Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 16:06
Tabular Output Report in Format: HTML
Building: US+MF+CZ1AWH+elecres+slab+IECC_2021
Environment: ANNUAL ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2024-06-27 16:06:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 578513.47 | 18.54 | 26.77 |
Net Site Energy | 578513.47 | 18.54 | 26.77 |
Total Source Energy | 1832152.16 | 58.70 | 84.78 |
Net Source Energy | 1832152.16 | 58.70 | 84.78 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 31210.83 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 9600.87 |
Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 8889.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 137988.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 31269.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 39549.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312247.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 578513.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312247.30 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 8889.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 137988.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation | 8652.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 22617.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312247.30 | |
Water Heater | 4468.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 35080.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Unassigned | 8889.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 137988.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 31269.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 39549.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312247.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 |
Other | 13.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 26.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 6.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 |
Other | 9.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 18.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 578513.471 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 578513.471 | 100.00 |
Total On-Site and Utility Electric Sources | 578513.471 | 100.00 |
Total Electricity End Uses | 578513.471 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 312247.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 312247.30 | 100.00 |
Total Water End Uses | 312247.30 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 43.83 |
Time Setpoint Not Met During Occupied Cooling | 2.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4005.33 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR |HEATING AND COOLING LOADS
| BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
GeneralValue | |
Program Version and Build | EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 16:06 |
RunPeriod | ANNUAL |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [ft] | 36.09 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16177.97 | 6115.58 | 1973.41 | 6115.58 | 1973.41 |
Above Ground Wall Area [ft2] | 16177.97 | 6115.58 | 1973.41 | 6115.58 | 1973.41 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.15 | 8.69 | 26.94 | 8.69 | 26.94 |
Above Ground Window-Wall Ratio [%] | 13.15 | 8.69 | 26.94 | 8.69 | 26.94 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
BREEZEWAY | 1798.16 | No | Yes | 30553.25 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
ATTIC | 7802.71 | No | Yes | 52795.56 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
Total | 31210.83 | 267088.19 | 16177.97 | 0.00 | 2126.74 | 2126.74 | 0.4037 | 866.97 | 2.0143 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.5831 | 600.28 | 2.9092 | |||
Unconditioned Total | 9600.87 | 83348.81 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | Tags | |
BREEZEWAY | 1798.16 | No | Yes | 1.00 | BREEZEWAY | GENERAL | BREEZEWAY | 0.0000 | 0.00 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.9092 | |
ATTIC | 7802.71 | No | Yes | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5831 | 600.28 | 2.9092 | |
Total | 31210.83 | 0.4037 | 866.97 | 2.0143 | |||||||
Conditioned Total | 21609.96 | 0.5831 | 600.28 | 2.9092 | |||||||
Unconditioned Total | 9600.87 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [ft2] | Conditioned Area [ft2] | Unconditioned Area [ft2] | Not Part of Total Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
GENERAL | 31210.83 | 21609.96 | 9600.87 | 0.00 | 0.4037 | 866.97 | 2.0143 |
Total | 31210.83 | 21609.96 | 9600.87 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 13-NOV-08:00 | - | - | - | - | - | - | - | - | - | - | - | 01-JAN-08:39 |
Heating | 69.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 33.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 32.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 148.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 69.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 5.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 0.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 4.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 3.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 3.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 19.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation | 0.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | |
Water Heater | 0.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Gasoline [kBtu] | Source Diesel [kBtu] | Source Coal [kBtu] | Source Fuel Oil No 1 [kBtu] | Source Fuel Oil No 2 [kBtu] | Source Propane [kBtu] | Source Other Fuel 1 [kBtu] | Source Other Fuel 2 [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 28153.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 437010.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 122590.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65251.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 954861.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 99031.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 125252.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1832152.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 1.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 84.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 14.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 30.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 58.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 348.06 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 195.18 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 264.64 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 352.42 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 204.53 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 269.42 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 378.31 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 216.46 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 285.09 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 383.90 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 225.51 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 289.68 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 331.36 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 326.99 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 445.84 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 287.96 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 281.66 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 450.77 |
Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | Sum of Air Terminal Maximum Flow Rates [ft3/min] | Adjusted Heating Design Air Flow Rate [ft3/min] | Adjusted Cooling Design Air Flow Rate [ft3/min] | Adjusted Main Design Air Flow Rate [ft3/min] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 348.06 | 348.06 | 348.06 | 348.06 | 348.06 | 348.06 | 1.00 | 1.00 | 348.06 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 195.18 | 195.18 | 195.18 | 195.18 | 195.18 | 195.18 | 1.00 | 1.00 | 195.18 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 264.64 | 264.64 | 264.64 | 264.64 | 264.64 | 264.64 | 1.00 | 1.00 | 264.64 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 352.42 | 352.42 | 352.42 | 352.42 | 352.42 | 352.42 | 1.00 | 1.00 | 352.42 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 204.53 | 204.53 | 204.53 | 204.53 | 204.53 | 204.53 | 1.00 | 1.00 | 204.53 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 269.42 | 269.42 | 269.42 | 269.42 | 269.42 | 269.42 | 1.00 | 1.00 | 269.42 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 378.31 | 378.31 | 378.31 | 378.31 | 378.31 | 378.31 | 1.00 | 1.00 | 378.31 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 216.46 | 216.46 | 216.46 | 216.46 | 216.46 | 216.46 | 1.00 | 1.00 | 216.46 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 285.09 | 285.09 | 285.09 | 285.09 | 285.09 | 285.09 | 1.00 | 1.00 | 285.09 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 383.90 | 383.90 | 383.90 | 383.90 | 383.90 | 383.90 | 1.00 | 1.00 | 383.90 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 225.51 | 225.51 | 225.51 | 225.51 | 225.51 | 225.51 | 1.00 | 1.00 | 225.51 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 289.68 | 289.68 | 289.68 | 289.68 | 289.68 | 289.68 | 1.00 | 1.00 | 289.68 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 445.84 | 445.84 | 445.84 | 445.84 | 445.84 | 445.84 | 1.00 | 1.00 | 445.84 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 281.66 | 281.66 | 281.66 | 281.66 | 281.66 | 281.66 | 1.00 | 1.00 | 281.66 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.99 | 326.99 | 326.99 | 326.99 | 326.99 | 326.99 | 1.00 | 1.00 | 326.99 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 450.77 | 450.77 | 450.77 | 450.77 | 450.77 | 450.77 | 1.00 | 1.00 | 450.77 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 287.96 | 287.96 | 287.96 | 287.96 | 287.96 | 287.96 | 1.00 | 1.00 | 287.96 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 331.36 | 331.36 | 331.36 | 331.36 | 331.36 | 331.36 | 1.00 | 1.00 | 331.36 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 348.06 | 1.16 | 0.701083 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 195.18 | 0.650465 | 0.701083 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 264.64 | 0.881962 | 0.701083 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 352.42 | 1.17 | 0.701083 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 204.53 | 0.681611 | 0.701083 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 269.42 | 0.897875 | 0.701083 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 378.31 | 1.26 | 0.701083 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 216.46 | 0.721387 | 0.701083 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 285.09 | 0.950095 | 0.701083 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 383.90 | 1.28 | 0.701083 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 225.51 | 0.751554 | 0.701083 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 289.68 | 0.965410 | 0.701083 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 445.84 | 1.49 | 0.701083 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 281.66 | 0.938670 | 0.701083 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 326.99 | 1.09 | 0.701083 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 450.77 | 1.50 | 0.701083 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 287.96 | 0.959653 | 0.701083 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 331.36 | 1.10 | 0.701083 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 348.06 | 348.06 | 348.06 | 4858.48 | 1.16 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 195.18 | 195.18 | 195.18 | 3807.26 | 0.650465 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 264.64 | 264.64 | 264.64 | 4858.55 | 0.881962 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 352.42 | 352.42 | 352.42 | 4860.41 | 1.17 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 204.53 | 204.53 | 204.53 | 3806.45 | 0.681611 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 269.42 | 269.42 | 269.42 | 4855.01 | 0.897875 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 378.31 | 378.31 | 378.31 | 4653.13 | 1.26 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 216.46 | 216.46 | 216.46 | 3616.94 | 0.721387 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 285.09 | 285.09 | 285.09 | 4651.21 | 0.950095 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 383.90 | 383.90 | 383.90 | 4654.33 | 1.28 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 225.51 | 225.51 | 225.51 | 3616.94 | 0.751554 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 289.68 | 289.68 | 289.68 | 4646.78 | 0.965410 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 445.84 | 445.84 | 445.84 | 5917.57 | 1.49 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 281.66 | 281.66 | 281.66 | 4727.94 | 0.938670 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 326.99 | 326.99 | 326.99 | 5914.08 | 1.09 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 450.77 | 450.77 | 450.77 | 5920.22 | 1.50 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 287.96 | 287.96 | 287.96 | 4728.46 | 0.959653 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 331.36 | 331.36 | 331.36 | 5912.60 | 1.10 | 1.00 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 348.06 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 195.18 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 264.64 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 352.42 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 204.53 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 269.42 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 378.31 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 216.46 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 285.09 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 383.90 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 225.51 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 289.68 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 445.84 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 281.66 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 326.99 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 450.77 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 287.96 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 331.36 |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | 160.01 |
Design Size Nominal Capacity [Btu/h] | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 5587.25 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 4378.35 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 5587.34 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 5589.48 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 4377.42 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 5583.26 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 5351.10 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 4159.48 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 5348.89 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 5352.48 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 4159.48 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 5343.80 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 6805.21 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 5437.13 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 6801.19 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 6808.25 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 5437.73 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 6799.50 |
Evaporator air flow rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 160.01 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 2.09 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
VersionVersion ID | |
1 | 23.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | No | Yes | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.200 | 0.200 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 72.07 | 69.64 | 68.99 | 69.55 | 72.82 | 76.50 | 79.95 | 82.44 | 83.17 | 82.00 | 79.18 | 75.61 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {ft} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Sensor Height Above Ground {ft} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 32.810 | 0.140 | 885.870 | 4.921 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {ft} | Standard Pressure at Elevation {psi} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 36.09 | 15. | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{F} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} | Fixed Default Water Mains Temperature{F} | |
1 | Correlation | NA | 76.08 | 15.66 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | US+MF+CZ1AWH+elecres+slab+IECC_2021 | 0.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Algorithm {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
Space Heat Balance Sizing |
Space Heat Balance Simulation |
|
1 | ThirdOrderBackwardDifference | No | No |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Gradient Coefficient {F/ft} | |
1 | 0.220 | 1213.970 | 0.003566 |
Material Name | ThermalResistance {m2-K/w} | Roughness | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | Absorptance:Thermal | Absorptance:Solar | Absorptance:Visible | |
1 | SHEATHING_CONSOL_LAYER | 0.1351 | Rough | 0.0417 | 9.402E-002 | 42.764 | 0.280 | 0.9000 | 0.7000 | 0.7000 |
2 | CEIL_CONSOL_LAYER | 4.9646 | Rough | 1.0053 | 6.172E-002 | 2.618 | 0.185 | 0.9000 | 0.7000 | 0.7000 |
3 | FLOOR_CONSOL_LAYER | 1.9554E-005 | Rough | 0.0008 | 12.990 | 3.438 | 0.219 | 0.9000 | 0.7000 | 0.7000 |
4 | BSMTWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
5 | CRAWLWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
6 | WALL_CONSOL_LAYER | 1.5339 | Rough | 0.2917 | 5.796E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
7 | VERY HIGH REFLECTIVITY SURFACE | 2.1097E-006 | Smooth | 0.0016 | 237.000 | 168.680 | 0.216 | 0.9000 | 5.0000E-002 | 5.0000E-002 |
8 | GYPSUMBOARD-5/16IN | 5.0054E-002 | Rough | 0.0260 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
9 | COPPERPIPE | 4.7506E-005 | MediumRough | 0.0625 | 401.000 | 140.026 | 0.200 | 0.9000 | 0.6500 | 0.6500 |
10 | F08 METAL SURFACE | 1.7668E-005 | Smooth | 0.0026 | 45.280 | 488.437 | 0.119 | 0.9000 | 0.7000 | 0.7000 |
11 | CONCRETE_4IN | 7.7356E-002 | Rough | 0.3330 | 1.312 | 140.014 | 0.111 | 0.9000 | 0.7000 | 0.7000 |
12 | ASPHALT_SHINGLE | 7.7448E-002 | MediumRough | 0.0208 | 8.186E-002 | 70.000 | 0.300 | 0.9000 | 0.7500 | 0.7000 |
13 | WOOD_SHINGLE | 0.1115 | MediumSmooth | 0.0417 | 0.114 | 26.600 | 0.390 | 0.9000 | 0.7000 | 0.7000 |
14 | SLATE_SHINGLE | 8.8061E-003 | MediumSmooth | 0.0417 | 1.442 | 100.000 | 0.300 | 0.9000 | 0.7000 | 0.7000 |
15 | CEMENT_STUCCO | 2.6422E-002 | MediumSmooth | 0.0625 | 0.721 | 116.464 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
16 | SYN_STUCCO | 3.5237E-002 | MediumSmooth | 0.0100 | 8.650E-002 | 24.971 | 0.210 | 0.7000 | 0.7000 | 0.7000 |
17 | DRYWALL_1/2IN | 7.9331E-002 | MediumSmooth | 0.0417 | 0.160 | 50.000 | 0.260 | 0.9000 | 0.7000 | 0.7000 |
18 | OSB_5/8IN | 0.1365 | MediumSmooth | 0.0521 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
19 | OSB_7/16IN | 9.5550E-002 | MediumSmooth | 0.0365 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
20 | BLOWN_R30 | 5.1614 | MediumRough | 0.6975 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
21 | BLOWN_R30_TOP | 2.8489 | MediumRough | 0.3849 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
22 | PLYWOOD_3/4IN | 0.1650 | Rough | 0.0625 | 0.115 | 34.003 | 0.161 | 0.9000 | 0.7000 | 0.7000 |
23 | BATT_R19 | 7.3089 | MediumRough | 0.0833 | 3.475E-003 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
24 | LUMBER_2X4 | 0.7709 | Rough | 0.2920 | 0.115 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
25 | CARPET_N_PAD | 0.4224 | MediumSmooth | 0.0833 | 6.013E-002 | 2.000 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
26 | BATT_R13 | 2.2936 | MediumRough | 0.2917 | 3.876E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
27 | OSB_1/2IN | 0.1092 | MediumSmooth | 0.0417 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
28 | SOIL_12IN | 0.1761 | Rough | 1.0000 | 1.731 | 115.011 | 0.056 | 0.9000 | 0.7000 | 0.7000 |
29 | DOOR_CONST | 0.3522 | Smooth | 0.0832 | 7.201E-002 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
30 | GYP_BOARD_1/2IN | 8.0130E-002 | Rough | 0.0417 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
31 | STD WOOD 6INCH | 1.2500 | MediumSmooth | 0.4921 | 0.120 | 33.711 | 0.289 | 0.9000 | 0.7000 | 0.7000 |
32 | PIPE INSULATION | 0.3830 | VeryRough | 0.0417 | 3.317E-002 | 5.681 | 0.200 | 0.9000 | 0.5000 | 0.5000 |
33 | MANF_WALL_AIRGAP | 0.1200 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
34 | BLDG_PAPER_FELT | 1.0567E-002 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
35 | R_HIGH | 177.0000 | MediumRough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
36 | CLEAR ACRYLIC PLASTIC | 3.3333E-003 | VerySmooth | 0.0098 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
37 | DIFFUSING ACRYLIC PLASTIC | 2.4444E-003 | VerySmooth | 0.0072 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
38 | INT_BLIND | 0.0000 | Rough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.0000 | 0.0000 | 0.0000 |
39 | GLASS | 0.1815 | VerySmooth | 0.0649 | 0.109 | 0.000 | 0.000 | 0.8400 | 0.0000 | 0.0000 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Name | Combined convective/radiative film coefficient {Btu/h-ft2-F} | User selected Constant Temperature {F} | Coefficient modifying the constant temperature term | Coefficient modifying the external dry bulb temperature term | Coefficient modifying the ground temperature term | Coefficient modifying the wind speed term {s/m} | Coefficient modifying the zone air temperature term | Constant Temperature Schedule Name | Sinusoidal Variation | Period of Sinusoidal Variation | Previous Other Side Temperature Coefficient | Minimum Other Side Temperature {F} | Maximum Other Side Temperature {F} | |
1 | SURFPROPOTHSDCOEFSLABAVERAGE | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABAVERAGESURFACETEMP | NO | 24.000 | 0.000 | N/A | N/A |
2 | SURFPROPOTHSDCOEFSLABPERIMETER | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABPERIMETERTEMP | NO | 24.000 | 0.000 | N/A | N/A |
3 | SURFPROPOTHSDCOEFSLABCORE | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABCORETEMP | NO | 24.000 | 0.000 | N/A | N/A |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{F} |
Surface Convection Coefficient Lower Limit {Btu/h-ft2-F} |
Surface Convection Coefficient Upper Limit {Btu/h-ft2-F} |
|
1 | CTF - ConductionTransferFunction | 392. | 0.02 | 176.1 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 60 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 20 | 171 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {ft} | Origin Y-Coordinate {ft} | Origin Z-Coordinate {ft} | Centroid X-Coordinate {ft} | Centroid Y-Coordinate {ft} | Centroid Z-Coordinate {ft} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {ft} | Maximum X {ft} | Minimum Y {ft} | Maximum Y {ft} | Minimum Z {ft} | Maximum Z {ft} | Ceiling Height {ft} | Volume {ft3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {ft2} | Exterior Gross Wall Area {ft2} | Exterior Net Wall Area {ft2} | Exterior Window Area {ft2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BREEZEWAY | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.55 | 13.26 | 1 | 1 | 1 | 0.00 | 119.89 | 30.05 | 35.04 | 0.49 | 25.99 | 17.00 | 30553.07 | TARP | DOE-2 | 1798.18 | 0.00 | 0.00 | 0.00 | 4 | 0 | 0 | Yes |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
4 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
5 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
6 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
7 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
8 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
9 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
10 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
11 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
12 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
13 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
14 | ATTIC | 0.0 | -134.9 | 51.61 | 0.00 | 59.94 | 32.55 | 29.56 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | 25.99 | 39.54 | 6.76 | 52795.39 | TARP | DOE-2 | 7802.66 | 881.33 | 881.33 | 0.00 | 11 | 0 | 0 | Yes |
15 | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
16 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
17 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
18 | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
19 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
20 | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
Zone Name | Floor Area {ft2} | # Occupants | Area per Occupant {ft2/person} | Occupant per Area {person/ft2} | Interior Lighting {Btu/h-ft2} | Electric Load {Btu/h-ft2} | Gas Load {Btu/h-ft2} | Other Load {Btu/h-ft2} | Hot Water Eq {Btu/h-ft2} | Steam Equipment {Btu/h-ft2} | Sum Loads per Area {Btu/h-ft2} | Outdoor Controlled Baseboard Heat | |
1 | BREEZEWAY | 1798.18 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
4 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
5 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
6 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
7 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
8 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
9 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
10 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
11 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
12 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
13 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
14 | ATTIC | 7802.66 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
15 | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
16 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
17 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
18 | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
19 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
20 | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Number of People {} | People/Floor Area {person/ft2} | Floor Area per person {ft2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
2 | PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
3 | PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
4 | PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
5 | PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
6 | PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
7 | PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
8 | PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
9 | PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
10 | PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
11 | PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
12 | PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
13 | PEOPLE_UNIT1_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
14 | PEOPLE_UNIT2_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
15 | PEOPLE_UNIT3_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
16 | PEOPLE_UNIT1_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
17 | PEOPLE_UNIT2_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
18 | PEOPLE_UNIT3_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Lighting Level {Btu/h} | Lights/Floor Area {Btu/h-ft2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {Btu/h} | Nominal Maximum Lighting Level {Btu/h} | |
1 | LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
2 | LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
3 | LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
4 | LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
5 | LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
6 | LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
7 | LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
8 | LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
9 | LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
10 | LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
11 | LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
12 | LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
13 | LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
14 | LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
15 | LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
16 | LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
17 | LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
18 | LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
19 | LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
20 | LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
21 | LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
22 | LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
23 | LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
24 | LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
25 | LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
26 | LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
27 | LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
28 | LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
29 | LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
30 | LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
31 | LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
32 | LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
33 | LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
34 | LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
35 | LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
36 | LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
1 | DISHWASHER1_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
2 | REFRIGERATOR1_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
3 | CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
4 | ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
5 | ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
6 | TELEVISION1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
7 | ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
8 | IECC_ADJ1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
9 | DISHWASHER2_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
10 | REFRIGERATOR2_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
11 | CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
12 | ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
13 | ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
14 | TELEVISION2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
15 | ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
16 | IECC_ADJ2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
17 | DISHWASHER3_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
18 | REFRIGERATOR3_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
19 | CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
20 | ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
21 | ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
22 | TELEVISION3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
23 | ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
24 | IECC_ADJ3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
25 | DISHWASHER1_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
26 | REFRIGERATOR1_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
27 | CLOTHESWASHER1_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
28 | ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
29 | ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
30 | TELEVISION1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
31 | ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
32 | IECC_ADJ1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
33 | DISHWASHER2_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
34 | REFRIGERATOR2_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
35 | CLOTHESWASHER2_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
36 | ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
37 | ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
38 | TELEVISION2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
39 | ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
40 | IECC_ADJ2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
41 | DISHWASHER3_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
42 | REFRIGERATOR3_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
43 | CLOTHESWASHER3_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
44 | ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
45 | ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
46 | TELEVISION3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
47 | ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
48 | IECC_ADJ3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
49 | DISHWASHER1_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
50 | REFRIGERATOR1_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
51 | CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
52 | ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
53 | ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
54 | TELEVISION1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
55 | ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
56 | IECC_ADJ1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
57 | DISHWASHER2_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
58 | REFRIGERATOR2_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
59 | CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
60 | ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
61 | ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
62 | TELEVISION2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
63 | ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
64 | IECC_ADJ2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
65 | DISHWASHER3_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
66 | REFRIGERATOR3_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
67 | CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
68 | ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
69 | ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
70 | TELEVISION3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
71 | ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
72 | IECC_ADJ3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
73 | DISHWASHER1_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
74 | REFRIGERATOR1_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
75 | CLOTHESWASHER1_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
76 | ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
77 | ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
78 | TELEVISION1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
79 | ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
80 | IECC_ADJ1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
