Table of Contents

Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 19:32

Tabular Output Report in Format: HTML

Building: US+SF+CZ6A+gasfurnace+crawlspace+IECC_2024

Environment: ANNUAL ** Rochester International Arpt MN USA TMY3 WMO#=726440

Simulation Timestamp: 2024-06-27 19:32:11


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 115232.27 22.36 48.48
Net Site Energy 115232.27 22.36 48.48
Total Source Energy 206979.97 40.16 87.07
Net Source Energy 206979.97 40.16 87.07


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 5154.23
Net Conditioned Building Area 2377.10
Unconditioned Building Area 2777.13


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 49967.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 5665.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3542.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 721.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 24063.37 11013.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5405.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 14851.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14862.19
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 39399.03 75833.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14862.19
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 49967.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 5665.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 3542.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 646.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 75.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 703.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 2283.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 359.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_dryer 259.30 5282.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_range 0.00 4496.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 10247.12 1235.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10211.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 2414.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 2991.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14862.19
  Water Heater 0.00 14851.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Unassigned 0.00 49967.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 5665.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 3542.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 721.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 24063.37 11013.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 5405.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 14851.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14862.19
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 4.66 27.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.25
Other 10.12 4.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 16.57 31.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.25


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 0.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 2.15 12.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.88
Other 4.67 2.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 7.64 14.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.88


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 39399.034 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 39399.034 100.00
     
Total On-Site and Utility Electric Sources 39399.034 100.00
Total Electricity End Uses 39399.034 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 167.74 1.34
Air to Air Heat Recovery for Heating 12310.24 98.66
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 12477.97 100.00


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 14862.19 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 14862.19 100.00
Total Water End Uses 14862.19 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 67.50
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 2054.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Annual Thermal Resilience Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1 |

COILLOADS

| MAIN FUEL HEATING COIL_UNIT1 | DX COOLING COIL_UNIT1 |

WATER HEATER: LOADS

| WATER HEATER_UNIT1 |

HEATING AND COOLING LOADS

| LIVING_UNIT1 | GARAGE1 | ATTIC_UNIT1 | CRAWLSPACE_UNIT1 |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

General

Value
Program Version and Build EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 19:32
RunPeriod ANNUAL
Weather File Rochester International Arpt MN USA TMY3 WMO#=726440
Latitude [deg] 43.90
Longitude [deg] -92.5
Elevation [ft] 1305.84
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 3178.51 756.60 832.66 756.60 832.66
Above Ground Wall Area [ft2] 2969.45 696.86 787.86 696.86 787.86
Window Opening Area [ft2] 355.40 88.85 88.85 88.85 88.85
Gross Window-Wall Ratio [%] 11.18 11.74 10.67 11.74 10.67
Above Ground Window-Wall Ratio [%] 11.97 12.75 11.28 12.75 11.28


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 2199.28 676.95 507.72 506.89 507.72
Above Ground Wall Area [ft2] 2199.28 676.95 507.72 506.89 507.72
Window Opening Area [ft2] 355.40 88.85 88.85 88.85 88.85
Gross Window-Wall Ratio [%] 16.16 13.12 17.50 17.53 17.50
Above Ground Window-Wall Ratio [%] 16.16 13.12 17.50 17.53 17.50


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 1656.61
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
LIVING_UNIT1 2377.10 Yes Yes 17050.56 1.00 2199.28 0.00 355.40 355.40 0.4851 792.37 3.1791
GARAGE1 400.04 No Yes 3968.09 1.00 566.85 0.00 0.00 0.00 0.0000   0.0000
ATTIC_UNIT1 1188.55 No Yes 2659.93 1.00 133.64 0.00 0.00 0.00 0.0000   0.0000
CRAWLSPACE_UNIT1 1188.55 No Yes 2377.82 1.00 69.69 209.06 0.00 0.00 0.0000   0.0000
Total 5154.23     26056.40   2969.45 209.06 355.40 355.40 0.2237 1718.08 1.4662
Conditioned Total 2377.10     17050.56   2199.28 0.00 355.40 355.40 0.4851 792.37 3.1791
Unconditioned Total 2777.13     9005.84   770.17 209.06 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2] Tags
LIVING_UNIT1 2377.10 Yes Yes 1.00 LIVING_UNIT1 GENERAL LIVING_UNIT1 0.4851 792.37 3.1791  
GARAGE1 400.04 No Yes 1.00 GARAGE1 GENERAL GARAGE1 0.0000 0.00 0.0000  
ATTIC_UNIT1 1188.55 No Yes 1.00 ATTIC_UNIT1 GENERAL ATTIC_UNIT1 0.0000 0.00 0.0000  
CRAWLSPACE_UNIT1 1188.55 No Yes 1.00 CRAWLSPACE_UNIT1 GENERAL CRAWLSPACE_UNIT1 0.0000 0.00 0.0000  
Total 5154.23             0.2237 1718.08 1.4662  
Conditioned Total 2377.10             0.4851 792.37 3.1791  
Unconditioned Total 2777.13             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [ft2] Conditioned Area [ft2] Unconditioned Area [ft2] Not Part of Total Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
GENERAL 5154.23 2377.10 2777.13 0.00 0.2237 1718.08 1.4662
Total 5154.23 2377.10 2777.13 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 25-JUN-18:20 09-DEC-17:20 - - - - - - - - - - 04-FEB-08:30
Heating 0.00 34.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 5.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 1.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3.82 2.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 1.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 9.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 12.08 46.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 34.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 5.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 1.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 0.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 0.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 0.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_dryer 0.04 0.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_range 0.00 1.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 1.62 0.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 0.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.05
  Water Heater 0.00 9.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 54165.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 17943.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 11220.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2285.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 76208.69 11939.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 17117.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 16098.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 124776.74 82203.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 22.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 7.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 32.06 5.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 6.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 52.49 34.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 10.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 14.79 2.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 3.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 3.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 24.21 15.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

ZoneHVAC:EnergyRecoveryVentilator

User-Specified Supply Air Flow Rate [ft3/min] User-Specified Exhaust Air Flow Rate [ft3/min]
ERV_UNIT1 59.99 59.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

User-Specified Maximum Flow Rate [ft3/min] Design Size Maximum Flow Rate [ft3/min]
OASUPPLYFAN_UNIT1 59.99  
OAEXHAUSTFAN_UNIT1 59.99  
SUPPLY FAN_UNIT1   755.58
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

User-Specified Nominal Supply Air Flow Rate [ft3/min]
OA_HEAT_RECOVERY_UNIT1 59.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1 755.58
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1 755.58 755.58 755.58 755.58 755.58 755.58 1.00 1.00 755.58
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1 755.58 2.24 0.740013
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1 755.58 755.58 755.58 32619.87 2.24 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [Btu/h]
MAIN FUEL HEATING COIL_UNIT1 40774.83
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1 1.05 2.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1 1.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1 38002.17 1.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
OVERHANG_SDR_1.UNIT1 WALL_SDR_1.UNIT1 | WALL_SDR_1.GARAGE1 |
Mir-OVERHANG_SDR_1.UNIT1 OVERHANG_SDR_2.UNIT1 | WALL_SDR_1.UNIT1 | WALL_SDR_2.UNIT1 | WALL_SDR_1.GARAGE1 | ROOF_RIGHT_GARAGE1 | ROOF_BACK_GARAGE1 | ROOF_RIGHT_UNIT1 |
OVERHANG_SDR_2.UNIT1 WALL_SDR_2.UNIT1 |
Mir-OVERHANG_SDR_2.UNIT1 WALL_SDR_2.UNIT1 | ROOF_RIGHT_UNIT1 |
WALL_LDF_1.UNIT1 WALL_SDL_1.GARAGE1 | ROOF_LEFT_GARAGE1 |
WALL_SDR_1.UNIT1 OVERHANG_SDR_1.UNIT1 | OVERHANG_SDR_2.UNIT1 |
WALL_LDF_2.UNIT1 ROOF_LEFT_GARAGE1 | ROOF_FRONT_GARAGE1 | ROOF_BACK_GARAGE1 |
WALL_SDR_2.UNIT1 OVERHANG_SDR_2.UNIT1 |
WALL_SDR_1.GARAGE1 OVERHANG_SDR_1.UNIT1 | OVERHANG_SDR_2.UNIT1 |
WALL_SDL_1.GARAGE1 WALL_LDF_1.UNIT1 | WALL_LDF_2.UNIT1 |
ROOF_RIGHT_GARAGE1 OVERHANG_SDR_2.UNIT1 |
ROOF_LEFT_GARAGE1 WALL_LDF_2.UNIT1 |
ROOF_FRONT_GARAGE1 OVERHANG_SDR_2.UNIT1 | WALL_LDF_2.UNIT1 |
ROOF_BACK_GARAGE1 OVERHANG_SDR_2.UNIT1 | WALL_LDF_2.UNIT1 |
BGWALL_UPPER_LDF WALL_SDL_1.GARAGE1 | ROOF_LEFT_GARAGE1 |
BGWALL_UPPER_SDR OVERHANG_SDR_1.UNIT1 | OVERHANG_SDR_2.UNIT1 |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1 WINDOW_LDF_1.UNIT1 |
WALL_SDR_1.UNIT1 WINDOW_SDR_1.UNIT1 |
WALL_LDB_1.UNIT1 DOOR_LDB_UNIT1 | WINDOW_LDB_1.UNIT1 |
WALL_SDL_1.UNIT1 WINDOW_SDL_1.UNIT1 |
WALL_LDF_2.UNIT1 WINDOW_LDF_2.UNIT1 |
WALL_SDR_2.UNIT1 WINDOW_SDR_2.UNIT1 |
WALL_LDB_2.UNIT1 WINDOW_LDB_2.UNIT1 |
WALL_SDL_2.UNIT1 WINDOW_SDL_2.UNIT1 |
WALL_LDF_1.GARAGE1 DOOR_GARAGE1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Version

Version ID
1 23.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No Yes Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40


Site:GroundTemperature:FCfactorMethod

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 28.06 18.73 16.21 18.41 30.99 45.09 58.35 67.95 70.75 66.24 55.38 41.68


Site:GroundTemperature:Shallow

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40


Site:GroundTemperature:Deep

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {ft} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Sensor Height Above Ground {ft} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 32.810 0.140 885.870 4.921 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {ft} Standard Pressure at Elevation {psi} Standard RhoAir at Elevation
1 Rochester International Arpt MN USA TMY3 WMO#=726440 43.90 -92.50 -6.00 1305.84 14. 1.1486


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{F} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} Fixed Default Water Mains Temperature{F}
1 Correlation NA 43.48 60.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 US+SF+CZ6A+gasfurnace+crawlspace+IECC_2024 0.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Algorithm {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
Space Heat Balance Sizing

Space Heat Balance Simulation

1 ThirdOrderBackwardDifference No No


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Gradient Coefficient {F/ft}
1 0.220 1213.970 0.003566


