Table of Contents

Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 16:15

Tabular Output Report in Format: HTML

Building: US+MF+CZ2AWH+elecres+slab+IECC_2018

Environment: ANNUAL ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880

Simulation Timestamp: 2024-06-27 16:15:55


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 675713.41 21.65 31.27
Net Site Energy 675713.41 21.65 31.27
Total Source Energy 2139984.38 68.57 99.03
Net Source Energy 2139984.38 68.57 99.03


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 31210.83
Net Conditioned Building Area 21609.96
Unconditioned Building Area 9600.87


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 33664.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 123435.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 41293.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 301503.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 38438.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 116773.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 675713.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 33664.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 123435.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 41293.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 17305.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 21133.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
  Water Heater 116773.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Unassigned 33664.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 123435.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 41293.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 301503.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 38438.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 116773.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 14.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.45
Other 13.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 31.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.45


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 10.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.00
Other 9.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 21.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.00


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 675713.414 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 675713.414 100.00
     
Total On-Site and Utility Electric Sources 675713.414 100.00
Total Electricity End Uses 675713.414 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 312247.30 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 312247.30 100.00
Total Water End Uses 312247.30 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 5.00
Time Setpoint Not Met During Occupied Cooling 16.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 3661.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Annual Thermal Resilience Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

HEATING AND COOLING LOADS

| BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

General

Value
Program Version and Build EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 16:15
RunPeriod ANNUAL
Weather File Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Latitude [deg] 27.85
Longitude [deg] -82.5
Elevation [ft] 26.25
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Above Ground Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94
Above Ground Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
BREEZEWAY 1798.16 No Yes 30553.25 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
ATTIC 7802.71 No Yes 52795.56 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
Total 31210.83     267088.19   16177.97 0.00 2126.74 2126.74 0.4307 866.97 2.0143
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.6220 600.28 2.9092
Unconditioned Total 9600.87     83348.81   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2] Tags
BREEZEWAY 1798.16 No Yes 1.00 BREEZEWAY GENERAL BREEZEWAY 0.0000 0.00 0.0000  
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.6220 600.28 2.9092  
ATTIC 7802.71 No Yes 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL LIVING_UNIT3_BACKROW_TOPFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT3_FRONTROW_TOPFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT1_FRONTROW_TOPFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL LIVING_UNIT2_BACKROW_TOPFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT2_FRONTROW_TOPFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL LIVING_UNIT1_BACKROW_TOPFLOOR 0.6220 600.28 2.9092  
Total 31210.83             0.4307 866.97 2.0143  
Conditioned Total 21609.96             0.6220 600.28 2.9092  
Unconditioned Total 9600.87             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [ft2] Conditioned Area [ft2] Unconditioned Area [ft2] Not Part of Total Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
GENERAL 31210.83 21609.96 9600.87 0.00 0.4307 866.97 2.0143
Total 31210.83 21609.96 9600.87 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 04-JAN-07:20 - - - - - - - - - - - 01-JAN-08:39
Heating 82.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 33.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 160.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 290.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 82.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 5.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 0.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 4.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 3.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 3.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 19.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 1.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 5.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13
  Water Heater 160.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 106614.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 390920.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 130776.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65251.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 954861.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 121736.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 369822.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2139984.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 4.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 18.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 6.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 3.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 44.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 17.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 99.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 3.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 12.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 30.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 3.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 11.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 68.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 369.37
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 207.36
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 277.67
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 350.77
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 194.47
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 263.15
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 402.26
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 229.85
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 303.51
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 382.98
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 217.50
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 286.26
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 330.44
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 342.13
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 455.12
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 281.52
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 283.05
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 451.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 369.37 369.37 369.37 369.37 369.37 369.37 1.00 1.00 369.37
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 207.36 207.36 207.36 207.36 207.36 207.36 1.00 1.00 207.36
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 277.67 277.67 277.67 277.67 277.67 277.67 1.00 1.00 277.67
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 350.77 350.77 350.77 350.77 350.77 350.77 1.00 1.00 350.77
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 194.47 194.47 194.47 194.47 194.47 194.47 1.00 1.00 194.47
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 263.15 263.15 263.15 263.15 263.15 263.15 1.00 1.00 263.15
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 402.26 402.26 402.26 402.26 402.26 402.26 1.00 1.00 402.26
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 229.85 229.85 229.85 229.85 229.85 229.85 1.00 1.00 229.85
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 303.51 303.51 303.51 303.51 303.51 303.51 1.00 1.00 303.51
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 382.98 382.98 382.98 382.98 382.98 382.98 1.00 1.00 382.98
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 217.50 217.50 217.50 217.50 217.50 217.50 1.00 1.00 217.50
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 286.26 286.26 286.26 286.26 286.26 286.26 1.00 1.00 286.26
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 455.12 455.12 455.12 455.12 455.12 455.12 1.00 1.00 455.12
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 283.05 283.05 283.05 283.05 283.05 283.05 1.00 1.00 283.05
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 342.13 342.13 342.13 342.13 342.13 342.13 1.00 1.00 342.13
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 451.99 451.99 451.99 451.99 451.99 451.99 1.00 1.00 451.99
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 281.52 281.52 281.52 281.52 281.52 281.52 1.00 1.00 281.52
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.44 330.44 330.44 330.44 330.44 330.44 1.00 1.00 330.44
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 369.37 1.23 0.701083
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 207.36 0.691062 0.701083
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 277.67 0.925383 0.701083
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 350.77 1.17 0.701083
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 194.47 0.648103 0.701083
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 263.15 0.876988 0.701083
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 402.26 1.34 0.701083
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 229.85 0.766016 0.701083
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 303.51 1.01 0.701083
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 382.98 1.28 0.701083
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 217.50 0.724856 0.701083
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 286.26 0.954012 0.701083
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 455.12 1.52 0.701083
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 283.05 0.943301 0.701083
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 342.13 1.14 0.701083
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 451.99 1.51 0.701083
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 281.52 0.938197 0.701083
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 330.44 1.10 0.701083
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 369.37 369.37 369.37 6533.43 1.23 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 207.36 207.36 207.36 5325.68 0.691062 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 277.67 277.67 277.67 6535.44 0.925383 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 350.77 350.77 350.77 6537.03 1.17 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 194.47 194.47 194.47 5326.69 0.648103 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 263.15 263.15 263.15 6533.84 0.876988 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 402.26 402.26 402.26 6083.29 1.34 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 229.85 229.85 229.85 4751.41 0.766016 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 303.51 303.51 303.51 6086.67 1.01 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 382.98 382.98 382.98 6085.83 1.28 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 217.50 217.50 217.50 4751.26 0.724856 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 286.26 286.26 286.26 6083.83 0.954012 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 455.12 455.12 455.12 7524.26 1.52 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 283.05 283.05 283.05 6180.60 0.943301 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 342.13 342.13 342.13 7527.72 1.14 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 451.99 451.99 451.99 7526.23 1.51 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 281.52 281.52 281.52 6180.58 0.938197 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 330.44 330.44 330.44 7525.74 1.10 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 369.37
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 207.36
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 277.67
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 350.77
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 194.47
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 263.15
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 402.26
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 229.85
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 303.51
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 382.98
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 217.50
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 286.26
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 455.12
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 283.05
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 342.13
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 451.99
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 281.52
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 330.44
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 7513.44
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 6124.53
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 7515.75
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 7517.58
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 6125.69
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 7513.91
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 6995.78
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 5464.12
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 6999.67
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 6998.70
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 5463.95
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 6996.40
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 8652.89
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 7107.69
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 8656.88
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR 8655.17
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR 7107.66
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR 8654.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 2.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 15354.00 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Version

Version ID
1 23.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No Yes Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40


Site:GroundTemperature:FCfactorMethod

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.72 60.73 59.63 60.58 65.98 72.03 77.72 81.82 83.03 81.10 76.44 70.56


Site:GroundTemperature:Shallow

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40


Site:GroundTemperature:Deep

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {ft} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Sensor Height Above Ground {ft} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 32.810 0.140 885.870 4.921 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {ft} Standard Pressure at Elevation {psi} Standard RhoAir at Elevation
1 Tampa-MacDill AFB FL USA TMY3 WMO#=747880 27.85 -82.52 -5.00 26.25 15. 1.2032


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{F} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} Fixed Default Water Mains Temperature{F}
1 Correlation NA 71.33 25.74 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 US+MF+CZ2AWH+elecres+slab+IECC_2018 0.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Algorithm {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
Space Heat Balance Sizing

Space Heat Balance Simulation

1 ThirdOrderBackwardDifference No No


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Gradient Coefficient {F/ft}
1 0.220 1213.970 0.003566


Material Details

Material Name ThermalResistance {m2-K/w} Roughness Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} Absorptance:Thermal Absorptance:Solar Absorptance:Visible
1 SHEATHING_CONSOL_LAYER 0.1351 Rough 0.0417 9.402E-002 42.764 0.280 0.9000 0.7000 0.7000
2 CEIL_CONSOL_LAYER 6.1981 Rough 1.2550 6.172E-002 2.618 0.185 0.9000 0.7000 0.7000
3 FLOOR_CONSOL_LAYER 1.9554E-005 Rough 0.0008 12.990 3.438 0.219 0.9000 0.7000 0.7000
4 BSMTWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
5 CRAWLWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
6 WALL_CONSOL_LAYER 1.5339 Rough 0.2917 5.796E-002 7.541 0.248 0.9000 0.7000 0.7000
7 VERY HIGH REFLECTIVITY SURFACE 2.1097E-006 Smooth 0.0016 237.000 168.680 0.216 0.9000 5.0000E-002 5.0000E-002
8 GYPSUMBOARD-5/16IN 5.0054E-002 Rough 0.0260 0.159 39.954 0.270 0.9000 0.4000 0.1000
9 COPPERPIPE 4.7506E-005 MediumRough 0.0625 401.000 140.026 0.200 0.9000 0.6500 0.6500
10 F08 METAL SURFACE 1.7668E-005 Smooth 0.0026 45.280 488.437 0.119 0.9000 0.7000 0.7000
11 CONCRETE_4IN 7.7356E-002 Rough 0.3330 1.312 140.014 0.111 0.9000 0.7000 0.7000
12 ASPHALT_SHINGLE 7.7448E-002 MediumRough 0.0208 8.186E-002 70.000 0.300 0.9000 0.7500 0.7000
13 WOOD_SHINGLE 0.1115 MediumSmooth 0.0417 0.114 26.600 0.390 0.9000 0.7000 0.7000
14 SLATE_SHINGLE 8.8061E-003 MediumSmooth 0.0417 1.442 100.000 0.300 0.9000 0.7000 0.7000
15 CEMENT_STUCCO 2.6422E-002 MediumSmooth 0.0625 0.721 116.464 0.210 0.9000 0.7000 0.7000
16 SYN_STUCCO 3.5237E-002 MediumSmooth 0.0100 8.650E-002 24.971 0.210 0.7000 0.7000 0.7000
17 DRYWALL_1/2IN 7.9331E-002 MediumSmooth 0.0417 0.160 50.000 0.260 0.9000 0.7000 0.7000
18 OSB_5/8IN 0.1365 MediumSmooth 0.0521 0.116 34.000 0.290 0.9000 0.7000 0.7000
19 OSB_7/16IN 9.5550E-002 MediumSmooth 0.0365 0.116 34.000 0.290 0.9000 0.7000 0.7000
20 BLOWN_R30 5.1614 MediumRough 0.6975 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
21 BLOWN_R30_TOP 2.8489 MediumRough 0.3849 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
22 PLYWOOD_3/4IN 0.1650 Rough 0.0625 0.115 34.003 0.161 0.9000 0.7000 0.7000
23 BATT_R19 7.3089 MediumRough 0.0833 3.475E-003 0.600 0.200 0.9000 0.7000 0.7000
24 LUMBER_2X4 0.7709 Rough 0.2920 0.115 32.003 0.183 0.9000 0.7000 0.7000
25 CARPET_N_PAD 0.4224 MediumSmooth 0.0833 6.013E-002 2.000 0.200 0.9000 0.7000 0.7000
26 BATT_R13 2.2936 MediumRough 0.2917 3.876E-002 0.600 0.200 0.9000 0.7000 0.7000
27 OSB_1/2IN 0.1092 MediumSmooth 0.0417 0.116 34.000 0.290 0.9000 0.7000 0.7000
28 SOIL_12IN 0.1761 Rough 1.0000 1.731 115.011 0.056 0.9000 0.7000 0.7000
29 DOOR_CONST 0.4402 Smooth 0.1040 7.201E-002 32.003 0.183 0.9000 0.7000 0.7000
30 GYP_BOARD_1/2IN 8.0130E-002 Rough 0.0417 0.159 39.954 0.270 0.9000 0.4000 0.1000
31 STD WOOD 6INCH 1.2500 MediumSmooth 0.4921 0.120 33.711 0.289 0.9000 0.7000 0.7000
32 PIPE INSULATION 0.3830 VeryRough 0.0417 3.317E-002 5.681 0.200 0.9000 0.5000 0.5000
33 MANF_WALL_AIRGAP 0.1200 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
34 BLDG_PAPER_FELT 1.0567E-002 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
35 R_HIGH 177.0000 MediumRough 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
36 CLEAR ACRYLIC PLASTIC 3.3333E-003 VerySmooth 0.0098 0.900 0.000 0.000 0.9000 0.0000 0.0000
37 DIFFUSING ACRYLIC PLASTIC 2.4444E-003 VerySmooth 0.0072 0.900 0.000 0.000 0.9000 0.0000 0.0000
38 INT_BLIND 0.0000 Rough 0.0000 0.000 0.000 0.000 0.0000 0.0000 0.0000
39 GLASS 0.2680 VerySmooth 0.1066 0.121 0.000 0.000 0.8400 0.0000 0.0000


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Other Side Coefficients

Name Combined convective/radiative film coefficient {Btu/h-ft2-F} User selected Constant Temperature {F} Coefficient modifying the constant temperature term Coefficient modifying the external dry bulb temperature term Coefficient modifying the ground temperature term Coefficient modifying the wind speed term {s/m} Coefficient modifying the zone air temperature term Constant Temperature Schedule Name Sinusoidal Variation Period of Sinusoidal Variation Previous Other Side Temperature Coefficient Minimum Other Side Temperature {F} Maximum Other Side Temperature {F}
1 SURFPROPOTHSDCOEFSLABAVERAGE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABAVERAGESURFACETEMP NO 24.000 0.000 N/A N/A
2 SURFPROPOTHSDCOEFSLABPERIMETER N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABPERIMETERTEMP NO 24.000 0.000 N/A N/A
3 SURFPROPOTHSDCOEFSLABCORE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABCORETEMP NO 24.000 0.000 N/A N/A


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{F}


Surface Convection Coefficient Lower Limit {Btu/h-ft2-F}


Surface Convection Coefficient Upper Limit {Btu/h-ft2-F}


1 CTF - ConductionTransferFunction 392. 0.02 176.1


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 60


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 20 171 48


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {ft} Origin Y-Coordinate {ft} Origin Z-Coordinate {ft} Centroid X-Coordinate {ft} Centroid Y-Coordinate {ft} Centroid Z-Coordinate {ft} Type Zone Multiplier Zone List Multiplier Minimum X {ft} Maximum X {ft} Minimum Y {ft} Maximum Y {ft} Minimum Z {ft} Maximum Z {ft} Ceiling Height {ft} Volume {ft3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {ft2} Exterior Gross Wall Area {ft2} Exterior Net Wall Area {ft2} Exterior Window Area {ft2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BREEZEWAY 0.0 0.00 0.00 0.00 59.94 32.55 13.26 1 1 1 0.00 119.89 30.05 35.04 0.49 25.99 17.00 30553.07 TARP DOE-2 1798.18 0.00 0.00 0.00 4 0 0 Yes
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 4.76 1 1 1 0.00 39.96 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 4.76 1 1 1 39.96 79.93 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 4.76 1 1 1 79.93 119.89 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 4.76 1 1 1 0.00 39.96 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 4.76 1 1 1 39.96 79.93 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 4.76 1 1 1 79.93 119.89 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 13.26 1 1 1 0.00 39.96 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 13.26 1 1 1 39.96 79.93 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 13.26 1 1 1 79.93 119.89 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 13.26 1 1 1 0.00 39.96 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 13.26 1 1 1 39.96 79.93 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 13.26 1 1 1 79.93 119.89 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
14 ATTIC 0.0 -134.9 51.61 0.00 59.94 32.55 29.56 1 1 1 0.00 119.89 0.00 65.10 25.99 39.54 6.76 52795.39 TARP DOE-2 7802.66 881.33 881.33 0.00 11 0 0 Yes
15 LIVING_UNIT3_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 21.75 1 1 1 79.93 119.89 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
16 LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 21.75 1 1 1 79.93 119.89 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
17 LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 21.75 1 1 1 0.00 39.96 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
18 LIVING_UNIT2_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 21.75 1 1 1 39.96 79.93 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
19 LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 21.75 1 1 1 39.96 79.93 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
20 LIVING_UNIT1_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 21.75 1 1 1 0.00 39.96 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {ft2} # Occupants Area per Occupant {ft2/person} Occupant per Area {person/ft2} Interior Lighting {Btu/h-ft2} Electric Load {Btu/h-ft2} Gas Load {Btu/h-ft2} Other Load {Btu/h-ft2} Hot Water Eq {Btu/h-ft2} Steam Equipment {Btu/h-ft2} Sum Loads per Area {Btu/h-ft2} Outdoor Controlled Baseboard Heat
1 BREEZEWAY 1798.18 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
14 ATTIC 7802.66 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
15 LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
16 LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
17 LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
18 LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
19 LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
20 LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Number of People {} People/Floor Area {person/ft2} Floor Area per person {ft2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
2 PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
3 PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
4 PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
5 PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
6 PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
7 PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
8 PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
9 PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
10 PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
11 PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
12 PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
13 PEOPLE_UNIT1_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
14 PEOPLE_UNIT2_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
15 PEOPLE_UNIT3_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
16 PEOPLE_UNIT1_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
17 PEOPLE_UNIT2_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
18 PEOPLE_UNIT3_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Lighting Level {Btu/h} Lights/Floor Area {Btu/h-ft2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {Btu/h} Nominal Maximum Lighting Level {Btu/h}
1 LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
2 LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
3 LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
4 LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
5 LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
6 LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
7 LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
8 LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
9 LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
10 LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
11 LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
12 LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
13 LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
14 LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
15 LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
16 LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
17 LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
18 LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
19 LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
20 LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
21 LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
22 LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
23 LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
24 LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
25 LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
26 LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
27 LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
28 LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
29 LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
30 LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
31 LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
32 LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
33 LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
34 LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
35 LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
36 LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 DISHWASHER1_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
2 REFRIGERATOR1_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
3 CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
4 ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
5 ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
6 TELEVISION1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
7 ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
8 IECC_ADJ1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
9 DISHWASHER2_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
10 REFRIGERATOR2_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
11 CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
12 ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
13 ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
14 TELEVISION2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
15 ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
16 IECC_ADJ2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
17 DISHWASHER3_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
18 REFRIGERATOR3_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
19 CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
20 ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
21 ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
22 TELEVISION3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
23 ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
24 IECC_ADJ3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
25 DISHWASHER1_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
26 REFRIGERATOR1_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
27 CLOTHESWASHER1_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
28 ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
29 ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
30 TELEVISION1_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
31 ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
32 IECC_ADJ1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
33 DISHWASHER2_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
34 REFRIGERATOR2_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
35 CLOTHESWASHER2_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
36 ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
37 ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
38 TELEVISION2_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
39 ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
40 IECC_ADJ2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
41 DISHWASHER3_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
42 REFRIGERATOR3_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
43 CLOTHESWASHER3_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
44 ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
45 ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
46 TELEVISION3_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
47 ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
48 IECC_ADJ3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
49 DISHWASHER1_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
50 REFRIGERATOR1_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
51 CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
52 ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
53 ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
54 TELEVISION1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
55 ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
56 IECC_ADJ1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
57 DISHWASHER2_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
58 REFRIGERATOR2_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
59 CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
60 ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
61 ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
62 TELEVISION2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
63 ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
64 IECC_ADJ2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
65 DISHWASHER3_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
66 REFRIGERATOR3_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
67 CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
68 ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
69 ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
70 TELEVISION3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
71 ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
72 IECC_ADJ3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
73 DISHWASHER1_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
74 REFRIGERATOR1_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
75 CLOTHESWASHER1_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
76 ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
77 ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
78 TELEVISION1_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
79 ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
80 IECC_ADJ1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
81 DISHWASHER2_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
82 REFRIGERATOR2_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
83 CLOTHESWASHER2_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
84 ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
85 ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
86 TELEVISION2_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
87 ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
88 IECC_ADJ2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
89 DISHWASHER3_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
90 REFRIGERATOR3_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
91 CLOTHESWASHER3_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
92 ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
93 ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
94 TELEVISION3_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
95 ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
96 IECC_ADJ3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
97 DISHWASHER1_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
98 REFRIGERATOR1_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
99 CLOTHESWASHER1_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
100 ELECTRIC_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
101 ELECTRIC_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
102 TELEVISION1_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
103 ELECTRIC_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
104 IECC_ADJ1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
105 DISHWASHER2_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
106 REFRIGERATOR2_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
107 CLOTHESWASHER2_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
108 ELECTRIC_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
109 ELECTRIC_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
110 TELEVISION2_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
111 ELECTRIC_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
112 IECC_ADJ2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
113 DISHWASHER3_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
114 REFRIGERATOR3_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
115 CLOTHESWASHER3_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
116 ELECTRIC_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
117 ELECTRIC_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
118 TELEVISION3_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
119 ELECTRIC_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
120 IECC_ADJ3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
121 DISHWASHER1_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
122 REFRIGERATOR1_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
123 CLOTHESWASHER1_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
124 ELECTRIC_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
125 ELECTRIC_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
126 TELEVISION1_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
127 ELECTRIC_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
128 IECC_ADJ1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
129 DISHWASHER2_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
130 REFRIGERATOR2_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
131 CLOTHESWASHER2_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
132 ELECTRIC_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
133 ELECTRIC_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
134 TELEVISION2_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
135 ELECTRIC_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
136 IECC_ADJ2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
137 DISHWASHER3_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
138 REFRIGERATOR3_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
139 CLOTHESWASHER3_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
140 ELECTRIC_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
141 ELECTRIC_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
142 TELEVISION3_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
143 ELECTRIC_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
144 IECC_ADJ3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736


