Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 16:47
Tabular Output Report in Format: HTML
Building: US+MF+CZ3B+oilfurnace+unheatedbsmt+IECC_2021
Environment: ANNUAL ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2024-06-27 16:47:20
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 605827.09 | 15.53 | 28.03 |
Net Site Energy | 605827.09 | 15.53 | 28.03 |
Total Source Energy | 1723362.47 | 44.18 | 79.75 |
Net Source Energy | 1723362.47 | 44.18 | 79.75 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.22 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 17395.26 |
Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 93755.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 67522.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 27595.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 56138.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312247.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 512071.96 | 93755.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312247.30 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 93755.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 67522.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation | 8652.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 18942.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312247.30 | |
Water Heater | 4468.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 51669.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Unassigned | 0.00 | 93755.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 67522.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 38708.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 27595.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 56138.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312247.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 7.00 | 4.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 |
Other | 13.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 23.70 | 4.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 3.88 | 2.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.01 |
Other | 7.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 13.13 | 2.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.01 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 512071.964 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 512071.964 | 100.00 |
Total On-Site and Utility Electric Sources | 512071.964 | 100.00 |
Total Electricity End Uses | 512071.964 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 312247.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 312247.30 | 100.00 |
Total Water End Uses | 312247.30 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1942.17 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 540.83 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR |HEATING AND COOLING LOADS
| UNHEATEDBSMT | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
GeneralValue | |
Program Version and Build | EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 16:47 |
RunPeriod | ANNUAL |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [ft] | 3891.27 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 18953.34 | 7014.93 | 2461.74 | 7014.93 | 2461.74 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 11.22 | 7.58 | 21.60 | 7.58 | 21.60 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
UNHEATEDBSMT | 7794.39 | No | Yes | 58539.52 | 1.00 | 185.02 | 2590.34 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.16 | No | Yes | 30553.25 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
ATTIC | 7802.71 | No | Yes | 52795.56 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.5831 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.5831 | 600.28 | 2.9092 |
Total | 39005.22 | 325627.71 | 16363.00 | 2590.34 | 2126.74 | 2126.74 | 0.3230 | 1083.48 | 1.6118 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.5831 | 600.28 | 2.9092 | |||
Unconditioned Total | 17395.26 | 141888.33 | 1066.39 | 2590.34 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | Tags | |
UNHEATEDBSMT | 7794.39 | No | Yes | 1.00 | UNHEATEDBSMT | GENERAL | UNHEATEDBSMT | 0.0000 | 0.00 | 0.0000 | |
BREEZEWAY | 1798.16 | No | Yes | 1.00 | BREEZEWAY | GENERAL | BREEZEWAY | 0.0000 | 0.00 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5831 | 600.28 | 2.9092 | |
ATTIC | 7802.71 | No | Yes | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5831 | 600.28 | 2.9092 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5831 | 600.28 | 2.9092 | |
Total | 39005.22 | 0.3230 | 1083.48 | 1.6118 | |||||||
Conditioned Total | 21609.96 | 0.5831 | 600.28 | 2.9092 | |||||||
Unconditioned Total | 17395.26 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [ft2] | Conditioned Area [ft2] | Unconditioned Area [ft2] | Not Part of Total Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
GENERAL | 39005.22 | 21609.96 | 17395.26 | 0.00 | 0.3230 | 1083.48 | 1.6118 |
Total | 39005.22 | 21609.96 | 17395.26 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 02-JUL-18:50 | 27-JAN-07:30 | - | - | - | - | - | - | - | - | - | - | 01-JAN-09:00 |
Heating | 0.00 | 163.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 11.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 4.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 52.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 32.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 129.82 | 163.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 163.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 22.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 11.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 4.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 6.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation | 0.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 4.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | |
Water Heater | 0.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Gasoline [kBtu] | Source Diesel [kBtu] | Source Coal [kBtu] | Source Fuel Oil No 1 [kBtu] | Source Fuel Oil No 2 [kBtu] | Source Propane [kBtu] | Source Other Fuel 1 [kBtu] | Source Other Fuel 2 [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 101630.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 213844.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 122590.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65251.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 954861.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 87393.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 177789.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1621731.91 | 101630.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 4.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 8.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 75.05 | 4.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 2.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 24.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 4.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 41.58 | 2.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 413.72 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 242.60 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 309.54 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 407.03 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 241.25 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 294.16 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 421.94 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 256.19 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 321.88 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 416.00 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 254.42 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 309.37 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 363.44 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 359.65 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 467.67 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 309.04 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 305.49 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 470.08 |
Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | Sum of Air Terminal Maximum Flow Rates [ft3/min] | Adjusted Heating Design Air Flow Rate [ft3/min] | Adjusted Cooling Design Air Flow Rate [ft3/min] | Adjusted Main Design Air Flow Rate [ft3/min] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 413.72 | 413.72 | 413.72 | 413.72 | 413.72 | 413.72 | 1.00 | 1.00 | 413.72 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 242.60 | 242.60 | 242.60 | 242.60 | 242.60 | 242.60 | 1.00 | 1.00 | 242.60 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 309.54 | 309.54 | 309.54 | 309.54 | 309.54 | 309.54 | 1.00 | 1.00 | 309.54 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 407.03 | 407.03 | 407.03 | 407.03 | 407.03 | 407.03 | 1.00 | 1.00 | 407.03 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 241.25 | 241.25 | 241.25 | 241.25 | 241.25 | 241.25 | 1.00 | 1.00 | 241.25 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 294.16 | 294.16 | 294.16 | 294.16 | 294.16 | 294.16 | 1.00 | 1.00 | 294.16 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 421.94 | 421.94 | 421.94 | 421.94 | 421.94 | 421.94 | 1.00 | 1.00 | 421.94 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 256.19 | 256.19 | 256.19 | 256.19 | 256.19 | 256.19 | 1.00 | 1.00 | 256.19 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.88 | 321.88 | 321.88 | 321.88 | 321.88 | 321.88 | 1.00 | 1.00 | 321.88 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 416.00 | 416.00 | 416.00 | 416.00 | 416.00 | 416.00 | 1.00 | 1.00 | 416.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 254.42 | 254.42 | 254.42 | 254.42 | 254.42 | 254.42 | 1.00 | 1.00 | 254.42 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 309.37 | 309.37 | 309.37 | 309.37 | 309.37 | 309.37 | 1.00 | 1.00 | 309.37 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 467.67 | 467.67 | 467.67 | 467.67 | 467.67 | 467.67 | 1.00 | 1.00 | 467.67 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 305.49 | 305.49 | 305.49 | 305.49 | 305.49 | 305.49 | 1.00 | 1.00 | 305.49 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 359.65 | 359.65 | 359.65 | 359.65 | 359.65 | 359.65 | 1.00 | 1.00 | 359.65 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 470.08 | 470.08 | 470.08 | 470.08 | 470.08 | 470.08 | 1.00 | 1.00 | 470.08 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 309.04 | 309.04 | 309.04 | 309.04 | 309.04 | 309.04 | 1.00 | 1.00 | 309.04 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 363.44 | 363.44 | 363.44 | 363.44 | 363.44 | 363.44 | 1.00 | 1.00 | 363.44 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 413.72 | 1.15 | 0.760570 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 242.60 | 0.696461 | 0.750515 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 309.54 | 0.926033 | 0.736021 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 407.03 | 1.14 | 0.760460 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 241.25 | 0.693029 | 0.750322 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 294.16 | 0.881495 | 0.735561 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 421.94 | 1.18 | 0.760676 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 256.19 | 0.725468 | 0.755436 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 321.88 | 0.957925 | 0.737453 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 416.00 | 1.16 | 0.760492 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 254.42 | 0.721009 | 0.755209 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 309.37 | 0.883631 | 0.752966 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 467.67 | 1.29 | 0.764928 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 305.49 | 0.846821 | 0.763653 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 359.65 | 1.01 | 0.758328 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 470.08 | 1.30 | 0.765044 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 309.04 | 0.860465 | 0.762349 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 363.44 | 1.01 | 0.760698 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 413.72 | 413.72 | 413.72 | 1.15 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 242.60 | 242.60 | 242.60 | 0.696461 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 309.54 | 309.54 | 309.54 | 0.926033 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 407.03 | 407.03 | 407.03 | 1.14 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 241.25 | 241.25 | 241.25 | 0.693029 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 294.16 | 294.16 | 294.16 | 0.881495 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 421.94 | 421.94 | 421.94 | 1.18 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 256.19 | 256.19 | 256.19 | 0.725468 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 321.88 | 321.88 | 321.88 | 0.957925 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 416.00 | 416.00 | 416.00 | 1.16 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 254.42 | 254.42 | 254.42 | 0.721009 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 309.37 | 309.37 | 309.37 | 0.883631 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 467.67 | 467.67 | 467.67 | 1.29 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 305.49 | 305.49 | 305.49 | 0.846821 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 359.65 | 359.65 | 359.65 | 1.01 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 470.08 | 470.08 | 470.08 | 1.30 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 309.04 | 309.04 | 309.04 | 0.860465 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 363.44 | 363.44 | 363.44 | 1.01 | 1.00 |
Design Size Rated Capacity [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 24736.04 | 2.54 | 371.15 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 15496.91 | 1.59 | 228.42 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 19111.31 | 1.96 | 284.26 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 24375.16 | 2.50 | 365.58 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 15423.56 | 1.58 | 227.29 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 18280.62 | 1.88 | 271.42 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 25179.69 | 2.58 | 377.96 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 16230.27 | 1.67 | 239.75 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 19777.23 | 2.03 | 294.51 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 24858.95 | 2.55 | 373.01 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 16134.44 | 1.66 | 238.26 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 19101.82 | 1.96 | 284.08 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 27649.60 | 2.84 | 416.07 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 18892.52 | 1.94 | 280.89 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 21817.01 | 2.24 | 326.01 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 27779.28 | 2.85 | 418.08 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 19084.10 | 1.96 | 283.85 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 22021.72 | 2.26 | 329.17 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 413.72 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 242.60 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 309.54 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 407.03 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 241.25 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 294.16 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 421.94 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 256.19 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 321.88 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 416.00 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 254.42 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 309.37 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 467.67 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 305.49 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 359.65 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 470.08 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 309.04 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 363.44 |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | 160.01 |
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | 160.01 |
Evaporator air flow rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 160.01 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 160.01 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 160.01 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 160.01 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
BOILER LOOP | 5.16 | 10.32 |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 2.09 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 2.09 |
Design Flow Rate [ft3/min] | |
BOILER CIRC PUMP | 5.16 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
CENTRAL BOILER | 375950.21 | 38.59 |
Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | 1.04 |
WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDF | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
BGWALL_UPPER_SDR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_LDB | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
BGWALL_UPPER_SDL | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
VersionVersion ID | |
1 | 23.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | No | Yes | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.200 | 0.200 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 54.59 | 48.72 | 47.12 | 48.51 | 56.43 | 65.30 | 73.65 | 79.68 | 81.45 | 78.62 | 71.78 | 63.16 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 |
Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
1 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {ft} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Sensor Height Above Ground {ft} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 32.810 | 0.140 | 885.870 | 4.921 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {ft} | Standard Pressure at Elevation {psi} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 3891.27 | 13. | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{F} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} | Fixed Default Water Mains Temperature{F} | |
1 | Correlation | NA | 64.29 | 37.98 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | US+MF+CZ3B+oilfurnace+unheatedbsmt+IECC_2021 | 0.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Algorithm {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
Space Heat Balance Sizing |
Space Heat Balance Simulation |
|
1 | ThirdOrderBackwardDifference | No | No |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Gradient Coefficient {F/ft} | |
1 | 0.220 | 1213.970 | 0.003566 |
Material Name | ThermalResistance {m2-K/w} | Roughness | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | Absorptance:Thermal | Absorptance:Solar | Absorptance:Visible | |
1 | SHEATHING_CONSOL_LAYER | 0.1351 | Rough | 0.0417 | 9.402E-002 | 42.764 | 0.280 | 0.9000 | 0.7000 | 0.7000 |
2 | CEIL_CONSOL_LAYER | 7.7625 | Rough | 1.5719 | 6.172E-002 | 2.618 | 0.185 | 0.9000 | 0.7000 | 0.7000 |
3 | FLOOR_CONSOL_LAYER | 2.8450 | Rough | 0.4584 | 4.910E-002 | 3.438 | 0.219 | 0.9000 | 0.7000 | 0.7000 |
4 | BSMTWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
5 | CRAWLWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
6 | WALL_CONSOL_LAYER | 2.4438 | Rough | 0.4584 | 5.717E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
7 | VERY HIGH REFLECTIVITY SURFACE | 2.1097E-006 | Smooth | 0.0016 | 237.000 | 168.680 | 0.216 | 0.9000 | 5.0000E-002 | 5.0000E-002 |
8 | GYPSUMBOARD-5/16IN | 5.0054E-002 | Rough | 0.0260 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
9 | COPPERPIPE | 4.7506E-005 | MediumRough | 0.0625 | 401.000 | 140.026 | 0.200 | 0.9000 | 0.6500 | 0.6500 |
10 | F08 METAL SURFACE | 1.7668E-005 | Smooth | 0.0026 | 45.280 | 488.437 | 0.119 | 0.9000 | 0.7000 | 0.7000 |
11 | CONCRETE_4IN | 7.7356E-002 | Rough | 0.3330 | 1.312 | 140.014 | 0.111 | 0.9000 | 0.7000 | 0.7000 |
12 | ASPHALT_SHINGLE | 7.7448E-002 | MediumRough | 0.0208 | 8.186E-002 | 70.000 | 0.300 | 0.9000 | 0.7500 | 0.7000 |
13 | WOOD_SHINGLE | 0.1115 | MediumSmooth | 0.0417 | 0.114 | 26.600 | 0.390 | 0.9000 | 0.7000 | 0.7000 |
14 | SLATE_SHINGLE | 8.8061E-003 | MediumSmooth | 0.0417 | 1.442 | 100.000 | 0.300 | 0.9000 | 0.7000 | 0.7000 |
15 | CEMENT_STUCCO | 2.6422E-002 | MediumSmooth | 0.0625 | 0.721 | 116.464 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
16 | SYN_STUCCO | 3.5237E-002 | MediumSmooth | 0.0100 | 8.650E-002 | 24.971 | 0.210 | 0.7000 | 0.7000 | 0.7000 |
17 | DRYWALL_1/2IN | 7.9331E-002 | MediumSmooth | 0.0417 | 0.160 | 50.000 | 0.260 | 0.9000 | 0.7000 | 0.7000 |
18 | OSB_5/8IN | 0.1365 | MediumSmooth | 0.0521 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
19 | OSB_7/16IN | 9.5550E-002 | MediumSmooth | 0.0365 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
20 | BLOWN_R30 | 5.1614 | MediumRough | 0.6975 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
21 | BLOWN_R30_TOP | 2.8489 | MediumRough | 0.3849 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
22 | PLYWOOD_3/4IN | 0.1650 | Rough | 0.0625 | 0.115 | 34.003 | 0.161 | 0.9000 | 0.7000 | 0.7000 |
23 | BATT_R19 | 7.3089 | MediumRough | 0.0833 | 3.475E-003 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
24 | LUMBER_2X4 | 0.7709 | Rough | 0.2920 | 0.115 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
25 | CARPET_N_PAD | 0.4224 | MediumSmooth | 0.0833 | 6.013E-002 | 2.000 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
26 | BATT_R13 | 2.2936 | MediumRough | 0.2917 | 3.876E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
27 | OSB_1/2IN | 0.1092 | MediumSmooth | 0.0417 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
28 | SOIL_12IN | 0.1761 | Rough | 1.0000 | 1.731 | 115.011 | 0.056 | 0.9000 | 0.7000 | 0.7000 |
29 | DOOR_CONST | 0.5870 | Smooth | 0.1387 | 7.201E-002 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
30 | GYP_BOARD_1/2IN | 8.0130E-002 | Rough | 0.0417 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
31 | STD WOOD 6INCH | 1.2500 | MediumSmooth | 0.4921 | 0.120 | 33.711 | 0.289 | 0.9000 | 0.7000 | 0.7000 |
32 | PIPE INSULATION | 0.3830 | VeryRough | 0.0417 | 3.317E-002 | 5.681 | 0.200 | 0.9000 | 0.5000 | 0.5000 |
33 | MANF_WALL_AIRGAP | 0.1200 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
34 | BLDG_PAPER_FELT | 1.0567E-002 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
35 | R_HIGH | 177.0000 | MediumRough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
36 | CLEAR ACRYLIC PLASTIC | 3.3333E-003 | VerySmooth | 0.0098 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
37 | DIFFUSING ACRYLIC PLASTIC | 2.4444E-003 | VerySmooth | 0.0072 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
38 | INT_BLIND | 0.0000 | Rough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.0000 | 0.0000 | 0.0000 |
39 | GLASS | 0.4127 | VerySmooth | 0.1373 | 0.101 | 0.000 | 0.000 | 0.8400 | 0.0000 | 0.0000 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Name | Combined convective/radiative film coefficient {Btu/h-ft2-F} | User selected Constant Temperature {F} | Coefficient modifying the constant temperature term | Coefficient modifying the external dry bulb temperature term | Coefficient modifying the ground temperature term | Coefficient modifying the wind speed term {s/m} | Coefficient modifying the zone air temperature term | Constant Temperature Schedule Name | Sinusoidal Variation | Period of Sinusoidal Variation | Previous Other Side Temperature Coefficient | Minimum Other Side Temperature {F} | Maximum Other Side Temperature {F} | |
1 | SURFPROPOTHSDCOEFBASEMENTAVGWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTWALLSURFACETEMP | NO | 24.000 | 0.000 | N/A | N/A |
2 | SURFPROPOTHSDCOEFBASEMENTAVGFLOOR | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTFLOORTEMP | NO | 24.000 | 0.000 | N/A | N/A |
3 | SURFPROPOTHSDCOEFBASEMENTUPPERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTUPPERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
4 | SURFPROPOTHSDCOEFBASEMENTLOWERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTLOWERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{F} |
Surface Convection Coefficient Lower Limit {Btu/h-ft2-F} |
Surface Convection Coefficient Upper Limit {Btu/h-ft2-F} |
|
1 | CTF - ConductionTransferFunction | 392. | 0.02 | 176.1 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 60 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 21 | 186 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {ft} | Origin Y-Coordinate {ft} | Origin Z-Coordinate {ft} | Centroid X-Coordinate {ft} | Centroid Y-Coordinate {ft} | Centroid Z-Coordinate {ft} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {ft} | Maximum X {ft} | Minimum Y {ft} | Maximum Y {ft} | Minimum Z {ft} | Maximum Z {ft} | Ceiling Height {ft} | Volume {ft3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {ft2} | Exterior Gross Wall Area {ft2} | Exterior Net Wall Area {ft2} | Exterior Window Area {ft2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | UNHEATEDBSMT | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.51 | -3.4 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | -7.0 | 0.49 | 7.51 | 58539.45 | TARP | DOE-2 | 7794.37 | 185.05 | 185.05 | 0.00 | 15 | 0 | 0 | Yes |
2 | BREEZEWAY | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.55 | 13.26 | 1 | 1 | 1 | 0.00 | 119.89 | 30.05 | 35.04 | 0.49 | 25.99 | 17.00 | 30553.07 | TARP | DOE-2 | 1798.18 | 0.00 | 0.00 | 0.00 | 4 | 0 | 0 | Yes |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
15 | ATTIC | 0.0 | -134.9 | 51.61 | 0.00 | 59.94 | 32.55 | 29.56 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | 25.99 | 39.54 | 6.76 | 52795.39 | TARP | DOE-2 | 7802.66 | 881.33 | 881.33 | 0.00 | 11 | 0 | 0 | Yes |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
Zone Name | Floor Area {ft2} | # Occupants | Area per Occupant {ft2/person} | Occupant per Area {person/ft2} | Interior Lighting {Btu/h-ft2} | Electric Load {Btu/h-ft2} | Gas Load {Btu/h-ft2} | Other Load {Btu/h-ft2} | Hot Water Eq {Btu/h-ft2} | Steam Equipment {Btu/h-ft2} | Sum Loads per Area {Btu/h-ft2} | Outdoor Controlled Baseboard Heat | |
1 | UNHEATEDBSMT | 7794.37 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
2 | BREEZEWAY | 1798.18 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
15 | ATTIC | 7802.66 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.583 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.492 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Number of People {} | People/Floor Area {person/ft2} | Floor Area per person {ft2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
1 | PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
2 | PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
3 | PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
4 | PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
5 | PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
6 | PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
7 | PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
8 | PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
9 | PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
10 | PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
11 | PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
12 | PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
13 | PEOPLE_UNIT1_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
14 | PEOPLE_UNIT2_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
15 | PEOPLE_UNIT3_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
16 | PEOPLE_UNIT1_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
17 | PEOPLE_UNIT2_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
18 | PEOPLE_UNIT3_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Lighting Level {Btu/h} | Lights/Floor Area {Btu/h-ft2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {Btu/h} | Nominal Maximum Lighting Level {Btu/h} | |
1 | LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
2 | LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
3 | LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
4 | LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
5 | LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
6 | LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
7 | LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
8 | LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
9 | LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
10 | LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
11 | LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
12 | LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
13 | LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
14 | LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
15 | LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
16 | LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
17 | LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
18 | LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
19 | LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
20 | LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
21 | LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
22 | LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
23 | LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
24 | LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
25 | LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
26 | LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
27 | LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
28 | LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
29 | LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
30 | LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
31 | LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
32 | LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
33 | LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
34 | LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
35 | LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 481.174 | 0.401 | 70.512 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 33.079 | 481.174 |
36 | LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
1 | DISHWASHER1_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
2 | REFRIGERATOR1_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
3 | CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
4 | ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
5 | ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
6 | TELEVISION1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
7 | ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
8 | IECC_ADJ1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
9 | DISHWASHER2_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
10 | REFRIGERATOR2_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
11 | CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
12 | ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
13 | ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
14 | TELEVISION2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
15 | ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
16 | IECC_ADJ2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
17 | DISHWASHER3_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
18 | REFRIGERATOR3_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
19 | CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
20 | ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
21 | ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
22 | TELEVISION3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
23 | ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
24 | IECC_ADJ3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
25 | DISHWASHER1_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
26 | REFRIGERATOR1_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
27 | CLOTHESWASHER1_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
28 | ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
29 | ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
30 | TELEVISION1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
31 | ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
32 | IECC_ADJ1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
33 | DISHWASHER2_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
34 | REFRIGERATOR2_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
35 | CLOTHESWASHER2_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
36 | ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
37 | ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
38 | TELEVISION2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
39 | ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
40 | IECC_ADJ2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
41 | DISHWASHER3_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
42 | REFRIGERATOR3_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
43 | CLOTHESWASHER3_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
44 | ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
45 | ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
46 | TELEVISION3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
47 | ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
48 | IECC_ADJ3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
49 | DISHWASHER1_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
50 | REFRIGERATOR1_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
51 | CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
52 | ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
53 | ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
54 | TELEVISION1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
55 | ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
56 | IECC_ADJ1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
57 | DISHWASHER2_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
58 | REFRIGERATOR2_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
59 | CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
60 | ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