Material Details

Material Name ThermalResistance {m2-K/w} Roughness Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} Absorptance:Thermal Absorptance:Solar Absorptance:Visible
1 SHEATHING_CONSOL_LAYER 0.8807 Rough 0.1021 3.533E-002 1.255 0.350 0.9000 0.7000 0.7000
2 CEIL_CONSOL_LAYER 6.4845 Rough 1.3131 6.172E-002 2.618 0.185 0.9000 0.7000 0.7000
3 FLOOR_CONSOL_LAYER 4.5576 Rough 0.7710 5.155E-002 3.438 0.219 0.9000 0.7000 0.7000
4 BSMTWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
5 CRAWLWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
6 WALL_CONSOL_LAYER 2.4438 Rough 0.4584 5.717E-002 7.541 0.248 0.9000 0.7000 0.7000
7 VERY HIGH REFLECTIVITY SURFACE 2.1097E-006 Smooth 0.0016 237.000 168.680 0.216 0.9000 5.0000E-002 5.0000E-002
8 GYPSUMBOARD-5/16IN 5.0054E-002 Rough 0.0260 0.159 39.954 0.270 0.9000 0.4000 0.1000
9 COPPERPIPE 4.7506E-005 MediumRough 0.0625 401.000 140.026 0.200 0.9000 0.6500 0.6500
10 F08 METAL SURFACE 1.7668E-005 Smooth 0.0026 45.280 488.437 0.119 0.9000 0.7000 0.7000
11 CONCRETE_4IN 7.7356E-002 Rough 0.3330 1.312 140.014 0.111 0.9000 0.7000 0.7000
12 ASPHALT_SHINGLE 7.7448E-002 MediumRough 0.0208 8.186E-002 70.000 0.300 0.9000 0.7500 0.7000
13 WOOD_SHINGLE 0.1115 MediumSmooth 0.0417 0.114 26.600 0.390 0.9000 0.7000 0.7000
14 SLATE_SHINGLE 8.8061E-003 MediumSmooth 0.0417 1.442 100.000 0.300 0.9000 0.7000 0.7000
15 CEMENT_STUCCO 2.6422E-002 MediumSmooth 0.0625 0.721 116.464 0.210 0.9000 0.7000 0.7000
16 SYN_STUCCO 3.5237E-002 MediumSmooth 0.0100 8.650E-002 24.971 0.210 0.7000 0.7000 0.7000
17 DRYWALL_1/2IN 7.9331E-002 MediumSmooth 0.0417 0.160 50.000 0.260 0.9000 0.7000 0.7000
18 OSB_5/8IN 0.1365 MediumSmooth 0.0521 0.116 34.000 0.290 0.9000 0.7000 0.7000
19 OSB_7/16IN 9.5550E-002 MediumSmooth 0.0365 0.116 34.000 0.290 0.9000 0.7000 0.7000
20 BLOWN_R30 5.1614 MediumRough 0.6975 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
21 BLOWN_R30_TOP 2.8489 MediumRough 0.3849 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
22 PLYWOOD_3/4IN 0.1650 Rough 0.0625 0.115 34.003 0.161 0.9000 0.7000 0.7000
23 BATT_R19 7.3089 MediumRough 0.0833 3.475E-003 0.600 0.200 0.9000 0.7000 0.7000
24 LUMBER_2X4 0.7709 Rough 0.2920 0.115 32.003 0.183 0.9000 0.7000 0.7000
25 CARPET_N_PAD 0.4224 MediumSmooth 0.0833 6.013E-002 2.000 0.200 0.9000 0.7000 0.7000
26 BATT_R13 2.2936 MediumRough 0.2917 3.876E-002 0.600 0.200 0.9000 0.7000 0.7000
27 OSB_1/2IN 0.1092 MediumSmooth 0.0417 0.116 34.000 0.290 0.9000 0.7000 0.7000
28 SOIL_12IN 0.1761 Rough 1.0000 1.731 115.011 0.056 0.9000 0.7000 0.7000
29 DOOR_CONST 0.6289 Smooth 0.1486 7.201E-002 32.003 0.183 0.9000 0.7000 0.7000
30 GYP_BOARD_1/2IN 8.0130E-002 Rough 0.0417 0.159 39.954 0.270 0.9000 0.4000 0.1000
31 STD WOOD 6INCH 1.2500 MediumSmooth 0.4921 0.120 33.711 0.289 0.9000 0.7000 0.7000
32 PIPE INSULATION 1.2255 VeryRough 0.1334 3.317E-002 5.681 0.200 0.9000 0.5000 0.5000
33 MANF_WALL_AIRGAP 0.1200 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
34 BLDG_PAPER_FELT 1.0567E-002 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
35 R_HIGH 177.0000 MediumRough 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
36 CLEAR ACRYLIC PLASTIC 3.3333E-003 VerySmooth 0.0098 0.900 0.000 0.000 0.9000 0.0000 0.0000
37 DIFFUSING ACRYLIC PLASTIC 2.4444E-003 VerySmooth 0.0072 0.900 0.000 0.000 0.9000 0.0000 0.0000
38 INT_BLIND 0.0000 Rough 0.0000 0.000 0.000 0.000 0.0000 0.0000 0.0000
39 GLASS 0.4542 VerySmooth 0.1425 9.560E-002 0.000 0.000 0.8400 0.0000 0.0000


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Other Side Coefficients

Name Combined convective/radiative film coefficient {Btu/h-ft2-F} User selected Constant Temperature {F} Coefficient modifying the constant temperature term Coefficient modifying the external dry bulb temperature term Coefficient modifying the ground temperature term Coefficient modifying the wind speed term {s/m} Coefficient modifying the zone air temperature term Constant Temperature Schedule Name Sinusoidal Variation Period of Sinusoidal Variation Previous Other Side Temperature Coefficient Minimum Other Side Temperature {F} Maximum Other Side Temperature {F}
1 SURFPROPOTHSDCOEFSLABAVERAGE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABAVERAGESURFACETEMP NO 24.000 0.000 N/A N/A
2 SURFPROPOTHSDCOEFSLABPERIMETER N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABPERIMETERTEMP NO 24.000 0.000 N/A N/A
3 SURFPROPOTHSDCOEFSLABCORE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABCORETEMP NO 24.000 0.000 N/A N/A


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{F}


Surface Convection Coefficient Lower Limit {Btu/h-ft2-F}


Surface Convection Coefficient Upper Limit {Btu/h-ft2-F}


1 CTF - ConductionTransferFunction 392. 0.02 176.1


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 4


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 4 49 12


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {ft} Origin Y-Coordinate {ft} Origin Z-Coordinate {ft} Centroid X-Coordinate {ft} Centroid Y-Coordinate {ft} Centroid Z-Coordinate {ft} Type Zone Multiplier Zone List Multiplier Minimum X {ft} Maximum X {ft} Minimum Y {ft} Maximum Y {ft} Minimum Z {ft} Maximum Z {ft} Ceiling Height {ft} Volume {ft3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {ft2} Exterior Gross Wall Area {ft2} Exterior Net Wall Area {ft2} Exterior Window Area {ft2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 LIVING_UNIT1 0.0 0.00 0.00 0.00 19.92 14.93 8.99 1 1 1 0.00 39.80 0.00 29.86 0.49 17.52 12.76 17050.65 TARP DOE-2 2377.12 2199.28 1803.88 355.35 12 10 4 Yes
2 GARAGE1 0.0 19.82 -20.0 0.00 29.82 -10.0 5.35 1 1 1 19.82 39.80 -20.0 0.00 0.49 11.84 9.91 3968.18 TARP DOE-2 400.03 566.88 454.82 0.00 9 2 0 Yes
3 ATTIC_UNIT1 0.0 0.00 0.00 0.00 19.92 14.93 18.67 1 1 1 0.00 39.80 0.00 29.86 17.52 21.98 2.23 2659.94 TARP DOE-2 1188.56 133.59 133.59 0.00 5 0 0 Yes
4 CRAWLSPACE_UNIT1 0.0 0.00 0.00 0.00 19.92 14.93 -0.5 1 1 1 0.00 39.80 0.00 29.86 -1.5 0.49 2.00 2377.73 TARP DOE-2 1188.56 69.65 69.65 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {ft2} # Occupants Area per Occupant {ft2/person} Occupant per Area {person/ft2} Interior Lighting {Btu/h-ft2} Electric Load {Btu/h-ft2} Gas Load {Btu/h-ft2} Other Load {Btu/h-ft2} Hot Water Eq {Btu/h-ft2} Steam Equipment {Btu/h-ft2} Sum Loads per Area {Btu/h-ft2} Outdoor Controlled Baseboard Heat
1 LIVING_UNIT1 2377.12 3.0 792.366 0.001 0.485 1.747 1.432 0.000 0.000 0.000 3.664 No
2 GARAGE1 400.03 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 ATTIC_UNIT1 1188.56 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
4 CRAWLSPACE_UNIT1 1188.56 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Number of People {} People/Floor Area {person/ft2} Floor Area per person {ft2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 PEOPLE_UNIT1 OCCUPANCY LIVING_UNIT1 2377.12 3.0 3.0 0.001 792.366 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 1 3


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Lighting Level {Btu/h} Lights/Floor Area {Btu/h-ft2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {Btu/h} Nominal Maximum Lighting Level {Btu/h}
1 LIVING HARDWIRED LIGHTING1 INTERIORLIGHTINGHE LIVING_UNIT1 2377.12 3.0 792.730 0.333 77.445 0.000 0.600 0.200 0.200 0.000 General 54.500 792.730
2 LIVING PLUG-IN LIGHTING1 INTERIORLIGHTINGHE LIVING_UNIT1 2377.12 3.0 360.491 0.152 35.218 0.000 0.600 0.200 0.200 0.000 General 24.785 360.491


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 DISHWASHER1 DISHWASHER_EQUIP_SCH LIVING_UNIT1 2377.12 3.0 224.165 0.094 21.900 0.150 0.600 0.250 0.000 dishwasher 0.000 224.165
2 REFRIGERATOR1 REFRIGERATOR LIVING_UNIT1 2377.12 3.0 310.690 0.131 30.353 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
3 CLOTHESWASHER1 CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1 2377.12 3.0 97.167 0.041 9.493 0.000 0.800 0.200 0.000 clotheswasher 0.000 97.167
4 GAS_DRYER1 CLOTHESDRYER LIVING_UNIT1 2377.12 3.0 66.254 0.028 6.473 0.000 1.000 0.000 0.000 gas_dryer 0.000 66.254
5 GAS_RANGE1 COOKINGRANGE LIVING_UNIT1 2377.12 3.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
6 TELEVISION1 INTERIORLIGHTING LIVING_UNIT1 2377.12 3.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
7 GAS_MELS1 MISCPLUGLOAD LIVING_UNIT1 2377.12 3.0 1730.396 0.728 169.050 6.000E-002 0.690 0.250 0.000 gas_mels 894.654 1730.396
8 IECC_ADJ1 MISCPLUGLOAD LIVING_UNIT1 2377.12 3.0 1724.425 0.726 168.467 6.244E-002 0.412 0.251 0.275 IECC_adj 891.566 1724.425