Construction CTF

Construction Name Index #Layers #CTFs Time Step {Hours} ThermalConductance {Btu/h-ft2-F} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 EXTERIOR WALL 1 5 10 0.167 0.0937 0.700 0.900 0.700 0.700 MediumSmooth
2 CEILING-FLOOR-LAYER 3 1 5 0.167 0.228 0.900 0.900 0.700 0.700 Rough
3 EXTERIOR FLOOR 4 3 4 0.167 0.300 0.900 0.900 0.700 0.700 Rough
4 INTERIOR CEILING 6 2 10 0.167 0.0281 0.900 0.900 0.700 0.700 Rough
5 ATTIC FLOOR 7 2 10 0.167 0.0281 0.900 0.900 0.700 0.700 MediumSmooth
6 INTERIORWALL 9 3 5 0.167 0.597 0.900 0.900 0.700 0.700 MediumSmooth
7 EXTERIOR ROOF 11 2 4 0.167 0.943 0.900 0.900 0.750 0.700 MediumRough
8 EXTERIOR DOOR 14 1 5 0.167 0.400 0.900 0.900 0.700 0.700 Smooth
9 GABLE_END 16 5 6 0.167 0.428 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} ThermalResistance {m2-K/w}
1 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
2 SHEATHING_CONSOL_LAYER 0.0417 0.094 42.764 0.280 0.1351
3 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
4 WALL_CONSOL_LAYER 0.2917 0.058 7.541 0.248 1.534
5 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
6 LUMBER_2X4 0.2920 0.115 32.003 0.183 0.7709
7 FLOOR_CONSOL_LAYER 0.0010 12.990 3.438 0.219 0.1955E-04
8 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
9 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
10 CEIL_CONSOL_LAYER 1.2550 0.062 2.618 0.185 6.198
11 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
12 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
13 CEIL_CONSOL_LAYER 1.2550 0.062 2.618 0.185 6.198
14 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
15 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
16 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
17 ASPHALT_SHINGLE 0.0207 0.082 70.000 0.300 0.7745E-01
18 OSB_1/2IN 0.0417 0.116 34.000 0.290 0.1092
19 DOOR_CONST 0.1040 0.072 32.003 0.183 0.4402
20 CEMENT_STUCCO 0.0627 0.721 116.464 0.210 0.2642E-01
21 BLDG_PAPER_FELT 0.0000 0.000 0.000 0.000 0.1057E-01
22 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
23 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


CTF

Time Outside Cross Inside Flux (except final one)
1 10 0.53690791E-10 -0.14086767E-13 0.12185568E-09 -0.56142619E-15
2 9 -0.78969438E-07 0.37271083E-11 -0.12786746E-06 0.41607738E-10
3 8 0.15644920E-04 0.57233592E-08 0.24713380E-04 -0.42390053E-07
4 7 -0.11010334E-02 0.13458163E-05 -0.17770580E-02 0.73075693E-05
5 6 0.34256138E-01 0.71913801E-04 0.57800664E-01 -0.42770275E-03
6 5 -0.50970556 0.10561809E-02 -0.91414050 0.10365322E-01
7 4 3.8008141 0.46021679E-02 7.1669335 -0.11749215
8 3 -14.731927 0.58137860E-02 -27.604869 0.65172867
9 2 29.625503 0.18019171E-02 52.431474 -1.7640469
10 1 -28.806601 0.81323549E-04 -47.206921 2.1946319
11 0 10.602175 0.49952751E-07 16.084904  
12 5 -0.10726087E-01 0.44268190E-05 -0.10726087E-01 0.97389233E-03
13 4 0.31857203 0.80150166E-03 0.31857203 -0.30727185E-01
14 3 -2.8372473 0.12516450E-01 -2.8372473 0.30041224
15 2 9.6667056 0.33176537E-01 9.6667056 -1.1584571
16 1 -13.322214 0.15207483E-01 -13.322214 1.8397512
17 0 6.2472388 0.62260140E-03 6.2472388  
18 4 0.29631924E-13 -0.40788276E-14 0.60443234E-14 -0.77798347E-16
19 3 -0.11254351E-04 0.79669069E-06 -0.23145793E-05 0.39394231E-13
20 2 0.49771861 0.29587917E-01 0.78801895E-01 -0.76025120E-05
21 1 -8.3915550 0.80192706 -1.1535996 0.21114735
22 0 9.2367617 0.51139848 2.4177143  
23 10 0.25332408E-17 -0.22101509E-14 0.15157692E-08 0.28211904E-17
24 9 -0.31506112E-08 -0.26974675E-14 -0.81843868E-03 0.20118786E-08
25 8 0.42861811E-03 0.11354105E-09 0.39097097E-01 -0.27370296E-03
26 7 -0.11368907E-01 0.51842634E-07 -0.64553953 0.74324363E-02
27 6 0.12484615 0.25047115E-05 5.3130581 -0.83937451E-01
28 5 -0.73775399 0.27964547E-04 -24.889648 0.51283867
29 4 2.5553417 0.92755650E-04 70.144414 -1.8477174
30 3 -5.2989438 0.96002462E-04 -120.51707 4.0111012
31 2 6.4233118 0.27752742E-04 123.06129 -5.1209931
32 1 -4.1707712 0.15163054E-05 -68.409714 3.5199891
33 0 1.1151582 0.34288690E-08 15.905180  
34 10 0.15157692E-08 -0.22101509E-14 0.25332408E-17 0.28211904E-17
35 9 -0.81843868E-03 -0.26974675E-14 -0.31506112E-08 0.20118786E-08
36 8 0.39097097E-01 0.11354105E-09 0.42861811E-03 -0.27370296E-03
37 7 -0.64553953 0.51842634E-07 -0.11368907E-01 0.74324363E-02
38 6 5.3130581 0.25047115E-05 0.12484615 -0.83937451E-01
39 5 -24.889648 0.27964547E-04 -0.73775399 0.51283867
40 4 70.144414 0.92755650E-04 2.5553417 -1.8477174
41 3 -120.51707 0.96002462E-04 -5.2989438 4.0111012
42 2 123.06129 0.27752742E-04 6.4233118 -5.1209931
43 1 -68.409714 0.15163054E-05 -4.1707712 3.5199891
44 0 15.905180 0.34288690E-08 1.1151582  
45 5 -0.27590492E-07 0.65241430E-08 -0.27590492E-07 0.17331255E-13
46 4 0.68608714E-03 0.11323974E-03 0.68608714E-03 -0.15705033E-07
47 3 -0.21538511 0.37821720E-01 -0.21538511 0.25667047E-03
48 2 5.0173519 0.62258424 5.0173519 -0.50236511E-01
49 1 -19.904252 0.86481321 -19.904252 0.58144210
50 0 16.688993 0.62060609E-01 16.688993  
51 4 0.75441920E-10 0.23883683E-10 0.47514224E-10 -0.69373194E-20
52 3 -0.33730907E-03 0.89366797E-04 -0.22574866E-03 0.77828620E-10
53 2 0.58624422 0.18542418 0.49024360 -0.17301269E-03
54 1 -11.299243 2.8799011 -8.6239668 0.15905732
55 0 15.219762 1.4410112 12.640375  
56 5 -0.14496306E-10 0.10482472E-10 -0.14496306E-10 0.15719123E-14
57 4 0.30894845E-05 0.19631753E-05 0.30894845E-05 -0.20134377E-08
58 3 -0.87121421E-02 0.40108201E-02 -0.87121421E-02 0.45430501E-04
59 2 0.83777567 0.24056749 0.83777567 -0.18447090E-01
60 1 -6.4029859 0.89203954 -6.4029859 0.42787762
61 0 6.9152593 0.20472012 6.9152593  
62 6 0.97988530E-11 0.43917118E-12 0.24496810E-11 -0.34892153E-15
63 5 -0.75005310E-05 0.16499726E-06 -0.28271466E-05 0.19166609E-11
64 4 0.32354224E-01 0.66949565E-03 0.10283773E-01 -0.11111676E-05
65 3 -1.8201547 0.67148336E-01 -0.62076152 0.38788549E-02
66 2 21.173821 0.53241617 7.5279938 -0.97325542E-01
67 1 -64.420211 0.46601667 -21.697519 0.64629334
68 0 46.121323 0.20873329E-01 15.867130  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {Btu/h-ft2-F} Conductance (Before Adjusted) {Btu/h-ft2-F} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 EXTERIOR WINDOW 12 1 VerySmooth 0.400 0.400 1.000 0.217    
2 INTERIOR WINDOW 13 1 VerySmooth 0.400 0.400 1.000 0.217    
3 WINDOW_W_BLINDS 18 2 VerySmooth 0.400 0.400 1.000 0.207    
4 TDD DOME 22 1 VerySmooth 1.071 1.071 1.000 0.929    
5 TDD DIFFUSER 23 1 VerySmooth 1.077 1.077 1.000 0.906    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {ft} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLASS SpectralAverage   0.10662 0.12813 0.65606 0.65606 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.12126 1.00000 No
2 GLASS SpectralAverage   0.10662 0.12813 0.65606 0.65606 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.12126 1.00000 No
3 GLASS SpectralAverage   0.10662 0.12813 0.65606 0.65606 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.12126 1.00000 No
4 CLEAR ACRYLIC PLASTIC SpectralAverage   0.00984 0.92000 5.00000E-002 5.00000E-002 0.92000 5.00000E-002 5.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No
5 DIFFUSING ACRYLIC PLASTIC SpectralAverage   0.00722 0.90000 8.00000E-002 8.00000E-002 0.90000 8.00000E-002 8.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No


WindowMaterial:Blind

Material Name Slat Width {ft} Slat Separation {ft} Slat Thickness {ft} Slat Angle {deg} Slat Beam Solar Transmittance Slat Beam Solar Front Reflectance Blind To Glass Distance {ft}
1 INT_BLIND 0.0820 0.0615 0.0033 45.000 0.000 0.500 0.164


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000. SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {ft3} Maximum Capacity {Btu/h} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
2 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
3 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
4 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
5 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
6 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
7 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
8 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
9 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
10 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
11 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
12 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
13 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
14 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
15 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
16 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
17 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
18 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
2 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
3 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
4 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
5 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
6 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
7 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
8 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
9 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
11 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
12 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
13 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
14 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
15 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
16 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
17 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
18 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
19 ATTICVENT ALWAYS_AVAIL ATTIC 7802.66 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/person Area {ft3/min-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {psi} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{F}/Schedule Maximum Indoor Temperature{F}/Schedule Delta Temperature{F}/Schedule Minimum Outdoor Temperature{F}/Schedule Maximum Outdoor Temperature{F}/Schedule Maximum WindSpeed{ft/min}
1 VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
2 VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
3 VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
4 VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
5 VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
6 VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
7 VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
8 VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
9 VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
10 VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
11 VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
12 VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
13 VENTILATION_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
14 VENTILATION_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
15 VENTILATION_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
16 VENTILATION_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
17 VENTILATION_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
18 VENTILATION_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BREEZEWAY Mixing/Well-Stirred
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
14 ATTIC Mixing/Well-Stirred
15 LIVING_UNIT3_BACKROW_TOPFLOOR Mixing/Well-Stirred
16 LIVING_UNIT3_FRONTROW_TOPFLOOR Mixing/Well-Stirred
17 LIVING_UNIT1_FRONTROW_TOPFLOOR Mixing/Well-Stirred
18 LIVING_UNIT2_BACKROW_TOPFLOOR Mixing/Well-Stirred
19 LIVING_UNIT2_FRONTROW_TOPFLOOR Mixing/Well-Stirred
20 LIVING_UNIT1_BACKROW_TOPFLOOR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {Btu/h} User Des Load {Btu/h} Calc Des Air Flow Rate {ft3/min} User Des Air Flow Rate {ft3/min} Design Day Name Date/Time of Peak Temperature at Peak {F} Humidity Ratio at Peak {lbWater/lbDryAir} Floor Area {ft2} # Occupants Calc Outdoor Air Flow Rate {ft3/min} Calc DOAS Heat Addition Rate {Btu/h}
1 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Cooling 8666.94908 8666.94908 369.36436 369.36436 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 90.55521 0.01653 1200.55323 2.00000 44.99491 0.00000
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Heating 5063.48225 5063.48225 92.25084 92.25084 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Cooling 4865.04623 4865.04623 207.36184 207.36184 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 92.73560 0.01654 1200.55323 2.00000 44.99491 0.00000
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Heating 3837.86114 3837.86114 69.92203 69.92203 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Cooling 6515.50627 6515.50627 277.66946 277.66946 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:30:00 90.46040 0.01653 1200.55323 2.00000 44.99491 0.00000
6 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Heating 5065.51972 5065.51972 92.28791 92.28791 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
7 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Cooling 8230.40869 8230.40869 350.76267 350.76267 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 90.31820 0.01653 1200.55323 2.00000 44.99491 0.00000
8 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Heating 5067.13428 5067.13428 92.31736 92.31736 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
9 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Cooling 4563.30597 4563.30597 194.47159 194.47159 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 87.82970 0.01653 1200.55323 2.00000 44.99491 0.00000
10 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Heating 3838.88242 3838.88242 69.94046 69.94046 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
11 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Cooling 6174.90061 6174.90061 263.15675 263.15675 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 89.74940 0.01653 1200.55323 2.00000 44.99491 0.00000
12 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Heating 5063.89363 5063.89363 92.25825 92.25825 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
13 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Cooling 9439.05070 9439.05070 402.26690 402.26690 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 90.08119 0.01653 1200.55323 2.00000 44.99491 0.00000
14 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Heating 4606.64841 4606.64841 83.92901 83.92901 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
15 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Cooling 5393.58976 5393.58976 229.85167 229.85167 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 88.54070 0.01653 1200.55323 2.00000 44.99491 0.00000
16 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Heating 3255.06387 3255.06387 59.30487 59.30487 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
17 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Cooling 7121.37208 7121.37208 303.51691 303.51691 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 93.02000 0.01654 1200.55323 2.00000 44.99491 0.00000
18 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Heating 4610.07842 4610.07842 83.99151 83.99151 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
19 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Cooling 8986.54809 8986.54809 382.98724 382.98724 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 89.84421 0.01653 1200.55323 2.00000 44.99491 0.00000
20 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Heating 4609.22655 4609.22655 83.97605 83.97605 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
21 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Cooling 5103.82447 5103.82447 217.49997 217.49997 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 87.47420 0.01653 1200.55323 2.00000 44.99491 0.00000
22 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Heating 3254.91797 3254.91797 59.30211 59.30211 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
23 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Cooling 6717.31031 6717.31031 286.27115 286.27115 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:20:00 90.22339 0.01653 1200.55323 2.00000 44.99491 0.00000
24 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Heating 4607.19978 4607.19978 83.93918 83.93918 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
25 LIVING_UNIT3_BACKROW_TOPFLOOR Cooling 7752.45829 7752.45829 330.44487 330.44487 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 92.45120 0.01654 1200.55323 2.00000 44.99491 0.00000
26 LIVING_UNIT3_BACKROW_TOPFLOOR Heating 6070.46707 6070.46707 110.59660 110.59660 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
27 LIVING_UNIT3_FRONTROW_TOPFLOOR Cooling 8026.72249 8026.72249 342.11860 342.11860 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 92.87780 0.01654 1200.55323 2.00000 44.99491 0.00000
28 LIVING_UNIT3_FRONTROW_TOPFLOOR Heating 6072.47581 6072.47581 110.63304 110.63304 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
29 LIVING_UNIT1_FRONTROW_TOPFLOOR Cooling 10678.92660 10678.92660 455.12706 455.12706 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 90.08119 0.01653 1200.55323 2.00000 44.99491 0.00000
30 LIVING_UNIT1_FRONTROW_TOPFLOOR Heating 6068.96128 6068.96128 110.56905 110.56905 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
31 LIVING_UNIT2_BACKROW_TOPFLOOR Cooling 6605.76476 6605.76476 281.52539 281.52539 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 88.18520 0.01653 1200.55323 2.00000 44.99491 0.00000
32 LIVING_UNIT2_BACKROW_TOPFLOOR Heating 4705.40230 4705.40230 85.72732 85.72732 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
33 LIVING_UNIT2_FRONTROW_TOPFLOOR Cooling 6641.64392 6641.64392 283.05081 283.05081 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 88.54070 0.01653 1200.55323 2.00000 44.99491 0.00000
34 LIVING_UNIT2_FRONTROW_TOPFLOOR Heating 4705.42857 4705.42857 85.72796 85.72796 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000
35 LIVING_UNIT1_BACKROW_TOPFLOOR Cooling 10605.52410 10605.52410 451.99147 451.99147 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 89.84421 0.01653 1200.55323 2.00000 44.99491 0.00000
36 LIVING_UNIT1_BACKROW_TOPFLOOR Heating 6070.96737 6070.96737 110.60571 110.60571 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 40.28000 0.00526 1200.55323 2.00000 44.99491 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [ft3/min] User Des Air Flow Rate [ft3/min] Design Day Name Date/Time of Peak
1 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Cooling Sensible 2727.38 369.36436 369.36436 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
2 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Heating Sensible 1914.84 92.25084 92.25084 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
3 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Cooling Sensible 1659.47 207.36184 207.36184 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
4 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Heating Sensible 1560.87 69.92203 69.92203 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
5 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Cooling Sensible 2104.09 277.66946 277.66946 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
6 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Heating Sensible 1915.43 92.28791 92.28791 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
7 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Cooling Sensible 2597.81 350.76267 350.76267 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
8 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Heating Sensible 1915.89 92.31736 92.31736 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
9 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Cooling Sensible 1502.22 194.47159 194.47159 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Heating Sensible 1561.16 69.94046 69.94046 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
11 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Cooling Sensible 1995.48 263.15675 263.15675 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
12 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Heating Sensible 1914.96 92.25825 92.25825 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
13 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Cooling Sensible 2943.81 402.26690 402.26690 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
14 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Heating Sensible 1782.91 83.92901 83.92901 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
15 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Cooling Sensible 1752.37 229.85167 229.85167 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
16 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Heating Sensible 1392.56 59.30487 59.30487 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
17 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Cooling Sensible 2315.76 303.51691 303.51691 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
18 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Heating Sensible 1783.90 83.99151 83.99151 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
19 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Cooling Sensible 2809.62 382.98724 382.98724 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
20 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Heating Sensible 1783.65 83.97605 83.97605 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
21 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Cooling Sensible 1653.39 217.49997 217.49997 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
22 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Heating Sensible 1392.52 59.30211 59.30211 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
23 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Cooling Sensible 2159.03 286.27115 286.27115 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
24 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Heating Sensible 1783.07 83.93918 83.93918 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
25 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Cooling Sensible 3302.24 455.12706 455.12706 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
26 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Heating Sensible 2205.23 110.56905 110.56905 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
27 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Cooling Sensible 2113.17 283.05081 283.05081 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
28 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Heating Sensible 1811.43 85.72796 85.72796 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
29 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Cooling Sensible 2575.47 342.11860 342.11860 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
30 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Heating Sensible 2206.25 110.63304 110.63304 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
31 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Cooling Sensible 3277.64 451.99147 451.99147 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
32 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Heating Sensible 2205.81 110.60571 110.60571 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
33 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Cooling Sensible 2097.72 281.52539 281.52539 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
34 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Heating Sensible 1811.42 85.72732 85.72732 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
35 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Cooling Sensible 2490.11 330.44487 330.44487 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
36 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Heating Sensible 2205.67 110.59660 110.59660 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 369.36436
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 207.36184
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 277.66946
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 350.76267
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 194.47159
6 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 263.15675
7 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 402.26690
8 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 229.85167
9 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 303.51691
10 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 382.98724
11 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 217.49997
12 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 286.27115
13 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 330.44487
14 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 342.11860
15 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 455.12706
16 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 281.52539
17 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 283.05081
18 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 451.99147
19 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 369.36436
20 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 369.36436
21 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 369.36436
22 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 369.36436
23 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 369.36436
24 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 369.36436
25 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
26 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
27 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 207.36184
28 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 207.36184
29 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 207.36184
30 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 207.36184
31 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 207.36184
32 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 207.36184
33 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
34 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
35 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 277.66946
36 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 277.66946
37 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 277.66946
38 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 277.66946
39 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 277.66946
40 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 277.66946
41 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
42 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
43 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 350.76267
44 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 350.76267
45 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 350.76267
46 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 350.76267
47 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 350.76267
48 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 350.76267
49 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
50 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
51 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 194.47159
52 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 194.47159
53 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 194.47159
54 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 194.47159
55 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 194.47159
56 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 194.47159
57 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
58 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
59 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 263.15675
60 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 263.15675
61 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 263.15675
62 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 263.15675
63 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 263.15675
64 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 263.15675
65 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
66 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
67 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 402.26690
68 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 402.26690
69 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 402.26690
70 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 402.26690
71 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 402.26690
72 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 402.26690
73 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
74 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
75 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 229.85167
76 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 229.85167
77 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 229.85167
78 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 229.85167
79 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 229.85167
80 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 229.85167
81 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
82 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
83 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 303.51691
84 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 303.51691
85 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 303.51691
86 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 303.51691
87 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 303.51691
88 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 303.51691
89 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
90 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
91 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 382.98724
92 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 382.98724
93 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 382.98724
94 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 382.98724
95 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 382.98724
96 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 382.98724
97 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
98 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
99 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 217.49997
100 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 217.49997
101 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 217.49997
102 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 217.49997
103 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 217.49997
104 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 217.49997
105 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
106 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
107 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 286.27115
108 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 286.27115
109 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 286.27115
110 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 286.27115
111 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 286.27115
112 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 286.27115
113 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
114 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
115 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 455.12706
116 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 455.12706
117 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 455.12706
118 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 455.12706
119 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 455.12706
120 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 455.12706
121 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
122 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
123 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 283.05081
124 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 283.05081
125 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 283.05081
126 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 283.05081
127 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 283.05081
128 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 283.05081
129 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
130 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
131 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 342.11860
132 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 342.11860
133 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 342.11860
134 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 342.11860
135 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 342.11860
136 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 342.11860
137 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
138 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
139 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 451.99147
140 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 451.99147
141 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 451.99147
142 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 451.99147
143 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 451.99147
144 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 451.99147
145 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
146 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
147 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 281.52539
148 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 281.52539
149 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 281.52539
150 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 281.52539
151 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 281.52539
152 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 281.52539
153 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
154 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
155 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 330.44487
156 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 330.44487
157 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 330.44487
158 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 330.44487
159 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 330.44487
160 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 330.44487
161 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
162 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
163 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 369.36436
164 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 207.36184
165 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 277.66946
166 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 350.76267
167 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 194.47159
168 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 263.15675
169 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 402.26690
170 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 229.85167
171 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 303.51691
172 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 382.98724
173 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 217.49997
174 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 286.27115
175 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 455.12706
176 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 283.05081
177 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 342.11860
178 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 451.99147
179 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 281.52539
180 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 330.44487
181 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 369.36436
182 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.23098
183 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
184 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 369.36436
185 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 369.36436
186 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 369.36436
187 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 6533.43036
188 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.23098
189 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
190 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 369.36436
191 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7513.44493
192 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 207.36184
193 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.69106
194 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
195 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 207.36184
196 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 207.36184
197 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 207.36184
198 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 5325.68093
199 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.69106
200 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
201 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 207.36184
202 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 6124.53307
203 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 277.66946
204 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.92538
205 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
206 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 277.66946
207 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 277.66946
208 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 277.66946
209 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 6535.43812
210 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.92538
211 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
212 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 277.66946
213 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7515.75386
214 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 350.76267
215 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.16898
216 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
217 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 350.76267
218 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 350.76267
219 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 350.76267
220 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 6537.02917
221 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.16898
222 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
223 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 350.76267
224 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7517.58355
225 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 194.47159
226 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.64810
227 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
228 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 194.47159
229 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 194.47159
230 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 194.47159
231 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 5326.68734
232 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.64810
233 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
234 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 194.47159
235 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 6125.69042
236 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 263.15675
237 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.87699
238 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
239 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 263.15675
240 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 263.15675
241 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 263.15675
242 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 6533.83574
243 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.87699
244 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
245 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 263.15675
246 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7513.91111
247 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 402.26690
248 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.34060
249 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
250 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 402.26690
251 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 402.26690
252 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 402.26690
253 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 6083.28674
254 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.34060
255 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
256 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 402.26690
257 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 6995.77977
258 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 229.85167
259 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.76602
260 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
261 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 229.85167
262 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 229.85167
263 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 229.85167
264 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 4751.40834
265 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.76602
266 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
267 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 229.85167
268 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 5464.11959
269 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 303.51691
270 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.01149
271 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
272 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 303.51691
273 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 303.51691
274 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 303.51691
275 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 6086.66673
276 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.01149
277 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
278 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 303.51691
279 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 6999.66675
280 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 382.98724
281 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.27633
282 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
283 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 382.98724
284 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 382.98724
285 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 382.98724
286 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 6085.82731
287 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.27633
288 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
289 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 382.98724
290 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 6998.70139
291 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 217.49997
292 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.72486
293 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
294 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 217.49997
295 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 217.49997
296 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 217.49997
297 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 4751.26459
298 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.72486
299 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
300 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 217.49997
301 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 5463.95428
302 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 286.27115
303 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.95401
304 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
305 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 286.27115
306 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 286.27115
307 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 286.27115
308 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 6083.83006
309 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.95401
310 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
311 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 286.27115
312 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 6996.40457
313 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 455.12706
314 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.51675
315 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
316 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 455.12706
317 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 455.12706
318 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 455.12706
319 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 7524.25588
320 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.51675
321 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
322 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 455.12706
323 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 8652.89423
324 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 283.05081
325 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.94330
326 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
327 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 283.05081
328 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 283.05081
329 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 283.05081
330 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 6180.60284
331 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.94330
332 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
333 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 283.05081
334 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 7107.69326
335 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 342.11860
336 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.14019
337 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
338 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 342.11860
339 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 342.11860
340 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 342.11860
341 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 7527.71920
342 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.14019
343 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
344 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 342.11860
345 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 8656.87706
346 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 451.99147
347 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.50633
348 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
349 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 451.99147
350 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 451.99147
351 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 451.99147
352 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 7526.23273
353 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.50633
354 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
355 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 451.99147
356 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 8655.16762
357 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 281.52539
358 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.93820
359 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
360 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 281.52539
361 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 281.52539
362 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 281.52539
363 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 6180.57695
364 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.93820
365 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
366 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 281.52539
367 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 7107.66348
368 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 330.44487
369 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.10123
370 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
371 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 330.44487
372 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 330.44487
373 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 330.44487
374 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 7525.73969
375 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.10123
376 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
377 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 330.44487
378 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 8654.60064
379 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
380 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
381 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
382 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
383 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
384 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
385 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
386 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
387 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
388 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
389 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
390 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
391 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
392 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
393 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
394 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
395 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
396 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
397 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
398 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
399 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
400 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
401 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
402 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
403 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
404 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
405 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
406 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
407 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
408 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
409 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
410 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
411 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
412 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
413 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
414 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
415 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
416 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
417 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
418 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
419 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
420 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
421 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
422 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
423 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
424 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
425 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
426 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
427 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
428 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
429 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
430 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
431 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
432 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
433 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
434 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
435 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
436 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
437 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
438 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
439 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
440 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
441 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
442 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
443 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
444 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
445 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
446 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
447 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
448 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
449 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
450 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
451 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
452 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
453 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
454 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
455 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
456 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
457 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
458 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
459 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
460 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
461 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
462 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
463 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
464 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
465 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
466 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
467 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
468 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {ton} Standard Rated Net COP {Btuh/Btuh} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.2 3.68 12.55 13.31 12.80 13.19
2 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.2 3.56 12.16 12.89 12.74 -99999.
3 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.7 3.68 12.55 13.31 12.80 13.19
4 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.7 3.56 12.16 12.89 12.74 -99999.
5 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 0.9 3.68 12.55 13.31 12.80 13.19
6 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 0.9 3.56 12.16 12.89 12.74 -99999.
7 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.1 3.68 12.55 13.31 12.80 13.19
8 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.1 3.56 12.16 12.89 12.74 -99999.
9 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.6 3.68 12.55 13.31 12.80 13.19
10 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.6 3.56 12.16 12.89 12.74 -99999.
11 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 0.8 3.68 12.55 13.31 12.80 13.19
12 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 0.8 3.56 12.16 12.89 12.74 -99999.
13 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.3 3.68 12.55 13.31 12.80 13.19
14 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.3 3.56 12.16 12.89 12.74 -99999.
15 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.7 3.68 12.55 13.31 12.80 13.19
16 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.7 3.56 12.16 12.89 12.74 -99999.
17 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 1.0 3.68 12.55 13.31 12.80 13.19
18 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 1.0 3.56 12.16 12.89 12.74 -99999.
19 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.2 3.68 12.55 13.31 12.80 13.19
20 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.2 3.56 12.16 12.89 12.74 -99999.
21 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.7 3.68 12.55 13.31 12.80 13.19
22 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.7 3.56 12.16 12.89 12.74 -99999.
23 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 0.9 3.68 12.55 13.31 12.80 13.19
24 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 0.9 3.56 12.16 12.89 12.74 -99999.
25 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.5 3.68 12.55 13.31 12.80 13.19
26 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.5 3.56 12.16 12.89 12.74 -99999.
27 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 0.9 3.68 12.55 13.31 12.80 13.19
28 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 0.9 3.56 12.16 12.89 12.74 -99999.
29 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 1.1 3.68 12.55 13.31 12.80 13.19
30 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 1.1 3.56 12.16 12.89 12.74 -99999.
31 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.5 3.68 12.55 13.31 12.80 13.19
32 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.4 3.56 12.16 12.89 12.74 -99999.
33 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 0.9 3.68 12.55 13.31 12.80 13.19
34 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 0.9 3.56 12.16 12.89 12.74 -99999.
35 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 1.1 3.68 12.55 13.31 12.80 13.19
36 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 1.1 3.56 12.16 12.89 12.74 -99999.