81 | DISHWASHER2_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
82 | REFRIGERATOR2_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
83 | CLOTHESWASHER2_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
84 | ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
85 | ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
86 | TELEVISION2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
87 | ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
88 | IECC_ADJ2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
89 | DISHWASHER3_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
90 | REFRIGERATOR3_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
91 | CLOTHESWASHER3_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
92 | ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
93 | ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
94 | TELEVISION3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
95 | ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
96 | IECC_ADJ3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
97 | DISHWASHER1_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
98 | REFRIGERATOR1_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
99 | CLOTHESWASHER1_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
100 | ELECTRIC_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
101 | ELECTRIC_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
102 | TELEVISION1_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
103 | ELECTRIC_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
104 | IECC_ADJ1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
105 | DISHWASHER2_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
106 | REFRIGERATOR2_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
107 | CLOTHESWASHER2_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
108 | ELECTRIC_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
109 | ELECTRIC_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
110 | TELEVISION2_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
111 | ELECTRIC_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
112 | IECC_ADJ2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
113 | DISHWASHER3_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
114 | REFRIGERATOR3_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
115 | CLOTHESWASHER3_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
116 | ELECTRIC_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
117 | ELECTRIC_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
118 | TELEVISION3_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
119 | ELECTRIC_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
120 | IECC_ADJ3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
121 | DISHWASHER1_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
122 | REFRIGERATOR1_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
123 | CLOTHESWASHER1_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
124 | ELECTRIC_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
125 | ELECTRIC_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
126 | TELEVISION1_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
127 | ELECTRIC_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
128 | IECC_ADJ1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
129 | DISHWASHER2_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
130 | REFRIGERATOR2_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
131 | CLOTHESWASHER2_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
132 | ELECTRIC_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
133 | ELECTRIC_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
134 | TELEVISION2_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
135 | ELECTRIC_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
136 | IECC_ADJ2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
137 | DISHWASHER3_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
138 | REFRIGERATOR3_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
139 | CLOTHESWASHER3_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
140 | ELECTRIC_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
141 | ELECTRIC_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
142 | TELEVISION3_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
143 | ELECTRIC_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
144 | IECC_ADJ3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
Construction Name | Index | #Layers | #CTFs | Time Step {Hours} | ThermalConductance {Btu/h-ft2-F} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | EXTERIOR WALL | 1 | 5 | 10 | 0.167 | 0.0937 | 0.700 | 0.900 | 0.700 | 0.700 | MediumSmooth |
2 | CEILING-FLOOR-LAYER | 3 | 1 | 5 | 0.167 | 0.228 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | EXTERIOR FLOOR | 4 | 3 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
4 | INTERIOR CEILING | 6 | 2 | 8 | 0.167 | 0.0349 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
5 | ATTIC FLOOR | 7 | 2 | 8 | 0.167 | 0.0349 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | INTERIORWALL | 9 | 3 | 5 | 0.167 | 0.597 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | EXTERIOR ROOF | 11 | 2 | 4 | 0.167 | 0.943 | 0.900 | 0.900 | 0.750 | 0.700 | MediumRough |
8 | EXTERIOR DOOR | 14 | 1 | 5 | 0.167 | 0.500 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | GABLE_END | 16 | 5 | 6 | 0.167 | 0.428 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | ThermalResistance {m2-K/w} | |
1 | SYN_STUCCO | 0.0098 | 0.086 | 24.971 | 0.210 | 0.3524E-01 |
2 | SHEATHING_CONSOL_LAYER | 0.0417 | 0.094 | 42.764 | 0.280 | 0.1351 |
3 | OSB_7/16IN | 0.0364 | 0.116 | 34.000 | 0.290 | 0.9555E-01 |
4 | WALL_CONSOL_LAYER | 0.2917 | 0.058 | 7.541 | 0.248 | 1.534 |
5 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
6 | LUMBER_2X4 | 0.2920 | 0.115 | 32.003 | 0.183 | 0.7709 |
7 | FLOOR_CONSOL_LAYER | 0.0010 | 12.990 | 3.438 | 0.219 | 0.1955E-04 |
8 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
9 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
10 | CEIL_CONSOL_LAYER | 1.0053 | 0.062 | 2.618 | 0.185 | 4.965 |
11 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
12 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
13 | CEIL_CONSOL_LAYER | 1.0053 | 0.062 | 2.618 | 0.185 | 4.965 |
14 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
15 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
16 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
17 | ASPHALT_SHINGLE | 0.0207 | 0.082 | 70.000 | 0.300 | 0.7745E-01 |
18 | OSB_1/2IN | 0.0417 | 0.116 | 34.000 | 0.290 | 0.1092 |
19 | DOOR_CONST | 0.0833 | 0.072 | 32.003 | 0.183 | 0.3522 |
20 | CEMENT_STUCCO | 0.0627 | 0.721 | 116.464 | 0.210 | 0.2642E-01 |
21 | BLDG_PAPER_FELT | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1057E-01 |
22 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
23 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 10 | 0.53690791E-10 | -0.14086767E-13 | 0.12185568E-09 | -0.56142619E-15 |
2 | 9 | -0.78969438E-07 | 0.37271083E-11 | -0.12786746E-06 | 0.41607738E-10 |
3 | 8 | 0.15644920E-04 | 0.57233592E-08 | 0.24713380E-04 | -0.42390053E-07 |
4 | 7 | -0.11010334E-02 | 0.13458163E-05 | -0.17770580E-02 | 0.73075693E-05 |
5 | 6 | 0.34256138E-01 | 0.71913801E-04 | 0.57800664E-01 | -0.42770275E-03 |
6 | 5 | -0.50970556 | 0.10561809E-02 | -0.91414050 | 0.10365322E-01 |
7 | 4 | 3.8008141 | 0.46021679E-02 | 7.1669335 | -0.11749215 |
8 | 3 | -14.731927 | 0.58137860E-02 | -27.604869 | 0.65172867 |
9 | 2 | 29.625503 | 0.18019171E-02 | 52.431474 | -1.7640469 |
10 | 1 | -28.806601 | 0.81323549E-04 | -47.206921 | 2.1946319 |
11 | 0 | 10.602175 | 0.49952751E-07 | 16.084904 | |
12 | 5 | -0.10726087E-01 | 0.44268190E-05 | -0.10726087E-01 | 0.97389233E-03 |
13 | 4 | 0.31857203 | 0.80150166E-03 | 0.31857203 | -0.30727185E-01 |
14 | 3 | -2.8372473 | 0.12516450E-01 | -2.8372473 | 0.30041224 |
15 | 2 | 9.6667056 | 0.33176537E-01 | 9.6667056 | -1.1584571 |
16 | 1 | -13.322214 | 0.15207483E-01 | -13.322214 | 1.8397512 |
17 | 0 | 6.2472388 | 0.62260140E-03 | 6.2472388 | |
18 | 4 | 0.29631924E-13 | -0.40788276E-14 | 0.60443234E-14 | -0.77798347E-16 |
19 | 3 | -0.11254351E-04 | 0.79669069E-06 | -0.23145793E-05 | 0.39394231E-13 |
20 | 2 | 0.49771861 | 0.29587917E-01 | 0.78801895E-01 | -0.76025120E-05 |
21 | 1 | -8.3915550 | 0.80192706 | -1.1535996 | 0.21114735 |
22 | 0 | 9.2367617 | 0.51139848 | 2.4177143 | |
23 | 8 | -0.19955962E-17 | 0.73322287E-16 | 0.22297369E-07 | 0.32822528E-16 |
24 | 7 | -0.41677264E-07 | 0.10019220E-10 | -0.10904919E-01 | 0.29209175E-07 |
25 | 6 | 0.51656634E-02 | 0.11264243E-06 | 0.41501785 | -0.36203283E-02 |
26 | 5 | -0.90145565E-01 | 0.13848923E-04 | -4.5221814 | 0.64991548E-01 |
27 | 4 | 0.61381812 | 0.20608367E-03 | 22.362906 | -0.45855939 |
28 | 3 | -2.0715279 | 0.66281990E-03 | -57.676573 | 1.6179231 |
29 | 2 | 3.6382511 | 0.50785658E-03 | 80.070402 | -3.0000438 |
30 | 1 | -3.1552904 | 0.73826575E-04 | -56.558927 | 2.7719184 |
31 | 0 | 1.0611943 | 0.67997522E-06 | 15.921725 | |
32 | 8 | 0.22297369E-07 | 0.73322287E-16 | -0.19955962E-17 | 0.32822528E-16 |
33 | 7 | -0.10904919E-01 | 0.10019220E-10 | -0.41677264E-07 | 0.29209175E-07 |
34 | 6 | 0.41501785 | 0.11264243E-06 | 0.51656634E-02 | -0.36203283E-02 |
35 | 5 | -4.5221814 | 0.13848923E-04 | -0.90145565E-01 | 0.64991548E-01 |
36 | 4 | 22.362906 | 0.20608367E-03 | 0.61381812 | -0.45855939 |
37 | 3 | -57.676573 | 0.66281990E-03 | -2.0715279 | 1.6179231 |
38 | 2 | 80.070402 | 0.50785658E-03 | 3.6382511 | -3.0000438 |
39 | 1 | -56.558927 | 0.73826575E-04 | -3.1552904 | 2.7719184 |
40 | 0 | 15.921725 | 0.67997522E-06 | 1.0611943 | |
41 | 5 | -0.27590492E-07 | 0.65241430E-08 | -0.27590492E-07 | 0.17331255E-13 |
42 | 4 | 0.68608714E-03 | 0.11323974E-03 | 0.68608714E-03 | -0.15705033E-07 |
43 | 3 | -0.21538511 | 0.37821720E-01 | -0.21538511 | 0.25667047E-03 |
44 | 2 | 5.0173519 | 0.62258424 | 5.0173519 | -0.50236511E-01 |
45 | 1 | -19.904252 | 0.86481321 | -19.904252 | 0.58144210 |
46 | 0 | 16.688993 | 0.62060609E-01 | 16.688993 | |
47 | 4 | 0.75441920E-10 | 0.23883683E-10 | 0.47514224E-10 | -0.69373194E-20 |
48 | 3 | -0.33730907E-03 | 0.89366797E-04 | -0.22574866E-03 | 0.77828620E-10 |
49 | 2 | 0.58624422 | 0.18542418 | 0.49024360 | -0.17301269E-03 |
50 | 1 | -11.299243 | 2.8799011 | -8.6239668 | 0.15905732 |
51 | 0 | 15.219762 | 1.4410112 | 12.640375 | |
52 | 5 | -0.12684112E-15 | 0.12265365E-15 | -0.12677399E-15 | -0.71473824E-21 |
53 | 4 | 0.79178029E-08 | 0.61809320E-08 | 0.79178029E-08 | -0.25173083E-13 |
54 | 3 | -0.59300915E-03 | 0.39287166E-03 | -0.59300915E-03 | 0.15952896E-06 |
55 | 2 | 0.32945260 | 0.15279768 | 0.32945260 | -0.17917361E-02 |
56 | 1 | -5.3454172 | 1.4378160 | -5.3454172 | 0.22827165 |
57 | 0 | 7.2128127 | 0.60524857 | 7.2128127 | |
58 | 6 | 0.97988530E-11 | 0.43917118E-12 | 0.24496810E-11 | -0.34892153E-15 |
59 | 5 | -0.75005310E-05 | 0.16499726E-06 | -0.28271466E-05 | 0.19166609E-11 |
60 | 4 | 0.32354224E-01 | 0.66949565E-03 | 0.10283773E-01 | -0.11111676E-05 |
61 | 3 | -1.8201547 | 0.67148336E-01 | -0.62076152 | 0.38788549E-02 |
62 | 2 | 21.173821 | 0.53241617 | 7.5279938 | -0.97325542E-01 |
63 | 1 | -64.420211 | 0.46601667 | -21.697519 | 0.64629334 |
64 | 0 | 46.121323 | 0.20873329E-01 | 15.867130 |
Construction Name | Index | #Layers | Roughness | Conductance {Btu/h-ft2-F} | Conductance (Before Adjusted) {Btu/h-ft2-F} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | EXTERIOR WINDOW | 12 | 1 | VerySmooth | 0.501 | 0.501 | 1.000 | 0.218 | ||
2 | INTERIOR WINDOW | 13 | 1 | VerySmooth | 0.501 | 0.501 | 1.000 | 0.218 | ||
3 | WINDOW_W_BLINDS | 18 | 2 | VerySmooth | 0.501 | 0.501 | 1.000 | 0.207 | ||
4 | TDD DOME | 22 | 1 | VerySmooth | 1.071 | 1.071 | 1.000 | 0.929 | ||
5 | TDD DIFFUSER | 23 | 1 | VerySmooth | 1.077 | 1.077 | 1.000 | 0.906 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {ft} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLASS | SpectralAverage | 0.06495 | 0.12813 | 0.64406 | 0.64406 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10908 | 1.00000 | No | |
2 | GLASS | SpectralAverage | 0.06495 | 0.12813 | 0.64406 | 0.64406 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10908 | 1.00000 | No | |
3 | GLASS | SpectralAverage | 0.06495 | 0.12813 | 0.64406 | 0.64406 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10908 | 1.00000 | No | |
4 | CLEAR ACRYLIC PLASTIC | SpectralAverage | 0.00984 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No | |
5 | DIFFUSING ACRYLIC PLASTIC | SpectralAverage | 0.00722 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No |
Material Name | Slat Width {ft} | Slat Separation {ft} | Slat Thickness {ft} | Slat Angle {deg} | Slat Beam Solar Transmittance | Slat Beam Solar Front Reflectance | Blind To Glass Distance {ft} | |
1 | INT_BLIND | 0.0820 | 0.0615 | 0.0033 | 45.000 | 0.000 | 0.500 | 0.164 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000. | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {ft3} | Maximum Capacity {Btu/h} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
2 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
3 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
4 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
5 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
6 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
7 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
8 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
9 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
10 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
11 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
12 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
13 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
14 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
15 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
16 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
17 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 | |
18 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 6.6825 | 4508.3 | 0.000 | 0.0000 | 736 |
Node Number | Height {ft} | Volume {ft3} | Maximum Capacity {Btu/h} | Off-Cycle UA {Btu/h-F} | On-Cycle UA {Btu/h-F} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
2 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
3 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
4 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
5 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
6 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
7 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
8 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
9 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
10 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
11 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
12 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
13 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
14 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
15 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
16 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
17 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
18 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
2 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
3 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
4 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
5 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
6 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
7 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
8 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
9 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
10 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
11 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
12 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
13 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
14 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
15 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
16 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
17 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
18 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
19 | ATTICVENT | ALWAYS_AVAIL | ATTIC | 7802.66 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/person Area {ft3/min-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {psi} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{F}/Schedule | Maximum Indoor Temperature{F}/Schedule | Delta Temperature{F}/Schedule | Minimum Outdoor Temperature{F}/Schedule | Maximum Outdoor Temperature{F}/Schedule | Maximum WindSpeed{ft/min} | |
1 | VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
2 | VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
3 | VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
4 | VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
5 | VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
6 | VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
7 | VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
8 | VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
9 | VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
10 | VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
11 | VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
12 | VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
13 | VENTILATION_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
14 | VENTILATION_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
15 | VENTILATION_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
16 | VENTILATION_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
17 | VENTILATION_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
18 | VENTILATION_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BREEZEWAY | Mixing/Well-Stirred |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
4 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
5 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
6 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
7 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
8 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
9 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
10 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
11 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
12 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
13 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
14 | ATTIC | Mixing/Well-Stirred |
15 | LIVING_UNIT3_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
16 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
17 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
18 | LIVING_UNIT2_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
19 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
20 | LIVING_UNIT1_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {Btu/h} | User Des Load {Btu/h} | Calc Des Air Flow Rate {ft3/min} | User Des Air Flow Rate {ft3/min} | Design Day Name | Date/Time of Peak | Temperature at Peak {F} | Humidity Ratio at Peak {lbWater/lbDryAir} | Floor Area {ft2} | # Occupants | Calc Outdoor Air Flow Rate {ft3/min} | Calc DOAS Heat Addition Rate {Btu/h} | |
1 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | 8163.87889 | 8163.87889 | 348.07199 | 348.07199 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 89.46860 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | 3728.58007 | 3728.58007 | 67.95804 | 67.95804 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | 4578.07198 | 4578.07198 | 195.18027 | 195.18027 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 87.65960 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | 2661.81120 | 2661.81120 | 48.51504 | 48.51504 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | 6207.34030 | 6207.34030 | 264.63980 | 264.63980 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 88.68470 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
6 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | 3728.65192 | 3728.65192 | 67.95953 | 67.95953 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
7 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | 8265.92700 | 8265.92700 | 352.41521 | 352.41521 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 89.26759 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
8 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Heating | 3730.54081 | 3730.54081 | 67.99385 | 67.99385 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
9 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | 4797.25381 | 4797.25381 | 204.52582 | 204.52582 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 87.65960 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
10 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Heating | 2660.99430 | 2660.99430 | 48.50021 | 48.50021 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
11 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | 6319.33678 | 6319.33678 | 269.42793 | 269.42793 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 88.68470 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
12 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Heating | 3725.05793 | 3725.05793 | 67.89385 | 67.89385 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
13 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | 8873.67401 | 8873.67401 | 378.30504 | 378.30504 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 89.26759 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
14 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | 3520.17661 | 3520.17661 | 64.16016 | 64.16016 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
15 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | 5077.38011 | 5077.38011 | 216.46184 | 216.46184 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 87.05660 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
16 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | 2325.82361 | 2325.82361 | 42.39152 | 44.99491 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
17 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | 6687.12608 | 6687.12608 | 285.08471 | 285.08471 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | 89.18721 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
18 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | 3518.22644 | 3518.22644 | 64.12457 | 64.12457 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
19 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | 9004.72702 | 9004.72702 | 383.89826 | 383.89826 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 89.06661 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
20 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Heating | 3521.40015 | 3521.40015 | 64.18241 | 64.18241 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
21 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | 5289.69375 | 5289.69375 | 225.50845 | 225.50845 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 87.05660 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
22 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Heating | 2324.19605 | 2324.19605 | 42.36186 | 44.99491 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
23 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | 6794.91447 | 6794.91447 | 289.68217 | 289.68217 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 88.98620 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
24 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Heating | 3513.73629 | 3513.73629 | 64.04258 | 64.04258 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
25 | LIVING_UNIT3_BACKROW_TOPFLOOR | Cooling | 7772.11353 | 7772.11353 | 331.35589 | 331.35589 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 88.56410 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
26 | LIVING_UNIT3_BACKROW_TOPFLOOR | Heating | 4798.28639 | 4798.28639 | 87.45486 | 87.45486 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
27 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Cooling | 7669.53021 | 7669.53021 | 326.99148 | 326.99148 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 89.46860 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
28 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Heating | 4799.78378 | 4799.78378 | 87.48198 | 87.48198 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
29 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Cooling | 10457.26015 | 10457.26015 | 445.84740 | 445.84740 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 89.06661 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
30 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Heating | 4803.32820 | 4803.32820 | 87.54660 | 87.54660 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
31 | LIVING_UNIT2_BACKROW_TOPFLOOR | Cooling | 6754.06997 | 6754.06997 | 287.96607 | 287.96607 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 87.65960 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
32 | LIVING_UNIT2_BACKROW_TOPFLOOR | Heating | 3596.63567 | 3596.63567 | 65.55338 | 65.55338 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
33 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Cooling | 6606.39932 | 6606.39932 | 281.65251 | 281.65251 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 87.35810 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
34 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Heating | 3596.10323 | 3596.10323 | 65.54364 | 65.54364 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
35 | LIVING_UNIT1_BACKROW_TOPFLOOR | Cooling | 10572.70848 | 10572.70848 | 450.76265 | 450.76265 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 89.06661 | 0.01716 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
36 | LIVING_UNIT1_BACKROW_TOPFLOOR | Heating | 4806.01085 | 4806.01085 | 87.59554 | 87.59554 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 47.66000 | 0.00699 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [ft3/min] | User Des Air Flow Rate [ft3/min] | Design Day Name | Date/Time of Peak | |
1 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2566.39 | 348.07199 | 348.07199 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 1423.94 | 67.95804 | 67.95804 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
3 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1504.01 | 195.18027 | 195.18027 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 1115.84 | 48.51504 | 48.51504 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
5 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1989.61 | 264.63980 | 264.63980 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 1423.96 | 67.95953 | 67.95953 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
7 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2593.02 | 352.41521 | 352.41521 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Heating | Sensible | 1424.51 | 67.99385 | 67.99385 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
9 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1567.37 | 204.52582 | 204.52582 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Heating | Sensible | 1115.61 | 48.50021 | 48.50021 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
11 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2021.99 | 269.42793 | 269.42793 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Heating | Sensible | 1422.92 | 67.89385 | 67.89385 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
13 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2768.70 | 378.30504 | 378.30504 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1363.75 | 64.16016 | 64.16016 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
15 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 1639.74 | 216.46184 | 216.46184 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1060.07 | 44.99491 | 44.99491 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
17 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2135.46 | 285.08471 | 285.08471 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1363.19 | 64.12457 | 64.12457 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
19 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2803.72 | 383.89826 | 383.89826 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1364.11 | 64.18241 | 64.18241 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
21 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1701.12 | 225.50845 | 225.50845 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
22 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1060.07 | 44.99491 | 44.99491 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
23 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2163.76 | 289.68217 | 289.68217 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
24 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1361.89 | 64.04258 | 64.04258 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
25 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Cooling | Sensible | 3223.62 | 445.84740 | 445.84740 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
26 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Heating | Sensible | 1734.34 | 87.54660 | 87.54660 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
27 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Cooling | Sensible | 2086.06 | 281.65251 | 281.65251 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
28 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Heating | Sensible | 1385.68 | 65.54364 | 65.54364 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
29 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Cooling | Sensible | 2423.48 | 326.99148 | 326.99148 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
30 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Heating | Sensible | 1733.32 | 87.48198 | 87.48198 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
31 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Cooling | Sensible | 3257.00 | 450.76265 | 450.76265 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
32 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Heating | Sensible | 1735.12 | 87.59554 | 87.59554 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
33 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Cooling | Sensible | 2133.05 | 287.96607 | 287.96607 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
34 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Heating | Sensible | 1385.83 | 65.55338 | 65.55338 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
35 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Cooling | Sensible | 2440.24 | 331.35589 | 331.35589 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
36 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Heating | Sensible | 1732.89 | 87.45486 | 87.45486 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 348.07199 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 195.18027 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 264.63980 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 352.41521 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 204.52582 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 269.42793 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 378.30504 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 216.46184 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 285.08471 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 383.89826 |
11 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 225.50845 |
12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 289.68217 |
13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 331.35589 |
14 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 326.99148 |
15 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 445.84740 |
16 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 287.96607 |
17 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 281.65251 |
18 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 450.76265 |
19 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 348.07199 |
20 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 348.07199 |
21 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 348.07199 |
22 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 348.07199 |
23 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 348.07199 |
24 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 348.07199 |
25 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 195.18027 |
28 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 195.18027 |
29 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 195.18027 |
30 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 195.18027 |
31 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 195.18027 |
32 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 195.18027 |
33 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 264.63980 |
36 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 264.63980 |
37 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 264.63980 |
38 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 264.63980 |
39 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 264.63980 |
40 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 264.63980 |
41 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 352.41521 |
44 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 352.41521 |
45 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 352.41521 |
46 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 352.41521 |
47 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 352.41521 |
48 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 352.41521 |
49 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 204.52582 |
52 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 204.52582 |
53 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 204.52582 |
54 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 204.52582 |
55 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 204.52582 |
56 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 204.52582 |
57 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 269.42793 |
60 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 269.42793 |
61 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 269.42793 |
62 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 269.42793 |
63 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 269.42793 |
64 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 269.42793 |
65 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 378.30504 |
68 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 378.30504 |
69 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 378.30504 |
70 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 378.30504 |
71 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 378.30504 |
72 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 378.30504 |
73 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 216.46184 |
76 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 216.46184 |
77 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 216.46184 |