61 | ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
62 | TELEVISION2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
63 | ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
64 | IECC_ADJ2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
65 | DISHWASHER3_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
66 | REFRIGERATOR3_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
67 | CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
68 | ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
69 | ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
70 | TELEVISION3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
71 | ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
72 | IECC_ADJ3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
73 | DISHWASHER1_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
74 | REFRIGERATOR1_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
75 | CLOTHESWASHER1_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
76 | ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
77 | ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
78 | TELEVISION1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
79 | ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
80 | IECC_ADJ1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
81 | DISHWASHER2_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
82 | REFRIGERATOR2_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
83 | CLOTHESWASHER2_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
84 | ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
85 | ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
86 | TELEVISION2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
87 | ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
88 | IECC_ADJ2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
89 | DISHWASHER3_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
90 | REFRIGERATOR3_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
91 | CLOTHESWASHER3_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
92 | ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
93 | ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
94 | TELEVISION3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
95 | ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
96 | IECC_ADJ3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
97 | DISHWASHER1_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
98 | REFRIGERATOR1_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
99 | CLOTHESWASHER1_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
100 | ELECTRIC_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
101 | ELECTRIC_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
102 | TELEVISION1_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
103 | ELECTRIC_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
104 | IECC_ADJ1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
105 | DISHWASHER2_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
106 | REFRIGERATOR2_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
107 | CLOTHESWASHER2_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
108 | ELECTRIC_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
109 | ELECTRIC_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
110 | TELEVISION2_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
111 | ELECTRIC_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
112 | IECC_ADJ2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
113 | DISHWASHER3_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
114 | REFRIGERATOR3_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
115 | CLOTHESWASHER3_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
116 | ELECTRIC_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
117 | ELECTRIC_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
118 | TELEVISION3_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
119 | ELECTRIC_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
120 | IECC_ADJ3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
121 | DISHWASHER1_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
122 | REFRIGERATOR1_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
123 | CLOTHESWASHER1_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
124 | ELECTRIC_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
125 | ELECTRIC_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
126 | TELEVISION1_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
127 | ELECTRIC_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
128 | IECC_ADJ1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
129 | DISHWASHER2_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
130 | REFRIGERATOR2_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
131 | CLOTHESWASHER2_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
132 | ELECTRIC_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
133 | ELECTRIC_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
134 | TELEVISION2_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
135 | ELECTRIC_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
136 | IECC_ADJ2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
137 | DISHWASHER3_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
138 | REFRIGERATOR3_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
139 | CLOTHESWASHER3_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
140 | ELECTRIC_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
141 | ELECTRIC_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
142 | TELEVISION3_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
143 | ELECTRIC_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
144 | IECC_ADJ3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
Construction Name | Index | #Layers | #CTFs | Time Step {Hours} | ThermalConductance {Btu/h-ft2-F} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | EXTERIOR WALL | 1 | 5 | 11 | 0.167 | 0.0631 | 0.700 | 0.900 | 0.700 | 0.700 | MediumSmooth |
2 | CEILING-FLOOR-LAYER | 3 | 1 | 5 | 0.167 | 0.228 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
3 | EXTERIOR FLOOR | 4 | 3 | 8 | 0.167 | 0.0513 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
4 | INTERIOR CEILING | 6 | 2 | 12 | 0.167 | 0.0225 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
5 | ATTIC FLOOR | 7 | 2 | 12 | 0.167 | 0.0225 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
6 | INTERIORWALL | 9 | 3 | 5 | 0.167 | 0.597 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
7 | EXTERIOR ROOF | 11 | 2 | 4 | 0.167 | 0.943 | 0.900 | 0.900 | 0.750 | 0.700 | MediumRough |
8 | EXTERIOR DOOR | 14 | 1 | 5 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | GABLE_END | 16 | 5 | 6 | 0.167 | 0.428 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
10 | BASEMENT WALL | 24 | 3 | 4 | 0.167 | 0.534 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
11 | iz-EXTERIOR FLOOR | 25 | 3 | 8 | 0.167 | 0.0513 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
Material Name | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | ThermalResistance {m2-K/w} | |
1 | SYN_STUCCO | 0.0098 | 0.086 | 24.971 | 0.210 | 0.3524E-01 |
2 | SHEATHING_CONSOL_LAYER | 0.0417 | 0.094 | 42.764 | 0.280 | 0.1351 |
3 | OSB_7/16IN | 0.0364 | 0.116 | 34.000 | 0.290 | 0.9555E-01 |
4 | WALL_CONSOL_LAYER | 0.4584 | 0.057 | 7.541 | 0.248 | 2.444 |
5 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
6 | LUMBER_2X4 | 0.2920 | 0.115 | 32.003 | 0.183 | 0.7709 |
7 | FLOOR_CONSOL_LAYER | 0.4584 | 0.049 | 3.438 | 0.219 | 2.845 |
8 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
9 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
10 | CEIL_CONSOL_LAYER | 1.5719 | 0.062 | 2.618 | 0.185 | 7.762 |
11 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
12 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
13 | CEIL_CONSOL_LAYER | 1.5719 | 0.062 | 2.618 | 0.185 | 7.762 |
14 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
15 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
16 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
17 | ASPHALT_SHINGLE | 0.0207 | 0.082 | 70.000 | 0.300 | 0.7745E-01 |
18 | OSB_1/2IN | 0.0417 | 0.116 | 34.000 | 0.290 | 0.1092 |
19 | DOOR_CONST | 0.1388 | 0.072 | 32.003 | 0.183 | 0.5870 |
20 | CEMENT_STUCCO | 0.0627 | 0.721 | 116.464 | 0.210 | 0.2642E-01 |
21 | BLDG_PAPER_FELT | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1057E-01 |
22 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
23 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
24 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
25 | BSMTWALL_CONSOL_LAYER | 0.0010 | 10.844 | 7.541 | 0.248 | 0.2342E-04 |
26 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
27 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
28 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
29 | FLOOR_CONSOL_LAYER | 0.4584 | 0.049 | 3.438 | 0.219 | 2.845 |
Material Name | ThermalResistance {m2-K/w} | |
1 | AIR_4_IN_VERT | 0.1585 |
2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
4 | AIR_4_IN_VERT | 0.1585 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 11 | -0.54724946E-11 | -0.29353179E-14 | -0.58361936E-11 | 0.17617726E-15 |
2 | 10 | 0.24755928E-06 | 0.16971160E-13 | 0.58954555E-06 | -0.42317085E-11 |
3 | 9 | -0.21700660E-03 | 0.26282512E-10 | -0.34360792E-03 | 0.18634160E-06 |
4 | 8 | 0.10400975E-01 | 0.16063655E-07 | 0.16710006E-01 | -0.10459154E-03 |
5 | 7 | -0.18466841 | 0.14497582E-05 | -0.31678806 | 0.33996447E-02 |
6 | 6 | 1.6813335 | 0.30890211E-04 | 3.0392820 | -0.45644738E-01 |
7 | 5 | -8.8640021 | 0.19737274E-03 | -16.399456 | 0.32465800 |
8 | 4 | 28.400945 | 0.41196590E-03 | 52.185337 | -1.3315683 |
9 | 3 | -55.684303 | 0.27160336E-03 | -99.213599 | 3.2198962 |
10 | 2 | 64.740984 | 0.46773103E-04 | 110.17164 | -4.4902555 |
11 | 1 | -40.701741 | 0.11975386E-05 | -65.686261 | 3.3169381 |
12 | 0 | 10.602230 | 0.29970883E-09 | 16.204438 | |
13 | 5 | -0.10726087E-01 | 0.44268190E-05 | -0.10726087E-01 | 0.97389233E-03 |
14 | 4 | 0.31857203 | 0.80150166E-03 | 0.31857203 | -0.30727185E-01 |
15 | 3 | -2.8372473 | 0.12516450E-01 | -2.8372473 | 0.30041224 |
16 | 2 | 9.6667056 | 0.33176537E-01 | 9.6667056 | -1.1584571 |
17 | 1 | -13.322214 | 0.15207483E-01 | -13.322214 | 1.8397512 |
18 | 0 | 6.2472388 | 0.62260140E-03 | 6.2472388 | |
19 | 8 | 0.57415395E-12 | 0.13118744E-13 | 0.10972129E-06 | -0.16121901E-12 |
20 | 7 | -0.11209345E-05 | 0.79302418E-09 | -0.25702593E-04 | 0.31491488E-06 |
21 | 6 | 0.21835020E-03 | 0.55842834E-06 | 0.16732899E-02 | -0.62999473E-04 |
22 | 5 | -0.11788181E-01 | 0.43793696E-04 | -0.40973943E-01 | 0.36016799E-02 |
23 | 4 | 0.21386917 | 0.66464187E-03 | 0.43752526 | -0.72376639E-01 |
24 | 3 | -1.3884299 | 0.23440260E-02 | -2.2272953 | 0.54574706 |
25 | 2 | 3.6315139 | 0.19014595E-02 | 5.4333867 | -1.6855834 |
26 | 1 | -4.0346078 | 0.26548191E-03 | -6.0131296 | 2.1907513 |
27 | 0 | 1.5944472 | 0.16612988E-05 | 2.4140608 | |
28 | 12 | 0.94888791E-16 | -0.11237443E-15 | 0.21480527E-09 | -0.52606005E-16 |
29 | 11 | -0.44509090E-09 | -0.12338758E-15 | -0.11566016E-03 | 0.28501063E-09 |
30 | 10 | 0.60393314E-04 | 0.62564840E-13 | 0.62960490E-02 | -0.38672578E-04 |
31 | 9 | -0.20055671E-02 | 0.85912012E-10 | -0.12885789 | 0.13084700E-02 |
32 | 8 | 0.28697042E-01 | 0.10381403E-07 | 1.3966036 | -0.19129448E-01 |
33 | 7 | -0.23229993 | 0.28493476E-06 | -9.1473517 | 0.15872626 |
34 | 6 | 1.1750436 | 0.24973161E-05 | 38.552224 | -0.82592201 |
35 | 5 | -3.8729952 | 0.80040830E-05 | -107.65441 | 2.8111251 |
36 | 4 | 8.4143451 | 0.96510929E-05 | 200.56463 | -6.3313915 |
37 | 3 | -11.897084 | 0.41099356E-05 | -245.77565 | 9.3152582 |
38 | 2 | 10.487404 | 0.50788650E-06 | 189.69676 | -8.5734564 |
39 | 1 | -5.2147174 | 0.10902359E-07 | -83.415737 | 4.4633233 |
40 | 0 | 1.1135774 | 0.38882120E-11 | 15.905642 | |
41 | 12 | 0.21480527E-09 | -0.11237443E-15 | 0.94888791E-16 | -0.52606005E-16 |
42 | 11 | -0.11566016E-03 | -0.12338758E-15 | -0.44509090E-09 | 0.28501063E-09 |
43 | 10 | 0.62960490E-02 | 0.62564840E-13 | 0.60393314E-04 | -0.38672578E-04 |
44 | 9 | -0.12885789 | 0.85912012E-10 | -0.20055671E-02 | 0.13084700E-02 |
45 | 8 | 1.3966036 | 0.10381403E-07 | 0.28697042E-01 | -0.19129448E-01 |
46 | 7 | -9.1473517 | 0.28493476E-06 | -0.23229993 | 0.15872626 |
47 | 6 | 38.552224 | 0.24973161E-05 | 1.1750436 | -0.82592201 |
48 | 5 | -107.65441 | 0.80040830E-05 | -3.8729952 | 2.8111251 |
49 | 4 | 200.56463 | 0.96510929E-05 | 8.4143451 | -6.3313915 |
50 | 3 | -245.77565 | 0.41099356E-05 | -11.897084 | 9.3152582 |
51 | 2 | 189.69676 | 0.50788650E-06 | 10.487404 | -8.5734564 |
52 | 1 | -83.415737 | 0.10902359E-07 | -5.2147174 | 4.4633233 |
53 | 0 | 15.905642 | 0.38882120E-11 | 1.1135774 | |
54 | 5 | -0.27590492E-07 | 0.65241430E-08 | -0.27590492E-07 | 0.17331255E-13 |
55 | 4 | 0.68608714E-03 | 0.11323974E-03 | 0.68608714E-03 | -0.15705033E-07 |
56 | 3 | -0.21538511 | 0.37821720E-01 | -0.21538511 | 0.25667047E-03 |
57 | 2 | 5.0173519 | 0.62258424 | 5.0173519 | -0.50236511E-01 |
58 | 1 | -19.904252 | 0.86481321 | -19.904252 | 0.58144210 |
59 | 0 | 16.688993 | 0.62060609E-01 | 16.688993 | |
60 | 4 | 0.75441920E-10 | 0.23883683E-10 | 0.47514224E-10 | -0.69373194E-20 |
61 | 3 | -0.33730907E-03 | 0.89366797E-04 | -0.22574866E-03 | 0.77828620E-10 |
62 | 2 | 0.58624422 | 0.18542418 | 0.49024360 | -0.17301269E-03 |
63 | 1 | -11.299243 | 2.8799011 | -8.6239668 | 0.15905732 |
64 | 0 | 15.219762 | 1.4410112 | 12.640375 | |
65 | 5 | -0.32935335E-06 | 0.42931990E-07 | -0.32935335E-06 | 0.47097488E-08 |
66 | 4 | 0.68052310E-03 | 0.12823787E-03 | 0.68052310E-03 | -0.14200104E-04 |
67 | 3 | -0.11535993 | 0.17375615E-01 | -0.11535993 | 0.40770076E-02 |
68 | 2 | 2.1922172 | 0.21284128 | 2.1922172 | -0.13171357 |
69 | 1 | -7.8704965 | 0.30308566 | -7.8704965 | 0.79499401 |
70 | 0 | 6.3596665 | 0.33276539E-01 | 6.3596665 | |
71 | 6 | 0.97988530E-11 | 0.43917118E-12 | 0.24496810E-11 | -0.34892153E-15 |
72 | 5 | -0.75005310E-05 | 0.16499726E-06 | -0.28271466E-05 | 0.19166609E-11 |
73 | 4 | 0.32354224E-01 | 0.66949565E-03 | 0.10283773E-01 | -0.11111676E-05 |
74 | 3 | -1.8201547 | 0.67148336E-01 | -0.62076152 | 0.38788549E-02 |
75 | 2 | 21.173821 | 0.53241617 | 7.5279938 | -0.97325542E-01 |
76 | 1 | -64.420211 | 0.46601667 | -21.697519 | 0.64629334 |
77 | 0 | 46.121323 | 0.20873329E-01 | 15.867130 | |
78 | 4 | 0.69987904E-07 | 0.26228811E-07 | 0.69987904E-07 | -0.89457852E-14 |
79 | 3 | -0.30987589E-02 | 0.10225415E-02 | -0.30987589E-02 | 0.11234143E-06 |
80 | 2 | 0.81559891 | 0.24124884 | 0.81559891 | -0.23762713E-02 |
81 | 1 | -7.9329461 | 1.4912083 | -7.9329461 | 0.29351368 |
82 | 0 | 9.2684202 | 0.41449462 | 9.2684202 | |
83 | 8 | 0.10972129E-06 | 0.13118744E-13 | 0.57415395E-12 | -0.16121901E-12 |
84 | 7 | -0.25702593E-04 | 0.79302418E-09 | -0.11209345E-05 | 0.31491488E-06 |
85 | 6 | 0.16732899E-02 | 0.55842834E-06 | 0.21835020E-03 | -0.62999473E-04 |
86 | 5 | -0.40973943E-01 | 0.43793696E-04 | -0.11788181E-01 | 0.36016799E-02 |
87 | 4 | 0.43752526 | 0.66464187E-03 | 0.21386917 | -0.72376639E-01 |
88 | 3 | -2.2272953 | 0.23440260E-02 | -1.3884299 | 0.54574706 |
89 | 2 | 5.4333867 | 0.19014595E-02 | 3.6315139 | -1.6855834 |
90 | 1 | -6.0131296 | 0.26548191E-03 | -4.0346078 | 2.1907513 |
91 | 0 | 2.4140608 | 0.16612988E-05 | 1.5944472 |
Construction Name | Index | #Layers | Roughness | Conductance {Btu/h-ft2-F} | Conductance (Before Adjusted) {Btu/h-ft2-F} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | EXTERIOR WINDOW | 12 | 1 | VerySmooth | 0.300 | 0.300 | 1.000 | 0.217 | ||
2 | INTERIOR WINDOW | 13 | 1 | VerySmooth | 0.300 | 0.300 | 1.000 | 0.217 | ||
3 | WINDOW_W_BLINDS | 18 | 2 | VerySmooth | 0.300 | 0.300 | 1.000 | 0.208 | ||
4 | TDD DOME | 22 | 1 | VerySmooth | 1.071 | 1.071 | 1.000 | 0.929 | ||
5 | TDD DIFFUSER | 23 | 1 | VerySmooth | 1.077 | 1.077 | 1.000 | 0.906 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {ft} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLASS | SpectralAverage | 0.13728 | 0.12813 | 0.66698 | 0.66698 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
2 | GLASS | SpectralAverage | 0.13728 | 0.12813 | 0.66698 | 0.66698 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
3 | GLASS | SpectralAverage | 0.13728 | 0.12813 | 0.66698 | 0.66698 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10138 | 1.00000 | No | |
4 | CLEAR ACRYLIC PLASTIC | SpectralAverage | 0.00984 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No | |
5 | DIFFUSING ACRYLIC PLASTIC | SpectralAverage | 0.00722 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No |
Material Name | Slat Width {ft} | Slat Separation {ft} | Slat Thickness {ft} | Slat Angle {deg} | Slat Beam Solar Transmittance | Slat Beam Solar Front Reflectance | Blind To Glass Distance {ft} | |
1 | INT_BLIND | 0.0820 | 0.0615 | 0.0033 | 45.000 | 0.000 | 0.500 | 0.164 |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 20 | 15000. | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {ft3} | Maximum Capacity {Btu/h} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | "DX Coil Total Cooling Rate {W | HPWH Only}" | |
1 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
2 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
3 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
4 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
5 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
6 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
7 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
8 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
9 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
10 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
11 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
12 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
13 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
14 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
15 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
16 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
17 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 | |
18 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 6.6825 | 4259.9 | 0.000 | 0.0000 | 736 |
Node Number | Height {ft} | Volume {ft3} | Maximum Capacity {Btu/h} | Off-Cycle UA {Btu/h-F} | On-Cycle UA {Btu/h-F} | Number Of Inlets | Number Of Outlets | |
1 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
2 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
3 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
4 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
5 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
6 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
7 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
8 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
9 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
10 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
11 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
12 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
13 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
14 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
15 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
16 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
17 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
18 | 1 | 5.2299 | 6.6825 | 0.000 | 2.8646 | 2.8646 | 1 | 1 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
2 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
3 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
4 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
5 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
6 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
7 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
8 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
9 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
10 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
11 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
12 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
13 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
14 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
15 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
16 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
17 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
18 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
19 | ATTICVENT | ALWAYS_AVAIL | ATTIC | 7802.66 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/person Area {ft3/min-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {psi} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{F}/Schedule | Maximum Indoor Temperature{F}/Schedule | Delta Temperature{F}/Schedule | Minimum Outdoor Temperature{F}/Schedule | Maximum Outdoor Temperature{F}/Schedule | Maximum WindSpeed{ft/min} | |
1 | VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
2 | VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
3 | VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
4 | VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
5 | VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
6 | VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
7 | VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
8 | VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
9 | VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
10 | VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
11 | VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
12 | VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
13 | VENTILATION_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
14 | VENTILATION_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
15 | VENTILATION_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
16 | VENTILATION_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
17 | VENTILATION_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
18 | VENTILATION_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | UNHEATEDBSMT | Mixing/Well-Stirred |
2 | BREEZEWAY | Mixing/Well-Stirred |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
15 | ATTIC | Mixing/Well-Stirred |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {Btu/h} | User Des Load {Btu/h} | Calc Des Air Flow Rate {ft3/min} | User Des Air Flow Rate {ft3/min} | Design Day Name | Date/Time of Peak | Temperature at Peak {F} | Humidity Ratio at Peak {lbWater/lbDryAir} | Floor Area {ft2} | # Occupants | Calc Outdoor Air Flow Rate {ft3/min} | Calc DOAS Heat Addition Rate {Btu/h} | |
1 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | 8427.69978 | 8427.69978 | 413.70757 | 413.70757 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 96.91399 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | 6531.06281 | 6531.06281 | 137.07583 | 137.07583 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | 4942.01668 | 4942.01668 | 242.60590 | 242.60590 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 92.62400 | 0.00686 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | 4985.13321 | 4985.13321 | 104.63050 | 104.63050 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | 6305.63951 | 6305.63951 | 309.53386 | 309.53386 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 100.58000 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
6 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | 6531.67485 | 6531.67485 | 137.08854 | 137.08854 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
7 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | 8291.54385 | 8291.54385 | 407.03385 | 407.03385 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 96.52401 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
8 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Heating | 6535.00957 | 6535.00957 | 137.15867 | 137.15867 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
9 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | 4914.34263 | 4914.34263 | 241.24997 | 241.24997 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 92.62400 | 0.00686 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
10 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Heating | 4986.42345 | 4986.42345 | 104.65761 | 104.65761 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
11 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | 5992.24523 | 5992.24523 | 294.15251 | 294.15251 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 100.11200 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
12 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Heating | 6530.22032 | 6530.22032 | 137.05803 | 137.05803 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
13 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | 8595.24488 | 8595.24488 | 421.94910 | 421.94910 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 96.52401 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
14 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | 5775.66460 | 5775.66460 | 121.22435 | 121.22435 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
15 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | 5218.78263 | 5218.78263 | 256.18641 | 256.18641 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 91.45400 | 0.00686 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
16 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | 4222.92629 | 4222.92629 | 88.63516 | 88.63516 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
17 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | 6556.99305 | 6556.99305 | 321.88555 | 321.88555 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 100.58000 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
18 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | 5777.73395 | 5777.73395 | 121.26778 | 121.26778 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
19 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | 8474.23096 | 8474.23096 | 415.99571 | 415.99571 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 96.13400 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
20 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Heating | 5778.62659 | 5778.62659 | 121.28643 | 121.28643 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
21 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | 5182.62386 | 5182.62386 | 254.42793 | 254.42793 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 91.45400 | 0.00686 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
22 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Heating | 4223.36562 | 4223.36562 | 88.64427 | 88.64427 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
23 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | 6302.15200 | 6302.15200 | 309.36437 | 309.36437 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 94.96400 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
24 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Heating | 5775.60827 | 5775.60827 | 121.22308 | 121.22308 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
25 | LIVING_UNIT3_BACKROW_TOPFLOOR | Cooling | 7403.60593 | 7403.60593 | 363.45334 | 363.45334 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 94.37900 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
26 | LIVING_UNIT3_BACKROW_TOPFLOOR | Heating | 7385.33142 | 7385.33142 | 155.00507 | 155.00507 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
27 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Cooling | 7326.38970 | 7326.38970 | 359.66097 | 359.66097 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 95.35401 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
28 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Heating | 7386.99010 | 7386.99010 | 155.03981 | 155.03981 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
29 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Cooling | 9526.87998 | 9526.87998 | 467.66943 | 467.66943 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 96.13400 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
30 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Heating | 7384.56963 | 7384.56963 | 154.98896 | 154.98896 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
31 | LIVING_UNIT2_BACKROW_TOPFLOOR | Cooling | 6295.34994 | 6295.34994 | 309.04657 | 309.04657 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 92.03900 | 0.00686 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
32 | LIVING_UNIT2_BACKROW_TOPFLOOR | Heating | 5826.32192 | 5826.32192 | 122.28537 | 122.28537 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
33 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Cooling | 6223.06556 | 6223.06556 | 305.48725 | 305.48725 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 91.45400 | 0.00686 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
34 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Heating | 5826.12119 | 5826.12119 | 122.28134 | 122.28134 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
35 | LIVING_UNIT1_BACKROW_TOPFLOOR | Cooling | 9575.80564 | 9575.80564 | 470.08469 | 470.08469 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 96.13400 | 0.00687 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
36 | LIVING_UNIT1_BACKROW_TOPFLOOR | Heating | 7386.62317 | 7386.62317 | 155.03218 | 155.03218 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22.64000 | 0.00281 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [ft3/min] | User Des Air Flow Rate [ft3/min] | Design Day Name | Date/Time of Peak | |
1 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2707.59 | 413.70757 | 413.70757 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 2497.34 | 137.07583 | 137.07583 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
3 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1646.85 | 242.60590 | 242.60590 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 2050.86 | 104.63050 | 104.63050 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
5 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2139.54 | 309.53386 | 309.53386 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 2497.51 | 137.08854 | 137.08854 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
7 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2663.41 | 407.03385 | 407.03385 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Heating | Sensible | 2498.48 | 137.15867 | 137.15867 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
9 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1638.85 | 241.24997 | 241.24997 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Heating | Sensible | 2051.23 | 104.65761 | 104.65761 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
11 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2043.15 | 294.15251 | 294.15251 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Heating | Sensible | 2497.09 | 137.05803 | 137.05803 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
13 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2751.20 | 421.94910 | 421.94910 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 2279.18 | 121.22435 | 121.22435 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
15 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 1712.37 | 256.18641 | 256.18641 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 1830.74 | 88.63516 | 88.63516 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
17 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2212.21 | 321.88555 | 321.88555 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 2279.78 | 121.26778 | 121.26778 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
19 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2711.39 | 415.99571 | 415.99571 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Heating | Sensible | 2280.04 | 121.28643 | 121.28643 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
21 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1701.91 | 254.42793 | 254.42793 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
22 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Heating | Sensible | 1830.86 | 88.64427 | 88.64427 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
23 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2069.00 | 309.36437 | 309.36437 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
24 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Heating | Sensible | 2279.17 | 121.22308 | 121.22308 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
25 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Cooling | Sensible | 3015.68 | 467.66943 | 467.66943 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
26 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Heating | Sensible | 2743.84 | 154.98896 | 154.98896 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
27 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Cooling | Sensible | 2002.68 | 305.48725 | 305.48725 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
28 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Heating | Sensible | 2293.74 | 122.28134 | 122.28134 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
29 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Cooling | Sensible | 2369.91 | 359.66097 | 359.66097 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
30 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Heating | Sensible | 2744.54 | 155.03981 | 155.03981 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
31 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Cooling | Sensible | 3029.83 | 470.08469 | 470.08469 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
32 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Heating | Sensible | 2744.43 | 155.03218 | 155.03218 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
33 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Cooling | Sensible | 2030.82 | 309.04657 | 309.04657 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
34 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Heating | Sensible | 2293.80 | 122.28537 | 122.28537 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
35 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Cooling | Sensible | 2380.16 | 363.45334 | 363.45334 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
