24150 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
24 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1560.48 | 70.38389 | 70.38389 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
25 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Cooling | Sensible | 2596.89 | 367.49995 | 367.49995 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
26 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Heating | Sensible | 1923.62 | 93.70507 | 93.70507 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
27 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Cooling | Sensible | 1553.52 | 217.37285 | 217.37285 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
28 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Heating | Sensible | 1615.26 | 73.90169 | 73.90169 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
29 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Cooling | Sensible | 1902.89 | 257.52115 | 257.52115 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
30 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Heating | Sensible | 1924.42 | 93.75677 | 93.75677 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
31 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Cooling | Sensible | 2561.64 | 362.20334 | 362.20334 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
32 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Heating | Sensible | 1924.29 | 93.74829 | 93.74829 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
33 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Cooling | Sensible | 1536.65 | 214.85167 | 214.85167 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
34 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Heating | Sensible | 1615.48 | 73.91546 | 73.91546 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
35 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Cooling | Sensible | 1742.56 | 241.54658 | 241.54658 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
36 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Heating | Sensible | 1924.13 | 93.73812 | 93.73812 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 280.12708 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 140.14045 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 191.99955 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 260.74149 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 127.99405 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 177.61142 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 326.69487 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 176.79998 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 231.37709 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 305.29657 |
11 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 162.24489 |
12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 213.24150 |
13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 241.54658 |
14 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 257.52115 |
15 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 367.49995 |
16 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 214.85167 |
17 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 217.37285 |
18 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 362.20334 |
19 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 280.12708 |
20 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 280.12708 |
21 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 280.12708 |
22 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 280.12708 |
23 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 280.12708 |
24 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 280.12708 |
25 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 140.14045 |
28 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 140.14045 |
29 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 140.14045 |
30 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 140.14045 |
31 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 140.14045 |
32 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 140.14045 |
33 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 191.99955 |
36 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 191.99955 |
37 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 191.99955 |
38 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 191.99955 |
39 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 191.99955 |
40 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 191.99955 |
41 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 260.74149 |
44 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 260.74149 |
45 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 260.74149 |
46 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 260.74149 |
47 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 260.74149 |
48 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 260.74149 |
49 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 127.99405 |
52 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 127.99405 |
53 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 127.99405 |
54 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 127.99405 |
55 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 127.99405 |
56 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 127.99405 |
57 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 177.61142 |
60 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 177.61142 |
61 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 177.61142 |
62 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 177.61142 |
63 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 177.61142 |
64 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 177.61142 |
65 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 326.69487 |
68 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 326.69487 |
69 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 326.69487 |
70 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 326.69487 |
71 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 326.69487 |
72 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 326.69487 |
73 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 176.79998 |
76 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 176.79998 |
77 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 176.79998 |
78 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 176.79998 |
79 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 176.79998 |
80 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 176.79998 |
81 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 231.37709 |
84 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 231.37709 |
85 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 231.37709 |
86 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 231.37709 |
87 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 231.37709 |
88 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 231.37709 |
89 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 305.29657 |
92 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 305.29657 |
93 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 305.29657 |
94 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 305.29657 |
95 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 305.29657 |
96 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 305.29657 |
97 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
98 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
99 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 162.24489 |
100 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 162.24489 |
101 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 162.24489 |
102 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 162.24489 |
103 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 162.24489 |
104 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 162.24489 |
105 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
106 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
107 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 213.24150 |
108 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 213.24150 |
109 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 213.24150 |
110 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 213.24150 |
111 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 213.24150 |
112 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 213.24150 |
113 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
114 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
115 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 367.49995 |
116 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 367.49995 |
117 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 367.49995 |
118 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 367.49995 |
119 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 367.49995 |
120 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 367.49995 |
121 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
122 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
123 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 217.37285 |
124 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 217.37285 |
125 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 217.37285 |
126 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 217.37285 |
127 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 217.37285 |
128 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 217.37285 |
129 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
130 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
131 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 257.52115 |
132 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 257.52115 |
133 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 257.52115 |
134 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 257.52115 |
135 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 257.52115 |
136 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 257.52115 |
137 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
138 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
139 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 362.20334 |
140 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 362.20334 |
141 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 362.20334 |
142 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 362.20334 |
143 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 362.20334 |
144 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 362.20334 |
145 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
146 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
147 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 214.85167 |
148 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 214.85167 |
149 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 214.85167 |
150 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 214.85167 |
151 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 214.85167 |
152 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 214.85167 |
153 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
154 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
155 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 241.54658 |
156 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 241.54658 |
157 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 241.54658 |
158 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 241.54658 |
159 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 241.54658 |
160 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 241.54658 |
161 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
162 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
163 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 280.12708 |
164 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 140.14045 |
165 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 191.99955 |
166 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 260.74149 |
167 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 127.99405 |
168 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 177.61142 |
169 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 326.69487 |
170 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 176.79998 |
171 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 231.37709 |
172 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 305.29657 |
173 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 162.24489 |
174 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 213.24150 |
175 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 367.49995 |
176 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 217.37285 |
177 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 257.52115 |
178 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 362.20334 |
179 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 214.85167 |
180 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 241.54658 |
181 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 280.12708 |
182 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.84671 |
183 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73221 |
184 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 280.12708 |
185 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 280.12708 |
186 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 280.12708 |
187 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 5620.14827 |
188 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.84671 |
189 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
190 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 280.12708 |
191 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 6463.17049 |
192 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 140.14045 |
193 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.45048 |
194 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.71209 |
195 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 140.14045 |
196 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 140.14045 |
197 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 140.14045 |
198 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 4690.40959 |
199 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.45048 |
200 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
201 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 140.14045 |
202 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 5393.97106 |
203 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 191.99955 |
204 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.58011 |
205 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73233 |
206 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 191.99955 |
207 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 191.99955 |
208 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 191.99955 |
209 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 5622.59133 |
210 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.58011 |
211 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
212 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 191.99955 |
213 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 6465.98000 |
214 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 260.74149 |
215 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.79120 |
216 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73116 |
217 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 260.74149 |
218 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 260.74149 |
219 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 260.74149 |
220 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 5622.43489 |
221 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.79120 |
222 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
223 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 260.74149 |
224 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 6465.80012 |
225 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 127.99405 |
226 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.41015 |
227 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.71389 |
228 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 127.99405 |
229 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 127.99405 |
230 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 127.99405 |
231 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 4690.54205 |
232 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.41015 |
233 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
234 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 127.99405 |
235 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 5394.12337 |
236 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 177.61142 |
237 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.53079 |
238 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73631 |
239 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 177.61142 |
240 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 177.61142 |
241 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 177.61142 |
242 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 5620.54618 |
243 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.53079 |
244 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
245 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 177.61142 |
246 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 6463.62811 |
247 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 326.69487 |
248 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.96749 |
249 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73981 |
250 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 326.69487 |
251 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 326.69487 |
252 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 326.69487 |
253 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 5322.27245 |
254 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.96749 |
255 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
256 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 326.69487 |
257 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 6120.61330 |
258 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 176.79998 |
259 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.54553 |
260 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.72570 |
261 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 176.79998 |
262 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 176.79998 |
263 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 176.79998 |
264 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 4291.32396 |
265 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.54553 |
266 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
267 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 176.79998 |
268 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 4935.02253 |
269 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 231.37709 |
270 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.69263 |
271 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73586 |
272 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 231.37709 |
273 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 231.37709 |
274 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 231.37709 |
275 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 5325.33840 |
276 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.69263 |
277 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
278 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 231.37709 |
279 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 6124.13916 |
280 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 305.29657 |
281 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.91031 |
282 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73692 |
283 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 305.29657 |
284 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 305.29657 |
285 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 305.29657 |
286 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 5325.75637 |
287 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.91031 |
288 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
289 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 305.29657 |
290 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 6124.61981 |
291 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 162.24489 |
292 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.50578 |
293 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.72200 |
294 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 162.24489 |
295 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 162.24489 |
296 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 162.24489 |
297 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 4292.59240 |
298 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.50578 |
299 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 162.24489 |
301 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 4936.48126 |
302 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 213.24150 |
303 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.63315 |
304 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73910 |
305 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 213.24150 |
306 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 213.24150 |
307 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 213.24150 |
308 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 5324.37376 |
309 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.63315 |
310 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
311 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 213.24150 |
312 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 6123.02981 |
313 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 367.49995 |
314 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.07890 |
315 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.74221 |
316 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 367.49995 |
317 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 367.49995 |
318 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 367.49995 |
319 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 6563.38141 |
320 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.07890 |
321 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
322 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 367.49995 |
323 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 7547.88859 |
324 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 217.37285 |
325 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.65905 |
326 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73140 |
327 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 217.37285 |
328 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 217.37285 |
329 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 217.37285 |
330 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 5511.28333 |
331 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.65905 |
332 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
333 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 217.37285 |
334 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 6337.97582 |
335 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 257.52115 |
336 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.79924 |
337 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.72416 |
338 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 257.52115 |
339 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 257.52115 |
340 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 257.52115 |
341 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 6566.13025 |
342 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.79924 |
343 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
344 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 257.52115 |
345 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 7551.04981 |
346 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 362.20334 |
347 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.06475 |
348 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.74185 |
349 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 362.20334 |
350 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 362.20334 |
351 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 362.20334 |
352 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 6565.68086 |
353 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.06475 |
354 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
355 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 362.20334 |
356 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 7550.53299 |
357 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 214.85167 |
358 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.65226 |
359 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73104 |
360 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 214.85167 |
361 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 214.85167 |
362 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 214.85167 |
363 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 5512.00797 |
364 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.65226 |
365 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
366 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 214.85167 |
367 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 6338.80916 |
368 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 241.54658 |
369 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.73624 |
370 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.72996 |
371 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 241.54658 |
372 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 241.54658 |
373 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 241.54658 |
374 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 6565.13538 |
375 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.73624 |
376 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
377 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 241.54658 |
378 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 7549.90570 |
379 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
380 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
381 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
382 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
383 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
384 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
385 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
386 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
387 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