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB SizingPeriod:DesignDay 01/21 01/21 WinterDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
2 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB SizingPeriod:DesignDay 08/21 08/21 SummerDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
3 ANNUAL WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No SizingPeriod:DesignDay    
2 No SizingPeriod:DesignDay    
3 No      


Environment:WarmupDays

NumberofWarmupDays
1 6
2 6
3 6


Environment:Design Day Data

Max Dry-Bulb Temp {F} Temp Range {dC} Temp Range Ind Type Hum Ind Type Hum Ind Value at Max Temp Hum Ind Units Pressure {psi} Wind Direction {deg CW from N} Wind Speed {ft/min} Clearness Rain Snow
1 40.28 0.00 DefaultMultipliers Wetbulb 4.60 {C} 15. 10 492.2 0.00 No No
2 93.02 7.90 DefaultMultipliers Wetbulb 25.10 {C} 15. 270 610.3 0.00 No No


Environment:Design Day Misc

DayOfYear ASHRAE A Coeff ASHRAE B Coeff ASHRAE C Coeff Solar Constant-Annual Variation Eq of Time {minutes} Solar Declination Angle {deg} Solar Model
1 21 1229.0 0.1415 5.7310E-002 1.0 -11.15 -20. ASHRAEClearSky
2 233 1106.3 0.2000 0.1216 1.0 -3.33 12.4 ASHRAETau


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaF} Std Dev Warmup Temperature Difference {deltaF} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {Btu/h} Std Dev Warmup Load Difference {Btu/h} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BREEZEWAY SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000002641 0.000001415 Pass Pass 0.000000000 0.000000000 Pass Pass
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.017378875 0.034198485 Pass Pass
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.023257382 0.046203105 Pass Pass
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.017372326 0.034184800 Pass Pass
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.017366423 0.034172770 Pass Pass
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.023252293 0.046191086 Pass Pass
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.017378710 0.034197560 Pass Pass
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.020285467 0.037137551 Pass Pass
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.029959273 0.055557311 Pass Pass
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.020268503 0.037105431 Pass Pass
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.020272640 0.037113414 Pass Pass
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.029959791 0.055559127 Pass Pass
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.020281741 0.037131038 Pass Pass
14 ATTIC SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000104992 0.000092032 Pass Pass 0.000000000 0.000000000 Pass Pass
15 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015093619 0.026183264 Pass Pass
16 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015088968 0.026174769 Pass Pass
17 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015099121 0.026192463 Pass Pass
18 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.019961324 0.034638995 Pass Pass
19 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.019962188 0.034640083 Pass Pass
20 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015093225 0.026182207 Pass Pass
21 BREEZEWAY SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.332835640 0.209743347 Pass Pass 0.000000000 0.000000000 Pass Pass
22 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000038197 0.000182715 Pass Pass 0.078016901 0.039196695 Pass Pass
23 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000030348 0.000110543 Pass Pass 0.056623954 0.038457760 Pass Pass
24 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000036268 0.000106952 Pass Pass 0.063908625 0.062099325 Pass Pass
25 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000041661 0.000196823 Pass Pass 0.075910145 0.038357741 Pass Pass
26 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000029259 0.000105875 Pass Pass 0.051575535 0.038513452 Pass Pass
27 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000038277 0.000118312 Pass Pass 0.061483284 0.063424767 Pass Pass
28 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000046930 0.000233462 Pass Pass 0.072554296 0.032440252 Pass Pass
29 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000035615 0.000136144 Pass Pass 0.050537417 0.034687419 Pass Pass
30 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000039641 0.000127463 Pass Pass 0.058787620 0.054829829 Pass Pass
31 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000044182 0.000221228 Pass Pass 0.070682025 0.031004345 Pass Pass
32 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000034272 0.000132046 Pass Pass 0.046306451 0.033854136 Pass Pass
33 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000048402 0.000171413 Pass Pass 0.056316683 0.055882637 Pass Pass
34 ATTIC SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.482405918 0.418382799 Pass Pass 0.000000000 0.000000000 Pass Pass
35 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000051674 0.000179234 Pass Pass 0.058977705 0.053520248 Pass Pass
36 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000053936 0.000187882 Pass Pass 0.059924087 0.053160444 Pass Pass
37 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000051100 0.000252054 Pass Pass 0.074446966 0.030570805 Pass Pass
38 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000042771 0.000155550 Pass Pass 0.054352195 0.031407155 Pass Pass
39 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000042733 0.000165439 Pass Pass 0.054649112 0.033748488 Pass Pass
40 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 0.000050520 0.000251068 Pass Pass 0.074320882 0.029660690 Pass Pass
41 BREEZEWAY RunPeriod: ANNUAL 0.295783973 0.228520351 Pass Pass 0.000000000 0.000000000 Pass Pass
42 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.041120533 0.064509443 Pass Pass 0.187410959 0.455656644 Pass Pass
43 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.030201599 0.049790765 Pass Pass 0.228904055 0.840327817 Pass Pass
44 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.041405330 0.079445058 Pass Pass 0.175497411 0.415353015 Pass Pass
45 LIVING_UNIT1_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.044614164 0.058806043 Pass Pass 0.202017619 0.509250846 Pass Pass
46 LIVING_UNIT2_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.034135750 0.046425305 Pass Pass 0.134834130 0.394545703 Pass Pass
47 LIVING_UNIT3_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.041938471 0.066700783 Pass Pass 0.198880097 0.602846491 Pass Pass
48 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.016634491 0.036632098 Pass Pass 0.238547468 0.508249070 Pass Pass
49 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.003435811 0.008876504 Pass Pass 0.209568542 0.383334975 Pass Pass
50 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.016635130 0.039756779 Pass Pass 0.207962256 0.440164868 Pass Pass
51 LIVING_UNIT1_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.020687285 0.037343223 Pass Pass 0.221688060 0.485710097 Pass Pass
52 LIVING_UNIT2_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.007605070 0.017310445 Pass Pass 0.197233261 0.396902579 Pass Pass
53 LIVING_UNIT3_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.018171223 0.040982890 Pass Pass 0.179652437 0.368108485 Pass Pass
54 ATTIC RunPeriod: ANNUAL 0.500624691 0.488689218 Pass Pass 0.000000000 0.000000000 Pass Pass
55 LIVING_UNIT3_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.023241911 0.049368460 Pass Pass 0.204996379 0.487149480 Pass Pass
56 LIVING_UNIT3_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.021906753 0.051567681 Pass Pass 0.226071147 0.582568008 Pass Pass
57 LIVING_UNIT1_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.022116955 0.042063956 Pass Pass 0.227214763 0.512793317 Pass Pass
58 LIVING_UNIT2_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.013289070 0.027482101 Pass Pass 0.213078579 0.429613488 Pass Pass
59 LIVING_UNIT2_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.009239043 0.025062554 Pass Pass 0.244739449 0.528266864 Pass Pass
60 LIVING_UNIT1_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.026232016 0.046428848 Pass Pass 0.205722284 0.441696090 Pass Pass



Table of Contents

Report: Annual Heat Emissions Report

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Annual Heat Emissions Summary

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kBtu] 2613854.37 86796.21 -57745.4 0.00 686224.82 3329142.16



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Heat Index Hours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
BREEZEWAY 6043.33 2151.50 565.17 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 5662.33 1091.00 961.00 983.33 62.33
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 5662.33 0.00 0.00 0.00 0.00
Max 8760.00 2151.50 961.00 983.33 62.33
Average 8469.28 162.13 76.31 49.17 3.12
Sum 169385.67 3242.50 1526.17 983.33 62.33


Heat Index OccupantHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12062.38 0.00 0.00 0.00 0.00
Average 10856.14 0.00 0.00 0.00 0.00
Sum 217122.86 0.00 0.00 0.00 0.00


Heat Index OccupiedHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 7884.00 0.00 0.00 0.00 0.00
Sum 157680.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BREEZEWAY 7298.83 1456.00 5.17 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5927.17 2832.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5469.00 3291.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6158.00 2602.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5773.83 2986.17 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5103.50 3656.50 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5954.83 2805.17 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7235.83 1524.17 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7263.17 1496.83 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7431.00 1329.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7153.83 1606.17 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7132.50 1627.50 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7375.00 1385.00 0.00 0.00 0.00
ATTIC 3667.33 3385.00 783.00 640.50 284.17
LIVING_UNIT3_BACKROW_TOPFLOOR 7198.67 1561.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7233.00 1527.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 6982.33 1777.67 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6839.83 1920.17 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6945.33 1814.67 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 6918.50 1841.50 0.00 0.00 0.00
Min 3667.33 1329.00 0.00 0.00 0.00
Max 7431.00 3656.50 783.00 640.50 284.17
Average 6553.08 2121.28 39.41 32.02 14.21
Sum 131061.50 42425.67 788.17 640.50 284.17


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 7606.01 4456.37 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7129.34 4933.04 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7558.35 4504.03 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7459.44 4602.94 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 6735.61 5326.77 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7318.08 4744.30 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9631.42 2430.96 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 9816.07 2246.31 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9719.29 2343.09 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9555.45 2506.93 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 9694.81 2367.57 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9645.03 2417.35 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 9384.50 2677.88 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 9417.57 2644.81 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9300.37 2762.01 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 9318.41 2743.97 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 9398.94 2663.44 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9246.09 2816.29 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 9816.07 5326.77 0.00 0.00 0.00
Average 7896.74 2959.40 0.00 0.00 0.00
Sum 157934.80 59188.06 0.00 0.00 0.00


Humidex OccupiedHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5927.17 2832.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5469.00 3291.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6158.00 2602.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5773.83 2986.17 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5103.50 3656.50 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5954.83 2805.17 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7235.83 1524.17 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7263.17 1496.83 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7431.00 1329.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7153.83 1606.17 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7132.50 1627.50 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7375.00 1385.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7198.67 1561.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7233.00 1527.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 6982.33 1777.67 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6839.83 1920.17 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6945.33 1814.67 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 6918.50 1841.50 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 7431.00 3656.50 0.00 0.00 0.00
Average 6004.77 1879.23 0.00 0.00 0.00
Sum 120095.33 37584.67 0.00 0.00 0.00


Hours of Safety for Cold Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7884.00 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Hours of Safety for Heat Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7884.00 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Unmet Degree-Hours

Cooling Setpoint Unmet Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] Heating Setpoint Unmet Degree-Hours [°F·hr] Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Heating Setpoint Unmet Occupied Degree-Hours [°C·hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.33 0.27 0.33 1.70 2.88 1.70
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 11.39 10.92 11.39 0.28 0.48 0.28
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6.22 3.20 6.22 1.76 3.37 1.76
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.29 0.26 0.29 2.73 3.95 2.73
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 7.88 11.48 7.88 0.82 1.06 0.82
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2.98 1.67 2.98 2.05 3.93 2.05
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.34 0.29 0.34 0.02 0.03 0.02
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 3.87 3.38 3.87 0.01 0.01 0.01
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3.24 1.77 3.24 0.10 0.18 0.10
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.30 0.29 0.30 0.18 0.23 0.18
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.76 2.64 1.76 0.01 0.02 0.01
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.20 0.84 1.20 0.17 0.30 0.17
ATTIC 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 2.02 1.32 2.02 2.61 4.77 2.61
LIVING_UNIT3_FRONTROW_TOPFLOOR 3.36 1.93 3.36 2.12 3.99 2.12
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.38 0.32 0.38 2.16 3.45 2.16
LIVING_UNIT2_BACKROW_TOPFLOOR 1.11 1.40 1.11 1.37 1.63 1.37
LIVING_UNIT2_FRONTROW_TOPFLOOR 2.25 2.14 2.25 0.58 0.91 0.58
LIVING_UNIT1_BACKROW_TOPFLOOR 0.35 0.32 0.35 3.46 4.54 3.46
Min 0.00 0.00 0.00 0.00 0.00 0.00
Max 11.39 11.48 11.39 3.46 4.77 3.46
Average 2.46 2.22 2.46 1.11 1.79 1.11
Sum 49.26 44.43 49.26 22.13 35.73 22.13


Discomfort-weighted Exceedance OccupantHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00


Discomfort-weighted Exceedance OccupiedHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 40.28 0.00 40.28 Wetbulb [F] 492.15 10.00
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 93.02 14.22 77.18 Wetbulb [F] 610.27 270.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [in] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [in] Monthly Total Roof Irrigation Depth [in] Monthly Total Rain Collection Volume [ft3]
Jan 2.60 12      
Feb 2.60 22      
Mar 4.96 32      
Apr 8.11 19      
May 5.67 46      
Jun 3.90 30      
Jul 7.56 52      
Aug 9.45 34      
Sep 12.20 44      
Oct 1.34 10      
Nov 2.48 12      
Dec 1.38 24      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BREEZEWAYROOF INTERIOR CEILING 0.30 0.027 0.028 599.39 599.39 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
iz-BREEZEWAYROOF ATTIC FLOOR 0.30 0.027 0.028 599.39 599.39 0.00 180.00  
iz-CEILING_UNIT3_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  


Exterior Fenestration

Construction Frame and Divider Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.400 0.217 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.400 0.217 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.400 0.217 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.400 0.217 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.400 0.217 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.400 0.217 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.400 0.217 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.400 0.217 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.400 0.217 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.400 0.217 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.400 0.217 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.400 0.217 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.400 0.217 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average             2126.74 0.400 0.217 0.883                      
North Total or Average             531.68 0.400 0.217 0.883                      
Non-North Total or Average             1595.05 0.400 0.217 0.883                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.88 0.47 1.00 0.99 0.99
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.88 0.47 1.00 0.99 0.99
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.88 0.47 1.00 0.99 0.99
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 0.97 0.00 0.99 0.96 0.00 1.00 0.97 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.96 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.96 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 0.97 0.00 0.99 0.96 0.00 1.00 0.97 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.96 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.88 0.47 1.00 0.99 0.99
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.88 0.47 1.00 0.99 0.99
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.88 0.47 1.00 0.99 0.99
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 0.97 0.00 0.99 0.96 0.00 1.00 0.97 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.96 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.96 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 0.97 0.00 0.99 0.96 0.00 1.00 0.97 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.96 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 0.97 0.00 0.99 0.96 0.00 1.00 0.97 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.96 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.88 0.47 1.00 0.99 0.99
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 0.97 0.00 0.99 0.96 0.00 1.00 0.97 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.88 0.47 1.00 0.99 0.99
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.96 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.88 0.47 1.00 0.99 0.99
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.96 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [Btu/h-ft2] Space Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total       0.3110 43219.92 13441.11               12093.82


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
Exterior Lighting Total 1377.69           6034.31



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Central Plant

Type Reference Capacity [Btu/h] Reference Efficiency [Btuh/Btuh] Rated Capacity [Btu/h] Rated Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   14771.75 10356.23 4415.52 0.70 4.30    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8292.74 5813.90 2478.84 0.70 4.30    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   11104.59 7785.24 3319.35 0.70 4.30    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   14027.74 9834.61 4193.13 0.70 4.30    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7777.24 5452.49 2324.75 0.70 4.30    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10523.85 7378.10 3145.76 0.70 4.30    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   16087.20 11278.46 4808.73 0.70 4.30    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9192.19 6444.49 2747.70 0.70 4.30    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   12137.84 8509.63 3628.20 0.70 4.30    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   15316.01 10737.80 4578.21 0.70 4.30    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8698.27 6098.21 2600.06 0.70 4.30    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   11448.15 8026.10 3422.04 0.70 4.30    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   18201.02 12760.43 5440.59 0.70 4.30    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11319.61 7935.99 3383.62 0.70 4.30    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13682.27 9592.41 4089.86 0.70 4.30    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   18075.94 12672.74 5403.20 0.70 4.30    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11258.36 7893.05 3365.31 0.70 4.30    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13214.76 9264.64 3950.11 0.70 4.30    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.2 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.7 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.9 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.1 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.6 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.8 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.3 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.7 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   1.0 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.2 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.7 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.9 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.5 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.9 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.1 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.5 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.9 3.68 12.55 13.31 12.80 13.19
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.1 3.68 12.55 13.31 12.80 13.19
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coils [ SEER2 ]

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP2 [Btuh/Btuh] EER2 [Btu/W-h] SEER2 User [Btu/W-h] SEER2 Standard [Btu/W-h] IEER2 [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.2 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.7 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.6 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.8 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.3 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.7 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.0 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.2 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.7 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.5 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.4 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.56 12.16 12.89 12.74  
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.56 12.16 12.89 12.74  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER2 User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER2 Standard is calculated using AHRI Std 210/240-2023 default PLF curve and cooling coefficient of degradation. IEER Calculation was removed from the 2023 Version of the Standard.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


Water-to-Air Heat Pumps at Rated Temperatures Report

Coil Type Rated Total Capacity [Btu/h] Rated Sensible Capacity [Btu/h] Rated Power[Btu/h] Rated COP [Btuh/Btuh] Rated Air Dry-bulb Temperature [F] Rated Air Wet-bulb Temperature [F] Rated Water Temperature [F] Design Day used for Sizing
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


DX Heating Coils [ HSPF2 ]

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF2 [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   7513.44 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   6124.53 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   7515.75 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   7517.58 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   6125.69 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   7513.91 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   6995.78 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   5464.12 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   6999.67 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   6998.70 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   5463.95 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   6996.40 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric   8652.89 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric   7107.69 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric   8656.88 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric   8655.17 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric   7107.66 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric   8654.60 1.00