36 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Heating | Sensible | 2744.06 | 155.00507 | 155.00507 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 413.70757 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 242.60590 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 309.53386 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 407.03385 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 241.24997 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 294.15251 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 421.94910 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 256.18641 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 321.88555 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 415.99571 |
11 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 254.42793 |
12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 309.36437 |
13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 363.45334 |
14 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 359.66097 |
15 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 467.66943 |
16 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 309.04657 |
17 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 305.48725 |
18 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 470.08469 |
19 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 413.70757 |
20 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 413.70757 |
21 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 413.70757 |
22 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 413.70757 |
23 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 413.70757 |
24 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 413.70757 |
25 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 242.60590 |
28 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 242.60590 |
29 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 242.60590 |
30 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 242.60590 |
31 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 242.60590 |
32 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 242.60590 |
33 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 309.53386 |
36 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 309.53386 |
37 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 309.53386 |
38 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 309.53386 |
39 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 309.53386 |
40 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 309.53386 |
41 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 407.03385 |
44 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 407.03385 |
45 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 407.03385 |
46 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 407.03385 |
47 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 407.03385 |
48 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 407.03385 |
49 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 241.24997 |
52 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 241.24997 |
53 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 241.24997 |
54 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 241.24997 |
55 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 241.24997 |
56 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 241.24997 |
57 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 294.15251 |
60 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 294.15251 |
61 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 294.15251 |
62 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 294.15251 |
63 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 294.15251 |
64 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 294.15251 |
65 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 421.94910 |
68 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 421.94910 |
69 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 421.94910 |
70 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 421.94910 |
71 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 421.94910 |
72 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 421.94910 |
73 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 256.18641 |
76 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 256.18641 |
77 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 256.18641 |
78 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 256.18641 |
79 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 256.18641 |
80 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 256.18641 |
81 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 321.88555 |
84 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 321.88555 |
85 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 321.88555 |
86 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 321.88555 |
87 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 321.88555 |
88 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 321.88555 |
89 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 415.99571 |
92 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 415.99571 |
93 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 415.99571 |
94 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 415.99571 |
95 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 415.99571 |
96 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 415.99571 |
97 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
98 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
99 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 254.42793 |
100 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 254.42793 |
101 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 254.42793 |
102 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 254.42793 |
103 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 254.42793 |
104 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 254.42793 |
105 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
106 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
107 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 309.36437 |
108 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 309.36437 |
109 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 309.36437 |
110 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 309.36437 |
111 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 309.36437 |
112 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 309.36437 |
113 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
114 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
115 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 467.66943 |
116 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 467.66943 |
117 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 467.66943 |
118 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 467.66943 |
119 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 467.66943 |
120 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 467.66943 |
121 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
122 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
123 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 305.48725 |
124 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 305.48725 |
125 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 305.48725 |
126 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 305.48725 |
127 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 305.48725 |
128 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 305.48725 |
129 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
130 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
131 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 359.66097 |
132 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 359.66097 |
133 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 359.66097 |
134 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 359.66097 |
135 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 359.66097 |
136 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 359.66097 |
137 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
138 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
139 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 470.08469 |
140 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 470.08469 |
141 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 470.08469 |
142 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 470.08469 |
143 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 470.08469 |
144 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 470.08469 |
145 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
146 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
147 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 309.04657 |
148 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 309.04657 |
149 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 309.04657 |
150 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 309.04657 |
151 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 309.04657 |
152 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 309.04657 |
153 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
154 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
155 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 363.45334 |
156 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 363.45334 |
157 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 363.45334 |
158 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 363.45334 |
159 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 363.45334 |
160 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 363.45334 |
161 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
162 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
163 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 413.70757 |
164 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 242.60590 |
165 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 309.53386 |
166 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 407.03385 |
167 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 241.24997 |
168 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 294.15251 |
169 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 421.94910 |
170 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 256.18641 |
171 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 321.88555 |
172 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 415.99571 |
173 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 254.42793 |
174 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 309.36437 |
175 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 467.66943 |
176 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 305.48725 |
177 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 359.66097 |
178 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 470.08469 |
179 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 309.04657 |
180 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 363.45334 |
181 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 413.70757 |
182 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.15498 |
183 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.76057 |
184 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 413.70757 |
185 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 413.70757 |
186 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 413.70757 |
187 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.15498 |
188 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 24736.03533 |
189 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.53908 |
190 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 371.15446 |
191 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
192 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 413.70757 |
193 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 242.60590 |
194 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.69646 |
195 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.75051 |
196 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 242.60590 |
197 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 242.60590 |
198 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 242.60590 |
199 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.69646 |
200 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 15496.91043 |
201 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.59070 |
202 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 228.42276 |
203 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
204 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 242.60590 |
205 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 309.53386 |
206 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.92603 |
207 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73602 |
208 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 309.53386 |
209 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 309.53386 |
210 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 309.53386 |
211 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.92603 |
212 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 19111.30542 |
213 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.96172 |
214 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 284.25628 |
215 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
216 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 309.53386 |
217 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 407.03385 |
218 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.13675 |
219 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.76046 |
220 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 407.03385 |
221 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 407.03385 |
222 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 407.03385 |
223 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.13675 |
224 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 24375.15750 |
225 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.50203 |
226 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 365.58343 |
227 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
228 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 407.03385 |
229 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 241.24997 |
230 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.69303 |
231 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.75032 |
232 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 241.24997 |
233 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 241.24997 |
234 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 241.24997 |
235 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.69303 |
236 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 15423.55891 |
237 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.58318 |
238 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 227.28747 |
239 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
240 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 241.24997 |
241 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 294.15251 |
242 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.88149 |
243 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73556 |
244 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 294.15251 |
245 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 294.15251 |
246 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 294.15251 |
247 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.88149 |
248 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 18280.61676 |
249 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.87645 |
250 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 271.41915 |
251 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
252 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 294.15251 |
253 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 421.94910 |
254 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.17752 |
255 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.76068 |
256 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 421.94910 |
257 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 421.94910 |
258 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 421.94910 |
259 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.17752 |
260 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 25179.69062 |
261 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.58461 |
262 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 377.95807 |
263 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
264 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 421.94910 |
265 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 256.18641 |
266 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.72547 |
267 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.75544 |
268 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 256.18641 |
269 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 256.18641 |
270 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 256.18641 |
271 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.72547 |
272 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 16230.27475 |
273 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.66598 |
274 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 239.74591 |
275 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
276 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 256.18641 |
277 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 321.88555 |
278 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.95793 |
279 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.73745 |
280 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 321.88555 |
281 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 321.88555 |
282 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 321.88555 |
283 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.95793 |
284 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 19777.22696 |
285 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.03007 |
286 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 294.51043 |
287 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
288 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 321.88555 |
289 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 415.99571 |
290 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.16167 |
291 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.76049 |
292 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 415.99571 |
293 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 415.99571 |
294 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 415.99571 |
295 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.16167 |
296 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 24858.95078 |
297 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.55170 |
298 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 373.00753 |
299 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
300 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 415.99571 |
301 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 254.42793 |
302 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.72101 |
303 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.75521 |
304 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 254.42793 |
305 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 254.42793 |
306 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 254.42793 |
307 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.72101 |
308 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 16134.43539 |
309 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.65615 |
310 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 238.26329 |
311 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
312 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 254.42793 |
313 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 309.36437 |
314 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.88363 |
315 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.75297 |
316 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 309.36437 |
317 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 309.36437 |
318 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 309.36437 |
319 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.88363 |
320 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 19101.82030 |
321 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.96073 |
322 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 284.07639 |
323 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
324 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 309.36437 |
325 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 467.66943 |
326 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.29080 |
327 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.76493 |
328 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 467.66943 |
329 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 467.66943 |
330 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 467.66943 |
331 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.29080 |
332 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 27649.59757 |
333 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.83814 |
334 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 416.07485 |
335 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
336 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 467.66943 |
337 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 305.48725 |
338 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.84682 |
339 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.76365 |
340 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 305.48725 |
341 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 305.48725 |
342 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 305.48725 |
343 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.84682 |
344 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 18892.51761 |
345 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.93925 |
346 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 280.89355 |
347 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
348 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 305.48725 |
349 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 359.66097 |
350 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.01180 |
351 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.75833 |
352 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 359.66097 |
353 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 359.66097 |
354 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 359.66097 |
355 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.01180 |
356 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 21817.01183 |
357 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.23944 |
358 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 326.01374 |
359 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
360 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 359.66097 |
361 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 470.08469 |
362 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.29692 |
363 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.76504 |
364 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 470.08469 |
365 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 470.08469 |
366 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 470.08469 |
367 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.29692 |
368 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 27779.28080 |
369 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.85146 |
370 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 418.07580 |
371 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
372 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 470.08469 |
373 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 309.04657 |
374 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.86047 |
375 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.76235 |
376 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 309.04657 |
377 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 309.04657 |
378 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 309.04657 |
379 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.86047 |
380 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 19084.09984 |
381 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.95893 |
382 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 283.85413 |
383 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
384 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 309.04657 |
385 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 363.45334 |
386 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.01419 |
387 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.76070 |
388 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 363.45334 |
389 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 363.45334 |
390 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 363.45334 |
391 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.01419 |
392 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 22021.71819 |
393 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.26046 |
394 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 329.17462 |
395 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 363.45334 |
397 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
398 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
399 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
400 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
401 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
402 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
403 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
404 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
405 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
406 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
407 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
408 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
409 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
410 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
411 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
412 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
413 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
414 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
415 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
416 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
417 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
418 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
419 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
420 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
421 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
422 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
423 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
424 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
425 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
426 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
427 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
428 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
429 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
430 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
431 | Fan:OnOff | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 160.01057 |
432 | WaterHeater:HeatPump:WrappedCondenser | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Evaporator air flow rate [ft3/min] | 160.01057 |
433 | PlantLoop | BOILER LOOP | Maximum Loop Flow Rate [ft3/min] | 5.15763 |
434 | PlantLoop | BOILER LOOP | Plant Loop Volume [ft3] | 10.31798 |
435 | Pump:VariableSpeed | BOILER CIRC PUMP | Design Flow Rate [ft3/min] | 5.15763 |
436 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [Btu/h] | 0.375950E+06 |
437 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [gal/min] | 38.59011 |
438 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
439 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
440 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
441 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
442 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
443 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
444 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
445 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
446 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
447 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
448 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
449 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
450 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
451 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
452 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
453 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
454 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
455 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
456 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
457 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
458 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
459 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
460 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
461 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
462 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
463 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
464 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
465 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
466 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
467 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
468 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
469 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
470 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
471 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
472 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
473 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
474 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
475 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
476 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
477 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
478 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
479 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
480 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
481 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
482 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
483 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
484 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
485 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
486 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
487 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
488 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
489 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
490 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
491 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
492 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
493 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
494 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
495 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
496 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
497 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
498 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
499 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
500 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
501 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
502 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
503 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
504 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
505 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
506 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
507 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
508 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
509 | WaterHeater:Stratified | WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {ton} | Standard Rated Net COP {Btuh/Btuh} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.1 | 3.57 | 12.19 | 12.92 | 12.42 | 12.59 |
2 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.1 | 3.44 | 11.75 | 12.44 | 12.30 | -99999. |
3 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.7 | 3.59 | 12.25 | 12.98 | 12.48 | 12.69 |
4 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.7 | 3.46 | 11.82 | 12.51 | 12.37 | -99999. |
5 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.9 | 3.61 | 12.33 | 13.08 | 12.57 | 12.83 |
6 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.9 | 3.49 | 11.92 | 12.62 | 12.48 | -99999. |
7 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.1 | 3.57 | 12.19 | 12.92 | 12.42 | 12.59 |
8 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.1 | 3.44 | 11.75 | 12.44 | 12.30 | -99999. |
9 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.7 | 3.59 | 12.25 | 12.99 | 12.48 | 12.69 |
10 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.7 | 3.46 | 11.82 | 12.51 | 12.37 | -99999. |
11 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.9 | 3.62 | 12.34 | 13.08 | 12.58 | 12.83 |
12 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.8 | 3.49 | 11.92 | 12.63 | 12.48 | -99999. |
13 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.1 | 3.57 | 12.19 | 12.92 | 12.42 | 12.59 |
14 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.1 | 3.44 | 11.75 | 12.44 | 12.30 | -99999. |
15 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.7 | 3.58 | 12.22 | 12.95 | 12.45 | 12.64 |
16 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.7 | 3.45 | 11.79 | 12.48 | 12.34 | -99999. |
17 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9 | 3.61 | 12.32 | 13.07 | 12.56 | 12.81 |
18 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9 | 3.49 | 11.91 | 12.61 | 12.46 | -99999. |
19 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.1 | 3.57 | 12.19 | 12.92 | 12.42 | 12.59 |
20 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.1 | 3.44 | 11.75 | 12.44 | 12.30 | -99999. |
21 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.7 | 3.58 | 12.22 | 12.95 | 12.45 | 12.64 |
22 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.7 | 3.46 | 11.79 | 12.48 | 12.34 | -99999. |