388 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
389 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
390 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
391 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
392 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
393 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
394 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
395 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
396 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
397 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
398 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
399 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
400 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
401 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
402 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
403 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
404 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
405 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
406 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
407 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
408 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
409 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
410 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
411 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
412 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
413 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
414 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
415 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
416 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
417 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
418 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
419 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
420 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
421 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
422 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
423 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
424 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
425 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
426 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
427 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
428 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
429 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
430 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
431 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
432 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
433 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
434 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
435 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
436 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
437 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
438 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
439 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
440 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
441 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
442 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
443 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
444 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
445 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
446 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
447 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
448 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
449 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
450 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
451 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
452 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
453 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
454 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
455 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
456 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
457 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
458 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
459 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
460 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
461 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
462 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
463 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
464 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
465 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
466 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
467 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
468 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
469 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
470 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
471 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
472 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
473 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
474 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
475 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
476 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
477 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
478 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
479 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
480 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
481 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
482 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
483 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
484 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
485 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
486 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {ton} | Standard Rated Net COP {Btuh/Btuh} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 0.8 | 3.62 | 12.36 | 13.10 | 12.59 | 12.86 |
2 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 0.8 | 3.50 | 11.94 | 12.65 | 12.50 | -99999. |
3 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4 | 3.66 | 12.48 | 13.24 | 12.72 | 13.07 |
4 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4 | 3.54 | 12.08 | 12.80 | 12.66 | -99999. |
5 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.6 | 3.62 | 12.35 | 13.10 | 12.59 | 12.86 |
6 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.6 | 3.50 | 11.94 | 12.65 | 12.50 | -99999. |
7 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.8 | 3.62 | 12.36 | 13.11 | 12.60 | 12.88 |
8 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.8 | 3.50 | 11.95 | 12.66 | 12.51 | -99999. |
9 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.4 | 3.65 | 12.47 | 13.23 | 12.72 | 13.06 |
10 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.4 | 3.54 | 12.08 | 12.79 | 12.65 | -99999. |
11 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.5 | 3.61 | 12.33 | 13.08 | 12.57 | 12.82 |
12 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.5 | 3.49 | 11.92 | 12.62 | 12.48 | -99999. |
13 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.9 | 3.61 | 12.31 | 13.06 | 12.55 | 12.79 |
14 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.9 | 3.49 | 11.90 | 12.59 | 12.45 | -99999. |
15 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.63 | 12.40 | 13.15 | 12.64 | 12.93 |
16 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.51 | 11.99 | 12.70 | 12.56 | -99999. |
17 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.62 | 12.34 | 13.08 | 12.57 | 12.83 |
18 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.49 | 11.92 | 12.62 | 12.48 | -99999. |
19 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.9 | 3.61 | 12.33 | 13.07 | 12.56 | 12.82 |
20 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.9 | 3.49 | 11.91 | 12.61 | 12.47 | -99999. |
21 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.5 | 3.64 | 12.42 | 13.17 | 12.66 | 12.97 |
22 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.5 | 3.52 | 12.01 | 12.73 | 12.58 | -99999. |
23 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.6 | 3.61 | 12.32 | 13.06 | 12.56 | 12.80 |
24 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.6 | 3.49 | 11.90 | 12.60 | 12.46 | -99999. |
25 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.0 | 3.60 | 12.30 | 13.04 | 12.53 | 12.76 |
26 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.0 | 3.48 | 11.87 | 12.57 | 12.43 | -99999. |
27 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.6 | 3.62 | 12.36 | 13.11 | 12.60 | 12.87 |
28 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.6 | 3.50 | 11.95 | 12.66 | 12.51 | -99999. |
29 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.8 | 3.64 | 12.41 | 13.16 | 12.65 | 12.95 |
30 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.8 | 3.52 | 12.00 | 12.71 | 12.57 | -99999. |
31 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.0 | 3.60 | 12.30 | 13.04 | 12.53 | 12.77 |
32 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.0 | 3.48 | 11.88 | 12.58 | 12.43 | -99999. |
33 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.6 | 3.62 | 12.36 | 13.11 | 12.60 | 12.88 |
34 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.6 | 3.50 | 11.95 | 12.66 | 12.52 | -99999. |
35 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.7 | 3.63 | 12.37 | 13.12 | 12.61 | 12.89 |
36 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.7 | 3.51 | 11.96 | 12.67 | 12.53 | -99999. |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | SizingPeriod:DesignDay | 12/21 | 12/21 | WinterDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
2 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | SizingPeriod:DesignDay | 08/21 | 08/21 | SummerDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
3 | ANNUAL | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | No | SizingPeriod:DesignDay | ||
2 | No | SizingPeriod:DesignDay | ||
3 | No |
NumberofWarmupDays | |
1 | 14 |
2 | 25 |
3 | 25 |
Max Dry-Bulb Temp {F} | Temp Range {dC} | Temp Range Ind Type | Hum Ind Type | Hum Ind Value at Max Temp | Hum Ind Units | Pressure {psi} | Wind Direction {deg CW from N} | Wind Speed {ft/min} | Clearness | Rain | Snow | |
1 | 38.84 | 0.00 | DefaultMultipliers | Wetbulb | 3.80 | {C} | 14. | 120 | 590.6 | 0.00 | No | No |
2 | 88.34 | 8.90 | DefaultMultipliers | Wetbulb | 18.40 | {C} | 14. | 280 | 807.1 | 0.00 | No | No |
DayOfYear | ASHRAE A Coeff | ASHRAE B Coeff | ASHRAE C Coeff | Solar Constant-Annual Variation | Eq of Time {minutes} | Solar Declination Angle {deg} | Solar Model | |
1 | 355 | 1232.8 | 0.1424 | 5.7719E-002 | 1.0 | 2.45 | -24. | ASHRAEClearSky |
2 | 233 | 1106.3 | 0.2000 | 0.1216 | 1.0 | -3.33 | 12.4 | ASHRAETau |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaF} | Std Dev Warmup Temperature Difference {deltaF} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {Btu/h} | Std Dev Warmup Load Difference {Btu/h} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BREEZEWAY | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000002783 | 0.000001626 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.083623518 | 0.200444856 | Pass | Pass | 0.186058087 | 0.441480051 | Pass | Pass |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.114370707 | 0.260282046 | Pass | Pass | 0.376466440 | 0.911982336 | Pass | Pass |
4 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.093687212 | 0.220695692 | Pass | Pass | 0.226990700 | 0.542102066 | Pass | Pass |
5 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.085751340 | 0.204685404 | Pass | Pass | 0.193464505 | 0.463845957 | Pass | Pass |
6 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.115838282 | 0.263264174 | Pass | Pass | 0.373209749 | 0.913356346 | Pass | Pass |
7 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.095468713 | 0.224290857 | Pass | Pass | 0.240190673 | 0.579903023 | Pass | Pass |
8 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.074788387 | 0.187651940 | Pass | Pass | 0.172110722 | 0.438708546 | Pass | Pass |
9 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.105282867 | 0.245941112 | Pass | Pass | 0.433285221 | 1.177727938 | Pass | Pass |
10 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.084631298 | 0.207557640 | Pass | Pass | 0.192785995 | 0.493141452 | Pass | Pass |
11 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.076917418 | 0.191913014 | Pass | Pass | 0.175814336 | 0.442736422 | Pass | Pass |
12 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.106872212 | 0.249055184 | Pass | Pass | 0.438215900 | 1.188469154 | Pass | Pass |
13 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.086586931 | 0.211608784 | Pass | Pass | 0.197956887 | 0.514015706 | Pass | Pass |
14 | ATTIC | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.000114213 | 0.000076041 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
15 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.073879317 | 0.185286415 | Pass | Pass | 0.127708848 | 0.317207175 | Pass | Pass |
16 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.072546216 | 0.182540450 | Pass | Pass | 0.124548745 | 0.309332023 | Pass | Pass |
17 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.063633189 | 0.163961316 | Pass | Pass | 0.107123520 | 0.264765343 | Pass | Pass |
18 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.083499729 | 0.204464941 | Pass | Pass | 0.195972198 | 0.498508632 | Pass | Pass |
19 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.083228084 | 0.203901610 | Pass | Pass | 0.195031697 | 0.495530139 | Pass | Pass |
20 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.064067924 | 0.164857506 | Pass | Pass | 0.108110039 | 0.266628332 | Pass | Pass |
21 | BREEZEWAY | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.319130116 | 0.191342309 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
22 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.042181460 | 0.170234722 | Pass | Pass | 0.216920413 | 0.676078201 | Pass | Pass |
23 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.061848669 | 0.198214724 | Pass | Pass | 0.166659420 | 0.389565409 | Pass | Pass |
24 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.013232710 | 0.076783327 | Pass | Pass | 0.106029644 | 0.152836742 | Pass | Pass |
25 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.053506083 | 0.189590599 | Pass | Pass | 0.304055321 | 1.492645805 | Pass | Pass |
26 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.079113261 | 0.223063568 | Pass | Pass | 0.268060591 | 0.757777247 | Pass | Fail |
27 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.017803531 | 0.081659658 | Pass | Pass | 0.120195461 | 0.173499624 | Pass | Pass |
28 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.021616843 | 0.124959722 | Pass | Pass | 0.157791128 | 0.561054794 | Pass | Pass |
29 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.030352087 | 0.138145169 | Pass | Pass | 0.152439443 | 0.573250027 | Pass | Pass |
30 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.000423671 | 0.002602883 | Pass | Pass | 0.073463019 | 0.072397658 | Pass | Pass |
31 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.029286353 | 0.134065146 | Pass | Pass | 0.172106269 | 0.555182413 | Pass | Pass |
32 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.042812806 | 0.161698197 | Pass | Pass | 0.189968397 | 0.678212754 | Pass | Fail |
33 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.001625352 | 0.008606455 | Pass | Fail | 0.072090793 | 0.078888655 | Pass | Pass |
34 | ATTIC | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.462068850 | 0.369313871 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
35 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.000065185 | 0.000211368 | Pass | Pass | 0.075149575 | 0.072111368 | Pass | Pass |
36 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.000055407 | 0.000185941 | Pass | Pass | 0.076279689 | 0.071656577 | Pass | Pass |
37 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.021130448 | 0.123021796 | Pass | Pass | 0.165199733 | 0.582489414 | Pass | Pass |
38 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.031248267 | 0.143164916 | Pass | Pass | 0.172293078 | 0.614628086 | Pass | Pass |
39 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.024838458 | 0.133542970 | Pass | Pass | 0.147173495 | 0.562490106 | Pass | Pass |
40 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 0.023202354 | 0.126168152 | Pass | Pass | 0.166182598 | 0.558660878 | Pass | Pass |
41 | BREEZEWAY | RunPeriod: ANNUAL | 0.137538982 | 0.111824137 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
42 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.014013748 | 0.059805660 | Pass | Pass | 5.404305180 | 0.546930E+02 | Fail | Fail |
43 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.013173293 | 0.057584557 | Pass | Pass | 0.734097705 | 1.670589511 | Fail | Pass |
44 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.024057777 | 0.062745331 | Pass | Pass | 0.702774366 | 3.316988245 | Pass | Fail |
45 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000679 | 0.000001680 | Pass | Pass | 0.135726768 | 0.206590356 | Pass | Pass |
46 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000509 | 0.000001354 | Pass | Pass | 0.143440673 | 0.311647115 | Pass | Pass |
47 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000000504 | 0.000001337 | Pass | Pass | 0.247223118 | 0.507273885 | Pass | Pass |
48 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.047849571 | 0.127470010 | Pass | Pass | 0.400048649 | 1.019858822 | Fail | Pass |
49 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.073301133 | 0.143743059 | Pass | Pass | 1.421596385 | 8.088299894 | Fail | Pass |
50 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.090558519 | 0.172246653 | Pass | Pass | 0.718463785 | 2.247554214 | Fail | Pass |
51 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.020894538 | 0.068300263 | Pass | Pass | 2.285027237 | 0.225422E+02 | Fail | Pass |
52 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.023869733 | 0.070261101 | Pass | Pass | 0.811455060 | 5.046363415 | Fail | Pass |
53 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.015671625 | 0.059786259 | Pass | Pass | 0.703903134 | 1.927823594 | Pass | Pass |
54 | ATTIC | RunPeriod: ANNUAL | 0.291143813 | 0.321664464 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
55 | LIVING_UNIT3_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000421 | 0.000001037 | Pass | Pass | 0.199770232 | 0.340249042 | Pass | Pass |
56 | LIVING_UNIT3_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.040831005 | 0.093448571 | Pass | Pass | 1.123613324 | 6.651057024 | Pass | Pass |
57 | LIVING_UNIT1_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.037002699 | 0.100447589 | Pass | Pass | 0.382747099 | 1.018087315 | Fail | Pass |
58 | LIVING_UNIT2_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.012138964 | 0.053159509 | Pass | Pass | 0.184026408 | 0.395775092 | Fail | Pass |
59 | LIVING_UNIT2_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.036991309 | 0.095087763 | Pass | Pass | 0.343851562 | 0.807803002 | Fail | Pass |
60 | LIVING_UNIT1_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000000622 | 0.000001734 | Pass | Pass | 0.198582944 | 0.405572920 | Pass | Pass |
Report: Annual Heat Emissions Report
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Annual Heat Emissions SummaryEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [kBtu] | 2942941.08 | 331471.04 | 114665.89 | 0.00 | 137029.47 | 3526114.02 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Heat Index HoursSafe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
BREEZEWAY | 8196.83 | 539.00 | 24.17 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 7411.00 | 1083.00 | 261.83 | 4.17 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 7411.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1083.00 | 261.83 | 4.17 | 0.00 |
Average | 8664.39 | 81.10 | 14.30 | 0.21 | 0.00 |
Sum | 173287.83 | 1622.00 | 286.00 | 4.17 | 0.00 |
Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 10856.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 217122.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 7884.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 157680.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BREEZEWAY | 8566.83 | 193.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8547.50 | 212.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8521.17 | 238.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8540.50 | 219.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8538.33 | 221.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8488.33 | 271.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8531.33 | 228.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8692.83 | 67.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8673.50 | 86.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8695.50 | 64.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8667.50 | 92.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 7361.67 | 1352.00 | 46.33 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8665.83 | 94.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8671.00 | 89.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8666.00 | 94.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8695.00 | 65.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8690.17 | 69.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8661.33 | 98.67 | 0.00 | 0.00 | 0.00 |
Min | 7361.67 | 9.17 | 0.00 | 0.00 | 0.00 |
Max | 8750.83 | 1352.00 | 46.33 | 0.00 | 0.00 |
Average | 8568.80 | 188.88 | 2.32 | 0.00 | 0.00 |
Sum | 171376.00 | 3777.67 | 46.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 11678.09 | 384.29 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 11626.05 | 436.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 11642.72 | 419.66 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 11667.45 | 394.93 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 11584.78 | 477.60 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 11629.74 | 432.64 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 11935.34 | 127.04 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12046.65 | 15.73 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 11893.64 | 168.75 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 11941.74 | 120.64 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12048.19 | 14.19 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 11881.29 | 181.09 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 11881.86 | 180.53 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 11890.81 | 171.57 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 11888.90 | 173.48 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 11943.09 | 119.29 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 11932.84 | 129.54 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 11886.66 | 175.72 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 12048.19 | 477.60 | 0.00 | 0.00 | 0.00 |
Average | 10649.99 | 206.15 | 0.00 | 0.00 | 0.00 |
Sum | 212999.85 | 4123.01 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8547.50 | 212.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8521.17 | 238.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8540.50 | 219.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8538.33 | 221.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8488.33 | 271.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8531.33 | 228.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8692.83 | 67.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8673.50 | 86.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8695.50 | 64.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8667.50 | 92.50 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8665.83 | 94.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8671.00 | 89.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8666.00 | 94.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8695.00 | 65.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8690.17 | 69.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8661.33 | 98.67 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8750.83 | 271.67 | 0.00 | 0.00 | 0.00 |
Average | 7772.38 | 111.62 | 0.00 | 0.00 | 0.00 |
Sum | 155447.50 | 2232.50 | 0.00 | 0.00 | 0.00 |
Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
BREEZEWAY | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Min | 0.00 | - | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Average | 7884.00 | - | 0.00 | 0.00 | 0.00 |
Sum | 157680.00 | - | 0.00 | 0.00 | 0.00 |
Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
BREEZEWAY | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Min | 0.00 | - | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Average | 7884.00 | - | 0.00 | 0.00 | 0.00 |
Sum | 157680.00 | - | 0.00 | 0.00 | 0.00 |
Cooling Setpoint Unmet Degree-Hours [°F·hr] | Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] | Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] | Heating Setpoint Unmet Degree-Hours [°F·hr] | Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] | Heating Setpoint Unmet Occupied Degree-Hours [°C·hr] | |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.05 | 0.07 | 0.05 | 85.39 | 109.48 | 85.39 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.59 | 0.36 | 0.59 | 117.45 | 152.60 | 117.45 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.97 | 0.52 | 0.97 | 86.84 | 121.39 | 86.84 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.05 | 0.08 | 0.05 | 96.41 | 119.98 | 96.41 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.05 | 0.09 | 0.05 | 137.78 | 175.10 | 137.78 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.06 | 0.08 | 0.06 | 104.38 | 127.08 | 104.38 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.08 | 0.11 | 0.08 | 61.66 | 76.66 | 61.66 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.07 | 0.10 | 0.07 | 88.04 | 109.92 | 88.04 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.31 | 0.22 | 0.31 | 61.37 | 88.97 | 61.37 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.06 | 0.10 | 0.06 | 81.40 | 95.39 | 81.40 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.04 | 0.08 | 0.04 | 130.58 | 155.89 | 130.58 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.08 | 0.11 | 0.08 | 90.30 | 114.27 | 90.30 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.06 | 0.10 | 0.06 | 71.70 | 87.96 | 71.70 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.07 | 0.10 | 0.07 | 54.99 | 72.02 | 54.99 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.08 | 0.11 | 0.08 | 59.88 | 70.55 | 59.88 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.06 | 0.10 | 0.06 | 86.01 | 101.21 | 86.01 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.07 | 0.10 | 0.07 | 66.98 | 77.09 | 66.98 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.06 | 0.09 | 0.06 | 64.32 | 75.16 | 64.32 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.97 | 0.52 | 0.97 | 137.78 | 175.10 | 137.78 |