78 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 216.46184 |
79 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 216.46184 |
80 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 216.46184 |
81 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 285.08471 |
84 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 285.08471 |
85 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 285.08471 |
86 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 285.08471 |
87 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 285.08471 |
88 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 285.08471 |
89 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 383.89826 |
92 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 383.89826 |
93 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 383.89826 |
94 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 383.89826 |
95 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 383.89826 |
96 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 383.89826 |
97 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
98 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
99 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 225.50845 |
100 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 225.50845 |
101 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 225.50845 |
102 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 225.50845 |
103 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 225.50845 |
104 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 225.50845 |
105 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
106 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
107 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 289.68217 |
108 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 289.68217 |
109 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 289.68217 |
110 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 289.68217 |
111 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 289.68217 |
112 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 289.68217 |
113 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
114 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
115 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 445.84740 |
116 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 445.84740 |
117 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 445.84740 |
118 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 445.84740 |
119 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 445.84740 |
120 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 445.84740 |
121 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
122 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
123 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 281.65251 |
124 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 281.65251 |
125 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 281.65251 |
126 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 281.65251 |
127 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 281.65251 |
128 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 281.65251 |
129 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
130 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
131 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 326.99148 |
132 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 326.99148 |
133 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 326.99148 |
134 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 326.99148 |
135 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 326.99148 |
136 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 326.99148 |
137 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
138 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
139 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 450.76265 |
140 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 450.76265 |
141 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 450.76265 |
142 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 450.76265 |
143 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 450.76265 |
144 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 450.76265 |
145 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
146 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
147 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 287.96607 |
148 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 287.96607 |
149 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 287.96607 |
150 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 287.96607 |
151 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 287.96607 |
152 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 287.96607 |
153 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
154 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
155 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 331.35589 |
156 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 331.35589 |
157 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 331.35589 |
158 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 331.35589 |
159 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 331.35589 |
160 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 331.35589 |
161 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
162 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
163 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 348.07199 |
164 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 195.18027 |
165 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 264.63980 |
166 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 352.41521 |
167 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 204.52582 |
168 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 269.42793 |
169 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 378.30504 |
170 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 216.46184 |
171 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 285.08471 |
172 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 383.89826 |
173 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 225.50845 |
174 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 289.68217 |
175 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 445.84740 |
176 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 281.65251 |
177 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 326.99148 |
178 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 450.76265 |
179 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 287.96607 |
180 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 331.35589 |
181 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 348.07199 |
182 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.15997 |
183 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
184 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 348.07199 |
185 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 348.07199 |
186 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 348.07199 |
187 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 4858.48250 |
188 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.15997 |
189 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
190 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 348.07199 |
191 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 5587.25488 |
192 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 195.18027 |
193 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.65047 |
194 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
195 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 195.18027 |
196 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 195.18027 |
197 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 195.18027 |
198 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 3807.25799 |
199 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.65047 |
200 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
201 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 195.18027 |
202 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 4378.34667 |
203 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 264.63980 |
204 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.88196 |
205 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
206 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 264.63980 |
207 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 264.63980 |
208 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 264.63980 |
209 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 4858.55329 |
210 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.88196 |
211 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
212 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 264.63980 |
213 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 5587.33630 |
214 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 352.41521 |
215 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.17447 |
216 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
217 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 352.41521 |
218 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 352.41521 |
219 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 352.41521 |
220 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 4860.41464 |
221 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.17447 |
222 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
223 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 352.41521 |
224 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 5589.47685 |
225 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 204.52582 |
226 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.68161 |
227 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
228 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 204.52582 |
229 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 204.52582 |
230 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 204.52582 |
231 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 3806.45299 |
232 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.68161 |
233 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
234 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 204.52582 |
235 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 4377.42096 |
236 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 269.42793 |
237 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.89788 |
238 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
239 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 269.42793 |
240 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 269.42793 |
241 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 269.42793 |
242 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 4855.01167 |
243 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.89788 |
244 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
245 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 269.42793 |
246 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 5583.26342 |
247 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 378.30504 |
248 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.26077 |
249 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
250 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 378.30504 |
251 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 378.30504 |
252 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 378.30504 |
253 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 4653.12831 |
254 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.26077 |
255 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
256 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 378.30504 |
257 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 5351.09754 |
258 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 216.46184 |
259 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.72139 |
260 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
261 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 216.46184 |
262 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 216.46184 |
263 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 216.46184 |
264 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 3616.94198 |
265 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.72139 |
266 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
267 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 216.46184 |
268 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 4159.48329 |
269 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 285.08471 |
270 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.95009 |
271 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
272 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 285.08471 |
273 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 285.08471 |
274 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 285.08471 |
275 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 4651.20657 |
276 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.95009 |
277 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
278 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 285.08471 |
279 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 5348.88755 |
280 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 383.89826 |
281 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.27939 |
282 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
283 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 383.89826 |
284 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 383.89826 |
285 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 383.89826 |
286 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 4654.33401 |
287 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.27939 |
288 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
289 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 383.89826 |
290 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 5352.48414 |
291 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 225.50845 |
292 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.75155 |
293 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
294 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 225.50845 |
295 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 225.50845 |
296 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 225.50845 |
297 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 3616.94198 |
298 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.75155 |
299 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 225.50845 |
301 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 4159.48329 |
302 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 289.68217 |
303 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.96541 |
304 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
305 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 289.68217 |
306 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 289.68217 |
307 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 289.68217 |
308 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 4646.78182 |
309 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.96541 |
310 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
311 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 289.68217 |
312 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 5343.79906 |
313 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 445.84740 |
314 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.48584 |
315 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
316 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 445.84740 |
317 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 445.84740 |
318 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 445.84740 |
319 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 5917.57330 |
320 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.48584 |
321 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
322 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 445.84740 |
323 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 6805.20930 |
324 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 281.65251 |
325 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.93867 |
326 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
327 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 281.65251 |
328 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 281.65251 |
329 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 281.65251 |
330 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 4727.93845 |
331 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.93867 |
332 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
333 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 281.65251 |
334 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 5437.12924 |
335 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 326.99148 |
336 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.08973 |
337 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
338 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 326.99148 |
339 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 326.99148 |
340 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 326.99148 |
341 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 5914.08054 |
342 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.08973 |
343 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
344 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 326.99148 |
345 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 6801.19259 |
346 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 450.76265 |
347 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.50224 |
348 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
349 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 450.76265 |
350 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 450.76265 |
351 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 450.76265 |
352 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 5920.21688 |
353 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.50224 |
354 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
355 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 450.76265 |
356 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 6808.24939 |
357 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 287.96607 |
358 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.95965 |
359 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
360 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 287.96607 |
361 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 287.96607 |
362 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 287.96607 |
363 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 4728.46315 |
364 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.95965 |
365 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
366 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 287.96607 |
367 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 5437.73262 |
368 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 331.35589 |
369 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.10431 |
370 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
371 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 331.35589 |
372 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 331.35589 |
373 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 331.35589 |
374 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 5912.60495 |
375 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.10431 |
376 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
377 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 331.35589 |
378 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 6799.49570 |
379 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
380 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
381 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
382 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
383 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
384 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
385 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
386 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
387 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
388 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
389 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
390 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
391 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
392 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
393 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
394 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
395 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
396 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
397 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
398 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
399 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
400 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
401 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
402 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
403 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
404 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
405 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
406 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
407 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
408 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
409 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
410 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
411 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
412 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
413 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
414 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
415 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
416 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
417 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
418 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
419 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
420 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
421 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
422 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
423 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
424 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
425 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
426 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
427 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
428 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
429 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
430 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
431 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
432 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
433 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
434 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
435 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
436 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
437 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
438 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
439 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
440 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
441 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
442 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
443 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
444 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
445 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
446 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
447 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
448 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
449 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
450 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
451 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
452 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
453 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
454 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
455 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
456 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
457 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
458 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
459 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
460 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
461 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
462 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
463 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
464 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
465 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
466 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
467 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
468 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
469 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
470 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
471 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
472 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
473 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
474 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
475 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
476 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
477 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
478 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
479 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
480 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
481 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
482 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
483 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
484 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
485 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
486 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {ton} | Standard Rated Net COP {Btuh/Btuh} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.1 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
2 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.1 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
3 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.6 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
4 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.6 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
5 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.9 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
6 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.8 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
7 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.1 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
8 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.1 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
9 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.7 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
10 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.7 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
11 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.9 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
12 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.9 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
13 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.2 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
14 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.2 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
15 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.7 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
16 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.7 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
17 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
18 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
19 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.2 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
20 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.2 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
21 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.7 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
22 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.7 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
23 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.9 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
24 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.9 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
25 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.4 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
26 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.4 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
27 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.9 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
28 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.9 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
29 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.1 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
30 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.0 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
31 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.5 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
32 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.4 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
33 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.9 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
34 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.9 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
35 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.1 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
36 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.1 | 3.56 | 12.16 | 12.89 | 12.74 | -99999. |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | SizingPeriod:DesignDay | 01/21 | 01/21 | WinterDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
2 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | SizingPeriod:DesignDay | 07/21 | 07/21 | SummerDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
3 | ANNUAL | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | No | SizingPeriod:DesignDay | ||
2 | No | SizingPeriod:DesignDay | ||
3 | No |
NumberofWarmupDays | |
1 | 25 |
2 | 6 |
3 | 25 |
Max Dry-Bulb Temp {F} | Temp Range {dC} | Temp Range Ind Type | Hum Ind Type | Hum Ind Value at Max Temp | Hum Ind Units | Pressure {psi} | Wind Direction {deg CW from N} | Wind Speed {ft/min} | Clearness | Rain | Snow | |
1 | 47.66 | 0.00 | DefaultMultipliers | Wetbulb | 8.70 | {C} | 15. | 340 | 748.1 | 0.00 | No | No |
2 | 91.76 | 6.70 | DefaultMultipliers | Wetbulb | 25.30 | {C} | 15. | 140 | 885.9 | 0.00 | No | No |
DayOfYear | ASHRAE A Coeff | ASHRAE B Coeff | ASHRAE C Coeff | Solar Constant-Annual Variation | Eq of Time {minutes} | Solar Declination Angle {deg} | Solar Model | |
1 | 21 | 1229.0 | 0.1415 | 5.7310E-002 | 1.0 | -11.15 | -20. | ASHRAEClearSky |
2 | 202 | 1084.4 | 0.2082 | 0.1365 | 1.0 | -6.23 | 20.6 | ASHRAETau |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaF} | Std Dev Warmup Temperature Difference {deltaF} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {Btu/h} | Std Dev Warmup Load Difference {Btu/h} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BREEZEWAY | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.000005085 | 0.000002960 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.038867523 | 0.114140427 | Pass | Pass | 0.107846644 | 0.311097961 | Fail | Pass |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.063298352 | 0.165917892 | Pass | Pass | 0.321369198 | 0.890009653 | Pass | Pass |
4 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.045862878 | 0.128066648 | Pass | Pass | 0.118021001 | 0.331721490 | Fail | Pass |
5 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.038516839 | 0.113469440 | Pass | Pass | 0.108534452 | 0.310894206 | Fail | Pass |
6 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.062330695 | 0.163643315 | Pass | Pass | 0.310684545 | 0.858093846 | Pass | Pass |
7 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.045464527 | 0.127249289 | Pass | Pass | 0.117307430 | 0.329518096 | Fail | Pass |
8 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.033775056 | 0.103875713 | Pass | Pass | 0.116804500 | 0.314186614 | Fail | Pass |
9 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.044673425 | 0.129636801 | Pass | Pass | 0.214958039 | 0.624011863 | Fail | Pass |
10 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.040462058 | 0.118231279 | Pass | Pass | 0.115037204 | 0.332508947 | Fail | Pass |
11 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.033436483 | 0.102913769 | Pass | Pass | 0.116064210 | 0.310986236 | Fail | Pass |
12 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.043683801 | 0.127766327 | Pass | Pass | 0.215712674 | 0.622003160 | Fail | Pass |
13 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.040114512 | 0.117568033 | Pass | Pass | 0.115318868 | 0.332265887 | Fail | Pass |
14 | ATTIC | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.000140187 | 0.000105401 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
15 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.034801144 | 0.106205775 | Pass | Pass | 0.080819635 | 0.225379636 | Fail | Pass |
16 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.035082346 | 0.106842030 | Pass | Pass | 0.080958492 | 0.226581219 | Fail | Pass |
17 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.028341072 | 0.089308160 | Pass | Pass | 0.073297628 | 0.192188249 | Fail | Pass |
18 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.040306224 | 0.118422665 | Pass | Pass | 0.112732736 | 0.325413296 | Fail | Pass |
19 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.040795246 | 0.119389556 | Pass | Pass | 0.113536344 | 0.326943371 | Fail | Pass |
20 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 0.028082398 | 0.088591543 | Pass | Pass | 0.072956167 | 0.191051545 | Fail | Pass |
21 | BREEZEWAY | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.292328209 | 0.172083039 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
22 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000035993 | 0.000186195 | Pass | Pass | 0.069452606 | 0.035020014 | Pass | Pass |
23 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000050444 | 0.000158760 | Pass | Pass | 0.047281156 | 0.034735854 | Pass | Pass |
24 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000060784 | 0.000197075 | Pass | Pass | 0.056242095 | 0.056645943 | Pass | Pass |