23 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.9 | 3.59 | 12.24 | 12.97 | 12.47 | 12.67 |
24 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.8 | 3.46 | 11.81 | 12.50 | 12.36 | -99999. |
25 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.2 | 3.56 | 12.16 | 12.89 | 12.39 | 12.55 |
26 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.2 | 3.44 | 11.72 | 12.41 | 12.27 | -99999. |
27 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.57 | 12.17 | 12.90 | 12.40 | 12.56 |
28 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.44 | 11.74 | 12.42 | 12.28 | -99999. |
29 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.0 | 3.58 | 12.21 | 12.94 | 12.44 | 12.61 |
30 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.0 | 3.45 | 11.77 | 12.46 | 12.32 | -99999. |
31 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.2 | 3.56 | 12.16 | 12.89 | 12.39 | 12.55 |
32 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.2 | 3.44 | 11.72 | 12.41 | 12.27 | -99999. |
33 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.57 | 12.18 | 12.91 | 12.41 | 12.58 |
34 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.44 | 11.75 | 12.43 | 12.29 | -99999. |
35 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.0 | 3.57 | 12.19 | 12.92 | 12.42 | 12.59 |
36 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.0 | 3.44 | 11.75 | 12.44 | 12.30 | -99999. |
Component Type | Name | Nominal Total Capacity {Btu/h} | |
1 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 25907.35 |
2 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 15707.93 |
3 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 19701.54 |
4 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 25509.58 |
5 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 15626.72 |
6 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 18784.05 |
7 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 26394.72 |
8 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 16518.75 |
9 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 20435.49 |
10 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 26041.24 |
11 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 16412.74 |
12 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 19689.87 |
13 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 29115.79 |
14 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 19460.68 |
15 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 22685.98 |
16 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 29258.65 |
17 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 19672.26 |
18 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 22911.75 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | SizingPeriod:DesignDay | 12/21 | 12/21 | WinterDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
2 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | SizingPeriod:DesignDay | 07/21 | 07/21 | SummerDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
3 | ANNUAL | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | No | SizingPeriod:DesignDay | ||
2 | No | SizingPeriod:DesignDay | ||
3 | No |
NumberofWarmupDays | |
1 | 6 |
2 | 7 |
3 | 12 |
Max Dry-Bulb Temp {F} | Temp Range {dC} | Temp Range Ind Type | Hum Ind Type | Hum Ind Value at Max Temp | Hum Ind Units | Pressure {psi} | Wind Direction {deg CW from N} | Wind Speed {ft/min} | Clearness | Rain | Snow | |
1 | 22.64 | 0.00 | DefaultMultipliers | Wetbulb | -5.20 | {C} | 13. | 20 | 433.1 | 0.00 | No | No |
2 | 100.58 | 13.00 | DefaultMultipliers | Wetbulb | 18.10 | {C} | 13. | 280 | 767.8 | 0.00 | No | No |
DayOfYear | ASHRAE A Coeff | ASHRAE B Coeff | ASHRAE C Coeff | Solar Constant-Annual Variation | Eq of Time {minutes} | Solar Declination Angle {deg} | Solar Model | |
1 | 355 | 1232.8 | 0.1424 | 5.7719E-002 | 1.0 | 2.45 | -24. | ASHRAEClearSky |
2 | 202 | 1084.4 | 0.2082 | 0.1365 | 1.0 | -6.23 | 20.6 | ASHRAETau |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaF} | Std Dev Warmup Temperature Difference {deltaF} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {Btu/h} | Std Dev Warmup Load Difference {Btu/h} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | UNHEATEDBSMT | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.001234170 | 0.001062310 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
2 | BREEZEWAY | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000135105 | 0.000049787 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000029822 | 0.000096957 | Pass | Pass | 0.014099451 | 0.025557848 | Pass | Pass |
4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000116021 | 0.000192814 | Pass | Pass | 0.018532983 | 0.033811416 | Pass | Pass |
5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000045789 | 0.000147617 | Pass | Pass | 0.014073268 | 0.025558080 | Pass | Pass |
6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000045564 | 0.000163752 | Pass | Pass | 0.014063491 | 0.025537974 | Pass | Pass |
7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000148577 | 0.000262207 | Pass | Pass | 0.018542593 | 0.033847202 | Pass | Pass |
8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000037070 | 0.000122699 | Pass | Pass | 0.014101563 | 0.025597971 | Pass | Pass |
9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000051897 | 0.000169702 | Pass | Pass | 0.015626718 | 0.028008070 | Pass | Pass |
10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000093738 | 0.000228868 | Pass | Pass | 0.021726772 | 0.039396986 | Pass | Pass |
11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000029940 | 0.000087239 | Pass | Pass | 0.015624502 | 0.028007596 | Pass | Pass |
12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000021718 | 0.000062770 | Pass | Pass | 0.015619118 | 0.028007049 | Pass | Pass |
13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000077559 | 0.000165472 | Pass | Pass | 0.021699056 | 0.039375340 | Pass | Pass |
14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000036836 | 0.000107813 | Pass | Pass | 0.015634485 | 0.028003881 | Pass | Pass |
15 | ATTIC | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000067461 | 0.000056518 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
16 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000059424 | 0.000181907 | Pass | Pass | 0.012207317 | 0.020747434 | Pass | Pass |
17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000046390 | 0.000145659 | Pass | Pass | 0.012157211 | 0.020631884 | Pass | Pass |
18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000018555 | 0.000052758 | Pass | Pass | 0.012168427 | 0.020629845 | Pass | Pass |
19 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000123077 | 0.000328774 | Pass | Pass | 0.015668042 | 0.026444913 | Pass | Pass |
20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000114965 | 0.000276468 | Pass | Pass | 0.015684725 | 0.026613383 | Pass | Pass |
21 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 0.000058736 | 0.000203628 | Pass | Pass | 0.012178310 | 0.020605321 | Pass | Pass |
22 | UNHEATEDBSMT | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.025321301 | 0.013233494 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
23 | BREEZEWAY | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.104467067 | 0.057006033 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
24 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.004648140 | 0.022509637 | Pass | Pass | 0.077353946 | 0.040481388 | Pass | Pass |
25 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.010135477 | 0.055210500 | Pass | Pass | 0.109631330 | 0.433965884 | Pass | Pass |
26 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000033492 | 0.000220080 | Pass | Pass | 0.066566116 | 0.059598683 | Pass | Pass |
27 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.003450721 | 0.017099972 | Pass | Pass | 0.076612455 | 0.036528036 | Pass | Pass |
28 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.008892673 | 0.047451591 | Pass | Pass | 0.106678340 | 0.423980125 | Pass | Pass |
29 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000080478 | 0.000303367 | Pass | Pass | 0.065856033 | 0.060998698 | Pass | Pass |
30 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000655221 | 0.005032023 | Pass | Pass | 0.067543511 | 0.026129402 | Pass | Pass |
31 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.005495426 | 0.027188199 | Pass | Pass | 0.062272412 | 0.133768859 | Pass | Pass |
32 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000073340 | 0.000318129 | Pass | Pass | 0.057320084 | 0.049500571 | Pass | Pass |
33 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000132389 | 0.000902151 | Pass | Pass | 0.067986380 | 0.027237822 | Pass | Pass |
34 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.004321208 | 0.020941723 | Pass | Pass | 0.052766514 | 0.066524349 | Pass | Pass |
35 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000056517 | 0.000237797 | Pass | Pass | 0.056433092 | 0.050760867 | Pass | Pass |
36 | ATTIC | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.598227290 | 0.457122457 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
37 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000036849 | 0.000212191 | Pass | Pass | 0.056237954 | 0.047402804 | Pass | Pass |
38 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000036243 | 0.000211391 | Pass | Pass | 0.056119016 | 0.047044527 | Pass | Pass |
39 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000030574 | 0.000195652 | Pass | Pass | 0.067962767 | 0.026679314 | Pass | Pass |
40 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.001645568 | 0.009213478 | Pass | Pass | 0.048218083 | 0.024937035 | Pass | Pass |
41 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.002524768 | 0.012625089 | Pass | Pass | 0.047857271 | 0.028689160 | Pass | Pass |
42 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 0.000030019 | 0.000195648 | Pass | Pass | 0.068180846 | 0.025901658 | Pass | Pass |
43 | UNHEATEDBSMT | RunPeriod: ANNUAL | 0.028171769 | 0.021933588 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
44 | BREEZEWAY | RunPeriod: ANNUAL | 0.064273113 | 0.039678678 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
45 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.083310216 | 0.216279825 | Pass | Pass | 0.404487553 | 0.856030651 | Pass | Pass |
46 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.120435778 | 0.271055407 | Pass | Pass | 0.411268684 | 1.035923142 | Pass | Pass |
47 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.145926094 | 0.290964340 | Pass | Pass | 0.678477935 | 2.636346655 | Pass | Pass |
48 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.178880412 | 0.303351714 | Pass | Pass | 1.177381794 | 4.486535779 | Pass | Pass |
49 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.066196123 | 0.202301877 | Pass | Pass | 4.162126535 | 0.341082E+02 | Pass | Pass |
50 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.036654848 | 0.078179056 | Pass | Pass | 0.808970488 | 3.883780804 | Pass | Pass |
51 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.091861563 | 0.235272071 | Pass | Pass | 0.643755410 | 1.944131082 | Pass | Pass |
52 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.123119245 | 0.254534724 | Pass | Pass | 0.447695387 | 1.167928653 | Pass | Pass |
53 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.142368568 | 0.277412426 | Pass | Pass | 0.678575678 | 2.473626858 | Pass | Pass |
54 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.172431395 | 0.294210891 | Pass | Pass | 0.959774658 | 3.484469522 | Pass | Pass |
55 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.097535954 | 0.225445018 | Pass | Pass | 0.431221413 | 0.963636692 | Pass | Pass |
56 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.089275357 | 0.175084070 | Pass | Pass | 0.953516311 | 3.588368654 | Pass | Pass |
57 | ATTIC | RunPeriod: ANNUAL | 0.541008826 | 0.471227035 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
58 | LIVING_UNIT3_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.062073201 | 0.134576241 | Pass | Pass | 0.968174918 | 3.331043904 | Pass | Pass |
59 | LIVING_UNIT3_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.138014377 | 0.270021560 | Pass | Pass | 0.915020620 | 3.373645003 | Pass | Pass |
60 | LIVING_UNIT1_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.105741671 | 0.229677157 | Pass | Pass | 0.288725735 | 0.584652974 | Pass | Pass |
61 | LIVING_UNIT2_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.086359715 | 0.204138760 | Pass | Pass | 0.572828987 | 1.479829458 | Pass | Pass |
62 | LIVING_UNIT2_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.135623268 | 0.283769679 | Pass | Pass | 0.734440135 | 2.509762618 | Pass | Pass |
63 | LIVING_UNIT1_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.132016737 | 0.254354820 | Pass | Pass | 1.159154905 | 3.818667153 | Pass | Pass |
Report: Annual Heat Emissions Report
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Annual Heat Emissions SummaryEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [kBtu] | 2870293.28 | 296173.77 | 85362.64 | 0.00 | 375276.99 | 3627122.14 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Heat Index HoursSafe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
UNHEATEDBSMT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 6282.67 | 2352.33 | 125.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 6569.33 | 997.83 | 789.67 | 403.17 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 6282.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2352.33 | 789.67 | 403.17 | 0.00 |
Average | 8537.71 | 159.53 | 43.56 | 19.20 | 0.00 |
Sum | 179292.00 | 3350.17 | 914.67 | 403.17 | 0.00 |
Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 10339.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 217122.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 7508.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 157680.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
UNHEATEDBSMT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 7586.17 | 1173.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8728.17 | 31.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8734.33 | 25.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8733.50 | 26.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8728.50 | 31.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8735.00 | 25.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8733.67 | 26.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 6695.83 | 1429.83 | 443.33 | 186.17 | 4.83 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8751.17 | 8.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
Min | 6695.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1429.83 | 443.33 | 186.17 | 4.83 |
Average | 8594.74 | 135.06 | 21.11 | 8.87 | 0.23 |
Sum | 180489.50 | 2836.17 | 443.33 | 186.17 | 4.83 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12006.95 | 55.43 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12019.52 | 42.86 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12012.98 | 49.41 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12006.79 | 55.59 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12020.12 | 42.26 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12013.52 | 48.86 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12050.90 | 11.49 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12058.74 | 3.64 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12053.72 | 8.66 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12052.60 | 9.78 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12058.74 | 3.64 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12052.72 | 9.66 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12051.46 | 10.92 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 12051.13 | 11.25 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12047.23 | 15.15 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 12056.07 | 6.31 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 12053.09 | 9.29 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12049.56 | 12.82 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 12058.74 | 55.59 | 0.00 | 0.00 | 0.00 |
Average | 10319.80 | 19.38 | 0.00 | 0.00 | 0.00 |
Sum | 216715.84 | 407.02 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8728.17 | 31.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8734.33 | 25.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8733.50 | 26.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8728.50 | 31.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8735.00 | 25.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8733.67 | 26.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8751.17 | 8.83 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8757.67 | 31.83 | 0.00 | 0.00 | 0.00 |
Average | 7497.50 | 11.07 | 0.00 | 0.00 | 0.00 |
Sum | 157447.50 | 232.50 | 0.00 | 0.00 | 0.00 |
Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
UNHEATEDBSMT | 0.00 | - | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Min | 0.00 | - | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Average | 7508.57 | - | 0.00 | 0.00 | 0.00 |
Sum | 157680.00 | - | 0.00 | 0.00 | 0.00 |
Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
UNHEATEDBSMT | 0.00 | - | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Min | 0.00 | - | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | - | 0.00 | 0.00 | 0.00 |
Average | 7508.57 | - | 0.00 | 0.00 | 0.00 |
Sum | 157680.00 | - | 0.00 | 0.00 | 0.00 |
Cooling Setpoint Unmet Degree-Hours [°F·hr] | Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] | Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] | Heating Setpoint Unmet Degree-Hours [°F·hr] | Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] | Heating Setpoint Unmet Occupied Degree-Hours [°C·hr] | |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.16 | 0.17 | 0.16 | 207.34 | 234.03 | 207.34 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.12 | 0.15 | 0.12 | 125.62 | 150.33 | 125.62 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.11 | 0.12 | 0.11 | 272.68 | 462.29 | 272.68 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.13 | 0.16 | 0.13 | 1180.37 | 907.62 | 1180.37 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.09 | 0.14 | 0.09 | 306.76 | 318.27 | 306.76 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.12 | 0.14 | 0.12 | 326.86 | 537.59 | 326.86 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.16 | 0.17 | 0.16 | 151.52 | 143.70 | 151.52 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.14 | 0.18 | 0.14 | 84.42 | 91.44 | 84.42 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.12 | 0.12 | 0.12 | 327.14 | 572.72 | 327.14 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.13 | 0.16 | 0.13 | 1055.80 | 880.50 | 1055.80 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.10 | 0.16 | 0.10 | 247.28 | 262.43 | 247.28 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.14 | 0.14 | 0.14 | 296.61 | 484.84 | 296.61 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.12 | 0.14 | 0.12 | 203.04 | 329.54 | 203.04 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.14 | 0.15 | 0.14 | 252.90 | 413.88 | 252.90 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.16 | 0.17 | 0.16 | 255.45 | 252.28 | 255.45 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.12 | 0.17 | 0.12 | 204.28 | 208.39 | 204.28 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.12 | 0.18 | 0.12 | 88.70 | 96.13 | 88.70 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.14 | 0.16 | 0.14 | 940.36 | 706.14 | 940.36 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.16 | 0.18 | 0.16 | 1180.37 | 907.62 | 1180.37 |
Average | 0.11 | 0.13 | 0.11 | 310.82 | 335.82 | 310.82 |
Sum | 2.30 | 2.77 | 2.30 | 6527.14 | 7052.12 | 6527.14 |
Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 0.00 | 0.00 | 0.00 | 0.00 |
Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 22.64 | 0.00 | 22.64 | Wetbulb [F] | 433.09 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 100.58 | 23.40 | 64.58 | Wetbulb [F] | 767.75 | 280.00 |
Monthly Total Precipitation from .epw [in] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [in] | Monthly Total Roof Irrigation Depth [in] | Monthly Total Rain Collection Volume [ft3] | |
Jan | 0.12 | 6 | |||
Feb | 0.12 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.71 | 7 | |||
Jul | 1.06 | 16 | |||
Aug | 1.61 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 0.91 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 0.28 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_LOWER_LDF | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 839.40 | 839.40 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_LOWER_SDR | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 455.77 | 455.77 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_LOWER_LDB | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 839.40 | 839.40 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BGWALL_LOWER_SDL | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 455.77 | 455.77 | 270.00 | 90.00 | W |
BGFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.39 | 599.39 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.39 | 599.39 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
BREEZEWAYROOF | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 599.39 | 599.39 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.048 | 0.051 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
iz-BREEZEWAYROOF | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 599.39 | 599.39 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
iz-CEILING_UNIT1_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT3_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT3_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT2_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
FLOOR_UNIT2_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT2_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
FLOOR_UNIT1_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
CEILING_UNIT1_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 |
Construction | Frame and Divider | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | NFRC Product Type | Assembly U-Factor [Btu/h-ft2-F] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | |||||||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | |||||||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.300 | 0.217 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.300 | 0.217 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | |||||||
Total or Average | 2126.74 | 0.300 | 0.217 | 0.883 | |||||||||||||||||
North Total or Average | 531.68 | 0.300 | 0.217 | 0.883 | |||||||||||||||||
Non-North Total or Average | 1595.05 | 0.300 | 0.217 | 0.883 |
Frame and Divider | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [Btu/h-ft2-F] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.239 | 0.300 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 0.96 | 0.00 | 0.99 | 0.93 | 0.00 | 1.00 | 0.95 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 0.96 | 0.00 | 0.99 | 0.93 | 0.00 | 1.00 | 0.95 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 0.96 | 0.00 | 0.99 | 0.93 | 0.00 | 1.00 | 0.95 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 0.96 | 0.00 | 0.99 | 0.93 | 0.00 | 1.00 | 0.95 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 0.96 | 0.00 | 0.99 | 0.93 | 0.00 | 1.00 | 0.95 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 0.96 | 0.00 | 0.99 | 0.93 | 0.00 | 1.00 | 0.95 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.00 | 0.94 | 0.85 | 1.00 | 0.99 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [Btu/h-ft2] | Space Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | 0.4008 | 1200.55 | 481.17 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 432.94 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.2915 | 43219.92 | 12599.76 | 11336.81 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
Exterior Lighting Total | 1377.69 | 6034.31 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Central PlantType | Reference Capacity [Btu/h] | Reference Efficiency [Btuh/Btuh] | Rated Capacity [Btu/h] | Rated Efficiency [Btuh/Btuh] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 375950.21 | 0.80 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 13859.72 | 10541.29 | 3318.43 | 0.76 | 4.30 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8357.53 | 6272.45 | 2085.08 | 0.75 | 4.30 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11112.40 | 8178.96 | 2933.44 | 0.74 | 4.30 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 13640.95 | 10373.40 | 3267.55 | 0.76 | 4.30 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8316.35 | 6239.94 | 2076.41 | 0.75 | 4.30 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10577.94 | 7780.71 | 2797.22 | 0.74 | 4.30 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 14130.19 | 10748.50 | 3381.69 | 0.76 | 4.30 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8705.61 | 6576.54 | 2129.08 | 0.76 | 4.30 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 11495.10 | 8477.10 | 3018.00 | 0.74 | 4.30 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 13940.03 | 10601.28 | 3338.75 | 0.76 | 4.30 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8652.11 | 6534.15 | 2117.95 | 0.76 | 4.30 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10603.57 | 7984.13 | 2619.44 | 0.75 | 4.30 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 15489.63 | 11848.45 | 3641.18 | 0.76 | 4.30 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10161.86 | 7760.13 | 2401.72 | 0.76 | 4.30 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12141.65 | 9207.35 | 2934.30 | 0.76 | 4.30 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 15563.05 | 11906.43 | 3656.63 | 0.77 | 4.30 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10325.58 | 7871.70 | 2453.88 | 0.76 | 4.30 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12170.28 | 9257.91 | 2912.37 | 0.76 | 4.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.1 | 3.57 | 12.19 | 12.92 | 12.42 | 12.59 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.7 | 3.59 | 12.25 | 12.98 | 12.48 | 12.69 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.9 | 3.61 | 12.33 | 13.08 | 12.57 | 12.83 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.1 | 3.57 | 12.19 | 12.92 | 12.42 | 12.59 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.7 | 3.59 | 12.25 | 12.99 | 12.48 | 12.69 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.9 | 3.62 | 12.34 | 13.08 | 12.58 | 12.83 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.1 | 3.57 | 12.19 | 12.92 | 12.42 | 12.59 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.7 | 3.58 | 12.22 | 12.95 | 12.45 | 12.64 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9 | 3.61 | 12.32 | 13.07 | 12.56 | 12.81 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.1 | 3.57 | 12.19 | 12.92 | 12.42 | 12.59 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.7 | 3.58 | 12.22 | 12.95 | 12.45 | 12.64 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.9 | 3.59 | 12.24 | 12.97 | 12.47 | 12.67 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.2 | 3.56 | 12.16 | 12.89 | 12.39 | 12.55 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.57 | 12.17 | 12.90 | 12.40 | 12.56 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.0 | 3.58 | 12.21 | 12.94 | 12.44 | 12.61 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.2 | 3.56 | 12.16 | 12.89 | 12.39 | 12.55 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.57 | 12.18 | 12.91 | 12.41 | 12.58 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.0 | 3.57 | 12.19 | 12.92 | 12.42 | 12.59 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP2 [Btuh/Btuh] | EER2 [Btu/W-h] | SEER2 User [Btu/W-h] | SEER2 Standard [Btu/W-h] | IEER2 [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 1.1 | 3.44 | 11.75 | 12.44 | 12.30 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.7 | 3.46 | 11.82 | 12.51 | 12.37 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.9 | 3.49 | 11.92 | 12.62 | 12.48 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 1.1 | 3.44 | 11.75 | 12.44 | 12.30 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.7 | 3.46 | 11.82 | 12.51 | 12.37 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.8 | 3.49 | 11.92 | 12.63 | 12.48 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 1.1 | 3.44 | 11.75 | 12.44 | 12.30 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.7 | 3.45 | 11.79 | 12.48 | 12.34 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.9 | 3.49 | 11.91 | 12.61 | 12.46 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 1.1 | 3.44 | 11.75 | 12.44 | 12.30 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.7 | 3.46 | 11.79 | 12.48 | 12.34 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.8 | 3.46 | 11.81 | 12.50 | 12.36 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.2 | 3.44 | 11.72 | 12.41 | 12.27 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.8 | 3.44 | 11.74 | 12.42 | 12.28 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.0 | 3.45 | 11.77 | 12.46 | 12.32 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.2 | 3.44 | 11.72 | 12.41 | 12.27 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.8 | 3.44 | 11.75 | 12.43 | 12.29 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.0 | 3.44 | 11.75 | 12.44 | 12.30 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
Coil Type | Rated Total Capacity [Btu/h] | Rated Sensible Capacity [Btu/h] | Rated Power[Btu/h] | Rated COP [Btuh/Btuh] | Rated Air Dry-bulb Temperature [F] | Rated Air Wet-bulb Temperature [F] | Rated Water Temperature [F] | Design Day used for Sizing | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF2 [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 24736.04 | 25907.36 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 15496.91 | 15707.94 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 19111.31 | 19701.52 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 24375.16 | 25509.58 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 15423.56 | 15626.73 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 18280.62 | 18784.06 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 25179.69 | 26394.73 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 16230.27 | 16518.77 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 19777.23 | 20435.50 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 24858.95 | 26041.25 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 16134.44 | 16412.73 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 19101.82 | 19689.87 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 27649.60 | 29115.79 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 18892.52 | 19460.68 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 21817.01 | 22685.98 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 27779.28 | 29258.64 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 19084.10 | 19672.25 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 22021.72 | 22911.76 | - |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | 3165.61 | 2.75 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.07 | 44.99 | 16.07 | 0.36 | 1.00 | 12.92 | Ventilation | ||
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 413.72 | 156.05 | 0.38 | 1.00 | 2.34 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 242.60 | 91.51 | 0.38 | 1.00 | 3.13 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 309.54 | 116.76 | 0.38 | 1.00 | 2.72 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 407.03 | 153.53 | 0.38 | 1.00 | 2.36 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 241.25 | 91.00 | 0.38 | 1.00 | 3.14 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 294.16 | 110.95 | 0.38 | 1.00 | 2.79 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 421.94 | 159.15 | 0.38 | 1.00 | 2.31 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 256.19 | 96.63 | 0.38 | 1.00 | 3.03 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 321.88 | 121.41 | 0.38 | 1.00 | 2.66 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 416.00 | 156.91 | 0.38 | 1.00 | 2.33 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 254.42 | 95.96 | 0.38 | 1.00 | 3.04 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 309.37 | 116.69 | 0.38 | 1.00 | 2.72 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 467.67 | 176.40 | 0.38 | 1.00 | 2.21 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 305.49 | 115.23 | 0.38 | 1.00 | 2.73 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 359.65 | 135.66 | 0.38 | 1.00 | 2.51 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 470.08 | 177.31 | 0.38 | 1.00 | 2.20 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 309.04 | 116.57 | 0.38 | 1.00 | 2.72 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 363.44 | 137.09 | 0.38 | 1.00 | 2.49 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General | ||
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.70 | 0.01 | 160.01 | 10.79 | 0.07 | 1.00 | 11.80 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electricity Rate [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | End Use Subcategory | |
BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 38.590051 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:HeatPump:WrappedCondenser | 6.69 | 4259.89 | 1.00 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8427.70 | 8427.70 | 7.02 | 413.715 | 413.715 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 75.00 | 75.00 | 0.00758 | 96.91 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4942.02 | 4942.02 | 4.12 | 242.605 | 242.605 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 75.00 | 75.00 | 0.00780 | 92.62 | 0.00686 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6305.64 | 6305.64 | 5.25 | 309.543 | 309.543 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 75.00 | 75.00 | 0.00754 | 100.58 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8291.54 | 8291.54 | 6.91 | 407.032 | 407.032 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 75.00 | 75.00 | 0.00760 | 96.52 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4914.34 | 4914.34 | 4.09 | 241.246 | 241.246 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 75.00 | 75.00 | 0.00780 | 92.62 | 0.00686 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5992.25 | 5992.25 | 4.99 | 294.158 | 294.158 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 75.00 | 75.00 | 0.00755 | 100.11 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8595.24 | 8595.24 | 7.16 | 421.941 | 421.941 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 75.00 | 75.00 | 0.00761 | 96.52 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5218.78 | 5218.78 | 4.35 | 256.193 | 256.193 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00783 | 91.45 | 0.00686 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6556.99 | 6556.99 | 5.46 | 321.883 | 321.883 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 75.00 | 75.00 | 0.00756 | 100.58 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8474.23 | 8474.23 | 7.06 | 416.001 | 416.001 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 75.00 | 75.00 | 0.00764 | 96.13 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5182.62 | 5182.62 | 4.32 | 254.418 | 254.418 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00783 | 91.45 | 0.00686 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6302.15 | 6302.15 | 5.25 | 309.374 | 309.374 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 75.00 | 75.00 | 0.00772 | 94.96 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7403.61 | 7403.61 | 6.17 | 363.444 | 363.444 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 75.00 | 75.00 | 0.00768 | 94.38 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7326.39 | 7326.39 | 6.10 | 359.653 | 359.653 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 75.00 | 75.00 | 0.00767 | 95.35 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9526.88 | 9526.88 | 7.94 | 467.675 | 467.675 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 75.00 | 75.00 | 0.00761 | 96.13 | 0.00687 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 6295.35 | 6295.35 | 5.24 | 309.041 | 309.041 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 75.00 | 75.00 | 0.00776 | 92.04 | 0.00686 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6223.07 | 6223.07 | 5.18 | 305.493 | 305.493 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00777 | 91.45 | 0.00686 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9575.81 | 9575.81 | 7.98 | 470.077 | 470.077 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 75.00 | 75.00 | 0.00761 | 96.13 | 0.00687 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 6531.06 | 6531.06 | 5.44 | 137.076 | 137.076 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00645 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4985.13 | 4985.13 | 4.15 | 104.631 | 104.631 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00622 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6531.67 | 6531.67 | 5.44 | 137.089 | 137.089 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00645 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6535.01 | 6535.01 | 5.44 | 137.159 | 137.159 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00645 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4986.42 | 4986.42 | 4.15 | 104.658 | 104.658 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00622 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6530.22 | 6530.22 | 5.44 | 137.058 | 137.058 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00645 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5775.66 | 5775.66 | 4.81 | 121.224 | 121.224 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00658 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4222.93 | 4222.93 | 3.52 | 88.635 | 88.635 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00633 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5777.73 | 5777.73 | 4.81 | 121.268 | 121.268 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00658 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5778.63 | 5778.63 | 4.81 | 121.286 | 121.286 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00658 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4223.37 | 4223.37 | 3.52 | 88.644 | 88.644 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 72.00 | 0.00633 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5775.61 | 5775.61 | 4.81 | 121.223 | 121.223 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00658 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7385.33 | 7385.33 | 6.15 | 155.005 | 155.005 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00657 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7386.99 | 7386.99 | 6.15 | 155.040 | 155.040 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00657 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 7384.57 | 7384.57 | 6.15 | 154.989 | 154.989 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00657 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 5826.32 | 5826.32 | 4.85 | 122.285 | 122.285 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00638 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5826.12 | 5826.12 | 4.85 | 122.281 | 122.281 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00638 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 7386.62 | 7386.62 | 6.15 | 155.032 | 155.032 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00657 | 22.64 | 0.00281 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | Adjusted cooling [ft3/min] | Adjusted heating [ft3/min] | Adjusted main [ft3/min] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 413.72 | 413.72 | 137.08 | 137.08 | 413.7154 | 413.7154 | 413.7154 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 242.60 | 242.60 | 104.63 | 104.63 | 242.6050 | 242.6050 | 242.6050 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 309.54 | 309.54 | 137.09 | 137.09 | 309.5429 | 309.5429 | 309.5429 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 407.03 | 407.03 | 137.16 | 137.16 | 407.0318 | 407.0318 | 407.0318 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 241.25 | 241.25 | 104.66 | 104.66 | 241.2465 | 241.2465 | 241.2465 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 294.16 | 294.16 | 137.06 | 137.06 | 294.1582 | 294.1582 | 294.1582 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 421.94 | 421.94 | 121.22 | 121.22 | 421.9414 | 421.9414 | 421.9414 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 256.19 | 256.19 | 88.64 | 88.64 | 256.1926 | 256.1926 | 256.1926 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.88 | 321.88 | 121.27 | 121.27 | 321.8829 | 321.8829 | 321.8829 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 416.00 | 416.00 | 121.29 | 121.29 | 416.0010 | 416.0010 | 416.0010 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 254.42 | 254.42 | 88.64 | 88.64 | 254.4175 | 254.4175 | 254.4175 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 309.37 | 309.37 | 121.22 | 121.22 | 309.3738 | 309.3738 | 309.3738 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 467.67 | 467.67 | 154.99 | 154.99 | 467.6748 | 467.6748 | 467.6748 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 305.49 | 305.49 | 122.28 | 122.28 | 305.4930 | 305.4930 | 305.4930 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 359.65 | 359.65 | 155.04 | 155.04 | 359.6530 | 359.6530 | 359.6530 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 470.08 | 470.08 | 155.03 | 155.03 | 470.0766 | 470.0766 | 470.0766 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 309.04 | 309.04 | 122.29 | 122.29 | 309.0412 | 309.0412 | 309.0412 | 1.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 363.44 | 363.44 | 155.00 | 155.00 | 363.4442 | 363.4442 | 363.4442 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 13859.716 | 10541.289 | 413.715375 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 12384.48 | 12376.07 | 413.715375 | 78.74 | 58.60 | 0.00750498 | 53.60 | 49.11 | 0.00750000 | 96.91 | 0.00686822 | 63.59 | 10.8758 | 75.00 | 0.00758268 | 35.6896 | 8427.70 | 0.00 | 13865.50 | 9859.34 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 24736.035 | 24736.035 | 413.715375 | 0.33935090 | 371.154 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 24736.04 | 21827.53 | 413.715375 | 66.63 | 51.80 | 0.00605006 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 10.8758 | 71.99 | 0.00644565 | 33.6250 | 6531.06 | 0.00 | 25896.15 | 25896.15 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 8357.532 | 6272.450 | 242.604971 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 7673.17 | 7548.20 | 242.604971 | 79.62 | 59.08 | 0.00762445 | 53.60 | 49.11 | 0.00750000 | 92.62 | 0.00686443 | 62.24 | 18.5466 | 75.00 | 0.00773411 | 36.3937 | 4903.22 | 0.00 | 8361.02 | 5877.11 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 15496.910 | 15496.910 | 242.604971 | 0.21260038 | 228.423 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 15496.91 | 13674.76 | 242.604971 | 62.84 | 49.45 | 0.00558418 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 18.5466 | 71.99 | 0.00621621 | 32.4393 | 4985.13 | 0.00 | 15696.11 | 15696.11 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 11112.401 | 8178.960 | 309.542888 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 9748.64 | 9748.64 | 309.542888 | 80.07 | 58.96 | 0.00744500 | 53.60 | 49.01 | 0.00744500 | 100.58 | 0.00687148 | 64.71 | 14.5359 | 75.00 | 0.00754255 | 35.5029 | 6305.64 | 0.00 | 11117.04 | 7679.79 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 19111.305 | 19111.305 | 309.542888 | 0.26218586 | 284.256 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 19111.31 | 16864.17 | 309.542888 | 64.82 | 50.85 | 0.00591702 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 14.5359 | 71.99 | 0.00644574 | 33.6255 | 6531.67 | 0.00 | 19691.15 | 19691.15 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 13640.946 | 10373.397 | 407.031752 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 12217.30 | 12182.44 | 407.031752 | 78.73 | 58.62 | 0.00752095 | 53.60 | 49.11 | 0.00750000 | 96.52 | 0.00686787 | 63.47 | 11.0544 | 75.00 | 0.00758379 | 35.6948 | 8278.91 | 0.00 | 13646.64 | 9702.34 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 24375.157 | 24375.157 | 407.031752 | 0.33440005 | 365.583 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 24375.16 | 21509.09 | 407.031752 | 66.54 | 51.76 | 0.00604411 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 11.0544 | 71.99 | 0.00644626 | 33.6282 | 6535.01 | 0.00 | 25498.44 | 25498.44 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 8316.351 | 6239.945 | 241.246451 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 7635.75 | 7511.26 | 241.246451 | 79.64 | 59.08 | 0.00762464 | 53.60 | 49.11 | 0.00750000 | 92.62 | 0.00686443 | 62.24 | 18.6510 | 75.00 | 0.00775024 | 36.4687 | 4872.64 | 0.00 | 8319.82 | 5846.69 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 15423.559 | 15423.559 | 241.246451 | 0.21159408 | 227.287 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 15423.56 | 13610.03 | 241.246451 | 62.79 | 49.42 | 0.00558084 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 18.6510 | 71.99 | 0.00621649 | 32.4408 | 4986.42 | 0.00 | 15614.91 | 15614.91 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 10577.937 | 7780.713 | 294.158169 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 9307.08 | 9307.08 | 294.158169 | 80.19 | 59.00 | 0.00744233 | 53.60 | 49.01 | 0.00744233 | 100.11 | 0.00687107 | 64.57 | 15.2962 | 75.00 | 0.00754360 | 35.5078 | 5986.57 | 0.00 | 10582.35 | 7307.92 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 18280.617 | 18280.617 | 294.158169 | 0.25078973 | 271.419 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 18280.62 | 16131.15 | 294.158169 | 64.44 | 50.65 | 0.00588917 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 15.2962 | 71.99 | 0.00644552 | 33.6243 | 6530.22 | 0.00 | 18773.80 | 18773.80 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 14130.193 | 10748.499 | 421.941443 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 12654.88 | 12594.11 | 421.941443 | 78.65 | 58.61 | 0.00753524 | 53.60 | 49.11 | 0.00750000 | 96.52 | 0.00686787 | 63.47 | 10.6638 | 75.00 | 0.00759670 | 35.7549 | 8581.41 | 0.00 | 14136.09 | 10053.12 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 25179.691 | 25179.691 | 421.941443 | 0.34543735 | 377.958 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 25179.69 | 22219.02 | 421.941443 | 66.73 | 52.06 | 0.00617514 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 10.6638 | 71.99 | 0.00657701 | 34.3017 | 5775.66 | 0.00 | 26385.34 | 26385.34 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 8705.615 | 6576.539 | 256.192568 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8039.50 | 7867.60 | 256.192568 | 79.24 | 59.00 | 0.00766241 | 53.60 | 49.11 | 0.00750000 | 91.45 | 0.00686340 | 61.87 | 17.5630 | 75.00 | 0.00776861 | 36.5541 | 5155.94 | 0.00 | 8709.25 | 6157.44 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 16230.275 | 16230.275 | 256.192568 | 0.22266132 | 239.746 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 16230.27 | 14321.89 | 256.192568 | 63.33 | 49.88 | 0.00571345 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 17.5630 | 72.00 | 0.00633236 | 33.0380 | 4222.93 | 0.00 | 16507.76 | 16507.76 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 11495.103 | 8477.099 | 321.882935 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 10082.97 | 10082.97 | 321.882935 | 79.93 | 58.94 | 0.00746319 | 53.60 | 49.05 | 0.00746319 | 100.58 | 0.00687148 | 64.71 | 13.9787 | 75.00 | 0.00755935 | 35.5811 | 6556.99 | 0.00 | 11499.90 | 7959.25 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 19777.227 | 19777.227 | 321.882935 | 0.27132156 | 294.510 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 19777.23 | 17451.79 | 321.882935 | 65.10 | 51.20 | 0.00605050 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 13.9787 | 71.99 | 0.00657736 | 34.3035 | 5777.73 | 0.00 | 20426.49 | 20426.49 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 13940.033 | 10601.280 | 416.001047 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 12513.70 | 12421.95 | 416.001047 | 78.64 | 58.64 | 0.00755393 | 53.60 | 49.11 | 0.00750000 | 96.13 | 0.00686752 | 63.35 | 10.8161 | 75.00 | 0.00761621 | 35.8456 | 8461.36 | 0.00 | 13945.85 | 9915.47 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 24858.951 | 24858.951 | 416.001047 | 0.34103716 | 373.008 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 24858.95 | 21936.00 | 416.001047 | 66.66 | 52.02 | 0.00616983 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 10.8161 | 71.99 | 0.00657750 | 34.3042 | 5778.63 | 0.00 | 26031.89 | 26031.89 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 8652.107 | 6534.152 | 254.417516 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7990.55 | 7819.31 | 254.417516 | 79.26 | 59.01 | 0.00766289 | 53.60 | 49.11 | 0.00750000 | 91.45 | 0.00686340 | 61.87 | 17.6855 | 75.00 | 0.00780538 | 36.7251 | 5157.47 | 0.00 | 8655.72 | 6117.80 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 16134.435 | 16134.435 | 254.417516 | 0.22134651 | 238.263 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 16134.44 | 14237.32 | 254.417516 | 63.27 | 49.85 | 0.00570922 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 17.6855 | 72.00 | 0.00633247 | 33.0385 | 4223.37 | 0.00 | 16401.74 | 16401.74 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 10603.575 | 7984.130 | 309.373796 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 9598.39 | 9479.85 | 309.373796 | 79.26 | 58.91 | 0.00759299 | 53.60 | 49.11 | 0.00750000 | 94.96 | 0.00686649 | 62.98 | 14.5439 | 75.00 | 0.00756165 | 35.5918 | 6244.20 | 0.00 | 10608.00 | 7478.05 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 19101.820 | 19101.820 | 309.373796 | 0.26205573 | 284.076 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 19101.82 | 16855.80 | 309.373796 | 64.82 | 51.05 | 0.00602890 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 14.5439 | 71.99 | 0.00657701 | 34.3017 | 5775.61 | 0.00 | 19680.89 | 19680.89 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 15489.632 | 11848.451 | 467.674792 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 13895.10 | 13816.97 | 467.674792 | 78.38 | 58.53 | 0.00754097 | 53.60 | 49.11 | 0.00750000 | 96.13 | 0.00686752 | 63.35 | 9.6210 | 75.00 | 0.00759296 | 35.7374 | 9520.66 | 0.00 | 15496.09 | 11077.80 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 27649.598 | 27649.598 | 467.674792 | 0.37932173 | 416.075 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 27649.60 | 24398.51 | 467.674792 | 67.24 | 52.31 | 0.00620565 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 9.6210 | 71.99 | 0.00656729 | 34.2531 | 7384.57 | 0.00 | 29106.05 | 29106.05 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 10161.857 | 7760.135 | 305.492968 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 9370.03 | 9202.21 | 305.492968 | 78.77 | 58.80 | 0.00763371 | 53.60 | 49.11 | 0.00750000 | 91.45 | 0.00686340 | 61.87 | 14.7286 | 75.00 | 0.00774477 | 36.4434 | 6183.83 | 0.00 | 10166.10 | 7255.62 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 18892.518 | 18892.518 | 305.492968 | 0.25918433 | 280.894 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 18892.52 | 16671.11 | 305.492968 | 64.72 | 50.70 | 0.00585332 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 14.7286 | 71.99 | 0.00637927 | 33.2818 | 5826.12 | 0.00 | 19449.64 | 19449.64 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 12141.650 | 9207.354 | 359.652989 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 10954.55 | 10856.36 | 359.652989 | 78.90 | 58.74 | 0.00756656 | 53.60 | 49.11 | 0.00750000 | 95.35 | 0.00686684 | 63.10 | 12.5107 | 75.00 | 0.00753888 | 35.4858 | 7259.88 | 0.00 | 12146.72 | 8617.48 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 21817.012 | 21817.012 | 359.652989 | 0.29930514 | 326.014 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 21817.01 | 19251.73 | 359.652989 | 65.82 | 51.57 | 0.00609731 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 12.5107 | 71.99 | 0.00656761 | 34.2548 | 7386.99 | 0.00 | 22676.72 | 22676.72 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 15563.051 | 11906.426 | 470.076574 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 13960.64 | 13882.12 | 470.076574 | 78.37 | 58.53 | 0.00754097 | 53.60 | 49.11 | 0.00750000 | 96.13 | 0.00686752 | 63.35 | 9.5718 | 75.00 | 0.00761226 | 35.8272 | 9575.81 | 0.00 | 15569.55 | 11131.97 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 27779.281 | 27779.281 | 470.076574 | 0.38110084 | 418.076 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 27779.28 | 24512.95 | 470.076574 | 67.27 | 52.33 | 0.00620774 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 9.5718 | 71.99 | 0.00656756 | 34.2545 | 7386.62 | 0.00 | 29248.88 | 29248.88 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 10325.582 | 7871.699 | 309.041184 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 9491.71 | 9328.21 | 309.041184 | 78.83 | 58.82 | 0.00762872 | 53.60 | 49.11 | 0.00750000 | 92.04 | 0.00686391 | 62.06 | 14.5595 | 75.00 | 0.00774243 | 36.4325 | 6270.90 | 0.00 | 10329.89 | 7362.45 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 19084.100 | 19084.100 | 309.041184 | 0.26181263 | 283.854 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 19084.10 | 16840.16 | 309.041184 | 64.81 | 50.75 | 0.00585939 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 14.5595 | 71.99 | 0.00637930 | 33.2820 | 5826.32 | 0.00 | 19661.18 | 19661.18 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 12170.284 | 9257.913 | 363.444233 | -999. | -999.00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 11037.63 | 10914.51 | 363.444233 | 78.75 | 58.72 | 0.00758264 | 53.60 | 49.11 | 0.00750000 | 94.38 | 0.00686598 | 62.80 | 12.3802 | 75.00 | 0.00765252 | 36.0144 | 7380.10 | 0.00 | 12175.36 | 8658.96 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 22021.718 | 22021.718 | 363.444233 | 0.30211348 | 329.175 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22021.72 | 19432.37 | 363.444233 | 65.88 | 51.60 | 0.00610202 | 122.00 | 72.00 | 0.00800000 | 22.64 | 0.00280840 | 22.64 | 12.3802 | 71.99 | 0.00656739 | 34.2536 | 7385.33 | 0.00 | 22902.48 | 22902.48 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3446.752 | 3381.263 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3456.778 | 3391.099 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3446.691 | 3381.204 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3446.666 | 3381.179 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3456.777 | 3391.098 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3446.763 | 3381.274 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3499.227 | 3432.742 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3514.349 | 3447.577 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3499.426 | 3432.937 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3499.369 | 3432.881 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3514.352 | 3447.579 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3499.439 | 3432.950 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3446.395 | 3380.914 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3456.630 | 3390.954 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3446.536 | 3381.052 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3446.475 | 3380.992 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3456.624 | 3390.948 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | 3446.537 | 3381.053 | 400.423678 | -999. | -999.00 | unknown | unknown | unknown | unknown | 3165.61 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999.0 | -999. | -999.0 | -999.000 | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [Btu/lbm-R] | Dry Air Heat Capacity [Btu/lbm-R] | Standard Air Density Adjusted for Elevation [lb/ft3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [ft3/min] | Supply Fan Maximum Air Mass Flow Rate [lb/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [Btu/lbm-R] | Plant Fluid Density [lb/ft3] | Plant Maximum Fluid Mass Flow Rate [lb/s] | Plant Design Fluid Return Temperature [F] | Plant Design Fluid Supply Temperature [F] | Plant Design Fluid Temperature Difference [deltaF] | Plant Design Capacity [Btu/h] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] | Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] | Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] | Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [F] | System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | Coil Air Mass Flow Rate at Rating Conditions [lb/s] | Coil Entering Air Drybulb at Rating Conditions [F] | Coil Entering Air Wetbulb at Rating Conditions [F] | Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] | Coil Leaving Air Drybulb at Rating Conditions [F] | Coil Leaving Air Wetbulb at Rating Conditions [F] | Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 13859.716 | 10541.289 | 413.715375 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 413.715375 | 0.44958519 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | Sensible | 12384.48 | 12376.07 | 0.8936 | 0.44958519 | 413.715375 | 78.74 | 58.60 | 0.00750498 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 532.444 | 11852.04 | 96.91 | 0.00686822 | 63.59 | 44.99498340 | 10.8758 | 75.00 | 0.00758268 | 75.00 | 0.00758268 | 35.6896 | 8427.70 | 0.00 | 13865.50 | 9859.34 | 0.43182997 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.00 | 53.95 | 0.00883444 | 8.3 | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 24736.035 | 24736.035 | 413.715375 | 0.33935090 | 371.154 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 413.715375 | 0.44958519 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 6.4498 | 6.579604 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 24736.04 | 21827.53 | 1.0000 | 0.44958519 | 413.715375 | 66.63 | 51.80 | 0.00605006 | 8.3 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.35308279 | 140.00 | 120.20 | 19.80 | 0.000 | 24736.04 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 10.8758 | 71.99 | 0.00644565 | 71.99 | 0.00644565 | 33.6250 | 6531.06 | 0.00 | 25896.15 | 25896.15 | 0.44958519 | 61.88 | 52.15 | 0.00605006 | 7.6 | 127.81 | 74.43 | 0.00605006 | 16.5 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 8357.532 | 6272.450 | 242.604971 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 242.604971 | 0.26363922 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 7673.17 | 7548.20 | 0.9181 | 0.26363922 | 242.604971 | 79.62 | 59.08 | 0.00762445 | 11.0 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 312.228 | 7360.95 | 92.62 | 0.00686443 | 62.24 | 44.99498340 | 18.5466 | 75.00 | 0.00779750 | 75.00 | 0.00773411 | 36.3937 | 4903.22 | 0.00 | 8361.02 | 5877.11 | 0.25322747 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.56 | 53.53 | 0.00869971 | 8.1 | |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 15496.910 | 15496.910 | 242.604971 | 0.21260038 | 228.423 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 242.604971 | 0.26363922 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 4.0407 | 4.122065 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 15496.91 | 13674.76 | 1.0000 | 0.26363922 | 242.604971 | 62.84 | 49.45 | 0.00558418 | 7.5 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.22120329 | 140.00 | 120.20 | 19.80 | 0.000 | 15496.91 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 18.5466 | 71.99 | 0.00621621 | 71.99 | 0.00621621 | 32.4393 | 4985.13 | 0.00 | 15696.11 | 15696.11 | 0.26363922 | 61.88 | 51.27 | 0.00558418 | 7.4 | 130.08 | 74.48 | 0.00558418 | 16.5 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 11112.401 | 8178.960 | 309.542888 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 309.542888 | 0.33638077 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 9748.64 | 9748.64 | 0.8773 | 0.33638077 | 309.542888 | 80.07 | 58.96 | 0.00744500 | 10.9 | 53.60 | 49.01 | 0.00744500 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 398.376 | 9350.26 | 100.58 | 0.00687148 | 64.71 | 44.99498340 | 14.5359 | 75.00 | 0.00754255 | 75.00 | 0.00754255 | 35.5029 | 6305.64 | 0.00 | 11117.04 | 7679.79 | 0.32309627 | 80.00 | 67.00 | 0.01118466 | 13.2 | 52.91 | 52.88 | 0.00848958 | 7.9 | |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 19111.305 | 19111.305 | 309.542888 | 0.26218586 | 284.256 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 309.542888 | 0.33638077 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 4.9832 | 5.083467 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 19111.31 | 16864.17 | 1.0000 | 0.33638077 | 309.542888 | 64.82 | 50.85 | 0.00591702 | 8.0 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.27279526 | 140.00 | 120.20 | 19.80 | 0.000 | 19111.31 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 14.5359 | 71.99 | 0.00644574 | 71.99 | 0.00644574 | 33.6255 | 6531.67 | 0.00 | 19691.15 | 19691.15 | 0.33638077 | 61.88 | 51.90 | 0.00591702 | 7.6 | 128.90 | 74.56 | 0.00591702 | 16.6 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 13640.946 | 10373.397 | 407.031752 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 407.031752 | 0.44232208 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | Sensible | 12217.30 | 12182.44 | 0.8956 | 0.44232208 | 407.031752 | 78.73 | 58.62 | 0.00752095 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 523.842 | 11693.46 | 96.52 | 0.00686787 | 63.47 | 44.99498340 | 11.0544 | 75.00 | 0.00760212 | 75.00 | 0.00758379 | 35.6948 | 8278.91 | 0.00 | 13646.64 | 9702.34 | 0.42485370 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.99 | 53.95 | 0.00883274 | 8.3 | |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 24375.157 | 24375.157 | 407.031752 | 0.33440005 | 365.583 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 407.031752 | 0.44232208 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 6.3557 | 6.483613 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 24375.16 | 21509.09 | 1.0000 | 0.44232208 | 407.031752 | 66.54 | 51.76 | 0.00604411 | 8.3 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.34793162 | 140.00 | 120.20 | 19.80 | 0.000 | 24375.16 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 11.0544 | 71.99 | 0.00644626 | 71.99 | 0.00644626 | 33.6282 | 6535.01 | 0.00 | 25498.44 | 25498.44 | 0.44232208 | 61.88 | 52.14 | 0.00604411 | 7.6 | 127.86 | 74.43 | 0.00604411 | 16.5 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 8316.351 | 6239.945 | 241.246451 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 241.246451 | 0.26216292 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 7635.75 | 7511.26 | 0.9182 | 0.26216292 | 241.246451 | 79.64 | 59.08 | 0.00762464 | 11.0 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 310.480 | 7325.27 | 92.62 | 0.00686443 | 62.24 | 44.99498340 | 18.6510 | 75.00 | 0.00779894 | 75.00 | 0.00775024 | 36.4687 | 4872.64 | 0.00 | 8319.82 | 5846.69 | 0.25180947 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.55 | 53.52 | 0.00869656 | 8.1 | |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 15423.559 | 15423.559 | 241.246451 | 0.21159408 | 227.287 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 241.246451 | 0.26216292 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 4.0216 | 4.102554 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 15423.56 | 13610.03 | 1.0000 | 0.26216292 | 241.246451 | 62.79 | 49.42 | 0.00558084 | 7.5 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.22015627 | 140.00 | 120.20 | 19.80 | 0.000 | 15423.56 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 18.6510 | 71.99 | 0.00621649 | 71.99 | 0.00621649 | 32.4408 | 4986.42 | 0.00 | 15614.91 | 15614.91 | 0.26216292 | 61.88 | 51.26 | 0.00558084 | 7.4 | 130.11 | 74.49 | 0.00558084 | 16.6 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10577.937 | 7780.713 | 294.158169 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 294.158169 | 0.31966217 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 9307.08 | 9307.08 | 0.8799 | 0.31966217 | 294.158169 | 80.19 | 59.00 | 0.00744233 | 11.0 | 53.60 | 49.01 | 0.00744233 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 378.576 | 8928.51 | 100.11 | 0.00687107 | 64.57 | 44.99498340 | 15.2962 | 75.00 | 0.00754549 | 75.00 | 0.00754360 | 35.5078 | 5986.57 | 0.00 | 10582.35 | 7307.92 | 0.30703793 | 80.00 | 67.00 | 0.01118466 | 13.2 | 52.88 | 52.85 | 0.00848296 | 7.9 | |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 18280.617 | 18280.617 | 294.158169 | 0.25078973 | 271.419 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 294.158169 | 0.31966217 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 4.7666 | 4.862510 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 18280.62 | 16131.15 | 1.0000 | 0.31966217 | 294.158169 | 64.44 | 50.65 | 0.00588917 | 7.9 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.26093799 | 140.00 | 120.20 | 19.80 | 0.000 | 18280.62 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 15.2962 | 71.99 | 0.00644552 | 71.99 | 0.00644552 | 33.6243 | 6530.22 | 0.00 | 18773.80 | 18773.80 | 0.31966217 | 61.88 | 51.85 | 0.00588917 | 7.5 | 129.12 | 74.59 | 0.00588917 | 16.6 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 14130.193 | 10748.499 | 421.941443 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 421.941443 | 0.45852447 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | Sensible | 12654.88 | 12594.11 | 0.8956 | 0.45852447 | 421.941443 | 78.65 | 58.61 | 0.00753524 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 543.031 | 12111.85 | 96.52 | 0.00686787 | 63.47 | 44.99498340 | 10.6638 | 75.00 | 0.00761490 | 75.00 | 0.00759670 | 35.7549 | 8581.41 | 0.00 | 14136.09 | 10053.12 | 0.44041622 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.00 | 53.96 | 0.00883608 | 8.3 | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 25179.691 | 25179.691 | 421.941443 | 0.34543735 | 377.958 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 421.941443 | 0.45852447 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 6.5655 | 6.697613 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 25179.69 | 22219.02 | 1.0000 | 0.45852447 | 421.941443 | 66.73 | 52.06 | 0.00617514 | 8.4 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.35941554 | 140.00 | 120.20 | 19.80 | 0.000 | 25179.69 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 10.6638 | 71.99 | 0.00657701 | 71.99 | 0.00657701 | 34.3017 | 5775.66 | 0.00 | 26385.34 | 26385.34 | 0.45852447 | 61.88 | 52.38 | 0.00617514 | 7.7 | 127.73 | 74.55 | 0.00617514 | 16.6 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 8705.615 | 6576.539 | 256.192568 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 256.192568 | 0.27840489 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8039.50 | 7867.60 | 0.9235 | 0.27840489 | 256.192568 | 79.24 | 59.00 | 0.00766241 | 11.0 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 329.715 | 7709.78 | 91.45 | 0.00686340 | 61.87 | 44.99498340 | 17.5630 | 75.00 | 0.00783264 | 75.00 | 0.00776861 | 36.5541 | 5155.94 | 0.00 | 8709.25 | 6157.44 | 0.26741000 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.77 | 53.74 | 0.00876718 | 8.2 | |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 16230.275 | 16230.275 | 256.192568 | 0.22266132 | 239.746 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 256.192568 | 0.27840489 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 4.2320 | 4.317134 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 16230.27 | 14321.89 | 1.0000 | 0.27840489 | 256.192568 | 63.33 | 49.88 | 0.00571345 | 7.6 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.23167135 | 140.00 | 120.20 | 19.80 | 0.000 | 16230.27 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 17.5630 | 72.00 | 0.00633236 | 72.00 | 0.00633236 | 33.0380 | 4222.93 | 0.00 | 16507.76 | 16507.76 | 0.27840489 | 61.88 | 51.52 | 0.00571345 | 7.4 | 129.79 | 74.56 | 0.00571345 | 16.6 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 11495.103 | 8477.099 | 321.882935 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 321.882935 | 0.34979072 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 10082.97 | 10082.97 | 0.8772 | 0.34979072 | 321.882935 | 79.93 | 58.94 | 0.00746319 | 10.9 | 53.60 | 49.05 | 0.00746319 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 414.257 | 9668.71 | 100.58 | 0.00687148 | 64.71 | 44.99498340 | 13.9787 | 75.00 | 0.00755935 | 75.00 | 0.00755935 | 35.5811 | 6556.99 | 0.00 | 11499.90 | 7959.25 | 0.33597663 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.01 | 52.96 | 0.00851493 | 7.9 | |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 19777.227 | 19777.227 | 321.882935 | 0.27132156 | 294.510 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 321.882935 | 0.34979072 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 5.1568 | 5.260597 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 19777.23 | 17451.79 | 1.0000 | 0.34979072 | 321.882935 | 65.10 | 51.20 | 0.00605050 | 8.1 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.28230064 | 140.00 | 120.20 | 19.80 | 0.000 | 19777.23 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 13.9787 | 71.99 | 0.00657736 | 71.99 | 0.00657736 | 34.3035 | 5777.73 | 0.00 | 20426.49 | 20426.49 | 0.34979072 | 61.88 | 52.15 | 0.00605050 | 7.6 | 128.72 | 74.67 | 0.00605050 | 16.7 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 13940.033 | 10601.280 | 416.001047 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 416.001047 | 0.45206903 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | Sensible | 12513.70 | 12421.95 | 0.8977 | 0.45206903 | 416.001047 | 78.64 | 58.64 | 0.00755393 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 535.386 | 11978.32 | 96.13 | 0.00686752 | 63.35 | 44.99498340 | 10.8161 | 75.00 | 0.00763718 | 75.00 | 0.00761621 | 35.8456 | 8461.36 | 0.00 | 13945.85 | 9915.47 | 0.43421572 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.99 | 53.95 | 0.00883323 | 8.3 | |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 24858.951 | 24858.951 | 416.001047 | 0.34103716 | 373.008 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 416.001047 | 0.45206903 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 6.4818 | 6.612299 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 24858.95 | 21936.00 | 1.0000 | 0.45206903 | 416.001047 | 66.66 | 52.02 | 0.00616983 | 8.4 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.35483729 | 140.00 | 120.20 | 19.80 | 0.000 | 24858.95 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 10.8161 | 71.99 | 0.00657750 | 71.99 | 0.00657750 | 34.3042 | 5778.63 | 0.00 | 26031.89 | 26031.89 | 0.45206903 | 61.88 | 52.37 | 0.00616983 | 7.7 | 127.78 | 74.56 | 0.00616983 | 16.6 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 8652.107 | 6534.152 | 254.417516 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 254.417516 | 0.27647594 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7990.55 | 7819.31 | 0.9235 | 0.27647594 | 254.417516 | 79.26 | 59.01 | 0.00766289 | 11.0 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 327.431 | 7663.12 | 91.45 | 0.00686340 | 61.87 | 44.99498340 | 17.6855 | 75.00 | 0.00783466 | 75.00 | 0.00780538 | 36.7251 | 5157.47 | 0.00 | 8655.72 | 6117.80 | 0.26555723 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.76 | 53.73 | 0.00876356 | 8.2 | |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 16134.435 | 16134.435 | 254.417516 | 0.22134651 | 238.263 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 254.417516 | 0.27647594 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 4.2070 | 4.291642 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 16134.44 | 14237.32 | 1.0000 | 0.27647594 | 254.417516 | 63.27 | 49.85 | 0.00570922 | 7.6 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.23030334 | 140.00 | 120.20 | 19.80 | 0.000 | 16134.44 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 17.6855 | 72.00 | 0.00633247 | 72.00 | 0.00633247 | 33.0385 | 4223.37 | 0.00 | 16401.74 | 16401.74 | 0.27647594 | 61.88 | 51.51 | 0.00570922 | 7.4 | 129.83 | 74.56 | 0.00570922 | 16.6 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10603.575 | 7984.130 | 309.373796 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 309.373796 | 0.33619702 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | Sensible | 9598.39 | 9479.85 | 0.9052 | 0.33619702 | 309.373796 | 79.26 | 58.91 | 0.00759299 | 10.9 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 398.158 | 9200.23 | 94.96 | 0.00686649 | 62.98 | 44.99498340 | 14.5439 | 75.00 | 0.00771663 | 75.00 | 0.00756165 | 35.5918 | 6244.20 | 0.00 | 10608.00 | 7478.05 | 0.32291978 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.62 | 53.61 | 0.00872919 | 8.1 | |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 19101.820 | 19101.820 | 309.373796 | 0.26205573 | 284.076 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 309.373796 | 0.33619702 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 4.9807 | 5.080944 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 19101.82 | 16855.80 | 1.0000 | 0.33619702 | 309.373796 | 64.82 | 51.05 | 0.00602890 | 8.0 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.27265987 | 140.00 | 120.20 | 19.80 | 0.000 | 19101.82 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 14.5439 | 71.99 | 0.00657701 | 71.99 | 0.00657701 | 34.3017 | 5775.61 | 0.00 | 19680.89 | 19680.89 | 0.33619702 | 61.88 | 52.11 | 0.00602890 | 7.6 | 128.89 | 74.69 | 0.00602890 | 16.7 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 15489.632 | 11848.451 | 467.674792 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 467.674792 | 0.50822297 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | Sensible | 13895.10 | 13816.97 | 0.8971 | 0.50822297 | 467.674792 | 78.38 | 58.53 | 0.00754097 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 601.889 | 13293.21 | 96.13 | 0.00686752 | 63.35 | 44.99498340 | 9.6210 | 75.00 | 0.00761266 | 75.00 | 0.00759296 | 35.7374 | 9520.66 | 0.00 | 15496.09 | 11077.80 | 0.48815201 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.16 | 54.12 | 0.00889172 | 8.3 | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 27649.598 | 27649.598 | 467.674792 | 0.37932173 | 416.075 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 467.674792 | 0.50822297 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 7.2095 | 7.354590 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 27649.60 | 24398.51 | 1.0000 | 0.50822297 | 467.674792 | 67.24 | 52.31 | 0.00620565 | 8.5 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.39467106 | 140.00 | 120.20 | 19.80 | 0.000 | 27649.60 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 9.6210 | 71.99 | 0.00656729 | 71.99 | 0.00656729 | 34.2531 | 7384.57 | 0.00 | 29106.05 | 29106.05 | 0.50822297 | 61.88 | 52.44 | 0.00620565 | 7.7 | 127.41 | 74.50 | 0.00620565 | 16.6 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10161.857 | 7760.135 | 305.492968 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 305.492968 | 0.33197972 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 9370.03 | 9202.21 | 0.9221 | 0.33197972 | 305.492968 | 78.77 | 58.80 | 0.00763371 | 10.9 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 393.164 | 8976.87 | 91.45 | 0.00686340 | 61.87 | 44.99498340 | 14.7286 | 75.00 | 0.00776676 | 75.00 | 0.00774477 | 36.4434 | 6183.83 | 0.00 | 10166.10 | 7255.62 | 0.31886903 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.09 | 54.06 | 0.00887235 | 8.3 | |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 18892.518 | 18892.518 | 305.492968 | 0.25918433 | 280.894 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 305.492968 | 0.33197972 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 4.9261 | 5.025271 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 18892.52 | 16671.11 | 1.0000 | 0.33197972 | 305.492968 | 64.72 | 50.70 | 0.00585332 | 7.9 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.26967227 | 140.00 | 120.20 | 19.80 | 0.000 | 18892.52 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 14.7286 | 71.99 | 0.00637927 | 71.99 | 0.00637927 | 33.2818 | 5826.12 | 0.00 | 19449.64 | 19449.64 | 0.33197972 | 61.88 | 51.78 | 0.00585332 | 7.5 | 128.96 | 74.50 | 0.00585332 | 16.6 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 12141.650 | 9207.354 | 359.652989 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 359.652989 | 0.39083550 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | Sensible | 10954.55 | 10856.36 | 0.9022 | 0.39083550 | 359.652989 | 78.90 | 58.74 | 0.00756656 | 10.9 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 462.867 | 10491.69 | 95.35 | 0.00686684 | 63.10 | 44.99498340 | 12.5107 | 75.00 | 0.00766662 | 75.00 | 0.00753888 | 35.4858 | 7259.88 | 0.00 | 12146.72 | 8617.48 | 0.37540045 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.86 | 53.84 | 0.00880301 | 8.2 | |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 21817.012 | 21817.012 | 359.652989 | 0.29930514 | 326.014 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 359.652989 | 0.39083550 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 5.6887 | 5.803165 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 21817.01 | 19251.73 | 1.0000 | 0.39083550 | 359.652989 | 65.82 | 51.57 | 0.00609731 | 8.2 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.31141658 | 140.00 | 120.20 | 19.80 | 0.000 | 21817.01 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 12.5107 | 71.99 | 0.00656761 | 71.99 | 0.00656761 | 34.2548 | 7386.99 | 0.00 | 22676.72 | 22676.72 | 0.39083550 | 61.88 | 52.24 | 0.00609731 | 7.7 | 128.29 | 74.61 | 0.00609731 | 16.6 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 15563.051 | 11906.426 | 470.076574 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 470.076574 | 0.51083299 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | Sensible | 13960.64 | 13882.12 | 0.8970 | 0.51083299 | 470.076574 | 78.37 | 58.53 | 0.00754097 | 10.8 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 604.980 | 13355.66 | 96.13 | 0.00686752 | 63.35 | 44.99498340 | 9.5718 | 75.00 | 0.00761226 | 75.00 | 0.00761226 | 35.8272 | 9575.81 | 0.00 | 15569.55 | 11131.97 | 0.49065895 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.17 | 54.13 | 0.00889348 | 8.3 | |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 27779.281 | 27779.281 | 470.076574 | 0.38110084 | 418.076 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 470.076574 | 0.51083299 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 7.2433 | 7.389085 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 27779.28 | 24512.95 | 1.0000 | 0.51083299 | 470.076574 | 67.27 | 52.33 | 0.00620774 | 8.5 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.39652216 | 140.00 | 120.20 | 19.80 | 0.000 | 27779.28 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 9.5718 | 71.99 | 0.00656756 | 71.99 | 0.00656756 | 34.2545 | 7386.62 | 0.00 | 29248.88 | 29248.88 | 0.51083299 | 61.88 | 52.44 | 0.00620774 | 7.7 | 127.40 | 74.50 | 0.00620774 | 16.6 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10325.582 | 7871.699 | 309.041184 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 309.041184 | 0.33583557 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 9491.71 | 9328.21 | 0.9192 | 0.33583557 | 309.041184 | 78.83 | 58.82 | 0.00762872 | 10.9 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 397.730 | 9093.98 | 92.04 | 0.00686391 | 62.06 | 44.99498340 | 14.5595 | 75.00 | 0.00775905 | 75.00 | 0.00774243 | 36.4325 | 6270.90 | 0.00 | 10329.89 | 7362.45 | 0.32257260 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.01 | 53.99 | 0.00885417 | 8.3 | |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 19084.100 | 19084.100 | 309.041184 | 0.26181263 | 283.854 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 309.041184 | 0.33583557 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 4.9761 | 5.076231 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 19084.10 | 16840.16 | 1.0000 | 0.33583557 | 309.041184 | 64.81 | 50.75 | 0.00585939 | 7.9 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.27240692 | 140.00 | 120.20 | 19.80 | 0.000 | 19084.10 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 14.5595 | 71.99 | 0.00637930 | 71.99 | 0.00637930 | 33.2820 | 5826.32 | 0.00 | 19661.18 | 19661.18 | 0.33583557 | 61.88 | 51.79 | 0.00585939 | 7.5 | 128.91 | 74.50 | 0.00585939 | 16.6 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 12170.284 | 9257.913 | 363.444233 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2434 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 363.444233 | 0.39495545 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | Sensible | 11037.63 | 10914.51 | 0.9069 | 0.39495545 | 363.444233 | 78.75 | 58.72 | 0.00758264 | 10.9 | 53.60 | 49.11 | 0.00750000 | 7.4 | -999. | -999.0 | -999.0 | -999.0 | 467.746 | 10569.88 | 94.38 | 0.00686598 | 62.80 | 44.99498340 | 12.3802 | 75.00 | 0.00768390 | 75.00 | 0.00765252 | 36.0144 | 7380.10 | 0.00 | 12175.36 | 8658.96 | 0.37935770 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.01 | 53.96 | 0.00883642 | 8.3 | |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 22021.718 | 22021.718 | 363.444233 | 0.30211348 | 329.175 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0652 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 363.444233 | 0.39495545 | 1.0027 | 62.4216 | 5.36632280 | 159.80 | 179.60 | 19.80 | 383516.36 | 5.7421 | 5.857616 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 22021.72 | 19432.37 | 1.0000 | 0.39495545 | 363.444233 | 65.88 | 51.60 | 0.00610202 | 8.2 | 122.00 | 72.00 | 0.00800000 | 17.0 | 0.31433856 | 140.00 | 120.20 | 19.80 | 0.000 | 22021.72 | 22.64 | 0.00280840 | 22.64 | 44.99498340 | 12.3802 | 71.99 | 0.00656739 | 71.99 | 0.00656739 | 34.2536 | 7385.33 | 0.00 | 22902.48 | 22902.48 | 0.39495545 | 61.88 | 52.25 | 0.00610202 | 7.7 | 128.25 | 74.60 | 0.00610202 | 16.6 | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3446.752 | 3381.263 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3456.778 | 3391.099 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3446.691 | 3381.204 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3446.666 | 3381.179 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3456.777 | 3391.098 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3446.763 | 3381.274 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3499.227 | 3432.742 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3514.349 | 3447.577 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3499.426 | 3432.937 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3499.369 | 3432.881 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3514.352 | 3447.579 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3499.439 | 3432.950 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3446.395 | 3380.914 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3456.630 | 3390.954 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3446.536 | 3381.052 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3446.475 | 3380.992 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3456.624 | 3390.948 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR | Coil:WaterHeating:AirToWaterHeatPump:Wrapped | unknown | unknown | unknown | N/A | N/A | N/A | N/A | No | No | unknown | No | 3446.537 | 3381.053 | 400.423678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2400 | 0.2400 | 0.0652 | HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 160.010573 | 0.17388376 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | unknown | unknown | unknown | unknown | unknown | unknown | Sensible | 3165.61 | -999.0 | 1.0000 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 3165.61 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | -999. | -999.0 | -999. | -999.000 | -999.0 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. |
Report: System Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2483.00 | 4729.50 | 262.50 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1822.67 | 5105.50 | 241.17 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2368.00 | 4624.67 | 206.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2447.17 | 5265.50 | 414.83 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1655.83 | 5585.83 | 255.67 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2176.00 | 5156.50 | 211.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2724.83 | 4221.33 | 122.50 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2135.00 | 4435.67 | 85.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2626.33 | 4130.67 | 86.33 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2649.83 | 4813.83 | 234.33 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1947.33 | 4986.00 | 90.33 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2521.83 | 4680.67 | 102.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 2743.17 | 4677.33 | 118.83 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 2848.67 | 4328.83 | 114.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 2848.50 | 4434.67 | 149.17 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2310.33 | 4947.33 | 114.67 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 2428.83 | 4621.33 | 108.17 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 2829.83 | 4803.83 | 252.00 |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 3435.50 | 5843.00 | 540.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 145.33 | 0.00 | 145.33 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 95.67 | 0.00 | 95.67 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 225.17 | 0.00 | 225.17 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 608.33 | 0.00 | 608.33 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 205.33 | 0.00 | 205.33 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 225.67 | 0.00 | 225.67 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 86.83 | 0.00 | 86.83 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 56.33 | 0.00 | 56.33 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 268.00 | 0.00 | 268.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 557.50 | 0.00 | 557.50 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 170.67 | 0.00 | 170.67 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 208.83 | 0.00 | 208.83 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 144.17 | 0.00 | 144.17 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 212.67 | 0.00 | 212.67 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 160.17 | 0.00 | 160.17 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 145.00 | 0.00 | 145.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 64.67 | 0.00 | 64.67 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 515.00 | 0.00 | 515.00 | 0.00 |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1942.17 | 0.00 | 1942.17 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.106 | 0.000 | 0.269 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.094 | 0.000 | 0.269 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.106 | 0.000 | 0.269 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.106 | 0.000 | 0.269 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.093 | 0.000 | 0.269 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.106 | 0.000 | 0.269 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.047 | 0.000 | 0.270 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.034 | 0.000 | 0.270 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.047 | 0.000 | 0.269 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.046 | 0.000 | 0.269 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.034 | 0.000 | 0.269 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.046 | 0.000 | 0.269 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.106 | 0.000 | 0.269 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.106 | 0.000 | 0.269 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.106 | 0.000 | 0.269 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.093 | 0.000 | 0.269 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.094 | 0.000 | 0.269 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.106 | 0.000 | 0.269 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Zone Area [ft2] | Design Zone Outdoor Airflow - Voz [ft3/min] | Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
Total Facility | 24.79 | 36.00 | 183739.38 | 21609.96 | 0.0000 | 0.000 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Infiltration [ft3] | Total Ventilation and Infiltration [ft3] | Dynamic Target Ventilation - Voz-dyn [ft3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 9391626.75 | 33233120.28 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 8277815.26 | 32119308.79 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 9397257.36 | 33238750.88 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 9345964.35 | 33187457.87 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 8240154.86 | 32081648.38 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 9359981.03 | 33201474.56 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 4121824.81 | 27964699.67 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 3001424.57 | 26844299.42 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 4123351.11 | 27966225.97 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 4101256.50 | 27944131.36 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 2986573.82 | 26829448.68 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 4107107.47 | 27949982.32 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 9376450.02 | 33220707.66 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 9404344.05 | 33248601.69 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 9399179.82 | 33243437.46 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 8254470.40 | 32098728.04 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 8284748.98 | 32129006.62 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 9362636.48 | 33206894.12 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
Total Facility | 0.00 | 0.429172E+09 | 0.429172E+09 | 0.130536E+09 | 0.559708E+09 | 0.428131E+09 | 3814.50 | 1362.50 | 3646.00 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Infiltration [ft3/min] | Total Ventilation and Infiltration [ft3/min] | Dynamic Target Ventilation - Voz-dyn [ft3/min] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 17.7664 | 62.8681 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 15.6594 | 60.7611 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 17.7771 | 62.8788 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 17.6801 | 62.7818 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 15.5882 | 60.6899 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 17.7066 | 62.8083 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 7.7974 | 52.9017 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 5.6779 | 50.7822 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 7.8003 | 52.9046 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 7.7585 | 52.8628 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 5.6498 | 50.7541 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 7.7695 | 52.8739 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 17.7377 | 62.8447 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 17.7905 | 62.8974 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 17.7807 | 62.8877 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 15.6152 | 60.7222 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 15.6725 | 60.7794 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 17.7116 | 62.8185 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
Total Facility | 0.0000 | 811.8776 | 811.8776 | 246.9394 | 1058.8170 | 809.9097 | 3814.50 | 1362.50 | 3646.00 |
Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 23841493.53 | 23841493.53 | 23785081.69 | 3814.50 | 1353.17 | 3640.33 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 23842874.86 | 23842874.86 | 23785081.69 | 3810.33 | 1354.50 | 3643.17 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 23844257.64 | 23844257.64 | 23785081.69 | 3805.17 | 1356.83 | 3646.00 | 0.00 |
Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 45.1017 | 45.1017 | 44.9950 | 3814.50 | 1353.17 | 3640.33 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 45.1043 | 45.1043 | 44.9950 | 3810.33 | 1354.50 | 3643.17 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 45.1069 | 45.1069 | 44.9950 | 3805.17 | 1356.83 | 3646.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [ft3/min] | Limits and Scheduled Limits [ft3/min] | Economizer [ft3/min] | Exhaust Flow [ft3/min] | Mixed Air Flow [ft3/min] | High Humidity [ft3/min] | Demand Controlled Ventilation [ft3/min] | Night Ventilation [ft3/min] | Demand Limiting [ft3/min] | Energy Management System [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 58 |
Floor | 29 | 4 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 60 | 60 |
Overhang | 30 | 30 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 2037 |
Defaulted Fields | 1872 |
Fields with Defaults | 7215 |
Autosized Fields | 400 |
Autosizable Fields | 582 |
Autocalculated Fields | 198 |
Autocalculatable Fields | 422 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 149973.46 | 8091.80 | 22-MAR-03:10 | 38021.33 | 02-JUL-18:40 |
Electricity:Building | 99639.89 | 6275.41 | 02-JAN-03:10 | 18829.48 | 01-JAN-18:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
Electricity:SpaceType:GENERAL | 99639.89 | 6275.41 | 02-JAN-03:10 | 18829.48 | 01-JAN-18:10 |
InteriorLights:Electricity | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
General:InteriorLights:Electricity | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:SpaceType:GENERAL | 11336.81 | 253.88 | 01-JAN-00:10 | 3692.78 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5535.55 | 348.63 | 02-JAN-03:10 | 1046.08 | 01-JAN-18:10 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 629.82 | 14.10 | 01-JAN-00:10 | 205.15 | 01-JAN-19:10 |
InteriorEquipment:Electricity | 88303.07 | 5995.41 | 02-JAN-04:10 | 15497.32 | 01-JAN-18:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 88303.07 | 5995.41 | 02-JAN-04:10 | 15497.32 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:10 | 985.58 | 01-JAN-19:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL | 3088.82 | 28.28 | 02-JAN-03:10 | 985.58 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:10 | 427.18 | 01-JAN-09:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL | 1577.30 | 15.15 | 02-JAN-02:10 | 427.18 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
electric_range:InteriorEquipment:Electricity:SpaceType:GENERAL | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
television:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
electric_mels:InteriorEquipment:Electricity:SpaceType:GENERAL | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
Electricity:HVAC | 27857.77 | 289.29 | 20-FEB-01:00 | 13512.49 | 05-JUN-17:10 |
Cooling:Electricity | 19775.81 | 0.00 | 01-JAN-00:10 | 11345.46 | 05-JUN-17:10 |
General:Cooling:Electricity | 19775.81 | 0.00 | 01-JAN-00:10 | 11345.46 | 05-JUN-17:10 |
Electricity:Plant | 16441.50 | 149.40 | 19-JUN-15:30 | 10176.00 | 19-JUL-09:20 |
WaterSystems:Electricity | 16441.50 | 149.40 | 19-JUN-15:30 | 10176.00 | 19-JUL-09:20 |
Fans:Electricity | 8081.96 | 289.29 | 20-FEB-01:00 | 2209.73 | 26-JUL-18:10 |
Ventilation:Fans:Electricity | 2534.14 | 289.29 | 01-JAN-00:10 | 289.29 | 01-JAN-00:10 |
General:Fans:Electricity | 5547.81 | 0.00 | 20-FEB-01:00 | 1920.45 | 26-JUL-18:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityPurchased:Facility | 149973.46 | 8091.80 | 22-MAR-03:10 | 38021.33 | 02-JUL-18:40 |
ElectricityPurchased:Plant | 149973.46 | 8091.80 | 22-MAR-03:10 | 38021.33 | 02-JUL-18:40 |
Cogeneration:ElectricityPurchased | 149973.46 | 8091.80 | 22-MAR-03:10 | 38021.33 | 02-JUL-18:40 |
General:Cogeneration:ElectricityPurchased | 149973.46 | 8091.80 | 22-MAR-03:10 | 38021.33 | 02-JUL-18:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 149973.46 | 8091.80 | 22-MAR-03:10 | 38021.33 | 02-JUL-18:40 |
ElectricityNet:Plant | 149973.46 | 8091.80 | 22-MAR-03:10 | 38021.33 | 02-JUL-18:40 |
Cogeneration:ElectricityNet | 149973.46 | 8091.80 | 22-MAR-03:10 | 38021.33 | 02-JUL-18:40 |
General:Cogeneration:ElectricityNet | 149973.46 | 8091.80 | 22-MAR-03:10 | 38021.33 | 02-JUL-18:40 |
ExteriorLights:Electricity | 6034.31 | 0.00 | 01-JAN-06:10 | 1377.69 | 01-JAN-00:10 |
Exterior-Lights:ExteriorLights:Electricity | 6034.31 | 0.00 | 01-JAN-06:10 | 1377.69 | 01-JAN-00:10 |
Garage-Lights:ExteriorLights:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:Electricity | 1308.75 | 149.40 | 30-MAR-08:10 | 149.40 | 01-JAN-08:50 |
Water Heater Parasitic:WaterSystems:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Natural Gas Annual Value [therm] | Natural Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 937.55 | 0.00 | 01-JAN-13:50 | 163389.30 | 27-JAN-07:20 |
NaturalGas:Plant | 937.55 | 0.00 | 01-JAN-13:50 | 163389.30 | 27-JAN-07:20 |
Heating:NaturalGas | 937.55 | 0.00 | 01-JAN-13:50 | 163389.30 | 27-JAN-07:20 |
Boiler:Heating:NaturalGas | 937.55 | 0.00 | 01-JAN-13:50 | 163389.30 | 27-JAN-07:20 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:50 |
Water:Plant | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:50 |
WaterSystems:Water | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:50 |
Domestic Hot Water:WaterSystems:Water | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:50 |
MainsWater:Facility | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:50 |
MainsWater:Plant | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:50 |
WaterSystems:MainsWater | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:50 |
Domestic Hot Water:WaterSystems:MainsWater | 41747.51 | 0.01 | 02-JAN-02:10 | 0.15 | 01-JAN-08:50 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 953535.57 | 351.39 | 25-SEP-03:00 | 401905.76 | 27-JAN-07:20 |
EnergyTransfer:HVAC | 452491.52 | 0.00 | 04-JAN-01:00 | 173336.37 | 27-JAN-07:20 |
CoolingCoils:EnergyTransfer | 379869.79 | 0.00 | 01-JAN-00:10 | 153800.93 | 26-JUL-18:10 |
EnergyTransfer:Building | 362463.01 | 0.00 | 20-FEB-01:00 | 136325.70 | 15-JUN-17:20 |
EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer | 56012.55 | 0.00 | 01-JAN-16:10 | 84700.28 | 27-DEC-07:10 |
Heating:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 56012.55 | 0.00 | 01-JAN-16:10 | 84700.28 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 306450.47 | 0.00 | 01-JAN-00:10 | 136325.70 | 15-JUN-17:20 |
Cooling:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer | 306450.47 | 0.00 | 01-JAN-00:10 | 136325.70 | 15-JUN-17:20 |