Average | 0.14 | 0.12 | 0.14 | 77.27 | 96.54 | 77.27 |
Sum | 2.81 | 2.48 | 2.81 | 1545.49 | 1930.74 | 1545.49 |
Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 0.00 | 0.00 | 0.00 | 0.00 |
Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 38.84 | 0.00 | 38.84 | Wetbulb [F] | 590.58 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 88.34 | 16.02 | 65.12 | Wetbulb [F] | 807.13 | 280.00 |
Monthly Total Precipitation from .epw [in] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [in] | Monthly Total Roof Irrigation Depth [in] | Monthly Total Rain Collection Volume [ft3] | |
Jan | 0.08 | 2 | |||
Feb | 2.32 | 53 | |||
Mar | 2.31 | 43 | |||
Apr | 1.83 | 14 | |||
May | 0.71 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.12 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 0.71 | 12 | |||
Dec | 0.16 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BREEZEWAYROOF | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 599.39 | 599.39 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-BREEZEWAYROOF | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 599.39 | 599.39 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 |
Construction | Frame and Divider | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | NFRC Product Type | Assembly U-Factor [Btu/h-ft2-F] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | |||||||
Total or Average | 2126.74 | 0.300 | 0.217 | 0.883 | |||||||||||||||||
North Total or Average | 531.68 | 0.300 | 0.217 | 0.883 | |||||||||||||||||
Non-North Total or Average | 1595.05 | 0.300 | 0.217 | 0.883 |
Frame and Divider | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [Btu/h-ft2-F] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 0.99 | 0.92 | 0.00 | 0.99 | 0.78 | 0.00 | 1.00 | 0.67 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 0.99 | 0.92 | 0.00 | 0.99 | 0.78 | 0.00 | 1.00 | 0.67 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 0.99 | 0.92 | 0.00 | 0.99 | 0.78 | 0.00 | 1.00 | 0.67 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 0.99 | 0.92 | 0.00 | 0.99 | 0.78 | 0.00 | 1.00 | 0.67 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 0.99 | 0.92 | 0.00 | 0.99 | 0.78 | 0.00 | 1.00 | 0.67 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 0.99 | 0.92 | 0.00 | 0.99 | 0.78 | 0.00 | 1.00 | 0.67 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.12 | 0.95 | 0.79 | 1.00 | 0.99 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [Btu/h-ft2] | Space Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.2915 | 43219.92 | 12599.76 | 11336.81 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 51.94 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 227.49 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
Exterior Lighting Total | 934.89 | 4094.83 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Central PlantType | Reference Capacity [Btu/h] | Reference Efficiency [Btuh/Btuh] | Rated Capacity [Btu/h] | Rated Efficiency [Btuh/Btuh] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10160.47 | 7439.65 | 2720.82 | 0.73 | 4.30 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 5405.73 | 3849.38 | 1556.35 | 0.71 | 4.30 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6961.34 | 5097.98 | 1863.36 | 0.73 | 4.30 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9494.46 | 6941.98 | 2552.48 | 0.73 | 4.30 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 4921.82 | 3513.62 | 1408.20 | 0.71 | 4.30 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6369.50 | 4689.90 | 1679.60 | 0.74 | 4.30 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 11609.92 | 8589.13 | 3020.79 | 0.74 | 4.30 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6546.41 | 4750.76 | 1795.65 | 0.73 | 4.30 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8311.52 | 6116.09 | 2195.43 | 0.74 | 4.30 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10923.66 | 8049.89 | 2873.78 | 0.74 | 4.30 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6069.39 | 4382.13 | 1687.26 | 0.72 | 4.30 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7597.79 | 5615.52 | 1982.27 | 0.74 | 4.30 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12946.81 | 9609.30 | 3337.51 | 0.74 | 4.30 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 7908.60 | 5784.38 | 2124.22 | 0.73 | 4.30 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 9590.92 | 6945.40 | 2645.51 | 0.72 | 4.30 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12776.95 | 9478.64 | 3298.31 | 0.74 | 4.30 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 7827.06 | 5721.90 | 2105.16 | 0.73 | 4.30 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 8834.83 | 6449.08 | 2385.75 | 0.73 | 4.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 0.8 | 3.62 | 12.36 | 13.10 | 12.59 | 12.86 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4 | 3.66 | 12.48 | 13.24 | 12.72 | 13.07 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.6 | 3.62 | 12.35 | 13.10 | 12.59 | 12.86 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.8 | 3.62 | 12.36 | 13.11 | 12.60 | 12.88 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.4 | 3.65 | 12.47 | 13.23 | 12.72 | 13.06 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.5 | 3.61 | 12.33 | 13.08 | 12.57 | 12.82 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.9 | 3.61 | 12.31 | 13.06 | 12.55 | 12.79 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.63 | 12.40 | 13.15 | 12.64 | 12.93 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.62 | 12.34 | 13.08 | 12.57 | 12.83 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.9 | 3.61 | 12.33 | 13.07 | 12.56 | 12.82 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.5 | 3.64 | 12.42 | 13.17 | 12.66 | 12.97 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.6 | 3.61 | 12.32 | 13.06 | 12.56 | 12.80 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.0 | 3.60 | 12.30 | 13.04 | 12.53 | 12.76 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.6 | 3.62 | 12.36 | 13.11 | 12.60 | 12.87 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.8 | 3.64 | 12.41 | 13.16 | 12.65 | 12.95 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.0 | 3.60 | 12.30 | 13.04 | 12.53 | 12.77 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.6 | 3.62 | 12.36 | 13.11 | 12.60 | 12.88 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.7 | 3.63 | 12.37 | 13.12 | 12.61 | 12.89 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP2 [Btuh/Btuh] | EER2 [Btu/W-h] | SEER2 User [Btu/W-h] | SEER2 Standard [Btu/W-h] | IEER2 [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.8 | 3.50 | 11.94 | 12.65 | 12.50 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.4 | 3.54 | 12.08 | 12.80 | 12.66 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.6 | 3.50 | 11.94 | 12.65 | 12.50 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.8 | 3.50 | 11.95 | 12.66 | 12.51 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.4 | 3.54 | 12.08 | 12.79 | 12.65 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.5 | 3.49 | 11.92 | 12.62 | 12.48 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.9 | 3.49 | 11.90 | 12.59 | 12.45 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.5 | 3.51 | 11.99 | 12.70 | 12.56 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.7 | 3.49 | 11.92 | 12.62 | 12.48 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.9 | 3.49 | 11.91 | 12.61 | 12.47 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.5 | 3.52 | 12.01 | 12.73 | 12.58 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.6 | 3.49 | 11.90 | 12.60 | 12.46 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.0 | 3.48 | 11.87 | 12.57 | 12.43 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.6 | 3.50 | 11.95 | 12.66 | 12.51 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.8 | 3.52 | 12.00 | 12.71 | 12.57 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.0 | 3.48 | 11.88 | 12.58 | 12.43 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.6 | 3.50 | 11.95 | 12.66 | 12.52 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.7 | 3.51 | 11.96 | 12.67 | 12.53 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
Coil Type | Rated Total Capacity [Btu/h] | Rated Sensible Capacity [Btu/h] | Rated Power[Btu/h] | Rated COP [Btuh/Btuh] | Rated Air Dry-bulb Temperature [F] | Rated Air Wet-bulb Temperature [F] | Rated Water Temperature [F] | Design Day used for Sizing | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF2 [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 6463.17 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 5393.97 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 6465.98 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 6465.80 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 5394.12 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 6463.63 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 6120.61 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 4935.02 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 6124.14 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 6124.62 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 4936.48 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 6123.03 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 7547.89 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 6337.98 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 7551.05 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | 7550.53 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | 6338.81 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | 7549.91 | 1.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3758.62 | 4.05 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 280.12 | 105.66 | 0.38 | 1.00 | 2.87 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 140.14 | 52.86 | 0.38 | 1.00 | 4.50 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 192.00 | 72.42 | 0.38 | 1.00 | 3.62 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 260.74 | 98.35 | 0.38 | 1.00 | 2.99 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 127.99 | 48.28 | 0.38 | 1.00 | 4.81 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 177.61 | 66.99 | 0.38 | 1.00 | 3.82 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 326.70 | 123.23 | 0.38 | 1.00 | 2.64 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 176.80 | 66.69 | 0.38 | 1.00 | 3.83 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 231.38 | 87.28 | 0.38 | 1.00 | 3.22 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 305.29 | 115.15 | 0.38 | 1.00 | 2.74 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 162.24 | 61.20 | 0.38 | 1.00 | 4.06 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 213.25 | 80.44 | 0.38 | 1.00 | 3.39 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 367.50 | 138.62 | 0.38 | 1.00 | 2.48 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 217.38 | 81.99 | 0.38 | 1.00 | 3.34 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 257.52 | 97.13 | 0.38 | 1.00 | 3.02 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 362.21 | 136.62 | 0.38 | 1.00 | 2.50 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 214.85 | 81.04 | 0.38 | 1.00 | 3.37 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 241.54 | 91.11 | 0.38 | 1.00 | 3.13 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electricity Rate [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | End Use Subcategory | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4477.63 | 1.00 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 6457.08 | 6457.08 | 5.38 | 280.117 | 280.117 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 75.00 | 75.00 | 0.00781 | 86.31 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 3230.41 | 3230.41 | 2.69 | 140.141 | 140.141 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 75.00 | 75.00 | 0.00822 | 83.29 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4425.86 | 4425.86 | 3.69 | 192.000 | 192.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 75.00 | 75.00 | 0.00790 | 83.05 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6010.28 | 6010.28 | 5.01 | 260.735 | 260.735 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 75.00 | 75.00 | 0.00784 | 85.83 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2950.41 | 2950.41 | 2.46 | 127.994 | 127.994 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 75.00 | 75.00 | 0.00831 | 82.09 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4094.20 | 4094.20 | 3.41 | 177.611 | 177.611 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 75.00 | 75.00 | 0.00796 | 81.34 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7530.97 | 7530.97 | 6.27 | 326.705 | 326.705 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 75.00 | 75.00 | 0.00777 | 85.83 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4075.42 | 4075.42 | 3.39 | 176.800 | 176.800 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 75.00 | 75.00 | 0.00815 | 82.09 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5333.70 | 5333.70 | 4.44 | 231.383 | 231.383 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 | 75.00 | 75.00 | 0.00781 | 84.25 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7037.31 | 7037.31 | 5.86 | 305.290 | 305.290 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 75.00 | 75.00 | 0.00781 | 85.56 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3739.92 | 3739.92 | 3.12 | 162.245 | 162.245 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 75.00 | 75.00 | 0.00820 | 82.09 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4915.77 | 4915.77 | 4.09 | 213.252 | 213.252 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 75.00 | 75.00 | 0.00786 | 82.65 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 5567.74 | 5567.74 | 4.64 | 241.538 | 241.538 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 75.00 | 75.00 | 0.00796 | 84.50 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 5936.00 | 5936.00 | 4.94 | 257.516 | 257.516 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 75.00 | 75.00 | 0.00779 | 88.34 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8471.35 | 8471.35 | 7.06 | 367.501 | 367.501 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 75.00 | 75.00 | 0.00778 | 85.56 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 4952.48 | 4952.48 | 4.13 | 214.849 | 214.849 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 75.00 | 75.00 | 0.00806 | 82.49 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5010.85 | 5010.85 | 4.17 | 217.381 | 217.381 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 75.00 | 75.00 | 0.00806 | 82.49 | 0.00823 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8349.40 | 8349.40 | 6.95 | 362.211 | 362.211 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 75.00 | 75.00 | 0.00778 | 85.56 | 0.00823 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4094.67 | 4094.67 | 3.41 | 75.951 | 75.951 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | 72.00 | 72.00 | 0.00693 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 3151.18 | 3151.18 | 2.62 | 58.451 | 58.451 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 | 72.00 | 72.00 | 0.00681 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4097.15 | 4097.15 | 3.41 | 75.997 | 75.997 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | 72.00 | 72.00 | 0.00693 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4096.99 | 4096.99 | 3.41 | 75.994 | 75.994 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | 72.00 | 72.00 | 0.00693 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3151.31 | 3151.31 | 2.62 | 58.453 | 58.453 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 | 72.00 | 72.00 | 0.00681 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4095.08 | 4095.08 | 3.41 | 75.958 | 75.958 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | 72.00 | 72.00 | 0.00693 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 3792.37 | 3792.37 | 3.16 | 70.344 | 70.344 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00705 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2746.17 | 2746.17 | 2.29 | 50.939 | 50.939 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00692 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 3795.48 | 3795.48 | 3.16 | 70.402 | 70.402 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00705 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 3795.91 | 3795.91 | 3.16 | 70.410 | 70.410 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00705 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2747.45 | 2747.45 | 2.29 | 50.963 | 50.963 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00692 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 3794.50 | 3794.50 | 3.16 | 70.384 | 70.384 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00705 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 5053.64 | 5053.64 | 4.21 | 93.738 | 93.738 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00704 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 5054.65 | 5054.65 | 4.21 | 93.757 | 93.757 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00704 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 5051.86 | 5051.86 | 4.21 | 93.705 | 93.705 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00704 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 3984.93 | 3984.93 | 3.32 | 73.915 | 73.915 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00694 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 3984.19 | 3984.19 | 3.32 | 73.902 | 73.902 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00694 | 38.84 | 0.00506 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 5054.19 | 5054.19 | 4.21 | 93.748 | 93.748 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00704 | 38.84 | 0.00506 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | Adjusted cooling [ft3/min] | Adjusted heating [ft3/min] | Adjusted main [ft3/min] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 280.12 | 280.12 | 75.95 | 75.95 | 280.1175 | 280.1175 | 280.1175 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 140.14 | 140.14 | 58.45 | 58.45 | 140.1406 | 140.1406 | 140.1406 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 192.00 | 192.00 | 76.00 | 76.00 | 191.9996 | 191.9996 | 191.9996 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 260.74 | 260.74 | 75.99 | 75.99 | 260.7353 | 260.7353 | 260.7353 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 127.99 | 127.99 | 58.45 | 58.45 | 127.9940 | 127.9940 | 127.9940 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 177.61 | 177.61 | 75.96 | 75.96 | 177.6115 | 177.6115 | 177.6115 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 326.70 | 326.70 | 70.34 | 70.34 | 326.7048 | 326.7048 | 326.7048 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 176.80 | 176.80 | 50.94 | 50.94 | 176.7999 | 176.7999 | 176.7999 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 231.38 | 231.38 | 70.40 | 70.40 | 231.3832 | 231.3832 | 231.3832 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 305.29 | 305.29 | 70.41 | 70.41 | 305.2896 | 305.2896 | 305.2896 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 162.24 | 162.24 | 50.96 | 50.96 | 162.2450 | 162.2450 | 162.2450 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 213.25 | 213.25 | 70.38 | 70.38 | 213.2521 | 213.2521 | 213.2521 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 367.50 | 367.50 | 93.71 | 93.71 | 367.5008 | 367.5008 | 367.5008 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 217.38 | 217.38 | 73.90 | 73.90 | 217.3807 | 217.3807 | 217.3807 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 257.52 | 257.52 | 93.76 | 93.76 | 257.5163 | 257.5163 | 257.5163 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 362.21 | 362.21 | 93.75 | 93.75 | 362.2108 | 362.2108 | 362.2108 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 214.85 | 214.85 | 73.92 | 73.92 | 214.8488 | 214.8488 | 214.8488 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 241.54 | 241.54 | 93.74 | 93.74 | 241.5384 | 241.5384 | 241.5384 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 10160.472 | 7439.649 | 280.117469 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 9850.33 | 9302.67 | 280.117469 | 78.01 | 61.19 | 0.00787882 | 53.60 | 51.04 | 0.00750000 | 86.31 | 0.00823169 | 64.54 | 16.0629 | 75.00 | 0.00780683 | 41.5665 | 6449.12 | 0.00 | 10164.71 | 7372.27 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 6463.171 | 6463.171 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | 6463.17 | 6463.17 | -999. | 66.67 | 54.87 | 0.00662617 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00692619 | 40.8506 | 4094.67 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 5405.727 | 3849.381 | 140.140551 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 5378.94 | 4850.31 | 140.140551 | 78.86 | 62.01 | 0.00822152 | 53.60 | 51.04 | 0.00750000 | 83.29 | 0.00822904 | 63.54 | 32.1070 | 75.00 | 0.00796741 | 42.4110 | 3185.99 | 0.00 | 5407.98 | 3817.11 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 5393.971 | 5393.971 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 | 5393.97 | 5393.97 | -999. | 61.35 | 52.00 | 0.00624865 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00681152 | 40.1811 | 3151.18 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 6961.344 | 5097.984 | 191.999599 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 6882.80 | 6409.94 | 191.999599 | 78.08 | 61.36 | 0.00797583 | 53.60 | 51.04 | 0.00750000 | 83.05 | 0.00822883 | 63.45 | 23.4349 | 75.00 | 0.00786912 | 41.8944 | 4351.18 | 0.00 | 6964.25 | 5051.88 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 6465.980 | 6465.980 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | 6465.98 | 6465.98 | -999. | 64.23 | 53.64 | 0.00648874 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00692653 | 40.8526 | 4097.15 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 9494.461 | 6941.982 | 260.735291 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 9235.62 | 8683.90 | 260.735291 | 78.06 | 61.25 | 0.00790955 | 53.60 | 51.04 | 0.00750000 | 85.83 | 0.00823127 | 64.38 | 17.2570 | 75.00 | 0.00783199 | 41.6988 | 5995.46 | 0.00 | 9498.42 | 6878.23 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 6465.800 | 6465.800 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | 6465.80 | 6465.80 | -999. | 66.28 | 54.67 | 0.00660414 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00692651 | 40.8524 | 4096.99 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 4921.818 | 3513.620 | 127.994008 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 4931.58 | 4407.01 | 127.994008 | 78.69 | 62.04 | 0.00828358 | 53.60 | 51.04 | 0.00750000 | 82.09 | 0.00822799 | 63.13 | 35.1540 | 75.00 | 0.00825095 | 43.9004 | 2929.20 | 0.00 | 4923.87 | 3483.89 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 5394.123 | 5394.123 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 | 5394.12 | 5394.12 | -999. | 60.34 | 51.47 | 0.00619525 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00681154 | 40.1813 | 3151.31 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 6369.500 | 4689.899 | 177.611458 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 6353.93 | 5870.64 | 177.611458 | 77.80 | 61.34 | 0.00802594 | 53.60 | 51.04 | 0.00750000 | 81.34 | 0.00822733 | 62.87 | 25.3334 | 75.00 | 0.00793170 | 42.2229 | 4047.88 | 0.00 | 6372.16 | 4646.32 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 6463.628 | 6463.628 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | 6463.63 | 6463.63 | -999. | 63.60 | 53.31 | 0.00645307 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00692625 | 40.8509 | 4095.08 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 11609.917 | 8589.129 | 326.704833 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 11263.00 | 10696.19 | 326.704833 | 77.68 | 61.01 | 0.00783721 | 53.60 | 51.04 | 0.00750000 | 85.83 | 0.00823127 | 64.38 | 13.7724 | 75.00 | 0.00777427 | 41.3953 | 7530.97 | 0.00 | 11614.76 | 8512.01 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 6120.613 | 6120.613 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 6120.61 | 6120.61 | -999. | 67.43 | 55.43 | 0.00677248 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00704625 | 41.5500 | 3792.37 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 6546.412 | 4750.762 | 176.799890 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6526.64 | 5910.63 | 176.799890 | 78.00 | 61.63 | 0.00817035 | 53.60 | 51.04 | 0.00750000 | 82.09 | 0.00822799 | 63.13 | 25.4497 | 75.00 | 0.00788805 | 41.9939 | 3843.76 | 0.00 | 6549.14 | 4708.86 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 4935.023 | 4935.023 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 4935.02 | 4935.02 | -999. | 63.56 | 53.28 | 0.00644584 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00691947 | 40.8102 | 2746.17 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 8311.521 | 6116.087 | 231.383157 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 | 8149.80 | 7681.53 | 231.383157 | 77.99 | 61.20 | 0.00789204 | 53.60 | 51.04 | 0.00750000 | 84.25 | 0.00822988 | 63.86 | 19.4461 | 75.00 | 0.00780116 | 41.5370 | 5312.77 | 0.00 | 8314.99 | 6060.73 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 6124.139 | 6124.139 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 6124.14 | 6124.14 | -999. | 65.55 | 54.48 | 0.00666004 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00704668 | 41.5525 | 3795.48 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 10923.663 | 8049.886 | 305.289563 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 10622.19 | 10031.73 | 305.289563 | 77.75 | 61.09 | 0.00787539 | 53.60 | 51.04 | 0.00750000 | 85.56 | 0.00823104 | 64.30 | 14.7385 | 75.00 | 0.00781391 | 41.6038 | 7037.31 | 0.00 | 10928.22 | 7975.69 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 6124.620 | 6124.620 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 6124.62 | 6124.62 | -999. | 67.11 | 55.27 | 0.00675369 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00704674 | 41.5529 | 3795.91 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 6069.395 | 4382.131 | 162.244981 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 6059.03 | 5463.32 | 162.244981 | 78.16 | 61.74 | 0.00820519 | 53.60 | 51.04 | 0.00750000 | 82.09 | 0.00822799 | 63.13 | 27.7327 | 75.00 | 0.00817538 | 43.5037 | 3708.98 | 0.00 | 6071.93 | 4343.66 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 4936.481 | 4936.481 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 4936.48 | 4936.48 | -999. | 62.80 | 52.89 | 0.00640353 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00691971 | 40.8116 | 2747.45 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 7597.789 | 5615.518 | 213.252057 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 7514.68 | 7034.86 | 213.252057 | 77.81 | 61.21 | 0.00793586 | 53.60 | 51.04 | 0.00750000 | 82.65 | 0.00822848 | 63.32 | 21.0994 | 75.00 | 0.00784132 | 41.7477 | 4894.40 | 0.00 | 7600.96 | 5564.60 