25 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000032854 | 0.000168626 | Pass | Pass | 0.069944928 | 0.036741761 | Pass | Pass |
26 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000050534 | 0.000162654 | Pass | Pass | 0.047711312 | 0.036015339 | Pass | Pass |
27 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000063664 | 0.000202091 | Pass | Pass | 0.057099039 | 0.059273136 | Pass | Pass |
28 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000037487 | 0.000203050 | Pass | Pass | 0.065684854 | 0.029169121 | Pass | Pass |
29 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000056646 | 0.000188510 | Pass | Pass | 0.043002376 | 0.031788521 | Pass | Pass |
30 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000069909 | 0.000235755 | Pass | Pass | 0.052101077 | 0.050329735 | Pass | Pass |
31 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000039277 | 0.000212852 | Pass | Pass | 0.066411932 | 0.029545055 | Pass | Pass |
32 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000057826 | 0.000197344 | Pass | Pass | 0.044314667 | 0.031311148 | Pass | Pass |
33 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000066647 | 0.000224485 | Pass | Pass | 0.053178355 | 0.052400913 | Pass | Pass |
34 | ATTIC | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.402551536 | 0.333897857 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
35 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000085391 | 0.000290771 | Pass | Pass | 0.055416260 | 0.050770008 | Pass | Pass |
36 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000082536 | 0.000281057 | Pass | Pass | 0.054969059 | 0.049368739 | Pass | Pass |
37 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000042397 | 0.000226946 | Pass | Pass | 0.069488695 | 0.028192820 | Pass | Pass |
38 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000075350 | 0.000257998 | Pass | Pass | 0.051641546 | 0.028520145 | Pass | Pass |
39 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000072221 | 0.000245480 | Pass | Pass | 0.050525023 | 0.029974820 | Pass | Pass |
40 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 0.000042833 | 0.000231008 | Pass | Pass | 0.070180302 | 0.027943124 | Pass | Pass |
41 | BREEZEWAY | RunPeriod: ANNUAL | 0.253370801 | 0.205936285 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
42 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.070786613 | 0.187249105 | Pass | Pass | 0.457664122 | 1.762391385 | Pass | Pass |
43 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.061306006 | 0.181504091 | Pass | Pass | 0.448325789 | 1.293464610 | Pass | Pass |
44 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.047110499 | 0.137942556 | Pass | Pass | 0.488677991 | 2.111046677 | Pass | Pass |
45 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.094607052 | 0.201045283 | Pass | Pass | 0.665800296 | 2.362689868 | Pass | Pass |
46 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.101054823 | 0.223893741 | Pass | Pass | 0.616015342 | 1.827888679 | Pass | Pass |
47 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.073578951 | 0.177076295 | Pass | Pass | 0.551864225 | 2.382385253 | Pass | Pass |
48 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.036622454 | 0.160312144 | Pass | Pass | 0.296743137 | 0.768211715 | Pass | Pass |
49 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.024559620 | 0.132941378 | Pass | Pass | 0.201388107 | 0.634550969 | Pass | Pass |
50 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.015259543 | 0.083699530 | Pass | Pass | 0.202252491 | 0.305809110 | Pass | Pass |
51 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.047889756 | 0.170026827 | Pass | Pass | 0.275907919 | 0.471773672 | Pass | Pass |
52 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.045522463 | 0.163632713 | Pass | Pass | 0.166967371 | 0.389415569 | Pass | Pass |
53 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.021798424 | 0.108693079 | Pass | Pass | 0.242548740 | 0.549240295 | Pass | Pass |
54 | ATTIC | RunPeriod: ANNUAL | 0.456004558 | 0.445932266 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
55 | LIVING_UNIT3_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.029993851 | 0.130107238 | Pass | Pass | 0.222412044 | 0.504793754 | Pass | Pass |
56 | LIVING_UNIT3_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.027207669 | 0.113137230 | Pass | Pass | 0.283167703 | 0.746164458 | Pass | Pass |
57 | LIVING_UNIT1_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.036874887 | 0.151934148 | Pass | Pass | 0.289385484 | 0.705007920 | Pass | Pass |
58 | LIVING_UNIT2_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.043845601 | 0.163145339 | Pass | Pass | 0.222101441 | 0.441431747 | Pass | Pass |
59 | LIVING_UNIT2_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.029459053 | 0.150543678 | Pass | Pass | 0.196494475 | 0.434652140 | Pass | Pass |
60 | LIVING_UNIT1_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.048241217 | 0.155672052 | Pass | Pass | 0.265852298 | 0.568586686 | Pass | Pass |
Report: Annual Heat Emissions Report
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Annual Heat Emissions SummaryEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [kBtu] | 2719268.50 | -33274.8 | -130099.9 | 0.00 | 766263.04 | 3322161.95 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Heat Index HoursSafe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
BREEZEWAY | 5106.50 | 3108.33 | 545.17 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 4939.83 | 1708.33 | 1278.67 | 833.17 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 4939.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3108.33 | 1278.67 | 833.17 | 0.00 |
Average | 8386.32 | 240.83 | 91.19 | 41.66 | 0.00 |
Sum | 167726.33 | 4816.67 | 1823.83 | 833.17 | 0.00 |
Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 10856.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 217122.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 7884.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 157680.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BREEZEWAY | 5972.33 | 2781.67 | 6.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5538.50 | 3221.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5102.50 | 3657.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5756.50 | 3003.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5375.17 | 3384.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4746.17 | 4013.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5560.00 | 3200.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7328.83 | 1431.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7418.83 | 1341.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7500.67 | 1259.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7247.67 | 1512.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 7307.00 | 1453.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7452.83 | 1307.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 2432.33 | 4643.50 | 989.67 | 600.50 | 94.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7020.67 | 1739.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7065.50 | 1694.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 6846.50 | 1913.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 6756.50 | 2003.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6848.50 | 1911.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 6780.50 | 1979.50 | 0.00 | 0.00 | 0.00 |
Min | 2432.33 | 1259.33 | 0.00 | 0.00 | 0.00 |
Max | 7500.67 | 4643.50 | 989.67 | 600.50 | 94.00 |
Average | 6302.88 | 2372.62 | 49.78 | 30.03 | 4.70 |
Sum | 126057.50 | 47452.33 | 995.67 | 600.50 | 94.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 6813.13 | 5249.25 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6389.33 | 5673.05 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6768.29 | 5294.10 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6649.58 | 5412.81 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 6058.64 | 6003.74 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6551.49 | 5510.89 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9697.67 | 2364.71 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9949.61 | 2112.77 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9802.97 | 2259.41 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9619.45 | 2442.93 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9854.41 | 2207.97 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9736.68 | 2325.70 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 9034.04 | 3028.34 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9078.20 | 2984.18 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8967.97 | 3094.41 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 9058.67 | 3003.71 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 9137.59 | 2924.79 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8913.97 | 3148.41 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 9949.61 | 6003.74 | 0.00 | 0.00 | 0.00 |
Average | 7604.08 | 3252.06 | 0.00 | 0.00 | 0.00 |
Sum | 152081.68 | 65041.18 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5538.50 | 3221.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5102.50 | 3657.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5756.50 | 3003.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5375.17 | 3384.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4746.17 | 4013.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5560.00 | 3200.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7328.83 | 1431.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7418.83 | 1341.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7500.67 | 1259.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7247.67 | 1512.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 7307.00 | 1453.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7452.83 | 1307.17 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7020.67 | 1739.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7065.50 | 1694.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 6846.50 | 1913.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 6756.50 | 2003.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6848.50 | 1911.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 6780.50 | 1979.50 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 7500.67 | 4013.83 | 0.00 | 0.00 | 0.00 |
Average | 5882.64 | 2001.36 | 0.00 | 0.00 | 0.00 |
Sum | 117652.83 | 40027.17 | 0.00 | 0.00 | 0.00 |
Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
BREEZEWAY | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Min | 0.00 | - | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Average | 7884.00 | - | 0.00 | 0.00 | 0.00 |
Sum | 157680.00 | - | 0.00 | 0.00 | 0.00 |
Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
BREEZEWAY | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Min | 0.00 | - | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Average | 7884.00 | - | 0.00 | 0.00 | 0.00 |
Sum | 157680.00 | - | 0.00 | 0.00 | 0.00 |
Cooling Setpoint Unmet Degree-Hours [°F·hr] | Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] | Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] | Heating Setpoint Unmet Degree-Hours [°F·hr] | Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] | Heating Setpoint Unmet Occupied Degree-Hours [°C·hr] | |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.47 | 0.34 | 0.47 | 13.65 | 18.11 | 13.65 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5.55 | 3.74 | 5.55 | 17.02 | 22.37 | 17.02 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.02 | 0.71 | 1.02 | 13.12 | 19.94 | 13.12 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.33 | 0.27 | 0.33 | 16.25 | 22.02 | 16.25 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.79 | 0.83 | 0.79 | 24.86 | 31.13 | 24.86 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.83 | 0.60 | 0.83 | 17.28 | 24.43 | 17.28 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.45 | 0.34 | 0.45 | 9.31 | 11.86 | 9.31 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.30 | 1.36 | 1.30 | 12.35 | 16.19 | 12.35 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.33 | 0.91 | 1.33 | 9.67 | 14.78 | 9.67 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.27 | 0.24 | 0.27 | 11.43 | 13.83 | 11.43 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.82 | 0.97 | 0.82 | 18.37 | 20.30 | 18.37 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.02 | 0.71 | 1.02 | 11.36 | 14.88 | 11.36 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.31 | 1.00 | 1.31 | 10.12 | 12.94 | 10.12 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.51 | 1.14 | 1.51 | 10.16 | 13.80 | 10.16 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.49 | 0.36 | 0.49 | 9.52 | 11.62 | 9.52 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.87 | 0.90 | 0.87 | 12.48 | 14.91 | 12.48 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.15 | 1.10 | 1.15 | 9.47 | 11.24 | 9.47 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.39 | 0.32 | 0.39 | 10.42 | 13.17 | 10.42 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 5.55 | 3.74 | 5.55 | 24.86 | 31.13 | 24.86 |
Average | 0.99 | 0.79 | 0.99 | 11.84 | 15.38 | 11.84 |
Sum | 19.89 | 15.84 | 19.89 | 236.82 | 307.51 | 236.82 |
Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 0.00 | 0.00 | 0.00 | 0.00 |
Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 47.66 | 0.00 | 47.66 | Wetbulb [F] | 748.07 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 91.76 | 12.06 | 77.54 | Wetbulb [F] | 885.87 | 140.00 |
Monthly Total Precipitation from .epw [in] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [in] | Monthly Total Roof Irrigation Depth [in] | Monthly Total Rain Collection Volume [ft3] | |
Jan | 2.56 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 1.50 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 15.39 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 8.86 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 0.20 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BREEZEWAYROOF | INTERIOR CEILING | 0.30 | 0.033 | 0.035 | 599.39 | 599.39 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-BREEZEWAYROOF | ATTIC FLOOR | 0.30 | 0.033 | 0.035 | 599.39 | 599.39 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.033 | 0.035 | 1200.55 | 1200.55 | 180.00 | 0.00 |
Construction | Frame and Divider | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | NFRC Product Type | Assembly U-Factor [Btu/h-ft2-F] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.218 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.218 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.218 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.218 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.218 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.218 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.218 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.218 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.218 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.218 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.218 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.218 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.218 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | |||||||
Total or Average | 2126.74 | 0.501 | 0.218 | 0.883 | |||||||||||||||||
North Total or Average | 531.68 | 0.501 | 0.218 | 0.883 | |||||||||||||||||
Non-North Total or Average | 1595.05 | 0.501 | 0.218 | 0.883 |
Frame and Divider | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [Btu/h-ft2-F] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.78 | 0.00 | 1.00 | 0.99 | 0.99 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.78 | 0.00 | 1.00 | 0.99 | 0.99 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.78 | 0.00 | 1.00 | 0.99 | 0.99 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.95 | 0.00 | 1.00 | 0.96 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 | 0.74 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 | 0.74 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.95 | 0.00 | 1.00 | 0.96 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 | 0.74 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.78 | 0.00 | 1.00 | 0.99 | 0.99 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.78 | 0.00 | 1.00 | 0.99 | 0.99 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.78 | 0.00 | 1.00 | 0.99 | 0.99 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.95 | 0.00 | 1.00 | 0.96 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 | 0.74 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 | 0.74 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.95 | 0.00 | 1.00 | 0.96 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 | 0.74 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.95 | 0.00 | 1.00 | 0.96 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 | 0.74 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.78 | 0.00 | 1.00 | 0.99 | 0.99 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 0.97 | 0.00 | 0.99 | 0.95 | 0.00 | 1.00 | 0.96 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.78 | 0.00 | 1.00 | 0.99 | 0.99 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 | 0.74 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.78 | 0.00 | 1.00 | 0.99 | 0.99 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.96 | 0.00 | 0.74 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [Btu/h-ft2] | Space Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.2915 | 43219.92 | 12599.76 | 11336.81 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
Exterior Lighting Total | 1377.69 | 6034.31 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Central PlantType | Reference Capacity [Btu/h] | Reference Efficiency [Btuh/Btuh] | Rated Capacity [Btu/h] | Rated Efficiency [Btuh/Btuh] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 13919.66 | 9758.84 | 4160.82 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 7805.59 | 5472.37 | 2333.22 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10583.55 | 7419.95 | 3163.60 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 14093.69 | 9880.85 | 4212.84 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8179.33 | 5734.39 | 2444.94 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10774.50 | 7553.82 | 3220.68 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 15129.26 | 10606.87 | 4522.39 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8656.64 | 6069.02 | 2587.61 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 11401.14 | 7993.15 | 3407.99 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 15352.74 | 10763.55 | 4589.19 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9018.64 | 6322.82 | 2695.82 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 11584.92 | 8122.00 | 3462.93 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 17830.08 | 12500.37 | 5329.71 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11264.04 | 7897.03 | 3367.01 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 13076.71 | 9167.86 | 3908.85 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 18026.94 | 12638.38 | 5388.55 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11515.83 | 8073.56 | 3442.28 | 0.70 | 4.30 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 13251.71 | 9290.55 | 3961.16 | 0.70 | 4.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.1 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.6 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.9 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.1 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.7 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.9 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.2 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.7 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.2 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.7 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.9 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.4 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.9 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.1 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.5 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.9 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.1 | 3.68 | 12.55 | 13.31 | 12.80 | 13.19 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP2 [Btuh/Btuh] | EER2 [Btu/W-h] | SEER2 User [Btu/W-h] | SEER2 Standard [Btu/W-h] | IEER2 [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 1.1 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.6 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.8 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 1.1 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.7 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.9 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 1.2 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.7 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.9 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 1.2 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.7 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.9 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.4 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.9 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.0 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.4 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.9 | 3.56 | 12.16 | 12.89 | 12.74 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.1 | 3.56 | 12.16 | 12.89 | 12.74 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
Coil Type | Rated Total Capacity [Btu/h] | Rated Sensible Capacity [Btu/h] | Rated Power[Btu/h] | Rated COP [Btuh/Btuh] | Rated Air Dry-bulb Temperature [F] | Rated Air Wet-bulb Temperature [F] | Rated Water Temperature [F] | Design Day used for Sizing | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF2 [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 5587.25 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 4378.35 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 5587.34 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 5589.48 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 4377.42 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 5583.26 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 5351.10 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 4159.48 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 5348.89 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 5352.48 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 4159.48 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 5343.80 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 6805.21 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 5437.13 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 6801.19 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | 6808.25 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | 5437.73 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | 6799.50 | 1.00 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 348.06 | 131.29 | 0.38 | 1.00 | 2.55 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 195.18 | 73.62 | 0.38 | 1.00 | 3.58 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 264.64 | 99.82 | 0.38 | 1.00 | 2.97 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 352.42 | 132.93 | 0.38 | 1.00 | 2.53 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 204.53 | 77.15 | 0.38 | 1.00 | 3.48 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 269.42 | 101.62 | 0.38 | 1.00 | 2.94 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 378.31 | 142.70 | 0.38 | 1.00 | 2.44 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 216.46 | 81.65 | 0.38 | 1.00 | 3.35 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 285.09 | 107.53 | 0.38 | 1.00 | 2.84 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 383.90 | 144.80 | 0.38 | 1.00 | 2.42 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 225.51 | 85.06 | 0.38 | 1.00 | 3.27 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 289.68 | 109.27 | 0.38 | 1.00 | 2.82 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 445.84 | 168.17 | 0.38 | 1.00 | 2.25 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 281.66 | 106.24 | 0.38 | 1.00 | 2.86 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 326.99 | 123.34 | 0.38 | 1.00 | 2.64 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 450.77 | 170.03 | 0.38 | 1.00 | 2.24 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 287.96 | 108.61 | 0.38 | 1.00 | 2.83 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 331.36 | 124.99 | 0.38 | 1.00 | 2.62 | General | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electricity Rate [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | End Use Subcategory | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4508.40 | 1.00 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8163.88 | 8163.88 | 6.80 | 348.064 | 348.064 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 75.00 | 74.99 | 0.00936 | 89.47 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4578.07 | 4578.07 | 3.81 | 195.180 | 195.180 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 75.00 | 75.00 | 0.01041 | 87.66 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6207.34 | 6207.34 | 5.17 | 264.644 | 264.644 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 75.00 | 75.00 | 0.00971 | 88.68 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8265.93 | 8265.93 | 6.89 | 352.416 | 352.416 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 75.00 | 74.99 | 0.00935 | 89.27 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4797.25 | 4797.25 | 4.00 | 204.526 | 204.526 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 75.00 | 75.00 | 0.01033 | 87.66 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6319.34 | 6319.34 | 5.26 | 269.419 | 269.419 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 75.00 | 75.00 | 0.00968 | 88.68 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8873.67 | 8873.67 | 7.39 | 378.310 | 378.310 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 75.00 | 75.00 | 0.00894 | 89.27 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5077.38 | 5077.38 | 4.23 | 216.461 | 216.461 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00979 | 87.06 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6687.13 | 6687.13 | 5.57 | 285.088 | 285.088 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | 75.00 | 75.00 | 0.00922 | 89.19 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9004.73 | 9004.73 | 7.50 | 383.898 | 383.898 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 75.00 | 75.00 | 0.00893 | 89.07 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5289.69 | 5289.69 | 4.41 | 225.513 | 225.513 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00972 | 87.06 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6794.91 | 6794.91 | 5.66 | 289.683 | 289.683 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 75.00 | 75.00 | 0.00919 | 88.99 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7772.11 | 7772.11 | 6.47 | 331.362 | 331.362 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 74.99 | 0.00947 | 88.56 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7669.53 | 7669.53 | 6.39 | 326.986 | 326.986 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 75.00 | 74.99 | 0.00945 | 89.47 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 10457.26 | 10457.26 | 8.71 | 445.845 | 445.845 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 75.00 | 74.99 | 0.00903 | 89.07 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 6754.07 | 6754.07 | 5.63 | 287.956 | 287.956 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 75.00 | 74.99 | 0.00966 | 87.66 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6606.40 | 6606.40 | 5.50 | 281.660 | 281.660 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 75.00 | 74.99 | 0.00971 | 87.36 | 0.01716 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 10572.71 | 10572.71 | 8.81 | 450.767 | 450.767 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 75.00 | 74.99 | 0.00901 | 89.07 | 0.01716 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 3728.58 | 3728.58 | 3.11 | 67.958 | 67.958 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00776 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2661.81 | 2661.81 | 2.22 | 48.515 | 48.515 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00775 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 3728.65 | 3728.65 | 3.11 | 67.959 | 67.959 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00776 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 3730.54 | 3730.54 | 3.11 | 67.994 | 67.994 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00776 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2660.99 | 2660.99 | 2.22 | 48.500 | 48.500 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00775 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 3725.06 | 3725.06 | 3.10 | 67.894 | 67.894 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00776 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 3520.18 | 3520.18 | 2.93 | 64.160 | 64.160 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00787 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2325.82 | 2325.82 | 1.94 | 42.391 | 44.995 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00788 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 3518.23 | 3518.23 | 2.93 | 64.125 | 64.125 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00787 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 3521.40 | 3521.40 | 2.93 | 64.182 | 64.182 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00787 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2324.20 | 2324.20 | 1.94 | 42.362 | 44.995 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00788 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 3513.74 | 3513.74 | 2.93 | 64.043 | 64.043 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00787 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 4798.29 | 4798.29 | 4.00 | 87.455 | 87.455 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00779 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 4799.78 | 4799.78 | 4.00 | 87.482 | 87.482 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00779 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 4803.33 | 4803.33 | 4.00 | 87.547 | 87.547 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00779 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 3596.64 | 3596.64 | 3.00 | 65.553 | 65.553 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00778 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 3596.10 | 3596.10 | 3.00 | 65.544 | 65.544 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00778 | 47.66 | 0.00699 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 4806.01 | 4806.01 | 4.00 | 87.596 | 87.596 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 72.00 | 0.00779 | 47.66 | 0.00699 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | Adjusted cooling [ft3/min] | Adjusted heating [ft3/min] | Adjusted main [ft3/min] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 348.06 | 348.06 | 67.96 | 67.96 | 348.0641 | 348.0641 | 348.0641 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 195.18 | 195.18 | 48.52 | 48.52 | 195.1804 | 195.1804 | 195.1804 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 264.64 | 264.64 | 67.96 | 67.96 | 264.6438 | 264.6438 | 264.6438 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 352.42 | 352.42 | 67.99 | 67.99 | 352.4156 | 352.4156 | 352.4156 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 204.53 | 204.53 | 48.50 | 48.50 | 204.5258 | 204.5258 | 204.5258 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 269.42 | 269.42 | 67.89 | 67.89 | 269.4187 | 269.4187 | 269.4187 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 378.31 | 378.31 | 64.16 | 64.16 | 378.3105 | 378.3105 | 378.3105 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 216.46 | 216.46 | 44.99 | 44.99 | 216.4611 | 216.4611 | 216.4611 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 285.09 | 285.09 | 64.12 | 64.12 | 285.0879 | 285.0879 | 285.0879 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 383.90 | 383.90 | 64.18 | 64.18 | 383.8985 | 383.8985 | 383.8985 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 225.51 | 225.51 | 44.99 | 44.99 | 225.5131 | 225.5131 | 225.5131 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 289.68 | 289.68 | 64.04 | 64.04 | 289.6835 | 289.6835 | 289.6835 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 445.84 | 445.84 | 87.55 | 87.55 | 445.8450 | 445.8450 | 445.8450 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 281.66 | 281.66 | 65.54 | 65.54 | 281.6598 | 281.6598 | 281.6598 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.99 | 326.99 | 87.48 | 87.48 | 326.9859 | 326.9859 | 326.9859 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 450.77 | 450.77 | 87.60 | 87.60 | 450.7675 | 450.7675 | 450.7675 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 287.96 | 287.96 | 65.55 | 65.55 | 287.9559 | 287.9559 | 287.9559 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 331.36 | 331.36 | 87.45 | 87.45 | 331.3618 | 331.3618 | 331.3618 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 13919.661 | 9758.841 | 348.064084 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 13983.16 | 9625.37 | 348.064084 | 78.03 | 65.22 | 0.01036824 | 53.60 | 51.31 | 0.00750000 | 89.47 | 0.01716479 | 77.00 | 12.9272 | 74.99 | 0.00934401 | 50.5180 | 8159.50 | 0.00 | 13925.47 | 9752.09 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 5587.255 | 5587.255 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5587.25 | 5587.25 | -999. | 68.85 | 57.79 | 0.00766138 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00776063 | 46.5186 | 3728.58 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 7805.587 | 5472.366 | 195.180351 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8271.70 | 4921.49 | 195.180351 | 79.08 | 67.78 | 0.01196881 | 53.60 | 51.31 | 0.00750000 | 87.66 | 0.01716288 | 76.53 | 23.0530 | 75.00 | 0.01039820 | 56.1227 | 4558.60 | 0.00 | 7808.84 | 5468.58 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 4378.347 | 4378.347 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4378.35 | 4378.35 | -999. | 66.39 | 56.69 | 0.00757559 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00775017 | 46.4565 | 2661.81 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 10583.547 | 7419.947 | 264.643846 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 10854.80 | 7045.31 | 264.643846 | 78.49 | 66.23 | 0.01097963 | 53.60 | 51.31 | 0.00750000 | 88.68 | 0.01716396 | 76.80 | 17.0021 | 75.00 | 0.00970893 | 52.4598 | 6207.07 | 0.00 | 10587.96 | 7414.81 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 5587.336 | 5587.336 