General:Cooling:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 21413.74 | 0.00 | 01-JAN-11:30 | 9643.40 | 15-JUN-17:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 3307.96 | 0.00 | 01-JAN-11:30 | 5218.38 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 3307.96 | 0.00 | 01-JAN-11:30 | 5218.38 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 18105.78 | 0.00 | 01-JAN-00:10 | 9643.40 | 15-JUN-17:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 18105.78 | 0.00 | 01-JAN-00:10 | 9643.40 | 15-JUN-17:10 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 15904.42 | 0.00 | 01-JAN-00:10 | 5477.26 | 14-JUN-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2020.27 | 0.00 | 01-JAN-00:10 | 3796.10 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2020.27 | 0.00 | 01-JAN-00:10 | 3796.10 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 13884.15 | 0.00 | 01-JAN-00:10 | 5477.26 | 14-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 13884.15 | 0.00 | 01-JAN-00:10 | 5477.26 | 14-JUN-18:10 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 20953.87 | 0.00 | 01-JAN-09:30 | 6906.48 | 15-JUN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 3038.93 | 0.00 | 01-JAN-09:30 | 5212.63 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 3038.93 | 0.00 | 01-JAN-09:30 | 5212.63 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 17914.94 | 0.00 | 01-JAN-00:10 | 6906.48 | 15-JUN-10:00 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 17914.94 | 0.00 | 01-JAN-00:10 | 6906.48 | 15-JUN-10:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 19915.06 | 0.00 | 01-JAN-12:30 | 9784.74 | 15-JUN-17:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4460.15 | 0.00 | 01-JAN-11:00 | 7610.20 | 15-FEB-11:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4460.15 | 0.00 | 01-JAN-11:00 | 7610.20 | 15-FEB-11:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 15454.91 | 0.00 | 01-JAN-00:10 | 9784.74 | 15-JUN-17:20 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 15454.91 | 0.00 | 01-JAN-00:10 | 9784.74 | 15-JUN-17:20 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 14586.48 | 0.00 | 01-JAN-16:10 | 5654.33 | 14-JUN-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3324.34 | 0.00 | 01-JAN-16:10 | 4502.34 | 18-DEC-17:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3324.34 | 0.00 | 01-JAN-16:10 | 4502.34 | 18-DEC-17:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 11262.14 | 0.00 | 01-JAN-00:10 | 5654.33 | 14-JUN-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 11262.14 | 0.00 | 01-JAN-00:10 | 5654.33 | 14-JUN-18:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 19209.20 | 0.00 | 01-JAN-12:50 | 6966.69 | 15-JUN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4165.38 | 0.00 | 01-JAN-12:50 | 5304.16 | 03-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4165.38 | 0.00 | 01-JAN-12:50 | 5304.16 | 03-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 15043.82 | 0.00 | 01-JAN-00:10 | 6966.69 | 15-JUN-10:00 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 15043.82 | 0.00 | 01-JAN-00:10 | 6966.69 | 15-JUN-10:00 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 22482.24 | 0.00 | 01-JAN-00:10 | 9629.07 | 15-JUN-17:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2259.95 | 0.00 | 01-JAN-00:10 | 4467.70 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2259.95 | 0.00 | 01-JAN-00:10 | 4467.70 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 20222.29 | 0.00 | 01-JAN-00:10 | 9629.07 | 15-JUN-17:20 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 20222.29 | 0.00 | 01-JAN-00:10 | 9629.07 | 15-JUN-17:20 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 17304.46 | 0.00 | 01-JAN-00:10 | 5593.36 | 02-JUL-18:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1176.75 | 0.00 | 01-JAN-00:10 | 3053.76 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1176.75 | 0.00 | 01-JAN-00:10 | 3053.76 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 16127.71 | 0.00 | 01-JAN-00:10 | 5593.36 | 02-JUL-18:20 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 16127.71 | 0.00 | 01-JAN-00:10 | 5593.36 | 02-JUL-18:20 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 22299.61 | 0.00 | 01-JAN-00:10 | 7091.54 | 19-SEP-14:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2056.95 | 0.00 | 01-JAN-00:10 | 5295.77 | 03-DEC-22:20 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2056.95 | 0.00 | 01-JAN-00:10 | 5295.77 | 03-DEC-22:20 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 20242.65 | 0.00 | 01-JAN-00:10 | 7091.54 | 19-SEP-14:00 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 20242.65 | 0.00 | 01-JAN-00:10 | 7091.54 | 19-SEP-14:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 20676.77 | 0.00 | 01-JAN-12:30 | 9793.69 | 15-JUN-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 3260.35 | 0.00 | 01-JAN-11:00 | 7295.11 | 27-JAN-11:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 3260.35 | 0.00 | 01-JAN-11:00 | 7295.11 | 27-JAN-11:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 17416.42 | 0.00 | 01-JAN-00:10 | 9793.69 | 15-JUN-17:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 17416.42 | 0.00 | 01-JAN-00:10 | 9793.69 | 15-JUN-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 15409.14 | 0.00 | 01-JAN-00:10 | 5760.24 | 15-JUN-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2177.11 | 0.00 | 01-JAN-00:10 | 3901.80 | 26-JAN-11:30 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2177.11 | 0.00 | 01-JAN-00:10 | 3901.80 | 26-JAN-11:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 13232.04 | 0.00 | 01-JAN-00:10 | 5760.24 | 15-JUN-18:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 13232.04 | 0.00 | 01-JAN-00:10 | 5760.24 | 15-JUN-18:30 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 20229.46 | 0.00 | 01-JAN-11:40 | 7133.07 | 15-JUN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 3039.48 | 0.00 | 01-JAN-11:40 | 4488.11 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 3039.48 | 0.00 | 01-JAN-11:40 | 4488.11 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 17189.98 | 0.00 | 01-JAN-00:10 | 7133.07 | 15-JUN-10:00 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 17189.98 | 0.00 | 01-JAN-00:10 | 7133.07 | 15-JUN-10:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 22969.37 | 0.00 | 01-JAN-13:20 | 8046.25 | 02-JUL-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4397.40 | 0.00 | 01-JAN-13:20 | 5851.57 | 03-FEB-07:00 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4397.40 | 0.00 | 01-JAN-13:20 | 5851.57 | 03-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 18571.97 | 0.00 | 01-JAN-00:10 | 8046.25 | 02-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 18571.97 | 0.00 | 01-JAN-00:10 | 8046.25 | 02-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 23910.27 | 0.00 | 01-JAN-09:50 | 7927.06 | 02-JUL-18:10 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 3291.02 | 0.00 | 01-JAN-09:50 | 5828.96 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 3291.02 | 0.00 | 01-JAN-09:50 | 5828.96 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 20619.26 | 0.00 | 01-JAN-00:10 | 7927.06 | 02-JUL-18:10 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 20619.26 | 0.00 | 01-JAN-00:10 | 7927.06 | 02-JUL-18:10 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 24382.81 | 0.00 | 01-JAN-00:10 | 10683.95 | 15-JUN-17:20 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 3585.42 | 0.00 | 01-JAN-00:10 | 5837.92 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 3585.42 | 0.00 | 01-JAN-00:10 | 5837.92 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 20797.39 | 0.00 | 01-JAN-00:10 | 10683.95 | 15-JUN-17:20 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 20797.39 | 0.00 | 01-JAN-00:10 | 10683.95 | 15-JUN-17:20 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 18255.29 | 0.00 | 01-JAN-15:50 | 6928.05 | 02-JUL-18:40 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 3490.93 | 0.00 | 01-JAN-14:40 | 4848.86 | 01-FEB-17:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 3490.93 | 0.00 | 01-JAN-14:40 | 4848.86 | 01-FEB-17:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 14764.36 | 0.00 | 01-JAN-00:10 | 6928.05 | 02-JUL-18:40 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 14764.36 | 0.00 | 01-JAN-00:10 | 6928.05 | 02-JUL-18:40 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 18922.73 | 0.00 | 01-JAN-00:10 | 6748.77 | 05-JUN-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 2253.15 | 0.00 | 01-JAN-00:10 | 4408.06 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 2253.15 | 0.00 | 01-JAN-00:10 | 4408.06 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 16669.58 | 0.00 | 01-JAN-00:10 | 6748.77 | 05-JUN-19:00 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 16669.58 | 0.00 | 01-JAN-00:10 | 6748.77 | 05-JUN-19:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 23638.08 | 0.00 | 01-JAN-13:50 | 10881.74 | 15-JUN-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4707.00 | 0.00 | 01-JAN-11:00 | 8255.28 | 30-JAN-12:20 |
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4707.00 | 0.00 | 01-JAN-11:00 | 8255.28 | 30-JAN-12:20 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 18931.08 | 0.00 | 01-JAN-00:10 | 10881.74 | 15-JUN-17:30 |
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 18931.08 | 0.00 | 01-JAN-00:10 | 10881.74 | 15-JUN-17:30 |
PlantLoopHeatingDemand:Facility | 136198.66 | 201.00 | 01-AUG-04:00 | 141998.54 | 27-JAN-07:20 |
PlantLoopHeatingDemand:Plant | 63576.94 | 201.00 | 01-AUG-04:00 | 19771.54 | 29-JAN-09:00 |
WaterSystems:PlantLoopHeatingDemand | 63576.94 | 201.00 | 01-AUG-04:00 | 19771.54 | 29-JAN-09:00 |
General:WaterSystems:PlantLoopHeatingDemand | 63576.94 | 201.00 | 01-AUG-04:00 | 19771.54 | 29-JAN-09:00 |
HeatingCoils:EnergyTransfer | 72621.72 | 0.00 | 01-JAN-13:50 | 124959.07 | 27-JAN-07:20 |
PlantLoopHeatingDemand:HVAC | 72621.72 | 0.00 | 01-JAN-13:50 | 124959.07 | 27-JAN-07:20 |
HeatingCoils:PlantLoopHeatingDemand | 72621.72 | 0.00 | 01-JAN-13:50 | 124959.07 | 27-JAN-07:20 |
EnergyTransfer:Plant | 138581.04 | 201.00 | 01-AUG-04:00 | 147750.91 | 27-JAN-07:20 |
WaterSystems:EnergyTransfer | 63576.94 | 201.00 | 01-AUG-04:00 | 19771.54 | 29-JAN-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 63576.94 | 201.00 | 01-AUG-04:00 | 19771.54 | 29-JAN-09:00 |
Boilers:EnergyTransfer | 75004.10 | 0.00 | 01-JAN-13:50 | 130711.44 | 27-JAN-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | -382.02 | 4498.161 | -1224.90 | 0.000 | 0.000 | 2984.719 | 2150.478 | 10464.601 | 10639.649 | 0.000 | 1340.278 | 0.001 | 0.000 | -3455.00 | 0.000 | -6745.48 | -2581.50 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | -380.92 | 3097.303 | -865.01 | 0.000 | 0.000 | 2976.351 | 2150.478 | 10464.601 | 4678.043 | 0.000 | 1295.837 | 0.066 | 0.000 | -1385.79 | 0.000 | -6540.12 | -1775.53 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | -385.35 | 3996.296 | -1186.29 | 0.000 | 0.000 | 2986.743 | 2150.478 | 10464.601 | 10665.075 | 0.000 | 1336.265 | 0.132 | 0.000 | -3329.18 | 0.000 | -6768.11 | -2629.87 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | -380.42 | 5807.447 | -1018.83 | 0.000 | 0.000 | 3008.220 | 2150.478 | 10464.601 | 7556.398 | 0.000 | 1343.170 | 0.040 | 0.000 | -3522.10 | 0.000 | -6545.97 | -3460.08 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | -379.59 | 4932.574 | -692.23 | 0.000 | 0.000 | 3003.284 | 2150.478 | 10464.601 | 1459.840 | 0.000 | 1302.680 | 0.000 | 0.000 | -1450.56 | 0.000 | -6357.03 | -2635.49 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | -384.19 | 5665.769 | -993.57 | 0.000 | 0.000 | 3007.213 | 2150.478 | 10464.601 | 7481.882 | 0.000 | 1337.590 | 0.002 | 0.000 | -3314.78 | 0.000 | -6610.62 | -3637.93 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | -384.80 | 3318.394 | -1387.40 | 0.000 | 0.000 | 2966.309 | 2150.478 | 10464.601 | 10574.883 | 0.000 | 1115.206 | 0.094 | 0.000 | -3546.74 | 0.000 | -5692.11 | -70.31 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | -383.86 | 2070.712 | -1033.67 | 0.000 | 0.000 | 2955.372 | 2150.478 | 10464.601 | 4646.197 | 0.000 | 1069.811 | 575.128 | 0.000 | -1421.91 | 0.000 | -5488.72 | -0.01 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | -388.09 | 2840.969 | -1362.96 | 0.000 | 0.000 | 2970.818 | 2150.478 | 10464.601 | 10596.962 | 0.000 | 1112.940 | 4.772 | 0.000 | -3412.44 | 0.000 | -5702.42 | -0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | -383.00 | 4436.058 | -1165.30 | 0.000 | 0.000 | 2992.848 | 2150.478 | 10464.601 | 7503.445 | 0.000 | 1117.368 | 0.184 | 0.000 | -3607.51 | 0.000 | -5525.39 | -939.79 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | -382.21 | 3571.987 | -835.89 | 0.000 | 0.000 | 2986.015 | 2150.478 | 10464.601 | 1444.315 | 0.000 | 1073.795 | 0.034 | 0.000 | -1486.25 | 0.000 | -5328.73 | -249.28 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | -385.74 | 4329.466 | -1153.23 | 0.000 | 0.000 | 2992.566 | 2150.478 | 10464.601 | 7424.866 | 0.000 | 1113.606 | 0.015 | 0.000 | -3394.35 | 0.000 | -5573.37 | -1027.87 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | -385.33 | 5877.998 | -1284.61 | 0.000 | 0.000 | 2995.265 | 2150.478 | 10464.601 | 7414.041 | 0.000 | 1327.177 | 0.032 | 0.000 | -3401.34 | 0.000 | -6684.44 | -91.17 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | -385.87 | 4302.097 | -1415.46 | 0.000 | 0.000 | 2979.970 | 2150.478 | 10464.601 | 10600.161 | 0.000 | 1326.634 | 2.998 | 0.000 | -3394.99 | 0.000 | -6801.58 | -0.10 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | -383.78 | 4740.581 | -1444.37 | 0.000 | 0.000 | 2977.519 | 2150.478 | 10464.601 | 10576.040 | 0.000 | 1329.147 | 20.910 | 0.000 | -3523.76 | 0.000 | -6782.99 | -0.20 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | -382.16 | 5049.909 | -977.22 | 0.000 | 0.000 | 2990.519 | 2150.478 | 10464.601 | 1438.862 | 0.000 | 1287.066 | 863.569 | 0.000 | -1485.74 | 0.000 | -6435.90 | -0.41 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | -382.91 | 3372.937 | -1098.55 | 0.000 | 0.000 | 2968.888 | 2150.478 | 10464.601 | 4645.765 | 0.000 | 1283.877 | 894.003 | 0.000 | -1411.81 | 0.000 | -6579.37 | -0.17 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | -382.90 | 6034.035 | -1304.14 | 0.000 | 0.000 | 2996.542 | 2150.478 | 10464.601 | 7484.668 | 0.000 | 1330.647 | 29.295 | 0.000 | -3606.01 | 0.000 | -6626.16 | -0.16 |
UNHEATEDBSMT | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26464.366 | 187634.178 | 0.000 | 0.000 | 0.000 | -214098.54 | -2.99 |
Total Facility | 0.000 | -6903.13 | 77942.695 | -20443.63 | 0.000 | 0.000 | 53739.161 | 38708.604 | 188362.826 | 126831.092 | 0.000 | 48907.460 | 190025.454 | 0.000 | -50150.27 | 0.000 | -326887.04 | -19102.86 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 15-JUN-17:10 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 263.17 | 469.21 | 1664.02 | 5608.97 | 0.00 | 1576.11 | 62.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 14-JUN-18:15 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 426.77 | 631.63 | 1724.99 | 466.74 | 0.00 | 1439.40 | 788.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 15-JUN-09:05 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 90.23 | 1096.02 | 4421.57 | 0.00 | 1256.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -73.1 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 15-JUN-17:19 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 263.17 | 469.21 | 1664.02 | 5879.18 | 0.00 | 1529.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19.6 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 14-JUN-18:15 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 426.77 | 631.63 | 1724.99 | 824.31 | 0.00 | 1439.40 | 607.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 15-JUN-09:05 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 90.23 | 1096.02 | 4331.14 | 0.00 | 1256.75 | 77.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 15-JUN-17:19 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 263.17 | 469.21 | 1664.02 | 5427.49 | 0.00 | 1190.67 | 615.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 02-JUL-18:24 | 0.00 | -0.3 | 0.00 | -0.2 | 0.00 | 0.00 | 426.76 | 631.63 | 1748.06 | 430.38 | 0.00 | 1020.11 | 1337.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 19-SEP-13:00 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.08 | 90.23 | 1084.63 | 3330.13 | 0.00 | 844.08 | 1627.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 15-JUN-17:30 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 263.17 | 469.21 | 1664.02 | 5758.22 | 0.00 | 1163.92 | 475.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 15-JUN-18:30 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 426.77 | 631.63 | 1724.99 | 924.57 | 0.00 | 966.50 | 1086.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 15-JUN-09:05 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 90.23 | 1096.02 | 4318.83 | 0.00 | 1002.82 | 510.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 02-JUL-18:13 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 426.76 | 631.63 | 1748.06 | 1398.88 | 0.00 | 1370.93 | 2470.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 02-JUL-18:13 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 426.76 | 631.63 | 1748.06 | 1118.07 | 0.00 | 1370.93 | 2632.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 15-JUN-17:19 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 263.17 | 469.21 | 1664.02 | 5407.85 | 0.00 | 1525.26 | 1354.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 02-JUL-18:45 | 0.00 | -0.3 | 0.00 | -0.3 | 0.00 | 0.00 | 426.77 | 631.63 | 1748.06 | 773.16 | 0.00 | 1211.19 | 2137.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 05-JUN-18:00 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 426.77 | 631.63 | 1724.99 | 334.46 | 0.00 | 1366.72 | 2264.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 15-JUN-17:30 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 263.17 | 469.21 | 1664.02 | 5735.88 | 0.00 | 1479.33 | 1270.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
UNHEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-JUN-17:19 | 0.00 | 0.00 | 0.00 | -11.4 | 0.00 | 0.00 | 4737.04 | 8445.78 | 29952.39 | 48176.37 | 0.00 | 25041.90 | 61684.43 | 0.00 | 0.00 | 0.00 | -41705.0 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 30-SEP-06:44 | 0.00 | 0.00 | 13031.98 | 0.00 | 0.00 | 0.00 | 565.13 | 336.87 | 1085.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -501.4 | 0.00 | -1119.7 | -13398.6 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 14-MAR-08:35 | 0.00 | 0.00 | 7573.44 | 0.00 | 0.00 | 0.00 | 215.87 | 132.34 | 1155.86 | 962.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1222.0 | -8818.2 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 26-MAR-03:33 | 0.00 | 0.00 | 10393.09 | 0.00 | 0.00 | 0.00 | 577.87 | 48.12 | 848.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1270.7 | 0.00 | -1733.7 | -8863.3 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 01-MAR-09:00 | 0.00 | 0.00 | 13597.56 | 0.00 | 0.00 | 0.00 | 135.97 | 90.23 | 1096.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -147.4 | 0.00 | -2322.5 | -12449.9 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 08-FEB-17:43 | 0.00 | 0.00 | 8883.30 | 0.00 | 0.00 | 0.00 | 305.04 | 469.21 | 1664.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -421.2 | 0.00 | -2403.0 | -8497.3 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 10-APR-23:23 | 0.00 | 0.00 | 9905.34 | 0.00 | 0.00 | 0.00 | 558.59 | 120.31 | 1150.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1179.0 | 0.00 | -2249.2 | -8306.5 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 11-APR-10:03 | 0.00 | 0.00 | 10933.16 | 0.00 | 0.00 | 0.00 | 137.16 | 90.23 | 1089.80 | 1596.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -987.7 | -12858.8 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 27-NOV-16:19 | -2925.7 | 0.00 | 9651.67 | 0.00 | 0.00 | 0.00 | 162.58 | 336.87 | 1350.56 | 421.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1227.4 | -7769.9 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 17-DEC-01:52 | 0.00 | 0.00 | 12164.62 | 0.00 | 0.00 | 0.00 | 539.98 | 48.12 | 894.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1561.7 | 0.00 | -1989.6 | -10095.5 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 04-DEC-09:32 | 0.00 | 0.00 | 14455.94 | 0.00 | 0.00 | 0.00 | 133.32 | 90.23 | 1096.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -544.5 | 0.00 | -1841.1 | -13389.9 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 14-JAN-01:10 | 0.00 | 0.00 | 8911.06 | 0.00 | 0.00 | 0.00 | 552.85 | 48.12 | 894.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -406.1 | 0.00 | -1156.5 | -8843.5 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 30-MAR-00:02 | 0.00 | 0.00 | 11123.76 | 0.00 | 0.00 | 0.00 | 555.56 | 48.12 | 962.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1361.9 | 0.00 | -1693.9 | -9634.4 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 25-MAR-00:31 | 0.00 | 0.00 | 12355.46 | 0.00 | 0.00 | 0.00 | 573.92 | 48.12 | 967.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1120.5 | 0.00 | -1501.5 | -11322.7 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 28-DEC-22:22 | 0.00 | 0.00 | 13930.97 | 0.00 | 0.00 | 0.00 | 582.62 | 294.76 | 1340.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1471.5 | 0.00 | -2257.3 | -12419.7 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 18-APR-07:06 | 0.00 | 0.00 | 12170.31 | 0.00 | 0.00 | 0.00 | 511.84 | 300.78 | 1210.75 | 321.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1338.8 | -13176.5 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 04-DEC-15:53 | 0.00 | 0.00 | 9889.14 | 0.00 | 0.00 | 0.00 | 139.63 | 156.40 | 1147.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -117.6 | 0.00 | -826.6 | -10388.4 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 07-NOV-08:25 | -2683.8 | 0.00 | 11400.13 | 0.00 | 0.00 | 0.00 | 215.03 | 132.34 | 1155.86 | 1670.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1612.3 | -10277.8 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 20-NOV-00:30 | 0.00 | 0.00 | 15118.79 | 0.00 | 0.00 | 0.00 | 561.03 | 48.12 | 962.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1320.1 | 0.00 | -1864.9 | -13505.8 |
UNHEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-DEC-07:10 | -8306.5 | 0.00 | 93006.72 | 0.00 | 0.00 | 0.00 | 8365.10 | 5413.96 | 21793.53 | 0.00 | 0.00 | 7339.27 | 0.00 | 0.00 | -26808.7 | 0.00 | -54601.1 | -46202.3 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 413.7154 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 413.7154 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 242.6050 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 242.6050 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 309.5429 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 309.5429 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 407.0318 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 407.0318 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 241.2465 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 241.2465 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 294.1582 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 294.1582 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 421.9414 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 421.9414 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 256.1926 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 256.1926 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.8829 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 321.8829 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 416.0010 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 416.0010 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 254.4175 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 254.4175 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 309.3738 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 309.3738 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 467.6748 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 467.6748 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 305.4930 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 305.4930 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 359.6530 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 359.6530 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 470.0766 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 470.0766 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 309.0412 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 309.0412 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 363.4442 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 363.4442 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 413.7154 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 413.7154 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 242.6050 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 242.6050 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 309.5429 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 309.5429 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 407.0318 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 407.0318 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 241.2465 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 241.2465 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 294.1582 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 294.1582 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 421.9414 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 421.9414 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 256.1926 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 256.1926 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.8829 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 321.8829 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 416.0010 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 416.0010 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 254.4175 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 254.4175 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 309.3738 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 309.3738 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 467.6748 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 467.6748 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 305.4930 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 305.4930 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 359.6530 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 359.6530 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 470.0766 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 470.0766 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 309.0412 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 309.0412 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 363.4442 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 363.4442 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 413.7154 | 413.7154 | 413.7154 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 242.6050 | 242.6050 | 242.6050 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 309.5429 | 309.5429 | 309.5429 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 407.0318 | 407.0318 | 407.0318 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 241.2465 | 241.2465 | 241.2465 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 294.1582 | 294.1582 | 294.1582 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 421.9414 | 421.9414 | 421.9414 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 256.1926 | 256.1926 | 256.1926 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 321.8829 | 321.8829 | 321.8829 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 416.0010 | 416.0010 | 416.0010 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 254.4175 | 254.4175 | 254.4175 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 309.3738 | 309.3738 | 309.3738 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 363.4442 | 363.4442 | 363.4442 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 359.6530 | 359.6530 | 359.6530 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 467.6748 | 467.6748 | 467.6748 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 309.0412 | 309.0412 | 309.0412 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 305.4930 | 305.4930 | 305.4930 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 470.0766 | 470.0766 | 470.0766 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 413.7154 | 413.7154 | 413.7154 | 413.7154 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 242.6050 | 242.6050 | 242.6050 | 242.6050 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 309.5429 | 309.5429 | 309.5429 | 309.5429 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 407.0318 | 407.0318 | 407.0318 | 407.0318 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 241.2465 | 241.2465 | 241.2465 | 241.2465 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 294.1582 | 294.1582 | 294.1582 | 294.1582 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 421.9414 | 421.9414 | 421.9414 | 421.9414 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 256.1926 | 256.1926 | 256.1926 | 256.1926 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.8829 | 321.8829 | 321.8829 | 321.8829 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 416.0010 | 416.0010 | 416.0010 | 416.0010 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 254.4175 | 254.4175 | 254.4175 | 254.4175 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 309.3738 | 309.3738 | 309.3738 | 309.3738 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 467.6748 | 467.6748 | 467.6748 | 467.6748 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 305.4930 | 305.4930 | 305.4930 | 305.4930 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 359.6530 | 359.6530 | 359.6530 | 359.6530 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 470.0766 | 470.0766 | 470.0766 | 470.0766 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 309.0412 | 309.0412 | 309.0412 | 309.0412 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 363.4442 | 363.4442 | 363.4442 | 363.4442 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 413.7154 | 413.7154 | 413.7154 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 242.6050 | 242.6050 | 242.6050 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 309.5429 | 309.5429 | 309.5429 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 407.0318 | 407.0318 | 407.0318 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 241.2465 | 241.2465 | 241.2465 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 294.1582 | 294.1582 | 294.1582 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 421.9414 | 421.9414 | 421.9414 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 256.1926 | 256.1926 | 256.1926 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 321.8829 | 321.8829 | 321.8829 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 416.0010 | 416.0010 | 416.0010 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 254.4175 | 254.4175 | 254.4175 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 309.3738 | 309.3738 | 309.3738 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 363.4442 | 363.4442 | 363.4442 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 359.6530 | 359.6530 | 359.6530 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 467.6748 | 467.6748 | 467.6748 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 309.0412 | 309.0412 | 309.0412 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 305.4930 | 305.4930 | 305.4930 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 470.0766 | 470.0766 | 470.0766 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 413.7154 | 413.7154 | 413.7154 | 413.7154 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 242.6050 | 242.6050 | 242.6050 | 242.6050 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 309.5429 | 309.5429 | 309.5429 | 309.5429 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 407.0318 | 407.0318 | 407.0318 | 407.0318 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 241.2465 | 241.2465 | 241.2465 | 241.2465 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 294.1582 | 294.1582 | 294.1582 | 294.1582 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 421.9414 | 421.9414 | 421.9414 | 421.9414 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 256.1926 | 256.1926 | 256.1926 | 256.1926 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 321.8829 | 321.8829 | 321.8829 | 321.8829 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 416.0010 | 416.0010 | 416.0010 | 416.0010 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 254.4175 | 254.4175 | 254.4175 | 254.4175 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 309.3738 | 309.3738 | 309.3738 | 309.3738 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 467.6748 | 467.6748 | 467.6748 | 467.6748 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 305.4930 | 305.4930 | 305.4930 | 305.4930 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 359.6530 | 359.6530 | 359.6530 | 359.6530 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 470.0766 | 470.0766 | 470.0766 | 470.0766 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 309.0412 | 309.0412 | 309.0412 | 309.0412 | 0.0000 | 1.0000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 363.4442 | 363.4442 | 363.4442 | 363.4442 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [ft2] | 39005.22 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
UNHEATEDBSMT | 7794.39 | 0.00 | 7794.39 | 0.00 |
BREEZEWAY | 1798.16 | 0.00 | 1798.16 | 0.00 |
ATTIC | 7802.71 | 0.00 | 7802.71 | 0.00 |
Totals | 39005.22 | 21609.96 | 17395.26 |
Data | |
Number of hours heating loads not met | 1942.17 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 1942.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Gasoline Use [therm] | Gasoline Demand [Btu/h] | Diesel Use [kBtu] | Diesel Demand [Btu/h] | Coal Use [kBtu] | Coal Demand [Btu/h] | Fuel Oil No 1 Use [kBtu] | Fuel Oil No 1 Demand [Btu/h] | Fuel Oil No 2 Use [kBtu] | Fuel Oil No 2 Demand [Btu/h] | Propane Use [kBtu] | Propane Demand [Btu/h] | Other Fuel 1 Use [kBtu] | Other Fuel 1 Demand [Btu/h] | Other Fuel 2 Use [kBtu] | Other Fuel 2 Demand [Btu/h] | District Cooling Use [ton-hrs] | District Cooling Demand [ton] | District Heating Use [kBtu] | District Heating Demand [Btu/h] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 937.55 | 163389.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 19775.81 | 11345.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- General | 11336.81 | 3692.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Exterior-Lights | 6034.31 | 1377.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- dishwasher | 3088.82 | 985.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- refrigerator | 12036.11 | 1639.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- clotheswasher | 1577.30 | 427.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_dryer | 12502.11 | 3196.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_range | 9058.39 | 3721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- electric_mels | 46926.68 | 7929.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- IECC_adj | 3113.66 | 526.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation | 2534.14 | 289.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 5547.81 | 1920.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 1308.75 | 149.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Other | 0.00 | 10026.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 301503.54 | 512071.96 |
Natural Gas | 0.00 | 93755.13 |
Additional | 0.00 | 0.00 |
Total | 301503.54 | 605827.09 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting (All) | 0.29 |
Space Heating | 0.00 |
Space Cooling | 0.51 |
Fans (All) | 0.21 |
Service Water Heating | 0.42 |
Receptacle Equipment | 2.26 |
Miscellaneous (All) | 3.84 |
Subtotal | 3.84 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.70 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.70 |
Subtotal | 0.70 |
Additional [kBtu/ft2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 6.39 |
Space Heating | 15.48 |
Space Cooling | 11.15 |
Fans (All) | 4.55 |
Service Water Heating | 9.27 |
Receptacle Equipment | 49.77 |
Miscellaneous | 3.40 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
OCCUPANCY | 6031. | 8760. |
INTERIORLIGHTING | 2852. | 8760. |
INTERIORLIGHTINGHE | 3070. | 8760. |
INTERIORLIGHTINGHE_OS | 2910. | 8760. |
INTERIORLIGHTINGHE_VS | 2149. | 8760. |
EXTERIORLIGHTING | 4380. | 4380. |
REFRIGERATOR | 7343. | 8760. |
MISCPLUGLOAD | 5918. | 8760. |
COOKINGRANGE | 2434. | 8760. |
DISHWASHER_FLOW_SCH | 2642. | 8760. |
CLOTHESWASHER_FLOW_SCH | 3113. | 8760. |
DISHWASHER_EQUIP_SCH | 3134. | 8760. |
CLOTHESWASHER_EQUIP_SCH | 3692. | 8760. |
CLOTHESDRYER | 3911. | 8760. |
SHADING_2012IECC | 0. | 0. |
SHADING_2012IECC_HERS | 7007. | 8760. |
SINKSENSSCHEDULE | 6025. | 8760. |
SINKLATSCHEDULE | 2735. | 8760. |
SHOWERSENSSCHEDULE | 4492. | 8760. |
SHOWERLATSCHEDULE | 4268. | 8760. |
BATHSENSSCHEDULE | 8760. | 8760. |
BATHLATSCHEDULE | 0. | 0. |
First Object Used | Month Assumed | 11am First Wednesday [F] | Days with Same 11am Value | 11pm First Wednesday [F] | Days with Same 11pm Value | |
HEATING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | January | 72.00 | 365 | 72.00 | 365 |
COOLING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | July | 75.00 | 365 | 75.00 | 365 |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 16:47:20
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 112.828 | 2.477 | 421.978 | 13.570 | 14.289 |
February | 140.475 | 3.936 | 299.972 | 11.632 | 14.769 |
March | 206.881 | 6.215 | 222.126 | 11.695 | 21.878 |
April | 406.844 | 15.682 | 44.349 | 16.898 | 23.142 |
May | 584.192 | 25.837 | 1.592 | 25.920 | 26.755 |
June | 674.706 | 36.230 | 0.000 | 36.230 | 36.230 |
July | 703.772 | 40.765 | 0.000 | 40.765 | 40.765 |
August | 690.411 | 35.926 | 0.000 | 35.926 | 35.926 |
September | 611.017 | 29.890 | 1.808 | 29.945 | 30.554 |
October | 415.177 | 17.565 | 39.793 | 18.389 | 21.741 |
November | 197.186 | 6.459 | 287.761 | 13.077 | 16.462 |