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 369.37 139.32 0.38 1.00 2.47 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 207.36 78.22 0.38 1.00 3.45 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 277.67 104.74 0.38 1.00 2.89 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 350.77 132.31 0.38 1.00 2.54 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 194.47 73.35 0.38 1.00 3.59 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 263.15 99.26 0.38 1.00 2.98 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 402.26 151.73 0.38 1.00 2.37 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 229.85 86.70 0.38 1.00 3.23 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 303.51 114.48 0.38 1.00 2.74 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 382.98 144.46 0.38 1.00 2.43 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 217.50 82.04 0.38 1.00 3.34 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 286.26 107.98 0.38 1.00 2.84 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 455.12 171.67 0.38 1.00 2.23 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 283.05 106.76 0.38 1.00 2.85 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 342.13 129.05 0.38 1.00 2.57 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 451.99 170.49 0.38 1.00 2.24 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 281.52 106.19 0.38 1.00 2.86 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 330.44 124.64 0.38 1.00 2.62 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8666.95 8666.95 7.22 369.371 369.371 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 75.00 75.00 0.00906 90.56 0.01653 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4865.05 4865.05 4.05 207.362 207.362 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 75.00 74.99 0.00982 92.74 0.01654 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6515.51 6515.51 5.43 277.673 277.673 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:30:00 75.00 75.00 0.00940 90.46 0.01653 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8230.41 8230.41 6.86 350.767 350.767 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 75.00 75.00 0.00915 90.32 0.01653 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4563.31 4563.31 3.80 194.471 194.471 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 75.00 75.00 0.01015 87.83 0.01653 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6174.90 6174.90 5.14 263.151 263.151 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 75.00 75.00 0.00949 89.75 0.01653 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9439.05 9439.05 7.86 402.264 402.264 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 75.00 75.00 0.00875 90.08 0.01653 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5393.59 5393.59 4.49 229.853 229.853 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 75.00 75.00 0.00948 88.54 0.01653 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7121.37 7121.37 5.93 303.509 303.509 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 75.00 74.99 0.00898 93.02 0.01654 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8986.55 8986.55 7.49 382.980 382.980 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 75.00 75.00 0.00881 89.84 0.01653 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5103.82 5103.82 4.25 217.502 217.502 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 75.00 75.00 0.00962 87.47 0.01653 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6717.31 6717.31 5.60 286.263 286.263 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:20:00 75.00 75.00 0.00907 90.22 0.01653 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7752.46 7752.46 6.46 330.438 330.438 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 75.00 74.99 0.00915 92.45 0.01654 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8026.72 8026.72 6.69 342.128 342.128 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 75.00 74.99 0.00910 92.88 0.01654 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 10678.93 10678.93 8.90 455.120 455.120 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 75.00 75.00 0.00883 90.08 0.01653 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6605.76 6605.76 5.50 281.518 281.518 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 75.00 75.00 0.00948 88.19 0.01653 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6641.64 6641.64 5.53 283.049 283.049 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 75.00 75.00 0.00946 88.54 0.01653 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 10605.52 10605.52 8.83 451.993 451.993 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 75.00 75.00 0.00884 89.84 0.01653 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5063.48 5063.48 4.22 92.251 92.251 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00699 40.28 0.00526 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3837.86 3837.86 3.20 69.922 69.922 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00688 40.28 0.00526 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5065.52 5065.52 4.22 92.288 92.288 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00699 40.28 0.00526 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5067.13 5067.13 4.22 92.317 92.317 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00699 40.28 0.00526 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3838.88 3838.88 3.20 69.941 69.941 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00688 40.28 0.00526 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5063.89 5063.89 4.22 92.258 92.258 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00699 40.28 0.00526 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4606.65 4606.65 3.84 83.929 83.929 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00715 40.28 0.00526 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 3255.06 3255.06 2.71 59.305 59.305 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00704 40.28 0.00526 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4610.08 4610.08 3.84 83.992 83.992 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00715 40.28 0.00526 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4609.23 4609.23 3.84 83.976 83.976 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00715 40.28 0.00526 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3254.92 3254.92 2.71 59.302 59.302 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00704 40.28 0.00526 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4607.20 4607.20 3.84 83.939 83.939 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00715 40.28 0.00526 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 6070.47 6070.47 5.06 110.597 110.597 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00709 40.28 0.00526 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 6072.48 6072.48 5.06 110.633 110.633 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00709 40.28 0.00526 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 6068.96 6068.96 5.06 110.569 110.569 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00709 40.28 0.00526 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 4705.40 4705.40 3.92 85.727 85.727 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00699 40.28 0.00526 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 4705.43 4705.43 3.92 85.728 85.728 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00699 40.28 0.00526 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 6070.97 6070.97 5.06 110.606 110.606 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00709 40.28 0.00526 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 369.37 369.37 92.25 92.25 369.3708 369.3708 369.3708 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 207.36 207.36 69.92 69.92 207.3617 207.3617 207.3617 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 277.67 277.67 92.29 92.29 277.6727 277.6727 277.6727 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 350.77 350.77 92.32 92.32 350.7666 350.7666 350.7666 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 194.47 194.47 69.94 69.94 194.4715 194.4715 194.4715 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 263.15 263.15 92.26 92.26 263.1512 263.1512 263.1512 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 402.26 402.26 83.93 83.93 402.2637 402.2637 402.2637 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 229.85 229.85 59.30 59.30 229.8527 229.8527 229.8527 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 303.51 303.51 83.99 83.99 303.5092 303.5092 303.5092 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 382.98 382.98 83.98 83.98 382.9801 382.9801 382.9801 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 217.50 217.50 59.30 59.30 217.5021 217.5021 217.5021 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 286.26 286.26 83.94 83.94 286.2634 286.2634 286.2634 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 455.12 455.12 110.57 110.57 455.1205 455.1205 455.1205 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 283.05 283.05 85.73 85.73 283.0494 283.0494 283.0494 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 342.13 342.13 110.63 110.63 342.1281 342.1281 342.1281 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 451.99 451.99 110.61 110.61 451.9927 451.9927 451.9927 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 281.52 281.52 85.73 85.73 281.5178 281.5178 281.5178 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.44 330.44 110.60 110.60 330.4378 330.4378 330.4378 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 14771.752 10356.228 369.370809 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 14621.04 10521.74 369.370809 78.06 64.66 0.00996959 53.60 51.31 0.00750000 90.56 0.01653379 76.59 12.1815 75.00 0.00905905 49.0160 8666.95 0.00 14777.92 10350.61
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 7513.445 7513.445 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 7513.44 7513.44 -999. 68.13 56.02 0.00678101 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00699239 41.9834 5063.48 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 8292.741 5813.901 207.361745 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 8428.68 5408.43 207.361745 80.01 67.14 0.01127857 53.60 51.31 0.00750000 92.74 0.01653608 77.16 21.6988 74.99 0.00982616 53.1058 4860.25 0.00 8296.20 5810.75
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 6124.533 6124.533 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6124.53 6124.53 -999. 65.11 54.37 0.00653150 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00688465 41.3431 3837.86 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 11104.595 7785.245 277.672750 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:30:00 11173.57 7590.90 277.672750 78.67 65.70 0.01055486 53.60 51.31 0.00750000 90.46 0.01653370 76.57 16.2043 74.99 0.00940892 50.8850 6460.74 0.00 11109.23 7781.02
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 7515.754 7515.754 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 7515.75 7515.75 -999. 66.86 55.39 0.00671138 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00699260 41.9847 5065.52 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 14027.738 9834.612 350.766580 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 13946.00 9903.08 350.766580 78.13 64.87 0.01009404 53.60 51.31 0.00750000 90.32 0.01653355 76.53 12.8276 75.00 0.00914646 49.4821 8230.41 0.00 14033.59 9829.28
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 7517.584 7517.584 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 7517.58 7517.58 -999. 67.93 55.92 0.00677014 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00699278 41.9857 5067.13 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 7777.238 5452.491 194.471480 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 8169.15 5018.66 194.471480 79.13 67.34 0.01162674 53.60 51.31 0.00750000 87.83 0.01653095 75.88 23.1371 75.00 0.01014276 54.7835 4536.80 0.00 7780.48 5449.53
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 6125.690 6125.690 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6125.69 6125.69 -999. 64.66 54.14 0.00650820 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00688479 41.3439 3838.88 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 10523.853 7378.097 263.151191 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 10668.86 7143.46 263.151191 78.69 65.91 0.01069613 53.60 51.31 0.00750000 89.75 0.01653295 76.38 17.0985 75.00 0.00948284 51.2738 6173.27 0.00 10528.24 7374.10
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 7513.911 7513.911 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 7513.91 7513.91 -999. 66.57 55.25 0.00669572 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00699243 41.9837 5063.89 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 16087.195 11278.462 402.263734 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 15834.64 11844.55 402.263734 77.85 64.09 0.00962006 53.60 51.31 0.00750000 90.08 0.01653329 76.47 11.1854 75.00 0.00873828 47.3033 9430.72 0.00 16093.91 11272.35
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 6995.780 6995.780 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6995.78 6995.78 -999. 68.45 56.42 0.00693983 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00715175 42.9283 4606.65 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 9192.192 6444.492 229.852717 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 9427.70 6215.04 229.852717 78.81 66.18 0.01086228 53.60 51.31 0.00750000 88.54 0.01653169 76.07 19.5756 75.00 0.00945548 51.1271 5370.24 0.00 9196.03 6441.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 5464.120 5464.120 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 5464.12 5464.12 -999. 65.79 54.92 0.00668937 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00703798 42.2525 3255.06 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 12137.838 8509.635 303.509229 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 11916.82 8518.96 303.509229 78.83 65.10 0.01009618 53.60 51.31 0.00750000 93.02 0.01653638 77.23 14.8249 74.99 0.00897525 48.5712 7121.37 0.00 12142.90 8505.02
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 6999.667 6999.667 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6999.67 6999.67 -999. 67.30 55.84 0.00687118 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00715211 42.9305 4610.08 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 15316.011 10737.798 382.980111 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 15132.46 11190.33 382.980111 77.91 64.25 0.00972143 53.60 51.31 0.00750000 89.84 0.01653305 76.41 11.7486 75.00 0.00880694 47.6699 8975.77 0.00 15322.40 10731.98
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 6998.701 6998.701 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6998.70 6998.70 -999. 68.27 56.33 0.00692940 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00715202 42.9299 4609.23 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 8698.269 6098.211 217.502079 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 9012.55 5826.47 217.502079 78.74 66.42 0.01104841 53.60 51.31 0.00750000 87.47 0.01653057 75.79 20.6872 75.00 0.00961149 51.9561 5076.84 0.00 8701.90 6094.90
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 5463.954 5463.954 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 5463.95 5463.95 -999. 65.44 54.74 0.00666956 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00703795 42.2524 3254.92 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 11448.147 8026.104 286.263353 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:20:00 11449.08 8033.31 286.263353 78.56 65.22 0.01024177 53.60 51.31 0.00750000 90.22 0.01653345 76.51 15.7180 75.00 0.00906432 49.0423 6708.82 0.00 11452.92 8021.75
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 6996.405 6996.405 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 6996.40 6996.40 -999. 67.01 55.70 0.00685400 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00715181 42.9287 4607.20 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 18201.025 12760.433 455.120493 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 17887.85 13403.62 455.120493 77.66 63.98 0.00959103 53.60 51.31 0.00750000 90.08 0.01653329 76.47 9.8864 75.00 0.00882939 47.7909 10678.93 0.00 18208.62 12753.51
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 8652.894 8652.894 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8652.89 8652.89 -999. 68.86 56.52 0.00690763 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00708870 42.5555 6068.96 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 11319.615 7935.992 283.049377 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 11506.50 7762.25 283.049377 78.32 65.63 0.01058480 53.60 51.31 0.00750000 88.54 0.01653169 76.07 15.8965 75.00 0.00945194 51.1097 6622.91 0.00 11324.34 7931.69
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 7107.693 7107.693 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 7107.69 7107.69 -999. 66.96 55.44 0.00671694 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00699286 41.9859 4705.43 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 13682.272 9592.411 342.128120 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 13416.81 9584.59 342.128120 78.51 64.97 0.01007426 53.60 51.31 0.00750000 92.88 0.01653623 77.19 13.1515 74.99 0.00909682 49.2216 8022.93 0.00 13687.98 9587.21
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 8656.877 8656.877 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8656.88 8656.88 -999. 67.83 56.01 0.00684809 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00708901 42.5573 6072.48 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 18075.940 12672.738 451.992717 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 17795.31 13302.39 451.992717 77.64 64.00 0.00961003 53.60 51.31 0.00750000 89.84 0.01653305 76.41 9.9548 75.00 0.00883758 47.8347 10605.17 0.00 18083.48 12665.87
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 8655.168 8655.168 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8655.17 8655.17 -999. 68.84 56.51 0.00690653 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00708888 42.5565 6070.97 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 11258.364 7893.050 281.517789 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 11470.89 7717.07 281.517789 78.27 65.64 0.01060599 53.60 51.31 0.00750000 88.19 0.01653132 75.98 15.9830 75.00 0.00947092 51.2094 6585.28 0.00 11263.06 7888.77
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 7107.663 7107.663 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 7107.66 7107.66 -999. 66.93 55.42 0.00671544 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00699286 41.9859 4705.40 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 13214.757 9264.644 330.437802 -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 13015.35 9219.17 330.437802 78.54 65.09 0.01015338 53.60 51.31 0.00750000 92.45 0.01653578 77.08 13.6168 74.99 0.00914723 49.4904 7749.16 0.00 13220.27 9259.62
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 8654.601 8654.601 -999. -999. -999.00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 8654.60 8654.60 -999. 67.68 55.94 0.00683942 122.00 75.15 0.00800000 40.28 0.00525715 40.28 -999.000 72.00 0.00708883 42.5562 6070.47 0.00 -999.0 -999.0