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 GAS_DRYER1 CLOTHESDRYER LIVING_UNIT1 2377.12 3.0 1349.774 0.568 131.865 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1349.774
2 GAS_RANGE1 COOKINGRANGE LIVING_UNIT1 2377.12 3.0 1845.691 0.777 180.314 6.000E-002 0.690 0.250 0.000 gas_range 43.459 1845.691
3 GAS_MELS1 MISCPLUGLOAD LIVING_UNIT1 2377.12 3.0 208.559 0.088 20.375 6.000E-002 0.690 0.250 0.000 gas_mels 107.829 208.559


Construction CTF

Construction Name Index #Layers #CTFs Time Step {Hours} ThermalConductance {Btu/h-ft2-F} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 EXTERIOR WALL 1 5 10 0.167 0.0498 0.700 0.900 0.700 0.700 MediumSmooth
2 INTERIORFURNISHINGS 2 1 9 0.167 0.1409 0.900 0.900 0.700 0.700 MediumSmooth
3 EXTERIOR FLOOR 4 3 9 0.167 0.0342 0.900 0.900 0.700 0.700 Rough
4 INTERIOR FLOOR 5 2 4 0.167 0.300 0.900 0.900 0.700 0.700 Rough
5 INTERIOR CEILING 6 2 10 0.167 0.0268 0.900 0.900 0.700 0.700 Rough
6 ATTIC FLOOR 7 2 10 0.167 0.0268 0.900 0.900 0.700 0.700 MediumSmooth
7 EXTERIOR ROOF 11 2 4 0.167 0.943 0.900 0.900 0.750 0.700 MediumRough
8 EXTERIOR DOOR 14 1 5 0.167 0.280 0.900 0.900 0.700 0.700 Smooth
9 GABLE_END 16 5 6 0.167 0.428 0.900 0.900 0.700 0.700 MediumSmooth
10 CRAWL WALL 24 1 5 0.167 2.28 0.900 0.900 0.700 0.700 Rough
11 iz-EXTERIOR WALL 25 5 10 0.167 0.0498 0.900 0.700 0.700 0.700 MediumSmooth
12 iz-EXTERIOR FLOOR 26 3 9 0.167 0.0342 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} ThermalResistance {m2-K/w}
1 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
2 SHEATHING_CONSOL_LAYER 0.1020 0.035 1.255 0.350 0.8807
3 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
4 WALL_CONSOL_LAYER 0.4584 0.057 7.541 0.248 2.444
5 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
6 STD WOOD 6INCH 0.4921 0.120 33.711 0.289 1.250
7 FLOOR_CONSOL_LAYER 0.7707 0.052 3.438 0.219 4.558
8 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
9 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
10 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
11 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
12 CEIL_CONSOL_LAYER 1.3131 0.062 2.618 0.185 6.484
13 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
14 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
15 CEIL_CONSOL_LAYER 1.3131 0.062 2.618 0.185 6.484
16 ASPHALT_SHINGLE 0.0207 0.082 70.000 0.300 0.7745E-01
17 OSB_1/2IN 0.0417 0.116 34.000 0.290 0.1092
18 DOOR_CONST 0.1486 0.072 32.003 0.183 0.6289
19 CEMENT_STUCCO 0.0627 0.721 116.464 0.210 0.2642E-01
20 BLDG_PAPER_FELT 0.0000 0.000 0.000 0.000 0.1057E-01
21 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
22 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
23 CONCRETE_4IN 0.3330 1.312 140.014 0.111 0.7736E-01
24 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
25 WALL_CONSOL_LAYER 0.4584 0.057 7.541 0.248 2.444
26 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
27 SHEATHING_CONSOL_LAYER 0.1020 0.035 1.255 0.350 0.8807
28 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
29 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
30 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
31 FLOOR_CONSOL_LAYER 0.7707 0.052 3.438 0.219 4.558


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


CTF

Time Outside Cross Inside Flux (except final one)
1 10 0.51360630E-08 -0.22035233E-13 0.91774209E-08 -0.50676220E-13
2 9 -0.14060012E-04 0.39159197E-12 -0.22958088E-04 0.29728831E-08
3 8 0.28980689E-02 0.65531654E-09 0.46215968E-02 -0.71708779E-05
4 7 -0.65978682E-01 0.13350779E-06 -0.16306378 0.13238707E-02
5 6 0.64596177 0.50193482E-05 2.1320981 -0.28125917E-01
6 5 -3.4215999 0.48298777E-04 -13.652056 0.25148823
7 4 10.645660 0.13839053E-03 47.881148 -1.1749737
8 3 -19.924231 0.11919231E-03 -96.040791 3.0621859
9 2 21.976583 0.26462555E-04 109.48934 -4.4404618
10 1 -13.118296 0.91387708E-06 -65.855375 3.3273744
11 0 3.2593552 0.33613880E-09 16.204438  
12 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
13 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
14 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
15 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
16 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
17 4 45.557404 0.63181060E-04 45.557404 -5.4853312
18 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
19 2 62.555368 0.93952058E-05 62.555368 -8.2111738
20 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
21 0 6.9260389 0.77047546E-09 6.9260389  
22 9 -0.61797381E-16 0.10275554E-15 -0.94176193E-10 0.70550100E-16
23 8 0.55018702E-09 0.40996745E-13 0.10446581E-03 -0.35964092E-09
24 7 -0.45325743E-03 0.10183730E-08 -0.10651944E-01 0.29628111E-03
25 6 0.35000963E-01 0.28248981E-06 0.18262466 -0.23007581E-01
26 5 -0.40204458 0.87190144E-05 -1.3453660 0.27251248
27 4 1.9371679 0.56641591E-04 5.2219591 -1.3641479
28 3 -4.7809977 0.95620201E-04 -11.428910 3.5178846
29 2 6.3416706 0.40914426E-04 14.116582 -4.8962826
30 1 -4.2976303 0.32019284E-05 -9.1505965 3.4916880
31 0 1.1674918 0.10995666E-07 2.4144591  
32 4 0.50405178E-13 0.16668152E-13 0.29402090E-13 -0.58636069E-16
33 3 -0.78967347E-05 0.18486376E-05 -0.51544008E-05 0.20741056E-12
34 2 0.37655193 0.34407043E-01 0.80677627E-01 -0.16328896E-04
35 1 -8.0349315 0.81344511 -1.1624309 0.21506451
36 0 8.9946927 0.48845120 2.4180636  
37 10 -0.96769015E-17 -0.20747839E-14 0.29297638E-08 0.78932515E-17
38 9 -0.56587496E-08 -0.24945017E-14 -0.14784763E-02 0.38539146E-08
39 8 0.72238700E-03 0.96019310E-10 0.66422612E-01 -0.49198669E-03
40 7 -0.17427411E-01 0.40956981E-07 -1.0050332 0.12133364E-01
41 6 0.17512309 0.18498148E-05 7.5797971 -0.12514619
42 5 -0.95338624 0.19370257E-04 -32.757448 0.70262168
43 4 3.0653739 0.60507497E-04 85.929347 -2.3420755
44 3 -5.9495223 0.59223871E-04 -138.69581 4.7385057
45 2 6.8074199 0.16249306E-04 134.19793 -5.6812110
46 1 -4.2061463 0.84447462E-06 -71.229973 3.6946262
47 0 1.0780011 0.18118629E-08 15.916399  
48 10 0.29297638E-08 -0.20747839E-14 -0.96769015E-17 0.78932515E-17
49 9 -0.14784763E-02 -0.24945017E-14 -0.56587496E-08 0.38539146E-08
50 8 0.66422612E-01 0.96019310E-10 0.72238700E-03 -0.49198669E-03
51 7 -1.0050332 0.40956981E-07 -0.17427411E-01 0.12133364E-01
52 6 7.5797971 0.18498148E-05 0.17512309 -0.12514619
53 5 -32.757448 0.19370257E-04 -0.95338624 0.70262168
54 4 85.929347 0.60507497E-04 3.0653739 -2.3420755
55 3 -138.69581 0.59223871E-04 -5.9495223 4.7385057
56 2 134.19793 0.16249306E-04 6.8074199 -5.6812110
57 1 -71.229973 0.84447462E-06 -4.2061463 3.6946262
58 0 15.916399 0.18118629E-08 1.0780011  
59 4 0.75441920E-10 0.23883683E-10 0.47514224E-10 -0.69373194E-20
60 3 -0.33730907E-03 0.89366797E-04 -0.22574866E-03 0.77828620E-10
61 2 0.58624422 0.18542418 0.49024360 -0.17301269E-03
62 1 -11.299243 2.8799011 -8.6239668 0.15905732
63 0 15.219762 1.4410112 12.640375  
64 5 -0.22386379E-05 0.14507658E-06 -0.22386379E-05 0.55751404E-07
65 4 0.19828726E-02 0.23087232E-03 0.19828726E-02 -0.63287341E-04
66 3 -0.19189141 0.19999256E-01 -0.19189141 0.89189542E-02
67 2 2.6725246 0.18376164 2.6725246 -0.18999148
68 1 -8.2383273 0.21538727 -8.2383273 0.90472632
69 0 6.1952067 0.20114026E-01 6.1952067  
70 6 0.97988530E-11 0.43917118E-12 0.24496810E-11 -0.34892153E-15
71 5 -0.75005310E-05 0.16499726E-06 -0.28271466E-05 0.19166609E-11
72 4 0.32354224E-01 0.66949565E-03 0.10283773E-01 -0.11111676E-05
73 3 -1.8201547 0.67148336E-01 -0.62076152 0.38788549E-02
74 2 21.173821 0.53241617 7.5279938 -0.97325542E-01
75 1 -64.420211 0.46601667 -21.697519 0.64629334
76 0 46.121323 0.20873329E-01 15.867130  
77 5 -0.15664505E-06 0.43005807E-07 -0.15664505E-06 0.11899247E-09
78 4 0.10791049E-02 0.34140917E-03 0.10791049E-02 -0.15677434E-05
79 3 -0.39592122 0.90314630E-01 -0.39592122 0.13116776E-02
80 2 11.651569 1.6702487 11.651569 -0.78737360E-01
81 1 -51.506798 3.1050242 -51.506798 0.66829999
82 0 45.538973 0.42297268 45.538973  
83 10 0.91774209E-08 -0.22035233E-13 0.51360630E-08 -0.50676220E-13
84 9 -0.22958088E-04 0.39159197E-12 -0.14060012E-04 0.29728831E-08
85 8 0.46215968E-02 0.65531654E-09 0.28980689E-02 -0.71708779E-05
86 7 -0.16306378 0.13350779E-06 -0.65978682E-01 0.13238707E-02
87 6 2.1320981 0.50193482E-05 0.64596177 -0.28125917E-01
88 5 -13.652056 0.48298777E-04 -3.4215999 0.25148823
89 4 47.881148 0.13839053E-03 10.645660 -1.1749737
90 3 -96.040791 0.11919231E-03 -19.924231 3.0621859
91 2 109.48934 0.26462555E-04 21.976583 -4.4404618
92 1 -65.855375 0.91387708E-06 -13.118296 3.3273744
93 0 16.204438 0.33613880E-09 3.2593552  
94 9 -0.94176193E-10 0.10275554E-15 -0.61797381E-16 0.70550100E-16
95 8 0.10446581E-03 0.40996745E-13 0.55018702E-09 -0.35964092E-09
96 7 -0.10651944E-01 0.10183730E-08 -0.45325743E-03 0.29628111E-03
97 6 0.18262466 0.28248981E-06 0.35000963E-01 -0.23007581E-01
98 5 -1.3453660 0.87190144E-05 -0.40204458 0.27251248
99 4 5.2219591 0.56641591E-04 1.9371679 -1.3641479
100 3 -11.428910 0.95620201E-04 -4.7809977 3.5178846
101 2 14.116582 0.40914426E-04 6.3416706 -4.8962826
102 1 -9.1505965 0.32019284E-05 -4.2976303 3.4916880
103 0 2.4144591 0.10995666E-07 1.1674918  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {Btu/h-ft2-F} Conductance (Before Adjusted) {Btu/h-ft2-F} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 EXTERIOR WINDOW 12 1 VerySmooth 0.280 0.280 1.000 0.335    
2 INTERIOR WINDOW 13 1 VerySmooth 0.280 0.280 1.000 0.335    
3 WINDOW_W_BLINDS 18 2 VerySmooth 0.280 0.280 1.000 0.309    
4 TDD DOME 22 1 VerySmooth 1.071 1.071 1.000 0.929    
5 TDD DIFFUSER 23 1 VerySmooth 1.077 1.077 1.000 0.906    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {ft} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLASS SpectralAverage   0.14246 0.24698 0.55318 0.55318 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 9.56013E-002 1.00000 No
2 GLASS SpectralAverage   0.14246 0.24698 0.55318 0.55318 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 9.56013E-002 1.00000 No
3 GLASS SpectralAverage   0.14246 0.24698 0.55318 0.55318 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 9.56013E-002 1.00000 No
4 CLEAR ACRYLIC PLASTIC SpectralAverage   0.00984 0.92000 5.00000E-002 5.00000E-002 0.92000 5.00000E-002 5.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No
5 DIFFUSING ACRYLIC PLASTIC SpectralAverage   0.00722 0.90000 8.00000E-002 8.00000E-002 0.90000 8.00000E-002 8.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No