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 6123.030 | 6123.030 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 6123.03 | 6123.03 | -999. | 65.00 | 54.20 | 0.00662706 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00704654 | 41.5518 | 3794.50 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 12946.806 | 9609.298 | 367.500776 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 12568.36 | 11934.02 | 367.500776 | 77.49 | 60.94 | 0.00783592 | 53.60 | 51.04 | 0.00750000 | 85.56 | 0.00823104 | 64.30 | 12.2435 | 75.00 | 0.00775931 | 41.3167 | 8465.48 | 0.00 | 12952.21 | 9519.99 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 7547.889 | 7547.889 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 7547.89 | 7547.89 | -999. | 67.94 | 55.67 | 0.00679709 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00703966 | 41.5126 | 5051.86 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 7908.599 | 5784.383 | 217.380697 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 7848.60 | 7180.58 | 217.380697 | 77.74 | 61.42 | 0.00809319 | 53.60 | 51.04 | 0.00750000 | 82.49 | 0.00822834 | 63.26 | 20.6987 | 75.00 | 0.00800925 | 42.6309 | 4968.46 | 0.00 | 7911.90 | 5731.43 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 6337.976 | 6337.976 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 6337.98 | 6337.98 | -999. | 65.13 | 54.11 | 0.00654996 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00693927 | 40.9267 | 3984.19 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 9590.919 | 6945.405 | 257.516323 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 9210.64 | 8725.59 | 257.516323 | 78.52 | 61.35 | 0.00786397 | 53.60 | 51.04 | 0.00750000 | 88.34 | 0.00823349 | 65.21 | 17.4727 | 75.00 | 0.00778573 | 41.4560 | 5936.00 | 0.00 | 9594.92 | 6884.71 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 7551.050 | 7551.050 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 7551.05 | 7551.05 | -999. | 66.20 | 54.80 | 0.00669374 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00703997 | 41.5144 | 5054.65 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 12776.951 | 9478.636 | 362.210776 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 12405.17 | 11772.60 | 362.210776 | 77.51 | 60.95 | 0.00783980 | 53.60 | 51.04 | 0.00750000 | 85.56 | 0.00823104 | 64.30 | 12.4223 | 75.00 | 0.00778431 | 41.4482 | 8349.40 | 0.00 | 12782.28 | 9390.14 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 7550.533 | 7550.533 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 7550.53 | 7550.53 | -999. | 67.88 | 55.64 | 0.00679377 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00703992 | 41.5141 | 5054.19 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 7827.062 | 5721.897 | 214.848805 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 7768.95 | 7103.02 | 214.848805 | 77.76 | 61.44 | 0.00809816 | 53.60 | 51.04 | 0.00750000 | 82.49 | 0.00822834 | 63.26 | 20.9426 | 75.00 | 0.00802957 | 42.7377 | 4928.20 | 0.00 | 7830.33 | 5669.27 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 6338.809 | 6338.809 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 6338.81 | 6338.81 | -999. | 65.05 | 54.07 | 0.00654546 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00693938 | 40.9273 | 3984.93 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 8834.832 | 6449.079 | 241.538390 | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 8668.19 | 8032.11 | 241.538390 | 77.96 | 61.37 | 0.00800874 | 53.60 | 51.04 | 0.00750000 | 84.50 | 0.00823009 | 63.94 | 18.6285 | 75.00 | 0.00780682 | 41.5663 | 5516.26 | 0.00 | 8838.52 | 6392.57 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 7549.906 | 7549.906 | -999. | -999. | -999.00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 7549.91 | 7549.91 | -999. | 65.82 | 54.61 | 0.00667075 | 122.00 | 74.75 | 0.00800000 | 38.84 | 0.00505843 | 38.84 | -999.000 | 72.00 | 0.00703986 | 41.5137 | 5053.64 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4520.192 | 4434.308 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4523.976 | 4438.020 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4519.278 | 4433.411 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4520.002 | 4434.122 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4523.799 | 4437.846 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4519.115 | 4433.252 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4562.756 | 4476.064 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4570.730 | 4483.886 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4562.574 | 4475.885 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4562.719 | 4476.027 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4570.644 | 4483.802 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4562.536 | 4475.848 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4520.462 | 4434.574 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4524.758 | 4438.788 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4519.455 | 4433.585 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4520.415 | 4434.527 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4524.723 | 4438.753 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4519.290 | 4433.424 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3758.62 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [Btu/lbm-R] | Dry Air Heat Capacity [Btu/lbm-R] | Standard Air Density Adjusted for Elevation [lb/ft3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [ft3/min] | Supply Fan Maximum Air Mass Flow Rate [lb/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [Btu/lbm-R] | Plant Fluid Density [lb/ft3] | Plant Maximum Fluid Mass Flow Rate [lb/s] | Plant Design Fluid Return Temperature [F] | Plant Design Fluid Supply Temperature [F] | Plant Design Fluid Temperature Difference [deltaF] | Plant Design Capacity [Btu/h] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] | Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] | Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] | Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [F] | System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | Coil Air Mass Flow Rate at Rating Conditions [lb/s] | Coil Entering Air Drybulb at Rating Conditions [F] | Coil Entering Air Wetbulb at Rating Conditions [F] | Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] | Coil Leaving Air Drybulb at Rating Conditions [F] | Coil Leaving Air Wetbulb at Rating Conditions [F] | Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10160.472 | 7439.649 | 280.117469 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 280.117469 | 0.34446745 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | Sensible | 9850.33 | 9302.67 | 0.9695 | 0.34446745 | 280.117469 | 78.01 | 61.19 | 0.00787882 | 10.9 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 360.506 | 9489.83 | 86.31 | 0.00823169 | 64.54 | 44.99498340 | 16.0629 | 75.00 | 0.00781129 | 75.00 | 0.00780683 | 41.5665 | 6449.12 | 0.00 | 10164.71 | 7372.27 | 0.33086359 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.63 | 54.59 | 0.00904656 | 8.5 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6463.171 | 6463.171 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 280.117469 | 0.34446745 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | Sensible | 6463.17 | 6463.17 | 1.0000 | -0.260274E+04 | -999. | 66.67 | 54.87 | 0.00662617 | 8.6 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6463.17 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00692619 | 72.00 | 0.00692619 | 40.8506 | 4094.67 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 5405.727 | 3849.381 | 140.140551 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2437 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 140.140551 | 0.17233434 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | Sensible | 5378.94 | 4850.31 | 0.9950 | 0.17233434 | 140.140551 | 78.86 | 62.01 | 0.00822152 | 11.3 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 180.358 | 5198.58 | 83.29 | 0.00822904 | 63.54 | 44.99498340 | 32.1070 | 75.00 | 0.00821797 | 75.00 | 0.00796741 | 42.4110 | 3185.99 | 0.00 | 5407.98 | 3817.11 | 0.16552844 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.73 | 53.69 | 0.00874990 | 8.2 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 5393.971 | 5393.971 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 140.140551 | 0.17233434 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 | Sensible | 5393.97 | 5393.97 | 1.0000 | -0.260274E+04 | -999. | 61.35 | 52.00 | 0.00624865 | 7.7 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5393.97 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00681152 | 72.00 | 0.00681152 | 40.1811 | 3151.18 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 6961.344 | 5097.984 | 191.999599 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 191.999599 | 0.23610671 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 6882.80 | 6409.94 | 0.9887 | 0.23610671 | 191.999599 | 78.08 | 61.36 | 0.00797583 | 11.0 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 247.100 | 6635.70 | 83.05 | 0.00822883 | 63.45 | 44.99498340 | 23.4349 | 75.00 | 0.00789839 | 75.00 | 0.00786912 | 41.8944 | 4351.18 | 0.00 | 6964.25 | 5051.88 | 0.22678228 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.64 | 54.60 | 0.00904840 | 8.5 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6465.980 | 6465.980 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 191.999599 | 0.23610671 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | Sensible | 6465.98 | 6465.98 | 1.0000 | -0.260274E+04 | -999. | 64.23 | 53.64 | 0.00648874 | 8.2 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6465.98 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00692653 | 72.00 | 0.00692653 | 40.8526 | 4097.15 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 9494.461 | 6941.982 | 260.735291 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 260.735291 | 0.32063271 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | Sensible | 9235.62 | 8683.90 | 0.9727 | 0.32063271 | 260.735291 | 78.06 | 61.25 | 0.00790955 | 11.0 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 335.561 | 8900.06 | 85.83 | 0.00823127 | 64.38 | 44.99498340 | 17.2570 | 75.00 | 0.00784246 | 75.00 | 0.00783199 | 41.6988 | 5995.46 | 0.00 | 9498.42 | 6878.23 | 0.30797014 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.57 | 54.53 | 0.00902931 | 8.5 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6465.800 | 6465.800 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 260.735291 | 0.32063271 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | Sensible | 6465.80 | 6465.80 | 1.0000 | -0.260274E+04 | -999. | 66.28 | 54.67 | 0.00660414 | 8.6 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6465.80 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00692651 | 72.00 | 0.00692651 | 40.8524 | 4096.99 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 4921.818 | 3513.620 | 127.994008 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2437 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 127.994008 | 0.15739743 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 4931.58 | 4407.01 | 1.0020 | 0.15739743 | 127.994008 | 78.69 | 62.04 | 0.00828358 | 11.3 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 164.726 | 4766.86 | 82.09 | 0.00822799 | 63.13 | 44.99498340 | 35.1540 | 75.00 | 0.00831371 | 75.00 | 0.00825095 | 43.9004 | 2929.20 | 0.00 | 4923.87 | 3483.89 | 0.15118142 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.75 | 53.74 | 0.00877169 | 8.2 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 5394.123 | 5394.123 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 127.994008 | 0.15739743 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:40:00 | Sensible | 5394.12 | 5394.12 | 1.0000 | -0.260274E+04 | -999. | 60.34 | 51.47 | 0.00619525 | 7.5 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5394.12 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00681154 | 72.00 | 0.00681154 | 40.1813 | 3151.31 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 6369.500 | 4689.899 | 177.611458 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 177.611458 | 0.21841325 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | Sensible | 6353.93 | 5870.64 | 0.9976 | 0.21841325 | 177.611458 | 77.80 | 61.34 | 0.00802594 | 11.0 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 228.583 | 6125.35 | 81.34 | 0.00822733 | 62.87 | 44.99498340 | 25.3334 | 75.00 | 0.00795761 | 75.00 | 0.00793170 | 42.2229 | 4047.88 | 0.00 | 6372.16 | 4646.32 | 0.20978758 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.79 | 54.75 | 0.00910059 | 8.5 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6463.628 | 6463.628 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 177.611458 | 0.21841325 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | Sensible | 6463.63 | 6463.63 | 1.0000 | -0.260274E+04 | -999. | 63.60 | 53.31 | 0.00645307 | 8.1 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6463.63 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00692625 | 72.00 | 0.00692625 | 40.8509 | 4095.08 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 11609.917 | 8589.129 | 326.704833 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 326.704833 | 0.40175710 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | Sensible | 11263.00 | 10696.19 | 0.9701 | 0.40175710 | 326.704833 | 77.68 | 61.01 | 0.00783721 | 10.9 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 420.463 | 10842.54 | 85.83 | 0.00823127 | 64.38 | 44.99498340 | 13.7724 | 75.00 | 0.00777427 | 75.00 | 0.00777427 | 41.3953 | 7530.97 | 0.00 | 11614.76 | 8512.01 | 0.38589073 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.89 | 54.87 | 0.00914773 | 8.6 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6120.613 | 6120.613 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 326.704833 | 0.40175710 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 6120.61 | 6120.61 | 1.0000 | -0.260274E+04 | -999. | 67.43 | 55.43 | 0.00677248 | 8.8 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6120.61 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00704625 | 72.00 | 0.00704625 | 41.5500 | 3792.37 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 6546.412 | 4750.762 | 176.799890 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 176.799890 | 0.21741524 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6526.64 | 5910.63 | 0.9970 | 0.21741524 | 176.799890 | 78.00 | 61.63 | 0.00817035 | 11.1 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 227.538 | 6299.10 | 82.09 | 0.00822799 | 63.13 | 44.99498340 | 25.4497 | 75.00 | 0.00815067 | 75.00 | 0.00788805 | 41.9939 | 3843.76 | 0.00 | 6549.14 | 4708.86 | 0.20882899 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.33 | 54.30 | 0.00895218 | 8.4 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 4935.023 | 4935.023 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 176.799890 | 0.21741524 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 4935.02 | 4935.02 | 1.0000 | -0.260274E+04 | -999. | 63.56 | 53.28 | 0.00644584 | 8.1 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 4935.02 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00691947 | 72.00 | 0.00691947 | 40.8102 | 2746.17 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 8311.521 | 6116.087 | 231.383157 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 231.383157 | 0.28453765 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 | Sensible | 8149.80 | 7681.53 | 0.9805 | 0.28453765 | 231.383157 | 77.99 | 61.20 | 0.00789204 | 10.9 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 297.786 | 7852.02 | 84.25 | 0.00822988 | 63.86 | 44.99498340 | 19.4461 | 75.00 | 0.00781048 | 75.00 | 0.00780116 | 41.5370 | 5312.77 | 0.00 | 8314.99 | 6060.73 | 0.27330057 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.76 | 54.73 | 0.00909509 | 8.5 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6124.139 | 6124.139 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 231.383157 | 0.28453765 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 6124.14 | 6124.14 | 1.0000 | -0.260274E+04 | -999. | 65.55 | 54.48 | 0.00666004 | 8.5 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6124.14 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00704668 | 72.00 | 0.00704668 | 41.5525 | 3795.48 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10923.663 | 8049.886 | 305.289563 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 305.289563 | 0.37542221 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | Sensible | 10622.19 | 10031.73 | 0.9724 | 0.37542221 | 305.289563 | 77.75 | 61.09 | 0.00787539 | 10.9 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 392.902 | 10229.29 | 85.56 | 0.00823104 | 64.30 | 44.99498340 | 14.7385 | 75.00 | 0.00781391 | 75.00 | 0.00781391 | 41.6038 | 7037.31 | 0.00 | 10928.22 | 7975.69 | 0.36059587 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.82 | 54.78 | 0.00911038 | 8.5 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6124.620 | 6124.620 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 305.289563 | 0.37542221 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 6124.62 | 6124.62 | 1.0000 | -0.260274E+04 | -999. | 67.11 | 55.27 | 0.00675369 | 8.8 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6124.62 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00704674 | 72.00 | 0.00704674 | 41.5529 | 3795.91 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 6069.395 | 4382.131 | 162.244981 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 162.244981 | 0.19951671 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | Sensible | 6059.03 | 5463.32 | 0.9983 | 0.19951671 | 162.244981 | 78.16 | 61.74 | 0.00820519 | 11.1 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 208.806 | 5850.22 | 82.09 | 0.00822799 | 63.13 | 44.99498340 | 27.7327 | 75.00 | 0.00819644 | 75.00 | 0.00817538 | 43.5037 | 3708.98 | 0.00 | 6071.93 | 4343.66 | 0.19163731 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.19 | 54.15 | 0.00889999 | 8.3 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 4936.481 | 4936.481 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 162.244981 | 0.19951671 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 4936.48 | 4936.48 | 1.0000 | -0.260274E+04 | -999. | 62.80 | 52.89 | 0.00640353 | 8.0 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 4936.48 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00691971 | 72.00 | 0.00691971 | 40.8116 | 2747.45 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 7597.789 | 5615.518 | 213.252057 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 213.252057 | 0.26224138 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | Sensible | 7514.68 | 7034.86 | 0.9891 | 0.26224138 | 213.252057 | 77.81 | 61.21 | 0.00793586 | 10.9 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 274.451 | 7240.23 | 82.65 | 0.00822848 | 63.32 | 44.99498340 | 21.0994 | 75.00 | 0.00785761 | 75.00 | 0.00784132 | 41.7477 | 4894.40 | 0.00 | 7600.96 | 5564.60 | 0.25188483 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.86 | 54.84 | 0.00913659 | 8.6 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6123.030 | 6123.030 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 213.252057 | 0.26224138 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 6123.03 | 6123.03 | 1.0000 | -0.260274E+04 | -999. | 65.00 | 54.20 | 0.00662706 | 8.4 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6123.03 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00704654 | 72.00 | 0.00704654 | 41.5518 | 3794.50 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 12946.806 | 9609.298 | 367.500776 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 367.500776 | 0.45192489 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | Sensible | 12568.36 | 11934.02 | 0.9708 | 0.45192489 | 367.500776 | 77.49 | 60.94 | 0.00783592 | 10.8 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 472.967 | 12095.39 | 85.56 | 0.00823104 | 64.30 | 44.99498340 | 12.2435 | 75.00 | 0.00778080 | 75.00 | 0.00775931 | 41.3167 | 8465.48 | 0.00 | 12952.21 | 9519.99 | 0.43407727 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.04 | 54.99 | 0.00918157 | 8.6 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 7547.889 | 7547.889 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 367.500776 | 0.45192489 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 7547.89 | 7547.89 | 1.0000 | -0.260274E+04 | -999. | 67.94 | 55.67 | 0.00679709 | 8.9 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 7547.89 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00703966 | 72.00 | 0.00703966 | 41.5126 | 5051.86 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 7908.599 | 5784.383 | 217.380697 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 217.380697 | 0.26731848 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 7848.60 | 7180.58 | 0.9924 | 0.26731848 | 217.380697 | 77.74 | 61.42 | 0.00809319 | 11.0 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 279.765 | 7568.83 | 82.49 | 0.00822834 | 63.26 | 44.99498340 | 20.6987 | 75.00 | 0.00805791 | 75.00 | 0.00800925 | 42.6309 | 4968.46 | 0.00 | 7911.90 | 5731.43 | 0.25676142 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.59 | 54.55 | 0.00903330 | 8.5 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6337.976 | 6337.976 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 217.380697 | 0.26731848 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 6337.98 | 6337.98 | 1.0000 | -0.260274E+04 | -999. | 65.13 | 54.11 | 0.00654996 | 8.4 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6337.98 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00693927 | 72.00 | 0.00693927 | 40.9267 | 3984.19 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 9590.919 | 6945.405 | 257.516323 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 257.516323 | 0.31667426 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 9210.64 | 8725.59 | 0.9604 | 0.31667426 | 257.516323 | 78.52 | 61.35 | 0.00786397 | 11.0 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 331.419 | 8879.22 | 88.34 | 0.00823349 | 65.21 | 44.99498340 | 17.4727 | 75.00 | 0.00778573 | 75.00 | 0.00778573 | 41.4560 | 5936.00 | 0.00 | 9594.92 | 6884.71 | 0.30416802 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.23 | 54.21 | 0.00892740 | 8.3 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 7551.050 | 7551.050 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 257.516323 | 0.31667426 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 7551.05 | 7551.05 | 1.0000 | -0.260274E+04 | -999. | 66.20 | 54.80 | 0.00669374 | 8.6 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 7551.05 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00703997 | 72.00 | 0.00703997 | 41.5144 | 5054.65 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 12776.951 | 9478.636 | 362.210776 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2435 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 362.210776 | 0.44541965 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | Sensible | 12405.17 | 11772.60 | 0.9709 | 0.44541965 | 362.210776 | 77.51 | 60.95 | 0.00783980 | 10.8 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 466.159 | 11939.01 | 85.56 | 0.00823104 | 64.30 | 44.99498340 | 12.4223 | 75.00 | 0.00778431 | 75.00 | 0.00778431 | 41.4482 | 8349.40 | 0.00 | 12782.28 | 9390.14 | 0.42782894 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.02 | 54.97 | 0.00917605 | 8.6 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 7550.533 | 7550.533 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 362.210776 | 0.44541965 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 7550.53 | 7550.53 | 1.0000 | -0.260274E+04 | -999. | 67.88 | 55.64 | 0.00679377 | 8.9 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 7550.53 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00703992 | 72.00 | 0.00703992 | 41.5141 | 5054.19 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 7827.062 | 5721.897 | 214.848805 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 214.848805 | 0.26420495 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 7768.95 | 7103.02 | 0.9926 | 0.26420495 | 214.848805 | 77.76 | 61.44 | 0.00809816 | 11.0 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 276.506 | 7492.44 | 82.49 | 0.00822834 | 63.26 | 44.99498340 | 20.9426 | 75.00 | 0.00806368 | 75.00 | 0.00802957 | 42.7377 | 4928.20 | 0.00 | 7830.33 | 5669.27 | 0.25377085 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.57 | 54.53 | 0.00902732 | 8.5 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6338.809 | 6338.809 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 214.848805 | 0.26420495 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 6338.81 | 6338.81 | 1.0000 | -0.260274E+04 | -999. | 65.05 | 54.07 | 0.00654546 | 8.4 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6338.81 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00693938 | 72.00 | 0.00693938 | 40.9273 | 3984.93 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 8834.832 | 6449.079 | 241.538390 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 241.538390 | 0.29702580 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | Sensible | 8668.19 | 8032.11 | 0.9811 | 0.29702580 | 241.538390 | 77.96 | 61.37 | 0.00800874 | 11.0 | 53.60 | 51.04 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 310.855 | 8357.34 | 84.50 | 0.00823009 | 63.94 | 44.99498340 | 18.6285 | 75.00 | 0.00795806 | 75.00 | 0.00780682 | 41.5663 | 5516.26 | 0.00 | 8838.52 | 6392.57 | 0.28529552 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.49 | 54.47 | 0.00901274 | 8.4 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 7549.906 | 7549.906 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0738 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 241.538390 | 0.29702580 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 7549.91 | 7549.91 | 1.0000 | -0.260274E+04 | -999. | 65.82 | 54.61 | 0.00667075 | 8.5 | 122.00 | 74.75 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 7549.91 | 38.84 | 0.00505843 | 38.84 | 44.99498340 | -999.000 | 72.00 | 0.00703986 | 72.00 | 0.00703986 | 41.5137 | 5053.64 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4520.192 | 4434.308 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4523.976 | 4438.020 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4519.278 | 4433.411 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4520.002 | 4434.122 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4523.799 | 4437.846 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4519.115 | 4433.252 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4562.756 | 4476.064 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4570.730 | 4483.886 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4562.574 | 4475.885 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4562.719 | 4476.027 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4570.644 | 4483.802 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4562.536 | 4475.848 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4520.462 | 4434.574 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4524.758 | 4438.788 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4519.455 | 4433.585 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4520.415 | 4434.527 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4524.723 | 4438.753 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4519.290 | 4433.424 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0738 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.19676900 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3758.62 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3758.62 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. |