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [Btu/lbm-R] Dry Air Heat Capacity [Btu/lbm-R] Standard Air Density Adjusted for Elevation [lb/ft3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [ft3/min] Supply Fan Maximum Air Mass Flow Rate [lb/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [Btu/lbm-R] Plant Fluid Density [lb/ft3] Plant Maximum Fluid Mass Flow Rate [lb/s] Plant Design Fluid Return Temperature [F] Plant Design Fluid Supply Temperature [F] Plant Design Fluid Temperature Difference [deltaF] Plant Design Capacity [Btu/h] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [F] System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h] Coil Air Mass Flow Rate at Rating Conditions [lb/s] Coil Entering Air Drybulb at Rating Conditions [F] Coil Entering Air Wetbulb at Rating Conditions [F] Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] Coil Leaving Air Drybulb at Rating Conditions [F] Coil Leaving Air Wetbulb at Rating Conditions [F] Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 14771.752 10356.228 369.370809 -999. -999.00 -999.0000 1.00000 0.81157 0.2444 0.2400 0.0751 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 369.370809 0.46244523   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 Sensible 14621.04 10521.74 0.9898 0.46244523 369.370809 78.06 64.66 0.00996959 12.2 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 475.373 14145.66 90.56 0.01653379 76.59 44.99498340 12.1815 75.00 0.00905905 75.00 0.00905905 49.0160 8666.95 0.00 14777.92 10350.61 0.44418214 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7513.445 7513.445 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 369.370809 0.46244523   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 7513.44 7513.44 1.0000 -0.264985E+04 -999. 68.13 56.02 0.00678101 8.9 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7513.44 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00699239 72.00 0.00699239 41.9834 5063.48 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 8292.741 5813.901 207.361745 -999. -999.00 -999.0000 1.00000 0.68263 0.2450 0.2400 0.0751 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 207.361745 0.25961296   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:20:00 Sensible 8428.68 5408.43 1.0164 0.25961296 207.361745 80.01 67.14 0.01127857 13.3 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 266.871 8161.81 92.74 0.01653608 77.16 44.99498340 21.6988 74.99 0.00982161 74.99 0.00982616 53.1058 4860.25 0.00 8296.20 5810.75 0.24936021 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6124.533 6124.533 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 207.361745 0.25961296   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 6124.53 6124.53 1.0000 -0.264985E+04 -999. 65.11 54.37 0.00653150 8.4 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 6124.53 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00688465 72.00 0.00688465 41.3431 3837.86 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11104.595 7785.245 277.672750 -999. -999.00 -999.0000 1.00000 0.75600 0.2447 0.2400 0.0751 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 277.672750 0.34764100   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:30:00 Sensible 11173.57 7590.90 1.0062 0.34764100 277.672750 78.67 65.70 0.01055486 12.6 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 357.360 10816.21 90.46 0.01653370 76.57 44.99498340 16.2043 75.00 0.00939868 74.99 0.00940892 50.8850 6460.74 0.00 11109.23 7781.02 0.33391181 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7515.754 7515.754 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 277.672750 0.34764100   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 7515.75 7515.75 1.0000 -0.264985E+04 -999. 66.86 55.39 0.00671138 8.7 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7515.75 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00699260 72.00 0.00699260 41.9847 5065.52 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 14027.738 9834.612 350.766580 -999. -999.00 -999.0000 1.00000 0.80097 0.2445 0.2400 0.0751 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 350.766580 0.43915309   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 Sensible 13946.00 9903.08 0.9942 0.43915309 350.766580 78.13 64.87 0.01009404 12.3 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 451.430 13494.57 90.32 0.01653355 76.53 44.99498340 12.8276 75.00 0.00914646 75.00 0.00914646 49.4821 8230.41 0.00 14033.59 9829.28 0.42180986 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7517.584 7517.584 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 350.766580 0.43915309   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 7517.58 7517.58 1.0000 -0.264985E+04 -999. 67.93 55.92 0.00677014 8.9 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7517.58 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00699278 72.00 0.00699278 41.9857 5067.13 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 7777.238 5452.491 194.471480 -999. -999.00 -999.0000 1.00000 0.69453 0.2452 0.2400 0.0751 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 194.471480 0.24347459   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 Sensible 8169.15 5018.66 1.0504 0.24347459 194.471480 79.13 67.34 0.01162674 13.4 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 250.281 7918.86 87.83 0.01653095 75.88 44.99498340 23.1371 75.00 0.01015049 75.00 0.01014276 54.7835 4536.80 0.00 7780.48 5449.53 0.23385919 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6125.690 6125.690 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 194.471480 0.24347459   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 6125.69 6125.69 1.0000 -0.264985E+04 -999. 64.66 54.14 0.00650820 8.3 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 6125.69 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00688479 72.00 0.00688479 41.3439 3838.88 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10523.853 7378.097 263.151191 -999. -999.00 -999.0000 1.00000 0.74909 0.2448 0.2400 0.0751 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 263.151191 0.32946029   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:00:00 Sensible 10668.86 7143.46 1.0138 0.32946029 263.151191 78.69 65.91 0.01069613 12.7 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 338.671 10330.19 89.75 0.01653295 76.38 44.99498340 17.0985 75.00 0.00949228 75.00 0.00948284 51.2738 6173.27 0.00 10528.24 7374.10 0.31644909 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7513.911 7513.911 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 263.151191 0.32946029   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 7513.91 7513.91 1.0000 -0.264985E+04 -999. 66.57 55.25 0.00669572 8.7 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7513.91 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00699243 72.00 0.00699243 41.9837 5063.89 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 16087.195 11278.462 402.263734 -999. -999.00 -999.0000 1.00000 0.84960 0.2443 0.2400 0.0751 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 402.263734 0.50362654   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 Sensible 15834.64 11844.55 0.9843 0.50362654 402.263734 77.85 64.09 0.00962006 12.0 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 517.706 15316.94 90.08 0.01653329 76.47 44.99498340 11.1854 75.00 0.00874939 75.00 0.00873828 47.3033 9430.72 0.00 16093.91 11272.35 0.48373710 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6995.780 6995.780 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 402.263734 0.50362654   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 6995.78 6995.78 1.0000 -0.264985E+04 -999. 68.45 56.42 0.00693983 9.1 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 6995.78 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00715175 72.00 0.00715175 42.9283 4606.65 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 9192.192 6444.492 229.852717 -999. -999.00 -999.0000 1.00000 0.74136 0.2448 0.2400 0.0751 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 229.852717 0.28777123   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 Sensible 9427.70 6215.04 1.0256 0.28777123 229.852717 78.81 66.18 0.01086228 12.9 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 295.816 9131.89 88.54 0.01653169 76.07 44.99498340 19.5756 75.00 0.00948232 75.00 0.00945548 51.1271 5370.24 0.00 9196.03 6441.00 0.27640644 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 5464.120 5464.120 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 229.852717 0.28777123   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 5464.12 5464.12 1.0000 -0.264985E+04 -999. 65.79 54.92 0.00668937 8.6 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5464.12 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00703798 72.00 0.00703798 42.2525 3255.06 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 12137.838 8509.635 303.509229 -999. -999.00 -999.0000 1.00000 0.77559 0.2445 0.2400 0.0751 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 303.509229 0.37998778   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:10:00 Sensible 11916.82 8518.96 0.9818 0.37998778 303.509229 78.83 65.10 0.01009618 12.4 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 390.611 11526.21 93.02 0.01653638 77.23 44.99498340 14.8249 74.99 0.00897525 74.99 0.00897525 48.5712 7121.37 0.00 12142.90 8505.02 0.36498114 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6999.667 6999.667 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 303.509229 0.37998778   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 6999.67 6999.67 1.0000 -0.264985E+04 -999. 67.30 55.84 0.00687118 8.9 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 6999.67 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00715211 72.00 0.00715211 42.9305 4610.08 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 15316.011 10737.798 382.980111 -999. -999.00 -999.0000 1.00000 0.84005 0.2443 0.2400 0.0751 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 382.980111 0.47948382   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 Sensible 15132.46 11190.33 0.9880 0.47948382 382.980111 77.91 64.25 0.00972143 12.0 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 492.888 14639.57 89.84 0.01653305 76.41 44.99498340 11.7486 75.00 0.00881461 75.00 0.00880694 47.6699 8975.77 0.00 15322.40 10731.98 0.46054783 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6998.701 6998.701 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 382.980111 0.47948382   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 6998.70 6998.70 1.0000 -0.264985E+04 -999. 68.27 56.33 0.00692940 9.0 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 6998.70 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00715202 72.00 0.00715202 42.9299 4609.23 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 8698.269 6098.211 217.502079 -999. -999.00 -999.0000 1.00000 0.73498 0.2449 0.2400 0.0751 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 217.502079 0.27230847   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 Sensible 9012.55 5826.47 1.0361 0.27230847 217.502079 78.74 66.42 0.01104841 13.0 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 279.921 8732.63 87.47 0.01653057 75.79 44.99498340 20.6872 75.00 0.00961850 75.00 0.00961149 51.9561 5076.84 0.00 8701.90 6094.90 0.26155434 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 5463.954 5463.954 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 217.502079 0.27230847   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 5463.95 5463.95 1.0000 -0.264985E+04 -999. 65.44 54.74 0.00666956 8.5 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 5463.95 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00703795 72.00 0.00703795 42.2524 3254.92 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11448.147 8026.104 286.263353 -999. -999.00 -999.0000 1.00000 0.78205 0.2445 0.2400 0.0751 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 286.263353 0.35839627   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 11:20:00 Sensible 11449.08 8033.31 1.0001 0.35839627 286.263353 78.56 65.22 0.01024177 12.4 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 368.416 11080.66 90.22 0.01653345 76.51 44.99498340 15.7180 75.00 0.00906842 75.00 0.00906432 49.0423 6708.82 0.00 11452.92 8021.75 0.34424233 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6996.405 6996.405 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 286.263353 0.35839627   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 6996.40 6996.40 1.0000 -0.264985E+04 -999. 67.01 55.70 0.00685400 8.8 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 6996.40 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00715181 72.00 0.00715181 42.9287 4607.20 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 18201.025 12760.433 455.120493 -999. -999.00 -999.0000 1.00000 0.85662 0.2443 0.2400 0.0751 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 455.120493 0.56980220   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 Sensible 17887.85 13403.62 0.9828 0.56980220 455.120493 77.66 63.98 0.00959103 11.9 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 585.732 17302.11 90.08 0.01653329 76.47 44.99498340 9.8864 75.00 0.00882939 75.00 0.00882939 47.7909 10678.93 0.00 18208.62 12753.51 0.54729932 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 8652.894 8652.894 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 455.120493 0.56980220   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 8652.89 8652.89 1.0000 -0.264985E+04 -999. 68.86 56.52 0.00690763 9.1 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8652.89 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00708870 72.00 0.00708870 42.5555 6068.96 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11319.615 7935.992 283.049377 -999. -999.00 -999.0000 1.00000 0.76809 0.2447 0.2400 0.0751 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 283.049377 0.35437244   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:10:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 Sensible 11506.50 7762.25 1.0165 0.35437244 283.049377 78.32 65.63 0.01058480 12.6 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 364.279 11142.22 88.54 0.01653169 76.07 44.99498340 15.8965 75.00 0.00946078 75.00 0.00945194 51.1097 6622.91 0.00 11324.34 7931.69 0.34037740 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7107.693 7107.693 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 283.049377 0.35437244   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 7107.69 7107.69 1.0000 -0.264985E+04 -999. 66.96 55.44 0.00671694 8.7 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7107.69 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00699286 72.00 0.00699286 41.9859 4705.43 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13682.272 9592.411 342.128120 -999. -999.00 -999.0000 1.00000 0.78361 0.2445 0.2400 0.0751 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 342.128120 0.42833790   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 Sensible 13416.81 9584.59 0.9806 0.42833790 342.128120 78.51 64.97 0.01007426 12.3 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 440.313 12976.50 92.88 0.01653623 77.19 44.99498340 13.1515 74.99 0.00909572 74.99 0.00909682 49.2216 8022.93 0.00 13687.98 9587.21 0.41142179 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 8656.877 8656.877 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 342.128120 0.42833790   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 8656.88 8656.88 1.0000 -0.264985E+04 -999. 67.83 56.01 0.00684809 8.9 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8656.88 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00708901 72.00 0.00708901 42.5573 6072.48 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 18075.940 12672.738 451.992717 -999. -999.00 -999.0000 1.00000 0.85624 0.2443 0.2400 0.0751 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 451.992717 0.56588628   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:50:00 Sensible 17795.31 13302.39 0.9845 0.56588628 451.992717 77.64 64.00 0.00961003 11.9 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 581.706 17213.60 89.84 0.01653305 76.41 44.99498340 9.9548 75.00 0.00884467 75.00 0.00883758 47.8347 10605.17 0.00 18083.48 12665.87 0.54353805 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 8655.168 8655.168 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 451.992717 0.56588628   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 8655.17 8655.17 1.0000 -0.264985E+04 -999. 68.84 56.51 0.00690653 9.1 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8655.17 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00708888 72.00 0.00708888 42.5565 6070.97 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11258.364 7893.050 281.517789 -999. -999.00 -999.0000 1.00000 0.76888 0.2447 0.2400 0.0751 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 281.517789 0.35245492   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 Sensible 11470.89 7717.07 1.0189 0.35245492 281.517789 78.27 65.64 0.01060599 12.6 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 362.308 11108.59 88.19 0.01653132 75.98 44.99498340 15.9830 75.00 0.00947878 75.00 0.00947092 51.2094 6585.28 0.00 11263.06 7888.77 0.33853561 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7107.663 7107.663 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 281.517789 0.35245492   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 7107.66 7107.66 1.0000 -0.264985E+04 -999. 66.93 55.42 0.00671544 8.7 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7107.66 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00699286 72.00 0.00699286 41.9859 4705.40 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13214.757 9264.644 330.437802 -999. -999.00 -999.0000 1.00000 0.77892 0.2445 0.2400 0.0751 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 330.437802 0.41370184   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 Sensible 13015.35 9219.17 0.9849 0.41370184 330.437802 78.54 65.09 0.01015338 12.4 53.60 51.31 0.00750000 7.4 -999. -999.0 -999.0 -999.0 425.267 12590.09 92.45 0.01653578 77.08 44.99498340 13.6168 74.99 0.00914731 74.99 0.00914723 49.4904 7749.16 0.00 13220.27 9259.62 0.39736375 80.00 67.00 0.01118466 13.2 53.45 53.41 0.00865960 8.1
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 8654.601 8654.601 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0751 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 330.437802 0.41370184   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 8654.60 8654.60 1.0000 -0.264985E+04 -999. 67.68 55.94 0.00683942 8.9 122.00 75.15 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8654.60 40.28 0.00525715 40.28 44.99498340 -999.000 72.00 0.00708883 72.00 0.00708883 42.5562 6070.47 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5910.33 5007.00 2846.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5823.00 5402.83 3213.83
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5891.67 4743.67 2606.17
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5788.33 5435.33 3007.33
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5747.50 6116.50 3564.33
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5790.17 5263.17 2802.33
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 6045.33 3233.67 1416.33
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5929.33 3005.50 1342.50
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6007.17 2993.33 1236.67
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5852.83 3630.17 1504.50
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5787.00 3555.83 1464.67
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5874.17 3407.17 1301.33
LIVING_UNIT3_BACKROW_TOPFLOOR 5959.83 3620.17 1514.17
LIVING_UNIT3_FRONTROW_TOPFLOOR 6078.33 3346.17 1475.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 6112.67 3628.33 1707.00
LIVING_UNIT2_BACKROW_TOPFLOOR 5915.83 3879.50 1774.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 6023.67 3488.50 1669.17
LIVING_UNIT1_BACKROW_TOPFLOOR 5972.33 3910.67 1778.67
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 6325.17 6257.50 3661.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2.33 0.00 2.33 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 12.33 0.00 12.33
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2.17 6.17 2.17 6.17
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 3.33 0.00 3.33 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.83 6.83 0.83 6.83
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2.67 2.83 2.67 2.83
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 3.17 0.00 3.17
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 3.83 0.00 3.83
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 3.33 0.00 3.33 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 2.67 3.00 2.67 3.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 2.83 0.00 2.83 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 2.00 0.00 2.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 4.17 0.00 4.17 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 5.00 16.33 5.00 16.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.139 0.000 0.265
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.123 0.000 0.265
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.139 0.000 0.265
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.139 0.000 0.265
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.122 0.000 0.265
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.139 0.000 0.265
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.061 0.000 0.265
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.045 0.000 0.265
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.061 0.000 0.265
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.061 0.000 0.265
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.044 0.000 0.265
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.061 0.000 0.265
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.139 0.000 0.265
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.139 0.000 0.265
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.139 0.000 0.265
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.123 0.000 0.265
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.123 0.000 0.265
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.139 0.000 0.265
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Zone Area [ft2] Design Zone Outdoor Airflow - Voz [ft3/min] Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
Total Facility   24.79 36.00 183739.38 21609.96 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Infiltration [ft3] Total Ventilation and Infiltration [ft3] Dynamic Target Ventilation - Voz-dyn [ft3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 23308013.34 23308013.34 12247457.26 35555470.60 23785081.69 5899.00 1183.00 1726.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 23308013.34 23308013.34 10800690.36 34108703.71 23785081.69 5899.00 1183.00 1726.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 23308013.34 23308013.34 12254068.41 35562081.75 23785081.69 5899.00 1183.00 1726.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 23308013.34 23308013.34 12223327.42 35531340.76 23785081.69 5899.00 1183.00 1726.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 23308013.34 23308013.34 10769990.15 34078003.49 23785081.69 5899.00 1183.00 1726.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 23308013.34 23308013.34 12227892.07 35535905.42 23785081.69 5899.00 1183.00 1726.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 23309344.78 23309344.78 5384407.35 28693752.14 23785081.69 5896.00 1183.67 1728.33 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 23309344.78 23309344.78 3923247.95 27232592.74 23785081.69 5896.00 1183.67 1728.33 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 23309344.78 23309344.78 5387293.04 28696637.82 23785081.69 5896.00 1183.67 1728.33 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 23309344.78 23309344.78 5373777.31 28683122.09 23785081.69 5896.00 1183.67 1728.33 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 23309344.78 23309344.78 3911939.39 27221284.17 23785081.69 5896.00 1183.67 1728.33 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 23309344.78 23309344.78 5375806.16 28685150.94 23785081.69 5896.00 1183.67 1728.33 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 23310677.62 23310677.62 12265204.76 35575882.39 23785081.69 5892.00 1184.83 1731.17 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 23310677.62 23310677.62 12284864.31 35595541.93 23785081.69 5892.00 1184.83 1731.17 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 23310677.62 23310677.62 12278367.06 35589044.68 23785081.69 5892.00 1184.83 1731.17 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 23310677.62 23310677.62 10806437.47 34117115.09 23785081.69 5892.00 1184.83 1731.17 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 23310677.62 23310677.62 10828814.07 34139491.69 23785081.69 5892.00 1184.83 1731.17 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 23310677.62 23310677.62 12260765.08 35571442.70 23785081.69 5892.00 1184.83 1731.17 0.00
Total Facility 0.00 0.419568E+09 0.419568E+09 0.170604E+09 0.590173E+09 0.428131E+09 5899.00 1190.00 1731.17 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Infiltration [ft3/min] Total Ventilation and Infiltration [ft3/min] Dynamic Target Ventilation - Voz-dyn [ft3/min] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 44.0925 44.0925 23.1689 67.2614 44.9950 5899.00 1183.00 1726.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 44.0925 44.0925 20.4320 64.5245 44.9950 5899.00 1183.00 1726.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 44.0925 44.0925 23.1814 67.2739 44.9950 5899.00 1183.00 1726.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 44.0925 44.0925 23.1233 67.2157 44.9950 5899.00 1183.00 1726.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 44.0925 44.0925 20.3739 64.4664 44.9950 5899.00 1183.00 1726.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 44.0925 44.0925 23.1319 67.2244 44.9950 5899.00 1183.00 1726.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 44.0950 44.0950 10.1859 54.2809 44.9950 5896.00 1183.67 1728.33
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 44.0950 44.0950 7.4217 51.5167 44.9950 5896.00 1183.67 1728.33
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 44.0950 44.0950 10.1913 54.2863 44.9950 5896.00 1183.67 1728.33
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 44.0950 44.0950 10.1657 54.2608 44.9950 5896.00 1183.67 1728.33
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 44.0950 44.0950 7.4003 51.4954 44.9950 5896.00 1183.67 1728.33
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 44.0950 44.0950 10.1696 54.2646 44.9950 5896.00 1183.67 1728.33
LIVING_UNIT3_BACKROW_TOPFLOOR 0.0000 44.0975 44.0975 23.2025 67.3000 44.9950 5892.00 1184.83 1731.17
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0000 44.0975 44.0975 23.2397 67.3372 44.9950 5892.00 1184.83 1731.17
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0000 44.0975 44.0975 23.2274 67.3249 44.9950 5892.00 1184.83 1731.17
LIVING_UNIT2_BACKROW_TOPFLOOR 0.0000 44.0975 44.0975 20.4429 64.5404 44.9950 5892.00 1184.83 1731.17
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0000 44.0975 44.0975 20.4852 64.5827 44.9950 5892.00 1184.83 1731.17
LIVING_UNIT1_BACKROW_TOPFLOOR 0.0000 44.0975 44.0975 23.1941 67.2916 44.9950 5892.00 1184.83 1731.17
Total Facility 0.0000 793.7103 793.7103 322.7376 1116.4479 809.9097 5899.00 1190.00 1731.17


Total Outdoor Air by AirLoop

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 23308013.34 23308013.34 23785081.69 5899.00 1183.00 1726.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 23308013.34 23308013.34 23785081.69 5899.00 1183.00 1726.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 23308013.34 23308013.34 23785081.69 5899.00 1183.00 1726.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 23308013.34 23308013.34 23785081.69 5899.00 1183.00 1726.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 23308013.34 23308013.34 23785081.69 5899.00 1183.00 1726.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 23308013.34 23308013.34 23785081.69 5899.00 1183.00 1726.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 23309344.78 23309344.78 23785081.69 5896.00 1183.67 1728.33 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 23309344.78 23309344.78 23785081.69 5896.00 1183.67 1728.33 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 23309344.78 23309344.78 23785081.69 5896.00 1183.67 1728.33 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 23309344.78 23309344.78 23785081.69 5896.00 1183.67 1728.33 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 23309344.78 23309344.78 23785081.69 5896.00 1183.67 1728.33 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 23309344.78 23309344.78 23785081.69 5896.00 1183.67 1728.33 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 23310677.62 23310677.62 23785081.69 5892.00 1184.83 1731.17 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 23310677.62 23310677.62 23785081.69 5892.00 1184.83 1731.17 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 23310677.62 23310677.62 23785081.69 5892.00 1184.83 1731.17 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 23310677.62 23310677.62 23785081.69 5892.00 1184.83 1731.17 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 23310677.62 23310677.62 23785081.69 5892.00 1184.83 1731.17 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 23310677.62 23310677.62 23785081.69 5892.00 1184.83 1731.17 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 44.0925 44.0925 44.9950 5899.00 1183.00 1726.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 44.0925 44.0925 44.9950 5899.00 1183.00 1726.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 44.0925 44.0925 44.9950 5899.00 1183.00 1726.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 44.0925 44.0925 44.9950 5899.00 1183.00 1726.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 44.0925 44.0925 44.9950 5899.00 1183.00 1726.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 44.0925 44.0925 44.9950 5899.00 1183.00 1726.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 44.0950 44.0950 44.9950 5896.00 1183.67 1728.33
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 44.0950 44.0950 44.9950 5896.00 1183.67 1728.33
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 44.0950 44.0950 44.9950 5896.00 1183.67 1728.33
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 44.0950 44.0950 44.9950 5896.00 1183.67 1728.33
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 44.0950 44.0950 44.9950 5896.00 1183.67 1728.33
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 44.0950 44.0950 44.9950 5896.00 1183.67 1728.33
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 44.0975 44.0975 44.9950 5892.00 1184.83 1731.17
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 44.0975 44.0975 44.9950 5892.00 1184.83 1731.17
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 44.0975 44.0975 44.9950 5892.00 1184.83 1731.17
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 44.0975 44.0975 44.9950 5892.00 1184.83 1731.17
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 44.0975 44.0975 44.9950 5892.00 1184.83 1731.17
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 44.0975 44.0975 44.9950 5892.00 1184.83 1731.17


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [ft3/min] Limits and Scheduled Limits [ft3/min] Economizer [ft3/min] Exhaust Flow [ft3/min] Mixed Air Flow [ft3/min] High Humidity [ft3/min] Demand Controlled Ventilation [ft3/min] Night Ventilation [ft3/min] Demand Limiting [ft3/min] Energy Management System [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Surfaces by Class

Total Outdoors
Wall 74 50
Floor 28 3
Roof 21 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 60 60
Overhang 30 30
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1910
Defaulted Fields 1685
Fields with Defaults 6153
Autosized Fields 342
Autosizable Fields 504
Autocalculated Fields 149
Autocalculatable Fields 328



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 197900.07 8248.63 16-FEB-03:10 85118.49 04-JAN-07:10
Electricity:Building 100396.90 6292.37 02-JAN-03:10 19051.98 01-JAN-18:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
Electricity:SpaceType:GENERAL 100396.90 6292.37 02-JAN-03:10 19051.98 01-JAN-18:10
InteriorLights:Electricity 12093.82 270.83 01-JAN-00:10 3939.36 01-JAN-19:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
InteriorLights:Electricity:SpaceType:GENERAL 12093.82 270.83 01-JAN-00:10 3939.36 01-JAN-19:10
General:InteriorLights:Electricity 12093.82 270.83 01-JAN-00:10 3939.36 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:SpaceType:GENERAL 12093.82 270.83 01-JAN-00:10 3939.36 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
InteriorEquipment:Electricity 88303.07 5995.41 02-JAN-04:10 15497.32 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
InteriorEquipment:Electricity:SpaceType:GENERAL 88303.07 5995.41 02-JAN-04:10 15497.32 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
electric_range:InteriorEquipment:Electricity:SpaceType:GENERAL 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:SpaceType:GENERAL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
electric_mels:InteriorEquipment:Electricity:SpaceType:GENERAL 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
Fans:Electricity 11257.82 578.57 02-JAN-09:00 2688.81 05-FEB-07:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 197900.07 8248.63 16-FEB-03:10 85118.49 04-JAN-07:10
ElectricityPurchased:Plant 197900.07 8248.63 16-FEB-03:10 85118.49 04-JAN-07:10
Cogeneration:ElectricityPurchased 197900.07 8248.63 16-FEB-03:10 85118.49 04-JAN-07:10
General:Cogeneration:ElectricityPurchased 197900.07 8248.63 16-FEB-03:10 85118.49 04-JAN-07:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 197900.07 8248.63 16-FEB-03:10 85118.49 04-JAN-07:10
ElectricityNet:Plant 197900.07 8248.63 16-FEB-03:10 85118.49 04-JAN-07:10
Cogeneration:ElectricityNet 197900.07 8248.63 16-FEB-03:10 85118.49 04-JAN-07:10
General:Cogeneration:ElectricityNet 197900.07 8248.63 16-FEB-03:10 85118.49 04-JAN-07:10
Electricity:HVAC 57268.62 578.57 02-JAN-09:00 35619.99 05-FEB-07:10
Ventilation:Fans:Electricity 5068.29 578.57 01-JAN-08:30 578.57 01-JAN-00:10
General:Fans:Electricity 6189.53 0.00 01-JAN-04:40 2110.24 05-FEB-07:10
ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Exterior-Lights:ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Garage-Lights:ExteriorLights:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:Electricity 9859.47 0.00 01-JAN-00:10 32931.17 05-FEB-07:10
General:Heating:Electricity 9859.47 0.00 01-JAN-00:10 32931.17 05-FEB-07:10
Cooling:Electricity 36151.33 0.00 01-JAN-04:40 14633.78 09-SEP-17:10
General:Cooling:Electricity 36151.33 0.00 01-JAN-04:40 14633.78 09-SEP-17:10
Electricity:Plant 34200.24 0.00 01-JAN-00:10 54383.64 01-JAN-07:10
WaterSystems:Electricity 34200.24 0.00 01-JAN-00:10 54383.64 01-JAN-07:10
Water Heater:WaterSystems:Electricity 34200.24 0.00 01-JAN-00:10 54383.64 01-JAN-07:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:30
Water:Plant 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:30
WaterSystems:Water 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:30
Domestic Hot Water:WaterSystems:Water 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:30
MainsWater:Facility 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:30
MainsWater:Plant 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:30
WaterSystems:MainsWater 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:30
Domestic Hot Water:WaterSystems:MainsWater 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:30
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 1038229.28 312.54 18-OCT-02:50 349484.26 09-SEP-17:10
EnergyTransfer:Building 396847.79 0.00 01-JAN-04:40 142803.79 09-SEP-17:10
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer 35814.42 0.00 01-JAN-00:10 119925.44 05-FEB-07:10
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 35814.42 0.00 01-JAN-00:10 119925.44 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 361033.37 0.00 01-JAN-04:40 142803.79 09-SEP-17:10
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer 361033.37 0.00 01-JAN-04:40 142803.79 09-SEP-17:10
General:Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 20622.82 0.00 01-JAN-00:10 9588.78 30-AUG-16:10
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2329.43 0.00 01-JAN-00:10 7038.40 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2329.43 0.00 01-JAN-00:10 7038.40 05-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 18293.39 0.00 01-JAN-00:10 9588.78 30-AUG-16:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 18293.39 0.00 01-JAN-00:10 9588.78 30-AUG-16:10
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 15787.29 0.00 01-JAN-00:10 5709.64 30-AUG-16:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1468.75 0.00 01-JAN-00:10 5606.03 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1468.75 0.00 01-JAN-00:10 5606.03 05-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 14318.54 0.00 01-JAN-00:10 5709.64 30-AUG-16:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 14318.54 0.00 01-JAN-00:10 5709.64 30-AUG-16:10
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 20348.70 0.00 01-JAN-00:10 7243.50 10-SEP-16:20
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2190.22 0.00 01-JAN-00:10 6916.12 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2190.22 0.00 01-JAN-00:10 6916.12 05-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 18158.48 0.00 01-JAN-00:10 7243.50 10-SEP-16:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 18158.48 0.00 01-JAN-00:10 7243.50 10-SEP-16:20
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 18909.34 0.00 01-JAN-00:10 8877.18 09-SEP-17:10
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2827.12 0.00 01-JAN-00:10 7016.83 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2827.12 0.00 01-JAN-00:10 7016.83 05-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 16082.22 0.00 01-JAN-00:10 8877.18 09-SEP-17:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 16082.22 0.00 01-JAN-00:10 8877.18 09-SEP-17:10
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 14268.88 0.00 01-JAN-00:10 5593.72 05-FEB-08:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2002.95 0.00 01-JAN-00:10 5593.72 05-FEB-08:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2002.95 0.00 01-JAN-00:10 5593.72 05-FEB-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12265.93 0.00 01-JAN-00:10 5163.29 03-AUG-17:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12265.93 0.00 01-JAN-00:10 5163.29 03-AUG-17:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 18625.71 0.00 01-JAN-00:10 6979.59 19-JUL-13:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2687.15 0.00 01-JAN-00:10 6894.75 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2687.15 0.00 01-JAN-00:10 6894.75 05-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 15938.56 0.00 01-JAN-00:10 6979.59 19-JUL-13:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 15938.56 0.00 01-JAN-00:10 6979.59 19-JUL-13:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 25278.52 0.00 01-JAN-02:30 10239.35 30-AUG-17:10
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1480.98 0.00 01-JAN-00:10 6608.32 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1480.98 0.00 01-JAN-00:10 6608.32 05-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 23797.54 0.00 01-JAN-02:30 10239.35 30-AUG-17:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 23797.54 0.00 01-JAN-02:30 10239.35 30-AUG-17:10
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 20268.47 0.00 01-JAN-04:40 6333.95 13-OCT-14:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 738.35 0.00 01-JAN-00:10 4633.50 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 738.35 0.00 01-JAN-00:10 4633.50 05-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 19530.12 0.00 01-JAN-04:40 6333.95 13-OCT-14:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 19530.12 0.00 01-JAN-04:40 6333.95 13-OCT-14:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 25163.53 0.00 01-JAN-02:20 8327.34 10-SEP-15:50
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1369.53 0.00 01-JAN-00:10 6492.79 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1369.53 0.00 01-JAN-00:10 6492.79 05-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 23794.00 0.00 01-JAN-02:20 8327.34 10-SEP-15:50
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 23794.00 0.00 01-JAN-02:20 8327.34 10-SEP-15:50
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 22840.94 0.00 01-JAN-02:10 9453.20 12-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1929.83 0.00 01-JAN-00:10 6602.61 05-FEB-08:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1929.83 0.00 01-JAN-00:10 6602.61 05-FEB-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 20911.11 0.00 01-JAN-02:10 9453.20 12-JUN-17:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 20911.11 0.00 01-JAN-02:10 9453.20 12-JUN-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 17770.33 0.00 01-JAN-04:30 5856.93 18-JUL-18:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1154.54 0.00 01-JAN-00:10 4873.90 05-FEB-08:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1154.54 0.00 01-JAN-00:10 4873.90 05-FEB-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 16615.78 0.00 01-JAN-04:30 5856.93 18-JUL-18:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 16615.78 0.00 01-JAN-04:30 5856.93 18-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 22654.07 0.00 01-JAN-01:50 7668.48 10-SEP-10:50
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1796.42 0.00 01-JAN-00:10 6468.19 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1796.42 0.00 01-JAN-00:10 6468.19 05-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 20857.65 0.00 01-JAN-01:50 7668.48 10-SEP-10:50
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 20857.65 0.00 01-JAN-01:50 7668.48 10-SEP-10:50
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 26551.14 0.00 01-JAN-01:30 8934.12 10-SEP-16:20
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2739.21 0.00 01-JAN-00:10 7982.28 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2739.21 0.00 01-JAN-00:10 7982.28 05-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 23811.93 0.00 01-JAN-01:30 8934.12 10-SEP-16:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 23811.93 0.00 01-JAN-01:30 8934.12 10-SEP-16:20
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 27983.10 0.00 01-JAN-01:50 9324.50 10-SEP-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 2248.87 0.00 01-JAN-00:10 7999.59 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 2248.87 0.00 01-JAN-00:10 7999.59 05-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 25734.23 0.00 01-JAN-01:50 9324.50 10-SEP-16:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 25734.23 0.00 01-JAN-01:50 9324.50 10-SEP-16:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 28233.78 0.00 01-JAN-02:00 11498.23 30-AUG-17:10
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 2418.47 0.00 01-JAN-00:10 8149.31 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 2418.47 0.00 01-JAN-00:10 8149.31 05-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 25815.31 0.00 01-JAN-02:00 11498.23 30-AUG-17:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 25815.31 0.00 01-JAN-02:00 11498.23 30-AUG-17:10
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 21649.62 0.00 01-JAN-03:40 7486.05 18-JUL-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2017.18 0.00 01-JAN-00:10 6568.68 05-FEB-08:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2017.18 0.00 01-JAN-00:10 6568.68 05-FEB-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 19632.44 0.00 01-JAN-03:40 7486.05 18-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 19632.44 0.00 01-JAN-03:40 7486.05 18-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 23049.45 0.00 01-JAN-04:00 7601.87 10-SEP-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 1496.48 0.00 01-JAN-00:10 6564.14 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 1496.48 0.00 01-JAN-00:10 6564.14 05-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 21552.97 0.00 01-JAN-04:00 7601.87 10-SEP-17:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 21552.97 0.00 01-JAN-04:00 7601.87 10-SEP-17:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 26842.09 0.00 01-JAN-01:40 11326.94 30-AUG-17:10
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2918.93 0.00 01-JAN-00:10 8147.79 05-FEB-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2918.93 0.00 01-JAN-00:10 8147.79 05-FEB-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 23923.16 0.00 01-JAN-01:40 11326.94 30-AUG-17:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 23923.16 0.00 01-JAN-01:40 11326.94 30-AUG-17:10
PlantLoopHeatingDemand:Facility 44928.04 35.14 25-JUL-06:00 14304.77 01-JAN-09:00
PlantLoopHeatingDemand:Plant 44928.04 35.14 25-JUL-06:00 14304.77 01-JAN-09:00
WaterSystems:PlantLoopHeatingDemand 44928.04 35.14 25-JUL-06:00 14304.77 01-JAN-09:00
General:WaterSystems:PlantLoopHeatingDemand 44928.04 35.14 25-JUL-06:00 14304.77 01-JAN-09:00
EnergyTransfer:HVAC 596453.44 0.00 01-JAN-04:40 203835.65 10-SEP-16:10
HeatingCoils:EnergyTransfer 33664.35 0.00 01-JAN-00:10 112361.17 05-FEB-07:10
CoolingCoils:EnergyTransfer 562789.10 0.00 01-JAN-04:40 203835.65 10-SEP-16:10
EnergyTransfer:Plant 44928.04 35.14 25-JUL-06:00 14304.77 01-JAN-09:00
WaterSystems:EnergyTransfer 44928.04 35.14 25-JUL-06:00 14304.77 01-JAN-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 44928.04 35.14 25-JUL-06:00 14304.77 01-JAN-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 2329.380 -1523.43 0.000 0.000 2945.044 2294.076 10464.601 9497.843 0.000 2023.367 0.002 0.000 -2340.59 0.000 -4378.30 -4542.07
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 1468.724 -1192.42 0.000 0.000 2936.354 2294.076 10464.601 4219.728 0.000 1937.733 0.000 0.000 -947.32 0.000 -4223.07 -3832.24
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 2190.177 -1512.20 0.000 0.000 2945.775 2294.076 10464.601 9606.979 0.000 2022.874 0.006 0.000 -2282.41 0.000 -4395.62 -4687.88
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 2827.075 -1339.29 0.000 0.000 2951.810 2294.076 10464.601 7163.588 0.000 2023.972 0.001 0.000 -2404.36 0.000 -4301.79 -4936.76
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 2002.917 -1021.48 0.000 0.000 2946.615 2294.076 10464.601 1808.804 0.000 1938.552 0.000 0.000 -1006.63 0.000 -4118.42 -4064.51
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 2687.110 -1327.33 0.000 0.000 2953.662 2294.076 10464.601 7229.496 0.000 2023.143 0.000 0.000 -2295.62 0.000 -4309.36 -5108.45
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 1480.954 -1981.81 0.000 0.000 2921.415 2294.076 10464.601 9336.830 0.000 1616.907 1768.980 0.000 -2533.89 0.000 -3552.29 -0.15
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 738.339 -1626.43 0.000 0.000 2910.037 2294.076 10464.601 4150.433 0.000 1532.368 1863.627 0.000 -1026.41 0.000 -3396.84 -0.03
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 1369.505 -1981.52 0.000 0.000 2922.093 2294.076 10464.601 9433.038 0.000 1616.725 1728.509 0.000 -2467.15 0.000 -3567.24 -0.11
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 1929.802 -1741.43 0.000 0.000 2928.996 2294.076 10464.601 7026.726 0.000 1617.087 730.295 0.000 -2589.91 0.000 -3490.49 -0.01
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 1154.528 -1383.73 0.000 0.000 2922.228 2294.076 10464.601 1761.829 0.000 1532.550 881.445 0.000 -1084.47 0.000 -3310.89 -0.14
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 1796.388 -1736.99 0.000 0.000 2931.539 2294.076 10464.601 7078.575 0.000 1616.853 642.127 0.000 -2470.22 0.000 -3496.12 -0.04
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 2739.166 -1983.02 0.000 0.000 2935.939 2294.076 10464.601 7020.310 0.000 2004.136 3281.411 0.000 -2494.20 0.000 -4433.32 -0.35
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 2248.831 -2143.10 0.000 0.000 2929.444 2294.076 10464.601 9390.973 0.000 2004.026 3375.314 0.000 -2471.35 0.000 -4501.50 -0.12
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 2418.424 -2149.84 0.000 0.000 2928.801 2294.076 10464.601 9291.349 0.000 2004.271 3433.287 0.000 -2534.08 0.000 -4485.35 -0.32
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 2017.154 -1634.95 0.000 0.000 2927.773 2294.076 10464.601 1737.863 0.000 1920.483 3616.265 0.000 -1091.86 0.000 -4253.78 -0.01
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 1496.453 -1794.89 0.000 0.000 2919.405 2294.076 10464.601 4131.291 0.000 1920.207 3687.310 0.000 -1026.10 0.000 -4334.14 -0.02
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 2918.891 -1992.27 0.000 0.000 2934.122 2294.076 10464.601 6957.767 0.000 2004.683 3376.921 0.000 -2600.58 0.000 -4427.26 -0.26
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 24298.679 180449.841 0.000 0.000 0.000 -204748.52 -1.04
Total Facility 0.000 0.000 35813.820 -30066.16 0.000 0.000 52791.053 41293.362 188362.826 116843.423 0.000 57658.617 208835.341 0.000 -35667.13 0.000 -277724.31 -27174.51