WindowMaterial:Blind

Material Name Slat Width {ft} Slat Separation {ft} Slat Thickness {ft} Slat Angle {deg} Slat Beam Solar Transmittance Slat Beam Solar Front Reflectance Blind To Glass Distance {ft}
1 INT_BLIND 0.0820 0.0615 0.0033 45.000 0.000 0.500 0.164


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000. SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {ft3} Maximum Capacity {Btu/h} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed WATER HEATER_UNIT1 5.3474 38002.2 0.821 0.5720


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/person Area {ft3/min-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {psi} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{F}/Schedule Maximum Indoor Temperature{F}/Schedule Delta Temperature{F}/Schedule Minimum Outdoor Temperature{F}/Schedule Maximum Outdoor Temperature{F}/Schedule Maximum WindSpeed{ft/min}
1 VENTILATION_UNIT1 ALWAYS_AVAIL LIVING_UNIT1 2377.12 3.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 LIVING_UNIT1 Mixing/Well-Stirred
2 GARAGE1 Mixing/Well-Stirred
3 ATTIC_UNIT1 Mixing/Well-Stirred
4 CRAWLSPACE_UNIT1 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 MultizoneWithDistribution


AirflowNetwork Model:Equivalent Rectangle Surface

Name Equivalent Height {ft} Equivalent Width {ft} AirflowNetwork Model:Equivalent Rectangle
1 ROOF_RIGHT_UNIT1 4.46 14.93
2 ROOF_LEFT_UNIT1 4.46 14.93
3 ROOF_RIGHT_GARAGE1 2.82 10.01
4 ROOF_LEFT_GARAGE1 2.82 10.01


AirflowNetwork Model:Wind Direction

Wind Direction #1 to n (degree)
1 0.0


AirflowNetwork Model:Wind Pressure Coefficients

Name Wind Pressure Coefficients #1 to n (dimensionless)
1 !WPCTABLE1 0.60
2 !WPCTABLE2 -0.36
3 !WPCTABLE3 -0.51
4 !WPCTABLE4 -0.36
5 !WPCTABLE5 -0.73


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {Btu/h} User Des Load {Btu/h} Calc Des Air Flow Rate {ft3/min} User Des Air Flow Rate {ft3/min} Design Day Name Date/Time of Peak Temperature at Peak {F} Humidity Ratio at Peak {lbWater/lbDryAir} Floor Area {ft2} # Occupants Calc Outdoor Air Flow Rate {ft3/min} Calc DOAS Heat Addition Rate {Btu/h}
1 LIVING_UNIT1 Cooling 16925.95262 16925.95262 755.59312 755.59312 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 83.10380 0.01536 2377.09544 3.00000 59.99321 0.00000
2 LIVING_UNIT1 Heating 27623.43429 27623.43429 527.09739 527.09739 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:20:00 -15.1600 0.00036 2377.09544 3.00000 59.99321 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [ft3/min] User Des Air Flow Rate [ft3/min] Design Day Name Date/Time of Peak
1 CENTRAL SYSTEM_UNIT1 Cooling Sensible 5040.10 755.59312 755.59312 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 CENTRAL SYSTEM_UNIT1 Heating Sensible 9560.34 527.09739 527.09739 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:20:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1 User-Specified Supply Air Flow Rate [ft3/min] 59.99321
2 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1 User-Specified Exhaust Air Flow Rate [ft3/min] 59.99321
3 Fan:OnOff OASUPPLYFAN_UNIT1 User-Specified Maximum Flow Rate [ft3/min] 59.99321
4 Fan:OnOff OAEXHAUSTFAN_UNIT1 User-Specified Maximum Flow Rate [ft3/min] 59.99321
5 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1 User-Specified Nominal Supply Air Flow Rate [ft3/min] 59.99321
6 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1 Design Size Maximum Air Flow Rate [ft3/min] 755.59312
7 AirLoopHVAC CENTRAL SYSTEM_UNIT1 Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 755.59312
8 AirLoopHVAC CENTRAL SYSTEM_UNIT1 Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 755.59312
9 AirLoopHVAC CENTRAL SYSTEM_UNIT1 Sum of Air Terminal Maximum Flow Rates [ft3/min] 755.59312
10 AirLoopHVAC CENTRAL SYSTEM_UNIT1 Adjusted Heating Design Air Flow Rate [ft3/min] 755.59312
11 AirLoopHVAC CENTRAL SYSTEM_UNIT1 Adjusted Cooling Design Air Flow Rate [ft3/min] 755.59312
12 AirLoopHVAC CENTRAL SYSTEM_UNIT1 Adjusted Main Design Air Flow Rate [ft3/min] 755.59312
13 AirLoopHVAC CENTRAL SYSTEM_UNIT1 User Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC CENTRAL SYSTEM_UNIT1 Calculated Heating Air Flow Ratio [] 1.00000
15 AirLoopHVAC CENTRAL SYSTEM_UNIT1 Design Supply Air Flow Rate [ft3/min] 755.59312
16 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1 Design Size Rated Air Flow Rate [ft3/min] 755.59312
17 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1 Design Size Gross Rated Total Cooling Capacity [ton] 2.23591
18 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1 Design Size Gross Rated Sensible Heat Ratio 0.74001
19 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1 Supply Air Flow Rate [ft3/min] 755.59312
20 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1 Supply Air Flow Rate During Heating Operation [ft3/min] 755.59312
21 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1 Supply Air Flow Rate During Cooling Operation [ft3/min] 755.59312
22 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1 Nominal Heating Capacity [Btu/h] 32619.86554
23 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1 Nominal Cooling Capacity [ton] 2.23591
24 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1 Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
25 Fan:OnOff SUPPLY FAN_UNIT1 Design Size Maximum Flow Rate [ft3/min] 755.59312
26 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT1 Design Size Nominal Capacity [Btu/h] 40774.83195
27 PlantLoop DHW LOOP_UNIT1 Maximum Loop Flow Rate [ft3/min] 1.04620
28 PlantLoop DHW LOOP_UNIT1 Plant Loop Volume [ft3] 2.09294
29 Pump:VariableSpeed MAINS PRESSURE_UNIT1 Design Flow Rate [ft3/min] 1.04620
30 WaterHeater:Mixed WATER HEATER_UNIT1 Maximum Heater Capacity [Btu/h] 38002.17360
31 WaterHeater:Mixed WATER HEATER_UNIT1 Use Side Design Flow Rate [ft3/min] 1.04620


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {ton} Standard Rated Net COP {Btuh/Btuh} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1 2.2 3.45 11.78 12.50 12.02 12.30
2 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1 2.1 3.34 11.40 12.07 11.94 -99999.