Report: System Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1589.83 | 5968.33 | 362.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1120.00 | 6444.83 | 353.17 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1388.00 | 6046.67 | 351.67 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1368.50 | 6606.17 | 366.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1033.17 | 7052.83 | 391.33 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1261.33 | 6701.50 | 373.67 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2060.00 | 4517.67 | 117.67 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1355.50 | 4464.67 | 27.33 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1837.33 | 4415.00 | 134.67 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1679.00 | 5362.67 | 119.33 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1169.17 | 5588.67 | 21.17 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1532.67 | 5436.33 | 145.67 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1822.00 | 5447.17 | 174.83 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 2036.33 | 4757.00 | 169.17 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 2213.67 | 4855.17 | 180.83 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1509.17 | 5610.67 | 117.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1668.17 | 4831.50 | 119.33 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1929.33 | 5487.00 | 185.83 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 2866.00 | 8037.00 | 519.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 10.17 | 0.00 | 10.17 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 32.00 | 0.00 | 32.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9.17 | 1.17 | 9.17 | 1.17 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 17.33 | 0.00 | 17.33 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 56.17 | 0.00 | 56.17 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 16.83 | 0.00 | 16.83 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 6.33 | 0.00 | 6.33 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 26.00 | 0.00 | 26.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8.33 | 0.00 | 8.33 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 11.33 | 0.00 | 11.33 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 49.00 | 0.00 | 49.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 13.83 | 0.00 | 13.83 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 4.83 | 0.00 | 4.83 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 3.33 | 0.00 | 3.33 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 4.50 | 0.00 | 4.50 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 13.67 | 0.00 | 13.67 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 7.67 | 0.00 | 7.67 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 3.83 | 0.00 | 3.83 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 213.67 | 1.17 | 213.67 | 1.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.087 | 0.000 | 0.270 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.077 | 0.000 | 0.270 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.087 | 0.000 | 0.270 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.087 | 0.000 | 0.270 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.076 | 0.000 | 0.270 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.087 | 0.000 | 0.270 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.038 | 0.000 | 0.271 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.028 | 0.000 | 0.271 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.039 | 0.000 | 0.271 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.038 | 0.000 | 0.271 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.028 | 0.000 | 0.271 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.038 | 0.000 | 0.271 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.087 | 0.000 | 0.270 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.088 | 0.000 | 0.271 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.088 | 0.000 | 0.271 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.077 | 0.000 | 0.271 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.077 | 0.000 | 0.271 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.087 | 0.000 | 0.270 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Zone Area [ft2] | Design Zone Outdoor Airflow - Voz [ft3/min] | Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
Total Facility | 24.79 | 36.00 | 183739.38 | 21609.96 | 0.0000 | 0.000 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Infiltration [ft3] | Total Ventilation and Infiltration [ft3] | Dynamic Target Ventilation - Voz-dyn [ft3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 23860822.00 | 23860822.00 | 7677433.08 | 31538255.08 | 23785081.69 | 2170.00 | 3433.17 | 3204.83 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 23860822.00 | 23860822.00 | 6763926.67 | 30624748.67 | 23785081.69 | 2170.00 | 3433.17 | 3204.83 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 23860822.00 | 23860822.00 | 7681644.48 | 31542466.48 | 23785081.69 | 2170.00 | 3433.17 | 3204.83 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 23860822.00 | 23860822.00 | 7646279.75 | 31507101.75 | 23785081.69 | 2170.00 | 3433.17 | 3204.83 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 23860822.00 | 23860822.00 | 6724540.96 | 30585362.96 | 23785081.69 | 2170.00 | 3433.17 | 3204.83 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 23860822.00 | 23860822.00 | 7643112.99 | 31503935.00 | 23785081.69 | 2170.00 | 3433.17 | 3204.83 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 23862211.51 | 23862211.51 | 3394287.96 | 27256499.48 | 23785081.69 | 2161.00 | 3432.17 | 3214.83 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 23862211.51 | 23862211.51 | 2474003.06 | 26336214.58 | 23785081.69 | 2161.00 | 3432.17 | 3214.83 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 23862211.51 | 23862211.51 | 3397199.61 | 27259411.12 | 23785081.69 | 2161.00 | 3432.17 | 3214.83 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 23862211.51 | 23862211.51 | 3379173.50 | 27241385.02 | 23785081.69 | 2161.00 | 3432.17 | 3214.83 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 23862211.51 | 23862211.51 | 2457100.58 | 26319312.09 | 23785081.69 | 2161.00 | 3432.17 | 3214.83 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 23862211.51 | 23862211.51 | 3379070.62 | 27241282.14 | 23785081.69 | 2161.00 | 3432.17 | 3214.83 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 23863602.49 | 23863602.49 | 7710080.77 | 31573683.26 | 23785081.69 | 2153.50 | 3431.67 | 3222.83 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 23863602.49 | 23863602.49 | 7742269.79 | 31605872.27 | 23785081.69 | 2153.50 | 3431.67 | 3222.83 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 23863602.49 | 23863602.49 | 7733905.09 | 31597507.58 | 23785081.69 | 2153.50 | 3431.67 | 3222.83 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 23863602.49 | 23863602.49 | 6788082.91 | 30651685.40 | 23785081.69 | 2153.50 | 3431.67 | 3222.83 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 23863602.49 | 23863602.49 | 6823074.81 | 30686677.30 | 23785081.69 | 2153.50 | 3431.67 | 3222.83 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 23863602.49 | 23863602.49 | 7708247.43 | 31571849.92 | 23785081.69 | 2153.50 | 3431.67 | 3222.83 | 0.00 |
Total Facility | 0.00 | 0.429520E+09 | 0.429520E+09 | 0.107123E+09 | 0.536643E+09 | 0.428131E+09 | 2170.00 | 3449.67 | 3222.83 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Infiltration [ft3/min] | Total Ventilation and Infiltration [ft3/min] | Dynamic Target Ventilation - Voz-dyn [ft3/min] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1383 | 45.1383 | 14.5236 | 59.6619 | 44.9950 | 2170.00 | 3433.17 | 3204.83 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1383 | 45.1383 | 12.7955 | 57.9338 | 44.9950 | 2170.00 | 3433.17 | 3204.83 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1383 | 45.1383 | 14.5316 | 59.6699 | 44.9950 | 2170.00 | 3433.17 | 3204.83 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1383 | 45.1383 | 14.4647 | 59.6030 | 44.9950 | 2170.00 | 3433.17 | 3204.83 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1383 | 45.1383 | 12.7210 | 57.8593 | 44.9950 | 2170.00 | 3433.17 | 3204.83 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1383 | 45.1383 | 14.4587 | 59.5970 | 44.9950 | 2170.00 | 3433.17 | 3204.83 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1409 | 45.1409 | 6.4211 | 51.5620 | 44.9950 | 2161.00 | 3432.17 | 3214.83 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1409 | 45.1409 | 4.6801 | 49.8210 | 44.9950 | 2161.00 | 3432.17 | 3214.83 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1409 | 45.1409 | 6.4266 | 51.5675 | 44.9950 | 2161.00 | 3432.17 | 3214.83 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1409 | 45.1409 | 6.3925 | 51.5334 | 44.9950 | 2161.00 | 3432.17 | 3214.83 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1409 | 45.1409 | 4.6482 | 49.7891 | 44.9950 | 2161.00 | 3432.17 | 3214.83 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1409 | 45.1409 | 6.3923 | 51.5332 | 44.9950 | 2161.00 | 3432.17 | 3214.83 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 45.1435 | 45.1435 | 14.5854 | 59.7289 | 44.9950 | 2153.50 | 3431.67 | 3222.83 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 45.1435 | 45.1435 | 14.6463 | 59.7898 | 44.9950 | 2153.50 | 3431.67 | 3222.83 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 45.1435 | 45.1435 | 14.6305 | 59.7740 | 44.9950 | 2153.50 | 3431.67 | 3222.83 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 45.1435 | 45.1435 | 12.8412 | 57.9848 | 44.9950 | 2153.50 | 3431.67 | 3222.83 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 45.1435 | 45.1435 | 12.9074 | 58.0509 | 44.9950 | 2153.50 | 3431.67 | 3222.83 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 45.1435 | 45.1435 | 14.5819 | 59.7255 | 44.9950 | 2153.50 | 3431.67 | 3222.83 |
Total Facility | 0.0000 | 812.5361 | 812.5361 | 202.6488 | 1015.1848 | 809.9097 | 2170.00 | 3449.67 | 3222.83 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 23860822.00 | 23860822.00 | 23785081.69 | 2170.00 | 3433.17 | 3204.83 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 23860822.00 | 23860822.00 | 23785081.69 | 2170.00 | 3433.17 | 3204.83 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 23860822.00 | 23860822.00 | 23785081.69 | 2170.00 | 3433.17 | 3204.83 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 23860822.00 | 23860822.00 | 23785081.69 | 2170.00 | 3433.17 | 3204.83 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 23860822.00 | 23860822.00 | 23785081.69 | 2170.00 | 3433.17 | 3204.83 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 23860822.00 | 23860822.00 | 23785081.69 | 2170.00 | 3433.17 | 3204.83 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 23862211.51 | 23862211.51 | 23785081.69 | 2161.00 | 3432.17 | 3214.83 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 23862211.51 | 23862211.51 | 23785081.69 | 2161.00 | 3432.17 | 3214.83 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 23862211.51 | 23862211.51 | 23785081.69 | 2161.00 | 3432.17 | 3214.83 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 23862211.51 | 23862211.51 | 23785081.69 | 2161.00 | 3432.17 | 3214.83 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 23862211.51 | 23862211.51 | 23785081.69 | 2161.00 | 3432.17 | 3214.83 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 23862211.51 | 23862211.51 | 23785081.69 | 2161.00 | 3432.17 | 3214.83 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 23863602.49 | 23863602.49 | 23785081.69 | 2153.50 | 3431.67 | 3222.83 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 23863602.49 | 23863602.49 | 23785081.69 | 2153.50 | 3431.67 | 3222.83 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 23863602.49 | 23863602.49 | 23785081.69 | 2153.50 | 3431.67 | 3222.83 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 23863602.49 | 23863602.49 | 23785081.69 | 2153.50 | 3431.67 | 3222.83 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 23863602.49 | 23863602.49 | 23785081.69 | 2153.50 | 3431.67 | 3222.83 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 23863602.49 | 23863602.49 | 23785081.69 | 2153.50 | 3431.67 | 3222.83 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1383 | 45.1383 | 44.9950 | 2170.00 | 3433.17 | 3204.83 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1383 | 45.1383 | 44.9950 | 2170.00 | 3433.17 | 3204.83 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1383 | 45.1383 | 44.9950 | 2170.00 | 3433.17 | 3204.83 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1383 | 45.1383 | 44.9950 | 2170.00 | 3433.17 | 3204.83 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1383 | 45.1383 | 44.9950 | 2170.00 | 3433.17 | 3204.83 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1383 | 45.1383 | 44.9950 | 2170.00 | 3433.17 | 3204.83 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1409 | 45.1409 | 44.9950 | 2161.00 | 3432.17 | 3214.83 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1409 | 45.1409 | 44.9950 | 2161.00 | 3432.17 | 3214.83 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1409 | 45.1409 | 44.9950 | 2161.00 | 3432.17 | 3214.83 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1409 | 45.1409 | 44.9950 | 2161.00 | 3432.17 | 3214.83 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1409 | 45.1409 | 44.9950 | 2161.00 | 3432.17 | 3214.83 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1409 | 45.1409 | 44.9950 | 2161.00 | 3432.17 | 3214.83 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 45.1435 | 45.1435 | 44.9950 | 2153.50 | 3431.67 | 3222.83 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 45.1435 | 45.1435 | 44.9950 | 2153.50 | 3431.67 | 3222.83 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 45.1435 | 45.1435 | 44.9950 | 2153.50 | 3431.67 | 3222.83 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 45.1435 | 45.1435 | 44.9950 | 2153.50 | 3431.67 | 3222.83 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 45.1435 | 45.1435 | 44.9950 | 2153.50 | 3431.67 | 3222.83 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 45.1435 | 45.1435 | 44.9950 | 2153.50 | 3431.67 | 3222.83 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [ft3/min] | Limits and Scheduled Limits [ft3/min] | Economizer [ft3/min] | Exhaust Flow [ft3/min] | Mixed Air Flow [ft3/min] | High Humidity [ft3/min] | Demand Controlled Ventilation [ft3/min] | Night Ventilation [ft3/min] | Demand Limiting [ft3/min] | Energy Management System [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Surfaces by ClassTotal | Outdoors | |
Wall | 74 | 50 |
Floor | 28 | 3 |
Roof | 21 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 60 | 60 |
Overhang | 30 | 30 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1982 |
Defaulted Fields | 1847 |
Fields with Defaults | 6981 |
Autosized Fields | 360 |
Autosizable Fields | 540 |
Autocalculated Fields | 185 |
Autocalculatable Fields | 400 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 138825.37 | 7538.96 | 27-APR-03:10 | 48764.26 | 03-JAN-07:20 |
Electricity:Building | 96523.25 | 6165.39 | 02-JAN-03:10 | 18233.89 | 01-JAN-18:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
Electricity:SpaceType:GENERAL | 96523.25 | 6165.39 | 02-JAN-03:10 | 18233.89 | 01-JAN-18:10 |
InteriorLights:Electricity | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
General:InteriorLights:Electricity | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:SpaceType:GENERAL | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5362.40 | 342.52 | 02-JAN-03:10 | 1012.99 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
InteriorEquipment:Electricity | 85186.44 | 5878.44 | 02-JAN-04:10 | 14981.54 | 01-JAN-17:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 85186.44 | 5878.44 | 02-JAN-04:10 | 14981.54 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity | 1717.21 | 15.72 | 02-JAN-03:10 | 547.93 | 01-JAN-19:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL | 1717.21 | 15.72 | 02-JAN-03:10 | 547.93 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity | 11154.55 | 1110.97 | 01-JAN-04:10 | 1518.99 | 01-JAN-18:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 11154.55 | 1110.97 | 01-JAN-04:10 | 1518.99 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity | 713.84 | 6.86 | 02-JAN-02:10 | 193.33 | 01-JAN-09:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL | 713.84 | 6.86 | 02-JAN-02:10 | 193.33 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
electric_range:InteriorEquipment:Electricity:SpaceType:GENERAL | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
electric_mels:InteriorEquipment:Electricity:SpaceType:GENERAL | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4732.58 | 326.58 | 02-JAN-04:10 | 832.31 | 01-JAN-17:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 95.40 | 0.87 | 02-JAN-03:10 | 30.44 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 619.70 | 61.72 | 01-JAN-04:10 | 84.39 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 39.66 | 0.38 | 02-JAN-02:10 | 10.74 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
Electricity:HVAC | 27795.68 | 289.29 | 31-MAR-13:50 | 31113.15 | 03-JAN-07:10 |
Cooling:Electricity | 6789.51 | 0.00 | 01-JAN-00:10 | 8196.55 | 29-SEP-13:50 |
General:Cooling:Electricity | 6789.51 | 0.00 | 01-JAN-00:10 | 8196.55 | 29-SEP-13:50 |
Electricity:Plant | 10411.61 | 149.40 | 01-JAN-00:10 | 6672.80 | 01-JAN-08:10 |
WaterSystems:Electricity | 10411.61 | 149.40 | 01-JAN-00:10 | 6672.80 | 01-JAN-08:10 |
Fans:Electricity | 4937.68 | 289.29 | 31-MAR-13:50 | 2088.55 | 03-JAN-07:10 |
Ventilation:Fans:Electricity | 2534.14 | 289.29 | 01-JAN-07:50 | 289.29 | 01-JAN-00:10 |
General:Fans:Electricity | 2403.54 | 0.00 | 15-JAN-23:10 | 1799.26 | 03-JAN-07:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 138825.37 | 7538.96 | 27-APR-03:10 | 48764.26 | 03-JAN-07:20 |
ElectricityPurchased:Plant | 138825.37 | 7538.96 | 27-APR-03:10 | 48764.26 | 03-JAN-07:20 |
Cogeneration:ElectricityPurchased | 138825.37 | 7538.96 | 27-APR-03:10 | 48764.26 | 03-JAN-07:20 |
General:Cogeneration:ElectricityPurchased | 138825.37 | 7538.96 | 27-APR-03:10 | 48764.26 | 03-JAN-07:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 138825.37 | 7538.96 | 27-APR-03:10 | 48764.26 | 03-JAN-07:20 |
ElectricityNet:Plant | 138825.37 | 7538.96 | 27-APR-03:10 | 48764.26 | 03-JAN-07:20 |
Cogeneration:ElectricityNet | 138825.37 | 7538.96 | 27-APR-03:10 | 48764.26 | 03-JAN-07:20 |
General:Cogeneration:ElectricityNet | 138825.37 | 7538.96 | 27-APR-03:10 | 48764.26 | 03-JAN-07:20 |
ExteriorLights:Electricity | 4094.83 | 0.00 | 01-JAN-06:10 | 934.89 | 01-JAN-00:10 |
Exterior-Lights:ExteriorLights:Electricity | 4094.83 | 0.00 | 01-JAN-06:10 | 934.89 | 01-JAN-00:10 |
Garage-Lights:ExteriorLights:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 16068.48 | 0.00 | 04-JAN-13:00 | 29024.60 | 03-JAN-07:10 |
General:Heating:Electricity | 16068.48 | 0.00 | 04-JAN-13:00 | 29024.60 | 03-JAN-07:10 |
Water Heater:WaterSystems:Electricity | 1308.75 | 149.40 | 01-JAN-00:10 | 149.40 | 01-JAN-07:50 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Natural Gas Annual Value [therm] | Natural Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:10 |
Water:Plant | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:10 |
WaterSystems:Water | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:Water | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:10 |
MainsWater:Facility | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:10 |
MainsWater:Plant | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:10 |
WaterSystems:MainsWater | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:10 |
Domestic Hot Water:WaterSystems:MainsWater | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 541151.20 | 742.15 | 05-SEP-03:00 | 237196.70 | 29-SEP-15:30 |
EnergyTransfer:HVAC | 275891.51 | 0.00 | 15-JAN-23:10 | 166604.51 | 03-JAN-07:10 |
CoolingCoils:EnergyTransfer | 221027.01 | 0.00 | 01-JAN-00:10 | 118005.73 | 29-SEP-15:30 |
EnergyTransfer:Building | 176387.70 | 0.00 | 15-JAN-23:10 | 111091.10 | 29-SEP-15:30 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer | 32162.26 | 0.00 | 04-JAN-13:00 | 60407.53 | 08-JAN-07:10 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 32162.26 | 0.00 | 04-JAN-13:00 | 60407.53 | 08-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 144225.44 | 0.00 | 01-JAN-00:10 | 111091.10 | 29-SEP-15:30 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer | 144225.44 | 0.00 | 01-JAN-00:10 | 111091.10 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 10132.33 | 0.00 | 01-JAN-15:10 | 7649.20 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2329.99 | 0.00 | 01-JAN-15:10 | 4619.95 | 08-JAN-06:50 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2329.99 | 0.00 | 01-JAN-15:10 | 4619.95 | 08-JAN-06:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 7802.34 | 0.00 | 01-JAN-00:10 | 7649.20 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 7802.34 | 0.00 | 01-JAN-00:10 | 7649.20 | 29-SEP-15:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6777.15 | 0.00 | 01-JAN-18:10 | 4614.59 | 29-SEP-14:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1463.70 | 0.00 | 01-JAN-18:10 | 3644.15 | 09-JAN-06:50 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1463.70 | 0.00 | 01-JAN-18:10 | 3644.15 | 09-JAN-06:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5313.45 | 0.00 | 01-JAN-00:10 | 4614.59 | 29-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5313.45 | 0.00 | 01-JAN-00:10 | 4614.59 | 29-SEP-14:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9375.94 | 0.00 | 01-JAN-08:40 | 6082.70 | 29-SEP-14:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2223.04 | 0.00 | 01-JAN-08:30 | 4867.64 | 08-JAN-06:50 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2223.04 | 0.00 | 01-JAN-08:30 | 4867.64 | 08-JAN-06:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7152.91 | 0.00 | 01-JAN-00:10 | 6082.70 | 29-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7152.91 | 0.00 | 01-JAN-00:10 | 6082.70 | 29-SEP-14:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8557.16 | 0.00 | 02-JAN-14:00 | 6270.88 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2905.18 | 0.00 | 02-JAN-14:00 | 4428.27 | 08-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2905.18 | 0.00 | 02-JAN-14:00 | 4428.27 | 08-JAN-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5651.98 | 0.00 | 01-JAN-00:10 | 6270.88 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5651.98 | 0.00 | 01-JAN-00:10 | 6270.88 | 29-SEP-15:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5521.69 | 0.00 | 03-JAN-18:10 | 3903.92 | 15-OCT-14:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2043.97 | 0.00 | 03-JAN-18:10 | 3742.47 | 09-JAN-07:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2043.97 | 0.00 | 03-JAN-18:10 | 3742.47 | 09-JAN-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3477.73 | 0.00 | 01-JAN-00:10 | 3903.92 | 15-OCT-14:50 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3477.73 | 0.00 | 01-JAN-00:10 | 3903.92 | 15-OCT-14:50 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 7839.35 | 0.00 | 03-JAN-11:50 | 4689.65 | 29-SEP-13:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2760.63 | 0.00 | 03-JAN-11:50 | 4301.58 | 08-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2760.63 | 0.00 | 03-JAN-11:50 | 4301.58 | 08-JAN-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5078.71 | 0.00 | 01-JAN-00:10 | 4689.65 | 29-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5078.71 | 0.00 | 01-JAN-00:10 | 4689.65 | 29-SEP-13:00 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12816.37 | 0.00 | 01-JAN-12:10 | 8655.41 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1117.07 | 0.00 | 01-JAN-12:10 | 3588.17 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1117.07 | 0.00 | 01-JAN-12:10 | 3588.17 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 11699.31 | 0.00 | 01-JAN-00:10 | 8655.41 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 11699.31 | 0.00 | 01-JAN-00:10 | 8655.41 | 29-SEP-15:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9356.38 | 0.00 | 01-JAN-00:10 | 5540.76 | 16-OCT-13:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 502.17 | 0.00 | 01-JAN-00:10 | 2848.12 | 03-JAN-07:30 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 502.17 | 0.00 | 01-JAN-00:10 | 2848.12 | 03-JAN-07:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8854.21 | 0.00 | 01-JAN-00:10 | 5540.76 | 16-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8854.21 | 0.00 | 01-JAN-00:10 | 5540.76 | 16-OCT-13:20 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12063.72 | 0.00 | 01-JAN-08:40 | 7464.31 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1026.04 | 0.00 | 01-JAN-08:40 | 3500.70 | 09-JAN-06:40 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1026.04 | 0.00 | 01-JAN-08:40 | 3500.70 | 09-JAN-06:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 11037.68 | 0.00 | 01-JAN-00:10 | 7464.31 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 11037.68 | 0.00 | 01-JAN-00:10 | 7464.31 | 16-OCT-12:10 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10138.72 | 0.00 | 01-JAN-15:30 | 7037.02 | 29-SEP-15:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1591.88 | 0.00 | 01-JAN-15:30 | 3982.45 | 03-JAN-07:30 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1591.88 | 0.00 | 01-JAN-15:30 | 3982.45 | 03-JAN-07:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8546.84 | 0.00 | 01-JAN-00:10 | 7037.02 | 29-SEP-15:40 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8546.84 | 0.00 | 01-JAN-00:10 | 7037.02 | 29-SEP-15:40 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6768.20 | 0.00 | 01-JAN-17:50 | 3975.37 | 14-OCT-17:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 905.38 | 0.00 | 01-JAN-17:50 | 3362.15 | 09-JAN-06:40 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 905.38 | 0.00 | 01-JAN-17:50 | 3362.15 | 09-JAN-06:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5862.83 | 0.00 | 01-JAN-00:10 | 3975.37 | 14-OCT-17:50 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5862.83 | 0.00 | 01-JAN-00:10 | 3975.37 | 14-OCT-17:50 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9381.83 | 0.00 | 01-JAN-08:40 | 5381.65 | 29-SEP-13:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1482.95 | 0.00 | 01-JAN-08:40 | 3805.46 | 09-JAN-06:40 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1482.95 | 0.00 | 01-JAN-08:40 | 3805.46 | 09-JAN-06:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7898.88 | 0.00 | 01-JAN-00:10 | 5381.65 | 29-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7898.88 | 0.00 | 01-JAN-00:10 | 5381.65 | 29-SEP-13:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 10950.41 | 0.00 | 03-JAN-12:00 | 6654.29 | 29-SEP-14:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 2392.71 | 0.00 | 03-JAN-12:00 | 5282.28 | 08-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 2392.71 | 0.00 | 03-JAN-12:00 | 5282.28 | 08-JAN-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 8557.70 | 0.00 | 01-JAN-00:10 | 6654.29 | 29-SEP-14:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 8557.70 | 0.00 | 01-JAN-00:10 | 6654.29 | 29-SEP-14:30 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 12724.97 | 0.00 | 01-JAN-08:40 | 8016.45 | 29-SEP-13:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 1850.63 | 0.00 | 01-JAN-08:40 | 4779.71 | 08-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 1850.63 | 0.00 | 01-JAN-08:40 | 4779.71 | 08-JAN-06:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 10874.34 | 0.00 | 01-JAN-00:10 | 8016.45 | 29-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 10874.34 | 0.00 | 01-JAN-00:10 | 8016.45 | 29-SEP-13:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 13696.06 | 0.00 | 01-JAN-14:50 | 9661.87 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 2024.83 | 0.00 | 01-JAN-14:50 | 4469.67 | 08-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 2024.83 | 0.00 | 01-JAN-14:50 | 4469.67 | 08-JAN-06:20 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 11671.23 | 0.00 | 01-JAN-00:10 | 9661.87 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 11671.23 | 0.00 | 01-JAN-00:10 | 9661.87 | 29-SEP-15:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 8347.64 | 0.00 | 01-JAN-18:10 | 5222.10 | 29-SEP-16:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 1761.73 | 0.00 | 01-JAN-18:10 | 3944.09 | 03-JAN-07:30 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 1761.73 | 0.00 | 01-JAN-18:10 | 3944.09 | 03-JAN-07:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 6585.91 | 0.00 | 01-JAN-00:10 | 5222.10 | 29-SEP-16:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 6585.91 | 0.00 | 01-JAN-00:10 | 5222.10 | 29-SEP-16:10 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 9939.98 | 0.00 | 01-JAN-14:50 | 6228.13 | 29-SEP-15:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 1158.90 | 0.00 | 01-JAN-14:50 | 3395.47 | 03-JAN-07:30 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 1158.90 | 0.00 | 01-JAN-14:50 | 3395.47 | 03-JAN-07:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 8781.08 | 0.00 | 01-JAN-00:10 | 6228.13 | 29-SEP-15:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 8781.08 | 0.00 | 01-JAN-00:10 | 6228.13 | 29-SEP-15:10 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 11999.79 | 0.00 | 02-JAN-13:50 | 8669.45 | 29-SEP-15:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 2621.48 | 0.00 | 02-JAN-13:50 | 5459.82 | 08-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 2621.48 | 0.00 | 02-JAN-13:50 | 5459.82 | 08-JAN-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 9378.31 | 0.00 | 01-JAN-00:10 | 8669.45 | 29-SEP-15:40 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 9378.31 | 0.00 | 01-JAN-00:10 | 8669.45 | 29-SEP-15:40 |