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 30-AUG-16:10 0.00 0.00 0.00 -0.8 0.00 0.00 140.35 359.36 1350.56 6002.19 0.00 1604.29 131.71 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 30-AUG-16:10 0.00 0.00 0.00 -0.5 0.00 0.00 140.35 359.36 1350.56 993.68 0.00 1534.38 1331.23 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 10-SEP-15:20 0.00 0.00 0.00 -0.6 0.00 0.00 111.87 166.85 1168.29 2411.11 0.00 1407.23 1983.60 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 09-SEP-17:10 0.00 0.00 0.00 -0.7 0.00 0.00 263.16 500.54 1685.13 4331.17 0.00 1805.91 292.34 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 03-AUG-17:19 0.00 0.00 0.00 -0.4 0.00 0.00 263.05 500.54 1664.02 640.72 0.00 1348.82 777.84 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 19-JUL-12:02 0.00 0.00 0.00 -0.6 0.00 0.00 115.09 96.26 1090.63 2336.47 0.00 2026.34 1315.43 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 30-AUG-17:15 0.00 0.00 0.00 -0.9 0.00 0.00 263.16 500.54 1664.02 4709.46 0.00 1100.07 2002.21 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 13-OCT-14:30 0.00 0.00 0.00 -0.5 0.00 0.00 115.09 96.26 1091.85 2305.22 0.00 880.41 1845.27 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 10-SEP-15:20 0.00 0.00 0.00 -0.7 0.00 0.00 113.47 166.85 1168.29 2403.72 0.00 1151.07 3325.07 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12-JUN-17:36 0.00 0.00 0.00 -0.8 0.00 0.00 263.16 500.54 1664.02 4943.53 0.00 788.68 1293.85 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 18-JUL-18:30 0.00 0.00 0.00 -0.5 0.00 0.00 426.32 673.81 1724.99 589.57 0.00 774.46 1671.36 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 10-SEP-10:56 0.00 0.00 0.00 -0.6 0.00 0.00 114.52 96.26 1121.12 3986.33 0.00 1087.68 1265.43 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 10-SEP-16:19 0.00 0.00 0.00 -0.7 0.00 0.00 140.09 359.36 1371.36 1498.44 0.00 1285.16 4279.86 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 10-SEP-16:34 0.00 0.00 0.00 -0.8 0.00 0.00 139.55 359.36 1371.36 1584.80 0.00 1248.73 4620.80 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 30-AUG-17:15 0.00 0.00 0.00 -1.0 0.00 0.00 263.16 500.54 1664.02 4681.25 0.00 1349.26 3040.25 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 18-JUL-18:10 0.00 0.00 0.00 -0.6 0.00 0.00 426.76 673.81 1724.99 664.82 0.00 1120.66 2875.91 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 10-SEP-17:40 0.00 0.00 0.00 -0.6 0.00 0.00 262.76 500.54 1685.13 343.85 0.00 1020.28 3800.92 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 30-AUG-17:15 0.00 0.00 0.00 -0.9 0.00 0.00 263.16 500.54 1664.02 4654.94 0.00 1349.26 2895.18 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 09-SEP-17:15 0.00 0.00 0.00 -11.9 0.00 0.00 4727.41 9009.74 30332.38 39307.23 0.00 29170.77 69952.65 0.00 0.00 0.00 -39693.4 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 05-FEB-07:10 0.00 0.00 7038.48 0.00 0.00 0.00 473.02 320.86 1225.98 0.00 0.00 0.00 0.00 0.00 -2385.4 0.00 -4775.9 -1897.1
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 05-FEB-07:10 0.00 0.00 5606.11 0.00 0.00 0.00 466.72 320.86 1225.98 0.00 0.00 0.00 0.00 0.00 -975.8 0.00 -4551.4 -2092.5
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 05-FEB-07:10 0.00 0.00 6916.21 0.00 0.00 0.00 475.62 320.86 1225.98 0.00 0.00 0.00 0.00 0.00 -2391.4 0.00 -4753.2 -1794.1
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 05-FEB-07:10 0.00 0.00 7016.91 0.00 0.00 0.00 473.79 320.86 1225.98 0.00 0.00 0.00 0.00 0.00 -2391.8 0.00 -4769.2 -1876.5
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 05-FEB-08:09 0.00 0.00 5593.70 0.00 0.00 0.00 217.50 141.18 1179.68 0.00 0.00 0.00 0.00 0.00 -842.2 0.00 -4496.1 -1793.7
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 05-FEB-07:10 0.00 0.00 6894.84 0.00 0.00 0.00 476.33 320.86 1225.98 0.00 0.00 0.00 0.00 0.00 -2397.9 0.00 -4747.0 -1773.1
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 05-FEB-07:10 0.00 0.00 6608.38 0.00 0.00 0.00 464.72 320.86 1225.98 0.00 0.00 0.00 0.00 0.00 -2419.0 0.00 -3532.5 -2668.5
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 05-FEB-07:10 0.00 0.00 4633.55 0.00 0.00 0.00 464.72 320.86 1225.98 0.00 0.00 0.00 0.00 0.00 -985.5 0.00 -3252.3 -2407.3
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 05-FEB-07:10 0.00 0.00 6492.85 0.00 0.00 0.00 466.03 320.86 1225.98 0.00 0.00 0.00 0.00 0.00 -2434.3 0.00 -3522.5 -2548.9
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 05-FEB-08:09 0.00 0.00 6602.56 0.00 0.00 0.00 215.61 141.18 1179.68 0.00 0.00 0.00 0.00 0.00 -2077.1 0.00 -3483.8 -2578.1
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 05-FEB-08:09 0.00 0.00 4873.87 0.00 0.00 0.00 215.03 141.18 1179.68 0.00 0.00 0.00 0.00 0.00 -859.8 0.00 -3211.0 -2338.9
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 05-FEB-07:10 0.00 0.00 6468.25 0.00 0.00 0.00 466.71 320.86 1225.98 0.00 0.00 0.00 0.00 0.00 -2444.8 0.00 -3518.2 -2518.8
LIVING_UNIT3_BACKROW_TOPFLOOR 05-FEB-07:10 0.00 0.00 7982.37 0.00 0.00 0.00 478.24 320.86 1225.98 0.00 0.00 0.00 0.00 0.00 -2405.4 0.00 -4737.3 -2864.7
LIVING_UNIT3_FRONTROW_TOPFLOOR 05-FEB-07:10 0.00 0.00 7999.68 0.00 0.00 0.00 477.31 320.86 1225.98 0.00 0.00 0.00 0.00 0.00 -2394.3 0.00 -4745.7 -2883.8
LIVING_UNIT1_FRONTROW_TOPFLOOR 05-FEB-07:10 0.00 0.00 8149.40 0.00 0.00 0.00 474.20 320.86 1225.98 0.00 0.00 0.00 0.00 0.00 -2381.6 0.00 -4773.0 -3015.9
LIVING_UNIT2_BACKROW_TOPFLOOR 05-FEB-08:09 0.00 0.00 6568.66 0.00 0.00 0.00 218.35 141.18 1179.68 0.00 0.00 0.00 0.00 0.00 -847.8 0.00 -4488.2 -2771.9
LIVING_UNIT2_FRONTROW_TOPFLOOR 05-FEB-07:10 0.00 0.00 6564.22 0.00 0.00 0.00 467.88 320.86 1225.98 0.00 0.00 0.00 0.00 0.00 -975.8 0.00 -4549.3 -3053.9
LIVING_UNIT1_BACKROW_TOPFLOOR 05-FEB-07:10 0.00 0.00 8147.87 0.00 0.00 0.00 474.83 320.86 1225.98 0.00 0.00 0.00 0.00 0.00 -2393.7 0.00 -4767.5 -3008.4
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 05-FEB-07:10 0.00 0.00 119926.80 0.00 0.00 0.00 8465.48 5775.48 22067.69 0.00 0.00 6522.93 0.00 0.00 -34779.6 0.00 -76868.6 -51110.2



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 369.3708 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 369.3708 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 207.3617 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 207.3617 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 277.6727 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 277.6727 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 350.7666 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 350.7666 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 194.4715 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 194.4715 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 263.1512 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 263.1512 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 402.2637 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 402.2637 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 229.8527 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 229.8527 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 303.5092 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 303.5092 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 382.9801 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 382.9801 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 217.5021 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 217.5021 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 286.2634 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 286.2634 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 455.1205 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 455.1205 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 283.0494 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 283.0494 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 342.1281 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 342.1281 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 451.9927 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 451.9927 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 281.5178 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 281.5178 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.4378 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 330.4378 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 369.3708 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 369.3708 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 207.3617 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 207.3617 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 277.6727 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 277.6727 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 350.7666 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 350.7666 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 194.4715 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 194.4715 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 263.1512 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 263.1512 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 402.2637 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 402.2637 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 229.8527 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 229.8527 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 303.5092 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 303.5092 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 382.9801 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 382.9801 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 217.5021 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 217.5021 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 286.2634 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 286.2634 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 455.1205 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 455.1205 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 283.0494 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 283.0494 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 342.1281 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 342.1281 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 451.9927 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 451.9927 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 281.5178 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 281.5178 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.4378 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 330.4378 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 369.3708 369.3708 369.3708 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 207.3617 207.3617 207.3617 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 277.6727 277.6727 277.6727 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 350.7666 350.7666 350.7666 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 194.4715 194.4715 194.4715 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 263.1512 263.1512 263.1512 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 402.2637 402.2637 402.2637 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 229.8527 229.8527 229.8527 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 303.5092 303.5092 303.5092 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 382.9801 382.9801 382.9801 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 217.5021 217.5021 217.5021 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 286.2634 286.2634 286.2634 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 330.4378 330.4378 330.4378 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 342.1281 342.1281 342.1281 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 455.1205 455.1205 455.1205 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 281.5178 281.5178 281.5178 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 283.0494 283.0494 283.0494 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 451.9927 451.9927 451.9927 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 369.3708 369.3708 369.3708 369.3708 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 207.3617 207.3617 207.3617 207.3617 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 277.6727 277.6727 277.6727 277.6727 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 350.7666 350.7666 350.7666 350.7666 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 194.4715 194.4715 194.4715 194.4715 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 263.1512 263.1512 263.1512 263.1512 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 402.2637 402.2637 402.2637 402.2637 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 229.8527 229.8527 229.8527 229.8527 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 303.5092 303.5092 303.5092 303.5092 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 382.9801 382.9801 382.9801 382.9801 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 217.5021 217.5021 217.5021 217.5021 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 286.2634 286.2634 286.2634 286.2634 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 455.1205 455.1205 455.1205 455.1205 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 283.0494 283.0494 283.0494 283.0494 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 342.1281 342.1281 342.1281 342.1281 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 451.9927 451.9927 451.9927 451.9927 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 281.5178 281.5178 281.5178 281.5178 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.4378 330.4378 330.4378 330.4378 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 369.3708 369.3708 369.3708 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 207.3617 207.3617 207.3617 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 277.6727 277.6727 277.6727 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 350.7666 350.7666 350.7666 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 194.4715 194.4715 194.4715 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 263.1512 263.1512 263.1512 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 402.2637 402.2637 402.2637 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 229.8527 229.8527 229.8527 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 303.5092 303.5092 303.5092 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 382.9801 382.9801 382.9801 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 217.5021 217.5021 217.5021 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 286.2634 286.2634 286.2634 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 330.4378 330.4378 330.4378 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 342.1281 342.1281 342.1281 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 455.1205 455.1205 455.1205 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 281.5178 281.5178 281.5178 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 283.0494 283.0494 283.0494 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 451.9927 451.9927 451.9927 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 369.3708 369.3708 369.3708 369.3708 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 207.3617 207.3617 207.3617 207.3617 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 277.6727 277.6727 277.6727 277.6727 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 350.7666 350.7666 350.7666 350.7666 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 194.4715 194.4715 194.4715 194.4715 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 263.1512 263.1512 263.1512 263.1512 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 402.2637 402.2637 402.2637 402.2637 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 229.8527 229.8527 229.8527 229.8527 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 303.5092 303.5092 303.5092 303.5092 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 382.9801 382.9801 382.9801 382.9801 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 217.5021 217.5021 217.5021 217.5021 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 286.2634 286.2634 286.2634 286.2634 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 455.1205 455.1205 455.1205 455.1205 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 283.0494 283.0494 283.0494 283.0494 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 342.1281 342.1281 342.1281 342.1281 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 451.9927 451.9927 451.9927 451.9927 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 281.5178 281.5178 281.5178 281.5178 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.4378 330.4378 330.4378 330.4378 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Sec1.1A-General Information

Data
Weather File ANNUAL ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Total gross floor area [ft2] 31210.83
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
BREEZEWAY 1798.16 0.00 1798.16 0.00
ATTIC 7802.71 0.00 7802.71 0.00
Totals 31210.83 21609.96 9600.87  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 5.00
Number of hours cooling loads not met 16.33
Number of hours not met 21.33


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 9859.47 32931.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 36151.33 14633.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 12093.82 3939.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Exterior-Lights 6034.31 1377.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- dishwasher 3088.82 985.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- refrigerator 12036.11 1639.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- clotheswasher 1577.30 427.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_dryer 12502.11 3196.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_range 9058.39 3721.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_mels 46926.68 7929.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- IECC_adj 3113.66 526.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation 5068.29 578.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 6189.53 2110.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 34200.24 54383.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 301503.54 675713.41
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 301503.54 675713.41


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.39
Space Heating 0.32
Space Cooling 1.16
Fans (All) 0.36
Service Water Heating 1.10
Receptacle Equipment 2.83
Miscellaneous (All) 6.34
Subtotal 6.34


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.11
Space Heating 4.98
Space Cooling 18.27
Fans (All) 5.69
Service Water Heating 17.28
Receptacle Equipment 44.62
Miscellaneous 3.05


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OCCUPANCY 6031. 8760.
INTERIORLIGHTING 2852. 8760.
INTERIORLIGHTINGHE 3070. 8760.
INTERIORLIGHTINGHE_OS 2910. 8760.
INTERIORLIGHTINGHE_VS 2149. 8760.
EXTERIORLIGHTING 4380. 4380.
REFRIGERATOR 7343. 8760.
MISCPLUGLOAD 5918. 8760.
COOKINGRANGE 2434. 8760.
DISHWASHER_FLOW_SCH 2642. 8760.
CLOTHESWASHER_FLOW_SCH 3113. 8760.
DISHWASHER_EQUIP_SCH 3134. 8760.
CLOTHESWASHER_EQUIP_SCH 3692. 8760.
CLOTHESDRYER 3911. 8760.
SHADING_2012IECC 0. 0.
SHADING_2012IECC_HERS 7007. 8760.
SINKSENSSCHEDULE 6025. 8760.
SINKLATSCHEDULE 2735. 8760.
SHOWERSENSSCHEDULE 4492. 8760.
SHOWERLATSCHEDULE 4268. 8760.
BATHSENSSCHEDULE 8760. 8760.
BATHLATSCHEDULE 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
HEATING_SCH THERMOSTAT_LIVING DUAL SP CONTROL January 72.00 365 72.00 365
COOLING_SCH THERMOSTAT_LIVING DUAL SP CONTROL July 75.00 365 75.00 365



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupiedHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 16:15:55

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupiedHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 202.111 5.735 324.500 20.441 20.441
February 224.336 7.493 227.000 16.726 16.726
March 284.236 8.592 237.556 16.599 16.599
April 478.014 15.683 47.556 16.451 16.451
May 744.000 33.580 0.000 33.580 33.580
June 720.000 40.212 0.000 40.212 40.212
July 744.000 44.954 0.000 44.954 44.954
August 744.000 43.837 0.000 43.837 43.837
September 720.000 38.750 0.000 38.750 38.750
October 650.692 30.197 26.000 30.541 30.541
November 418.764 13.662 118.056 16.414 16.414
December 278.806 9.198 267.194 19.659 19.659
           
Annual Sum or Average 6208.958 291.892 1247.861 338.164 338.164
Minimum of Months 202.111 5.735 0.000 16.414 16.414
Maximum of Months 744.000 44.954 324.500 44.954 44.954