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5587.34 | 5587.34 | -999. | 67.86 | 57.36 | 0.00763009 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00776063 | 46.5186 | 3728.65 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 14093.687 | 9880.848 | 352.415647 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 14165.78 | 9764.47 | 352.415647 | 77.98 | 65.18 | 0.01035079 | 53.60 | 51.31 | 0.00750000 | 89.27 | 0.01716457 | 76.95 | 12.7676 | 74.99 | 0.00934396 | 50.5178 | 8256.92 | 0.00 | 14099.57 | 9874.01 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 5589.477 | 5589.477 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5589.48 | 5589.48 | -999. | 68.89 | 57.81 | 0.00766265 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00776069 | 46.5189 | 3730.54 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 8179.328 | 5734.390 | 204.525839 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8632.50 | 5191.89 | 204.525839 | 78.95 | 67.55 | 0.01183100 | 53.60 | 51.31 | 0.00750000 | 87.66 | 0.01716288 | 76.53 | 21.9997 | 74.99 | 0.01032622 | 55.7409 | 4786.64 | 0.00 | 8182.74 | 5730.42 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 4377.421 | 4377.421 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 4377.42 | 4377.42 | -999. | 66.64 | 56.81 | 0.00758354 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00775014 | 46.4563 | 2660.99 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 10774.503 | 7553.823 | 269.418741 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 11035.57 | 7195.39 | 269.418741 | 78.45 | 66.15 | 0.01092969 | 53.60 | 51.31 | 0.00750000 | 88.68 | 0.01716396 | 76.80 | 16.7008 | 75.00 | 0.00967812 | 52.2958 | 6311.24 | 0.00 | 10779.00 | 7548.59 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 5583.263 | 5583.263 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5583.26 | 5583.26 | -999. | 67.93 | 57.39 | 0.00763232 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00776053 | 46.5180 | 3725.06 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 15129.264 | 10606.873 | 378.310467 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 15056.37 | 10876.76 | 378.310467 | 77.86 | 64.52 | 0.00991997 | 53.60 | 51.31 | 0.00750000 | 89.27 | 0.01716457 | 76.95 | 11.8937 | 75.00 | 0.00894200 | 48.3739 | 8873.67 | 0.00 | 15135.58 | 10599.53 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 5351.098 | 5351.098 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5351.10 | 5351.10 | -999. | 69.10 | 58.06 | 0.00776607 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00787045 | 47.1682 | 3520.18 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 8656.639 | 6069.025 | 216.461111 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 9044.95 | 5686.12 | 216.461111 | 78.67 | 66.77 | 0.01132463 | 53.60 | 51.31 | 0.00750000 | 87.06 | 0.01716224 | 76.37 | 20.7866 | 75.00 | 0.00977976 | 52.8353 | 5056.36 | 0.00 | 8660.25 | 6064.82 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 4159.483 | 4159.483 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 4159.48 | 4159.48 | -999. | 66.94 | 57.12 | 0.00769837 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00831302 | 49.7845 | 1518.10 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 11401.138 | 7993.147 | 285.087889 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | 11519.83 | 7874.48 | 285.087889 | 78.40 | 65.49 | 0.01047038 | 53.60 | 51.31 | 0.00750000 | 89.19 | 0.01716449 | 76.93 | 15.7828 | 75.00 | 0.00921414 | 49.8239 | 6683.75 | 0.00 | 11405.90 | 7987.61 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 5348.888 | 5348.888 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5348.89 | 5348.89 | -999. | 68.16 | 57.64 | 0.00773191 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00787041 | 47.1680 | 3518.23 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 15352.738 | 10763.547 | 383.898481 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 15286.08 | 11064.85 | 383.898481 | 77.81 | 64.47 | 0.00989848 | 53.60 | 51.31 | 0.00750000 | 89.07 | 0.01716436 | 76.89 | 11.7205 | 75.00 | 0.00893381 | 48.3303 | 9004.73 | 0.00 | 15359.14 | 10756.10 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 5352.484 | 5352.484 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5352.48 | 5352.48 | -999. | 69.15 | 58.08 | 0.00776761 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00787047 | 47.1683 | 3521.40 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 9018.645 | 6322.820 | 225.513127 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 9392.43 | 5964.46 | 225.513127 | 78.57 | 66.58 | 0.01120852 | 53.60 | 51.31 | 0.00750000 | 87.06 | 0.01716224 | 76.37 | 19.9523 | 75.00 | 0.00971864 | 52.5103 | 5284.17 | 0.00 | 9022.41 | 6318.44 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 4159.483 | 4159.483 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 4159.48 | 4159.48 | -999. | 67.14 | 57.21 | 0.00770579 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00831311 | 49.7851 | 1516.63 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 11584.923 | 8121.995 | 289.683462 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 11705.56 | 8027.85 | 289.683462 | 78.34 | 65.41 | 0.01043278 | 53.60 | 51.31 | 0.00750000 | 88.99 | 0.01716428 | 76.87 | 15.5325 | 75.00 | 0.00919105 | 49.7009 | 6794.41 | 0.00 | 11589.76 | 8116.37 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 5343.799 | 5343.799 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5343.80 | 5343.80 | -999. | 68.22 | 57.67 | 0.00773405 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00787034 | 47.1676 | 3513.74 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 17830.082 | 12500.371 | 445.844998 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 17714.56 | 12866.61 | 445.844998 | 77.58 | 64.33 | 0.00984982 | 53.60 | 51.31 | 0.00750000 | 89.07 | 0.01716436 | 76.89 | 10.0921 | 74.99 | 0.00902177 | 48.8010 | 10455.66 | 0.00 | 17837.52 | 12491.72 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 6805.209 | 6805.209 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6805.21 | 6805.21 | -999. | 69.54 | 58.13 | 0.00770730 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00778749 | 46.6777 | 4803.33 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 11264.042 | 7897.031 | 281.659773 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 11599.59 | 7559.35 | 281.659773 | 78.14 | 66.00 | 0.01089810 | 53.60 | 51.31 | 0.00750000 | 87.36 | 0.01716255 | 76.45 | 15.9749 | 74.99 | 0.00969753 | 52.3997 | 6595.96 | 0.00 | 11268.74 | 7891.56 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 5437.129 | 5437.129 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5437.13 | 5437.13 | -999. | 68.11 | 57.49 | 0.00765294 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00777844 | 46.6239 | 3596.10 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 13076.709 | 9167.861 | 326.985883 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 13186.36 | 8949.12 | 326.985883 | 78.15 | 65.47 | 0.01051215 | 53.60 | 51.31 | 0.00750000 | 89.47 | 0.01716479 | 77.00 | 13.7605 | 74.99 | 0.00937010 | 50.6619 | 7659.83 | 0.00 | 13082.17 | 9161.51 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 6801.193 | 6801.193 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6801.19 | 6801.19 | -999. | 68.65 | 57.74 | 0.00767808 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00778741 | 46.6773 | 4799.78 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 18026.939 | 12638.385 | 450.767456 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 17900.58 | 13032.91 | 450.767456 | 77.57 | 64.29 | 0.00982800 | 53.60 | 51.31 | 0.00750000 | 89.07 | 0.01716436 | 76.89 | 9.9819 | 74.99 | 0.00901450 | 48.7622 | 10572.71 | 0.00 | 18034.46 | 12629.64 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 6808.249 | 6808.249 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6808.25 | 6808.25 | -999. | 69.57 | 58.14 | 0.00770823 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00778755 | 46.6781 | 4806.01 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 11515.835 | 8073.558 | 287.955894 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 11821.35 | 7753.97 | 287.955894 | 78.14 | 65.92 | 0.01083552 | 53.60 | 51.31 | 0.00750000 | 87.66 | 0.01716288 | 76.53 | 15.6257 | 74.99 | 0.00966118 | 52.2063 | 6741.79 | 0.00 | 11520.64 | 8067.97 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 5437.733 | 5437.733 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5437.73 | 5437.73 | -999. | 68.20 | 57.53 | 0.00765570 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00777845 | 46.6240 | 3596.64 | 0.00 | -999.0 | -999.0 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 13251.710 | 9290.552 | 331.361837 | -999. | -999.00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 13425.39 | 9090.86 | 331.361837 | 78.00 | 65.42 | 0.01051766 | 53.60 | 51.31 | 0.00750000 | 88.56 | 0.01716384 | 76.77 | 13.5788 | 74.99 | 0.00937174 | 50.6706 | 7653.47 | 0.00 | 13257.24 | 9284.12 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 6799.496 | 6799.496 | -999. | -999. | -999.00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6799.50 | 6799.50 | -999. | 68.69 | 57.76 | 0.00767949 | 122.00 | 75.14 | 0.00800000 | 47.66 | 0.00699286 | 47.66 | -999.000 | 72.00 | 0.00778738 | 46.6771 | 4798.29 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4165.988 | 4086.835 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4174.087 | 4094.779 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4166.185 | 4087.027 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4165.977 | 4086.824 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4174.087 | 4094.779 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4166.175 | 4087.018 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4206.518 | 4126.594 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4220.053 | 4139.872 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4206.896 | 4126.965 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4206.492 | 4126.568 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4220.074 | 4139.892 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4206.881 | 4126.950 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4165.018 | 4085.883 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4173.582 | 4094.284 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4165.524 | 4086.379 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4164.993 | 4085.858 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4173.565 | 4094.268 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 4165.508 | 4086.363 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [Btu/lbm-R] | Dry Air Heat Capacity [Btu/lbm-R] | Standard Air Density Adjusted for Elevation [lb/ft3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [ft3/min] | Supply Fan Maximum Air Mass Flow Rate [lb/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [Btu/lbm-R] | Plant Fluid Density [lb/ft3] | Plant Maximum Fluid Mass Flow Rate [lb/s] | Plant Design Fluid Return Temperature [F] | Plant Design Fluid Supply Temperature [F] | Plant Design Fluid Temperature Difference [deltaF] | Plant Design Capacity [Btu/h] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] | Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] | Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] | Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [F] | System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | Coil Air Mass Flow Rate at Rating Conditions [lb/s] | Coil Entering Air Drybulb at Rating Conditions [F] | Coil Entering Air Wetbulb at Rating Conditions [F] | Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] | Coil Leaving Air Drybulb at Rating Conditions [F] | Coil Leaving Air Wetbulb at Rating Conditions [F] | Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 13919.661 | 9758.841 | 348.064084 | -999. | -999.00 | -999.0000 | 1.00000 | 0.78493 | 0.2446 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 348.064084 | 0.43561461 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | Sensible | 13983.16 | 9625.37 | 1.0046 | 0.43561461 | 348.064084 | 78.03 | 65.22 | 0.01036824 | 12.4 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 447.952 | 13535.21 | 89.47 | 0.01716479 | 77.00 | 44.99498340 | 12.9272 | 74.99 | 0.00935920 | 74.99 | 0.00934401 | 50.5180 | 8159.50 | 0.00 | 13925.47 | 9752.09 | 0.41841113 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 5587.255 | 5587.255 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 348.064084 | 0.43561461 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 5587.25 | 5587.25 | 1.0000 | -0.264891E+04 | -999. | 68.85 | 57.79 | 0.00766138 | 9.6 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5587.25 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00776063 | 72.00 | 0.00776063 | 46.5186 | 3728.58 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 7805.587 | 5472.366 | 195.180351 | -999. | -999.00 | -999.0000 | 1.00000 | 0.67805 | 0.2453 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 195.180351 | 0.24427517 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8271.70 | 4921.49 | 1.0597 | 0.24427517 | 195.180351 | 79.08 | 67.78 | 0.01196881 | 13.6 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 251.193 | 8020.51 | 87.66 | 0.01716288 | 76.53 | 44.99498340 | 23.0530 | 75.00 | 0.01041269 | 75.00 | 0.01039820 | 56.1227 | 4558.60 | 0.00 | 7808.84 | 5468.58 | 0.23462815 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 4378.347 | 4378.347 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 195.180351 | 0.24427517 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 4378.35 | 4378.35 | 1.0000 | -0.264891E+04 | -999. | 66.39 | 56.69 | 0.00757559 | 9.2 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 4378.35 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00775017 | 72.00 | 0.00775017 | 46.4565 | 2661.81 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10583.547 | 7419.947 | 264.643846 | -999. | -999.00 | -999.0000 | 1.00000 | 0.73795 | 0.2449 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 264.643846 | 0.33121121 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | Sensible | 10854.80 | 7045.31 | 1.0256 | 0.33121121 | 264.643846 | 78.49 | 66.23 | 0.01097963 | 12.9 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 340.592 | 10514.21 | 88.68 | 0.01716396 | 76.80 | 44.99498340 | 17.0021 | 75.00 | 0.00971277 | 75.00 | 0.00970893 | 52.4598 | 6207.07 | 0.00 | 10587.96 | 7414.81 | 0.31813087 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 5587.336 | 5587.336 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 264.643846 | 0.33121121 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 5587.34 | 5587.34 | 1.0000 | -0.264891E+04 | -999. | 67.86 | 57.36 | 0.00763009 | 9.4 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5587.34 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00776063 | 72.00 | 0.00776063 | 46.5186 | 3728.65 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 14093.687 | 9880.848 | 352.415647 | -999. | -999.00 | -999.0000 | 1.00000 | 0.78806 | 0.2446 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 352.415647 | 0.44106075 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | Sensible | 14165.78 | 9764.47 | 1.0051 | 0.44106075 | 352.415647 | 77.98 | 65.18 | 0.01035079 | 12.4 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 453.552 | 13712.22 | 89.27 | 0.01716457 | 76.95 | 44.99498340 | 12.7676 | 74.99 | 0.00935350 | 74.99 | 0.00934396 | 50.5178 | 8256.92 | 0.00 | 14099.57 | 9874.01 | 0.42364218 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 5589.477 | 5589.477 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 352.415647 | 0.44106075 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 5589.48 | 5589.48 | 1.0000 | -0.264891E+04 | -999. | 68.89 | 57.81 | 0.00766265 | 9.6 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5589.48 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00776069 | 72.00 | 0.00776069 | 46.5189 | 3730.54 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 8179.328 | 5734.390 | 204.525839 | -999. | -999.00 | -999.0000 | 1.00000 | 0.68666 | 0.2453 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 204.525839 | 0.25597138 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8632.50 | 5191.89 | 1.0554 | 0.25597138 | 204.525839 | 78.95 | 67.55 | 0.01183100 | 13.5 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 263.221 | 8369.28 | 87.66 | 0.01716288 | 76.53 | 44.99498340 | 21.9997 | 75.00 | 0.01032717 | 74.99 | 0.01032622 | 55.7409 | 4786.64 | 0.00 | 8182.74 | 5730.42 | 0.24586245 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 4377.421 | 4377.421 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 204.525839 | 0.25597138 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 4377.42 | 4377.42 | 1.0000 | -0.264891E+04 | -999. | 66.64 | 56.81 | 0.00758354 | 9.2 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 4377.42 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00775014 | 72.00 | 0.00775014 | 46.4563 | 2660.99 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10774.503 | 7553.823 | 269.418741 | -999. | -999.00 | -999.0000 | 1.00000 | 0.74181 | 0.2449 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 269.418741 | 0.33718716 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | Sensible | 11035.57 | 7195.39 | 1.0242 | 0.33718716 | 269.418741 | 78.45 | 66.15 | 0.01092969 | 12.8 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 346.737 | 10688.83 | 88.68 | 0.01716396 | 76.80 | 44.99498340 | 16.7008 | 75.00 | 0.00967977 | 75.00 | 0.00967812 | 52.2958 | 6311.24 | 0.00 | 10779.00 | 7548.59 | 0.32387082 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 5583.263 | 5583.263 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 269.418741 | 0.33718716 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 5583.26 | 5583.26 | 1.0000 | -0.264891E+04 | -999. | 67.93 | 57.39 | 0.00763232 | 9.4 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5583.26 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00776053 | 72.00 | 0.00776053 | 46.5180 | 3725.06 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 15129.264 | 10606.873 | 378.310467 | -999. | -999.00 | -999.0000 | 1.00000 | 0.82606 | 0.2444 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 378.310467 | 0.47346904 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | Sensible | 15056.37 | 10876.76 | 0.9952 | 0.47346904 | 378.310467 | 77.86 | 64.52 | 0.00991997 | 12.2 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 486.879 | 14569.49 | 89.27 | 0.01716457 | 76.95 | 44.99498340 | 11.8937 | 75.00 | 0.00894200 | 75.00 | 0.00894200 | 48.3739 | 8873.67 | 0.00 | 15135.58 | 10599.53 | 0.45477059 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 5351.098 | 5351.098 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 378.310467 | 0.47346904 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 5351.10 | 5351.10 | 1.0000 | -0.264891E+04 | -999. | 69.10 | 58.06 | 0.00776607 | 9.7 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5351.10 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00787045 | 72.00 | 0.00787045 | 47.1682 | 3520.18 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 8656.639 | 6069.025 | 216.461111 | -999. | -999.00 | -999.0000 | 1.00000 | 0.72095 | 0.2450 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 216.461111 | 0.27090880 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 9044.95 | 5686.12 | 1.0449 | 0.27090880 | 216.461111 | 78.67 | 66.77 | 0.01132463 | 13.1 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 278.581 | 8766.36 | 87.06 | 0.01716224 | 76.37 | 44.99498340 | 20.7866 | 75.00 | 0.00979277 | 75.00 | 0.00977976 | 52.8353 | 5056.36 | 0.00 | 8660.25 | 6064.82 | 0.26020995 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 4159.483 | 4159.483 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 216.461111 | 0.27090880 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 4159.48 | 4159.48 | 1.0000 | -0.264891E+04 | -999. | 66.94 | 57.12 | 0.00769837 | 9.3 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 4159.48 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00788351 | 72.00 | 0.00831302 | 49.7845 | 1518.10 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 11401.138 | 7993.147 | 285.087889 | -999. | -999.00 | -999.0000 | 1.00000 | 0.77231 | 0.2447 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 285.087889 | 0.35679766 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | Sensible | 11519.83 | 7874.48 | 1.0104 | 0.35679766 | 285.087889 | 78.40 | 65.49 | 0.01047038 | 12.6 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 366.903 | 11152.93 | 89.19 | 0.01716449 | 76.93 | 44.99498340 | 15.7828 | 75.00 | 0.00921586 | 75.00 | 0.00921414 | 49.8239 | 6683.75 | 0.00 | 11405.90 | 7987.61 | 0.34270685 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 5348.888 | 5348.888 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 285.087889 | 0.35679766 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 5348.89 | 5348.89 | 1.0000 | -0.264891E+04 | -999. | 68.16 | 57.64 | 0.00773191 | 9.5 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5348.89 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00787041 | 72.00 | 0.00787041 | 47.1680 | 3518.23 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 15352.738 | 10763.547 | 383.898481 | -999. | -999.00 | -999.0000 | 1.00000 | 0.82989 | 0.2444 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 383.898481 | 0.48046264 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | Sensible | 15286.08 | 11064.85 | 0.9957 | 0.48046264 | 383.898481 | 77.81 | 64.47 | 0.00989848 | 12.1 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 494.070 | 14792.01 | 89.07 | 0.01716436 | 76.89 | 44.99498340 | 11.7205 | 75.00 | 0.00893381 | 75.00 | 0.00893381 | 48.3303 | 9004.73 | 0.00 | 15359.14 | 10756.10 | 0.46148799 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 5352.484 | 5352.484 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 383.898481 | 0.48046264 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 5352.48 | 5352.48 | 1.0000 | -0.264891E+04 | -999. | 69.15 | 58.08 | 0.00776761 | 9.7 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5352.48 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00787047 | 72.00 | 0.00787047 | 47.1683 | 3521.40 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 9018.645 | 6322.820 | 225.513127 | -999. | -999.00 | -999.0000 | 1.00000 | 0.72936 | 0.2450 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 225.513127 | 0.28223772 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 9392.43 | 5964.46 | 1.0414 | 0.28223772 | 225.513127 | 78.57 | 66.58 | 0.01120852 | 13.0 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 290.231 | 9102.19 | 87.06 | 0.01716224 | 76.37 | 44.99498340 | 19.9523 | 75.00 | 0.00972453 | 75.00 | 0.00971864 | 52.5103 | 5284.17 | 0.00 | 9022.41 | 6318.44 | 0.27109146 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 4159.483 | 4159.483 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 225.513127 | 0.28223772 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 4159.48 | 4159.48 | 1.0000 | -0.264891E+04 | -999. | 67.14 | 57.21 | 0.00770579 | 9.4 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 4159.48 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00788349 | 72.00 | 0.00831311 | 49.7851 | 1516.63 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 11584.923 | 8121.995 | 289.683462 | -999. | -999.00 | -999.0000 | 1.00000 | 0.77712 | 0.2446 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 289.683462 | 0.36254918 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | Sensible | 11705.56 | 8027.85 | 1.0104 | 0.36254918 | 289.683462 | 78.34 | 65.41 | 0.01043278 | 12.5 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 372.817 | 11332.74 | 88.99 | 0.01716428 | 76.87 | 44.99498340 | 15.5325 | 75.00 | 0.00919495 | 75.00 | 0.00919105 | 49.7009 | 6794.41 | 0.00 | 11589.76 | 8116.37 | 0.34823123 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 5343.799 | 5343.799 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 289.683462 | 0.36254918 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 5343.80 | 5343.80 | 1.0000 | -0.264891E+04 | -999. | 68.22 | 57.67 | 0.00773405 | 9.5 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5343.80 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00787034 | 72.00 | 0.00787034 | 47.1676 | 3513.74 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 17830.082 | 12500.371 | 445.844998 | -999. | -999.00 | -999.0000 | 1.00000 | 0.83889 | 0.2444 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 445.844998 | 0.55799091 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | Sensible | 17714.56 | 12866.61 | 0.9935 | 0.55799091 | 445.844998 | 77.58 | 64.33 | 0.00984982 | 12.1 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 573.794 | 17140.77 | 89.07 | 0.01716436 | 76.89 | 44.99498340 | 10.0921 | 74.99 | 0.00902877 | 74.99 | 0.00902177 | 48.8010 | 10455.66 | 0.00 | 17837.52 | 12491.72 | 0.53595449 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6805.209 | 6805.209 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 445.844998 | 0.55799091 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 6805.21 | 6805.21 | 1.0000 | -0.264891E+04 | -999. | 69.54 | 58.13 | 0.00770730 | 9.7 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6805.21 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00778749 | 72.00 | 0.00778749 | 46.6777 | 4803.33 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 11264.042 | 7897.031 | 281.659773 | -999. | -999.00 | -999.0000 | 1.00000 | 0.75436 | 0.2448 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 281.659773 | 0.35250725 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 11599.59 | 7559.35 | 1.0298 | 0.35250725 | 281.659773 | 78.14 | 66.00 | 0.01089810 | 12.8 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 362.491 | 11237.10 | 87.36 | 0.01716255 | 76.45 | 44.99498340 | 15.9749 | 74.99 | 0.00970710 | 74.99 | 0.00969753 | 52.3997 | 6595.96 | 0.00 | 11268.74 | 7891.56 | 0.33858588 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 5437.129 | 5437.129 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 281.659773 | 0.35250725 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 5437.13 | 5437.13 | 1.0000 | -0.264891E+04 | -999. | 68.11 | 57.49 | 0.00765294 | 9.5 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5437.13 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00777844 | 72.00 | 0.00777844 | 46.6239 | 3596.10 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 13076.709 | 9167.861 | 326.985883 | -999. | -999.00 | -999.0000 | 1.00000 | 0.77202 | 0.2447 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 326.985883 | 0.40923449 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | Sensible | 13186.36 | 8949.12 | 1.0084 | 0.40923449 | 326.985883 | 78.15 | 65.47 | 0.01051215 | 12.6 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 420.825 | 12765.53 | 89.47 | 0.01716479 | 77.00 | 44.99498340 | 13.7605 | 74.99 | 0.00945065 | 74.99 | 0.00937010 | 50.6619 | 7659.83 | 0.00 | 13082.17 | 9161.51 | 0.39307282 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6801.193 | 6801.193 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 326.985883 | 0.40923449 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 6801.19 | 6801.19 | 1.0000 | -0.264891E+04 | -999. | 68.65 | 57.74 | 0.00767808 | 9.5 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6801.19 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00778741 | 72.00 | 0.00778741 | 46.6773 | 4799.78 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 18026.939 | 12638.385 | 450.767456 | -999. | -999.00 | -999.0000 | 1.00000 | 0.84121 | 0.2444 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 450.767456 | 0.56415154 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | Sensible | 17900.58 | 13032.91 | 0.9930 | 0.56415154 | 450.767456 | 77.57 | 64.29 | 0.00982800 | 12.1 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 580.129 | 17320.45 | 89.07 | 0.01716436 | 76.89 | 44.99498340 | 9.9819 | 74.99 | 0.00901450 | 74.99 | 0.00901450 | 48.7622 | 10572.71 | 0.00 | 18034.46 | 12629.64 | 0.54187182 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6808.249 | 6808.249 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 450.767456 | 0.56415154 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 6808.25 | 6808.25 | 1.0000 | -0.264891E+04 | -999. | 69.57 | 58.14 | 0.00770823 | 9.7 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6808.25 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00778755 | 72.00 | 0.00778755 | 46.6781 | 4806.01 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 11515.835 | 8073.558 | 287.955894 | -999. | -999.00 | -999.0000 | 1.00000 | 0.75726 | 0.2448 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 287.955894 | 0.36038707 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 11821.35 | 7753.97 | 1.0265 | 0.36038707 | 287.955894 | 78.14 | 65.92 | 0.01083552 | 12.7 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 370.594 | 11450.76 | 87.66 | 0.01716288 | 76.53 | 44.99498340 | 15.6257 | 74.99 | 0.00966374 | 74.99 | 0.00966118 | 52.2063 | 6741.79 | 0.00 | 11520.64 | 8067.97 | 0.34615450 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 5437.733 | 5437.733 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 287.955894 | 0.36038707 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 5437.73 | 5437.73 | 1.0000 | -0.264891E+04 | -999. | 68.20 | 57.53 | 0.00765570 | 9.5 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 5437.73 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00777845 | 72.00 | 0.00777845 | 46.6240 | 3596.64 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 13251.710 | 9290.552 | 331.361837 | -999. | -999.00 | -999.0000 | 1.00000 | 0.77820 | 0.2447 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 331.361837 | 0.41471115 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 13425.39 | 9090.86 | 1.0131 | 0.41471115 | 331.361837 | 78.00 | 65.42 | 0.01051766 | 12.5 | 53.60 | 51.31 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 426.457 | 12998.93 | 88.56 | 0.01716384 | 76.77 | 44.99498340 | 13.5788 | 74.99 | 0.00947338 | 74.99 | 0.00937174 | 50.6706 | 7653.47 | 0.00 | 13257.24 | 9284.12 | 0.39833320 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.45 | 53.41 | 0.00865782 | 8.1 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 6799.496 | 6799.496 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0751 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 331.361837 | 0.41471115 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | Sensible | 6799.50 | 6799.50 | 1.0000 | -0.264891E+04 | -999. | 68.69 | 57.76 | 0.00767949 | 9.5 | 122.00 | 75.14 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 6799.50 | 47.66 | 0.00699286 | 47.66 | 44.99498340 | -999.000 | 72.00 | 0.00778738 | 72.00 | 0.00778738 | 46.6771 | 4798.29 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4165.988 | 4086.835 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4174.087 | 4094.779 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4166.185 | 4087.027 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4165.977 | 4086.824 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4174.087 | 4094.779 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4166.175 | 4087.018 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4206.518 | 4126.594 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4220.053 | 4139.872 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4206.896 | 4126.965 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4206.492 | 4126.568 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4220.074 | 4139.892 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4206.881 | 4126.950 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4165.018 | 4085.883 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4173.582 | 4094.284 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4165.524 | 4086.379 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4164.993 | 4085.858 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4173.565 | 4094.268 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 4165.508 | 4086.363 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0751 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.20025894 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. |
Report: System Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 6968.17 | 4263.50 | 3140.33 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6792.83 | 4600.50 | 3475.83 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6957.67 | 3996.33 | 2904.83 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6805.50 | 4613.00 | 3299.83 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 6620.17 | 5270.83 | 3843.17 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6797.00 | 4407.17 | 3094.17 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7108.50 | 2178.00 | 1317.83 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6975.17 | 1918.00 | 1169.50 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7116.17 | 1947.50 | 1150.17 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 6923.67 | 2440.00 | 1388.83 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6783.67 | 2293.33 | 1272.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6944.83 | 2194.67 | 1195.17 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7112.00 | 2632.00 | 1637.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7249.33 | 2449.67 | 1582.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 7244.50 | 2727.83 | 1810.33 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 7008.50 | 2870.00 | 1850.83 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 7164.33 | 2605.83 | 1753.67 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 7117.00 | 2929.67 | 1880.33 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 7465.50 | 5581.17 | 4005.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4.00 | 0.00 | 4.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9.00 | 2.50 | 9.00 | 2.50 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4.67 | 0.00 | 4.67 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5.50 | 0.00 | 5.50 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 11.17 | 0.00 | 11.17 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5.67 | 0.00 | 5.67 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 3.17 | 0.00 | 3.17 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7.17 | 0.00 | 7.17 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4.17 | 0.00 | 4.17 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 3.67 | 0.00 | 3.67 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 10.33 | 0.00 | 10.33 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4.50 | 0.00 | 4.50 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 2.00 | 0.00 | 2.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 3.17 | 0.00 | 3.17 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 3.33 | 0.00 | 3.33 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 5.17 | 0.00 | 5.17 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 4.33 | 0.00 | 4.33 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 3.83 | 0.00 | 3.83 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 43.83 | 2.50 | 43.83 | 2.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.158 | 0.000 | 0.262 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.139 | 0.000 | 0.262 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.158 | 0.000 | 0.262 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.158 | 0.000 | 0.262 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.139 | 0.000 | 0.262 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.158 | 0.000 | 0.262 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.069 | 0.000 | 0.262 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.050 | 0.000 | 0.262 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.069 | 0.000 | 0.262 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.069 | 0.000 | 0.262 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.050 | 0.000 | 0.262 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.069 | 0.000 | 0.262 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.158 | 0.000 | 0.262 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.158 | 0.000 | 0.262 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.158 | 0.000 | 0.262 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.139 | 0.000 | 0.262 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.139 | 0.000 | 0.262 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.158 | 0.000 | 0.262 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Zone Area [ft2] | Design Zone Outdoor Airflow - Voz [ft3/min] | Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