PlantLoopHeatingDemand:Facility | 88872.00 | 729.64 | 04-AUG-03:00 | 21100.50 | 12-FEB-08:10 |
PlantLoopHeatingDemand:Plant | 88872.00 | 729.64 | 04-AUG-03:00 | 21100.50 | 12-FEB-08:10 |
WaterSystems:PlantLoopHeatingDemand | 88872.00 | 729.64 | 04-AUG-03:00 | 21100.50 | 12-FEB-08:10 |
General:WaterSystems:PlantLoopHeatingDemand | 88872.00 | 729.64 | 04-AUG-03:00 | 21100.50 | 12-FEB-08:10 |
HeatingCoils:EnergyTransfer | 54864.50 | 0.00 | 04-JAN-13:00 | 99031.95 | 03-JAN-07:10 |
EnergyTransfer:Plant | 88872.00 | 729.64 | 04-AUG-03:00 | 21100.50 | 12-FEB-08:10 |
WaterSystems:EnergyTransfer | 88872.00 | 729.64 | 04-AUG-03:00 | 21100.50 | 12-FEB-08:10 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 88872.00 | 729.64 | 04-AUG-03:00 | 21100.50 | 12-FEB-08:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | -385.37 | 3875.135 | -393.06 | 0.000 | 0.000 | 3043.763 | 2150.478 | 10010.237 | 9491.089 | 0.000 | 93.630 | 0.000 | 0.000 | -3436.77 | 0.000 | -7362.51 | -8517.63 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | -378.90 | 2973.664 | -189.33 | 0.000 | 0.000 | 3037.538 | 2150.478 | 10010.237 | 4168.445 | 0.000 | 92.618 | 0.000 | 0.000 | -1397.74 | 0.000 | -7145.35 | -7066.54 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | -384.61 | 3528.147 | -319.76 | 0.000 | 0.000 | 3047.715 | 2150.478 | 10010.237 | 8874.876 | 0.000 | 89.271 | 0.000 | 0.000 | -3360.38 | 0.000 | -7370.97 | -8511.39 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | -382.20 | 4897.150 | -254.37 | 0.000 | 0.000 | 3059.220 | 2150.478 | 10010.237 | 6529.397 | 0.000 | 100.309 | 0.000 | 0.000 | -3451.85 | 0.000 | -7232.93 | -8418.13 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | -376.03 | 4260.031 | -98.13 | 0.000 | 0.000 | 3060.102 | 2150.478 | 10010.237 | 1119.704 | 0.000 | 101.968 | 0.000 | 0.000 | -1406.22 | 0.000 | -6962.88 | -6639.70 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | -381.34 | 4618.219 | -196.30 | 0.000 | 0.000 | 3065.333 | 2150.478 | 10010.237 | 5860.936 | 0.000 | 94.442 | 0.000 | 0.000 | -3310.85 | 0.000 | -7214.59 | -8337.93 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | -392.72 | 2187.181 | -670.68 | 0.000 | 0.000 | 2990.363 | 2150.478 | 10010.237 | 9365.191 | 0.000 | 77.306 | 0.010 | 0.000 | -3653.96 | 0.000 | -6566.64 | -3790.84 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | -386.98 | 1408.917 | -425.88 | 0.000 | 0.000 | 2974.425 | 2150.478 | 10010.237 | 4114.227 | 0.000 | 75.188 | 0.030 | 0.000 | -1489.77 | 0.000 | -6387.17 | -3095.67 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | -392.84 | 1841.571 | -594.27 | 0.000 | 0.000 | 2994.200 | 2150.478 | 10010.237 | 8746.897 | 0.000 | 73.751 | 0.021 | 0.000 | -3569.52 | 0.000 | -6582.91 | -3811.54 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | -387.91 | 3068.919 | -446.85 | 0.000 | 0.000 | 3009.294 | 2150.478 | 10010.237 | 6426.269 | 0.000 | 82.300 | 0.000 | 0.000 | -3650.34 | 0.000 | -6447.71 | -4625.67 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | -381.06 | 2436.493 | -234.69 | 0.000 | 0.000 | 3004.385 | 2150.478 | 10010.237 | 1084.561 | 0.000 | 81.881 | 0.000 | 0.000 | -1486.64 | 0.000 | -6211.46 | -3676.08 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | -387.12 | 2732.625 | -374.74 | 0.000 | 0.000 | 3017.314 | 2150.478 | 10010.237 | 5751.054 | 0.000 | 77.032 | 0.000 | 0.000 | -3496.36 | 0.000 | -6442.47 | -4651.42 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | -390.54 | 3786.774 | -438.21 | 0.000 | 0.000 | 3023.756 | 2150.478 | 10010.237 | 5750.875 | 0.000 | 89.619 | 0.000 | 0.000 | -3505.77 | 0.000 | -7467.87 | -3886.35 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | -394.34 | 2865.592 | -595.77 | 0.000 | 0.000 | 3006.910 | 2150.478 | 10010.237 | 8755.260 | 0.000 | 86.019 | 0.000 | 0.000 | -3556.93 | 0.000 | -7601.02 | -3827.26 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | -393.40 | 3300.355 | -684.77 | 0.000 | 0.000 | 3004.308 | 2150.478 | 10010.237 | 9362.136 | 0.000 | 90.255 | 0.000 | 0.000 | -3629.73 | 0.000 | -7575.59 | -3765.78 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | -384.72 | 3385.191 | -298.93 | 0.000 | 0.000 | 3012.717 | 2150.478 | 10010.237 | 1082.624 | 0.000 | 94.877 | 0.000 | 0.000 | -1487.00 | 0.000 | -7235.48 | -2804.33 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | -388.49 | 2298.913 | -437.71 | 0.000 | 0.000 | 2990.939 | 2150.478 | 10010.237 | 4114.545 | 0.000 | 88.276 | 0.000 | 0.000 | -1481.91 | 0.000 | -7395.48 | -2854.96 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | -390.22 | 4229.089 | -524.65 | 0.000 | 0.000 | 3018.490 | 2150.478 | 10010.237 | 6409.115 | 0.000 | 96.045 | 0.000 | 0.000 | -3640.60 | 0.000 | -7466.80 | -3820.22 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26458.946 | 202220.009 | 0.000 | 0.000 | 0.000 | -228678.96 | -1.04 |
Total Facility | 0.000 | -6958.79 | 57693.966 | -7178.10 | 0.000 | 0.000 | 54360.771 | 38708.604 | 180184.270 | 107007.199 | 0.000 | 28043.735 | 202220.069 | 0.000 | -51012.32 | 0.000 | -355348.78 | -92102.48 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 29-SEP-15:30 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 156.40 | 1096.95 | 6001.21 | 0.00 | 996.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -717.3 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 29-SEP-13:00 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 113.90 | 90.23 | 1026.06 | 2048.46 | 0.00 | 1160.93 | 176.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 29-SEP-14:30 | 0.00 | -0.3 | 0.00 | -0.2 | 0.00 | 0.00 | 114.73 | 90.23 | 1039.63 | 2693.69 | 0.00 | 1151.50 | 1163.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 29-SEP-15:30 | 0.00 | -0.3 | 0.00 | -0.2 | 0.00 | 0.00 | 115.09 | 156.40 | 1096.95 | 5291.57 | 0.00 | 996.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1386.2 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 29-SEP-16:24 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 144.18 | 336.87 | 1297.67 | 383.62 | 0.00 | 798.48 | 1277.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 17-OCT-09:25 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 118.56 | 90.23 | 1021.02 | 4097.91 | 0.00 | 621.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -889.9 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 29-SEP-15:30 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.09 | 156.40 | 1096.95 | 5962.47 | 0.00 | 833.99 | 490.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 16-OCT-13:20 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.09 | 90.23 | 1026.06 | 2802.83 | 0.00 | 898.77 | 607.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 16-OCT-12:15 | 0.00 | -0.3 | 0.00 | -0.3 | 0.00 | 0.00 | 114.53 | 90.23 | 1031.69 | 4273.70 | 0.00 | 1184.80 | 1107.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 29-SEP-15:45 | 0.00 | -0.3 | 0.00 | -0.3 | 0.00 | 0.00 | 115.09 | 156.40 | 1096.95 | 5053.12 | 0.00 | 814.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -198.7 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 14-OCT-18:54 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 431.45 | 631.63 | 1666.21 | 0.00 | 0.00 | 0.00 | 1979.13 | 0.00 | -143.5 | 0.00 | -139.4 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 29-SEP-12:05 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 115.09 | 90.23 | 1031.69 | 1984.80 | 0.00 | 1174.92 | 986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 29-SEP-14:35 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 90.23 | 1039.63 | 1608.15 | 0.00 | 1147.97 | 2653.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 29-SEP-13:30 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.09 | 90.23 | 1026.06 | 3426.59 | 0.00 | 1319.13 | 2039.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 29-SEP-15:30 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 115.09 | 156.40 | 1096.95 | 5934.97 | 0.00 | 992.75 | 1365.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 29-SEP-16:15 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 140.35 | 336.87 | 1297.67 | 389.17 | 0.00 | 841.33 | 2216.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 29-SEP-15:15 | 0.00 | -0.3 | 0.00 | -0.2 | 0.00 | 0.00 | 115.09 | 156.40 | 1096.95 | 1400.33 | 0.00 | 1009.95 | 2449.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 29-SEP-15:39 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.08 | 156.40 | 1096.95 | 5017.62 | 0.00 | 966.01 | 1318.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-SEP-15:30 | 0.00 | -1.1 | 0.00 | -8.1 | 0.00 | 0.00 | 2071.63 | 2815.26 | 19745.07 | 48341.29 | 0.00 | 16756.69 | 75962.78 | 0.00 | 0.00 | 0.00 | -54602.5 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 08-JAN-06:49 | 0.00 | 0.00 | 5835.59 | 0.00 | 0.00 | 0.00 | 547.21 | 336.87 | 1049.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1510.8 | 0.00 | -2736.7 | -3522.1 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 09-JAN-06:00 | 0.00 | 0.00 | 4816.38 | 0.00 | 0.00 | 0.00 | 537.15 | 336.87 | 1044.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -229.3 | 0.00 | -2377.4 | -4128.2 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 08-JAN-06:49 | 0.00 | 0.00 | 5767.42 | 0.00 | 0.00 | 0.00 | 550.49 | 336.87 | 1049.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1506.3 | 0.00 | -2720.1 | -3478.3 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 08-JAN-07:15 | 0.00 | 0.00 | 5749.40 | 0.00 | 0.00 | 0.00 | 487.13 | 300.78 | 1173.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1341.0 | 0.00 | -2665.4 | -3704.9 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 09-JAN-06:00 | 0.00 | 0.00 | 4806.94 | 0.00 | 0.00 | 0.00 | 540.02 | 336.87 | 1044.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -530.3 | 0.00 | -2362.8 | -3835.3 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 08-JAN-07:15 | 0.00 | 0.00 | 5683.91 | 0.00 | 0.00 | 0.00 | 488.44 | 300.78 | 1173.96 | 274.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2670.1 | -5251.7 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 03-FEB-23:49 | 0.00 | 0.00 | 4341.53 | 0.00 | 0.00 | 0.00 | 543.58 | 120.31 | 1113.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1006.8 | 0.00 | -1241.1 | -3870.6 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 03-JAN-07:40 | 0.00 | 0.00 | 4436.96 | 0.00 | 0.00 | 0.00 | 468.06 | 300.78 | 1163.30 | 694.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1682.8 | -5380.3 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 09-JAN-06:40 | 0.00 | 0.00 | 5504.67 | 0.00 | 0.00 | 0.00 | 540.21 | 336.87 | 1044.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1435.7 | 0.00 | -2120.2 | -3870.4 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 03-JAN-07:40 | 0.00 | 0.00 | 5590.29 | 0.00 | 0.00 | 0.00 | 465.81 | 300.78 | 1163.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -964.3 | 0.00 | -1757.9 | -4798.0 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 09-JAN-06:49 | 0.00 | 0.00 | 4433.65 | 0.00 | 0.00 | 0.00 | 526.27 | 336.87 | 1044.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -579.5 | 0.00 | -2030.9 | -3731.0 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 09-JAN-06:40 | 0.00 | 0.00 | 5488.77 | 0.00 | 0.00 | 0.00 | 544.58 | 336.87 | 1044.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1422.7 | 0.00 | -2102.4 | -3889.7 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 08-JAN-07:15 | 0.00 | 0.00 | 6480.64 | 0.00 | 0.00 | 0.00 | 479.45 | 300.78 | 1173.96 | 252.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2726.6 | -5960.7 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 08-JAN-06:10 | -1844.6 | 0.00 | 6624.03 | 0.00 | 0.00 | 0.00 | 535.30 | 336.87 | 1049.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1427.2 | 0.00 | -2552.1 | -2722.3 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 30-MAR-06:34 | -1186.1 | 0.00 | 5799.16 | 0.00 | 0.00 | 0.00 | 532.16 | 336.87 | 1044.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -870.7 | 0.00 | -2141.2 | -3514.7 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 03-JAN-07:40 | 0.00 | 0.00 | 5695.04 | 0.00 | 0.00 | 0.00 | 467.19 | 300.78 | 1163.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -386.8 | 0.00 | -2000.4 | -5239.2 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 09-JAN-06:40 | 0.00 | 0.00 | 5676.79 | 0.00 | 0.00 | 0.00 | 536.62 | 336.87 | 1044.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -580.9 | 0.00 | -2482.3 | -4531.6 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 08-JAN-07:15 | 0.00 | 0.00 | 6592.86 | 0.00 | 0.00 | 0.00 | 477.61 | 300.78 | 1173.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1352.5 | 0.00 | -2726.5 | -4466.2 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 09-JAN-06:40 | -6841.6 | 0.00 | 79016.75 | 0.00 | 0.00 | 0.00 | 9643.26 | 6063.64 | 18802.00 | 0.00 | 0.00 | 7490.23 | 0.00 | 0.00 | -20691.5 | 0.00 | -42856.1 | -50626.6 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 280.1175 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 280.1175 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 140.1406 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 140.1406 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 191.9996 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 191.9996 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 260.7353 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 260.7353 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 127.9940 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 127.9940 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 177.6115 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 177.6115 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 326.7048 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 326.7048 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 176.7999 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 176.7999 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 231.3832 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 231.3832 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 305.2896 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 305.2896 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 162.2450 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 162.2450 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 213.2521 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 213.2521 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 367.5008 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 367.5008 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 217.3807 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 217.3807 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 257.5163 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 257.5163 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 362.2108 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 362.2108 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 214.8488 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 214.8488 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 241.5384 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 241.5384 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 280.1175 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 280.1175 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 140.1406 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 140.1406 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 191.9996 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 191.9996 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 260.7353 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 260.7353 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 127.9940 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 127.9940 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 177.6115 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 177.6115 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 326.7048 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 326.7048 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 176.7999 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 176.7999 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 231.3832 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 231.3832 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 305.2896 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 305.2896 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 162.2450 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 162.2450 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 213.2521 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 213.2521 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 367.5008 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 367.5008 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 217.3807 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 217.3807 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 257.5163 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 257.5163 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 362.2108 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 362.2108 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 214.8488 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 214.8488 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 241.5384 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 241.5384 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 280.1175 | 280.1175 | 280.1175 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 140.1406 | 140.1406 | 140.1406 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 191.9996 | 191.9996 | 191.9996 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 260.7353 | 260.7353 | 260.7353 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 127.9940 | 127.9940 | 127.9940 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 177.6115 | 177.6115 | 177.6115 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 326.7048 | 326.7048 | 326.7048 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 176.7999 | 176.7999 | 176.7999 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 231.3832 | 231.3832 | 231.3832 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 305.2896 | 305.2896 | 305.2896 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 162.2450 | 162.2450 | 162.2450 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 213.2521 | 213.2521 | 213.2521 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 241.5384 | 241.5384 | 241.5384 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 257.5163 | 257.5163 | 257.5163 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 367.5008 | 367.5008 | 367.5008 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 214.8488 | 214.8488 | 214.8488 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 217.3807 | 217.3807 | 217.3807 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 362.2108 | 362.2108 | 362.2108 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 280.1175 | 280.1175 | 280.1175 | 280.1175 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 140.1406 | 140.1406 | 140.1406 | 140.1406 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 191.9996 | 191.9996 | 191.9996 | 191.9996 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 260.7353 | 260.7353 | 260.7353 | 260.7353 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 127.9940 | 127.9940 | 127.9940 | 127.9940 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 177.6115 | 177.6115 | 177.6115 | 177.6115 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 326.7048 | 326.7048 | 326.7048 | 326.7048 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 176.7999 | 176.7999 | 176.7999 | 176.7999 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 231.3832 | 231.3832 | 231.3832 | 231.3832 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 305.2896 | 305.2896 | 305.2896 | 305.2896 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 162.2450 | 162.2450 | 162.2450 | 162.2450 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 213.2521 | 213.2521 | 213.2521 | 213.2521 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 367.5008 | 367.5008 | 367.5008 | 367.5008 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 217.3807 | 217.3807 | 217.3807 | 217.3807 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 257.5163 | 257.5163 | 257.5163 | 257.5163 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 362.2108 | 362.2108 | 362.2108 | 362.2108 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 214.8488 | 214.8488 | 214.8488 | 214.8488 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 241.5384 | 241.5384 | 241.5384 | 241.5384 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 280.1175 | 280.1175 | 280.1175 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 140.1406 | 140.1406 | 140.1406 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 191.9996 | 191.9996 | 191.9996 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 260.7353 | 260.7353 | 260.7353 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 127.9940 | 127.9940 | 127.9940 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 177.6115 | 177.6115 | 177.6115 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 326.7048 | 326.7048 | 326.7048 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 176.7999 | 176.7999 | 176.7999 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 231.3832 | 231.3832 | 231.3832 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 305.2896 | 305.2896 | 305.2896 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 162.2450 | 162.2450 | 162.2450 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 213.2521 | 213.2521 | 213.2521 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 241.5384 | 241.5384 | 241.5384 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 257.5163 | 257.5163 | 257.5163 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 367.5008 | 367.5008 | 367.5008 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 214.8488 | 214.8488 | 214.8488 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 217.3807 | 217.3807 | 217.3807 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 362.2108 | 362.2108 | 362.2108 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 280.1175 | 280.1175 | 280.1175 | 280.1175 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 140.1406 | 140.1406 | 140.1406 | 140.1406 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 191.9996 | 191.9996 | 191.9996 | 191.9996 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 260.7353 | 260.7353 | 260.7353 | 260.7353 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 127.9940 | 127.9940 | 127.9940 | 127.9940 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 177.6115 | 177.6115 | 177.6115 | 177.6115 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 326.7048 | 326.7048 | 326.7048 | 326.7048 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 176.7999 | 176.7999 | 176.7999 | 176.7999 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 231.3832 | 231.3832 | 231.3832 | 231.3832 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 305.2896 | 305.2896 | 305.2896 | 305.2896 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 162.2450 | 162.2450 | 162.2450 | 162.2450 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 213.2521 | 213.2521 | 213.2521 | 213.2521 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 367.5008 | 367.5008 | 367.5008 | 367.5008 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 217.3807 | 217.3807 | 217.3807 | 217.3807 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 257.5163 | 257.5163 | 257.5163 | 257.5163 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 362.2108 | 362.2108 | 362.2108 | 362.2108 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 214.8488 | 214.8488 | 214.8488 | 214.8488 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 241.5384 | 241.5384 | 241.5384 | 241.5384 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [ft2] | 31210.83 |