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 199.153 3.925 287.444 10.665 10.665
February 230.828 5.243 176.806 9.515 9.515
March 304.450 6.000 202.450 9.649 9.649
April 513.750 10.993 34.167 11.200 11.200
May 744.000 26.341 0.000 26.341 26.341
June 720.000 31.896 0.000 31.896 31.896
July 744.000 36.274 0.000 36.274 36.274
August 744.000 35.439 0.000 35.439 35.439
September 720.000 31.889 0.000 31.889 31.889
October 663.419 24.344 9.667 24.420 24.420
November 454.347 11.066 74.542 11.991 11.991
December 308.833 7.082 235.819 11.739 11.739
           
Annual Sum or Average 6346.781 230.491 1020.894 251.018 251.018
Minimum of Months 199.153 3.925 0.000 9.515 9.515
Maximum of Months 744.000 36.274 287.444 36.274 36.274



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 201.903 4.829 309.472 15.457 15.457
February 230.069 6.575 212.417 13.192 13.192
March 307.250 8.440 224.972 14.175 14.175
April 499.736 15.009 39.333 15.510 15.510
May 744.000 33.888 0.000 33.888 33.888
June 720.000 39.813 0.000 39.813 39.813
July 744.000 44.617 0.000 44.617 44.617
August 744.000 42.904 0.000 42.904 42.904
September 720.000 37.788 0.000 37.788 37.788
October 655.278 29.285 23.167 29.515 29.515
November 434.897 12.979 104.000 14.812 14.812
December 279.403 8.058 260.333 15.771 15.771
           
Annual Sum or Average 6280.536 284.186 1173.694 317.443 317.443
Minimum of Months 201.903 4.829 0.000 13.192 13.192
Maximum of Months 744.000 44.617 309.472 44.617 44.617



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 122.250 2.537 413.611 20.149 20.149
February 167.458 3.988 279.583 14.799 14.799
March 256.167 6.260 258.042 14.560 14.560
April 464.861 13.869 50.611 14.637 14.637
May 744.000 33.243 0.000 33.243 33.243
June 720.000 40.419 0.000 40.419 40.419
July 744.000 44.839 0.000 44.839 44.839
August 744.000 42.640 0.000 42.640 42.640
September 720.000 36.425 0.000 36.425 36.425
October 640.250 25.782 30.167 26.172 26.172
November 357.819 8.379 150.006 11.772 11.772
December 205.167 4.785 324.333 16.996 16.996
           
Annual Sum or Average 5885.972 263.167 1506.353 316.652 316.652
Minimum of Months 122.250 2.537 0.000 11.772 11.772
Maximum of Months 744.000 44.839 413.611 44.839 44.839



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 111.028 1.328 429.417 10.485 10.485
February 154.417 1.987 253.650 7.534 7.534
March 261.028 3.857 237.389 7.847 7.847
April 488.250 9.223 36.639 9.435 9.435
May 744.000 25.984 0.000 25.984 25.984
June 720.000 32.054 0.000 32.054 32.054
July 744.000 36.082 0.000 36.082 36.082
August 744.000 34.197 0.000 34.197 34.197
September 720.000 29.550 0.000 29.550 29.550
October 644.972 19.908 12.583 20.004 20.004
November 360.667 5.899 114.667 7.235 7.235
December 208.444 3.025 310.917 9.014 9.014
           
Annual Sum or Average 5900.806 203.095 1395.261 229.420 229.420
Minimum of Months 111.028 1.328 0.000 7.235 7.235
Maximum of Months 744.000 36.082 429.417 36.082 36.082



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 120.858 1.887 418.722 14.892 14.892
February 174.031 3.067 271.292 10.876 10.876
March 275.986 6.043 253.722 12.027 12.027
April 485.292 13.145 40.250 13.638 13.638
May 744.000 33.468 0.000 33.468 33.468
June 720.000 39.878 0.000 39.878 39.878
July 744.000 44.370 0.000 44.370 44.370
August 744.000 41.683 0.000 41.683 41.683
September 720.000 35.525 0.000 35.525 35.525
October 641.625 24.939 25.667 25.183 25.183
November 361.681 7.615 136.694 9.773 9.773
December 204.861 3.799 326.611 12.887 12.887
           
Annual Sum or Average 5936.333 255.419 1472.958 294.202 294.202
Minimum of Months 120.858 1.887 0.000 9.773 9.773
Maximum of Months 744.000 44.370 418.722 44.370 44.370



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 296.000 9.642 239.708 20.774 20.774
February 321.497 11.962 140.650 18.825 18.825
March 404.139 13.958 166.567 19.766 19.766
April 593.111 23.646 23.931 23.892 23.892
May 744.000 42.801 0.000 42.801 42.801
June 720.000 45.303 0.000 45.303 45.303
July 744.000 49.004 0.000 49.004 49.004
August 744.000 47.677 0.000 47.677 47.677
September 720.000 42.502 0.000 42.502 42.502
October 682.236 37.505 11.000 37.673 37.673
November 497.972 19.757 68.708 21.471 21.471
December 379.833 14.181 212.361 22.268 22.268
           
Annual Sum or Average 6846.789 357.938 862.925 391.955 391.955
Minimum of Months 296.000 9.642 0.000 18.825 18.825
Maximum of Months 744.000 49.004 239.708 49.004 49.004



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 344.542 8.044 180.708 12.351 12.351
February 369.544 9.924 105.167 12.737 12.737
March 440.514 11.409 122.333 13.626 13.626
April 643.722 18.832 3.050 18.844 18.844
May 744.000 34.561 0.000 34.561 34.561
June 720.000 36.126 0.000 36.126 36.126
July 744.000 39.565 0.000 39.565 39.565
August 744.000 38.551 0.000 38.551 38.551
September 720.000 35.109 0.000 35.109 35.109
October 698.778 31.128 4.333 31.152 31.152
November 549.750 17.386 38.806 17.722 17.722
December 423.222 12.285 153.333 15.250 15.250
           
Annual Sum or Average 7142.072 292.921 607.731 305.595 305.595
Minimum of Months 344.542 8.044 0.000 12.351 12.351
Maximum of Months 744.000 39.565 180.708 39.565 39.565



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 299.597 8.696 222.625 16.634 16.634
February 331.006 11.064 132.500 15.919 15.919
March 426.389 14.100 152.500 18.209 18.209
April 611.722 23.112 16.833 23.259 23.259
May 744.000 42.921 0.000 42.921 42.921
June 720.000 44.868 0.000 44.868 44.868
July 744.000 48.728 0.000 48.728 48.728
August 744.000 46.729 0.000 46.729 46.729
September 720.000 41.523 0.000 41.523 41.523
October 687.083 36.414 9.667 36.520 36.520
November 516.339 19.166 58.028 20.246 20.246
December 384.306 12.896 204.222 18.849 18.849
           
Annual Sum or Average 6928.442 350.218 796.375 374.407 374.407
Minimum of Months 299.597 8.696 0.000 15.919 15.919
Maximum of Months 744.000 48.728 222.625 48.728 48.728



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 196.075 4.900 332.722 19.346 19.346
February 261.431 7.318 187.581 15.909 15.909
March 371.000 10.990 185.972 17.206 17.206
April 584.597 21.604 26.042 21.862 21.862
May 744.000 42.431 0.000 42.431 42.431
June 720.000 45.531 0.000 45.531 45.531
July 744.000 48.903 0.000 48.903 48.903
August 744.000 46.424 0.000 46.424 46.424
September 720.000 40.032 0.000 40.032 40.032
October 673.875 32.646 13.000 32.854 32.854
November 442.694 13.238 96.333 15.648 15.648
December 308.000 8.393 268.056 18.611 18.611
           
Annual Sum or Average 6509.672 322.412 1109.706 364.757 364.757
Minimum of Months 196.075 4.900 0.000 15.648 15.648
Maximum of Months 744.000 48.903 332.722 48.903 48.903



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 202.528 3.593 315.972 10.396 10.396
February 287.608 5.213 163.000 9.342 9.342
March 394.125 8.447 153.250 11.007 11.007
April 632.389 16.730 3.467 16.744 16.744
May 744.000 34.173 0.000 34.173 34.173
June 720.000 36.328 0.000 36.328 36.328
July 744.000 39.426 0.000 39.426 39.426
August 744.000 37.279 0.000 37.279 37.279
September 720.000 32.614 0.000 32.614 32.614
October 684.028 26.189 6.000 26.234 26.234
November 469.333 10.684 71.778 11.424 11.424
December 307.056 6.479 235.972 11.000 11.000
           
Annual Sum or Average 6649.067 257.154 949.439 275.967 275.967
Minimum of Months 202.528 3.593 0.000 9.342 9.342
Maximum of Months 744.000 39.426 315.972 39.426 39.426



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 188.278 4.167 347.875 14.574 14.574
February 268.644 6.363 175.083 12.442 12.442
March 389.597 11.098 172.917 15.415 15.415
April 609.083 21.042 17.667 21.192 21.192
May 744.000 42.417 0.000 42.417 42.417
June 720.000 44.903 0.000 44.903 44.903
July 744.000 48.445 0.000 48.445 48.445
August 744.000 45.414 0.000 45.414 45.414
September 720.000 39.078 0.000 39.078 39.078
October 676.528 31.613 11.667 31.734 31.734
November 458.847 12.529 78.319 13.930 13.930
December 291.111 7.236 268.889 14.801 14.801
           
Annual Sum or Average 6554.089 314.303 1072.417 344.344 344.344
Minimum of Months 188.278 4.167 0.000 12.442 12.442
Maximum of Months 744.000 48.445 347.875 48.445 48.445



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 252.458 9.138 287.167 25.315 25.315
February 288.803 11.962 178.944 22.008 22.008
March 369.694 14.507 198.722 23.218 23.218
April 571.167 25.675 37.083 26.310 26.310
May 744.000 48.721 0.000 48.721 48.721
June 720.000 51.293 0.000 51.293 51.293
July 744.000 55.411 0.000 55.411 55.411
August 744.000 53.460 0.000 53.460 53.460
September 720.000 46.893 0.000 46.893 46.893
October 666.558 41.096 21.000 41.496 41.496
November 470.667 20.075 96.333 23.094 23.094
December 351.944 14.063 246.972 26.230 26.230
           
Annual Sum or Average 6643.292 392.293 1066.222 443.449 443.449
Minimum of Months 252.458 9.138 0.000 22.008 22.008
Maximum of Months 744.000 55.411 287.167 55.411 55.411



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 286.500 7.536 241.972 15.426 15.426
February 316.394 9.935 139.417 15.025 15.025
March 400.819 12.013 166.556 16.280 16.280
April 608.111 20.876 18.125 20.986 20.986
May 744.000 40.596 0.000 40.596 40.596
June 720.000 42.229 0.000 42.229 42.229
July 744.000 46.078 0.000 46.078 46.078
August 744.000 44.454 0.000 44.454 44.454
September 720.000 39.664 0.000 39.664 39.664
October 683.125 34.828 8.833 34.935 34.935
November 507.972 17.679 63.556 18.758 18.758
December 379.292 12.144 212.500 17.996 17.996
           
Annual Sum or Average 6854.214 328.031 850.958 352.425 352.425
Minimum of Months 286.500 7.536 0.000 15.025 15.025
Maximum of Months 744.000 46.078 241.972 46.078 46.078



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 256.778 8.171 273.006 19.736 19.736
February 300.525 11.008 166.861 18.159 18.159
March 390.403 14.505 186.056 20.673 20.673
April 590.861 25.001 27.333 25.363 25.363
May 744.000 48.657 0.000 48.657 48.657
June 720.000 50.675 0.000 50.675 50.675
July 744.000 54.938 0.000 54.938 54.938
August 744.000 52.354 0.000 52.354 52.354
September 720.000 45.812 0.000 45.812 45.812
October 670.667 39.884 18.333 40.144 40.144
November 486.889 19.339 82.500 21.272 21.272
December 348.361 12.748 244.222 21.706 21.706
           
Annual Sum or Average 6716.483 383.092 998.311 419.488 419.488
Minimum of Months 256.778 8.171 0.000 18.159 18.159
Maximum of Months 744.000 54.938 273.006 54.938 54.938



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 190.472 5.666 359.889 25.848 25.848
February 251.361 8.769 215.361 20.796 20.796
March 351.944 12.897 210.944 22.162 22.162
April 565.750 24.775 39.125 25.439 25.439
May 744.000 48.715 0.000 48.715 48.715
June 720.000 51.593 0.000 51.593 51.593
July 744.000 55.526 0.000 55.526 55.526
August 744.000 52.997 0.000 52.997 52.997
September 720.000 45.681 0.000 45.681 45.681
October 659.500 37.944 24.750 38.425 38.425
November 427.889 15.177 121.611 19.102 19.102
December 300.222 9.565 291.500 24.355 24.355
           
Annual Sum or Average 6419.139 369.305 1263.181 430.638 430.638
Minimum of Months 190.472 5.666 0.000 19.102 19.102
Maximum of Months 744.000 55.526 359.889 55.526 55.526



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 191.847 4.266 356.583 15.581 15.581
February 261.603 6.649 186.597 13.355 13.355
March 380.167 10.371 188.167 15.126 15.126
April 601.861 19.953 20.264 20.077 20.077
May 744.000 40.597 0.000 40.597 40.597
June 720.000 42.534 0.000 42.534 42.534
July 744.000 46.195 0.000 46.195 46.195
August 744.000 43.995 0.000 43.995 43.995
September 720.000 38.456 0.000 38.456 38.456
October 672.778 31.614 12.083 31.759 31.759
November 445.944 12.584 88.694 14.265 14.265
December 295.500 7.609 274.833 15.597 15.597
           
Annual Sum or Average 6521.700 304.823 1127.222 337.537 337.537
Minimum of Months 191.847 4.266 0.000 13.355 13.355
Maximum of Months 744.000 46.195 356.583 46.195 46.195



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 182.208 4.852 375.625 19.242 19.242
February 255.200 7.755 202.567 16.144 16.144
March 374.556 12.870 200.225 19.244 19.244
April 588.194 24.047 28.083 24.408 24.408
May 744.000 48.461 0.000 48.461 48.461
June 720.000 50.737 0.000 50.737 50.737
July 744.000 54.811 0.000 54.811 54.811
August 744.000 51.727 0.000 51.727 51.727
September 720.000 44.525 0.000 44.525 44.525
October 664.411 36.717 20.667 37.007 37.007
November 441.028 14.329 104.833 16.702 16.702
December 284.750 8.331 291.806 19.063 19.063
           
Annual Sum or Average 6462.347 359.162 1223.806 402.071 402.071
Minimum of Months 182.208 4.852 0.000 16.144 16.144
Maximum of Months 744.000 54.811 375.625 54.811 54.811



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 926.91 0.00 0.00
February 644.33 0.00 0.00
March 504.68 0.00 0.00
April 50.07 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 21.65 0.00 0.00
November 179.22 0.00 0.00
December 659.38 0.00 0.00
       
Annual Sum or Average 247.70 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 926.91 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 616.86 0.00 0.00
February 432.94 0.00 0.00
March 333.96 0.00 0.00
April 19.59 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 6.91 0.00 0.00
November 87.47 0.00 0.00
December 426.22 0.00 0.00
       
Annual Sum or Average 159.55 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 616.86 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 891.42 0.00 0.00
February 614.39 0.00 0.00
March 480.99 0.00 0.00
April 43.41 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 19.35 0.00 0.00
November 158.81 0.00 0.00
December 646.84 0.00 0.00
       
Annual Sum or Average 236.89 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 891.42 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1169.64 0.00 0.00
February 794.84 0.00 0.00
March 551.18 0.00 0.00
April 52.72 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 25.90 0.00 0.00
November 232.82 0.00 0.00
December 810.91 0.00 0.00
       
Annual Sum or Average 301.67 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1169.64 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 893.76 0.00 0.00
February 599.34 0.00 0.00
March 389.36 0.00 0.00
April 21.36 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 9.45 0.00 0.00
November 134.68 0.00 0.00
December 584.56 0.00 0.00
       
Annual Sum or Average 218.23 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 893.76 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1150.65 0.00 0.00
February 764.92 0.00 0.00
March 529.48 0.00 0.00
April 45.06 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 21.65 0.00 0.00
November 197.34 0.00 0.00
December 804.07 0.00 0.00
       
Annual Sum or Average 291.43 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1150.65 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 599.88 0.00 0.00
February 409.49 0.00 0.00
March 312.94 0.00 0.00
April 13.71 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 9.07 0.00 0.00
November 95.43 0.00 0.00
December 435.78 0.00 0.00
       
Annual Sum or Average 155.69 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 599.88 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 317.20 0.00 0.00
February 229.40 0.00 0.00
March 163.32 0.00 0.00
April 0.95 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 1.75 0.00 0.00
November 25.57 0.00 0.00
December 218.44 0.00 0.00
       
Annual Sum or Average 79.29 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 317.20 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 567.25 0.00 0.00
February 384.13 0.00 0.00
March 293.62 0.00 0.00
April 10.80 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 7.60 0.00 0.00
November 79.78 0.00 0.00
December 425.45 0.00 0.00
       
Annual Sum or Average 146.81 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 567.25 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 817.96 0.00 0.00
February 538.57 0.00 0.00
March 352.00 0.00 0.00
April 15.10 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 11.75 0.00 0.00
November 140.96 0.00 0.00
December 578.62 0.00 0.00
       
Annual Sum or Average 203.65 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 817.96 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 529.60 0.00 0.00
February 355.88 0.00 0.00
March 199.26 0.00 0.00
April 1.17 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 3.49 0.00 0.00
November 59.57 0.00 0.00
December 351.86 0.00 0.00
       
Annual Sum or Average 124.38 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 529.60 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 788.13 0.00 0.00
February 509.70 0.00 0.00
March 326.99 0.00 0.00
April 11.73 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 9.23 0.00 0.00
November 109.62 0.00 0.00
December 572.91 0.00 0.00
       
Annual Sum or Average 193.22 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 788.13 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 953.04 0.00 0.00
February 655.27 0.00 0.00
March 513.22 0.00 0.00
April 38.64 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 23.58 0.00 0.00
November 183.75 0.00 0.00
December 716.75 0.00 0.00
       
Annual Sum or Average 255.95 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 953.04 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 613.90 0.00 0.00
February 438.48 0.00 0.00
March 332.05 0.00 0.00
April 8.84 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 8.32 0.00 0.00
November 86.68 0.00 0.00
December 455.33 0.00 0.00
       
Annual Sum or Average 161.21 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 613.90 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 906.77 0.00 0.00
February 620.72 0.00 0.00
March 483.57 0.00 0.00
April 29.27 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 20.40 0.00 0.00
November 156.60 0.00 0.00
December 702.34 0.00 0.00
       
Annual Sum or Average 242.36 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 906.77 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1197.49 0.00 0.00
February 790.06 0.00 0.00
March 549.75 0.00 0.00
April 40.71 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 28.54 0.00 0.00
November 240.63 0.00 0.00
December 877.53 0.00 0.00
       
Annual Sum or Average 309.08 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1197.49 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 885.15 0.00 0.00
February 580.84 0.00 0.00
March 371.95 0.00 0.00
April 10.03 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 11.39 0.00 0.00
November 135.93 0.00 0.00
December 624.92 0.00 0.00
       
Annual Sum or Average 217.36 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 885.15 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1167.83 0.00 0.00
February 753.78 0.00 0.00
March 517.25 0.00 0.00
April 30.27 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 23.53 0.00 0.00
November 199.04 0.00 0.00
December 870.96 0.00 0.00
       
Annual Sum or Average 295.76 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1167.83 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.09
March 0.00 0.00 0.09
April 0.00 0.00 0.18
May 0.00 0.00 0.37
June 0.00 0.00 0.46
July 0.00 0.00 0.51
August 0.00 0.00 0.49
September 0.00 0.00 0.45
October 0.00 0.00 0.34
November 0.00 0.00 0.16
December 0.00 0.00 0.10
       
Annual Sum or Average 0.00 0.00 0.28
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.51



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.07
March 0.00 0.00 0.07
April 0.00 0.00 0.13
May 0.00 0.00 0.30
June 0.00 0.00 0.38
July 0.00 0.00 0.43
August 0.00 0.00 0.42
September 0.00 0.00 0.39
October 0.00 0.00 0.29
November 0.00 0.00 0.13
December 0.00 0.00 0.08
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.08
March 0.00 0.00 0.09
April 0.00 0.00 0.17
May 0.00 0.00 0.39
June 0.00 0.00 0.47
July 0.00 0.00 0.52
August 0.00 0.00 0.50
September 0.00 0.00 0.46
October 0.00 0.00 0.34
November 0.00 0.00 0.15
December 0.00 0.00 0.09
       
Annual Sum or Average 0.00 0.00 0.28
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.05
March 0.00 0.00 0.07
April 0.00 0.00 0.16
May 0.00 0.00 0.37
June 0.00 0.00 0.47
July 0.00 0.00 0.51
August 0.00 0.00 0.48
September 0.00 0.00 0.43
October 0.00 0.00 0.29
November 0.00 0.00 0.10
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.25
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.51



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.03
March 0.00 0.00 0.04
April 0.00 0.00 0.11
May 0.00 0.00 0.30
June 0.00 0.00 0.39
July 0.00 0.00 0.43
August 0.00 0.00 0.41
September 0.00 0.00 0.37
October 0.00 0.00 0.23
November 0.00 0.00 0.07
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.04
March 0.00 0.00 0.07
April 0.00 0.00 0.15
May 0.00 0.00 0.38
June 0.00 0.00 0.47
July 0.00 0.00 0.52
August 0.00 0.00 0.49
September 0.00 0.00 0.43
October 0.00 0.00 0.29
November 0.00 0.00 0.09
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.25
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.11
February 0.00 0.00 0.15
March 0.00 0.00 0.15
April 0.00 0.00 0.27
May 0.00 0.00 0.47
June 0.00 0.00 0.51
July 0.00 0.00 0.54
August 0.00 0.00 0.53
September 0.00 0.00 0.49
October 0.00 0.00 0.41
November 0.00 0.00 0.22
December 0.00 0.00 0.16
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.11
Maximum of Months 0.00 0.00 0.54



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.09
February 0.00 0.00 0.13
March 0.00 0.00 0.13
April 0.00 0.00 0.22
May 0.00 0.00 0.40
June 0.00 0.00 0.43
July 0.00 0.00 0.46
August 0.00 0.00 0.45
September 0.00 0.00 0.42
October 0.00 0.00 0.36
November 0.00 0.00 0.20
December 0.00 0.00 0.14
       
Annual Sum or Average 0.00 0.00 0.29
Minimum of Months 0.00 0.00 0.09
Maximum of Months 0.00 0.00 0.46



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.10
February 0.00 0.00 0.14
March 0.00 0.00 0.16
April 0.00 0.00 0.27
May 0.00 0.00 0.48
June 0.00 0.00 0.52
July 0.00 0.00 0.56
August 0.00 0.00 0.53
September 0.00 0.00 0.49
October 0.00 0.00 0.41
November 0.00 0.00 0.22
December 0.00 0.00 0.14
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.10
Maximum of Months 0.00 0.00 0.56



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.09
March 0.00 0.00 0.12
April 0.00 0.00 0.24
May 0.00 0.00 0.47
June 0.00 0.00 0.52
July 0.00 0.00 0.54
August 0.00 0.00 0.52
September 0.00 0.00 0.46
October 0.00 0.00 0.36
November 0.00 0.00 0.15
December 0.00 0.00 0.09
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.54