Total Facility | 24.79 | 36.00 | 183739.38 | 21609.96 | 0.0000 | 0.000 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Infiltration [ft3] | Total Ventilation and Infiltration [ft3] | Dynamic Target Ventilation - Voz-dyn [ft3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 23032711.24 | 23032711.24 | 13897597.35 | 36930308.60 | 23785081.69 | 7458.83 | 808.67 | 540.50 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 23032711.24 | 23032711.24 | 12247809.03 | 35280520.27 | 23785081.69 | 7458.83 | 808.67 | 540.50 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 23032711.24 | 23032711.24 | 13900093.93 | 36932805.17 | 23785081.69 | 7458.83 | 808.67 | 540.50 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 23032711.24 | 23032711.24 | 13889012.39 | 36921723.63 | 23785081.69 | 7458.83 | 808.67 | 540.50 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 23032711.24 | 23032711.24 | 12237937.91 | 35270649.15 | 23785081.69 | 7458.83 | 808.67 | 540.50 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 23032711.24 | 23032711.24 | 13889205.12 | 36921916.36 | 23785081.69 | 7458.83 | 808.67 | 540.50 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 23034014.39 | 23034014.39 | 6095616.62 | 29129631.01 | 23785081.69 | 7453.50 | 812.17 | 542.33 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 23034014.39 | 23034014.39 | 4437069.95 | 27471084.34 | 23785081.69 | 7453.50 | 812.17 | 542.33 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 23034014.39 | 23034014.39 | 6096880.82 | 29130895.21 | 23785081.69 | 7453.50 | 812.17 | 542.33 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 23034014.39 | 23034014.39 | 6092063.31 | 29126077.70 | 23785081.69 | 7453.50 | 812.17 | 542.33 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 23034014.39 | 23034014.39 | 4433468.35 | 27467482.74 | 23785081.69 | 7453.50 | 812.17 | 542.33 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 23034014.39 | 23034014.39 | 6092584.41 | 29126598.80 | 23785081.69 | 7453.50 | 812.17 | 542.33 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 23035318.91 | 23035318.91 | 13905179.83 | 36940498.74 | 23785081.69 | 7448.17 | 816.00 | 543.83 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 23035318.91 | 23035318.91 | 13912553.41 | 36947872.32 | 23785081.69 | 7448.17 | 816.00 | 543.83 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 23035318.91 | 23035318.91 | 13909582.12 | 36944901.02 | 23785081.69 | 7448.17 | 816.00 | 543.83 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 23035318.91 | 23035318.91 | 12250790.74 | 35286109.65 | 23785081.69 | 7448.17 | 816.00 | 543.83 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 23035318.91 | 23035318.91 | 12257952.42 | 35293271.33 | 23785081.69 | 7448.17 | 816.00 | 543.83 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 23035318.91 | 23035318.91 | 13903608.46 | 36938927.37 | 23785081.69 | 7448.17 | 816.00 | 543.83 | 0.00 |
Total Facility | 0.00 | 0.414612E+09 | 0.414612E+09 | 0.193449E+09 | 0.608061E+09 | 0.428131E+09 | 7458.83 | 819.33 | 543.83 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Infiltration [ft3/min] | Total Ventilation and Infiltration [ft3/min] | Dynamic Target Ventilation - Voz-dyn [ft3/min] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 43.5717 | 43.5717 | 26.2905 | 69.8622 | 44.9950 | 7458.83 | 808.67 | 540.50 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 43.5717 | 43.5717 | 23.1696 | 66.7413 | 44.9950 | 7458.83 | 808.67 | 540.50 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 43.5717 | 43.5717 | 26.2952 | 69.8669 | 44.9950 | 7458.83 | 808.67 | 540.50 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 43.5717 | 43.5717 | 26.2743 | 69.8460 | 44.9950 | 7458.83 | 808.67 | 540.50 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 43.5717 | 43.5717 | 23.1509 | 66.7226 | 44.9950 | 7458.83 | 808.67 | 540.50 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 43.5717 | 43.5717 | 26.2746 | 69.8463 | 44.9950 | 7458.83 | 808.67 | 540.50 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 43.5742 | 43.5742 | 11.5313 | 55.1054 | 44.9950 | 7453.50 | 812.17 | 542.33 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 43.5742 | 43.5742 | 8.3937 | 51.9679 | 44.9950 | 7453.50 | 812.17 | 542.33 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 43.5742 | 43.5742 | 11.5337 | 55.1078 | 44.9950 | 7453.50 | 812.17 | 542.33 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 43.5742 | 43.5742 | 11.5245 | 55.0987 | 44.9950 | 7453.50 | 812.17 | 542.33 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 43.5742 | 43.5742 | 8.3869 | 51.9611 | 44.9950 | 7453.50 | 812.17 | 542.33 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 43.5742 | 43.5742 | 11.5255 | 55.0997 | 44.9950 | 7453.50 | 812.17 | 542.33 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 43.5766 | 43.5766 | 26.3049 | 69.8815 | 44.9950 | 7448.17 | 816.00 | 543.83 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 43.5766 | 43.5766 | 26.3188 | 69.8954 | 44.9950 | 7448.17 | 816.00 | 543.83 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 43.5766 | 43.5766 | 26.3132 | 69.8898 | 44.9950 | 7448.17 | 816.00 | 543.83 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 43.5766 | 43.5766 | 23.1752 | 66.7518 | 44.9950 | 7448.17 | 816.00 | 543.83 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 43.5766 | 43.5766 | 23.1888 | 66.7654 | 44.9950 | 7448.17 | 816.00 | 543.83 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 43.5766 | 43.5766 | 26.3019 | 69.8785 | 44.9950 | 7448.17 | 816.00 | 543.83 |
Total Facility | 0.0000 | 784.3350 | 784.3350 | 365.9535 | 1150.2885 | 809.9097 | 7458.83 | 819.33 | 543.83 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 23032711.24 | 23032711.24 | 23785081.69 | 7458.83 | 808.67 | 540.50 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 23032711.24 | 23032711.24 | 23785081.69 | 7458.83 | 808.67 | 540.50 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 23032711.24 | 23032711.24 | 23785081.69 | 7458.83 | 808.67 | 540.50 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 23032711.24 | 23032711.24 | 23785081.69 | 7458.83 | 808.67 | 540.50 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 23032711.24 | 23032711.24 | 23785081.69 | 7458.83 | 808.67 | 540.50 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 23032711.24 | 23032711.24 | 23785081.69 | 7458.83 | 808.67 | 540.50 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 23034014.39 | 23034014.39 | 23785081.69 | 7453.50 | 812.17 | 542.33 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 23034014.39 | 23034014.39 | 23785081.69 | 7453.50 | 812.17 | 542.33 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 23034014.39 | 23034014.39 | 23785081.69 | 7453.50 | 812.17 | 542.33 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 23034014.39 | 23034014.39 | 23785081.69 | 7453.50 | 812.17 | 542.33 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 23034014.39 | 23034014.39 | 23785081.69 | 7453.50 | 812.17 | 542.33 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 23034014.39 | 23034014.39 | 23785081.69 | 7453.50 | 812.17 | 542.33 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 23035318.91 | 23035318.91 | 23785081.69 | 7448.17 | 816.00 | 543.83 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 23035318.91 | 23035318.91 | 23785081.69 | 7448.17 | 816.00 | 543.83 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 23035318.91 | 23035318.91 | 23785081.69 | 7448.17 | 816.00 | 543.83 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 23035318.91 | 23035318.91 | 23785081.69 | 7448.17 | 816.00 | 543.83 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 23035318.91 | 23035318.91 | 23785081.69 | 7448.17 | 816.00 | 543.83 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 23035318.91 | 23035318.91 | 23785081.69 | 7448.17 | 816.00 | 543.83 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 43.5717 | 43.5717 | 44.9950 | 7458.83 | 808.67 | 540.50 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 43.5717 | 43.5717 | 44.9950 | 7458.83 | 808.67 | 540.50 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 43.5717 | 43.5717 | 44.9950 | 7458.83 | 808.67 | 540.50 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 43.5717 | 43.5717 | 44.9950 | 7458.83 | 808.67 | 540.50 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 43.5717 | 43.5717 | 44.9950 | 7458.83 | 808.67 | 540.50 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 43.5717 | 43.5717 | 44.9950 | 7458.83 | 808.67 | 540.50 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 43.5742 | 43.5742 | 44.9950 | 7453.50 | 812.17 | 542.33 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 43.5742 | 43.5742 | 44.9950 | 7453.50 | 812.17 | 542.33 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 43.5742 | 43.5742 | 44.9950 | 7453.50 | 812.17 | 542.33 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 43.5742 | 43.5742 | 44.9950 | 7453.50 | 812.17 | 542.33 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 43.5742 | 43.5742 | 44.9950 | 7453.50 | 812.17 | 542.33 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 43.5742 | 43.5742 | 44.9950 | 7453.50 | 812.17 | 542.33 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 43.5766 | 43.5766 | 44.9950 | 7448.17 | 816.00 | 543.83 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 43.5766 | 43.5766 | 44.9950 | 7448.17 | 816.00 | 543.83 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 43.5766 | 43.5766 | 44.9950 | 7448.17 | 816.00 | 543.83 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 43.5766 | 43.5766 | 44.9950 | 7448.17 | 816.00 | 543.83 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 43.5766 | 43.5766 | 44.9950 | 7448.17 | 816.00 | 543.83 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 43.5766 | 43.5766 | 44.9950 | 7448.17 | 816.00 | 543.83 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [ft3/min] | Limits and Scheduled Limits [ft3/min] | Economizer [ft3/min] | Exhaust Flow [ft3/min] | Mixed Air Flow [ft3/min] | High Humidity [ft3/min] | Demand Controlled Ventilation [ft3/min] | Night Ventilation [ft3/min] | Demand Limiting [ft3/min] | Energy Management System [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Surfaces by ClassTotal | Outdoors | |
Wall | 74 | 50 |
Floor | 28 | 3 |
Roof | 21 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 60 | 60 |
Overhang | 30 | 30 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1982 |
Defaulted Fields | 1847 |
Fields with Defaults | 6981 |
Autosized Fields | 360 |
Autosizable Fields | 540 |
Autocalculated Fields | 185 |
Autocalculatable Fields | 400 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 169432.56 | 8091.80 | 01-FEB-03:10 | 43525.56 | 13-NOV-07:50 |
Electricity:Building | 99639.89 | 6275.41 | 02-JAN-03:10 | 18829.48 | 01-JAN-18:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
Electricity:SpaceType:GENERAL | 99639.89 | 6275.41 | 02-JAN-03:10 | 18829.48 | 01-JAN-18:10 |
InteriorLights:Electricity | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
General:InteriorLights:Electricity | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:SpaceType:GENERAL | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
InteriorEquipment:Electricity | 88303.07 | 5995.41 | 02-JAN-04:10 | 15497.32 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 88303.07 | 5995.41 | 02-JAN-04:10 | 15497.32 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:10 | 985.58 | 01-JAN-19:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL | 3088.82 | 28.28 | 02-JAN-03:10 | 985.58 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:10 | 427.18 | 01-JAN-09:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL | 1577.30 | 15.15 | 02-JAN-02:10 | 427.18 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
electric_range:InteriorEquipment:Electricity:SpaceType:GENERAL | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
electric_mels:InteriorEquipment:Electricity:SpaceType:GENERAL | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
Electricity:HVAC | 52175.33 | 289.29 | 02-JAN-07:30 | 25496.25 | 04-FEB-08:20 |
Cooling:Electricity | 40413.60 | 0.00 | 01-JAN-07:50 | 13580.00 | 29-JUL-16:10 |
General:Cooling:Electricity | 40413.60 | 0.00 | 01-JAN-07:50 | 13580.00 | 29-JUL-16:10 |
Electricity:Plant | 11583.04 | 149.40 | 05-AUG-12:20 | 10274.90 | 02-JAN-10:40 |
WaterSystems:Electricity | 11583.04 | 149.40 | 05-AUG-12:20 | 10274.90 | 02-JAN-10:40 |
Fans:Electricity | 9158.14 | 289.29 | 02-JAN-07:30 | 2351.58 | 04-FEB-08:20 |
Ventilation:Fans:Electricity | 2534.14 | 289.29 | 01-JAN-00:10 | 289.29 | 01-JAN-00:10 |
General:Fans:Electricity | 6624.00 | 0.00 | 02-JAN-07:30 | 2062.29 | 04-FEB-08:20 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 169432.56 | 8091.80 | 01-FEB-03:10 | 43525.56 | 13-NOV-07:50 |
ElectricityPurchased:Plant | 169432.56 | 8091.80 | 01-FEB-03:10 | 43525.56 | 13-NOV-07:50 |
Cogeneration:ElectricityPurchased | 169432.56 | 8091.80 | 01-FEB-03:10 | 43525.56 | 13-NOV-07:50 |
General:Cogeneration:ElectricityPurchased | 169432.56 | 8091.80 | 01-FEB-03:10 | 43525.56 | 13-NOV-07:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 169432.56 | 8091.80 | 01-FEB-03:10 | 43525.56 | 13-NOV-07:50 |
ElectricityNet:Plant | 169432.56 | 8091.80 | 01-FEB-03:10 | 43525.56 | 13-NOV-07:50 |
Cogeneration:ElectricityNet | 169432.56 | 8091.80 | 01-FEB-03:10 | 43525.56 | 13-NOV-07:50 |
General:Cogeneration:ElectricityNet | 169432.56 | 8091.80 | 01-FEB-03:10 | 43525.56 | 13-NOV-07:50 |
ExteriorLights:Electricity | 6034.31 | 0.00 | 01-JAN-06:10 | 1377.69 | 01-JAN-00:10 |
Exterior-Lights:ExteriorLights:Electricity | 6034.31 | 0.00 | 01-JAN-06:10 | 1377.69 | 01-JAN-00:10 |
Garage-Lights:ExteriorLights:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 2603.59 | 0.00 | 01-JAN-00:10 | 23144.67 | 04-FEB-08:20 |
General:Heating:Electricity | 2603.59 | 0.00 | 01-JAN-00:10 | 23144.67 | 04-FEB-08:20 |
Water Heater:WaterSystems:Electricity | 1308.75 | 149.40 | 05-AUG-12:20 | 149.40 | 01-JAN-08:30 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Natural Gas Annual Value [therm] | Natural Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:30 |
Water:Plant | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:30 |
WaterSystems:Water | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:30 |
Domestic Hot Water:WaterSystems:Water | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:30 |
MainsWater:Facility | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:30 |
MainsWater:Plant | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:30 |
WaterSystems:MainsWater | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:30 |
Domestic Hot Water:WaterSystems:MainsWater | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:30 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1200846.23 | 228.10 | 19-APR-02:20 | 333268.81 | 29-JUL-16:20 |
EnergyTransfer:HVAC | 713420.37 | 0.00 | 02-JAN-07:30 | 191070.44 | 27-JUL-17:10 |
CoolingCoils:EnergyTransfer | 704530.65 | 0.00 | 02-JAN-07:30 | 191070.44 | 27-JUL-17:10 |
EnergyTransfer:Building | 453342.49 | 0.00 | 02-JAN-07:30 | 142938.41 | 29-JUL-16:20 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer | 6317.82 | 0.00 | 01-JAN-00:10 | 74994.48 | 04-FEB-06:30 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 6317.82 | 0.00 | 01-JAN-00:10 | 74994.48 | 04-FEB-06:30 |
General:Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 447024.67 | 0.00 | 02-JAN-07:30 | 142938.41 | 29-JUL-16:20 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer | 447024.67 | 0.00 | 02-JAN-07:30 | 142938.41 | 29-JUL-16:20 |
General:Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 23065.39 | 0.00 | 01-JAN-00:10 | 8756.79 | 29-JUL-16:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 453.09 | 0.00 | 01-JAN-00:10 | 4478.03 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 453.09 | 0.00 | 01-JAN-00:10 | 4478.03 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 22612.30 | 0.00 | 01-JAN-00:10 | 8756.79 | 29-JUL-16:20 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 22612.30 | 0.00 | 01-JAN-00:10 | 8756.79 | 29-JUL-16:20 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 18503.12 | 0.00 | 01-JAN-00:10 | 5594.04 | 29-JUL-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 212.88 | 0.00 | 01-JAN-00:10 | 3929.34 | 04-FEB-08:40 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 212.88 | 0.00 | 01-JAN-00:10 | 3929.34 | 04-FEB-08:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 18290.24 | 0.00 | 01-JAN-00:10 | 5594.04 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 18290.24 | 0.00 | 01-JAN-00:10 | 5594.04 | 29-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 23066.40 | 0.00 | 01-JAN-01:30 | 7026.92 | 29-JUL-16:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 393.31 | 0.00 | 01-JAN-00:10 | 4478.06 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 393.31 | 0.00 | 01-JAN-00:10 | 4478.06 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 22673.09 | 0.00 | 01-JAN-01:30 | 7026.92 | 29-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 22673.09 | 0.00 | 01-JAN-01:30 | 7026.92 | 29-JUL-16:10 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 21004.77 | 0.00 | 01-JAN-00:10 | 8665.32 | 29-JUL-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 548.14 | 0.00 | 01-JAN-00:10 | 5130.49 | 04-FEB-08:20 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 548.14 | 0.00 | 01-JAN-00:10 | 5130.49 | 04-FEB-08:20 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 20456.63 | 0.00 | 01-JAN-00:10 | 8665.32 | 29-JUL-16:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 20456.63 | 0.00 | 01-JAN-00:10 | 8665.32 | 29-JUL-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 16453.40 | 0.00 | 01-JAN-00:10 | 5513.29 | 29-JUL-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 294.92 | 0.00 | 01-JAN-00:10 | 3965.79 | 04-FEB-08:20 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 294.92 | 0.00 | 01-JAN-00:10 | 3965.79 | 04-FEB-08:20 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 16158.48 | 0.00 | 01-JAN-00:10 | 5513.29 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 16158.48 | 0.00 | 01-JAN-00:10 | 5513.29 | 29-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 20904.59 | 0.00 | 01-JAN-00:10 | 6968.62 | 25-JUL-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 461.16 | 0.00 | 01-JAN-00:10 | 4517.54 | 15-DEC-06:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 461.16 | 0.00 | 01-JAN-00:10 | 4517.54 | 15-DEC-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 20443.43 | 0.00 | 01-JAN-00:10 | 6968.62 | 25-JUL-10:00 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 20443.43 | 0.00 | 01-JAN-00:10 | 6968.62 | 25-JUL-10:00 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 28765.74 | 0.00 | 01-JAN-08:40 | 9354.20 | 29-JUL-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 256.63 | 0.00 | 01-JAN-00:10 | 3841.93 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 256.63 | 0.00 | 01-JAN-00:10 | 3841.93 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 28509.10 | 0.00 | 01-JAN-08:40 | 9354.20 | 29-JUL-16:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 28509.10 | 0.00 | 01-JAN-08:40 | 9354.20 | 29-JUL-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23848.02 | 0.00 | 02-JAN-07:30 | 6037.44 | 07-NOV-14:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 79.83 | 0.00 | 01-JAN-00:10 | 3747.59 | 04-FEB-06:30 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 79.83 | 0.00 | 01-JAN-00:10 | 3747.59 | 04-FEB-06:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23768.19 | 0.00 | 02-JAN-07:30 | 6037.44 | 07-NOV-14:40 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23768.19 | 0.00 | 02-JAN-07:30 | 6037.44 | 07-NOV-14:40 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 28910.85 | 0.00 | 02-JAN-07:30 | 7772.73 | 14-OCT-13:50 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 213.22 | 0.00 | 01-JAN-00:10 | 3781.44 | 04-FEB-06:30 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 213.22 | 0.00 | 01-JAN-00:10 | 3781.44 | 04-FEB-06:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 28697.62 | 0.00 | 02-JAN-07:30 | 7772.73 | 14-OCT-13:50 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 28697.62 | 0.00 | 02-JAN-07:30 | 7772.73 | 14-OCT-13:50 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 26222.65 | 0.00 | 01-JAN-08:40 | 9259.12 | 29-JUL-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 336.96 | 0.00 | 01-JAN-00:10 | 3948.96 | 04-FEB-08:40 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 336.96 | 0.00 | 01-JAN-00:10 | 3948.96 | 04-FEB-08:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 25885.69 | 0.00 | 01-JAN-08:40 | 9259.12 | 29-JUL-16:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 25885.69 | 0.00 | 01-JAN-08:40 | 9259.12 | 29-JUL-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 21178.99 | 0.00 | 01-JAN-08:40 | 5996.36 | 29-JUL-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 131.13 | 0.00 | 01-JAN-00:10 | 3226.25 | 04-FEB-09:20 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 131.13 | 0.00 | 01-JAN-00:10 | 3226.25 | 04-FEB-09:20 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 21047.86 | 0.00 | 01-JAN-08:40 | 5996.36 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 21047.86 | 0.00 | 01-JAN-08:40 | 5996.36 | 29-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 26237.93 | 0.00 | 02-JAN-05:00 | 7516.17 | 29-JUL-16:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 265.80 | 0.00 | 01-JAN-00:10 | 3925.95 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 265.80 | 0.00 | 01-JAN-00:10 | 3925.95 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 25972.13 | 0.00 | 02-JAN-05:00 | 7516.17 | 29-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 25972.13 | 0.00 | 02-JAN-05:00 | 7516.17 | 29-JUL-16:10 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 29974.62 | 0.00 | 01-JAN-04:00 | 9358.77 | 29-JUL-16:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 515.77 | 0.00 | 01-JAN-00:10 | 5597.47 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 515.77 | 0.00 | 01-JAN-00:10 | 5597.47 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 29458.85 | 0.00 | 01-JAN-04:00 | 9358.77 | 29-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 29458.85 | 0.00 | 01-JAN-04:00 | 9358.77 | 29-JUL-16:10 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 31749.48 | 0.00 | 01-JAN-04:00 | 9360.09 | 29-JUL-16:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 438.53 | 0.00 | 01-JAN-00:10 | 5670.50 | 04-FEB-07:50 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 438.53 | 0.00 | 01-JAN-00:10 | 5670.50 | 04-FEB-07:50 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 31310.95 | 0.00 | 01-JAN-04:00 | 9360.09 | 29-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 31310.95 | 0.00 | 01-JAN-04:00 | 9360.09 | 29-JUL-16:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 31738.93 | 0.00 | 01-JAN-04:20 | 11145.79 | 29-JUL-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 520.89 | 0.00 | 01-JAN-00:10 | 5518.83 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 520.89 | 0.00 | 01-JAN-00:10 | 5518.83 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 31218.04 | 0.00 | 01-JAN-04:20 | 11145.79 | 29-JUL-16:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 31218.04 | 0.00 | 01-JAN-04:20 | 11145.79 | 29-JUL-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 24935.31 | 0.00 | 01-JAN-08:40 | 7826.15 | 29-JUL-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 331.19 | 0.00 | 01-JAN-00:10 | 4922.87 | 04-FEB-08:40 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 331.19 | 0.00 | 01-JAN-00:10 | 4922.87 | 04-FEB-08:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 24604.12 | 0.00 | 01-JAN-08:40 | 7826.15 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 24604.12 | 0.00 | 01-JAN-08:40 | 7826.15 | 29-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 26736.58 | 0.00 | 01-JAN-08:40 | 7804.65 | 29-JUL-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 245.58 | 0.00 | 01-JAN-00:10 | 3945.62 | 04-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 245.58 | 0.00 | 01-JAN-00:10 | 3945.62 | 04-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 26491.00 | 0.00 | 01-JAN-08:40 | 7804.65 | 29-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 26491.00 | 0.00 | 01-JAN-08:40 | 7804.65 | 29-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 30045.74 | 0.00 | 01-JAN-04:00 | 11170.32 | 29-JUL-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 618.80 | 0.00 | 01-JAN-00:10 | 6020.43 | 04-FEB-08:40 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 618.80 | 0.00 | 01-JAN-00:10 | 6020.43 | 04-FEB-08:40 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 29426.94 | 0.00 | 01-JAN-04:00 | 11170.32 | 29-JUL-16:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 29426.94 | 0.00 | 01-JAN-04:00 | 11170.32 | 29-JUL-16:30 |
PlantLoopHeatingDemand:Facility | 34083.37 | -542.7 | 14-JUL-06:10 | 10581.92 | 07-JAN-09:00 |
PlantLoopHeatingDemand:Plant | 34083.37 | -542.7 | 14-JUL-06:10 | 10581.92 | 07-JAN-09:00 |
WaterSystems:PlantLoopHeatingDemand | 34083.37 | -542.7 | 14-JUL-06:10 | 10581.92 | 07-JAN-09:00 |
General:WaterSystems:PlantLoopHeatingDemand | 34083.37 | -542.7 | 14-JUL-06:10 | 10581.92 | 07-JAN-09:00 |
HeatingCoils:EnergyTransfer | 8889.73 | 0.00 | 01-JAN-00:10 | 78969.63 | 04-FEB-08:20 |
EnergyTransfer:Plant | 34083.37 | -542.7 | 14-JUL-06:10 | 10581.92 | 07-JAN-09:00 |
WaterSystems:EnergyTransfer | 34083.37 | -542.7 | 14-JUL-06:10 | 10581.92 | 07-JAN-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 34083.37 | -542.7 | 14-JUL-06:10 | 10581.92 | 07-JAN-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | -227.91 | 655.963 | -1672.08 | 0.000 | 0.000 | 2907.975 | 2150.478 | 10464.601 | 9797.039 | 0.000 | 2600.254 | 0.000 | 0.000 | -1398.31 | 0.000 | -1661.58 | -2701.33 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | -222.86 | 382.538 | -1314.44 | 0.000 | 0.000 | 2902.727 | 2150.478 | 10464.601 | 4149.488 | 0.000 | 2480.735 | 0.000 | 0.000 | -562.74 | 0.000 | -1613.65 | -1894.29 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | -229.89 | 556.472 | -1671.87 | 0.000 | 0.000 | 2907.442 | 2150.478 | 10464.601 | 10007.435 | 0.000 | 2595.620 | 0.000 | 0.000 | -1346.45 | 0.000 | -1675.90 | -2823.35 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | -224.32 | 810.108 | -1501.07 | 0.000 | 0.000 | 2911.175 | 2150.478 | 10464.601 | 7856.316 | 0.000 | 2606.224 | 0.000 | 0.000 | -1421.23 | 0.000 | -1628.90 | -3030.25 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | -218.07 | 541.874 | -1148.14 | 0.000 | 0.000 | 2907.560 | 2150.478 | 10464.601 | 2146.101 | 0.000 | 2491.481 | 0.000 | 0.000 | -584.52 | 0.000 | -1569.94 | -2142.20 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | -225.88 | 680.073 | -1494.84 | 0.000 | 0.000 | 2911.490 | 2150.478 | 10464.601 | 8037.441 | 0.000 | 2599.542 | 0.000 | 0.000 | -1335.85 | 0.000 | -1636.94 | -3208.38 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | -244.78 | 409.922 | -2142.16 | 0.000 | 0.000 | 2894.491 | 2150.478 | 10464.601 | 9589.987 | 0.000 | 2010.569 | 4083.660 | 0.000 | -1576.17 | 0.000 | -1365.15 | -0.26 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | -241.14 | 196.948 | -1747.98 | 0.000 | 0.000 | 2888.119 | 2150.478 | 10464.601 | 4063.634 | 0.000 | 1889.458 | 4177.555 | 0.000 | -632.78 | 0.000 | -1312.65 | -0.01 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | -247.09 | 331.371 | -2152.63 | 0.000 | 0.000 | 2893.981 | 2150.478 | 10464.601 | 9784.767 | 0.000 | 2008.364 | 4072.416 | 0.000 | -1513.68 | 0.000 | -1376.36 | -0.04 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | -240.87 | 538.866 | -1931.64 | 0.000 | 0.000 | 2897.588 | 2150.478 | 10464.601 | 7673.095 | 0.000 | 2013.404 | 3286.905 | 0.000 | -1595.78 | 0.000 | -1341.54 | -0.06 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | -235.75 | 304.045 | -1531.47 | 0.000 | 0.000 | 2892.856 | 2150.478 | 10464.601 | 2082.119 | 0.000 | 1894.165 | 3368.578 | 0.000 | -654.95 | 0.000 | -1281.06 | -0.02 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | -242.99 | 424.131 | -1933.11 | 0.000 | 0.000 | 2897.707 | 2150.478 | 10464.601 | 7836.307 | 0.000 | 2009.098 | 3197.740 | 0.000 | -1499.52 | 0.000 | -1349.92 | -0.07 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | -240.82 | 701.824 | -2227.96 | 0.000 | 0.000 | 2900.527 | 2150.478 | 10464.601 | 7732.272 | 0.000 | 2565.761 | 6355.735 | 0.000 | -1516.12 | 0.000 | -1710.00 | -0.06 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | -243.26 | 592.645 | -2377.09 | 0.000 | 0.000 | 2897.777 | 2150.478 | 10464.601 | 9695.765 | 0.000 | 2565.193 | 6353.696 | 0.000 | -1517.66 | 0.000 | -1737.24 | -0.05 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | -241.30 | 709.067 | -2374.13 | 0.000 | 0.000 | 2898.367 | 2150.478 | 10464.601 | 9499.786 | 0.000 | 2567.814 | 6414.447 | 0.000 | -1575.84 | 0.000 | -1722.53 | -0.10 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | -235.05 | 535.290 | -1830.93 | 0.000 | 0.000 | 2895.943 | 2150.478 | 10464.601 | 2039.872 | 0.000 | 2450.875 | 6576.699 | 0.000 | -660.63 | 0.000 | -1644.86 | -0.01 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | -238.00 | 396.052 | -1980.64 | 0.000 | 0.000 | 2892.904 | 2150.478 | 10464.601 | 4024.839 | 0.000 | 2447.719 | 6572.492 | 0.000 | -633.36 | 0.000 | -1674.21 | -0.08 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | -238.91 | 845.526 | -2230.58 | 0.000 | 0.000 | 2900.730 | 2150.478 | 10464.601 | 7563.452 | 0.000 | 2571.122 | 6459.634 | 0.000 | -1602.34 | 0.000 | -1699.56 | -0.01 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 25377.810 | 159788.057 | 0.000 | 0.000 | 0.000 | -185165.87 | -2.48 |