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB SizingPeriod:DesignDay 01/21 01/21 WinterDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
2 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB SizingPeriod:DesignDay 07/21 07/21 SummerDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
3 ANNUAL WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No SizingPeriod:DesignDay    
2 No SizingPeriod:DesignDay    
3 No      


Environment:WarmupDays

NumberofWarmupDays
1 6
2 6
3 6


Environment:Design Day Data

Max Dry-Bulb Temp {F} Temp Range {dC} Temp Range Ind Type Hum Ind Type Hum Ind Value at Max Temp Hum Ind Units Pressure {psi} Wind Direction {deg CW from N} Wind Speed {ft/min} Clearness Rain Snow
1 -15.2 0.00 DefaultMultipliers Wetbulb -26.20 {C} 14. 310 1122.1 0.00 No No
2 88.16 10.60 DefaultMultipliers Wetbulb 23.10 {C} 14. 200 1319.0 0.00 No No


Environment:Design Day Misc

DayOfYear ASHRAE A Coeff ASHRAE B Coeff ASHRAE C Coeff Solar Constant-Annual Variation Eq of Time {minutes} Solar Declination Angle {deg} Solar Model
1 21 1229.0 0.1415 5.7310E-002 1.0 -11.15 -20. ASHRAEClearSky
2 202 1084.4 0.2082 0.1365 1.0 -6.23 20.6 ASHRAETau


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaF} Std Dev Warmup Temperature Difference {deltaF} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {Btu/h} Std Dev Warmup Load Difference {Btu/h} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 LIVING_UNIT1 SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 0.000294199 0.000607455 Pass Pass 0.006500764 0.011156764 Pass Pass
2 GARAGE1 SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 0.000106512 0.000089619 Pass Pass 0.000000000 0.000000000 Pass Pass
3 ATTIC_UNIT1 SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 0.000159580 0.000221799 Pass Pass 0.000000000 0.000000000 Pass Pass
4 CRAWLSPACE_UNIT1 SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 0.003804584 0.005051084 Pass Pass 0.000000000 0.000000000 Pass Pass
5 LIVING_UNIT1 SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 0.001109222 0.002252238 Pass Pass 0.099725634 0.085102306 Pass Pass
6 GARAGE1 SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 0.555764757 0.449327015 Pass Pass 0.000000000 0.000000000 Pass Pass
7 ATTIC_UNIT1 SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 0.346003979 0.224525652 Pass Pass 0.000000000 0.000000000 Pass Pass
8 CRAWLSPACE_UNIT1 SizingPeriod: ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 0.205580411 0.120249994 Pass Pass 0.000000000 0.000000000 Pass Pass
9 LIVING_UNIT1 RunPeriod: ANNUAL 0.004149491 0.009333314 Pass Pass 0.046957605 0.052164360 Pass Pass
10 GARAGE1 RunPeriod: ANNUAL 0.169075269 0.188553044 Pass Pass 0.000000000 0.000000000 Pass Pass
11 ATTIC_UNIT1 RunPeriod: ANNUAL 0.131345457 0.111872295 Pass Pass 0.000000000 0.000000000 Pass Pass
12 CRAWLSPACE_UNIT1 RunPeriod: ANNUAL 0.339953908 0.356261326 Pass Pass 0.000000000 0.000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Report

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Annual Heat Emissions Summary

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kBtu] 505341.33 126792.35 0.00 0.00 33865.12 665999.42



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Heat Index Hours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
LIVING_UNIT1 8760.00 0.00 0.00 0.00 0.00
GARAGE1 7553.00 529.67 436.50 238.00 2.83
ATTIC_UNIT1 8121.50 448.67 164.00 25.83 0.00
CRAWLSPACE_UNIT1 8653.33 102.33 4.33 0.00 0.00
Min 7553.00 0.00 0.00 0.00 0.00
Max 8760.00 529.67 436.50 238.00 2.83
Average 8271.96 270.17 151.21 65.96 0.71
Sum 33087.83 1080.67 604.83 263.83 2.83


Heat Index OccupantHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
LIVING_UNIT1 18093.57 0.00 0.00 0.00 0.00
GARAGE1 0.00 0.00 0.00 0.00 0.00
ATTIC_UNIT1 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 18093.57 0.00 0.00 0.00 0.00
Average 4523.39 0.00 0.00 0.00 0.00
Sum 18093.57 0.00 0.00 0.00 0.00


Heat Index OccupiedHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
LIVING_UNIT1 8760.00 0.00 0.00 0.00 0.00
GARAGE1 0.00 0.00 0.00 0.00 0.00
ATTIC_UNIT1 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 2190.00 0.00 0.00 0.00 0.00
Sum 8760.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
LIVING_UNIT1 8722.17 37.83 0.00 0.00 0.00
GARAGE1 7405.83 936.17 258.50 134.50 25.00
ATTIC_UNIT1 7843.17 825.00 74.33 15.83 1.67
CRAWLSPACE_UNIT1 8292.50 466.00 1.50 0.00 0.00
Min 7405.83 37.83 0.00 0.00 0.00
Max 8722.17 936.17 258.50 134.50 25.00
Average 8065.92 566.25 83.58 37.58 6.67
Sum 32263.67 2265.00 334.33 150.33 26.67


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
LIVING_UNIT1 17996.41 97.16 0.00 0.00 0.00
GARAGE1 0.00 0.00 0.00 0.00 0.00
ATTIC_UNIT1 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17996.41 97.16 0.00 0.00 0.00
Average 4499.10 24.29 0.00 0.00 0.00
Sum 17996.41 97.16 0.00 0.00 0.00


Humidex OccupiedHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
LIVING_UNIT1 8722.17 37.83 0.00 0.00 0.00
GARAGE1 0.00 0.00 0.00 0.00 0.00
ATTIC_UNIT1 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8722.17 37.83 0.00 0.00 0.00
Average 2180.54 9.46 0.00 0.00 0.00
Sum 8722.17 37.83 0.00 0.00 0.00


Hours of Safety for Cold Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
LIVING_UNIT1 8760.00 - 0.00 0.00 0.00
GARAGE1 0.00 - 0.00 0.00 0.00
ATTIC_UNIT1 0.00 - 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 2190.00 - 0.00 0.00 0.00
Sum 8760.00 - 0.00 0.00 0.00


Hours of Safety for Heat Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
LIVING_UNIT1 8760.00 - 0.00 0.00 0.00
GARAGE1 0.00 - 0.00 0.00 0.00
ATTIC_UNIT1 0.00 - 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 2190.00 - 0.00 0.00 0.00
Sum 8760.00 - 0.00 0.00 0.00


Unmet Degree-Hours

Cooling Setpoint Unmet Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] Heating Setpoint Unmet Degree-Hours [°F·hr] Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Heating Setpoint Unmet Occupied Degree-Hours [°C·hr]
LIVING_UNIT1 0.81 1.81 0.81 275.31 591.84 275.31
GARAGE1 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC_UNIT1 0.00 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00 0.00
Max 0.81 1.81 0.81 275.31 591.84 275.31
Average 0.20 0.45 0.20 68.83 147.96 68.83
Sum 0.81 1.81 0.81 275.31 591.84 275.31


Discomfort-weighted Exceedance OccupantHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
LIVING_UNIT1 0.00 0.00 0.00 0.00
GARAGE1 0.00 0.00 0.00 0.00
ATTIC_UNIT1 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00


Discomfort-weighted Exceedance OccupiedHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
LIVING_UNIT1 0.00 0.00 0.00 0.00
GARAGE1 0.00 0.00 0.00 0.00
ATTIC_UNIT1 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB -15.2 0.00 -15.2 Wetbulb [F] 1122.10 310.00
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 88.16 19.08 73.58 Wetbulb [F] 1318.96 200.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [in] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [in] Monthly Total Roof Irrigation Depth [in] Monthly Total Rain Collection Volume [ft3]
Jan 1.02 35      
Feb 0.00 0      
Mar 0.00 0      
Apr 1.14 23      
May 0.00 0      
Jun 4.21 45      
Jul 2.83 29      
Aug 0.00 0      
Sep 0.79 11      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.16 8      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
WALL_LDF_1.UNIT1 EXTERIOR WALL 0.30 0.048 0.050 168.42 123.99 180.00 90.00 S
WALL_SDR_1.UNIT1 EXTERIOR WALL 0.30 0.048 0.050 253.86 209.43 90.00 90.00 E
WALL_LDB_1.UNIT1 EXTERIOR WALL 0.30 0.048 0.050 338.48 254.03 0.00 90.00 N
WALL_SDL_1.UNIT1 EXTERIOR WALL 0.30 0.048 0.050 253.86 209.43 270.00 90.00 W
WALL_LDF_2.UNIT1 EXTERIOR WALL 0.30 0.048 0.050 338.48 294.05 180.00 90.00 S
WALL_SDR_2.UNIT1 EXTERIOR WALL 0.30 0.048 0.050 253.86 209.43 90.00 90.00 E
WALL_LDB_2.UNIT1 EXTERIOR WALL 0.30 0.048 0.050 338.48 294.05 0.00 90.00 N
WALL_SDL_2.UNIT1 EXTERIOR WALL 0.30 0.048 0.050 253.86 209.43 270.00 90.00 W
WALL_LDF_1.GARAGE1 GABLE_END 0.30 0.314 0.428 170.06 58.02 180.00 90.00 S
WALL_SDR_1.GARAGE1 GABLE_END 0.30 0.314 0.428 170.06 170.06 90.00 90.00 E
WALL_SDL_1.GARAGE1 GABLE_END 0.30 0.314 0.428 170.06 170.06 270.00 90.00 W
ROOF_RIGHT_GARAGE1 GABLE_END 0.30 0.314 0.428 28.33 28.33 90.00 90.00 E
ROOF_LEFT_GARAGE1 GABLE_END 0.30 0.314 0.428 28.33 28.33 270.00 90.00 W
ROOF_FRONT_GARAGE1 EXTERIOR ROOF 0.25 0.543 0.943 207.89 207.89 180.00 15.82  
ROOF_BACK_GARAGE1 EXTERIOR ROOF 0.25 0.543 0.943 207.89 207.89 0.00 15.82  
ROOF_RIGHT_UNIT1 GABLE_END 0.30 0.314 0.428 66.82 66.82 90.00 90.00 E
ROOF_LEFT_UNIT1 GABLE_END 0.30 0.314 0.428 66.82 66.82 270.00 90.00 W
ROOF_FRONT_UNIT1 EXTERIOR ROOF 0.25 0.543 0.943 620.41 620.41 180.00 16.69  
ROOF_BACK_UNIT1 EXTERIOR ROOF 0.25 0.543 0.943 620.41 620.41 0.00 16.69  
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 19.91 19.91 180.00 90.00 S
BGWALL_LOWER_LDF CRAWL WALL 0.30 0.893 2.276 59.73 59.73 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 14.93 14.93 90.00 90.00 E
BGWALL_LOWER_SDR CRAWL WALL 0.30 0.893 2.276 44.80 44.80 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 19.91 19.91 0.00 90.00 N
BGWALL_LOWER_LDB CRAWL WALL 0.30 0.893 2.276 59.73 59.73 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 14.93 14.93 270.00 90.00 W
BGWALL_LOWER_SDL CRAWL WALL 0.30 0.893 2.276 44.80 44.80 270.00 90.00 W
EXTFLOOR_UNIT1 INTERIOR FLOOR 0.30 0.235 0.300 1188.55 1188.55 90.00 180.00  