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.07
March 0.00 0.00 0.10
April 0.00 0.00 0.20
May 0.00 0.00 0.39
June 0.00 0.00 0.43
July 0.00 0.00 0.46
August 0.00 0.00 0.43
September 0.00 0.00 0.39
October 0.00 0.00 0.30
November 0.00 0.00 0.13
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.25
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.46



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.08
March 0.00 0.00 0.12
April 0.00 0.00 0.24
May 0.00 0.00 0.48
June 0.00 0.00 0.53
July 0.00 0.00 0.56
August 0.00 0.00 0.52
September 0.00 0.00 0.46
October 0.00 0.00 0.36
November 0.00 0.00 0.14
December 0.00 0.00 0.08
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.56



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.10
February 0.00 0.00 0.15
March 0.00 0.00 0.16
April 0.00 0.00 0.29
May 0.00 0.00 0.53
June 0.00 0.00 0.58
July 0.00 0.00 0.62
August 0.00 0.00 0.59
September 0.00 0.00 0.54
October 0.00 0.00 0.46
November 0.00 0.00 0.23
December 0.00 0.00 0.16
       
Annual Sum or Average 0.00 0.00 0.37
Minimum of Months 0.00 0.00 0.10
Maximum of Months 0.00 0.00 0.62



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.09
February 0.00 0.00 0.12
March 0.00 0.00 0.13
April 0.00 0.00 0.24
May 0.00 0.00 0.46
June 0.00 0.00 0.50
July 0.00 0.00 0.53
August 0.00 0.00 0.51
September 0.00 0.00 0.48
October 0.00 0.00 0.40
November 0.00 0.00 0.21
December 0.00 0.00 0.14
       
Annual Sum or Average 0.00 0.00 0.32
Minimum of Months 0.00 0.00 0.09
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.09
February 0.00 0.00 0.14
March 0.00 0.00 0.16
April 0.00 0.00 0.29
May 0.00 0.00 0.55
June 0.00 0.00 0.59
July 0.00 0.00 0.63
August 0.00 0.00 0.60
September 0.00 0.00 0.54
October 0.00 0.00 0.45
November 0.00 0.00 0.22
December 0.00 0.00 0.14
       
Annual Sum or Average 0.00 0.00 0.37
Minimum of Months 0.00 0.00 0.09
Maximum of Months 0.00 0.00 0.63



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.11
March 0.00 0.00 0.14
April 0.00 0.00 0.28
May 0.00 0.00 0.54
June 0.00 0.00 0.59
July 0.00 0.00 0.62
August 0.00 0.00 0.59
September 0.00 0.00 0.53
October 0.00 0.00 0.42
November 0.00 0.00 0.17
December 0.00 0.00 0.11
       
Annual Sum or Average 0.00 0.00 0.35
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.62



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.08
March 0.00 0.00 0.12
April 0.00 0.00 0.23
May 0.00 0.00 0.46
June 0.00 0.00 0.50
July 0.00 0.00 0.54
August 0.00 0.00 0.51
September 0.00 0.00 0.46
October 0.00 0.00 0.36
November 0.00 0.00 0.15
December 0.00 0.00 0.09
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.54



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.10
March 0.00 0.00 0.14
April 0.00 0.00 0.28
May 0.00 0.00 0.55
June 0.00 0.00 0.59
July 0.00 0.00 0.63
August 0.00 0.00 0.59
September 0.00 0.00 0.53
October 0.00 0.00 0.42
November 0.00 0.00 0.17
December 0.00 0.00 0.09
       
Annual Sum or Average 0.00 0.00 0.35
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.68 656.44
February 0.00 0.00 874.17 587.86
March 0.00 0.00 828.75 617.03
April 0.00 0.00 762.42 549.33
May 0.00 0.00 686.61 511.20
June 0.00 0.00 627.05 451.80
July 0.00 0.00 600.97 447.44
August 0.00 0.00 605.59 450.88
September 0.00 0.00 653.38 470.77
October 0.00 0.00 722.02 537.56
November 0.00 0.00 794.15 572.19
December 0.00 0.00 855.12 636.66
         
Annual Sum or Average 0.00 0.00 740.24 6489.14
Minimum of Months 0.00 0.00 600.97 447.44
Maximum of Months 0.00 0.00 881.68 656.44



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.54 656.33
February 0.00 0.00 874.18 587.87
March 0.00 0.00 828.88 617.13
April 0.00 0.00 762.24 549.20
May 0.00 0.00 684.72 509.80
June 0.00 0.00 629.19 453.34
July 0.00 0.00 598.94 445.93
August 0.00 0.00 608.06 452.71
September 0.00 0.00 653.17 470.61
October 0.00 0.00 719.61 535.77
November 0.00 0.00 794.16 572.20
December 0.00 0.00 855.17 636.70
         
Annual Sum or Average 0.00 0.00 740.07 6487.59
Minimum of Months 0.00 0.00 598.94 445.93
Maximum of Months 0.00 0.00 881.54 656.33



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.64 656.41
February 0.00 0.00 874.35 587.98
March 0.00 0.00 828.68 616.97
April 0.00 0.00 762.10 549.10
May 0.00 0.00 686.45 511.08
June 0.00 0.00 627.05 451.79
July 0.00 0.00 600.62 447.17
August 0.00 0.00 605.93 451.14
September 0.00 0.00 653.39 470.77
October 0.00 0.00 721.99 537.55
November 0.00 0.00 794.05 572.12
December 0.00 0.00 855.26 636.76
         
Annual Sum or Average 0.00 0.00 740.21 6488.84
Minimum of Months 0.00 0.00 600.62 447.17
Maximum of Months 0.00 0.00 881.64 656.41



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 882.13 656.77
February 0.00 0.00 873.99 587.74
March 0.00 0.00 831.03 618.73
April 0.00 0.00 762.37 549.30
May 0.00 0.00 684.65 509.74
June 0.00 0.00 629.17 453.33
July 0.00 0.00 598.93 445.92
August 0.00 0.00 608.05 452.71
September 0.00 0.00 653.19 470.63
October 0.00 0.00 719.64 535.79
November 0.00 0.00 794.13 572.18
December 0.00 0.00 857.38 638.34
         
Annual Sum or Average 0.00 0.00 740.48 6491.18
Minimum of Months 0.00 0.00 598.93 445.92
Maximum of Months 0.00 0.00 882.13 656.77



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 884.19 658.31
February 0.00 0.00 871.75 586.23
March 0.00 0.00 830.98 618.69
April 0.00 0.00 760.27 547.78
May 0.00 0.00 686.78 511.32
June 0.00 0.00 626.99 451.76
July 0.00 0.00 600.77 447.29
August 0.00 0.00 607.94 452.63
September 0.00 0.00 653.16 470.61
October 0.00 0.00 719.61 535.77
November 0.00 0.00 794.25 572.26
December 0.00 0.00 857.46 638.40
         
Annual Sum or Average 0.00 0.00 740.46 6491.05
Minimum of Months 0.00 0.00 600.77 447.29
Maximum of Months 0.00 0.00 884.19 658.31



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 883.24 657.60
February 0.00 0.00 872.78 586.92
March 0.00 0.00 831.11 618.79
April 0.00 0.00 760.23 547.76
May 0.00 0.00 686.81 511.35
June 0.00 0.00 627.19 451.90
July 0.00 0.00 600.68 447.22
August 0.00 0.00 607.90 452.60
September 0.00 0.00 651.13 469.14
October 0.00 0.00 721.85 537.44
November 0.00 0.00 794.10 572.16
December 0.00 0.00 857.34 638.32
         
Annual Sum or Average 0.00 0.00 740.48 6491.19
Minimum of Months 0.00 0.00 600.68 447.22
Maximum of Months 0.00 0.00 883.24 657.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.76 656.50
February 0.00 0.00 871.13 585.82
March 0.00 0.00 828.71 617.00
April 0.00 0.00 762.04 549.06
May 0.00 0.00 686.36 511.01
June 0.00 0.00 627.05 451.80
July 0.00 0.00 600.44 447.05
August 0.00 0.00 606.10 451.26
September 0.00 0.00 653.40 470.78
October 0.00 0.00 721.99 537.54
November 0.00 0.00 792.12 570.73
December 0.00 0.00 855.16 636.69
         
Annual Sum or Average 0.00 0.00 739.80 6485.23
Minimum of Months 0.00 0.00 600.44 447.05
Maximum of Months 0.00 0.00 881.76 656.50



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.79 656.52
February 0.00 0.00 871.69 586.19
March 0.00 0.00 826.64 615.46
April 0.00 0.00 762.07 549.08
May 0.00 0.00 686.36 511.01
June 0.00 0.00 627.05 451.79
July 0.00 0.00 599.61 446.43
August 0.00 0.00 606.94 451.88
September 0.00 0.00 653.41 470.79
October 0.00 0.00 719.82 535.93
November 0.00 0.00 794.39 572.37
December 0.00 0.00 854.95 636.54
         
Annual Sum or Average 0.00 0.00 739.66 6483.98
Minimum of Months 0.00 0.00 599.61 446.43
Maximum of Months 0.00 0.00 881.79 656.52



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.73 656.47
February 0.00 0.00 871.52 586.08
March 0.00 0.00 828.56 616.88
April 0.00 0.00 762.11 549.11
May 0.00 0.00 684.62 509.72
June 0.00 0.00 629.16 453.31
July 0.00 0.00 598.92 445.92
August 0.00 0.00 608.05 452.71
September 0.00 0.00 653.19 470.63
October 0.00 0.00 719.59 535.76
November 0.00 0.00 793.95 572.05
December 0.00 0.00 854.95 636.53
         
Annual Sum or Average 0.00 0.00 739.79 6485.17
Minimum of Months 0.00 0.00 598.92 445.92
Maximum of Months 0.00 0.00 881.73 656.47



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.70 656.45
February 0.00 0.00 874.24 587.91
March 0.00 0.00 828.68 616.98
April 0.00 0.00 760.16 547.70
May 0.00 0.00 686.76 511.31
June 0.00 0.00 627.07 451.81
July 0.00 0.00 600.72 447.25
August 0.00 0.00 607.87 452.57
September 0.00 0.00 651.11 469.13
October 0.00 0.00 721.82 537.41
November 0.00 0.00 794.14 572.18
December 0.00 0.00 855.02 636.59
         
Annual Sum or Average 0.00 0.00 740.04 6487.31
Minimum of Months 0.00 0.00 600.72 447.25
Maximum of Months 0.00 0.00 881.70 656.45



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.72 656.46
February 0.00 0.00 874.25 587.91
March 0.00 0.00 826.80 615.58
April 0.00 0.00 762.22 549.19
May 0.00 0.00 686.37 511.02
June 0.00 0.00 627.05 451.79
July 0.00 0.00 600.49 447.08
August 0.00 0.00 606.06 451.23
September 0.00 0.00 653.40 470.78
October 0.00 0.00 720.69 536.58
November 0.00 0.00 793.54 571.76
December 0.00 0.00 854.98 636.56
         
Annual Sum or Average 0.00 0.00 739.88 6485.94
Minimum of Months 0.00 0.00 600.49 447.08
Maximum of Months 0.00 0.00 881.72 656.46



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.78 656.51
February 0.00 0.00 874.35 587.98
March 0.00 0.00 828.41 616.78
April 0.00 0.00 760.18 547.72
May 0.00 0.00 686.59 511.18
June 0.00 0.00 627.06 451.80
July 0.00 0.00 600.75 447.28
August 0.00 0.00 607.84 452.56
September 0.00 0.00 651.10 469.13
October 0.00 0.00 721.82 537.41
November 0.00 0.00 794.11 572.16
December 0.00 0.00 855.23 636.75
         
Annual Sum or Average 0.00 0.00 740.03 6487.26
Minimum of Months 0.00 0.00 600.75 447.28
Maximum of Months 0.00 0.00 881.78 656.51



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.95 656.64
February 0.00 0.00 871.70 586.20
March 0.00 0.00 828.71 617.00
April 0.00 0.00 762.32 549.26
May 0.00 0.00 686.58 511.18
June 0.00 0.00 627.05 451.80
July 0.00 0.00 600.97 447.44
August 0.00 0.00 605.59 450.88
September 0.00 0.00 653.38 470.77
October 0.00 0.00 722.01 537.56
November 0.00 0.00 794.10 572.15
December 0.00 0.00 853.23 635.26
         
Annual Sum or Average 0.00 0.00 739.90 6486.13
Minimum of Months 0.00 0.00 600.97 447.44
Maximum of Months 0.00 0.00 881.95 656.64



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.76 656.50
February 0.00 0.00 871.21 585.87
March 0.00 0.00 828.73 617.01
April 0.00 0.00 762.01 549.04
May 0.00 0.00 686.36 511.01
June 0.00 0.00 627.05 451.79
July 0.00 0.00 600.05 446.75
August 0.00 0.00 606.50 451.55
September 0.00 0.00 653.40 470.78
October 0.00 0.00 721.97 537.53
November 0.00 0.00 792.25 570.82
December 0.00 0.00 855.16 636.69
         
Annual Sum or Average 0.00 0.00 739.81 6485.35
Minimum of Months 0.00 0.00 600.05 446.75
Maximum of Months 0.00 0.00 881.76 656.50



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.94 656.63
February 0.00 0.00 871.56 586.10
March 0.00 0.00 828.72 617.01
April 0.00 0.00 762.22 549.19
May 0.00 0.00 686.41 511.05
June 0.00 0.00 627.05 451.79
July 0.00 0.00 600.58 447.15
August 0.00 0.00 605.97 451.16
September 0.00 0.00 653.39 470.78
October 0.00 0.00 721.99 537.54
November 0.00 0.00 791.82 570.52
December 0.00 0.00 855.24 636.75
         
Annual Sum or Average 0.00 0.00 739.85 6485.67
Minimum of Months 0.00 0.00 600.58 447.15
Maximum of Months 0.00 0.00 881.94 656.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.80 656.53
February 0.00 0.00 874.23 587.90
March 0.00 0.00 828.76 617.04
April 0.00 0.00 762.16 549.14
May 0.00 0.00 684.70 509.78
June 0.00 0.00 629.19 453.34
July 0.00 0.00 598.93 445.92
August 0.00 0.00 608.05 452.71
September 0.00 0.00 653.19 470.63
October 0.00 0.00 719.62 535.78
November 0.00 0.00 794.19 572.22
December 0.00 0.00 855.06 636.62
         
Annual Sum or Average 0.00 0.00 740.07 6487.61
Minimum of Months 0.00 0.00 598.93 445.92
Maximum of Months 0.00 0.00 881.80 656.53



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.81 656.53
February 0.00 0.00 874.36 587.98
March 0.00 0.00 828.60 616.92
April 0.00 0.00 760.17 547.71
May 0.00 0.00 686.67 511.25
June 0.00 0.00 627.06 451.81
July 0.00 0.00 600.74 447.27
August 0.00 0.00 607.85 452.56
September 0.00 0.00 651.11 469.13
October 0.00 0.00 721.81 537.41
November 0.00 0.00 794.18 572.21
December 0.00 0.00 855.28 636.78
         
Annual Sum or Average 0.00 0.00 740.06 6487.56
Minimum of Months 0.00 0.00 600.74 447.27
Maximum of Months 0.00 0.00 881.81 656.53



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 881.87 656.57
February 0.00 0.00 874.29 587.94
March 0.00 0.00 828.81 617.07
April 0.00 0.00 760.27 547.78
May 0.00 0.00 686.76 511.31
June 0.00 0.00 627.07 451.81
July 0.00 0.00 600.73 447.26
August 0.00 0.00 607.86 452.57
September 0.00 0.00 651.11 469.13
October 0.00 0.00 721.84 537.43
November 0.00 0.00 794.01 572.09
December 0.00 0.00 855.22 636.74
         
Annual Sum or Average 0.00 0.00 740.08 6487.71
Minimum of Months 0.00 0.00 600.73 447.26
Maximum of Months 0.00 0.00 881.87 656.57



Table of Contents

Report: HEATING AND COOLING LOADS

For: BREEZEWAY

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 34.01 740.32
February 43.57 464.85
March 48.96 403.09
April 86.89 38.70
May 168.37 0.00
June 208.20 0.00
July 224.50 0.00
August 223.39 0.00
September 196.35 0.00
October 157.84 17.30
November 77.87 138.53
December 53.46 526.65
     
Annual Sum or Average 1523.43 2329.43
Minimum of Months 34.01 0.00
Maximum of Months 224.50 740.32



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 22.44 482.28
February 29.41 305.73
March 32.60 261.10
April 57.99 14.82
May 129.98 0.00
June 164.46 0.00
July 181.95 0.00
August 181.61 0.00
September 162.68 0.00
October 126.74 5.40
November 62.29 66.18
December 40.28 333.23
     
Annual Sum or Average 1192.41 1468.75
Minimum of Months 22.44 0.00
Maximum of Months 181.95 482.28



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 27.98 699.97
February 37.56 435.76
March 47.68 377.69
April 82.89 32.99
May 174.88 0.00
June 212.43 0.00
July 231.23 0.00
August 225.16 0.00
September 196.45 0.00
October 155.74 15.20
November 74.01 120.68
December 46.18 507.93
     
Annual Sum or Average 1512.20 2190.22
Minimum of Months 27.98 0.00
Maximum of Months 231.23 699.97



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 13.16 930.97
February 21.08 571.46
March 33.71 438.71
April 75.18 40.61
May 166.80 0.00
June 210.87 0.00
July 225.15 0.00
August 216.27 0.00
September 181.20 0.00
October 128.52 20.61
November 42.90 179.34
December 24.45 645.44
     
Annual Sum or Average 1339.29 2827.12
Minimum of Months 13.16 0.00
Maximum of Months 225.15 930.97



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 6.26 696.70
February 9.50 421.99
March 19.15 303.51
April 46.92 16.12
May 128.50 0.00
June 167.26 0.00
July 182.59 0.00
August 174.37 0.00
September 147.30 0.00
October 97.00 7.36
November 28.45 101.60
December 14.18 455.67
     
Annual Sum or Average 1021.48 2002.95
Minimum of Months 6.26 0.00
Maximum of Months 182.59 696.70



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 9.24 901.10
February 15.33 541.05
March 31.77 414.65
April 70.58 34.15
May 173.03 0.00
June 214.70 0.00
July 231.47 0.00
August 217.80 0.00
September 181.14 0.00
October 125.73 16.96
November 38.09 149.56
December 18.42 629.69
     
Annual Sum or Average 1327.33 2687.15
Minimum of Months 9.24 0.00
Maximum of Months 231.47 901.10



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 59.81 484.63
February 72.88 298.81
March 83.34 252.82
April 137.89 10.72
May 231.29 0.00
June 246.14 0.00
July 257.16 0.00
August 254.54 0.00
September 225.95 0.00
October 209.06 7.33
November 118.00 74.61
December 85.74 352.06
     
Annual Sum or Average 1981.80 1480.98
Minimum of Months 59.81 0.00
Maximum of Months 257.16 484.63



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 49.39 250.87
February 59.74 163.87
March 67.08 129.16
April 107.79 0.73
May 187.16 0.00
June 196.32 0.00
July 208.74 0.00
August 207.13 0.00
September 188.38 0.00
October 175.40 1.38
November 104.82 19.57
December 74.47 172.76
     
Annual Sum or Average 1626.42 738.35
Minimum of Months 49.39 0.00
Maximum of Months 208.74 250.87



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 53.49 449.44
February 67.11 274.89
March 84.83 232.64
April 135.94 8.28
May 239.50 0.00
June 251.35 0.00
July 265.19 0.00
August 256.81 0.00
September 226.47 0.00
October 207.34 6.02
November 115.66 61.18
December 77.81 337.09
     
Annual Sum or Average 1981.51 1369.53
Minimum of Months 53.49 0.00
Maximum of Months 265.19 449.44



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 27.13 658.32
February 41.15 391.51
March 62.78 283.30
April 123.95 11.76
May 229.76 0.00
June 249.20 0.00
July 257.99 0.00
August 246.85 0.00
September 209.30 0.00
October 175.07 9.46
November 72.61 109.79
December 45.63 465.69
     
Annual Sum or Average 1741.43 1929.83
Minimum of Months 27.13 0.00
Maximum of Months 257.99 658.32



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 19.01 417.53
February 27.82 253.42
March 46.67 157.09
April 93.42 0.89
May 185.70 0.00
June 199.55 0.00
July 209.65 0.00
August 199.29 0.00
September 171.18 0.00
October 139.93 2.75
November 57.51 45.45
December 33.99 277.41
     
Annual Sum or Average 1383.72 1154.54
Minimum of Months 19.01 0.00
Maximum of Months 209.65 417.53



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 22.38 622.32
February 34.77 363.52
March 63.48 258.19
April 121.43 8.96
May 237.62 0.00
June 253.96 0.00
July 265.58 0.00
August 248.87 0.00
September 209.56 0.00
October 172.54 7.28
November 68.45 83.76
December 38.34 452.37
     
Annual Sum or Average 1736.98 1796.42
Minimum of Months 22.38 0.00
Maximum of Months 265.58 622.32



Table of Contents

Report: HEATING AND COOLING LOADS

For: ATTIC

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 26.51 918.61
February 43.60 535.56
March 74.62 406.87
April 140.05 23.05
May 270.31 0.00
June 285.38 0.00
July 297.91 0.00
August 281.67 0.00
September 237.83 0.00
October 200.88 18.51
November 79.34 151.51
December 44.92 685.10
     
Annual Sum or Average 1983.00 2739.21
Minimum of Months 26.51 0.00
Maximum of Months 297.91 918.61



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 49.00 714.60
February 65.78 441.84
March 86.08 381.09
April 146.47 22.32
May 270.44 0.00
June 283.37 0.00
July 297.17 0.00
August 284.94 0.00
September 246.33 0.00
October 223.41 16.08
November 114.63 119.43
December 75.47 553.50
     
Annual Sum or Average 2143.09 2248.87
Minimum of Months 49.00 0.00
Maximum of Months 297.17 714.60



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 55.44 764.81
February 71.98 474.99
March 85.75 411.86
April 149.49 30.01
May 262.81 0.00
June 278.57 0.00
July 289.49 0.00
August 282.92 0.00
September 246.01 0.00
October 225.59 18.92
November 118.19 142.70
December 83.61 575.18
     
Annual Sum or Average 2149.84 2418.47
Minimum of Months 55.44 0.00
Maximum of Months 289.49 764.81



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 22.96 697.65
February 36.72 413.52
March 58.43 293.16
April 112.94 7.65
May 219.27 0.00
June 231.46 0.00
July 242.37 0.00
August 232.59 0.00
September 200.15 0.00
October 169.02 8.98
November 68.55 103.68
December 40.49 492.55
     
Annual Sum or Average 1634.94 2017.18
Minimum of Months 22.96 0.00
Maximum of Months 242.37 697.65



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 44.91 484.00
February 58.81 312.26
March 69.72 261.79
April 119.28 6.74
May 219.18 0.00
June 229.12 0.00
July 241.36 0.00
August 235.81 0.00
September 208.78 0.00
October 192.06 6.56
November 104.14 66.14
December 71.72 358.99
     
Annual Sum or Average 1794.88 1496.48
Minimum of Months 44.91 0.00
Maximum of Months 241.36 484.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 16:15:55

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 31.75 960.47
February 50.32 572.41
March 74.64 440.94
April 143.35 31.60
May 262.88 0.00
June 280.86 0.00
July 290.50 0.00
August 279.80 0.00
September 237.63 0.00
October 203.55 22.89
November 84.28 186.78
December 52.69 703.85
     
Annual Sum or Average 1992.26 2918.93
Minimum of Months 31.75 0.00