Total Facility | 0.000 | -4238.88 | 9612.716 | -33262.75 | 0.000 | 0.000 | 52199.359 | 38708.604 | 188362.826 | 123579.714 | 0.000 | 67745.208 | 220707.614 | 0.000 | -21627.94 | 0.000 | -213167.86 | -15803.05 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 29-JUL-16:24 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 140.35 | 336.87 | 1371.36 | 4861.69 | 0.00 | 1574.20 | 472.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 29-JUL-17:00 | 0.00 | -0.2 | 0.00 | -0.3 | 0.00 | 0.00 | 261.62 | 469.21 | 1685.13 | 505.48 | 0.00 | 1346.13 | 2046.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 29-JUL-16:10 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 140.35 | 336.87 | 1371.36 | 2390.99 | 0.00 | 1603.97 | 1183.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 29-JUL-16:34 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 140.35 | 336.87 | 1371.36 | 4887.88 | 0.00 | 1544.50 | 384.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 29-JUL-18:19 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 426.61 | 631.63 | 1748.06 | 486.83 | 0.00 | 1292.85 | 929.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 25-JUL-09:03 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 90.23 | 1096.02 | 4792.74 | 0.00 | 1136.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -261.2 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 29-JUL-16:34 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 140.35 | 336.87 | 1371.36 | 4758.42 | 0.00 | 1196.16 | 1551.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 07-NOV-14:39 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.09 | 90.23 | 1091.85 | 2391.79 | 0.00 | 422.67 | 1925.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 14-OCT-13:39 | 0.00 | -0.1 | 0.00 | -0.5 | 0.00 | 0.00 | 115.09 | 90.23 | 1109.73 | 3672.35 | 0.00 | 857.50 | 1927.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 29-JUL-16:34 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 140.35 | 336.87 | 1371.36 | 4846.69 | 0.00 | 1196.16 | 1368.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 29-JUL-18:10 | 0.00 | -0.2 | 0.00 | -0.3 | 0.00 | 0.00 | 426.77 | 631.63 | 1748.06 | 531.10 | 0.00 | 971.41 | 1688.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 29-JUL-16:10 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 140.35 | 336.87 | 1371.36 | 2425.18 | 0.00 | 1240.29 | 2003.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 29-JUL-16:10 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 140.35 | 336.87 | 1371.36 | 2379.13 | 0.00 | 1598.97 | 3532.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 29-JUL-16:10 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 140.35 | 336.87 | 1371.36 | 2326.99 | 0.00 | 1598.98 | 3585.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 29-JUL-16:34 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 140.35 | 336.87 | 1371.36 | 4703.24 | 0.00 | 1539.48 | 3054.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 29-JUL-18:15 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 426.76 | 631.63 | 1748.06 | 511.77 | 0.00 | 1315.45 | 3192.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 29-JUL-18:10 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 426.76 | 631.63 | 1748.06 | 453.02 | 0.00 | 1315.46 | 3229.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 29-JUL-16:34 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 140.35 | 336.87 | 1371.36 | 4788.65 | 0.00 | 1539.47 | 2993.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JUL-16:19 | 0.00 | 0.00 | 0.00 | -11.9 | 0.00 | 0.00 | 2525.68 | 6063.64 | 24684.52 | 48751.41 | 0.00 | 25707.90 | 108283.97 | 0.00 | 0.00 | 0.00 | -73078.2 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 15-DEC-07:19 | 0.00 | 0.00 | 5081.79 | 0.00 | 0.00 | 0.00 | 481.32 | 300.78 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1535.1 | 0.00 | -2385.6 | -3153.9 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 15-DEC-06:30 | 0.00 | 0.00 | 3954.92 | 0.00 | 0.00 | 0.00 | 545.12 | 336.87 | 1077.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -687.2 | 0.00 | -2361.7 | -2865.9 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 15-DEC-06:30 | 0.00 | 0.00 | 5061.86 | 0.00 | 0.00 | 0.00 | 542.44 | 336.87 | 1077.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1677.5 | 0.00 | -2523.3 | -2818.4 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 04-FEB-08:20 | 0.00 | 0.00 | 5314.72 | 0.00 | 0.00 | 0.00 | 216.89 | 132.34 | 1179.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1185.3 | 0.00 | -2642.3 | -3016.0 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 04-FEB-08:20 | 0.00 | 0.00 | 3989.15 | 0.00 | 0.00 | 0.00 | 229.76 | 132.34 | 1179.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -471.0 | 0.00 | -2329.0 | -2731.0 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 04-FEB-08:20 | 0.00 | 0.00 | 5085.69 | 0.00 | 0.00 | 0.00 | 222.87 | 132.34 | 1179.68 | 1414.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2596.8 | -5438.1 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 15-DEC-08:09 | 0.00 | 0.00 | 4917.53 | 0.00 | 0.00 | 0.00 | 219.05 | 132.34 | 1155.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -793.1 | 0.00 | -1714.0 | -3917.6 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 04-FEB-06:30 | 0.00 | 0.00 | 3780.29 | 0.00 | 0.00 | 0.00 | 548.97 | 336.87 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -814.6 | 0.00 | -2004.3 | -2932.9 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 04-FEB-07:45 | 0.00 | 0.00 | 4808.73 | 0.00 | 0.00 | 0.00 | 486.58 | 300.78 | 1225.98 | 293.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2101.2 | -5013.9 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 04-FEB-08:36 | 0.00 | 0.00 | 4965.69 | 0.00 | 0.00 | 0.00 | 225.17 | 132.34 | 1179.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1036.4 | 0.00 | -1777.0 | -3689.5 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 16-MAR-08:56 | 0.00 | 0.00 | 3793.35 | 0.00 | 0.00 | 0.00 | 222.77 | 132.34 | 1155.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -281.3 | 0.00 | -1374.9 | -3648.2 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 04-FEB-08:36 | 0.00 | 0.00 | 4854.60 | 0.00 | 0.00 | 0.00 | 220.52 | 132.34 | 1179.68 | 1727.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1851.5 | -6262.7 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 04-FEB-03:20 | 0.00 | 0.00 | 6173.03 | 0.00 | 0.00 | 0.00 | 536.51 | 48.12 | 848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1758.5 | 0.00 | -2579.6 | -3268.2 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 04-FEB-07:49 | 0.00 | 0.00 | 6037.46 | 0.00 | 0.00 | 0.00 | 481.85 | 300.78 | 1225.98 | 772.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2908.0 | -5910.1 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 04-FEB-08:53 | 0.00 | 0.00 | 6277.70 | 0.00 | 0.00 | 0.00 | 221.32 | 132.34 | 1179.68 | 319.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2313.8 | -5816.8 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 04-FEB-08:46 | 0.00 | 0.00 | 4943.22 | 0.00 | 0.00 | 0.00 | 225.35 | 132.34 | 1179.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -372.3 | 0.00 | -2320.6 | -3787.6 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 04-FEB-09:23 | 0.00 | 0.00 | 4935.42 | 0.00 | 0.00 | 0.00 | 130.22 | 90.23 | 1126.15 | 1204.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1916.1 | -5570.9 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 04-FEB-08:43 | 0.00 | 0.00 | 6250.30 | 0.00 | 0.00 | 0.00 | 223.63 | 132.34 | 1179.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -895.3 | 0.00 | -2435.5 | -4455.1 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 04-FEB-06:30 | 0.00 | 0.00 | 74998.13 | 0.00 | 0.00 | 0.00 | 9495.09 | 6063.64 | 19542.30 | 0.00 | 0.00 | 3349.87 | 0.00 | 0.00 | -29448.1 | 0.00 | -49752.1 | -34248.8 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 348.0641 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 348.0641 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 195.1804 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 195.1804 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 264.6438 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 264.6438 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 352.4156 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 352.4156 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 204.5258 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 204.5258 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 269.4187 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 269.4187 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 378.3105 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 378.3105 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 216.4611 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 216.4611 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 285.0879 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 285.0879 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 383.8985 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 383.8985 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 225.5131 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 225.5131 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 289.6835 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 289.6835 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 445.8450 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 445.8450 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 281.6598 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 281.6598 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.9859 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 326.9859 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 450.7675 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 450.7675 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 287.9559 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 287.9559 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 331.3618 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 331.3618 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 348.0641 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 348.0641 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 195.1804 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 195.1804 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 264.6438 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 264.6438 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 352.4156 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 352.4156 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 204.5258 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 204.5258 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 269.4187 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 269.4187 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 378.3105 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 378.3105 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 216.4611 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 216.4611 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 285.0879 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 285.0879 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 383.8985 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 383.8985 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 225.5131 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 225.5131 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 289.6835 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 289.6835 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 445.8450 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 445.8450 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 281.6598 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 281.6598 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.9859 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 326.9859 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 450.7675 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 450.7675 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 287.9559 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 287.9559 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 331.3618 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 331.3618 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 348.0641 | 348.0641 | 348.0641 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 195.1804 | 195.1804 | 195.1804 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 264.6438 | 264.6438 | 264.6438 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 352.4156 | 352.4156 | 352.4156 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 204.5258 | 204.5258 | 204.5258 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 269.4187 | 269.4187 | 269.4187 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 378.3105 | 378.3105 | 378.3105 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 216.4611 | 216.4611 | 216.4611 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 285.0879 | 285.0879 | 285.0879 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 383.8985 | 383.8985 | 383.8985 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 225.5131 | 225.5131 | 225.5131 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 289.6835 | 289.6835 | 289.6835 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 331.3618 | 331.3618 | 331.3618 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 326.9859 | 326.9859 | 326.9859 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 445.8450 | 445.8450 | 445.8450 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 287.9559 | 287.9559 | 287.9559 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 281.6598 | 281.6598 | 281.6598 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 450.7675 | 450.7675 | 450.7675 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 348.0641 | 348.0641 | 348.0641 | 348.0641 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 195.1804 | 195.1804 | 195.1804 | 195.1804 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 264.6438 | 264.6438 | 264.6438 | 264.6438 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 352.4156 | 352.4156 | 352.4156 | 352.4156 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 204.5258 | 204.5258 | 204.5258 | 204.5258 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 269.4187 | 269.4187 | 269.4187 | 269.4187 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 378.3105 | 378.3105 | 378.3105 | 378.3105 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 216.4611 | 216.4611 | 216.4611 | 216.4611 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 285.0879 | 285.0879 | 285.0879 | 285.0879 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 383.8985 | 383.8985 | 383.8985 | 383.8985 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 225.5131 | 225.5131 | 225.5131 | 225.5131 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 289.6835 | 289.6835 | 289.6835 | 289.6835 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 445.8450 | 445.8450 | 445.8450 | 445.8450 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 281.6598 | 281.6598 | 281.6598 | 281.6598 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.9859 | 326.9859 | 326.9859 | 326.9859 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 450.7675 | 450.7675 | 450.7675 | 450.7675 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 287.9559 | 287.9559 | 287.9559 | 287.9559 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 331.3618 | 331.3618 | 331.3618 | 331.3618 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 348.0641 | 348.0641 | 348.0641 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 195.1804 | 195.1804 | 195.1804 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 264.6438 | 264.6438 | 264.6438 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 352.4156 | 352.4156 | 352.4156 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 204.5258 | 204.5258 | 204.5258 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 269.4187 | 269.4187 | 269.4187 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 378.3105 | 378.3105 | 378.3105 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 216.4611 | 216.4611 | 216.4611 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 285.0879 | 285.0879 | 285.0879 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 383.8985 | 383.8985 | 383.8985 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 225.5131 | 225.5131 | 225.5131 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 289.6835 | 289.6835 | 289.6835 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 331.3618 | 331.3618 | 331.3618 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 326.9859 | 326.9859 | 326.9859 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 445.8450 | 445.8450 | 445.8450 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 287.9559 | 287.9559 | 287.9559 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 281.6598 | 281.6598 | 281.6598 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 450.7675 | 450.7675 | 450.7675 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 348.0641 | 348.0641 | 348.0641 | 348.0641 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 195.1804 | 195.1804 | 195.1804 | 195.1804 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 264.6438 | 264.6438 | 264.6438 | 264.6438 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 352.4156 | 352.4156 | 352.4156 | 352.4156 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 204.5258 | 204.5258 | 204.5258 | 204.5258 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 269.4187 | 269.4187 | 269.4187 | 269.4187 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 378.3105 | 378.3105 | 378.3105 | 378.3105 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 216.4611 | 216.4611 | 216.4611 | 216.4611 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 285.0879 | 285.0879 | 285.0879 | 285.0879 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 383.8985 | 383.8985 | 383.8985 | 383.8985 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 225.5131 | 225.5131 | 225.5131 | 225.5131 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 289.6835 | 289.6835 | 289.6835 | 289.6835 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 445.8450 | 445.8450 | 445.8450 | 445.8450 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 281.6598 | 281.6598 | 281.6598 | 281.6598 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 326.9859 | 326.9859 | 326.9859 | 326.9859 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 450.7675 | 450.7675 | 450.7675 | 450.7675 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 287.9559 | 287.9559 | 287.9559 | 287.9559 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 331.3618 | 331.3618 | 331.3618 | 331.3618 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [ft2] | 31210.83 |
Principal Heating Source | Electricity |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
BREEZEWAY | 1798.16 | 0.00 | 1798.16 | 0.00 |
ATTIC | 7802.71 | 0.00 | 7802.71 | 0.00 |
Totals | 31210.83 | 21609.96 | 9600.87 |
Data | |
Number of hours heating loads not met | 43.83 |
Number of hours cooling loads not met | 2.50 |
Number of hours not met | 46.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Gasoline Use [therm] | Gasoline Demand [Btu/h] | Diesel Use [kBtu] | Diesel Demand [Btu/h] | Coal Use [kBtu] | Coal Demand [Btu/h] | Fuel Oil No 1 Use [kBtu] | Fuel Oil No 1 Demand [Btu/h] | Fuel Oil No 2 Use [kBtu] | Fuel Oil No 2 Demand [Btu/h] | Propane Use [kBtu] | Propane Demand [Btu/h] | Other Fuel 1 Use [kBtu] | Other Fuel 1 Demand [Btu/h] | Other Fuel 2 Use [kBtu] | Other Fuel 2 Demand [Btu/h] | District Cooling Use [ton-hrs] | District Cooling Demand [ton] | District Heating Use [kBtu] | District Heating Demand [Btu/h] | |
Heating -- General | 2603.59 | 23144.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 40413.60 | 13580.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- General | 11336.81 | 3692.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Exterior-Lights | 6034.31 | 1377.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- dishwasher | 3088.82 | 985.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- refrigerator | 12036.11 | 1639.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- clotheswasher | 1577.30 | 427.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_dryer | 12502.11 | 3196.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_range | 9058.39 | 3721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_mels | 46926.68 | 7929.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- IECC_adj | 3113.66 | 526.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation | 2534.14 | 289.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 6624.00 | 2062.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 1308.75 | 149.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 10125.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 301503.54 | 578513.47 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 301503.54 | 578513.47 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting (All) | 0.36 |
Space Heating | 0.08 |
Space Cooling | 1.29 |
Fans (All) | 0.29 |
Service Water Heating | 0.37 |
Receptacle Equipment | 2.83 |
Miscellaneous (All) | 5.43 |
Subtotal | 5.43 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [kBtu/ft2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.69 |
Space Heating | 1.54 |
Space Cooling | 23.85 |
Fans (All) | 5.41 |
Service Water Heating | 6.84 |
Receptacle Equipment | 52.12 |
Miscellaneous | 3.56 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OCCUPANCY | 6031. | 8760. |
INTERIORLIGHTING | 2852. | 8760. |
INTERIORLIGHTINGHE | 3070. | 8760. |
INTERIORLIGHTINGHE_OS | 2910. | 8760. |
INTERIORLIGHTINGHE_VS | 2149. | 8760. |
EXTERIORLIGHTING | 4380. | 4380. |
REFRIGERATOR | 7343. | 8760. |
MISCPLUGLOAD | 5918. | 8760. |
COOKINGRANGE | 2434. | 8760. |
DISHWASHER_FLOW_SCH | 2642. | 8760. |
CLOTHESWASHER_FLOW_SCH | 3113. | 8760. |
DISHWASHER_EQUIP_SCH | 3134. | 8760. |
CLOTHESWASHER_EQUIP_SCH | 3692. | 8760. |
CLOTHESDRYER | 3911. | 8760. |
SHADING_2012IECC | 0. | 0. |
SHADING_2012IECC_HERS | 7007. | 8760. |
SINKSENSSCHEDULE | 6025. | 8760. |
SINKLATSCHEDULE | 2735. | 8760. |
SHOWERSENSSCHEDULE | 4492. | 8760. |
SHOWERLATSCHEDULE | 4268. | 8760. |
BATHSENSSCHEDULE | 8760. | 8760. |
BATHLATSCHEDULE | 0. | 0. |
First Object Used | Month Assumed | 11am First Wednesday [F] | Days with Same 11am Value | 11pm First Wednesday [F] | Days with Same 11pm Value | |
HEATING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | January | 72.00 | 365 | 72.00 | 365 |
COOLING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | July | 75.00 | 365 | 75.00 | 365 |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 16:06:37
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 350.275 | 10.075 | 119.044 | 14.388 | 14.388 |
February | 382.653 | 12.094 | 73.367 | 15.684 | 15.684 |
March | 501.000 | 15.521 | 76.539 | 18.708 | 18.708 |
April | 613.294 | 21.222 | 5.042 | 21.353 | 21.353 |
May | 701.433 | 30.715 | 0.000 | 30.715 | 30.715 |
June | 705.000 | 38.955 | 0.000 | 38.955 | 38.955 |
July | 730.200 | 43.101 | 0.000 | 43.101 | 43.101 |
August | 731.069 | 43.218 | 0.000 | 43.218 | 43.218 |
September | 702.375 | 40.552 | 0.000 | 40.552 | 40.552 |
October | 702.678 | 32.721 | 0.000 | 32.721 | 32.721 |
November | 570.103 | 21.651 | 29.306 | 22.831 | 22.831 |
December | 414.236 | 13.043 | 83.128 | 16.892 | 16.892 |
Annual Sum or Average | 7104.317 | 322.868 | 386.425 | 339.118 | 339.118 |
Minimum of Months | 350.275 | 10.075 | 0.000 | 14.388 | 14.388 |
Maximum of Months | 731.069 | 43.218 | 119.044 | 43.218 | 43.218 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 371.369 | 8.138 | 77.992 | 9.887 | 9.887 |
February | 389.833 | 9.236 | 53.583 | 10.852 | 10.852 |
March | 501.972 | 11.302 | 55.464 | 12.672 | 12.672 |
April | 606.644 | 15.541 | 0.778 | 15.591 | 15.591 |
May | 686.681 | 23.203 | 0.000 | 23.203 | 23.203 |
June | 697.042 | 30.930 | 0.000 | 30.930 | 30.930 |
July | 726.278 | 33.950 | 0.000 | 33.950 | 33.950 |
August | 725.719 | 34.303 | 0.000 | 34.303 | 34.303 |
September | 697.986 | 32.826 | 0.000 | 32.826 | 32.826 |
October | 698.833 | 26.452 | 0.000 | 26.452 | 26.452 |
November | 583.903 | 17.838 | 21.694 | 18.319 | 18.319 |
December | 436.300 | 10.517 | 62.750 | 12.197 | 12.197 |
Annual Sum or Average | 7122.561 | 254.235 | 272.261 | 261.181 | 261.181 |
Minimum of Months | 371.369 | 8.138 | 0.000 | 9.887 | 9.887 |
Maximum of Months | 726.278 | 34.303 | 77.992 | 34.303 | 34.303 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 367.664 | 9.860 | 102.325 | 12.715 | 12.715 |
February | 393.706 | 11.570 | 67.153 | 14.081 | 14.081 |
March | 516.754 | 14.557 | 58.708 | 16.310 | 16.310 |
April | 624.892 | 20.730 | 4.333 | 20.760 | 20.760 |
May | 711.556 | 30.250 | 0.000 | 30.250 | 30.250 |
June | 711.083 | 38.972 | 0.000 | 38.972 | 38.972 |
July | 734.917 | 42.595 | 0.000 | 42.595 | 42.595 |
August | 730.042 | 42.091 | 0.000 | 42.091 | 42.091 |
September | 706.167 | 40.142 | 0.000 | 40.142 | 40.142 |
October | 711.778 | 32.284 | 0.000 | 32.284 | 32.284 |
November | 577.611 | 21.172 | 26.722 | 21.985 | 21.985 |
December | 417.406 | 11.989 | 77.489 | 14.722 | 14.722 |
Annual Sum or Average | 7203.573 | 316.214 | 336.731 | 326.907 | 326.907 |
Minimum of Months | 367.664 | 9.860 | 0.000 | 12.715 | 12.715 |
Maximum of Months | 734.917 | 42.595 | 102.325 | 42.595 | 42.595 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 280.250 | 5.816 | 146.244 | 11.501 | 11.501 |
February | 336.833 | 8.588 | 87.553 | 12.971 | 12.971 |
March | 483.139 | 13.055 | 87.361 | 16.842 | 16.842 |
April | 606.525 | 19.682 | 5.042 | 19.814 | 19.814 |
May | 702.919 | 30.761 | 0.000 | 30.761 | 30.761 |
June | 706.389 | 39.548 | 0.000 | 39.548 | 39.548 |
July | 731.122 | 43.468 | 0.000 | 43.468 | 43.468 |
August | 731.153 | 42.636 | 0.000 | 42.636 | 42.636 |
September | 700.792 | 38.546 | 0.000 | 38.546 | 38.546 |
October | 693.049 | 28.877 | 0.000 | 28.877 | 28.877 |
November | 536.322 | 17.337 | 34.292 | 18.713 | 18.713 |
December | 351.694 | 8.805 | 104.694 | 13.733 | 13.733 |
Annual Sum or Average | 6860.188 | 297.119 | 465.186 | 317.410 | 317.410 |
Minimum of Months | 280.250 | 5.816 | 0.000 | 11.501 | 11.501 |
Maximum of Months | 731.153 | 43.468 | 146.244 | 43.468 | 43.468 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 277.667 | 4.143 | 111.928 | 7.051 | 7.051 |
February | 339.611 | 5.847 | 70.656 | 8.123 | 8.123 |
March | 466.222 | 8.983 | 69.250 | 10.873 | 10.873 |
April | 598.489 | 14.056 | 0.819 | 14.109 | 14.109 |
May | 687.272 | 23.316 | 0.000 | 23.316 | 23.316 |
June | 699.389 | 31.641 | 0.000 | 31.641 | 31.641 |
July | 726.781 | 34.463 | 0.000 | 34.463 | 34.463 |
August | 725.494 | 33.876 | 0.000 | 33.876 | 33.876 |
September | 696.736 | 30.979 | 0.000 | 30.979 | 30.979 |
October | 678.573 | 22.680 | 0.000 | 22.680 | 22.680 |
November | 540.786 | 13.625 | 25.056 | 14.243 | 14.243 |
December | 348.403 | 6.387 | 89.833 | 8.925 | 8.925 |
Annual Sum or Average | 6785.423 | 229.996 | 367.542 | 240.279 | 240.279 |
Minimum of Months | 277.667 | 4.143 | 0.000 | 7.051 | 7.051 |
Maximum of Months | 726.781 | 34.463 | 111.928 | 34.463 | 34.463 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 282.567 | 5.530 | 124.136 | 9.270 | 9.270 |
February | 355.661 | 8.001 | 79.875 | 10.897 | 10.897 |
March | 483.750 | 12.024 | 64.625 | 14.149 | 14.149 |
April | 624.069 | 19.191 | 4.458 | 19.234 | 19.234 |
May | 713.033 | 30.283 | 0.000 | 30.283 | 30.283 |
June | 711.583 | 39.481 | 0.000 | 39.481 | 39.481 |
July | 734.917 | 42.910 | 0.000 | 42.910 | 42.910 |
August | 729.958 | 41.539 | 0.000 | 41.539 | 41.539 |
September | 706.000 | 38.266 | 0.000 | 38.266 | 38.266 |
October | 707.833 | 28.601 | 0.000 | 28.601 | 28.601 |
November | 552.069 | 16.857 | 28.306 | 17.770 | 17.770 |
December | 343.772 | 7.766 | 101.417 | 11.351 | 11.351 |
Annual Sum or Average | 6945.214 | 290.450 | 402.817 | 303.753 | 303.753 |
Minimum of Months | 282.567 | 5.530 | 0.000 | 9.270 | 9.270 |
Maximum of Months | 734.917 | 42.910 | 124.136 | 42.910 | 42.910 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 453.406 | 15.490 | 72.153 | 18.282 | 18.282 |
February | 465.689 | 17.838 | 47.556 | 20.395 | 20.395 |
March | 573.139 | 22.638 | 49.611 | 24.843 | 24.843 |
April | 654.167 | 29.037 | 0.542 | 29.090 | 29.090 |
May | 719.389 | 38.632 | 0.000 | 38.632 | 38.632 |
June | 706.556 | 42.801 | 0.000 | 42.801 | 42.801 |
July | 735.011 | 46.691 | 0.000 | 46.691 | 46.691 |
August | 734.167 | 46.177 | 0.000 | 46.177 | 46.177 |
September | 704.750 | 43.606 | 0.000 | 43.606 | 43.606 |
October | 720.369 | 39.936 | 0.000 | 39.936 | 39.936 |
November | 615.425 | 28.433 | 20.461 | 29.262 | 29.262 |
December | 511.375 | 19.077 | 62.333 | 22.043 | 22.043 |
Annual Sum or Average | 7593.442 | 390.357 | 252.656 | 401.759 | 401.759 |
Minimum of Months | 453.406 | 15.490 | 0.000 | 18.282 | 18.282 |
Maximum of Months | 735.011 | 46.691 | 72.153 | 46.691 | 46.691 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 494.964 | 13.880 | 25.781 | 14.900 | 14.900 |
February | 497.886 | 14.956 | 25.858 | 15.964 | 15.964 |
March | 575.111 | 17.888 | 25.000 | 18.712 | 18.712 |
April | 646.014 | 22.638 | 0.111 | 22.646 | 22.646 |
May | 710.722 | 30.140 | 0.000 | 30.140 | 30.140 |
June | 704.403 | 34.099 | 0.000 | 34.099 | 34.099 |
July | 729.747 | 36.754 | 0.000 | 36.754 | 36.754 |
August | 729.556 | 36.599 | 0.000 | 36.599 | 36.599 |
September | 702.556 | 35.351 | 0.000 | 35.351 | 35.351 |
October | 714.278 | 32.890 | 0.000 | 32.890 | 32.890 |
November | 631.486 | 24.373 | 9.806 | 24.649 | 24.649 |
December | 549.761 | 16.631 | 36.708 | 17.634 | 17.634 |
Annual Sum or Average | 7686.483 | 316.200 | 123.264 | 320.339 | 320.339 |
Minimum of Months | 494.964 | 13.880 | 0.000 | 14.900 | 14.900 |
Maximum of Months | 729.747 | 36.754 | 36.708 | 36.754 | 36.754 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 479.006 | 15.469 | 60.806 | 17.272 | 17.272 |
February | 480.467 | 17.376 | 42.333 | 19.065 | 19.065 |
March | 588.629 | 21.670 | 31.722 | 22.708 | 22.708 |
April | 670.014 | 28.479 | 0.000 | 28.479 | 28.479 |
May | 729.056 | 37.960 | 0.000 | 37.960 | 37.960 |
June | 714.000 | 42.814 | 0.000 | 42.814 | 42.814 |
July | 737.750 | 46.140 | 0.000 | 46.140 | 46.140 |
August | 733.333 | 44.993 | 0.000 | 44.993 | 44.993 |
September | 709.444 | 43.218 | 0.000 | 43.218 | 43.218 |
October | 724.222 | 39.252 | 0.000 | 39.252 | 39.252 |
November | 627.319 | 27.884 | 18.428 | 28.411 | 28.411 |
December | 519.458 | 17.861 | 56.083 | 19.913 | 19.913 |
Annual Sum or Average | 7712.698 | 383.115 | 209.372 | 390.226 | 390.226 |
Minimum of Months | 479.006 | 15.469 | 0.000 | 17.272 | 17.272 |
Maximum of Months | 737.750 | 46.140 | 60.806 | 46.140 | 46.140 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 391.028 | 10.061 | 99.003 | 14.228 | 14.228 |
February | 427.083 | 13.695 | 59.436 | 16.978 | 16.978 |
March | 549.806 | 19.736 | 59.100 | 22.460 | 22.460 |
April | 649.922 | 27.403 | 0.542 | 27.457 | 27.457 |
May | 720.972 | 38.727 | 0.000 | 38.727 | 38.727 |
June | 708.056 | 43.447 | 0.000 | 43.447 | 43.447 |
July | 736.889 | 47.109 | 0.000 | 47.109 | 47.109 |
August | 734.361 | 45.585 | 0.000 | 45.585 | 45.585 |
September | 703.764 | 41.491 | 0.000 | 41.491 | 41.491 |
October | 716.694 | 35.813 | 0.000 | 35.813 | 35.813 |
November | 593.469 | 23.556 | 23.306 | 24.550 | 24.550 |
December | 455.419 | 13.840 | 78.667 | 17.795 | 17.795 |
Annual Sum or Average | 7387.464 | 360.463 | 320.053 | 375.640 | 375.640 |
Minimum of Months | 391.028 | 10.061 | 0.000 | 14.228 | 14.228 |
Maximum of Months | 736.889 | 47.109 | 99.003 | 47.109 | 47.109 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 400.472 | 8.377 | 53.286 | 10.186 | 10.186 |
February | 437.228 | 10.752 | 39.869 | 12.222 | 12.222 |
March | 534.889 | 15.017 | 35.319 | 16.243 | 16.243 |
April | 635.806 | 21.028 | 0.111 | 21.037 | 21.037 |
May | 712.403 | 30.319 | 0.000 | 30.319 | 30.319 |
June | 706.667 | 34.844 | 0.000 | 34.844 | 34.844 |
July | 733.958 | 37.303 | 0.000 | 37.303 | 37.303 |
August | 728.917 | 36.108 | 0.000 | 36.108 | 36.108 |
September | 700.472 | 33.333 | 0.000 | 33.333 | 33.333 |
October | 704.458 | 28.812 | 0.000 | 28.812 | 28.812 |
November | 603.056 | 19.524 | 12.917 | 19.903 | 19.903 |
December | 471.511 | 11.300 | 60.278 | 13.045 | 13.045 |
Annual Sum or Average | 7369.836 | 286.718 | 201.781 | 293.355 | 293.355 |
Minimum of Months | 400.472 | 8.377 | 0.000 | 10.186 | 10.186 |
Maximum of Months | 733.958 | 37.303 | 60.278 | 37.303 | 37.303 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 403.292 | 9.863 | 76.869 | 12.346 | 12.346 |
February | 440.556 | 13.177 | 51.597 | 15.288 | 15.288 |
March | 559.419 | 18.646 | 36.556 | 19.889 | 19.889 |
April | 668.583 | 26.887 | 0.000 | 26.887 | 26.887 |
May | 729.278 | 38.010 | 0.000 | 38.010 | 38.010 |
June | 714.417 | 43.354 | 0.000 | 43.354 | 43.354 |
July | 737.750 | 46.480 | 0.000 | 46.480 | 46.480 |
August | 733.333 | 44.418 | 0.000 | 44.418 | 44.418 |
September | 709.056 | 41.208 | 0.000 | 41.208 | 41.208 |
October | 723.722 | 35.376 | 0.000 | 35.376 | 35.376 |
November | 611.058 | 23.139 | 20.500 | 23.779 | 23.779 |
December | 453.764 | 12.583 | 72.111 | 15.354 | 15.354 |
Annual Sum or Average | 7484.227 | 353.143 | 257.633 | 362.391 | 362.391 |
Minimum of Months | 403.292 | 9.863 | 0.000 | 12.346 | 12.346 |
Maximum of Months | 737.750 | 46.480 | 76.869 | 46.480 | 46.480 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 427.625 | 16.002 | 106.331 | 20.849 | 20.849 |
February | 447.389 | 19.037 | 63.014 | 23.005 | 23.005 |
March | 567.917 | 24.645 | 68.616 | 28.157 | 28.157 |
April | 655.689 | 32.460 | 3.903 | 32.569 | 32.569 |
May | 725.681 | 44.864 | 0.000 | 44.864 | 44.864 |
June | 709.806 | 49.630 | 0.000 | 49.630 | 49.630 |
July | 735.611 | 53.873 | 0.000 | 53.873 | 53.873 |
August | 733.514 | 52.757 | 0.000 | 52.757 | 52.757 |
September | 707.889 | 49.519 | 0.000 | 49.519 | 49.519 |
October | 720.794 | 44.729 | 0.000 | 44.729 | 44.729 |
November | 606.208 | 31.094 | 26.539 | 32.470 | 32.470 |
December | 483.775 | 19.951 | 77.556 | 24.528 | 24.528 |
Annual Sum or Average | 7521.897 | 438.561 | 345.958 | 456.950 | 456.950 |
Minimum of Months | 427.625 | 16.002 | 0.000 | 20.849 | 20.849 |
Maximum of Months | 735.611 | 53.873 | 106.331 | 53.873 | 53.873 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 458.725 | 14.326 | 66.986 | 16.288 | 16.288 |
February | 466.678 | 16.143 | 44.769 | 18.014 | 18.014 |
March | 567.778 | 20.021 | 46.208 | 21.672 | 21.672 |
April | 653.167 | 26.226 | 0.514 | 26.263 | 26.263 |
May | 721.181 | 36.524 | 0.000 | 36.524 | 36.524 |
June | 707.764 | 41.076 | 0.000 | 41.076 | 41.076 |
July | 732.942 | 44.126 | 0.000 | 44.126 | 44.126 |
August | 732.139 | 43.336 | 0.000 | 43.336 | 43.336 |
September | 705.250 | 41.437 | 0.000 | 41.437 | 41.437 |
October | 717.069 | 37.954 | 0.000 | 37.954 | 37.954 |
November | 621.472 | 27.157 | 19.861 | 27.777 | 27.777 |
December | 509.472 | 17.501 | 57.194 | 19.635 | 19.635 |
Annual Sum or Average | 7593.636 | 365.827 | 235.533 | 374.101 | 374.101 |
Minimum of Months | 458.725 | 14.326 | 0.000 | 16.288 | 16.288 |
Maximum of Months | 732.942 | 44.126 | 66.986 | 44.126 | 44.126 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 443.542 | 15.763 | 91.306 | 18.756 | 18.756 |
February | 457.672 | 18.361 | 53.583 | 20.920 | 20.920 |
March | 577.974 | 23.454 | 51.361 | 25.260 | 25.260 |
April | 670.767 | 31.749 | 3.139 | 31.775 | 31.775 |
May | 730.806 | 43.903 | 0.000 | 43.903 | 43.903 |
June | 714.278 | 49.277 | 0.000 | 49.277 | 49.277 |
July | 736.417 | 52.996 | 0.000 | 52.996 | 52.996 |
August | 738.000 | 51.238 | 0.000 | 51.238 | 51.238 |
September | 710.750 | 48.800 | 0.000 | 48.800 | 48.800 |
October | 727.222 | 43.905 | 0.000 | 43.905 | 43.905 |
November | 614.639 | 30.404 | 24.539 | 31.311 | 31.311 |
December | 485.294 | 18.606 | 74.750 | 21.861 | 21.861 |
Annual Sum or Average | 7607.360 | 428.456 | 298.678 | 440.001 | 440.001 |
Minimum of Months | 443.542 | 15.763 | 0.000 | 18.756 | 18.756 |
Maximum of Months | 738.000 | 52.996 | 91.306 | 52.996 | 52.996 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 377.611 | 11.756 | 126.097 | 17.950 | 17.950 |
February | 419.972 | 16.034 | 72.433 | 20.714 | 20.714 |
March | 553.861 | 22.944 | 74.728 | 26.852 | 26.852 |
April | 653.936 | 31.689 | 3.986 | 31.798 | 31.798 |
May | 726.069 | 44.999 | 0.000 | 44.999 | 44.999 |
June | 711.222 | 50.044 | 0.000 | 50.044 | 50.044 |
July | 736.194 | 54.190 | 0.000 | 54.190 | 54.190 |
August | 733.569 | 52.525 | 0.000 | 52.525 | 52.525 |
September | 707.375 | 48.472 | 0.000 | 48.472 | 48.472 |
October | 715.939 | 42.038 | 0.000 | 42.038 | 42.038 |
November | 586.289 | 27.343 | 30.083 | 28.890 | 28.890 |
December | 442.333 | 15.772 | 93.111 | 21.469 | 21.469 |
Annual Sum or Average | 7364.372 | 417.807 | 400.439 | 439.940 | 439.940 |
Minimum of Months | 377.611 | 11.756 | 0.000 | 17.950 | 17.950 |
Maximum of Months | 736.194 | 54.190 | 126.097 | 54.190 | 54.190 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 395.097 | 9.948 | 90.875 | 13.044 | 13.044 |
February | 430.861 | 13.051 | 57.908 | 15.540 | 15.540 |
March | 544.194 | 18.276 | 52.058 | 20.257 | 20.257 |
April | 650.403 | 25.469 | 0.514 | 25.507 | 25.507 |
May | 720.722 | 36.702 | 0.000 | 36.702 | 36.702 |
June | 709.056 | 41.540 | 0.000 | 41.540 | 41.540 |
July | 734.961 | 44.496 | 0.000 | 44.496 | 44.496 |
August | 732.681 | 43.154 | 0.000 | 43.154 | 43.154 |
September | 703.917 | 40.434 | 0.000 | 40.434 | 40.434 |
October | 712.306 | 35.262 | 0.000 | 35.262 | 35.262 |
November | 602.319 | 23.312 | 21.972 | 24.056 | 24.056 |
December | 453.778 | 13.148 | 76.806 | 16.213 | 16.213 |
Annual Sum or Average | 7390.294 | 344.792 | 300.133 | 356.205 | 356.205 |
Minimum of Months | 395.097 | 9.948 | 0.000 | 13.044 | 13.044 |