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
WALL_LDB_1.GARAGE1 EXTERIOR WALL 0.30 0.047 0.050 170.06 149.05 180.00 90.00 S
INTER ZONE FLOOR 1 INTERIOR FLOOR 0.30 0.193 0.300 1188.55 1188.55 90.00 180.00  
FLOOR_UNIT1 EXTERIOR FLOOR 0.30 0.033 0.034 1188.55 1188.55 90.00 180.00  
CEILING_UNIT1 INTERIOR CEILING 0.30 0.026 0.027 1188.55 1188.55 180.00 0.00  
iz-WALL_LDB_1.GARAGE1 iz-EXTERIOR WALL 0.30 0.047 0.050 170.06 149.05 0.00 90.00 N
FLOOR_GARAGE1 INTERIOR FLOOR 0.30 0.235 0.300 400.04 400.04 90.00 180.00  
iz-CEILING_UNIT1 ATTIC FLOOR 0.30 0.026 0.027 1188.55 1188.55 0.00 180.00  
iz-FLOOR_UNIT1 iz-EXTERIOR FLOOR 0.30 0.033 0.034 1188.55 1188.55 270.00 0.00  
INTERNALMASS_UNIT1 INTERIORFURNISHINGS 0.30   0.141 106.53   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_1.UNIT1 EXTERIOR WINDOW   44.43 0.00 0.00 44.43 44.43 0.280 0.335 0.882             Yes WALL_LDF_1.UNIT1 180.00 90.00 S
WINDOW_SDR_1.UNIT1 EXTERIOR WINDOW   44.43 0.00 0.00 44.43 44.43 0.280 0.335 0.882             Yes WALL_SDR_1.UNIT1 90.00 90.00 E
WINDOW_LDB_1.UNIT1 EXTERIOR WINDOW   44.43 0.00 0.00 44.43 44.43 0.280 0.335 0.882             Yes WALL_LDB_1.UNIT1 0.00 90.00 N
WINDOW_SDL_1.UNIT1 EXTERIOR WINDOW   44.43 0.00 0.00 44.43 44.43 0.280 0.335 0.882             Yes WALL_SDL_1.UNIT1 270.00 90.00 W
WINDOW_LDF_2.UNIT1 EXTERIOR WINDOW   44.43 0.00 0.00 44.43 44.43 0.280 0.335 0.882             Yes WALL_LDF_2.UNIT1 180.00 90.00 S
WINDOW_SDR_2.UNIT1 EXTERIOR WINDOW   44.43 0.00 0.00 44.43 44.43 0.280 0.335 0.882             Yes WALL_SDR_2.UNIT1 90.00 90.00 E
WINDOW_LDB_2.UNIT1 EXTERIOR WINDOW   44.43 0.00 0.00 44.43 44.43 0.280 0.335 0.882             Yes WALL_LDB_2.UNIT1 0.00 90.00 N
WINDOW_SDL_2.UNIT1 EXTERIOR WINDOW   44.43 0.00 0.00 44.43 44.43 0.280 0.335 0.882             Yes WALL_SDL_2.UNIT1 270.00 90.00 W
Total or Average             355.40 0.280 0.335 0.882                      
North Total or Average             88.85 0.280 0.335 0.882                      
Non-North Total or Average             266.55 0.280 0.335 0.882                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1 EXTERIOR DOOR 0.226 0.280 40.02 WALL_LDB_1.UNIT1
DOOR_GARAGE1 EXTERIOR DOOR 0.226 0.280 112.04 WALL_LDF_1.GARAGE1


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
INT_DOOR_GARAGE1 EXTERIOR DOOR 0.203 0.280 21.01 WALL_LDB_1.GARAGE1
iz-INT_DOOR_GARAGE1 EXTERIOR DOOR 0.203 0.280 21.01 iz-WALL_LDB_1.GARAGE1



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_1.UNIT1 0.61 1.00 1.00 1.00 1.00 1.00 0.06 1.00 1.00
WINDOW_SDR_1.UNIT1 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.96 0.00
WINDOW_LDB_1.UNIT1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_1.UNIT1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_2.UNIT1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_2.UNIT1 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.96 0.00
WINDOW_LDB_2.UNIT1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_2.UNIT1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_1.UNIT1 SHADES-LIVING_UNIT1 Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_1.UNIT1 SHADES-LIVING_UNIT1 Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_1.UNIT1 SHADES-LIVING_UNIT1 Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_1.UNIT1 SHADES-LIVING_UNIT1 Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_2.UNIT1 SHADES-LIVING_UNIT1 Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_2.UNIT1 SHADES-LIVING_UNIT1 Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_2.UNIT1 SHADES-LIVING_UNIT1 Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_2.UNIT1 SHADES-LIVING_UNIT1 Interior Blind WINDOW_W_BLINDS AlwaysOff No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [Btu/h-ft2] Space Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1 LIVING_UNIT1 LIVING_UNIT1 GENERAL 0.3335 2377.10 792.73 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 713.27
LIVING PLUG-IN LIGHTING1 LIVING_UNIT1 LIVING_UNIT1 GENERAL 0.1517 2377.10 360.49 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 324.36
Interior Lighting Total       0.2426 4754.19 1153.22               1037.63


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1 43.24 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 189.40
GARAGE-LIGHTS_UNIT1 7.16 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 21.99
Exterior Lighting Total 50.41           211.39



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Central Plant

Type Reference Capacity [Btu/h] Reference Efficiency [Btuh/Btuh] Rated Capacity [Btu/h] Rated Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1 Coil:Cooling:DX:SingleSpeed   26830.94 19855.25 6975.68 0.74 4.09    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1   2.2 3.45 11.78 12.50 12.02 12.30
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coils [ SEER2 ]

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP2 [Btuh/Btuh] EER2 [Btu/W-h] SEER2 User [Btu/W-h] SEER2 Standard [Btu/W-h] IEER2 [Btu/W-h]
DX COOLING COIL_UNIT1 Coil:Cooling:DX:SingleSpeed 2.1 3.34 11.40 12.07 11.94  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER2 User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER2 Standard is calculated using AHRI Std 210/240-2023 default PLF curve and cooling coefficient of degradation. IEER Calculation was removed from the 2023 Version of the Standard.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1 Coil:Cooling:DX:SingleSpeed                


Water-to-Air Heat Pumps at Rated Temperatures Report

Coil Type Rated Total Capacity [Btu/h] Rated Sensible Capacity [Btu/h] Rated Power[Btu/h] Rated COP [Btuh/Btuh] Rated Air Dry-bulb Temperature [F] Rated Air Wet-bulb Temperature [F] Rated Water Temperature [F] Design Day used for Sizing
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


DX Heating Coils [ HSPF2 ]

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF2 [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN FUEL HEATING COIL_UNIT1 Coil:Heating:Fuel   40774.83 0.95


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
OASUPPLYFAN_UNIT1 Fan:OnOff 0.60 0.15 59.99 50.00 0.83 0.00 7.79 Ventilation    
OAEXHAUSTFAN_UNIT1 Fan:OnOff 0.60 0.15 59.99 50.00 0.83 0.00 7.79 Ventilation    
SUPPLY FAN_UNIT1 Fan:OnOff 0.50 0.06 755.58 285.00 0.38 1.00 1.82 General ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:20:00


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
MAINS PRESSURE_UNIT1 Pump:VariableSpeed Intermittent 0.00 7.827838 0.00 0.00 1.00 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1 WaterHeater:Mixed 5.35 38002.17 0.80 0.82 0.57



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1 16925.95 16925.95 7.12 755.584 755.584 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 75.00 75.00 0.00827 83.10 0.01536 59.993 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1 27623.43 27623.43 11.62 527.104 527.104 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:20:00 72.00 71.99 0.00674 -15.2 0.00036 59.993 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CENTRAL SYSTEM_UNIT1 755.58 755.58 527.10 527.10 755.5842 755.5842 755.5842 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
DX COOLING COIL_UNIT1 Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1 26830.935 19855.251 755.584247 -999. -999.00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 26630.84 22006.97 755.584247 76.87 61.72 0.00883482 53.60 50.60 0.00750000 83.10 0.01535988 72.26 7.9400 75.00 0.00826568 42.7441 16924.38 0.00 26842.13 19422.18
MAIN FUEL HEATING COIL_UNIT1 Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT1 40774.832 40774.832 -999. -999. -999.00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:20:00 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:20:00 40774.83 40774.83 -999. 65.07 53.07 0.00623764 122.00 74.12 0.00800000 -15.2 0.00036134 -15.2 -999.000 71.99 0.00674446 38.6834 27623.43 0.00 -999.0 -999.0



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [Btu/lbm-R] Dry Air Heat Capacity [Btu/lbm-R] Standard Air Density Adjusted for Elevation [lb/ft3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [ft3/min] Supply Fan Maximum Air Mass Flow Rate [lb/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [Btu/lbm-R] Plant Fluid Density [lb/ft3] Plant Maximum Fluid Mass Flow Rate [lb/s] Plant Design Fluid Return Temperature [F] Plant Design Fluid Supply Temperature [F] Plant Design Fluid Temperature Difference [deltaF] Plant Design Capacity [Btu/h] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [F] System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h] Coil Air Mass Flow Rate at Rating Conditions [lb/s] Coil Entering Air Drybulb at Rating Conditions [F] Coil Entering Air Wetbulb at Rating Conditions [F] Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] Coil Leaving Air Drybulb at Rating Conditions [F] Coil Leaving Air Wetbulb at Rating Conditions [F] Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R]
DX COOLING COIL_UNIT1 Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1 LIVING_UNIT1 Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 26830.935 19855.251 755.584247 -999. -999.00 -999.0000 1.00000 1.00000 0.2439 0.2400 0.0717 SUPPLY FAN_UNIT1 Fan:OnOff 755.584247 0.90303974   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 Sensible 26630.84 22006.97 0.9925 0.90303974 755.584247 76.87 61.72 0.00883482 11.4 53.60 50.60 0.00750000 7.4 -999. -999.0 -999.0 -999.0 972.423 25658.42 83.10 0.01535988 72.26 59.99331119 7.9400 75.00 0.00827204 75.00 0.00826568 42.7441 16924.38 0.00 26842.13 19422.18 0.86737649 80.00 67.00 0.01118466 13.2 54.51 54.49 0.00901752 8.4
MAIN FUEL HEATING COIL_UNIT1 Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1 LIVING_UNIT1 Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 40774.832 40774.832 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0717 SUPPLY FAN_UNIT1 Fan:OnOff 755.584247 0.90303974   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:20:00 unknown unknown ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:20:00 Sensible 40774.83 40774.83 1.0000 -0.252957E+04 -999. 65.07 53.07 0.00623764 8.2 122.00 74.12 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 40774.83 -15.2 0.00036134 -15.2 59.99331119 -999.000 71.99 0.00674446 71.99 0.00674446 38.6834 27623.43 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1 3901.67 5897.83 2054.17
GARAGE1 0.00 0.00 0.00
ATTIC_UNIT1 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 0.00 0.00
Facility 3901.67 5897.83 2054.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1 67.50 0.00 67.50 0.00
GARAGE1 0.00 0.00 0.00 0.00
ATTIC_UNIT1 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 0.00 0.00 0.00 0.00
Facility 67.50 0.00 67.50 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1 2.07 3.00 17050.56 0.215 0.000 0.241 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1 2.07 3.00 17050.56 0.207 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Zone Area [ft2] Design Zone Outdoor Airflow - Voz [ft3/min] Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min]
LIVING_UNIT1 CENTRAL SYSTEM_UNIT1 2.07 3.00 17050.56 2377.10 0.0000 0.000
Total Facility   2.07 3.00 17050.56 2377.10 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Infiltration [ft3] Total Ventilation and Infiltration [ft3] Dynamic Target Ventilation - Voz-dyn [ft3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
LIVING_UNIT1 31713442.25 0.00 31713442.25 35678519.65 67391961.90 31713442.25 0.00 8808.00 0.00 0.00
Total Facility 31713442.25 0.00 31713442.25 35678519.65 67391961.90 31713442.25 0.00 8808.00 0.00 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Infiltration [ft3/min] Total Ventilation and Infiltration [ft3/min] Dynamic Target Ventilation - Voz-dyn [ft3/min] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
LIVING_UNIT1 59.9933 0.0000 59.9933 67.4942 127.4875 59.9933 0.00 8808.00 0.00
Total Facility 59.9933 0.0000 59.9933 67.4942 127.4875 59.9933 0.00 8808.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
CENTRAL SYSTEM_UNIT1 0.00 0.00 0.00 31713442.25 8808.00 0.00 0.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
CENTRAL SYSTEM_UNIT1 0.0000 0.0000 0.0000 59.9933 8808.00 0.00 0.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
CENTRAL SYSTEM_UNIT1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [ft3/min] Limits and Scheduled Limits [ft3/min] Economizer [ft3/min] Exhaust Flow [ft3/min] Mixed Air Flow [ft3/min] High Humidity [ft3/min] Demand Controlled Ventilation [ft3/min] Night Ventilation [ft3/min] Demand Limiting [ft3/min] Energy Management System [ft3/min]
CENTRAL SYSTEM_UNIT1 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Surfaces by Class