Principal Heating Source | Electricity |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
BREEZEWAY | 1798.16 | 0.00 | 1798.16 | 0.00 |
ATTIC | 7802.71 | 0.00 | 7802.71 | 0.00 |
Totals | 31210.83 | 21609.96 | 9600.87 |
Data | |
Number of hours heating loads not met | 213.67 |
Number of hours cooling loads not met | 1.17 |
Number of hours not met | 214.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Gasoline Use [therm] | Gasoline Demand [Btu/h] | Diesel Use [kBtu] | Diesel Demand [Btu/h] | Coal Use [kBtu] | Coal Demand [Btu/h] | Fuel Oil No 1 Use [kBtu] | Fuel Oil No 1 Demand [Btu/h] | Fuel Oil No 2 Use [kBtu] | Fuel Oil No 2 Demand [Btu/h] | Propane Use [kBtu] | Propane Demand [Btu/h] | Other Fuel 1 Use [kBtu] | Other Fuel 1 Demand [Btu/h] | Other Fuel 2 Use [kBtu] | Other Fuel 2 Demand [Btu/h] | District Cooling Use [ton-hrs] | District Cooling Demand [ton] | District Heating Use [kBtu] | District Heating Demand [Btu/h] | |
Heating -- General | 16068.48 | 29024.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 6789.51 | 8196.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- General | 11336.81 | 3692.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Exterior-Lights | 4094.83 | 934.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- dishwasher | 1717.21 | 547.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- refrigerator | 11154.55 | 1518.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- clotheswasher | 713.84 | 193.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_dryer | 12502.11 | 3196.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_range | 9058.39 | 3721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_mels | 46926.68 | 7929.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- IECC_adj | 3113.66 | 526.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation | 2534.14 | 289.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2403.54 | 1799.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 1308.75 | 149.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 6523.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 290862.05 | 474007.73 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 290862.05 | 474007.73 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting (All) | 0.36 |
Space Heating | 0.51 |
Space Cooling | 0.22 |
Fans (All) | 0.16 |
Service Water Heating | 0.33 |
Receptacle Equipment | 2.73 |
Miscellaneous (All) | 4.45 |
Subtotal | 4.45 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [kBtu/ft2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.17 |
Space Heating | 11.57 |
Space Cooling | 4.89 |
Fans (All) | 3.56 |
Service Water Heating | 7.50 |
Receptacle Equipment | 61.36 |
Miscellaneous | 2.95 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OCCUPANCY | 6031. | 8760. |
INTERIORLIGHTING | 2852. | 8760. |
INTERIORLIGHTINGHE | 3070. | 8760. |
INTERIORLIGHTINGHE_OS | 2910. | 8760. |
INTERIORLIGHTINGHE_VS | 2149. | 8760. |
EXTERIORLIGHTING | 4380. | 4380. |
REFRIGERATOR | 7343. | 8760. |
MISCPLUGLOAD | 5918. | 8760. |
COOKINGRANGE | 2434. | 8760. |
DISHWASHER_FLOW_SCH | 2642. | 8760. |
CLOTHESWASHER_FLOW_SCH | 3113. | 8760. |
DISHWASHER_EQUIP_SCH | 3134. | 8760. |
CLOTHESWASHER_EQUIP_SCH | 3692. | 8760. |
CLOTHESDRYER | 3911. | 8760. |
SHADING_2012IECC | 0. | 0. |
SHADING_2012IECC_HERS | 7007. | 8760. |
SINKSENSSCHEDULE | 6025. | 8760. |
SINKLATSCHEDULE | 2735. | 8760. |
SHOWERSENSSCHEDULE | 4492. | 8760. |
SHOWERLATSCHEDULE | 4268. | 8760. |
BATHSENSSCHEDULE | 8760. | 8760. |
BATHLATSCHEDULE | 0. | 0. |
First Object Used | Month Assumed | 11am First Wednesday [F] | Days with Same 11am Value | 11pm First Wednesday [F] | Days with Same 11pm Value | |
HEATING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | January | 72.00 | 365 | 72.00 | 365 |
COOLING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | July | 75.00 | 365 | 75.00 | 365 |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 17:20:07
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 123.764 | 2.340 | 335.228 | 13.979 | 13.979 |
February | 81.528 | 1.648 | 342.314 | 11.792 | 11.792 |
March | 85.444 | 1.856 | 420.825 | 15.062 | 15.062 |
April | 160.778 | 3.848 | 246.308 | 9.762 | 9.762 |
May | 141.750 | 2.752 | 227.225 | 8.170 | 8.170 |
June | 264.278 | 6.665 | 26.411 | 7.683 | 7.683 |
July | 402.331 | 11.788 | 2.700 | 11.950 | 11.950 |
August | 434.347 | 13.295 | 2.389 | 13.428 | 13.428 |
September | 348.092 | 10.308 | 10.997 | 10.813 | 10.813 |
October | 298.236 | 8.013 | 82.972 | 10.328 | 10.328 |
November | 136.286 | 3.032 | 264.189 | 10.365 | 10.365 |
December | 135.653 | 2.971 | 319.697 | 13.777 | 13.777 |
Annual Sum or Average | 2612.487 | 68.514 | 2281.256 | 137.108 | 137.108 |
Minimum of Months | 81.528 | 1.648 | 2.389 | 7.683 | 7.683 |
Maximum of Months | 434.347 | 13.295 | 420.825 | 15.062 | 15.062 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 101.861 | 1.085 | 279.014 | 6.371 | 6.371 |
February | 56.597 | 0.492 | 303.744 | 5.327 | 5.327 |
March | 48.500 | 0.429 | 404.219 | 7.021 | 7.021 |
April | 90.083 | 0.735 | 208.698 | 3.616 | 3.616 |
May | 39.181 | 0.205 | 187.927 | 3.169 | 3.169 |
June | 234.028 | 2.219 | 12.531 | 2.702 | 2.702 |
July | 413.169 | 5.995 | 1.372 | 6.041 | 6.041 |
August | 479.569 | 7.735 | 0.964 | 7.765 | 7.765 |
September | 366.289 | 6.115 | 5.133 | 6.306 | 6.306 |
October | 296.192 | 4.876 | 52.436 | 5.831 | 5.831 |
November | 114.800 | 1.365 | 203.183 | 4.601 | 4.601 |
December | 115.678 | 1.527 | 268.097 | 6.340 | 6.340 |
Annual Sum or Average | 2355.948 | 32.777 | 1927.318 | 65.091 | 65.091 |
Minimum of Months | 39.181 | 0.205 | 0.964 | 2.702 | 2.702 |
Maximum of Months | 479.569 | 7.735 | 404.219 | 7.765 | 7.765 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 130.086 | 1.785 | 311.969 | 9.338 | 9.338 |
February | 79.067 | 1.035 | 327.994 | 7.794 | 7.794 |
March | 80.744 | 1.205 | 397.927 | 9.919 | 9.919 |
April | 158.815 | 2.519 | 221.611 | 6.005 | 6.005 |
May | 130.192 | 1.336 | 209.950 | 4.625 | 4.625 |
June | 276.289 | 5.175 | 20.917 | 5.596 | 5.596 |
July | 411.692 | 10.627 | 1.389 | 10.685 | 10.685 |
August | 435.981 | 12.443 | 1.194 | 12.497 | 12.497 |
September | 345.267 | 8.757 | 11.242 | 9.033 | 9.033 |
October | 295.419 | 6.904 | 75.694 | 8.162 | 8.162 |
November | 131.789 | 2.117 | 245.527 | 6.802 | 6.802 |
December | 127.892 | 2.302 | 301.292 | 9.344 | 9.344 |
Annual Sum or Average | 2603.232 | 56.206 | 2126.707 | 99.798 | 99.798 |
Minimum of Months | 79.067 | 1.035 | 1.194 | 4.625 | 4.625 |
Maximum of Months | 435.981 | 12.443 | 397.927 | 12.497 | 12.497 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 22.708 | 0.243 | 459.969 | 15.270 | 15.270 |
February | 16.972 | 0.170 | 420.542 | 12.132 | 12.132 |
March | 33.708 | 0.491 | 486.517 | 14.585 | 14.585 |
April | 114.833 | 2.167 | 274.281 | 8.427 | 8.427 |
May | 129.056 | 2.292 | 227.947 | 7.410 | 7.410 |
June | 266.272 | 6.521 | 24.289 | 7.406 | 7.406 |
July | 406.094 | 11.223 | 2.264 | 11.345 | 11.345 |
August | 418.467 | 11.199 | 2.297 | 11.322 | 11.322 |
September | 300.429 | 6.988 | 14.783 | 7.607 | 7.607 |
October | 226.872 | 4.042 | 103.225 | 6.940 | 6.940 |
November | 33.361 | 0.360 | 360.825 | 10.056 | 10.056 |
December | 33.389 | 0.318 | 436.942 | 14.477 | 14.477 |
Annual Sum or Average | 2002.162 | 46.014 | 2813.881 | 126.977 | 126.977 |
Minimum of Months | 16.972 | 0.170 | 2.264 | 6.940 | 6.940 |
Maximum of Months | 418.467 | 11.223 | 486.517 | 15.270 | 15.270 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 13.722 | 0.036 | 503.406 | 7.782 | 7.782 |
February | 0.000 | 0.000 | 449.903 | 6.368 | 6.368 |
March | 0.000 | 0.000 | 515.222 | 7.560 | 7.560 |
April | 18.639 | 0.107 | 249.150 | 3.518 | 3.518 |
May | 24.611 | 0.100 | 189.738 | 2.884 | 2.884 |
June | 233.714 | 2.202 | 11.044 | 2.586 | 2.586 |
July | 427.403 | 5.533 | 1.472 | 5.577 | 5.577 |
August | 457.606 | 5.837 | 1.122 | 5.875 | 5.875 |
September | 292.020 | 2.954 | 7.494 | 3.227 | 3.227 |
October | 176.036 | 1.579 | 76.983 | 3.046 | 3.046 |
November | 2.556 | 0.006 | 338.402 | 5.009 | 5.009 |
December | 4.417 | 0.020 | 464.683 | 7.332 | 7.332 |
Annual Sum or Average | 1650.723 | 18.374 | 2808.620 | 60.764 | 60.764 |
Minimum of Months | 0.000 | 0.000 | 1.122 | 2.586 | 2.586 |
Maximum of Months | 457.606 | 5.837 | 515.222 | 7.782 | 7.782 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 24.583 | 0.127 | 464.419 | 10.114 | 10.114 |
February | 4.264 | 0.019 | 416.242 | 8.214 | 8.214 |
March | 21.750 | 0.133 | 464.262 | 9.552 | 9.552 |
April | 91.982 | 0.969 | 239.511 | 4.772 | 4.772 |
May | 111.717 | 0.945 | 209.427 | 4.047 | 4.047 |
June | 284.108 | 5.156 | 21.094 | 5.571 | 5.571 |
July | 411.303 | 10.157 | 1.472 | 10.207 | 10.207 |
August | 431.867 | 10.477 | 0.944 | 10.507 | 10.507 |
September | 313.839 | 5.432 | 12.389 | 5.723 | 5.723 |
October | 212.906 | 2.929 | 89.633 | 4.558 | 4.558 |
November | 14.678 | 0.106 | 333.997 | 6.625 | 6.625 |
December | 20.167 | 0.107 | 465.258 | 9.621 | 9.621 |
Annual Sum or Average | 1943.162 | 36.557 | 2718.650 | 89.512 | 89.512 |
Minimum of Months | 4.264 | 0.019 | 0.944 | 4.047 | 4.047 |
Maximum of Months | 431.867 | 10.477 | 465.258 | 10.507 | 10.507 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 203.597 | 5.131 | 211.872 | 13.848 | 13.848 |
February | 145.694 | 3.670 | 212.131 | 10.841 | 10.841 |
March | 145.444 | 3.938 | 274.348 | 13.746 | 13.746 |
April | 263.194 | 7.798 | 97.489 | 11.113 | 11.113 |
May | 242.014 | 6.347 | 78.453 | 9.345 | 9.345 |
June | 399.219 | 11.055 | 6.381 | 11.546 | 11.546 |
July | 576.697 | 17.715 | 0.750 | 17.768 | 17.768 |
August | 585.656 | 19.178 | 0.575 | 19.218 | 19.218 |
September | 456.204 | 14.795 | 4.419 | 15.160 | 15.160 |
October | 437.678 | 14.067 | 33.031 | 15.358 | 15.358 |
November | 225.983 | 6.117 | 147.544 | 11.055 | 11.055 |
December | 220.103 | 5.861 | 209.256 | 13.756 | 13.756 |
Annual Sum or Average | 3901.485 | 115.671 | 1276.248 | 162.754 | 162.754 |
Minimum of Months | 145.444 | 3.670 | 0.575 | 9.345 | 9.345 |
Maximum of Months | 585.656 | 19.178 | 274.348 | 19.218 | 19.218 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 219.458 | 3.616 | 147.242 | 7.297 | 7.297 |
February | 144.167 | 2.157 | 136.150 | 5.436 | 5.436 |
March | 124.486 | 1.861 | 204.508 | 6.683 | 6.683 |
April | 234.972 | 3.541 | 44.638 | 5.129 | 5.129 |
May | 211.236 | 2.253 | 40.069 | 3.751 | 3.751 |
June | 415.125 | 5.869 | 4.275 | 6.101 | 6.101 |
July | 582.825 | 11.250 | 0.125 | 11.255 | 11.255 |
August | 596.097 | 13.127 | 0.089 | 13.130 | 13.130 |
September | 509.247 | 10.401 | 2.444 | 10.526 | 10.526 |
October | 461.481 | 10.557 | 8.069 | 10.978 | 10.978 |
November | 239.097 | 4.152 | 70.633 | 6.048 | 6.048 |
December | 242.453 | 4.236 | 143.164 | 7.546 | 7.546 |
Annual Sum or Average | 3980.644 | 73.021 | 801.407 | 93.880 | 93.880 |
Minimum of Months | 124.486 | 1.861 | 0.089 | 3.751 | 3.751 |
Maximum of Months | 596.097 | 13.127 | 204.508 | 13.130 | 13.130 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 220.489 | 4.566 | 191.486 | 10.026 | 10.026 |
February | 145.831 | 2.991 | 203.364 | 7.776 | 7.776 |
March | 145.103 | 3.209 | 257.153 | 9.628 | 9.628 |
April | 273.319 | 6.447 | 88.633 | 8.036 | 8.036 |
May | 262.879 | 4.799 | 66.606 | 6.240 | 6.240 |
June | 395.508 | 9.404 | 4.139 | 9.655 | 9.655 |
July | 556.653 | 16.283 | 0.167 | 16.291 | 16.291 |
August | 587.225 | 18.229 | 0.222 | 18.240 | 18.240 |
September | 451.075 | 12.999 | 3.611 | 13.156 | 13.156 |
October | 448.256 | 12.839 | 26.625 | 13.387 | 13.387 |
November | 234.339 | 5.014 | 129.558 | 7.965 | 7.965 |
December | 222.858 | 5.056 | 192.394 | 10.085 | 10.085 |
Annual Sum or Average | 3943.534 | 101.837 | 1163.958 | 130.485 | 130.485 |
Minimum of Months | 145.103 | 2.991 | 0.167 | 6.240 | 6.240 |
Maximum of Months | 587.225 | 18.229 | 257.153 | 18.240 | 18.240 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 62.528 | 0.785 | 325.242 | 13.599 | 13.599 |
February | 52.444 | 0.631 | 293.792 | 9.879 | 9.879 |
March | 85.222 | 1.451 | 330.233 | 12.512 | 12.512 |
April | 212.681 | 5.155 | 119.585 | 8.906 | 8.906 |
May | 237.750 | 5.702 | 74.686 | 8.435 | 8.435 |
June | 405.533 | 10.938 | 7.272 | 11.451 | 11.451 |
July | 584.636 | 17.156 | 0.500 | 17.185 | 17.185 |
August | 569.342 | 16.723 | 0.622 | 16.764 | 16.764 |
September | 409.851 | 10.678 | 6.983 | 11.111 | 11.111 |
October | 371.394 | 8.495 | 45.919 | 10.405 | 10.405 |
November | 102.389 | 1.147 | 234.949 | 8.541 | 8.541 |
December | 70.208 | 0.861 | 320.386 | 12.900 | 12.900 |
Annual Sum or Average | 3163.979 | 79.724 | 1760.171 | 141.688 | 141.688 |
Minimum of Months | 52.444 | 0.631 | 0.500 | 8.435 | 8.435 |
Maximum of Months | 584.636 | 17.156 | 330.233 | 17.185 | 17.185 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 45.806 | 0.352 | 296.633 | 7.289 | 7.289 |
February | 4.556 | 0.014 | 236.156 | 5.190 | 5.190 |
March | 25.417 | 0.139 | 281.731 | 6.158 | 6.158 |
April | 135.986 | 1.251 | 59.519 | 3.208 | 3.208 |
May | 185.639 | 1.680 | 41.603 | 3.149 | 3.149 |
June | 424.525 | 5.916 | 2.989 | 6.051 | 6.051 |
July | 587.503 | 10.719 | 0.056 | 10.722 | 10.722 |
August | 587.464 | 10.749 | 0.056 | 10.752 | 10.752 |
September | 461.264 | 6.340 | 3.300 | 6.503 | 6.503 |
October | 361.492 | 5.148 | 20.839 | 5.994 | 5.994 |
November | 39.222 | 0.229 | 172.211 | 4.275 | 4.275 |
December | 39.889 | 0.236 | 289.575 | 6.682 | 6.682 |
Annual Sum or Average | 2898.762 | 42.773 | 1404.667 | 75.973 | 75.973 |
Minimum of Months | 4.556 | 0.014 | 0.056 | 3.149 | 3.149 |
Maximum of Months | 587.503 | 10.749 | 296.633 | 10.752 | 10.752 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 55.028 | 0.576 | 295.222 | 9.068 | 9.068 |
February | 22.847 | 0.116 | 278.319 | 6.497 | 6.497 |
March | 69.603 | 0.784 | 305.831 | 8.079 | 8.079 |
April | 222.783 | 3.683 | 103.497 | 5.488 | 5.488 |
May | 252.592 | 4.107 | 65.014 | 5.426 | 5.426 |
June | 402.094 | 9.445 | 4.222 | 9.665 | 9.665 |
July | 559.806 | 15.841 | 0.167 | 15.847 | 15.847 |
August | 570.547 | 16.007 | 0.333 | 16.024 | 16.024 |
September | 419.375 | 9.033 | 5.939 | 9.238 | 9.238 |
October | 384.842 | 7.139 | 33.936 | 7.859 | 7.859 |
November | 54.894 | 0.447 | 199.650 | 5.330 | 5.330 |
December | 61.133 | 0.492 | 292.594 | 8.504 | 8.504 |
Annual Sum or Average | 3075.544 | 67.672 | 1584.725 | 107.024 | 107.024 |
Minimum of Months | 22.847 | 0.116 | 0.167 | 5.330 | 5.330 |
Maximum of Months | 570.547 | 16.007 | 305.831 | 16.024 | 16.024 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 187.639 | 4.623 | 263.867 | 16.454 | 16.454 |
February | 125.111 | 3.338 | 275.031 | 13.242 | 13.242 |
March | 133.292 | 3.921 | 345.267 | 17.145 | 17.145 |
April | 246.014 | 8.339 | 155.156 | 12.880 | 12.880 |
May | 236.556 | 7.063 | 131.714 | 11.117 | 11.117 |
June | 360.322 | 11.925 | 19.497 | 12.767 | 12.767 |
July | 510.044 | 19.107 | 1.750 | 19.221 | 19.221 |
August | 530.258 | 20.339 | 1.764 | 20.454 | 20.454 |
September | 402.123 | 15.071 | 15.328 | 15.784 | 15.784 |
October | 418.239 | 14.613 | 54.064 | 16.516 | 16.516 |
November | 200.033 | 5.636 | 204.669 | 12.710 | 12.710 |
December | 195.083 | 5.272 | 263.061 | 16.107 | 16.107 |
Annual Sum or Average | 3544.715 | 119.248 | 1731.167 | 184.396 | 184.396 |
Minimum of Months | 125.111 | 3.338 | 1.750 | 11.117 | 11.117 |
Maximum of Months | 530.258 | 20.339 | 345.267 | 20.454 | 20.454 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 185.278 | 3.156 | 206.706 | 8.968 | 8.968 |
February | 118.833 | 1.849 | 219.633 | 6.924 | 6.924 |
March | 108.875 | 1.936 | 296.163 | 9.219 | 9.219 |
April | 221.847 | 4.147 | 97.058 | 6.459 | 6.459 |
May | 207.069 | 3.008 | 83.067 | 5.148 | 5.148 |
June | 361.947 | 6.681 | 8.011 | 7.124 | 7.124 |
July | 537.272 | 12.481 | 0.764 | 12.515 | 12.515 |
August | 556.175 | 14.119 | 0.581 | 14.146 | 14.146 |
September | 432.758 | 10.526 | 4.925 | 10.794 | 10.794 |
October | 427.850 | 11.127 | 28.400 | 11.893 | 11.893 |
November | 205.694 | 3.715 | 133.969 | 6.905 | 6.905 |
December | 200.167 | 3.653 | 205.786 | 8.914 | 8.914 |
Annual Sum or Average | 3563.767 | 76.398 | 1285.062 | 109.009 | 109.009 |
Minimum of Months | 108.875 | 1.849 | 0.581 | 5.148 | 5.148 |
Maximum of Months | 556.175 | 14.119 | 296.163 | 14.146 | 14.146 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 193.792 | 3.758 | 234.669 | 11.305 | 11.305 |
February | 127.306 | 2.430 | 266.742 | 8.971 | 8.971 |
March | 132.533 | 2.952 | 319.459 | 11.584 | 11.584 |
April | 258.572 | 6.545 | 131.300 | 8.994 | 8.994 |
May | 249.961 | 5.075 | 114.467 | 7.232 | 7.232 |
June | 365.069 | 9.778 | 11.644 | 10.090 | 10.090 |
July | 515.936 | 17.079 | 1.081 | 17.133 | 17.133 |
August | 542.947 | 18.650 | 0.667 | 18.682 | 18.682 |
September | 407.271 | 12.763 | 13.986 | 13.106 | 13.106 |
October | 418.017 | 12.786 | 45.481 | 13.721 | 13.721 |
November | 206.969 | 4.284 | 177.747 | 8.693 | 8.693 |
December | 194.764 | 4.211 | 239.181 | 11.211 | 11.211 |
Annual Sum or Average | 3613.138 | 100.312 | 1556.423 | 140.721 | 140.721 |
Minimum of Months | 127.306 | 2.430 | 0.667 | 7.232 | 7.232 |
Maximum of Months | 542.947 | 18.650 | 319.459 | 18.682 | 18.682 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 69.361 | 1.064 | 363.797 | 17.448 | 17.448 |
February | 65.028 | 0.956 | 343.792 | 13.396 | 13.396 |
March | 94.972 | 2.225 | 385.153 | 16.911 | 16.911 |
April | 222.097 | 6.826 | 172.034 | 11.836 | 11.836 |
May | 238.319 | 6.813 | 132.731 | 10.746 | 10.746 |
June | 359.475 | 12.039 | 16.517 | 12.903 | 12.903 |
July | 522.617 | 19.020 | 1.194 | 19.102 | 19.102 |
August | 520.214 | 19.036 | 1.747 | 19.146 | 19.146 |
September | 374.789 | 12.527 | 17.533 | 13.291 | 13.291 |
October | 361.817 | 10.323 | 73.544 | 12.878 | 12.878 |
November | 103.000 | 1.565 | 285.449 | 11.498 | 11.498 |
December | 73.564 | 1.167 | 360.250 | 16.699 | 16.699 |
Annual Sum or Average | 3005.253 | 93.561 | 2153.741 | 175.852 | 175.852 |
Minimum of Months | 65.028 | 0.956 | 1.194 | 10.746 | 10.746 |
Maximum of Months | 522.617 | 19.036 | 385.153 | 19.146 | 19.146 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 50.944 | 0.550 | 345.986 | 10.295 | 10.295 |
February | 11.778 | 0.071 | 324.236 | 7.390 | 7.390 |
March | 53.736 | 0.587 | 360.383 | 9.185 | 9.185 |
April | 175.278 | 2.700 | 119.492 | 5.454 | 5.454 |
May | 192.958 | 2.729 | 81.203 | 4.894 | 4.894 |
June | 369.667 | 6.869 | 6.519 | 7.225 | 7.225 |
July | 548.258 | 12.348 | 0.722 | 12.385 | 12.385 |
August | 549.194 | 12.850 | 0.839 | 12.887 | 12.887 |
September | 389.940 | 7.990 | 6.817 | 8.332 | 8.332 |
October | 355.008 | 6.847 | 41.925 | 8.065 | 8.065 |
November | 50.389 | 0.438 | 247.156 | 6.224 | 6.224 |
December | 46.986 | 0.396 | 344.794 | 9.511 | 9.511 |
Annual Sum or Average | 2794.138 | 54.374 | 1880.072 | 101.846 | 101.846 |
Minimum of Months | 11.778 | 0.071 | 0.722 | 4.894 | 4.894 |
Maximum of Months | 549.194 | 12.850 | 360.383 | 12.887 | 12.887 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 60.875 | 0.769 | 341.339 | 11.154 | 11.154 |
February | 31.250 | 0.237 | 324.372 | 8.248 | 8.248 |
March | 80.211 | 1.319 | 353.370 | 10.497 | 10.497 |
April | 233.108 | 4.937 | 140.583 | 7.465 | 7.465 |
May | 244.342 | 4.790 | 112.225 | 6.791 | 6.791 |
June | 368.214 | 10.018 | 12.594 | 10.304 | 10.304 |
July | 519.761 | 17.121 | 1.006 | 17.167 | 17.167 |
August | 530.331 | 17.578 | 0.653 | 17.608 | 17.608 |
September | 382.053 | 10.360 | 16.089 | 10.757 | 10.757 |
October | 378.844 | 8.528 | 55.769 | 9.717 | 9.717 |
November | 69.003 | 0.670 | 249.878 | 6.895 | 6.895 |
December | 64.208 | 0.658 | 352.844 | 10.628 | 10.628 |
Annual Sum or Average | 2962.200 | 76.987 | 1960.723 | 127.230 | 127.230 |
Minimum of Months | 31.250 | 0.237 | 0.653 | 6.791 | 6.791 |
Maximum of Months | 530.331 | 17.578 | 353.370 | 17.608 | 17.608 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 832.11 | 0.00 | 0.00 |
February | 802.96 | 0.00 | 0.00 |
March | 944.13 | 0.00 | 0.00 |
April | 436.94 | 0.00 | 0.00 |
May | 387.32 | 0.00 | 0.00 |
June | 75.17 | 0.00 | 0.00 |
July | 11.59 | 0.00 | 0.00 |
August | 9.55 | 0.00 | 0.00 |
September | 37.31 | 0.00 | 0.00 |
October | 165.55 | 0.00 | 0.00 |
November | 541.76 | 0.00 | 0.00 |
December | 772.56 | 0.00 | 0.00 |
Annual Sum or Average | 416.51 | 0.00 | 0.00 |
Minimum of Months | 9.55 | 0.00 | 0.00 |
Maximum of Months | 944.13 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 630.40 | 0.00 | 0.00 |
February | 638.48 | 0.00 | 0.00 |
March | 786.28 | 0.00 | 0.00 |
April | 355.10 | 0.00 | 0.00 |
May | 353.55 | 0.00 | 0.00 |
June | 59.58 | 0.00 | 0.00 |
July | 5.56 | 0.00 | 0.00 |
August | 3.57 | 0.00 | 0.00 |
September | 23.51 | 0.00 | 0.00 |
October | 113.98 | 0.00 | 0.00 |
November | 398.74 | 0.00 | 0.00 |
December | 574.04 | 0.00 | 0.00 |
Annual Sum or Average | 327.33 | 0.00 | 0.00 |
Minimum of Months | 3.57 | 0.00 | 0.00 |
Maximum of Months | 786.28 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 788.17 | 0.00 | 0.00 |
February | 780.85 | 0.00 | 0.00 |
March | 909.31 | 0.00 | 0.00 |
April | 375.88 | 0.00 | 0.00 |
May | 343.16 | 0.00 | 0.00 |
June | 45.42 | 0.00 | 0.00 |
July | 6.01 | 0.00 | 0.00 |
August | 5.65 | 0.00 | 0.00 |
September | 29.68 | 0.00 | 0.00 |
October | 131.27 | 0.00 | 0.00 |
November | 505.13 | 0.00 | 0.00 |
December | 734.79 | 0.00 | 0.00 |
Annual Sum or Average | 386.35 | 0.00 | 0.00 |
Minimum of Months | 5.65 | 0.00 | 0.00 |
Maximum of Months | 909.31 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1154.73 | 0.00 | 0.00 |
February | 1017.64 | 0.00 | 0.00 |
March | 1082.99 | 0.00 | 0.00 |
April | 497.01 | 0.00 | 0.00 |
May | 393.28 | 0.00 | 0.00 |
June | 70.25 | 0.00 | 0.00 |
July | 9.33 | 0.00 | 0.00 |
August | 9.48 | 0.00 | 0.00 |
September | 49.15 | 0.00 | 0.00 |
October | 222.64 | 0.00 | 0.00 |
November | 769.86 | 0.00 | 0.00 |
December | 1088.00 | 0.00 | 0.00 |
Annual Sum or Average | 528.37 | 0.00 | 0.00 |
Minimum of Months | 9.33 | 0.00 | 0.00 |
Maximum of Months | 1154.73 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1011.56 | 0.00 | 0.00 |
February | 920.71 | 0.00 | 0.00 |
March | 987.17 | 0.00 | 0.00 |
April | 460.29 | 0.00 | 0.00 |
May | 363.63 | 0.00 | 0.00 |
June | 51.75 | 0.00 | 0.00 |
July | 5.79 | 0.00 | 0.00 |
August | 4.86 | 0.00 | 0.00 |
September | 36.90 | 0.00 | 0.00 |
October | 191.49 | 0.00 | 0.00 |
November | 675.14 | 0.00 | 0.00 |
December | 954.82 | 0.00 | 0.00 |
Annual Sum or Average | 470.14 | 0.00 | 0.00 |
Minimum of Months | 4.86 | 0.00 | 0.00 |
Maximum of Months | 1011.56 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1126.16 | 0.00 | 0.00 |
February | 1023.08 | 0.00 | 0.00 |
March | 1062.12 | 0.00 | 0.00 |
April | 443.16 | 0.00 | 0.00 |
May | 349.80 | 0.00 | 0.00 |
June | 48.36 | 0.00 | 0.00 |
July | 5.63 | 0.00 | 0.00 |
August | 3.38 | 0.00 | 0.00 |
September | 33.94 | 0.00 | 0.00 |
October | 183.71 | 0.00 | 0.00 |
November | 759.66 | 0.00 | 0.00 |
December | 1072.81 | 0.00 | 0.00 |
Annual Sum or Average | 507.16 | 0.00 | 0.00 |
Minimum of Months | 3.38 | 0.00 | 0.00 |
Maximum of Months | 1126.16 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 506.07 | 0.00 | 0.00 |
February | 460.89 | 0.00 | 0.00 |
March | 569.40 | 0.00 | 0.00 |
April | 198.85 | 0.00 | 0.00 |
May | 174.05 | 0.00 | 0.00 |
June | 29.48 | 0.00 | 0.00 |
July | 3.05 | 0.00 | 0.00 |
August | 2.36 | 0.00 | 0.00 |
September | 21.90 | 0.00 | 0.00 |
October | 74.89 | 0.00 | 0.00 |
November | 296.16 | 0.00 | 0.00 |
December | 458.32 | 0.00 | 0.00 |
Annual Sum or Average | 232.13 | 0.00 | 0.00 |
Minimum of Months | 2.36 | 0.00 | 0.00 |
Maximum of Months | 569.40 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 318.33 | 0.00 | 0.00 |
February | 314.03 | 0.00 | 0.00 |
March | 417.04 | 0.00 | 0.00 |
April | 141.89 | 0.00 | 0.00 |
May | 129.58 | 0.00 | 0.00 |
June | 20.75 | 0.00 | 0.00 |
July | 0.39 | 0.00 | 0.00 |
August | 0.25 | 0.00 | 0.00 |
September | 11.16 | 0.00 | 0.00 |
October | 36.46 | 0.00 | 0.00 |
November | 169.46 | 0.00 | 0.00 |
December | 286.26 | 0.00 | 0.00 |
Annual Sum or Average | 153.23 | 0.00 | 0.00 |
Minimum of Months | 0.25 | 0.00 | 0.00 |
Maximum of Months | 417.04 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 447.75 | 0.00 | 0.00 |
February | 434.42 | 0.00 | 0.00 |
March | 526.42 | 0.00 | 0.00 |
April | 134.64 | 0.00 | 0.00 |
May | 118.22 | 0.00 | 0.00 |
June | 21.29 | 0.00 | 0.00 |
July | 0.66 | 0.00 | 0.00 |
August | 0.89 | 0.00 | 0.00 |
September | 13.32 | 0.00 | 0.00 |
October | 44.91 | 0.00 | 0.00 |
November | 250.08 | 0.00 | 0.00 |
December | 412.49 | 0.00 | 0.00 |
Annual Sum or Average | 199.55 | 0.00 | 0.00 |
Minimum of Months | 0.66 | 0.00 | 0.00 |
Maximum of Months | 526.42 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 796.54 | 0.00 | 0.00 |
February | 636.48 | 0.00 | 0.00 |
March | 687.57 | 0.00 | 0.00 |
April | 240.94 | 0.00 | 0.00 |
May | 169.87 | 0.00 | 0.00 |
June | 32.93 | 0.00 | 0.00 |
July | 1.82 | 0.00 | 0.00 |
August | 2.58 | 0.00 | 0.00 |
September | 27.77 | 0.00 | 0.00 |
October | 118.69 | 0.00 | 0.00 |
November | 474.98 | 0.00 | 0.00 |
December | 748.36 | 0.00 | 0.00 |
Annual Sum or Average | 327.15 | 0.00 | 0.00 |
Minimum of Months | 1.82 | 0.00 | 0.00 |
Maximum of Months | 796.54 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 653.99 | 0.00 | 0.00 |
February | 540.28 | 0.00 | 0.00 |
March | 567.48 | 0.00 | 0.00 |
April | 190.67 | 0.00 | 0.00 |
May | 138.52 | 0.00 | 0.00 |
June | 13.24 | 0.00 | 0.00 |
July | 0.23 | 0.00 | 0.00 |
August | 0.20 | 0.00 | 0.00 |
September | 15.86 | 0.00 | 0.00 |
October | 79.74 | 0.00 | 0.00 |
November | 394.21 | 0.00 | 0.00 |
December | 607.73 | 0.00 | 0.00 |
Annual Sum or Average | 265.84 | 0.00 | 0.00 |
Minimum of Months | 0.20 | 0.00 | 0.00 |
Maximum of Months | 653.99 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 755.53 | 0.00 | 0.00 |
February | 628.52 | 0.00 | 0.00 |
March | 649.00 | 0.00 | 0.00 |
April | 165.94 | 0.00 | 0.00 |
May | 117.30 | 0.00 | 0.00 |
June | 20.15 | 0.00 | 0.00 |
July | 0.50 | 0.00 | 0.00 |
August | 1.48 | 0.00 | 0.00 |