Maximum of Months | 734.961 | 44.496 | 90.875 | 44.496 | 44.496 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 391.992 | 11.474 | 107.089 | 15.233 | 15.233 |
February | 442.850 | 15.381 | 64.161 | 18.469 | 18.469 |
March | 565.111 | 21.753 | 55.653 | 23.783 | 23.783 |
April | 669.700 | 31.028 | 3.139 | 31.055 | 31.055 |
May | 730.972 | 44.021 | 0.000 | 44.021 | 44.021 |
June | 715.083 | 49.644 | 0.000 | 49.644 | 49.644 |
July | 736.583 | 53.278 | 0.000 | 53.278 | 53.278 |
August | 738.000 | 51.032 | 0.000 | 51.032 | 51.032 |
September | 710.750 | 47.846 | 0.000 | 47.846 | 47.846 |
October | 727.278 | 41.397 | 0.000 | 41.397 | 41.397 |
November | 599.750 | 26.745 | 26.567 | 27.766 | 27.766 |
December | 439.772 | 14.397 | 90.583 | 18.322 | 18.322 |
Annual Sum or Average | 7467.842 | 407.996 | 347.192 | 421.845 | 421.845 |
Minimum of Months | 391.992 | 11.474 | 0.000 | 15.233 | 15.233 |
Maximum of Months | 738.000 | 53.278 | 107.089 | 53.278 | 53.278 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 214.50 | 0.00 | 0.00 |
February | 197.70 | 0.00 | 0.00 |
March | 158.55 | 0.00 | 0.00 |
April | 6.74 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 60.64 | 0.00 | 0.00 |
December | 191.48 | 0.00 | 0.00 |
Annual Sum or Average | 68.65 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 214.50 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 121.53 | 0.00 | 0.00 |
February | 124.36 | 0.00 | 0.00 |
March | 95.27 | 0.00 | 0.00 |
April | 3.59 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 34.52 | 0.00 | 0.00 |
December | 116.78 | 0.00 | 0.00 |
Annual Sum or Average | 41.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 124.36 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 186.76 | 0.00 | 0.00 |
February | 181.83 | 0.00 | 0.00 |
March | 114.65 | 0.00 | 0.00 |
April | 2.05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 54.90 | 0.00 | 0.00 |
December | 178.75 | 0.00 | 0.00 |
Annual Sum or Average | 59.41 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 186.76 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 279.39 | 0.00 | 0.00 |
February | 238.46 | 0.00 | 0.00 |
March | 186.11 | 0.00 | 0.00 |
April | 6.73 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 69.89 | 0.00 | 0.00 |
December | 242.19 | 0.00 | 0.00 |
Annual Sum or Average | 84.69 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 279.39 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 192.85 | 0.00 | 0.00 |
February | 167.12 | 0.00 | 0.00 |
March | 125.33 | 0.00 | 0.00 |
April | 3.66 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 42.32 | 0.00 | 0.00 |
December | 168.34 | 0.00 | 0.00 |
Annual Sum or Average | 57.92 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 192.85 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 240.17 | 0.00 | 0.00 |
February | 205.89 | 0.00 | 0.00 |
March | 136.50 | 0.00 | 0.00 |
April | 2.84 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 60.56 | 0.00 | 0.00 |
December | 230.24 | 0.00 | 0.00 |
Annual Sum or Average | 72.55 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 240.17 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 122.34 | 0.00 | 0.00 |
February | 124.05 | 0.00 | 0.00 |
March | 96.63 | 0.00 | 0.00 |
April | 2.41 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 37.58 | 0.00 | 0.00 |
December | 130.01 | 0.00 | 0.00 |
Annual Sum or Average | 42.44 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 130.01 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 60.76 | 0.00 | 0.00 |
February | 66.46 | 0.00 | 0.00 |
March | 49.05 | 0.00 | 0.00 |
April | 0.51 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 17.01 | 0.00 | 0.00 |
December | 59.70 | 0.00 | 0.00 |
Annual Sum or Average | 20.93 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.46 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 104.83 | 0.00 | 0.00 |
February | 108.73 | 0.00 | 0.00 |
March | 60.36 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 31.67 | 0.00 | 0.00 |
December | 119.33 | 0.00 | 0.00 |
Annual Sum or Average | 35.11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.33 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 180.02 | 0.00 | 0.00 |
February | 157.05 | 0.00 | 0.00 |
March | 117.67 | 0.00 | 0.00 |
April | 2.38 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 44.38 | 0.00 | 0.00 |
December | 170.85 | 0.00 | 0.00 |
Annual Sum or Average | 55.69 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 180.02 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 103.39 | 0.00 | 0.00 |
February | 93.02 | 0.00 | 0.00 |
March | 70.06 | 0.00 | 0.00 |
April | 0.51 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 22.38 | 0.00 | 0.00 |
December | 99.74 | 0.00 | 0.00 |
Annual Sum or Average | 32.22 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 103.39 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 141.94 | 0.00 | 0.00 |
February | 133.56 | 0.00 | 0.00 |
March | 71.07 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 37.79 | 0.00 | 0.00 |
December | 158.38 | 0.00 | 0.00 |
Annual Sum or Average | 44.89 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 158.38 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 229.23 | 0.00 | 0.00 |
February | 207.80 | 0.00 | 0.00 |
March | 166.12 | 0.00 | 0.00 |
April | 5.30 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 67.23 | 0.00 | 0.00 |
December | 216.50 | 0.00 | 0.00 |
Annual Sum or Average | 73.87 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 229.23 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 117.32 | 0.00 | 0.00 |
February | 123.87 | 0.00 | 0.00 |
March | 98.73 | 0.00 | 0.00 |
April | 2.25 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 38.37 | 0.00 | 0.00 |
December | 127.67 | 0.00 | 0.00 |
Annual Sum or Average | 42.03 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 127.67 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 192.87 | 0.00 | 0.00 |
February | 182.59 | 0.00 | 0.00 |
March | 116.37 | 0.00 | 0.00 |
April | 1.76 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 60.38 | 0.00 | 0.00 |
December | 209.76 | 0.00 | 0.00 |
Annual Sum or Average | 63.19 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 209.76 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 289.85 | 0.00 | 0.00 |
February | 242.46 | 0.00 | 0.00 |
March | 182.87 | 0.00 | 0.00 |
April | 5.27 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 74.80 | 0.00 | 0.00 |
December | 266.61 | 0.00 | 0.00 |
Annual Sum or Average | 87.97 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 289.85 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 181.15 | 0.00 | 0.00 |
February | 161.22 | 0.00 | 0.00 |
March | 115.90 | 0.00 | 0.00 |
April | 2.27 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 44.99 | 0.00 | 0.00 |
December | 179.37 | 0.00 | 0.00 |
Annual Sum or Average | 56.72 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 181.15 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 238.98 | 0.00 | 0.00 |
February | 217.37 | 0.00 | 0.00 |
March | 129.07 | 0.00 | 0.00 |
April | 1.75 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 67.08 | 0.00 | 0.00 |
December | 249.58 | 0.00 | 0.00 |
Annual Sum or Average | 74.79 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 249.58 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.11 |
February | 0.00 | 0.00 | 0.15 |
March | 0.00 | 0.00 | 0.17 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.34 |
June | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.00 | 0.37 |
November | 0.00 | 0.00 | 0.25 |
December | 0.00 | 0.00 | 0.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.11 |
Maximum of Months | 0.00 | 0.00 | 0.49 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.09 |
February | 0.00 | 0.00 | 0.12 |
March | 0.00 | 0.00 | 0.13 |
April | 0.00 | 0.00 | 0.18 |
May | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.00 | 0.41 |
October | 0.00 | 0.00 | 0.31 |
November | 0.00 | 0.00 | 0.22 |
December | 0.00 | 0.00 | 0.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.09 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.11 |
February | 0.00 | 0.00 | 0.14 |
March | 0.00 | 0.00 | 0.16 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.00 | 0.37 |
November | 0.00 | 0.00 | 0.25 |
December | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.11 |
Maximum of Months | 0.00 | 0.00 | 0.49 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.10 |
March | 0.00 | 0.00 | 0.15 |
April | 0.00 | 0.00 | 0.22 |
May | 0.00 | 0.00 | 0.34 |
June | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.20 |
December | 0.00 | 0.00 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.49 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.10 |
April | 0.00 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.00 | 0.38 |
October | 0.00 | 0.00 | 0.26 |
November | 0.00 | 0.00 | 0.16 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.23 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.10 |
March | 0.00 | 0.00 | 0.14 |
April | 0.00 | 0.00 | 0.22 |
May | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.00 | 0.33 |
November | 0.00 | 0.00 | 0.20 |
December | 0.00 | 0.00 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.50 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.17 |
February | 0.00 | 0.00 | 0.22 |
March | 0.00 | 0.00 | 0.25 |
April | 0.00 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.00 | 0.44 |
November | 0.00 | 0.00 | 0.33 |
December | 0.00 | 0.00 | 0.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.00 | 0.00 | 0.52 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.16 |
February | 0.00 | 0.00 | 0.19 |
March | 0.00 | 0.00 | 0.20 |
April | 0.00 | 0.00 | 0.26 |
May | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.00 | 0.43 |
October | 0.00 | 0.00 | 0.38 |
November | 0.00 | 0.00 | 0.29 |
December | 0.00 | 0.00 | 0.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.00 | 0.00 | 0.43 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.17 |
February | 0.00 | 0.00 | 0.21 |
March | 0.00 | 0.00 | 0.24 |
April | 0.00 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.00 | 0.51 |
July | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.00 | 0.51 |
October | 0.00 | 0.00 | 0.45 |
November | 0.00 | 0.00 | 0.33 |
December | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.00 | 0.00 | 0.53 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.11 |
February | 0.00 | 0.00 | 0.17 |
March | 0.00 | 0.00 | 0.22 |
April | 0.00 | 0.00 | 0.31 |
May | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.00 | 0.39 |
November | 0.00 | 0.00 | 0.27 |
December | 0.00 | 0.00 | 0.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.11 |
Maximum of Months | 0.00 | 0.00 | 0.52 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.09 |
February | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.17 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.00 | 0.40 |
October | 0.00 | 0.00 | 0.33 |
November | 0.00 | 0.00 | 0.23 |
December | 0.00 | 0.00 | 0.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.09 |
Maximum of Months | 0.00 | 0.00 | 0.43 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.11 |
February | 0.00 | 0.00 | 0.16 |
March | 0.00 | 0.00 | 0.21 |
April | 0.00 | 0.00 | 0.31 |
May | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.00 | 0.51 |
July | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.00 | 0.40 |
November | 0.00 | 0.00 | 0.27 |
December | 0.00 | 0.00 | 0.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.11 |
Maximum of Months | 0.00 | 0.00 | 0.53 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.17 |
February | 0.00 | 0.00 | 0.23 |
March | 0.00 | 0.00 | 0.27 |
April | 0.00 | 0.00 | 0.37 |
May | 0.00 | 0.00 | 0.50 |
June | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.00 | 0.50 |
November | 0.00 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.00 | 0.00 | 0.60 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.16 |
February | 0.00 | 0.00 | 0.20 |
March | 0.00 | 0.00 | 0.23 |
April | 0.00 | 0.00 | 0.30 |
May | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.00 | 0.44 |
November | 0.00 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.16 |
Maximum of Months | 0.00 | 0.00 | 0.51 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.18 |
February | 0.00 | 0.00 | 0.23 |
March | 0.00 | 0.00 | 0.26 |
April | 0.00 | 0.00 | 0.37 |
May | 0.00 | 0.00 | 0.50 |
June | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.00 | 0.58 |
October | 0.00 | 0.00 | 0.50 |
November | 0.00 | 0.00 | 0.36 |
December | 0.00 | 0.00 | 0.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.41 |
Minimum of Months | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.00 | 0.00 | 0.61 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.13 |
February | 0.00 | 0.00 | 0.19 |
March | 0.00 | 0.00 | 0.25 |
April | 0.00 | 0.00 | 0.36 |
May | 0.00 | 0.00 | 0.50 |
June | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.00 | 0.56 |
October | 0.00 | 0.00 | 0.46 |
November | 0.00 | 0.00 | 0.31 |
December | 0.00 | 0.00 | 0.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.13 |
Maximum of Months | 0.00 | 0.00 | 0.60 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.11 |
February | 0.00 | 0.00 | 0.16 |
March | 0.00 | 0.00 | 0.21 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.00 | 0.40 |
November | 0.00 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.11 |
Maximum of Months | 0.00 | 0.00 | 0.51 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.13 |
February | 0.00 | 0.00 | 0.19 |
March | 0.00 | 0.00 | 0.24 |
April | 0.00 | 0.00 | 0.36 |
May | 0.00 | 0.00 | 0.50 |
June | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.00 | 0.31 |
December | 0.00 | 0.00 | 0.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.13 |
Maximum of Months | 0.00 | 0.00 | 0.61 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.04 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.05 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.04 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.05 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.05 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.05 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.04 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.04 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.04 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.04 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.05 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.04 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.04 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.04 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.04 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.04 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.04 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.04 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.05 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.47 | 49.44 |
February | 0.00 | 0.00 | 74.32 | 44.13 |
March | 0.00 | 0.00 | 71.29 | 47.23 |
April | 0.00 | 0.00 | 65.49 | 42.68 |
May | 0.00 | 0.00 | 59.92 | 41.24 |
June | 0.00 | 0.00 | 56.40 | 37.65 |
July | 0.00 | 0.00 | 55.21 | 37.88 |
August | 0.00 | 0.00 | 55.93 | 38.55 |
September | 0.00 | 0.00 | 59.02 | 39.22 |
October | 0.00 | 0.00 | 63.39 | 43.49 |
November | 0.00 | 0.00 | 68.51 | 44.99 |
December | 0.00 | 0.00 | 73.22 | 48.80 |
Annual Sum or Average | 0.00 | 0.00 | 64.80 | 515.30 |
Minimum of Months | 0.00 | 0.00 | 55.21 | 37.65 |
Maximum of Months | 0.00 | 0.00 | 75.47 | 49.44 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.37 | 49.44 |
February | 0.00 | 0.00 | 74.08 | 44.08 |
March | 0.00 | 0.00 | 71.06 | 47.22 |
April | 0.00 | 0.00 | 65.23 | 42.72 |
May | 0.00 | 0.00 | 59.24 | 41.03 |
June | 0.00 | 0.00 | 56.29 | 37.83 |
July | 0.00 | 0.00 | 54.67 | 37.81 |
August | 0.00 | 0.00 | 55.98 | 38.82 |
September | 0.00 | 0.00 | 58.76 | 39.27 |
October | 0.00 | 0.00 | 62.71 | 43.22 |
November | 0.00 | 0.00 | 68.47 | 45.06 |
December | 0.00 | 0.00 | 72.91 | 48.70 |
Annual Sum or Average | 0.00 | 0.00 | 64.51 | 515.20 |
Minimum of Months | 0.00 | 0.00 | 54.67 | 37.81 |
Maximum of Months | 0.00 | 0.00 | 75.37 | 49.44 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.44 | 49.44 |
February | 0.00 | 0.00 | 74.27 | 44.11 |
March | 0.00 | 0.00 | 71.33 | 47.24 |
April | 0.00 | 0.00 | 65.56 | 42.67 |
May | 0.00 | 0.00 | 60.06 | 41.23 |
June | 0.00 | 0.00 | 56.60 | 37.65 |
July | 0.00 | 0.00 | 55.40 | 37.91 |
August | 0.00 | 0.00 | 56.24 | 38.69 |
September | 0.00 | 0.00 | 59.24 | 39.27 |
October | 0.00 | 0.00 | 63.17 | 43.24 |
November | 0.00 | 0.00 | 68.62 | 45.02 |
December | 0.00 | 0.00 | 73.07 | 48.74 |
Annual Sum or Average | 0.00 | 0.00 | 64.87 | 515.20 |
Minimum of Months | 0.00 | 0.00 | 55.40 | 37.65 |
Maximum of Months | 0.00 | 0.00 | 75.44 | 49.44 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.10 | 49.39 |
February | 0.00 | 0.00 | 74.78 | 44.47 |
March | 0.00 | 0.00 | 70.83 | 47.01 |
April | 0.00 | 0.00 | 65.39 | 42.69 |
May | 0.00 | 0.00 | 59.93 | 41.23 |
June | 0.00 | 0.00 | 56.44 | 37.65 |
July | 0.00 | 0.00 | 55.24 | 37.88 |
August | 0.00 | 0.00 | 55.90 | 38.55 |
September | 0.00 | 0.00 | 58.87 | 39.22 |
October | 0.00 | 0.00 | 63.00 | 43.44 |
November | 0.00 | 0.00 | 68.28 | 45.06 |
December | 0.00 | 0.00 | 72.92 | 48.83 |
Annual Sum or Average | 0.00 | 0.00 | 64.67 | 515.42 |
Minimum of Months | 0.00 | 0.00 | 55.24 | 37.65 |
Maximum of Months | 0.00 | 0.00 | 75.10 | 49.39 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.06 | 49.46 |
February | 0.00 | 0.00 | 74.42 | 44.38 |
March | 0.00 | 0.00 | 70.56 | 47.00 |
April | 0.00 | 0.00 | 65.04 | 42.68 |
May | 0.00 | 0.00 | 59.31 | 41.07 |
June | 0.00 | 0.00 | 56.35 | 37.83 |
July | 0.00 | 0.00 | 54.74 | 37.82 |
August | 0.00 | 0.00 | 55.57 | 38.58 |
September | 0.00 | 0.00 | 58.92 | 39.49 |
October | 0.00 | 0.00 | 62.71 | 43.50 |
November | 0.00 | 0.00 | 67.49 | 44.68 |
December | 0.00 | 0.00 | 72.80 | 48.90 |
Annual Sum or Average | 0.00 | 0.00 | 64.36 | 515.39 |
Minimum of Months | 0.00 | 0.00 | 54.74 | 37.82 |
Maximum of Months | 0.00 | 0.00 | 75.06 | 49.46 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.22 | 49.45 |
February | 0.00 | 0.00 | 74.64 | 44.44 |
March | 0.00 | 0.00 | 70.72 | 46.96 |
April | 0.00 | 0.00 | 65.58 | 42.75 |
May | 0.00 | 0.00 | 59.94 | 41.16 |
June | 0.00 | 0.00 | 56.64 | 37.65 |
July | 0.00 | 0.00 | 55.43 | 37.91 |
August | 0.00 | 0.00 | 56.20 | 38.69 |
September | 0.00 | 0.00 | 59.10 | 39.27 |
October | 0.00 | 0.00 | 62.79 | 43.21 |
November | 0.00 | 0.00 | 68.32 | 45.06 |
December | 0.00 | 0.00 | 72.63 | 48.69 |
Annual Sum or Average | 0.00 | 0.00 | 64.71 | 515.24 |
Minimum of Months | 0.00 | 0.00 | 55.43 | 37.65 |
Maximum of Months | 0.00 | 0.00 | 75.22 | 49.45 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 76.01 | 49.51 |
February | 0.00 | 0.00 | 74.99 | 44.12 |
March | 0.00 | 0.00 | 71.93 | 47.09 |
April | 0.00 | 0.00 | 66.23 | 42.52 |
May | 0.00 | 0.00 | 61.15 | 41.22 |
June | 0.00 | 0.00 | 57.31 | 37.65 |
July | 0.00 | 0.00 | 56.00 | 37.93 |
August | 0.00 | 0.00 | 56.86 | 38.64 |
September | 0.00 | 0.00 | 60.02 | 39.35 |
October | 0.00 | 0.00 | 64.23 | 43.28 |
November | 0.00 | 0.00 | 69.79 | 45.11 |
December | 0.00 | 0.00 | 73.49 | 48.48 |
Annual Sum or Average | 0.00 | 0.00 | 65.62 | 514.91 |
Minimum of Months | 0.00 | 0.00 | 56.00 | 37.65 |
Maximum of Months | 0.00 | 0.00 | 76.01 | 49.51 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.69 | 49.33 |
February | 0.00 | 0.00 | 75.32 | 44.34 |
March | 0.00 | 0.00 | 71.55 | 46.98 |
April | 0.00 | 0.00 | 65.97 | 42.52 |
May | 0.00 | 0.00 | 60.72 | 41.18 |
June | 0.00 | 0.00 | 56.93 | 37.65 |
July | 0.00 | 0.00 | 55.88 | 38.14 |
August | 0.00 | 0.00 | 56.51 | 38.64 |
September | 0.00 | 0.00 | 59.61 | 39.30 |
October | 0.00 | 0.00 | 64.24 | 43.42 |
November | 0.00 | 0.00 | 69.13 | 44.71 |
December | 0.00 | 0.00 | 73.70 | 48.68 |
Annual Sum or Average | 0.00 | 0.00 | 65.38 | 514.88 |
Minimum of Months | 0.00 | 0.00 | 55.88 | 37.65 |
Maximum of Months | 0.00 | 0.00 | 75.69 | 49.33 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.70 | 49.29 |
February | 0.00 | 0.00 | 75.06 | 44.16 |
March | 0.00 | 0.00 | 71.98 | 47.11 |
April | 0.00 | 0.00 | 66.55 | 42.64 |
May | 0.00 | 0.00 | 61.40 | 41.30 |
June | 0.00 | 0.00 | 57.23 | 37.49 |
July | 0.00 | 0.00 | 56.50 | 38.14 |
August | 0.00 | 0.00 | 57.00 | 38.66 |
September | 0.00 | 0.00 | 59.65 | 39.01 |
October | 0.00 | 0.00 | 65.06 | 43.73 |
November | 0.00 | 0.00 | 69.27 | 44.71 |
December | 0.00 | 0.00 | 73.66 | 48.61 |
Annual Sum or Average | 0.00 | 0.00 | 65.71 | 514.85 |
Minimum of Months | 0.00 | 0.00 | 56.50 | 37.49 |
Maximum of Months | 0.00 | 0.00 | 75.70 | 49.29 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.57 | 49.46 |
February | 0.00 | 0.00 | 74.55 | 44.05 |
March | 0.00 | 0.00 | 71.98 | 47.21 |
April | 0.00 | 0.00 | 66.18 | 42.55 |
May | 0.00 | 0.00 | 61.16 | 41.22 |
June | 0.00 | 0.00 | 57.36 | 37.65 |
July | 0.00 | 0.00 | 56.04 | 37.93 |
August | 0.00 | 0.00 | 56.83 | 38.64 |
September | 0.00 | 0.00 | 59.88 | 39.36 |
October | 0.00 | 0.00 | 63.92 | 43.29 |
November | 0.00 | 0.00 | 69.36 | 45.10 |
December | 0.00 | 0.00 | 73.13 | 48.54 |
Annual Sum or Average | 0.00 | 0.00 | 65.45 | 515.02 |
Minimum of Months | 0.00 | 0.00 | 56.04 | 37.65 |
Maximum of Months | 0.00 | 0.00 | 75.57 | 49.46 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.56 | 49.51 |
February | 0.00 | 0.00 | 74.56 | 44.12 |
March | 0.00 | 0.00 | 71.46 | 47.07 |
April | 0.00 | 0.00 | 65.88 | 42.55 |
May | 0.00 | 0.00 | 60.73 | 41.18 |
June | 0.00 | 0.00 | 57.03 | 37.67 |
July | 0.00 | 0.00 | 55.63 | 37.93 |
August | 0.00 | 0.00 | 56.46 | 38.66 |
September | 0.00 | 0.00 | 59.37 | 39.26 |
October | 0.00 | 0.00 | 64.13 | 43.65 |
November | 0.00 | 0.00 | 68.55 | 44.67 |
December | 0.00 | 0.00 | 73.19 | 48.69 |
Annual Sum or Average | 0.00 | 0.00 | 65.16 | 514.95 |
Minimum of Months | 0.00 | 0.00 | 55.63 | 37.67 |
Maximum of Months | 0.00 | 0.00 | 75.56 | 49.51 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.61 | 49.45 |
February | 0.00 | 0.00 | 74.54 | 44.04 |
March | 0.00 | 0.00 | 71.98 | 47.22 |
April | 0.00 | 0.00 | 66.27 | 42.54 |
May | 0.00 | 0.00 | 61.41 | 41.31 |
June | 0.00 | 0.00 | 57.28 | 37.49 |
July | 0.00 | 0.00 | 56.53 | 38.14 |
August | 0.00 | 0.00 | 56.96 | 38.66 |
September | 0.00 | 0.00 | 59.98 | 39.32 |
October | 0.00 | 0.00 | 64.27 | 43.39 |
November | 0.00 | 0.00 | 68.92 | 44.76 |
December | 0.00 | 0.00 | 73.48 | 48.84 |
Annual Sum or Average | 0.00 | 0.00 | 65.56 | 515.16 |
Minimum of Months | 0.00 | 0.00 | 56.53 | 37.49 |
Maximum of Months | 0.00 | 0.00 | 75.61 | 49.45 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.96 | 49.47 |
February | 0.00 | 0.00 | 74.79 | 44.09 |
March | 0.00 | 0.00 | 71.94 | 47.20 |
April | 0.00 | 0.00 | 66.02 | 42.52 |
May | 0.00 | 0.00 | 60.82 | 41.18 |
June | 0.00 | 0.00 | 57.11 | 37.66 |
July | 0.00 | 0.00 | 56.14 | 38.14 |
August | 0.00 | 0.00 | 56.63 | 38.63 |
September | 0.00 | 0.00 | 59.66 | 39.30 |
October | 0.00 | 0.00 | 64.16 | 43.41 |
November | 0.00 | 0.00 | 69.23 | 44.89 |
December | 0.00 | 0.00 | 73.37 | 48.50 |
Annual Sum or Average | 0.00 | 0.00 | 65.44 | 514.98 |
Minimum of Months | 0.00 | 0.00 | 56.14 | 37.66 |
Maximum of Months | 0.00 | 0.00 | 75.96 | 49.47 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.92 | 49.50 |
February | 0.00 | 0.00 | 74.76 | 44.11 |
March | 0.00 | 0.00 | 71.53 | 47.07 |
April | 0.00 | 0.00 | 65.85 | 42.55 |
May | 0.00 | 0.00 | 60.53 | 41.18 |
June | 0.00 | 0.00 | 56.79 | 37.65 |
July | 0.00 | 0.00 | 55.79 | 38.13 |
August | 0.00 | 0.00 | 56.31 | 38.65 |
September | 0.00 | 0.00 | 59.44 | 39.32 |
October | 0.00 | 0.00 | 63.95 | 43.39 |
November | 0.00 | 0.00 | 69.13 | 44.88 |
December | 0.00 | 0.00 | 73.27 | 48.51 |
Annual Sum or Average | 0.00 | 0.00 | 65.22 | 514.95 |
Minimum of Months | 0.00 | 0.00 | 55.79 | 37.65 |
Maximum of Months | 0.00 | 0.00 | 75.92 | 49.50 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.66 | 49.30 |
February | 0.00 | 0.00 | 75.04 | 44.21 |
March | 0.00 | 0.00 | 71.95 | 47.19 |
April | 0.00 | 0.00 | 66.17 | 42.54 |
May | 0.00 | 0.00 | 61.01 | 41.21 |
June | 0.00 | 0.00 | 57.26 | 37.63 |
July | 0.00 | 0.00 | 55.94 | 37.90 |
August | 0.00 | 0.00 | 56.78 | 38.69 |
September | 0.00 | 0.00 | 59.92 | 39.35 |
October | 0.00 | 0.00 | 64.18 | 43.34 |
November | 0.00 | 0.00 | 69.24 | 44.87 |
December | 0.00 | 0.00 | 73.62 | 48.69 |
Annual Sum or Average | 0.00 | 0.00 | 65.51 | 514.93 |
Minimum of Months | 0.00 | 0.00 | 55.94 | 37.63 |
Maximum of Months | 0.00 | 0.00 | 75.66 | 49.30 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.68 | 49.45 |
February | 0.00 | 0.00 | 74.60 | 44.08 |
March | 0.00 | 0.00 | 71.91 | 47.22 |
April | 0.00 | 0.00 | 66.03 | 42.56 |
May | 0.00 | 0.00 | 60.83 | 41.18 |
June | 0.00 | 0.00 | 57.14 | 37.66 |
July | 0.00 | 0.00 | 56.17 | 38.14 |
August | 0.00 | 0.00 | 56.61 | 38.63 |
September | 0.00 | 0.00 | 59.59 | 39.30 |
October | 0.00 | 0.00 | 63.73 | 43.25 |
November | 0.00 | 0.00 | 69.18 | 45.06 |
December | 0.00 | 0.00 | 73.41 | 48.74 |
Annual Sum or Average | 0.00 | 0.00 | 65.36 | 515.25 |
Minimum of Months | 0.00 | 0.00 | 56.17 | 37.66 |
Maximum of Months | 0.00 | 0.00 | 75.68 | 49.45 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.59 | 49.43 |
February | 0.00 | 0.00 | 74.46 | 44.08 |
March | 0.00 | 0.00 | 71.67 | 47.21 |
April | 0.00 | 0.00 | 65.79 | 42.56 |
May | 0.00 | 0.00 | 60.54 | 41.18 |
June | 0.00 | 0.00 | 56.82 | 37.65 |
July | 0.00 | 0.00 | 55.82 | 38.13 |
August | 0.00 | 0.00 | 56.29 | 38.65 |
September | 0.00 | 0.00 | 59.35 | 39.32 |
October | 0.00 | 0.00 | 63.73 | 43.40 |
November | 0.00 | 0.00 | 68.80 | 44.89 |
December | 0.00 | 0.00 | 73.25 | 48.73 |
Annual Sum or Average | 0.00 | 0.00 | 65.13 | 515.21 |
Minimum of Months | 0.00 | 0.00 | 55.82 | 37.65 |
Maximum of Months | 0.00 | 0.00 | 75.59 | 49.43 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 75.82 | 49.54 |
February | 0.00 | 0.00 | 74.63 | 44.09 |
March | 0.00 | 0.00 | 71.73 | 47.13 |
April | 0.00 | 0.00 | 66.12 | 42.55 |
May | 0.00 | 0.00 | 61.02 | 41.21 |
June | 0.00 | 0.00 | 57.29 | 37.63 |
July | 0.00 | 0.00 | 55.96 | 37.90 |
August | 0.00 | 0.00 | 56.76 | 38.69 |
September | 0.00 | 0.00 | 59.86 | 39.35 |
October | 0.00 | 0.00 | 63.92 | 43.28 |
November | 0.00 | 0.00 | 69.14 | 44.98 |
December | 0.00 | 0.00 | 73.35 | 48.74 |
Annual Sum or Average | 0.00 | 0.00 | 65.42 | 515.09 |
Minimum of Months | 0.00 | 0.00 | 55.96 | 37.63 |
Maximum of Months | 0.00 | 0.00 | 75.82 | 49.54 |
Report: HEATING AND COOLING LOADS
For: BREEZEWAY
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 75.41 | 111.54 |
February | 86.22 | 103.10 |
March | 102.74 | 91.69 |
April | 134.17 | 2.43 |
May | 172.32 | 0.00 |
June | 210.54 | 0.00 |
July | 237.32 | 0.00 |
August | 234.92 | 0.00 |
September | 225.14 | 0.00 |
October | 186.08 | 0.00 |
November | 129.73 | 31.11 |
December | 88.52 | 113.22 |
Annual Sum or Average | 1883.10 | 453.09 |
Minimum of Months | 75.41 | 0.00 |
Maximum of Months | 237.32 | 113.22 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 64.72 | 43.95 |
February | 69.48 | 54.46 |
March | 77.90 | 44.27 |
April | 100.46 | 0.65 |
May | 131.59 | 0.00 |
June | 171.02 | 0.00 |
July | 190.38 | 0.00 |
August | 190.76 | 0.00 |
September | 187.55 | 0.00 |
October | 154.00 | 0.00 |
November | 110.64 | 13.42 |
December | 74.66 | 56.12 |
Annual Sum or Average | 1523.17 | 212.88 |
Minimum of Months | 64.72 | 0.00 |
Maximum of Months | 190.76 | 56.12 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 75.22 | 96.07 |
February | 83.74 | 94.27 |
March | 98.17 | 68.47 |
April | 132.57 | 1.30 |
May | 173.05 | 0.00 |
June | 217.58 | 0.00 |
July | 242.06 | 0.00 |
August | 235.57 | 0.00 |
September | 229.99 | 0.00 |
October | 187.96 | 0.00 |
November | 129.43 | 28.91 |
December | 82.84 | 104.29 |
Annual Sum or Average | 1888.16 | 393.31 |
Minimum of Months | 75.22 | 0.00 |
Maximum of Months | 242.06 | 104.29 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 45.58 | 142.39 |
February | 61.92 | 120.28 |
March | 85.32 | 105.97 |
April | 123.55 | 2.43 |
May | 172.22 | 0.00 |
June | 214.11 | 0.00 |
July | 239.32 | 0.00 |
August | 230.24 | 0.00 |
September | 210.49 | 0.00 |
October | 159.64 | 0.00 |
November | 101.35 | 36.44 |
December | 59.84 | 140.63 |
Annual Sum or Average | 1703.58 | 548.14 |
Minimum of Months | 45.58 | 0.00 |
Maximum of Months | 239.32 | 142.39 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 35.85 | 69.91 |
February | 45.63 | 69.87 |
March | 61.42 | 56.54 |
April | 90.04 | 0.68 |
May | 131.53 | 0.00 |
June | 174.65 | 0.00 |
July | 192.51 | 0.00 |
August | 185.95 | 0.00 |
September | 172.72 | 0.00 |
October | 127.11 | 0.00 |
November | 81.72 | 16.58 |
December | 46.52 | 81.33 |
Annual Sum or Average | 1345.64 | 294.92 |
Minimum of Months | 35.85 | 0.00 |
Maximum of Months | 192.51 | 81.33 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 44.75 | 118.62 |
February | 58.86 | 104.91 |
March | 80.07 | 75.92 |
April | 121.58 | 1.44 |
May | 172.70 | 0.00 |
June | 220.63 | 0.00 |
July | 243.58 | 0.00 |
August | 230.61 | 0.00 |
September | 215.06 | 0.00 |
October | 161.00 | 0.00 |
November | 99.78 | 31.56 |
December | 53.87 | 128.70 |
Annual Sum or Average | 1702.48 | 461.16 |
Minimum of Months | 44.75 | 0.00 |
Maximum of Months | 243.58 | 128.70 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 112.10 | 55.16 |
February | 125.13 | 60.25 |
March | 150.72 | 50.15 |
April | 187.47 | 0.44 |
May | 228.91 | 0.00 |
June | 242.94 | 0.00 |
July | 268.01 | 0.00 |
August | 262.33 | 0.00 |
September | 252.27 | 0.00 |
October | 238.39 | 0.00 |
November | 176.92 | 17.39 |
December | 128.98 | 73.25 |
Annual Sum or Average | 2374.17 | 256.63 |
Minimum of Months | 112.10 | 0.00 |
Maximum of Months | 268.01 | 73.25 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 104.46 | 15.22 |
February | 108.98 | 21.97 |
March | 122.97 | 16.03 |
April | 149.35 | 0.07 |
May | 181.97 | 0.00 |
June | 198.00 | 0.00 |
July | 214.88 | 0.00 |
August | 212.20 | 0.00 |
September | 210.18 | 0.00 |
October | 202.40 | 0.00 |
November | 157.13 | 3.55 |
December | 116.82 | 22.99 |
Annual Sum or Average | 1979.36 | 79.83 |
Minimum of Months | 104.46 | 0.00 |
Maximum of Months | 214.88 | 22.99 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 113.88 | 46.25 |
February | 124.16 | 53.33 |
March | 147.16 | 32.43 |
April | 186.91 | 0.00 |
May | 230.36 | 0.00 |
June | 251.20 | 0.00 |
July | 273.64 | 0.00 |
August | 263.16 | 0.00 |
September | 258.02 | 0.00 |
October | 241.06 | 0.00 |
November | 177.37 | 14.53 |
December | 122.95 | 66.68 |
Annual Sum or Average | 2389.87 | 213.22 |
Minimum of Months | 113.88 | 0.00 |
Maximum of Months | 273.64 | 66.68 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 72.93 | 82.16 |
February | 94.96 | 75.95 |
March | 129.41 | 60.01 |
April | 175.45 | 0.41 |
May | 229.05 | 0.00 |
June | 246.95 | 0.00 |
July | 270.34 | 0.00 |
August | 257.36 | 0.00 |
September | 236.32 | 0.00 |
October | 208.29 | 0.00 |
November | 142.54 | 20.74 |
December | 92.10 | 97.69 |
Annual Sum or Average | 2155.70 | 336.96 |
Minimum of Months | 72.93 | 0.00 |
Maximum of Months | 270.34 | 97.69 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 63.93 | 27.80 |
February | 77.64 | 32.48 |
March | 101.48 | 24.65 |
April | 137.06 | 0.07 |
May | 182.18 | 0.00 |
June | 202.12 | 0.00 |
July | 217.30 | 0.00 |
August | 207.07 | 0.00 |
September | 193.63 | 0.00 |
October | 171.11 | 0.00 |
November | 121.32 | 5.66 |
December | 77.97 | 40.47 |
Annual Sum or Average | 1752.82 | 131.13 |
Minimum of Months | 63.93 | 0.00 |
Maximum of Months | 217.30 | 40.47 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 73.16 | 62.31 |
February | 92.74 | 64.73 |
March | 124.79 | 36.82 |
April | 174.54 | 0.00 |
May | 230.12 | 0.00 |
June | 254.63 | 0.00 |
July | 275.45 | 0.00 |
August | 257.91 | 0.00 |
September | 241.80 | 0.00 |
October | 210.60 | 0.00 |
November | 142.22 | 17.42 |
December | 84.94 | 84.52 |
Annual Sum or Average | 2162.90 | 265.80 |
Minimum of Months | 73.16 | 0.00 |
Maximum of Months | 275.45 | 84.52 |
Report: HEATING AND COOLING LOADS
For: ATTIC
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 81.89 | 129.08 |
February | 105.09 | 116.93 |
March | 141.47 | 77.53 |
April | 198.15 | 0.94 |
May | 261.04 | 0.00 |
June | 286.05 | 0.00 |
July | 311.45 | 0.00 |
August | 291.36 | 0.00 |
September | 277.50 | 0.00 |
October | 243.42 | 0.00 |
November | 161.17 | 38.06 |
December | 94.67 | 153.24 |
Annual Sum or Average | 2453.26 | 515.77 |
Minimum of Months | 81.89 | 0.00 |
Maximum of Months | 311.45 | 153.24 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 113.12 | 107.31 |
February | 127.29 | 98.15 |
March | 154.18 | 70.53 |
April | 203.90 | 0.94 |
May | 260.73 | 0.00 |
June | 283.96 | 0.00 |
July | 310.05 | 0.00 |
August | 293.67 | 0.00 |
September | 285.57 | 0.00 |
October | 263.03 | 0.00 |
November | 187.76 | 33.46 |
December | 124.24 | 128.14 |
Annual Sum or Average | 2607.50 | 438.53 |
Minimum of Months | 113.12 | 0.00 |
Maximum of Months | 310.05 | 128.14 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 112.53 | 128.00 |
February | 129.52 | 114.54 |
March | 158.89 | 99.83 |
April | 205.03 | 1.77 |
May | 259.77 | 0.00 |
June | 276.26 | 0.00 |
July | 304.89 | 0.00 |
August | 293.16 | 0.00 |
September | 280.19 | 0.00 |
October | 260.62 | 0.00 |
November | 187.70 | 38.32 |
December | 131.21 | 138.43 |
Annual Sum or Average | 2599.77 | 520.89 |
Minimum of Months | 112.53 | 0.00 |
Maximum of Months | 304.89 | 138.43 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 71.83 | 76.64 |
February | 90.23 | 76.38 |
March | 118.91 | 57.96 |
April | 161.74 | 0.35 |
May | 214.13 | 0.00 |
June | 234.22 | 0.00 |
July | 253.92 | 0.00 |
August | 241.15 | 0.00 |
September | 230.20 | 0.00 |
October | 204.97 | 0.00 |
November | 140.39 | 20.32 |
December | 87.29 | 99.54 |
Annual Sum or Average | 2048.97 | 331.19 |
Minimum of Months | 71.83 | 0.00 |
Maximum of Months | 253.92 | 99.54 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 103.85 | 48.71 |
February | 112.84 | 58.66 |
March | 131.68 | 50.89 |
April | 167.51 | 0.34 |
May | 213.54 | 0.00 |
June | 231.75 | 0.00 |
July | 252.17 | 0.00 |
August | 243.36 | 0.00 |
September | 238.39 | 0.00 |
October | 225.21 | 0.00 |
November | 167.77 | 16.75 |
December | 118.04 | 70.24 |
Annual Sum or Average | 2206.11 | 245.58 |
Minimum of Months | 103.85 | 0.00 |
Maximum of Months | 252.17 | 70.24 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:06:37
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 82.17 | 160.09 |
February | 108.02 | 132.20 |
March | 146.89 | 112.07 |
April | 199.44 | 2.08 |
May | 260.32 | 0.00 |
June | 278.68 | 0.00 |
July | 306.62 | 0.00 |
August | 291.03 | 0.00 |
September | 272.28 | 0.00 |
October | 241.18 | 0.00 |
November | 161.85 | 43.19 |
December | 102.14 | 169.16 |
Annual Sum or Average | 2450.61 | 618.80 |
Minimum of Months | 82.17 | 0.00 |