Total Outdoors
Wall 25 23
Floor 5 1
Roof 6 4
Internal Mass 1 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 8 8
Door 4 2
Glass Door 0 0
Shading 4 4
Overhang 2 2
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 1
Conditioned Zones 1
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 498
Defaulted Fields 453
Fields with Defaults 2110
Autosized Fields 19
Autosizable Fields 33
Autocalculated Fields 38
Autocalculatable Fields 80



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 11539.02 789.81 11-APR-03:10 3538.65 25-JUN-18:10
Electricity:Building 8085.21 646.07 02-JAN-03:10 1518.56 01-JAN-20:10
Electricity:Zone:LIVING_UNIT1 8085.21 646.07 02-JAN-03:10 1518.56 01-JAN-20:10
Electricity:SpaceType:GENERAL 8085.21 646.07 02-JAN-03:10 1518.56 01-JAN-20:10
InteriorLights:Electricity 1037.63 23.24 01-JAN-00:10 337.99 01-JAN-19:10
InteriorLights:Electricity:Zone:LIVING_UNIT1 1037.63 23.24 01-JAN-00:10 337.99 01-JAN-19:10
InteriorLights:Electricity:SpaceType:GENERAL 1037.63 23.24 01-JAN-00:10 337.99 01-JAN-19:10
General:InteriorLights:Electricity 1037.63 23.24 01-JAN-00:10 337.99 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1 1037.63 23.24 01-JAN-00:10 337.99 01-JAN-19:10
General:InteriorLights:Electricity:SpaceType:GENERAL 1037.63 23.24 01-JAN-00:10 337.99 01-JAN-19:10
InteriorEquipment:Electricity 7047.58 602.34 02-JAN-04:10 1180.57 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1 7047.58 602.34 02-JAN-04:10 1180.57 01-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 7047.58 602.34 02-JAN-04:10 1180.57 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity 205.90 1.89 02-JAN-03:10 65.70 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1 205.90 1.89 02-JAN-03:10 65.70 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL 205.90 1.89 02-JAN-03:10 65.70 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity 105.15 1.01 02-JAN-02:10 28.48 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1 105.15 1.01 02-JAN-02:10 28.48 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL 105.15 1.01 02-JAN-02:10 28.48 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity 75.94 0.39 02-JAN-03:10 19.42 01-JAN-11:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1 75.94 0.39 02-JAN-03:10 19.42 01-JAN-11:10
gas_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL 75.94 0.39 02-JAN-03:10 19.42 01-JAN-11:10
gas_range:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_range:InteriorEquipment:Electricity:SpaceType:GENERAL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:SpaceType:GENERAL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity 3001.13 262.21 01-JAN-09:10 507.15 01-JAN-20:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1 3001.13 262.21 01-JAN-09:10 507.15 01-JAN-20:10
gas_mels:InteriorEquipment:Electricity:SpaceType:GENERAL 3001.13 262.21 01-JAN-09:10 507.15 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity 2990.78 261.30 01-JAN-09:10 505.40 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1 2990.78 261.30 01-JAN-09:10 505.40 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL 2990.78 261.30 01-JAN-09:10 505.40 01-JAN-20:10
Fans:Electricity 1583.01 100.00 12-APR-11:30 385.00 18-JAN-14:50
Fans:Electricity:Zone:LIVING_UNIT1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Electricity:HVAC 3242.42 100.00 12-APR-11:30 2182.81 11-JUN-15:30
General:Fans:Electricity 707.01 0.00 12-JAN-14:20 285.00 18-JAN-14:50
Ventilation:Fans:Electricity 876.00 100.00 10-JAN-02:00 100.00 01-JAN-00:30
ElectricityPurchased:Facility 11539.02 789.81 11-APR-03:10 3538.65 25-JUN-18:10
ElectricityPurchased:Plant 11539.02 789.81 11-APR-03:10 3538.65 25-JUN-18:10
Cogeneration:ElectricityPurchased 11539.02 789.81 11-APR-03:10 3538.65 25-JUN-18:10
General:Cogeneration:ElectricityPurchased 11539.02 789.81 11-APR-03:10 3538.65 25-JUN-18:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 11539.02 789.81 11-APR-03:10 3538.65 25-JUN-18:10
ElectricityNet:Plant 11539.02 789.81 11-APR-03:10 3538.65 25-JUN-18:10
Cogeneration:ElectricityNet 11539.02 789.81 11-APR-03:10 3538.65 25-JUN-18:10
General:Cogeneration:ElectricityNet 11539.02 789.81 11-APR-03:10 3538.65 25-JUN-18:10
HeatRecovery:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:HeatRecovery:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ExteriorLights:Electricity 211.39 0.92 01-JAN-09:10 50.41 01-JAN-19:10
Exterior-Lights:ExteriorLights:Electricity 189.40 0.00 01-JAN-06:10 43.24 01-JAN-00:10
Garage-Lights:ExteriorLights:Electricity 21.99 0.49 01-JAN-00:10 7.16 01-JAN-19:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 1659.41 0.00 01-JAN-00:10 1803.83 11-JUN-15:30
General:Cooling:Electricity 1659.41 0.00 01-JAN-00:10 1803.83 11-JUN-15:30
Electricity:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 758.33 184.05 11-APR-03:10 46593.04 09-DEC-17:10
NaturalGas:Building 110.14 184.05 02-JAN-03:10 2927.62 01-JAN-17:10
NaturalGas:Zone:LIVING_UNIT1 110.14 184.05 02-JAN-03:10 2927.62 01-JAN-17:10
NaturalGas:SpaceType:GENERAL 110.14 184.05 02-JAN-03:10 2927.62 01-JAN-17:10
InteriorEquipment:NaturalGas 110.14 184.05 02-JAN-03:10 2927.62 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1 110.14 184.05 02-JAN-03:10 2927.62 01-JAN-17:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 110.14 184.05 02-JAN-03:10 2927.62 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas 52.83 26.91 02-JAN-03:10 1349.77 01-JAN-11:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1 52.83 26.91 02-JAN-03:10 1349.77 01-JAN-11:10
gas_dryer:InteriorEquipment:NaturalGas:SpaceType:GENERAL 52.83 26.91 02-JAN-03:10 1349.77 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas 44.96 43.46 01-JAN-02:10 1845.69 01-JAN-17:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1 44.96 43.46 01-JAN-02:10 1845.69 01-JAN-17:10
gas_range:InteriorEquipment:NaturalGas:SpaceType:GENERAL 44.96 43.46 01-JAN-02:10 1845.69 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas 12.35 107.83 01-JAN-09:10 208.56 01-JAN-20:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1 12.35 107.83 01-JAN-09:10 208.56 01-JAN-20:10
gas_mels:InteriorEquipment:NaturalGas:SpaceType:GENERAL 12.35 107.83 01-JAN-09:10 208.56 01-JAN-20:10
NaturalGas:HVAC 499.68 0.00 12-JAN-14:20 34336.70 18-JAN-14:50
Heating:NaturalGas 499.68 0.00 12-JAN-14:20 34336.70 18-JAN-14:50
General:Heating:NaturalGas 499.68 0.00 12-JAN-14:20 34336.70 18-JAN-14:50
NaturalGas:Plant 148.51 0.00 01-JAN-00:10 9531.40 18-FEB-09:00
WaterSystems:NaturalGas 148.51 0.00 01-JAN-00:10 9531.40 18-FEB-09:00
Water Heater:WaterSystems:NaturalGas 148.51 0.00 01-JAN-00:10 9531.40 18-FEB-09:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 1987.08 0.00 02-JAN-02:20 0.01 04-FEB-08:20
Water:Plant 1987.08 0.00 02-JAN-02:20 0.01 04-FEB-08:20
WaterSystems:Water 1987.08 0.00 02-JAN-02:20 0.01 04-FEB-08:20
Domestic Hot Water:WaterSystems:Water 1987.08 0.00 02-JAN-02:20 0.01 04-FEB-08:20
MainsWater:Facility 1987.08 0.00 02-JAN-02:20 0.01 04-FEB-08:20
MainsWater:Plant 1987.08 0.00 02-JAN-02:20 0.01 04-FEB-08:20
WaterSystems:MainsWater 1987.08 0.00 02-JAN-02:20 0.01 04-FEB-08:20
Domestic Hot Water:WaterSystems:MainsWater 1987.08 0.00 02-JAN-02:20 0.01 04-FEB-08:20
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 151566.59 697.64 19-AUG-02:50 65682.64 03-FEB-08:10
EnergyTransfer:Building 58856.46 0.95 21-OCT-10:10 27020.56 03-FEB-06:00
EnergyTransfer:Zone:LIVING_UNIT1 58856.46 0.95 21-OCT-10:10 27020.56 03-FEB-06:00
Heating:EnergyTransfer 39627.05 0.00 12-JAN-14:20 27020.56 03-FEB-06:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1 39627.05 0.00 12-JAN-14:20 27020.56 03-FEB-06:00
General:Heating:EnergyTransfer 39627.05 0.00 12-JAN-14:20 27020.56 03-FEB-06:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1 39627.05 0.00 12-JAN-14:20 27020.56 03-FEB-06:00
Cooling:EnergyTransfer 19229.41 0.00 01-JAN-00:10 17678.68 25-JUN-17:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT1 19229.41 0.00 01-JAN-00:10 17678.68 25-JUN-17:30
General:Cooling:EnergyTransfer 19229.41 0.00 01-JAN-00:10 17678.68 25-JUN-17:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1 19229.41 0.00 01-JAN-00:10 17678.68 25-JUN-17:30
EnergyTransfer:Zone:GARAGE1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:GARAGE1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:GARAGE1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:GARAGE1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:GARAGE1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:ATTIC_UNIT1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC_UNIT1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC_UNIT1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC_UNIT1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC_UNIT1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:CRAWLSPACE_UNIT1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:CRAWLSPACE_UNIT1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CRAWLSPACE_UNIT1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CRAWLSPACE_UNIT1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:CRAWLSPACE_UNIT1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 7061.82 59.23 22-AUG-03:00 1848.19 19-FEB-09:00
PlantLoopHeatingDemand:Plant 7061.82 59.23 22-AUG-03:00 1848.19 19-FEB-09:00
WaterSystems:PlantLoopHeatingDemand 7061.82 59.23 22-AUG-03:00 1848.19 19-FEB-09:00
General:WaterSystems:PlantLoopHeatingDemand 7061.82 59.23 22-AUG-03:00 1848.19 19-FEB-09:00
EnergyTransfer:HVAC 85648.32 358.96 21-OCT-12:50 37312.29 02-FEB-06:30
HeatRecoveryForHeating:EnergyTransfer 12310.24 0.00 15-APR-10:30 4692.42 02-FEB-06:30
HeatRecoveryForCooling:EnergyTransfer 167.74 0.00 01-JAN-00:10 854.61 04-AUG-15:00
HeatingCoils:EnergyTransfer 47469.54 0.00 12-JAN-14:20 32619.87 18-JAN-14:50
CoolingCoils:EnergyTransfer 25700.80 0.00 01-JAN-00:10 25439.86 11-JUN-15:30
EnergyTransfer:Plant 7061.82 59.23 22-AUG-03:00 1848.19 19-FEB-09:00
WaterSystems:EnergyTransfer 7061.82 59.23 22-AUG-03:00 1848.19 19-FEB-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 7061.82 59.23 22-AUG-03:00 1848.19 19-FEB-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1 273.177 -235.72 42144.642 -1598.08 0.000 0.000 4581.592 3542.897 21815.363 18092.785 11.094 188.597 0.000 0.000 -16052.84 -1032.37 -21731.47 -29813.26
GARAGE1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 6.772 7.866 4192.886 0.000 0.000 -47.12 -4160.40 0.000
ATTIC_UNIT1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 16641.621 767.887 21494.926 0.000 0.000 -225.30 -38679.13 -0.27
CRAWLSPACE_UNIT1 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.004 3200.275 60493.660 0.000 0.000 -0.00 -63693.93 0.000
Total Facility 273.177 -235.72 42144.642 -1598.08 0.000 0.000 4581.592 3542.897 21815.363 18092.785 16659.490 4164.624 86181.472 0.000 -16052.84 -1304.80 -128264.94 -29813.53