September | 18.88 | 0.00 | 0.00 |
October | 64.04 | 0.00 | 0.00 |
November | 448.91 | 0.00 | 0.00 |
December | 712.82 | 0.00 | 0.00 |
Annual Sum or Average | 297.36 | 0.00 | 0.00 |
Minimum of Months | 0.50 | 0.00 | 0.00 |
Maximum of Months | 755.53 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 752.92 | 0.00 | 0.00 |
February | 697.86 | 0.00 | 0.00 |
March | 841.57 | 0.00 | 0.00 |
April | 298.58 | 0.00 | 0.00 |
May | 257.96 | 0.00 | 0.00 |
June | 55.35 | 0.00 | 0.00 |
July | 7.22 | 0.00 | 0.00 |
August | 7.27 | 0.00 | 0.00 |
September | 46.90 | 0.00 | 0.00 |
October | 121.12 | 0.00 | 0.00 |
November | 465.23 | 0.00 | 0.00 |
December | 689.54 | 0.00 | 0.00 |
Annual Sum or Average | 352.13 | 0.00 | 0.00 |
Minimum of Months | 7.22 | 0.00 | 0.00 |
Maximum of Months | 841.57 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 525.07 | 0.00 | 0.00 |
February | 507.63 | 0.00 | 0.00 |
March | 657.98 | 0.00 | 0.00 |
April | 215.81 | 0.00 | 0.00 |
May | 193.35 | 0.00 | 0.00 |
June | 41.38 | 0.00 | 0.00 |
July | 3.02 | 0.00 | 0.00 |
August | 2.43 | 0.00 | 0.00 |
September | 25.01 | 0.00 | 0.00 |
October | 69.20 | 0.00 | 0.00 |
November | 297.85 | 0.00 | 0.00 |
December | 475.30 | 0.00 | 0.00 |
Annual Sum or Average | 250.22 | 0.00 | 0.00 |
Minimum of Months | 2.43 | 0.00 | 0.00 |
Maximum of Months | 657.98 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 685.68 | 0.00 | 0.00 |
February | 657.96 | 0.00 | 0.00 |
March | 784.33 | 0.00 | 0.00 |
April | 229.97 | 0.00 | 0.00 |
May | 195.93 | 0.00 | 0.00 |
June | 29.27 | 0.00 | 0.00 |
July | 4.92 | 0.00 | 0.00 |
August | 2.87 | 0.00 | 0.00 |
September | 32.13 | 0.00 | 0.00 |
October | 84.97 | 0.00 | 0.00 |
November | 414.03 | 0.00 | 0.00 |
December | 635.95 | 0.00 | 0.00 |
Annual Sum or Average | 311.83 | 0.00 | 0.00 |
Minimum of Months | 2.87 | 0.00 | 0.00 |
Maximum of Months | 784.33 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1058.28 | 0.00 | 0.00 |
February | 889.68 | 0.00 | 0.00 |
March | 948.57 | 0.00 | 0.00 |
April | 334.37 | 0.00 | 0.00 |
May | 254.05 | 0.00 | 0.00 |
June | 57.68 | 0.00 | 0.00 |
July | 5.34 | 0.00 | 0.00 |
August | 7.07 | 0.00 | 0.00 |
September | 50.94 | 0.00 | 0.00 |
October | 164.98 | 0.00 | 0.00 |
November | 663.00 | 0.00 | 0.00 |
December | 1003.26 | 0.00 | 0.00 |
Annual Sum or Average | 451.45 | 0.00 | 0.00 |
Minimum of Months | 5.34 | 0.00 | 0.00 |
Maximum of Months | 1058.28 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 890.81 | 0.00 | 0.00 |
February | 740.84 | 0.00 | 0.00 |
March | 786.04 | 0.00 | 0.00 |
April | 260.17 | 0.00 | 0.00 |
May | 197.91 | 0.00 | 0.00 |
June | 33.58 | 0.00 | 0.00 |
July | 3.34 | 0.00 | 0.00 |
August | 3.39 | 0.00 | 0.00 |
September | 32.32 | 0.00 | 0.00 |
October | 111.37 | 0.00 | 0.00 |
November | 546.61 | 0.00 | 0.00 |
December | 833.36 | 0.00 | 0.00 |
Annual Sum or Average | 368.59 | 0.00 | 0.00 |
Minimum of Months | 3.34 | 0.00 | 0.00 |
Maximum of Months | 890.81 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1005.75 | 0.00 | 0.00 |
February | 859.04 | 0.00 | 0.00 |
March | 888.92 | 0.00 | 0.00 |
April | 252.99 | 0.00 | 0.00 |
May | 193.81 | 0.00 | 0.00 |
June | 28.61 | 0.00 | 0.00 |
July | 4.47 | 0.00 | 0.00 |
August | 2.82 | 0.00 | 0.00 |
September | 39.70 | 0.00 | 0.00 |
October | 115.13 | 0.00 | 0.00 |
November | 622.93 | 0.00 | 0.00 |
December | 965.68 | 0.00 | 0.00 |
Annual Sum or Average | 413.30 | 0.00 | 0.00 |
Minimum of Months | 2.82 | 0.00 | 0.00 |
Maximum of Months | 1005.75 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.07 |
July | 0.00 | 0.00 | 0.12 |
August | 0.00 | 0.00 | 0.14 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.08 |
November | 0.00 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.14 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.02 |
July | 0.00 | 0.00 | 0.07 |
August | 0.00 | 0.00 | 0.09 |
September | 0.00 | 0.00 | 0.07 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.09 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.11 |
August | 0.00 | 0.00 | 0.13 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.13 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.07 |
July | 0.00 | 0.00 | 0.12 |
August | 0.00 | 0.00 | 0.12 |
September | 0.00 | 0.00 | 0.07 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.12 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.02 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.03 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.10 |
August | 0.00 | 0.00 | 0.11 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.11 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.08 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.11 |
July | 0.00 | 0.00 | 0.18 |
August | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.14 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.12 |
August | 0.00 | 0.00 | 0.14 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.11 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.14 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.13 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.03 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.11 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.17 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.08 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.12 |
August | 0.00 | 0.00 | 0.12 |
September | 0.00 | 0.00 | 0.07 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.12 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.16 |
August | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.16 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.08 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.20 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.14 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.20 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.03 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.07 |
July | 0.00 | 0.00 | 0.13 |
August | 0.00 | 0.00 | 0.15 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.11 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.15 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.18 |
August | 0.00 | 0.00 | 0.20 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.13 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.03 |
Maximum of Months | 0.00 | 0.00 | 0.20 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.19 |
August | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.10 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.19 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.07 |
July | 0.00 | 0.00 | 0.13 |
August | 0.00 | 0.00 | 0.13 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.13 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.11 |
July | 0.00 | 0.00 | 0.18 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.08 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.18 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.44 | 57.68 |
February | 0.00 | 0.00 | 63.28 | 52.46 |
March | 0.00 | 0.00 | 61.13 | 56.99 |
April | 0.00 | 0.00 | 59.08 | 54.09 |
May | 0.00 | 0.00 | 56.60 | 53.58 |
June | 0.00 | 0.00 | 53.46 | 50.09 |
July | 0.00 | 0.00 | 51.55 | 50.81 |
August | 0.00 | 0.00 | 51.02 | 50.55 |
September | 0.00 | 0.00 | 53.04 | 49.93 |
October | 0.00 | 0.00 | 56.49 | 53.21 |
November | 0.00 | 0.00 | 60.58 | 53.53 |
December | 0.00 | 0.00 | 63.86 | 56.92 |
Annual Sum or Average | 0.00 | 0.00 | 57.76 | 639.84 |
Minimum of Months | 0.00 | 0.00 | 51.02 | 49.93 |
Maximum of Months | 0.00 | 0.00 | 63.86 | 57.68 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.61 | 57.85 |
February | 0.00 | 0.00 | 63.05 | 52.28 |
March | 0.00 | 0.00 | 61.33 | 57.23 |
April | 0.00 | 0.00 | 58.52 | 53.72 |
May | 0.00 | 0.00 | 56.54 | 53.63 |
June | 0.00 | 0.00 | 53.23 | 50.07 |
July | 0.00 | 0.00 | 51.38 | 50.93 |
August | 0.00 | 0.00 | 50.81 | 50.58 |
September | 0.00 | 0.00 | 52.86 | 49.91 |
October | 0.00 | 0.00 | 56.55 | 53.30 |
November | 0.00 | 0.00 | 60.14 | 53.18 |
December | 0.00 | 0.00 | 63.86 | 56.92 |
Annual Sum or Average | 0.00 | 0.00 | 57.63 | 639.60 |
Minimum of Months | 0.00 | 0.00 | 50.81 | 49.91 |
Maximum of Months | 0.00 | 0.00 | 63.86 | 57.85 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.43 | 57.68 |
February | 0.00 | 0.00 | 63.26 | 52.45 |
March | 0.00 | 0.00 | 61.35 | 57.21 |
April | 0.00 | 0.00 | 58.76 | 53.90 |
May | 0.00 | 0.00 | 56.25 | 53.32 |
June | 0.00 | 0.00 | 53.72 | 50.41 |
July | 0.00 | 0.00 | 51.48 | 50.72 |
August | 0.00 | 0.00 | 51.19 | 50.65 |
September | 0.00 | 0.00 | 53.05 | 49.97 |
October | 0.00 | 0.00 | 56.35 | 53.17 |
November | 0.00 | 0.00 | 60.10 | 53.15 |
December | 0.00 | 0.00 | 64.16 | 57.20 |
Annual Sum or Average | 0.00 | 0.00 | 57.73 | 639.83 |
Minimum of Months | 0.00 | 0.00 | 51.19 | 49.97 |
Maximum of Months | 0.00 | 0.00 | 64.16 | 57.68 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.55 | 57.71 |
February | 0.00 | 0.00 | 63.21 | 52.37 |
March | 0.00 | 0.00 | 61.21 | 57.11 |
April | 0.00 | 0.00 | 59.01 | 54.07 |
May | 0.00 | 0.00 | 56.62 | 53.60 |
June | 0.00 | 0.00 | 53.49 | 50.12 |
July | 0.00 | 0.00 | 51.52 | 50.78 |
August | 0.00 | 0.00 | 51.19 | 50.82 |
September | 0.00 | 0.00 | 52.89 | 49.91 |
October | 0.00 | 0.00 | 56.44 | 53.19 |
November | 0.00 | 0.00 | 60.13 | 53.12 |
December | 0.00 | 0.00 | 64.01 | 56.95 |
Annual Sum or Average | 0.00 | 0.00 | 57.74 | 639.77 |
Minimum of Months | 0.00 | 0.00 | 51.19 | 49.91 |
Maximum of Months | 0.00 | 0.00 | 64.01 | 57.71 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.77 | 57.93 |
February | 0.00 | 0.00 | 63.00 | 52.16 |
March | 0.00 | 0.00 | 61.48 | 57.35 |
April | 0.00 | 0.00 | 58.44 | 53.66 |
May | 0.00 | 0.00 | 56.48 | 53.59 |
June | 0.00 | 0.00 | 53.50 | 50.36 |
July | 0.00 | 0.00 | 51.11 | 50.70 |
August | 0.00 | 0.00 | 50.88 | 50.84 |
September | 0.00 | 0.00 | 52.66 | 49.93 |
October | 0.00 | 0.00 | 56.34 | 53.19 |
November | 0.00 | 0.00 | 60.14 | 53.13 |
December | 0.00 | 0.00 | 64.04 | 56.96 |
Annual Sum or Average | 0.00 | 0.00 | 57.63 | 639.80 |
Minimum of Months | 0.00 | 0.00 | 50.88 | 49.93 |
Maximum of Months | 0.00 | 0.00 | 64.04 | 57.93 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.57 | 57.71 |
February | 0.00 | 0.00 | 63.24 | 52.37 |
March | 0.00 | 0.00 | 61.22 | 57.11 |
April | 0.00 | 0.00 | 58.93 | 54.07 |
May | 0.00 | 0.00 | 56.54 | 53.63 |
June | 0.00 | 0.00 | 53.39 | 50.10 |
July | 0.00 | 0.00 | 51.49 | 50.76 |
August | 0.00 | 0.00 | 50.96 | 50.56 |
September | 0.00 | 0.00 | 52.77 | 49.94 |
October | 0.00 | 0.00 | 56.37 | 53.23 |
November | 0.00 | 0.00 | 60.65 | 53.56 |
December | 0.00 | 0.00 | 64.08 | 56.99 |
Annual Sum or Average | 0.00 | 0.00 | 57.74 | 640.04 |
Minimum of Months | 0.00 | 0.00 | 50.96 | 49.94 |
Maximum of Months | 0.00 | 0.00 | 64.08 | 57.71 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.29 | 57.75 |
February | 0.00 | 0.00 | 63.03 | 52.39 |
March | 0.00 | 0.00 | 61.06 | 57.02 |
April | 0.00 | 0.00 | 58.95 | 53.97 |
May | 0.00 | 0.00 | 56.30 | 53.30 |
June | 0.00 | 0.00 | 53.89 | 50.39 |
July | 0.00 | 0.00 | 51.88 | 50.80 |
August | 0.00 | 0.00 | 51.49 | 50.66 |
September | 0.00 | 0.00 | 53.22 | 49.91 |
October | 0.00 | 0.00 | 56.30 | 52.92 |
November | 0.00 | 0.00 | 60.32 | 53.47 |
December | 0.00 | 0.00 | 63.52 | 56.91 |
Annual Sum or Average | 0.00 | 0.00 | 57.74 | 639.50 |
Minimum of Months | 0.00 | 0.00 | 51.49 | 49.91 |
Maximum of Months | 0.00 | 0.00 | 63.52 | 57.75 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.29 | 57.77 |
February | 0.00 | 0.00 | 63.03 | 52.44 |
March | 0.00 | 0.00 | 60.86 | 56.92 |
April | 0.00 | 0.00 | 58.60 | 53.80 |
May | 0.00 | 0.00 | 56.39 | 53.58 |
June | 0.00 | 0.00 | 53.38 | 50.06 |
July | 0.00 | 0.00 | 51.95 | 51.08 |
August | 0.00 | 0.00 | 51.22 | 50.54 |
September | 0.00 | 0.00 | 53.20 | 49.96 |
October | 0.00 | 0.00 | 56.44 | 53.12 |
November | 0.00 | 0.00 | 59.79 | 53.07 |
December | 0.00 | 0.00 | 63.75 | 57.16 |
Annual Sum or Average | 0.00 | 0.00 | 57.63 | 639.49 |
Minimum of Months | 0.00 | 0.00 | 51.22 | 49.96 |
Maximum of Months | 0.00 | 0.00 | 63.75 | 57.77 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.34 | 57.80 |
February | 0.00 | 0.00 | 63.03 | 52.43 |
March | 0.00 | 0.00 | 61.02 | 57.02 |
April | 0.00 | 0.00 | 58.57 | 53.70 |
May | 0.00 | 0.00 | 56.47 | 53.57 |
June | 0.00 | 0.00 | 53.62 | 50.13 |
July | 0.00 | 0.00 | 51.97 | 50.84 |
August | 0.00 | 0.00 | 51.59 | 50.65 |
September | 0.00 | 0.00 | 53.22 | 49.93 |
October | 0.00 | 0.00 | 56.42 | 53.14 |
November | 0.00 | 0.00 | 59.94 | 53.19 |
December | 0.00 | 0.00 | 63.67 | 57.05 |
Annual Sum or Average | 0.00 | 0.00 | 57.71 | 639.45 |
Minimum of Months | 0.00 | 0.00 | 51.59 | 49.93 |
Maximum of Months | 0.00 | 0.00 | 63.67 | 57.80 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.48 | 57.90 |
February | 0.00 | 0.00 | 62.72 | 52.13 |
March | 0.00 | 0.00 | 61.07 | 57.09 |
April | 0.00 | 0.00 | 58.85 | 53.94 |
May | 0.00 | 0.00 | 56.55 | 53.58 |
June | 0.00 | 0.00 | 53.62 | 50.08 |
July | 0.00 | 0.00 | 51.83 | 50.77 |
August | 0.00 | 0.00 | 51.61 | 50.88 |
September | 0.00 | 0.00 | 53.05 | 49.91 |
October | 0.00 | 0.00 | 56.22 | 52.90 |
November | 0.00 | 0.00 | 60.14 | 53.35 |
December | 0.00 | 0.00 | 63.96 | 57.20 |
Annual Sum or Average | 0.00 | 0.00 | 57.73 | 639.74 |
Minimum of Months | 0.00 | 0.00 | 51.61 | 49.91 |
Maximum of Months | 0.00 | 0.00 | 63.96 | 57.90 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.50 | 57.90 |
February | 0.00 | 0.00 | 63.01 | 52.39 |
March | 0.00 | 0.00 | 60.90 | 56.99 |
April | 0.00 | 0.00 | 58.60 | 53.93 |
May | 0.00 | 0.00 | 56.06 | 53.27 |
June | 0.00 | 0.00 | 53.75 | 50.42 |
July | 0.00 | 0.00 | 51.62 | 50.74 |
August | 0.00 | 0.00 | 51.10 | 50.57 |
September | 0.00 | 0.00 | 52.76 | 49.82 |
October | 0.00 | 0.00 | 56.41 | 53.18 |
November | 0.00 | 0.00 | 60.30 | 53.49 |
December | 0.00 | 0.00 | 63.78 | 57.03 |
Annual Sum or Average | 0.00 | 0.00 | 57.62 | 639.75 |
Minimum of Months | 0.00 | 0.00 | 51.10 | 49.82 |
Maximum of Months | 0.00 | 0.00 | 63.78 | 57.90 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.52 | 57.90 |
February | 0.00 | 0.00 | 62.84 | 52.25 |
March | 0.00 | 0.00 | 61.18 | 57.21 |
April | 0.00 | 0.00 | 58.43 | 53.68 |
May | 0.00 | 0.00 | 56.49 | 53.61 |
June | 0.00 | 0.00 | 53.61 | 50.14 |
July | 0.00 | 0.00 | 51.94 | 50.84 |
August | 0.00 | 0.00 | 51.46 | 50.64 |
September | 0.00 | 0.00 | 52.99 | 49.91 |
October | 0.00 | 0.00 | 56.34 | 53.15 |
November | 0.00 | 0.00 | 60.07 | 53.26 |
December | 0.00 | 0.00 | 63.91 | 57.09 |
Annual Sum or Average | 0.00 | 0.00 | 57.70 | 639.66 |
Minimum of Months | 0.00 | 0.00 | 51.46 | 49.91 |
Maximum of Months | 0.00 | 0.00 | 63.91 | 57.90 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.40 | 57.66 |
February | 0.00 | 0.00 | 63.22 | 52.42 |
March | 0.00 | 0.00 | 61.27 | 57.10 |
April | 0.00 | 0.00 | 59.07 | 54.02 |
May | 0.00 | 0.00 | 56.37 | 53.30 |
June | 0.00 | 0.00 | 53.92 | 50.38 |
July | 0.00 | 0.00 | 51.81 | 50.81 |
August | 0.00 | 0.00 | 51.34 | 50.61 |
September | 0.00 | 0.00 | 53.28 | 49.99 |
October | 0.00 | 0.00 | 56.39 | 52.93 |
November | 0.00 | 0.00 | 60.50 | 53.48 |
December | 0.00 | 0.00 | 63.75 | 56.88 |
Annual Sum or Average | 0.00 | 0.00 | 57.83 | 639.57 |
Minimum of Months | 0.00 | 0.00 | 51.34 | 49.99 |
Maximum of Months | 0.00 | 0.00 | 63.75 | 57.66 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.54 | 57.82 |
February | 0.00 | 0.00 | 63.01 | 52.26 |
March | 0.00 | 0.00 | 61.31 | 57.19 |
April | 0.00 | 0.00 | 58.62 | 53.71 |
May | 0.00 | 0.00 | 56.54 | 53.58 |
June | 0.00 | 0.00 | 53.43 | 50.06 |
July | 0.00 | 0.00 | 51.82 | 51.03 |
August | 0.00 | 0.00 | 51.15 | 50.59 |
September | 0.00 | 0.00 | 53.08 | 49.92 |
October | 0.00 | 0.00 | 56.57 | 53.17 |
November | 0.00 | 0.00 | 60.01 | 53.10 |
December | 0.00 | 0.00 | 64.00 | 57.15 |
Annual Sum or Average | 0.00 | 0.00 | 57.73 | 639.57 |
Minimum of Months | 0.00 | 0.00 | 51.15 | 49.92 |
Maximum of Months | 0.00 | 0.00 | 64.00 | 57.82 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.60 | 57.84 |
February | 0.00 | 0.00 | 63.01 | 52.24 |
March | 0.00 | 0.00 | 61.31 | 57.16 |
April | 0.00 | 0.00 | 58.93 | 53.94 |
May | 0.00 | 0.00 | 56.33 | 53.30 |
June | 0.00 | 0.00 | 53.62 | 50.11 |
July | 0.00 | 0.00 | 52.22 | 51.09 |
August | 0.00 | 0.00 | 51.55 | 50.65 |
September | 0.00 | 0.00 | 52.90 | 49.65 |
October | 0.00 | 0.00 | 56.71 | 53.26 |
November | 0.00 | 0.00 | 60.41 | 53.43 |
December | 0.00 | 0.00 | 63.77 | 56.92 |
Annual Sum or Average | 0.00 | 0.00 | 57.84 | 639.58 |
Minimum of Months | 0.00 | 0.00 | 51.55 | 49.65 |
Maximum of Months | 0.00 | 0.00 | 63.77 | 57.84 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.54 | 57.76 |
February | 0.00 | 0.00 | 63.41 | 52.54 |
March | 0.00 | 0.00 | 61.17 | 57.04 |
April | 0.00 | 0.00 | 58.72 | 53.71 |
May | 0.00 | 0.00 | 56.65 | 53.58 |
June | 0.00 | 0.00 | 53.63 | 50.08 |
July | 0.00 | 0.00 | 51.77 | 50.78 |
August | 0.00 | 0.00 | 51.31 | 50.64 |
September | 0.00 | 0.00 | 53.09 | 49.91 |
October | 0.00 | 0.00 | 56.77 | 53.34 |
November | 0.00 | 0.00 | 60.18 | 53.20 |
December | 0.00 | 0.00 | 64.03 | 57.03 |
Annual Sum or Average | 0.00 | 0.00 | 57.83 | 639.61 |
Minimum of Months | 0.00 | 0.00 | 51.31 | 49.91 |
Maximum of Months | 0.00 | 0.00 | 64.03 | 57.76 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.70 | 57.91 |
February | 0.00 | 0.00 | 62.92 | 52.15 |
March | 0.00 | 0.00 | 61.20 | 57.13 |
April | 0.00 | 0.00 | 58.97 | 54.07 |
May | 0.00 | 0.00 | 56.21 | 53.28 |
June | 0.00 | 0.00 | 53.76 | 50.40 |
July | 0.00 | 0.00 | 51.54 | 50.74 |
August | 0.00 | 0.00 | 51.09 | 50.60 |
September | 0.00 | 0.00 | 52.88 | 49.88 |
October | 0.00 | 0.00 | 56.63 | 53.27 |
November | 0.00 | 0.00 | 60.13 | 53.16 |
December | 0.00 | 0.00 | 63.93 | 56.94 |
Annual Sum or Average | 0.00 | 0.00 | 57.72 | 639.54 |
Minimum of Months | 0.00 | 0.00 | 51.09 | 49.88 |
Maximum of Months | 0.00 | 0.00 | 63.93 | 57.91 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 63.59 | 57.76 |
February | 0.00 | 0.00 | 63.23 | 52.38 |
March | 0.00 | 0.00 | 61.28 | 57.17 |
April | 0.00 | 0.00 | 58.87 | 53.94 |
May | 0.00 | 0.00 | 56.31 | 53.30 |
June | 0.00 | 0.00 | 53.61 | 50.11 |
July | 0.00 | 0.00 | 52.19 | 51.10 |
August | 0.00 | 0.00 | 51.45 | 50.63 |
September | 0.00 | 0.00 | 53.07 | 49.92 |
October | 0.00 | 0.00 | 56.31 | 52.96 |
November | 0.00 | 0.00 | 60.55 | 53.53 |
December | 0.00 | 0.00 | 63.91 | 56.90 |
Annual Sum or Average | 0.00 | 0.00 | 57.84 | 639.70 |
Minimum of Months | 0.00 | 0.00 | 51.45 | 49.92 |
Maximum of Months | 0.00 | 0.00 | 63.91 | 57.76 |
Report: HEATING AND COOLING LOADS
For: BREEZEWAY
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 33.76 | 426.38 |
February | 25.00 | 345.37 |
March | 24.71 | 480.20 |
April | 42.12 | 181.14 |
May | 35.93 | 163.51 |
June | 61.88 | 17.89 |
July | 89.92 | 1.85 |
August | 97.39 | 1.24 |
September | 84.35 | 7.71 |
October | 75.06 | 64.33 |
November | 39.47 | 246.90 |
December | 40.16 | 393.48 |
Annual Sum or Average | 649.76 | 2329.99 |
Minimum of Months | 24.71 | 1.24 |
Maximum of Months | 97.39 | 480.20 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 27.10 | 267.47 |
February | 17.71 | 219.84 |
March | 15.40 | 333.89 |
April | 22.74 | 110.91 |
May | 18.65 | 107.78 |
June | 36.04 | 11.70 |
July | 57.05 | 0.71 |
August | 66.50 | 0.34 |
September | 61.17 | 3.81 |
October | 58.04 | 29.71 |
November | 29.82 | 139.33 |
December | 32.27 | 238.21 |
Annual Sum or Average | 442.49 | 1463.70 |
Minimum of Months | 15.40 | 0.34 |
Maximum of Months | 66.50 | 333.89 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 32.17 | 404.76 |
February | 22.64 | 338.74 |
March | 22.86 | 464.59 |
April | 37.07 | 171.08 |
May | 29.53 | 153.52 |
June | 54.18 | 12.20 |
July | 83.51 | 1.20 |
August | 93.38 | 1.10 |
September | 76.08 | 7.17 |
October | 70.83 | 57.36 |
November | 35.52 | 236.28 |
December | 37.89 | 375.02 |
Annual Sum or Average | 595.68 | 2223.04 |
Minimum of Months | 22.64 | 1.10 |
Maximum of Months | 93.38 | 464.59 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 12.03 | 578.89 |
February | 10.39 | 435.87 |
March | 12.38 | 541.06 |
April | 29.84 | 204.02 |
May | 32.80 | 162.24 |
June | 61.59 | 16.75 |
July | 87.05 | 1.25 |
August | 84.95 | 1.32 |
September | 63.28 | 11.57 |
October | 47.11 | 79.36 |
November | 15.21 | 336.72 |
December | 14.04 | 536.14 |
Annual Sum or Average | 470.68 | 2905.18 |
Minimum of Months | 10.39 | 1.25 |
Maximum of Months | 87.05 | 578.89 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 8.06 | 414.07 |
February | 5.93 | 312.53 |
March | 6.24 | 407.85 |
April | 14.39 | 134.48 |
May | 17.53 | 109.16 |
June | 36.40 | 9.77 |
July | 54.19 | 0.86 |
August | 54.51 | 0.68 |
September | 40.49 | 6.51 |
October | 32.11 | 45.30 |
November | 10.64 | 224.42 |
December | 9.15 | 378.32 |
Annual Sum or Average | 289.62 | 2043.97 |
Minimum of Months | 5.93 | 0.68 |
Maximum of Months | 54.51 | 414.07 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 11.15 | 538.43 |
February | 9.77 | 430.18 |
March | 11.47 | 524.66 |
April | 25.75 | 196.82 |
May | 26.86 | 152.49 |
June | 53.54 | 11.44 |
July | 80.35 | 0.82 |
August | 80.51 | 0.54 |
September | 54.53 | 7.71 |
October | 42.45 | 71.46 |
November | 14.56 | 325.87 |
December | 12.00 | 500.22 |
Annual Sum or Average | 422.94 | 2760.63 |
Minimum of Months | 9.77 | 0.54 |
Maximum of Months | 80.51 | 538.43 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 56.69 | 237.83 |
February | 42.49 | 162.34 |
March | 42.67 | 251.13 |
April | 71.25 | 57.46 |
May | 62.61 | 55.71 |
June | 89.87 | 5.48 |
July | 124.84 | 0.32 |
August | 132.01 | 0.38 |
September | 111.57 | 4.28 |
October | 113.77 | 21.76 |
November | 63.04 | 113.04 |
December | 63.50 | 207.35 |
Annual Sum or Average | 974.29 | 1117.07 |
Minimum of Months | 42.49 | 0.32 |
Maximum of Months | 132.01 | 251.13 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 50.07 | 108.61 |
February | 34.86 | 72.55 |
March | 30.73 | 135.03 |
April | 46.05 | 27.54 |
May | 38.01 | 25.60 |
June | 59.02 | 3.20 |
July | 87.71 | 0.05 |
August | 97.87 | 0.01 |
September | 87.22 | 1.43 |
October | 96.28 | 4.97 |
November | 53.34 | 38.07 |
December | 56.19 | 85.11 |
Annual Sum or Average | 737.36 | 502.17 |
Minimum of Months | 30.73 | 0.01 |
Maximum of Months | 97.87 | 135.03 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 56.20 | 216.31 |
February | 40.16 | 159.23 |
March | 41.05 | 242.38 |
April | 66.40 | 49.11 |
May | 55.71 | 42.18 |
June | 80.51 | 4.54 |
July | 118.08 | 0.02 |
August | 128.62 | 0.06 |
September | 102.52 | 2.47 |
October | 109.82 | 15.26 |
November | 58.68 | 101.76 |
December | 61.43 | 192.70 |
Annual Sum or Average | 919.19 | 1026.04 |
Minimum of Months | 40.16 | 0.02 |
Maximum of Months | 128.62 | 242.38 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 20.69 | 370.43 |
February | 17.96 | 232.38 |
March | 23.62 | 305.03 |
April | 53.08 | 72.88 |
May | 58.88 | 52.25 |
June | 89.57 | 6.25 |
July | 122.18 | 0.29 |
August | 117.29 | 0.27 |
September | 85.55 | 6.14 |
October | 75.65 | 32.92 |
November | 24.81 | 176.93 |
December | 22.48 | 336.12 |
Annual Sum or Average | 711.76 | 1591.88 |
Minimum of Months | 17.96 | 0.27 |
Maximum of Months | 122.18 | 370.43 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 16.28 | 223.31 |
February | 12.29 | 130.10 |
March | 14.30 | 184.80 |
April | 29.52 | 36.61 |
May | 33.99 | 26.32 |
June | 60.22 | 1.89 |
July | 85.06 | 0.01 |
August | 83.18 | 0.00 |
September | 60.86 | 2.47 |
October | 57.45 | 11.85 |
November | 18.24 | 93.88 |
December | 16.86 | 194.13 |
Annual Sum or Average | 488.24 | 905.38 |
Minimum of Months | 12.29 | 0.00 |
Maximum of Months | 85.06 | 223.31 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 20.40 | 337.26 |
February | 16.11 | 232.14 |
March | 22.01 | 293.37 |
April | 47.18 | 57.81 |
May | 51.35 | 41.94 |
June | 80.76 | 4.01 |
July | 115.15 | 0.00 |
August | 113.68 | 0.26 |
September | 76.14 | 3.72 |
October | 70.50 | 20.79 |
November | 22.97 | 177.83 |
December | 21.55 | 313.82 |
Annual Sum or Average | 657.80 | 1482.95 |
Minimum of Months | 16.11 | 0.00 |
Maximum of Months | 115.15 | 337.26 |
Report: HEATING AND COOLING LOADS
For: ATTIC
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 20.87 | 519.11 |
February | 15.78 | 375.90 |
March | 24.36 | 462.13 |
April | 54.91 | 110.80 |
May | 54.88 | 84.69 |
June | 84.93 | 7.30 |
July | 124.12 | 0.63 |
August | 124.82 | 0.61 |
September | 84.77 | 10.10 |
October | 79.19 | 46.24 |
November | 23.13 | 288.22 |
December | 20.89 | 487.00 |
Annual Sum or Average | 712.67 | 2392.71 |
Minimum of Months | 15.78 | 0.61 |
Maximum of Months | 124.82 | 519.11 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 48.92 | 369.03 |
February | 34.87 | 291.55 |
March | 37.36 | 408.82 |
April | 66.50 | 100.98 |
May | 56.99 | 86.47 |
June | 83.88 | 7.68 |
July | 124.77 | 0.79 |
August | 133.11 | 0.48 |
September | 101.69 | 8.72 |
October | 110.45 | 35.88 |
November | 52.54 | 197.75 |
December | 54.51 | 342.47 |
Annual Sum or Average | 905.59 | 1850.63 |
Minimum of Months | 34.87 | 0.48 |
Maximum of Months | 133.11 | 408.82 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 51.28 | 410.31 |
February | 38.19 | 305.65 |
March | 40.09 | 435.30 |
April | 72.97 | 117.64 |
May | 65.09 | 100.01 |
June | 93.78 | 13.77 |
July | 132.01 | 1.09 |
August | 137.38 | 1.25 |
September | 111.40 | 12.82 |
October | 115.11 | 46.01 |
November | 57.21 | 213.76 |
December | 57.45 | 367.23 |
Annual Sum or Average | 971.95 | 2024.83 |
Minimum of Months | 38.19 | 1.09 |
Maximum of Months | 137.38 | 435.30 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 17.75 | 409.04 |
February | 12.36 | 267.41 |
March | 16.55 | 344.91 |
April | 37.10 | 71.10 |
May | 39.32 | 58.27 |
June | 64.61 | 6.68 |
July | 93.26 | 0.50 |
August | 94.31 | 0.31 |
September | 69.63 | 5.70 |
October | 66.98 | 28.71 |
November | 18.54 | 197.19 |
December | 18.05 | 371.91 |
Annual Sum or Average | 548.46 | 1761.73 |
Minimum of Months | 12.36 | 0.31 |
Maximum of Months | 94.31 | 409.04 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 44.13 | 238.72 |
February | 30.15 | 178.57 |
March | 28.45 | 285.77 |
April | 48.02 | 62.64 |
May | 41.33 | 57.60 |
June | 62.86 | 8.16 |
July | 93.96 | 0.39 |
August | 102.31 | 0.26 |
September | 86.19 | 4.77 |
October | 97.25 | 16.51 |
November | 47.28 | 101.51 |
December | 49.34 | 204.00 |
Annual Sum or Average | 731.27 | 1158.90 |
Minimum of Months | 28.45 | 0.26 |
Maximum of Months | 102.31 | 285.77 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:20:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 21.89 | 571.18 |
February | 18.90 | 395.22 |
March | 27.49 | 498.13 |
April | 62.11 | 131.47 |
May | 63.84 | 97.88 |
June | 94.41 | 12.41 |
July | 131.69 | 0.71 |
August | 129.51 | 1.10 |
September | 95.10 | 12.51 |
October | 85.83 | 60.51 |
November | 26.49 | 309.72 |
December | 23.75 | 530.63 |
Annual Sum or Average | 781.00 | 2621.48 |
Minimum of Months | 18.90 | 0.71 |
Maximum of Months | 131.69 | 571.18 |