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1 25-JUN-17:34 0.00 0.03 0.00 -1.5 0.00 0.00 395.19 773.02 3989.18 9556.05 1.25 1487.18 1478.67 0.00 0.00 0.00 0.00 0.00
GARAGE1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC_UNIT1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 25-JUN-17:34 0.00 0.03 0.00 -1.5 0.00 0.00 395.19 773.02 3989.18 9556.05 1.25 8664.64 1298.22 0.00 0.00 -1117.2 -5879.8 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1 03-FEB-05:00 -1381.3 0.00 28401.78 0.00 0.00 0.00 811.46 495.53 1825.09 0.00 0.00 0.00 0.00 0.00 -8251.1 -874.4 -8717.3 -12309.8
GARAGE1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC_UNIT1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE_UNIT1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 03-FEB-05:00 -1381.3 0.00 28401.78 0.00 0.00 0.00 811.46 495.53 1825.09 0.00 7690.03 0.00 6079.78 0.00 -8251.1 -874.4 -34796.9 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1 755.5842 0.0000 3.0000 1.0000 Calculated from schedules 0.0000 755.5842 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1 755.5842 0.0000 3.0000 1.0000 Calculated from schedules 0.0000 755.5842 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1 CENTRAL SYSTEM_UNIT1 0.000000 3.0000 0.000000 2377.10 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1 0.000000 3.00 0.000000 2377.0955 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1 CENTRAL SYSTEM_UNIT1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 755.5842 755.5842 755.5842 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1 755.5842 755.5842 755.5842 755.5842 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1 CENTRAL SYSTEM_UNIT1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 755.5842 755.5842 755.5842 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1 755.5842 755.5842 755.5842 755.5842 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Sec1.1A-General Information

Data
Weather File ANNUAL ** Rochester International Arpt MN USA TMY3 WMO#=726440
Total gross floor area [ft2] 5154.23
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1 2377.10 2377.10 0.00 168.00
GARAGE1 400.04 0.00 400.04 0.00
ATTIC_UNIT1 1188.55 0.00 1188.55 0.00
CRAWLSPACE_UNIT1 1188.55 0.00 1188.55 0.00
Totals 5154.23 2377.10 2777.13  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 67.50
Number of hours cooling loads not met 0.00
Number of hours not met 67.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 0.00 0.00 499.68 34336.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 1659.41 1803.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 1037.63 337.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Exterior-Lights 189.40 43.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Garage-Lights 21.99 7.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- dishwasher 205.90 65.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- refrigerator 668.67 91.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- clotheswasher 105.15 28.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- gas_dryer 75.94 19.42 52.83 1349.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- gas_range 0.00 0.00 44.96 1845.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- gas_mels 3001.13 507.15 12.35 208.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- IECC_adj 2990.78 505.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 707.01 285.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation 876.00 100.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 148.51 9531.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 24063.37 39399.03
Natural Gas 11013.86 75833.24
Additional 0.00 0.00
Total 35077.23 115232.27


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.20
Space Heating 0.00
Space Cooling 0.32
Fans (All) 0.31
Service Water Heating 0.00
Receptacle Equipment 1.37
Miscellaneous (All) 2.24
Subtotal 2.24


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 2.84
Service Water Heating 0.84
Miscellaneous (All) 4.31
Subtotal 4.31


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 3.07
Space Heating 43.36
Space Cooling 4.92
Fans (All) 4.69
Service Water Heating 12.89
Receptacle Equipment 30.44
Miscellaneous 0.63


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OCCUPANCY 6031. 8760.
INTERIORLIGHTING 2852. 8760.
INTERIORLIGHTINGHE 3070. 8760.
INTERIORLIGHTINGHE_OS 2910. 8760.
INTERIORLIGHTINGHE_VS 2149. 8760.
EXTERIORLIGHTING 4380. 4380.
REFRIGERATOR 7343. 8760.
MISCPLUGLOAD 5918. 8760.
COOKINGRANGE 2434. 8760.
DISHWASHER_FLOW_SCH 1777. 8760.
CLOTHESWASHER_FLOW_SCH 2094. 8760.
DISHWASHER_EQUIP_SCH 3134. 8760.
CLOTHESWASHER_EQUIP_SCH 3692. 8760.
CLOTHESDRYER 3911. 8760.
SHADING_2012IECC 0. 0.
SHADING_2012IECC_HERS 7007. 8760.
SINKSENSSCHEDULE 6025. 8760.
SINKLATSCHEDULE 2735. 8760.
SHOWERSENSSCHEDULE 4492. 8760.
SHOWERLATSCHEDULE 4268. 8760.
BATHSENSSCHEDULE 8760. 8760.
BATHLATSCHEDULE 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
HEATING_SCH THERMOSTAT_LIVING DUAL SP CONTROL January 72.00 365 72.00 365
COOLING_SCH THERMOSTAT_LIVING DUAL SP CONTROL July 75.00 365 75.00 365



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupiedHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 19:32:11

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupiedHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1

Timestamp: 2024-06-27 19:32:11

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 740.833 111.372 111.372
February 4.333 0.137 640.528 75.713 75.713
March 38.222 1.083 626.444 46.396 46.396
April 189.800 14.809 407.942 34.505 34.505
May 450.128 31.190 100.958 33.278 33.278
June 597.250 62.422 39.917 63.025 63.025
July 712.278 75.235 0.000 75.235 75.235
August 663.472 65.085 2.667 65.109 65.109
September 431.719 36.720 139.736 40.102 40.102
October 122.944 4.973 429.458 20.334 20.334
November 26.181 0.907 610.083 53.448 53.448
December 0.000 0.000 740.139 88.494 88.494
           
Annual Sum or Average 3236.328 292.562 4478.706 707.012 707.012
Minimum of Months 0.000 0.000 0.000 20.334 20.334
Maximum of Months 712.278 75.235 740.833 111.372 111.372



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1

Timestamp: 2024-06-27 19:32:11

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 17133.19 0.00 0.00
February 12872.11 0.00 0.00
March 6970.84 0.00 0.00
April 3131.00 0.00 0.00
May 321.20 0.00 0.00
June 95.83 0.00 0.00
July 0.00 0.00 0.00
August 3.59 0.00 0.00
September 537.64 0.00 0.00
October 2363.14 0.00 0.00
November 8352.23 0.00 0.00
December 13613.70 0.00 0.00
       
Annual Sum or Average 5415.06 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 17133.19 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1

Timestamp: 2024-06-27 19:32:11

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.15
May 0.00 0.00 0.30
June 0.00 0.00 0.64
July 0.00 0.00 0.75
August 0.00 0.00 0.65
September 0.00 0.00 0.36
October 0.00 0.00 0.05
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.24
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1

Timestamp: 2024-06-27 19:32:11

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1509.23 1123.67
February 0.00 0.00 1535.35 1032.48
March 0.00 0.00 1518.01 1130.20
April 0.00 0.00 1458.54 1050.89
May 0.00 0.00 1360.29 1012.77
June 0.00 0.00 1269.60 914.76
July 0.00 0.00 1200.90 894.10
August 0.00 0.00 1168.23 869.78
September 0.00 0.00 1194.49 860.64
October 0.00 0.00 1266.11 942.65
November 0.00 0.00 1351.92 974.07
December 0.00 0.00 1444.04 1075.12
         
Annual Sum or Average 0.00 0.00 1355.33 11881.15
Minimum of Months 0.00 0.00 1168.23 860.64
Maximum of Months 0.00 0.00 1535.35 1130.20



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1

Timestamp: 2024-06-27 19:32:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.10 10530.10
February 1.91 7180.72
March 8.33 4368.79
April 88.06 1910.55
May 181.68 194.26
June 333.75 56.46
July 395.00 0.00
August 339.01 1.95
September 211.03 324.83
October 35.17 1491.01
November 7.22 5069.18
December 0.12 8499.20
     
Annual Sum or Average 1601.38 39627.05
Minimum of Months 0.10 0.00
Maximum of Months 395.00 10530.10



Table of Contents

Report: HEATING AND COOLING LOADS

For: GARAGE1

Timestamp: 2024-06-27 19:32:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: ATTIC_UNIT1

Timestamp: 2024-06-27 19:32:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: CRAWLSPACE_UNIT1

Timestamp: 2024-06-27 19:32:11

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00