December | 96.300 | 1.949 | 445.209 | 14.377 | 14.827 |
Annual Sum or Average | 4839.789 | 222.932 | 1764.588 | 268.424 | 297.338 |
Minimum of Months | 96.300 | 1.949 | 0.000 | 11.632 | 14.289 |
Maximum of Months | 703.772 | 40.765 | 445.209 | 40.765 | 40.765 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 93.389 | 1.246 | 371.786 | 6.425 | 7.233 |
February | 124.111 | 2.329 | 251.783 | 5.865 | 7.385 |
March | 175.750 | 3.135 | 212.379 | 5.845 | 8.838 |
April | 394.819 | 9.726 | 44.996 | 10.229 | 12.521 |
May | 589.861 | 17.106 | 0.514 | 17.127 | 17.568 |
June | 659.684 | 25.208 | 0.000 | 25.208 | 25.208 |
July | 693.431 | 29.630 | 0.000 | 29.630 | 29.630 |
August | 683.214 | 26.402 | 0.000 | 26.402 | 26.402 |
September | 622.775 | 22.010 | 1.014 | 22.049 | 22.063 |
October | 422.533 | 12.685 | 26.178 | 13.070 | 13.297 |
November | 201.269 | 4.342 | 243.775 | 7.409 | 8.268 |
December | 91.633 | 0.960 | 382.016 | 6.738 | 7.797 |
Annual Sum or Average | 4752.469 | 154.779 | 1534.441 | 175.997 | 186.210 |
Minimum of Months | 91.633 | 0.960 | 0.000 | 5.845 | 7.233 |
Maximum of Months | 693.431 | 29.630 | 382.016 | 29.630 | 29.630 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 93.844 | 1.217 | 348.327 | 11.770 | 18.194 |
February | 139.216 | 2.977 | 226.788 | 9.694 | 17.422 |
March | 208.185 | 4.718 | 175.710 | 9.433 | 17.749 |
April | 456.345 | 14.110 | 31.517 | 14.832 | 17.147 |
May | 636.097 | 24.070 | 0.319 | 24.086 | 24.415 |
June | 701.653 | 34.220 | 0.000 | 34.220 | 34.220 |
July | 722.028 | 38.576 | 0.000 | 38.576 | 38.576 |
August | 713.536 | 33.982 | 0.000 | 33.982 | 33.982 |
September | 632.536 | 27.914 | 0.436 | 27.919 | 28.436 |
October | 430.536 | 15.306 | 21.514 | 15.677 | 20.206 |
November | 202.199 | 5.050 | 226.033 | 11.195 | 18.214 |
December | 78.005 | 0.903 | 361.703 | 12.817 | 20.024 |
Annual Sum or Average | 5014.180 | 203.042 | 1392.347 | 244.200 | 288.584 |
Minimum of Months | 78.005 | 0.903 | 0.000 | 9.433 | 17.147 |
Maximum of Months | 722.028 | 38.576 | 361.703 | 38.576 | 38.576 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 3.444 | 0.021 | 422.791 | 14.966 | 42.181 |
February | 52.000 | 0.838 | 316.067 | 11.288 | 30.586 |
March | 133.472 | 2.784 | 256.554 | 9.964 | 25.699 |
April | 379.772 | 12.834 | 54.828 | 14.353 | 20.181 |
May | 580.517 | 25.071 | 3.400 | 25.194 | 25.651 |
June | 675.267 | 36.369 | 0.000 | 36.369 | 36.369 |
July | 704.442 | 40.451 | 0.000 | 40.451 | 40.451 |
August | 685.114 | 33.807 | 0.000 | 33.807 | 33.807 |
September | 587.400 | 24.722 | 4.044 | 24.843 | 25.233 |
October | 339.032 | 10.898 | 62.337 | 12.398 | 15.784 |
November | 78.389 | 1.254 | 311.384 | 10.557 | 25.404 |
December | 0.000 | 0.000 | 445.458 | 17.169 | 46.135 |
Annual Sum or Average | 4218.849 | 189.048 | 1876.862 | 251.359 | 367.481 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 9.964 | 15.784 |
Maximum of Months | 704.442 | 40.451 | 445.458 | 40.451 | 46.135 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 574.968 | 8.942 | 13.661 |
February | 28.736 | 0.192 | 383.205 | 6.279 | 9.709 |
March | 79.889 | 0.635 | 287.644 | 4.764 | 8.891 |
April | 340.400 | 7.203 | 56.585 | 7.888 | 10.685 |
May | 585.842 | 16.442 | 0.389 | 16.457 | 16.844 |
June | 659.020 | 25.416 | 0.000 | 25.416 | 25.416 |
July | 690.708 | 29.383 | 0.000 | 29.383 | 29.383 |
August | 673.553 | 24.372 | 0.000 | 24.372 | 24.372 |
September | 588.017 | 16.956 | 0.794 | 16.994 | 17.150 |
October | 314.886 | 6.226 | 40.672 | 6.915 | 7.881 |
November | 29.694 | 0.247 | 367.730 | 5.464 | 9.180 |
December | 0.000 | 0.000 | 612.000 | 9.787 | 15.695 |
Annual Sum or Average | 3990.745 | 127.071 | 2323.987 | 162.660 | 188.865 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 4.764 | 7.881 |
Maximum of Months | 690.708 | 29.383 | 612.000 | 29.383 | 29.383 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.000 | 0.000 | 592.497 | 15.964 | 19.744 |
February | 40.686 | 0.374 | 354.792 | 10.075 | 17.584 |
March | 120.964 | 1.500 | 229.089 | 7.424 | 16.119 |
April | 417.820 | 11.232 | 33.825 | 12.007 | 14.627 |
May | 633.894 | 23.237 | 0.375 | 23.254 | 23.530 |
June | 702.803 | 34.143 | 0.000 | 34.143 | 34.143 |
July | 721.444 | 38.033 | 0.000 | 38.033 | 38.033 |
August | 711.678 | 31.846 | 0.000 | 31.846 | 31.846 |
September | 613.328 | 22.965 | 0.517 | 22.987 | 23.439 |
October | 358.978 | 8.751 | 28.797 | 9.306 | 14.904 |
November | 50.944 | 0.554 | 332.293 | 8.988 | 18.537 |
December | 0.000 | 0.000 | 639.342 | 17.863 | 21.058 |
Annual Sum or Average | 4372.540 | 172.635 | 2211.527 | 231.889 | 273.566 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 7.424 | 14.627 |
Maximum of Months | 721.444 | 38.033 | 639.342 | 38.033 | 38.033 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 135.606 | 2.900 | 373.011 | 12.677 | 13.114 |
February | 164.625 | 4.542 | 241.804 | 11.070 | 12.860 |
March | 250.139 | 7.226 | 170.870 | 11.625 | 18.912 |
April | 464.306 | 18.037 | 30.153 | 18.828 | 22.475 |
May | 641.092 | 29.383 | 0.367 | 29.416 | 29.757 |
June | 685.689 | 40.002 | 0.000 | 40.002 | 40.002 |
July | 710.675 | 44.682 | 0.000 | 44.682 | 44.682 |
August | 704.496 | 40.050 | 0.000 | 40.050 | 40.050 |
September | 643.777 | 33.739 | 0.275 | 33.764 | 33.909 |
October | 476.617 | 20.269 | 22.469 | 20.841 | 21.536 |
November | 234.625 | 7.491 | 236.878 | 12.937 | 15.922 |
December | 118.635 | 2.274 | 387.281 | 13.440 | 13.644 |
Annual Sum or Average | 5230.280 | 250.596 | 1463.108 | 289.332 | 306.864 |
Minimum of Months | 118.635 | 2.274 | 0.000 | 11.070 | 12.860 |
Maximum of Months | 710.675 | 44.682 | 387.281 | 44.682 | 44.682 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 133.932 | 1.844 | 292.496 | 5.401 | 6.162 |
February | 157.964 | 3.120 | 183.613 | 5.500 | 6.356 |
March | 225.261 | 4.247 | 132.184 | 6.006 | 7.863 |
April | 473.522 | 12.386 | 21.043 | 12.683 | 13.493 |
May | 639.008 | 20.765 | 0.000 | 20.765 | 20.883 |
June | 674.880 | 28.934 | 0.000 | 28.934 | 28.934 |
July | 702.200 | 33.621 | 0.000 | 33.621 | 33.621 |
August | 694.610 | 30.459 | 0.000 | 30.459 | 30.459 |
September | 654.033 | 26.034 | 0.164 | 26.039 | 26.043 |
October | 521.278 | 15.894 | 4.714 | 16.057 | 16.178 |
November | 250.873 | 5.670 | 175.179 | 7.697 | 8.318 |
December | 117.998 | 1.453 | 313.505 | 5.610 | 6.574 |
Annual Sum or Average | 5245.560 | 184.427 | 1122.898 | 198.774 | 204.885 |
Minimum of Months | 117.998 | 1.453 | 0.000 | 5.401 | 6.162 |
Maximum of Months | 702.200 | 33.621 | 313.505 | 33.621 | 33.621 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 116.870 | 1.689 | 269.041 | 9.098 | 19.788 |
February | 169.154 | 3.732 | 159.053 | 8.332 | 16.541 |
March | 250.121 | 5.936 | 108.141 | 8.873 | 17.463 |
April | 507.091 | 16.914 | 12.500 | 17.203 | 19.441 |
May | 685.583 | 27.796 | 0.000 | 27.796 | 27.855 |
June | 708.947 | 37.963 | 0.000 | 37.963 | 37.963 |
July | 726.583 | 42.391 | 0.000 | 42.391 | 42.391 |
August | 717.828 | 38.010 | 0.000 | 38.010 | 38.010 |
September | 670.057 | 31.729 | 0.117 | 31.733 | 31.729 |
October | 496.503 | 18.046 | 2.789 | 18.127 | 21.565 |
November | 241.119 | 6.193 | 161.947 | 10.218 | 19.448 |
December | 100.634 | 1.286 | 293.384 | 9.860 | 20.052 |
Annual Sum or Average | 5390.490 | 231.685 | 1006.971 | 259.604 | 312.245 |
Minimum of Months | 100.634 | 1.286 | 0.000 | 8.332 | 16.541 |
Maximum of Months | 726.583 | 42.391 | 293.384 | 42.391 | 42.391 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 4.806 | 0.030 | 380.976 | 11.598 | 38.473 |
February | 64.111 | 1.046 | 251.291 | 8.537 | 29.102 |
March | 165.792 | 3.466 | 191.416 | 8.464 | 22.809 |
April | 432.317 | 15.086 | 35.940 | 15.954 | 19.619 |
May | 636.947 | 28.625 | 0.500 | 28.658 | 28.834 |
June | 687.108 | 40.151 | 0.000 | 40.151 | 40.151 |
July | 713.047 | 44.389 | 0.000 | 44.389 | 44.389 |
August | 703.573 | 37.982 | 0.000 | 37.982 | 37.982 |
September | 626.956 | 28.623 | 0.075 | 28.630 | 28.932 |
October | 405.563 | 13.236 | 26.969 | 13.868 | 16.574 |
November | 105.181 | 1.651 | 263.270 | 8.448 | 22.151 |
December | 0.250 | 0.002 | 406.437 | 13.318 | 42.713 |
Annual Sum or Average | 4545.651 | 214.287 | 1556.875 | 259.997 | 371.729 |
Minimum of Months | 0.250 | 0.002 | 0.000 | 8.448 | 16.574 |
Maximum of Months | 713.047 | 44.389 | 406.437 | 44.389 | 44.389 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 0.444 | 0.001 | 501.567 | 6.863 | 10.582 |
February | 41.403 | 0.367 | 307.222 | 4.781 | 8.378 |
March | 123.569 | 1.227 | 199.645 | 3.921 | 8.186 |
April | 427.211 | 9.609 | 28.571 | 9.944 | 11.408 |
May | 635.011 | 20.139 | 0.000 | 20.139 | 20.288 |
June | 674.395 | 29.139 | 0.000 | 29.139 | 29.139 |
July | 702.972 | 33.386 | 0.000 | 33.386 | 33.386 |
August | 686.423 | 28.457 | 0.000 | 28.457 | 28.457 |
September | 623.692 | 20.951 | 0.339 | 20.962 | 20.966 |
October | 422.381 | 8.783 | 12.783 | 9.097 | 9.392 |
November | 65.417 | 0.591 | 282.756 | 4.242 | 7.566 |
December | 0.000 | 0.000 | 544.314 | 7.541 | 13.300 |
Annual Sum or Average | 4402.919 | 152.650 | 1877.198 | 178.471 | 201.048 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 3.921 | 7.566 |
Maximum of Months | 702.972 | 33.386 | 544.314 | 33.386 | 33.386 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 1.278 | 0.003 | 489.575 | 12.452 | 19.161 |
February | 56.583 | 0.653 | 271.359 | 7.683 | 16.058 |
March | 164.956 | 2.373 | 159.386 | 6.197 | 15.587 |
April | 489.483 | 14.499 | 16.025 | 14.863 | 17.030 |
May | 679.450 | 27.910 | 0.000 | 27.910 | 27.910 |
June | 709.917 | 39.166 | 0.000 | 39.166 | 39.166 |
July | 727.083 | 43.196 | 0.000 | 43.196 | 43.196 |
August | 721.453 | 37.046 | 0.000 | 37.046 | 37.046 |
September | 658.825 | 27.727 | 0.164 | 27.735 | 27.772 |
October | 415.688 | 11.550 | 8.894 | 11.934 | 14.376 |
November | 76.083 | 0.960 | 250.696 | 6.979 | 17.149 |
December | 0.000 | 0.000 | 555.252 | 14.345 | 19.291 |
Annual Sum or Average | 4700.800 | 205.084 | 1751.351 | 249.507 | 293.744 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 6.197 | 14.376 |
Maximum of Months | 727.083 | 43.196 | 555.252 | 43.196 | 43.196 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 89.958 | 1.774 | 414.578 | 16.142 | 19.245 |
February | 135.194 | 3.571 | 270.841 | 13.137 | 19.877 |
March | 207.972 | 6.182 | 195.613 | 12.368 | 26.152 |
April | 442.433 | 18.618 | 38.991 | 19.858 | 25.298 |
May | 630.892 | 31.828 | 0.828 | 31.881 | 32.293 |
June | 690.539 | 44.973 | 0.000 | 44.973 | 44.973 |
July | 716.972 | 50.004 | 0.000 | 50.004 | 50.004 |
August | 706.223 | 44.086 | 0.000 | 44.086 | 44.086 |
September | 641.127 | 35.900 | 0.239 | 35.919 | 36.350 |
October | 447.223 | 20.116 | 25.694 | 20.907 | 23.692 |
November | 203.083 | 6.301 | 268.293 | 14.707 | 20.393 |
December | 76.347 | 1.163 | 438.944 | 17.545 | 20.551 |
Annual Sum or Average | 4987.965 | 264.516 | 1654.022 | 321.528 | 362.914 |
Minimum of Months | 76.347 | 1.163 | 0.000 | 12.368 | 19.245 |
Maximum of Months | 716.972 | 50.004 | 438.944 | 50.004 | 50.004 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 73.944 | 0.853 | 376.392 | 6.938 | 8.342 |
February | 118.139 | 2.356 | 251.454 | 6.450 | 7.714 |
March | 185.528 | 3.534 | 201.900 | 6.652 | 8.403 |
April | 447.925 | 13.128 | 40.300 | 13.724 | 14.498 |
May | 635.911 | 23.446 | 0.292 | 23.457 | 23.613 |
June | 682.486 | 34.191 | 0.000 | 34.191 | 34.191 |
July | 708.972 | 39.274 | 0.000 | 39.274 | 39.274 |
August | 700.200 | 34.849 | 0.000 | 34.849 | 34.849 |
September | 646.567 | 28.518 | 0.517 | 28.536 | 28.536 |
October | 477.190 | 15.790 | 17.600 | 16.086 | 16.420 |
November | 202.327 | 4.420 | 239.261 | 7.851 | 9.595 |
December | 59.347 | 0.494 | 400.002 | 7.482 | 8.696 |
Annual Sum or Average | 4938.537 | 200.854 | 1527.718 | 225.492 | 234.132 |
Minimum of Months | 59.347 | 0.494 | 0.000 | 6.450 | 7.714 |
Maximum of Months | 708.972 | 39.274 | 400.002 | 39.274 | 39.274 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 64.544 | 0.789 | 361.214 | 11.847 | 20.101 |
February | 127.108 | 2.886 | 227.613 | 9.782 | 17.800 |
March | 208.559 | 5.061 | 165.144 | 9.875 | 17.145 |
April | 486.706 | 17.834 | 24.761 | 18.503 | 21.083 |
May | 677.756 | 31.050 | 0.000 | 31.050 | 31.056 |
June | 710.856 | 44.073 | 0.000 | 44.073 | 44.073 |
July | 729.333 | 48.942 | 0.000 | 48.942 | 48.942 |
August | 724.931 | 43.167 | 0.000 | 43.167 | 43.167 |
September | 663.689 | 34.901 | 0.122 | 34.906 | 35.067 |
October | 457.197 | 18.391 | 16.172 | 18.901 | 21.763 |
November | 199.600 | 5.035 | 220.631 | 11.104 | 19.813 |
December | 49.504 | 0.441 | 379.963 | 12.737 | 24.896 |
Annual Sum or Average | 5099.782 | 252.569 | 1395.619 | 294.887 | 344.907 |
Minimum of Months | 49.504 | 0.441 | 0.000 | 9.782 | 17.145 |
Maximum of Months | 729.333 | 48.942 | 379.963 | 48.942 | 48.942 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 3.889 | 0.033 | 428.036 | 16.214 | 43.424 |
February | 62.000 | 1.128 | 295.788 | 11.833 | 32.325 |
March | 155.611 | 3.770 | 220.828 | 10.690 | 27.026 |
April | 424.547 | 16.935 | 48.441 | 18.309 | 24.030 |
May | 631.289 | 31.535 | 0.739 | 31.580 | 31.898 |
June | 692.058 | 45.297 | 0.000 | 45.297 | 45.297 |
July | 718.117 | 50.110 | 0.000 | 50.110 | 50.110 |
August | 705.629 | 43.067 | 0.000 | 43.067 | 43.067 |
September | 629.585 | 32.826 | 1.583 | 32.865 | 33.328 |
October | 390.872 | 14.927 | 41.606 | 15.941 | 19.853 |
November | 100.000 | 1.828 | 297.870 | 10.948 | 27.274 |
December | 0.000 | 0.000 | 479.595 | 19.026 | 44.671 |
Annual Sum or Average | 4513.597 | 241.457 | 1814.486 | 305.880 | 422.303 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 10.690 | 19.853 |
Maximum of Months | 718.117 | 50.110 | 479.595 | 50.110 | 50.110 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 1.167 | 0.003 | 558.725 | 9.947 | 14.133 |
February | 41.139 | 0.480 | 363.016 | 6.918 | 10.400 |
March | 118.069 | 1.522 | 256.632 | 5.606 | 10.123 |
April | 411.836 | 11.376 | 43.190 | 11.970 | 14.036 |
May | 634.575 | 23.106 | 0.292 | 23.117 | 23.261 |
June | 682.936 | 34.413 | 0.000 | 34.413 | 34.413 |
July | 709.353 | 39.259 | 0.000 | 39.259 | 39.259 |
August | 695.667 | 33.717 | 0.000 | 33.717 | 33.717 |
September | 625.661 | 25.317 | 0.667 | 25.347 | 25.374 |
October | 393.048 | 10.441 | 27.258 | 10.965 | 11.368 |
November | 60.194 | 0.669 | 347.284 | 6.189 | 9.181 |
December | 0.000 | 0.000 | 600.803 | 11.038 | 17.026 |
Annual Sum or Average | 4373.645 | 180.302 | 2197.867 | 218.485 | 242.293 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 5.606 | 9.181 |
Maximum of Months | 709.353 | 39.259 | 600.803 | 39.259 | 39.259 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
January | 1.222 | 0.004 | 568.128 | 16.396 | 22.107 |
February | 53.611 | 0.728 | 340.995 | 10.369 | 18.685 |
March | 146.083 | 2.550 | 209.505 | 8.256 | 16.589 |
April | 469.233 | 16.158 | 27.239 | 16.852 | 18.924 |
May | 675.589 | 30.998 | 0.000 | 30.998 | 31.002 |
June | 712.344 | 44.689 | 0.000 | 44.689 | 44.689 |
July | 730.500 | 49.359 | 0.000 | 49.359 | 49.359 |
August | 724.778 | 42.495 | 0.000 | 42.495 | 42.495 |
September | 658.383 | 32.156 | 0.219 | 32.165 | 32.309 |
October | 403.300 | 13.147 | 21.228 | 13.773 | 17.296 |
November | 73.944 | 1.043 | 319.514 | 9.871 | 16.986 |
December | 0.000 | 0.000 | 628.904 | 18.845 | 22.162 |
Annual Sum or Average | 4648.989 | 233.327 | 2115.731 | 294.068 | 332.603 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 8.256 | 16.589 |
Maximum of Months | 730.500 | 49.359 | 628.904 | 49.359 | 49.359 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1401.40 | 0.00 | 0.00 |
February | 1077.04 | 0.00 | 0.00 |
March | 665.80 | 0.00 | 0.00 |
April | 135.99 | 0.00 | 0.00 |
May | 7.69 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 3.23 | 0.00 | 0.00 |
October | 71.79 | 0.00 | 0.00 |
November | 838.84 | 0.00 | 0.00 |
December | 1637.71 | 0.00 | 0.00 |
Annual Sum or Average | 484.42 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1637.71 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 983.23 | 0.00 | 0.00 |
February | 748.86 | 0.00 | 0.00 |
March | 491.37 | 0.00 | 0.00 |
April | 87.91 | 0.00 | 0.00 |
May | 2.94 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 5.59 | 0.00 | 0.00 |
October | 57.12 | 0.00 | 0.00 |
November | 587.02 | 0.00 | 0.00 |
December | 1148.14 | 0.00 | 0.00 |
Annual Sum or Average | 341.24 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1148.14 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1266.16 | 0.00 | 0.00 |
February | 902.08 | 0.00 | 0.00 |
March | 554.85 | 0.00 | 0.00 |
April | 83.03 | 0.00 | 0.00 |
May | 1.55 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.31 | 0.00 | 0.00 |
October | 38.27 | 0.00 | 0.00 |
November | 746.38 | 0.00 | 0.00 |
December | 1494.60 | 0.00 | 0.00 |
Annual Sum or Average | 422.38 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1494.60 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1699.83 | 0.00 | 0.00 |
February | 1291.92 | 0.00 | 0.00 |
March | 772.61 | 0.00 | 0.00 |
April | 151.73 | 0.00 | 0.00 |
May | 10.48 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 10.56 | 0.00 | 0.00 |
October | 124.09 | 0.00 | 0.00 |
November | 1047.95 | 0.00 | 0.00 |
December | 2026.95 | 0.00 | 0.00 |
Annual Sum or Average | 592.15 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2026.95 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1593.83 | 0.00 | 0.00 |
February | 1196.48 | 0.00 | 0.00 |
March | 707.54 | 0.00 | 0.00 |
April | 114.76 | 0.00 | 0.00 |
May | 2.18 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 5.23 | 0.00 | 0.00 |
October | 97.59 | 0.00 | 0.00 |
November | 935.66 | 0.00 | 0.00 |
December | 1837.09 | 0.00 | 0.00 |
Annual Sum or Average | 538.51 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1837.09 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1903.54 | 0.00 | 0.00 |
February | 1294.97 | 0.00 | 0.00 |
March | 705.82 | 0.00 | 0.00 |
April | 92.06 | 0.00 | 0.00 |
May | 1.63 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 2.26 | 0.00 | 0.00 |
October | 58.24 | 0.00 | 0.00 |
November | 1033.29 | 0.00 | 0.00 |
December | 2215.63 | 0.00 | 0.00 |
Annual Sum or Average | 606.90 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2215.63 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1060.38 | 0.00 | 0.00 |
February | 788.89 | 0.00 | 0.00 |
March | 460.14 | 0.00 | 0.00 |
April | 72.80 | 0.00 | 0.00 |
May | 2.86 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 2.14 | 0.00 | 0.00 |
October | 52.44 | 0.00 | 0.00 |
November | 596.23 | 0.00 | 0.00 |
December | 1265.46 | 0.00 | 0.00 |
Annual Sum or Average | 357.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1265.46 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 666.50 | 0.00 | 0.00 |
February | 499.36 | 0.00 | 0.00 |
March | 309.36 | 0.00 | 0.00 |
April | 50.16 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.76 | 0.00 | 0.00 |
October | 24.71 | 0.00 | 0.00 |
November | 382.40 | 0.00 | 0.00 |
December | 818.53 | 0.00 | 0.00 |
Annual Sum or Average | 228.42 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 818.53 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 904.15 | 0.00 | 0.00 |
February | 629.48 | 0.00 | 0.00 |
March | 352.87 | 0.00 | 0.00 |
April | 33.64 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.22 | 0.00 | 0.00 |
October | 3.87 | 0.00 | 0.00 |
November | 497.36 | 0.00 | 0.00 |
December | 1098.25 | 0.00 | 0.00 |
Annual Sum or Average | 292.32 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1098.25 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1324.28 | 0.00 | 0.00 |
February | 947.75 | 0.00 | 0.00 |
March | 550.47 | 0.00 | 0.00 |
April | 89.08 | 0.00 | 0.00 |
May | 3.02 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.43 | 0.00 | 0.00 |
October | 58.92 | 0.00 | 0.00 |
November | 776.68 | 0.00 | 0.00 |
December | 1596.80 | 0.00 | 0.00 |
Annual Sum or Average | 444.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1596.80 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1207.44 | 0.00 | 0.00 |
February | 862.49 | 0.00 | 0.00 |
March | 454.44 | 0.00 | 0.00 |
April | 53.55 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 1.59 | 0.00 | 0.00 |
October | 45.73 | 0.00 | 0.00 |
November | 649.18 | 0.00 | 0.00 |
December | 1406.40 | 0.00 | 0.00 |
Annual Sum or Average | 388.53 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1406.40 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1491.56 | 0.00 | 0.00 |
February | 952.53 | 0.00 | 0.00 |
March | 462.97 | 0.00 | 0.00 |
April | 43.87 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.70 | 0.00 | 0.00 |
October | 40.60 | 0.00 | 0.00 |
November | 743.55 | 0.00 | 0.00 |
December | 1788.54 | 0.00 | 0.00 |
Annual Sum or Average | 459.20 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1788.54 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1490.75 | 0.00 | 0.00 |
February | 1098.91 | 0.00 | 0.00 |
March | 625.50 | 0.00 | 0.00 |
April | 113.07 | 0.00 | 0.00 |
May | 4.22 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 1.41 | 0.00 | 0.00 |
October | 68.74 | 0.00 | 0.00 |
November | 879.98 | 0.00 | 0.00 |
December | 1772.60 | 0.00 | 0.00 |
Annual Sum or Average | 502.52 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1772.60 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1080.74 | 0.00 | 0.00 |
February | 809.14 | 0.00 | 0.00 |
March | 525.79 | 0.00 | 0.00 |
April | 96.94 | 0.00 | 0.00 |
May | 1.61 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 2.61 | 0.00 | 0.00 |
October | 43.96 | 0.00 | 0.00 |
November | 617.72 | 0.00 | 0.00 |
December | 1301.13 | 0.00 | 0.00 |
Annual Sum or Average | 371.85 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1301.13 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1385.18 | 0.00 | 0.00 |
February | 967.88 | 0.00 | 0.00 |
March | 588.61 | 0.00 | 0.00 |
April | 80.67 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.57 | 0.00 | 0.00 |
October | 54.43 | 0.00 | 0.00 |
November | 774.57 | 0.00 | 0.00 |
December | 1619.56 | 0.00 | 0.00 |
Annual Sum or Average | 454.40 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1619.56 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1835.48 | 0.00 | 0.00 |
February | 1335.06 | 0.00 | 0.00 |
March | 757.12 | 0.00 | 0.00 |
April | 133.45 | 0.00 | 0.00 |
May | 3.80 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 3.41 | 0.00 | 0.00 |
October | 94.07 | 0.00 | 0.00 |
November | 1036.79 | 0.00 | 0.00 |
December | 2233.70 | 0.00 | 0.00 |
Annual Sum or Average | 617.10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2233.70 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1678.15 | 0.00 | 0.00 |
February | 1210.14 | 0.00 | 0.00 |
March | 669.76 | 0.00 | 0.00 |
April | 97.74 | 0.00 | 0.00 |
May | 1.52 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 3.36 | 0.00 | 0.00 |
October | 74.63 | 0.00 | 0.00 |
November | 948.41 | 0.00 | 0.00 |
December | 1963.24 | 0.00 | 0.00 |
Annual Sum or Average | 551.72 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1963.24 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
January | 1984.75 | 0.00 | 0.00 |
February | 1313.05 | 0.00 | 0.00 |
March | 691.16 | 0.00 | 0.00 |
April | 83.90 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 1.03 | 0.00 | 0.00 |
October | 66.03 | 0.00 | 0.00 |
November | 1092.01 | 0.00 | 0.00 |
December | 2370.12 | 0.00 | 0.00 |
Annual Sum or Average | 631.64 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2370.12 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.14 |
May | 0.00 | 0.00 | 0.22 |
June | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.27 |
October | 0.00 | 0.00 | 0.15 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.16 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.35 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.09 |
May | 0.00 | 0.00 | 0.15 |
June | 0.00 | 0.00 | 0.23 |
July | 0.00 | 0.00 | 0.27 |
August | 0.00 | 0.00 | 0.24 |
September | 0.00 | 0.00 | 0.21 |
October | 0.00 | 0.00 | 0.12 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.27 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.13 |
May | 0.00 | 0.00 | 0.22 |
June | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.00 | 0.27 |
October | 0.00 | 0.00 | 0.14 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.16 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.11 |
May | 0.00 | 0.00 | 0.21 |
June | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.00 | 0.29 |
September | 0.00 | 0.00 | 0.22 |
October | 0.00 | 0.00 | 0.09 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.35 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.14 |
June | 0.00 | 0.00 | 0.23 |
July | 0.00 | 0.00 | 0.27 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.16 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.27 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.10 |
May | 0.00 | 0.00 | 0.21 |
June | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.22 |
October | 0.00 | 0.00 | 0.08 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.36 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.03 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.25 |
June | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.00 | 0.31 |
October | 0.00 | 0.00 | 0.18 |
November | 0.00 | 0.00 | 0.07 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.11 |
May | 0.00 | 0.00 | 0.18 |
June | 0.00 | 0.00 | 0.26 |
July | 0.00 | 0.00 | 0.30 |
August | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.00 | 0.25 |
October | 0.00 | 0.00 | 0.14 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.30 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.25 |
June | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.00 | 0.31 |
October | 0.00 | 0.00 | 0.17 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.40 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.13 |
May | 0.00 | 0.00 | 0.24 |
June | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.00 | 0.26 |
October | 0.00 | 0.00 | 0.11 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.09 |
May | 0.00 | 0.00 | 0.18 |
June | 0.00 | 0.00 | 0.26 |
July | 0.00 | 0.00 | 0.30 |
August | 0.00 | 0.00 | 0.25 |
September | 0.00 | 0.00 | 0.20 |
October | 0.00 | 0.00 | 0.08 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.30 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.13 |
May | 0.00 | 0.00 | 0.25 |
June | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.00 | 0.26 |
October | 0.00 | 0.00 | 0.10 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.17 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.43 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.11 |
May | 0.00 | 0.00 | 0.20 |
June | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.26 |
October | 0.00 | 0.00 | 0.14 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.35 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.16 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.44 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.15 |
May | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.00 | 0.43 |
August | 0.00 | 0.00 | 0.37 |
September | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.13 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.43 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.10 |
May | 0.00 | 0.00 | 0.20 |
June | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.23 |
October | 0.00 | 0.00 | 0.09 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.35 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.14 |
May | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.00 | 0.37 |
September | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.11 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.44 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportHEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 120.03 | 67.34 |
February | 0.00 | 0.00 | 122.01 | 61.08 |
March | 0.00 | 0.00 | 116.16 | 64.25 |
April | 0.00 | 0.00 | 104.58 | 57.30 |
May | 0.00 | 0.00 | 89.44 | 52.95 |
June | 0.00 | 0.00 | 77.95 | 45.91 |
July | 0.00 | 0.00 | 69.18 | 44.63 |
August | 0.00 | 0.00 | 70.69 | 44.87 |
September | 0.00 | 0.00 | 75.10 | 45.92 |
October | 0.00 | 0.00 | 86.90 | 53.22 |
November | 0.00 | 0.00 | 104.24 | 57.24 |
December | 0.00 | 0.00 | 117.40 | 64.81 |
Annual Sum or Average | 0.00 | 0.00 | 95.99 | 659.51 |
Minimum of Months | 0.00 | 0.00 | 69.18 | 44.63 |
Maximum of Months | 0.00 | 0.00 | 122.01 | 67.34 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 120.31 | 67.52 |
February | 0.00 | 0.00 | 121.52 | 60.90 |
March | 0.00 | 0.00 | 116.34 | 64.37 |
April | 0.00 | 0.00 | 104.35 | 57.26 |
May | 0.00 | 0.00 | 89.22 | 52.84 |
June | 0.00 | 0.00 | 77.77 | 45.84 |
July | 0.00 | 0.00 | 69.45 | 44.93 |
August | 0.00 | 0.00 | 69.96 | 44.46 |
September | 0.00 | 0.00 | 75.16 | 46.01 |
October | 0.00 | 0.00 | 86.71 | 53.20 |
November | 0.00 | 0.00 | 104.09 | 57.25 |
December | 0.00 | 0.00 | 117.12 | 64.71 |
Annual Sum or Average | 0.00 | 0.00 | 95.85 | 659.29 |
Minimum of Months | 0.00 | 0.00 | 69.45 | 44.46 |
Maximum of Months | 0.00 | 0.00 | 121.52 | 67.52 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 120.55 | 67.52 |
February | 0.00 | 0.00 | 121.65 | 60.87 |
March | 0.00 | 0.00 | 116.04 | 64.22 |
April | 0.00 | 0.00 | 104.59 | 57.43 |
May | 0.00 | 0.00 | 89.22 | 52.80 |
June | 0.00 | 0.00 | 78.32 | 45.91 |
July | 0.00 | 0.00 | 69.83 | 44.67 |
August | 0.00 | 0.00 | 70.68 | 44.54 |
September | 0.00 | 0.00 | 76.10 | 46.22 |
October | 0.00 | 0.00 | 86.78 | 53.09 |
November | 0.00 | 0.00 | 104.36 | 57.31 |
December | 0.00 | 0.00 | 117.06 | 64.56 |
Annual Sum or Average | 0.00 | 0.00 | 96.12 | 659.14 |
Minimum of Months | 0.00 | 0.00 | 69.83 | 44.54 |
Maximum of Months | 0.00 | 0.00 | 121.65 | 67.52 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 121.68 | 67.72 |
February | 0.00 | 0.00 | 122.68 | 61.02 |
March | 0.00 | 0.00 | 116.81 | 64.31 |
April | 0.00 | 0.00 | 104.73 | 57.31 |
May | 0.00 | 0.00 | 89.44 | 52.95 |
June | 0.00 | 0.00 | 77.95 | 45.91 |
July | 0.00 | 0.00 | 69.19 | 44.62 |
August | 0.00 | 0.00 | 70.63 | 44.87 |
September | 0.00 | 0.00 | 74.87 | 45.89 |
October | 0.00 | 0.00 | 86.99 | 53.31 |
November | 0.00 | 0.00 | 105.07 | 57.36 |
December | 0.00 | 0.00 | 118.59 | 64.92 |
Annual Sum or Average | 0.00 | 0.00 | 96.40 | 660.17 |
Minimum of Months | 0.00 | 0.00 | 69.19 | 44.62 |
Maximum of Months | 0.00 | 0.00 | 122.68 | 67.72 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 120.74 | 67.48 |
February | 0.00 | 0.00 | 122.66 | 61.18 |
March | 0.00 | 0.00 | 116.87 | 64.44 |
April | 0.00 | 0.00 | 104.69 | 57.35 |
May | 0.00 | 0.00 | 89.24 | 52.85 |
June | 0.00 | 0.00 | 77.79 | 45.84 |
July | 0.00 | 0.00 | 69.46 | 44.93 |
August | 0.00 | 0.00 | 69.88 | 44.46 |
September | 0.00 | 0.00 | 75.08 | 46.07 |
October | 0.00 | 0.00 | 86.75 | 53.23 |
November | 0.00 | 0.00 | 104.82 | 57.35 |
December | 0.00 | 0.00 | 118.17 | 64.97 |
Annual Sum or Average | 0.00 | 0.00 | 96.19 | 660.14 |
Minimum of Months | 0.00 | 0.00 | 69.46 | 44.46 |
Maximum of Months | 0.00 | 0.00 | 122.66 | 67.48 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 120.99 | 67.59 |
February | 0.00 | 0.00 | 122.65 | 61.10 |
March | 0.00 | 0.00 | 116.60 | 64.25 |
April | 0.00 | 0.00 | 104.70 | 57.43 |
May | 0.00 | 0.00 | 89.23 | 52.80 |
June | 0.00 | 0.00 | 78.34 | 45.91 |
July | 0.00 | 0.00 | 69.78 | 44.63 |
August | 0.00 | 0.00 | 70.64 | 44.57 |
September | 0.00 | 0.00 | 75.89 | 46.22 |
October | 0.00 | 0.00 | 86.64 | 53.05 |
November | 0.00 | 0.00 | 105.13 | 57.45 |
December | 0.00 | 0.00 | 117.87 | 64.79 |
Annual Sum or Average | 0.00 | 0.00 | 96.38 | 659.80 |
Minimum of Months | 0.00 | 0.00 | 69.78 | 44.57 |
Maximum of Months | 0.00 | 0.00 | 122.65 | 67.59 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 118.97 | 67.25 |
February | 0.00 | 0.00 | 120.55 | 60.84 |
March | 0.00 | 0.00 | 115.45 | 64.41 |
April | 0.00 | 0.00 | 103.93 | 57.41 |
May | 0.00 | 0.00 | 88.80 | 52.82 |
June | 0.00 | 0.00 | 77.89 | 45.92 |
July | 0.00 | 0.00 | 69.65 | 44.67 |
August | 0.00 | 0.00 | 70.48 | 44.55 |
September | 0.00 | 0.00 | 75.79 | 46.20 |
October | 0.00 | 0.00 | 86.62 | 53.20 |
November | 0.00 | 0.00 | 103.18 | 57.05 |
December | 0.00 | 0.00 | 116.24 | 64.68 |
Annual Sum or Average | 0.00 | 0.00 | 95.48 | 658.99 |
Minimum of Months | 0.00 | 0.00 | 69.65 | 44.55 |
Maximum of Months | 0.00 | 0.00 | 120.55 | 67.25 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 118.81 | 67.24 |
February | 0.00 | 0.00 | 120.86 | 61.11 |
March | 0.00 | 0.00 | 114.45 | 64.00 |
April | 0.00 | 0.00 | 103.61 | 57.38 |
May | 0.00 | 0.00 | 88.91 | 52.95 |
June | 0.00 | 0.00 | 77.67 | 45.85 |
July | 0.00 | 0.00 | 69.33 | 44.61 |
August | 0.00 | 0.00 | 70.45 | 44.61 |
September | 0.00 | 0.00 | 75.72 | 46.20 |
October | 0.00 | 0.00 | 86.45 | 53.16 |
November | 0.00 | 0.00 | 102.85 | 57.01 |
December | 0.00 | 0.00 | 115.96 | 64.62 |
Annual Sum or Average | 0.00 | 0.00 | 95.27 | 658.75 |
Minimum of Months | 0.00 | 0.00 | 69.33 | 44.61 |
Maximum of Months | 0.00 | 0.00 | 120.86 | 67.24 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 119.23 | 67.28 |
February | 0.00 | 0.00 | 121.13 | 61.13 |
March | 0.00 | 0.00 | 114.98 | 64.22 |
April | 0.00 | 0.00 | 103.47 | 57.29 |
May | 0.00 | 0.00 | 88.81 | 52.76 |
June | 0.00 | 0.00 | 78.29 | 45.92 |
July | 0.00 | 0.00 | 70.27 | 44.69 |
August | 0.00 | 0.00 | 71.09 | 44.61 |
September | 0.00 | 0.00 | 76.30 | 46.19 |
October | 0.00 | 0.00 | 86.60 | 53.04 |
November | 0.00 | 0.00 | 103.31 | 57.12 |
December | 0.00 | 0.00 | 116.62 | 64.76 |
Annual Sum or Average | 0.00 | 0.00 | 95.69 | 658.99 |
Minimum of Months | 0.00 | 0.00 | 70.27 | 44.61 |
Maximum of Months | 0.00 | 0.00 | 121.13 | 67.28 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 120.31 | 67.46 |
February | 0.00 | 0.00 | 122.18 | 61.20 |
March | 0.00 | 0.00 | 115.91 | 64.41 |
April | 0.00 | 0.00 | 103.48 | 57.09 |
May | 0.00 | 0.00 | 89.16 | 53.01 |
June | 0.00 | 0.00 | 77.80 | 45.87 |
July | 0.00 | 0.00 | 69.66 | 44.67 |
August | 0.00 | 0.00 | 70.42 | 44.55 |
September | 0.00 | 0.00 | 75.69 | 46.23 |
October | 0.00 | 0.00 | 86.20 | 52.97 |
November | 0.00 | 0.00 | 104.60 | 57.50 |
December | 0.00 | 0.00 | 117.84 | 64.86 |
Annual Sum or Average | 0.00 | 0.00 | 95.95 | 659.83 |
Minimum of Months | 0.00 | 0.00 | 69.66 | 44.55 |
Maximum of Months | 0.00 | 0.00 | 122.18 | 67.46 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 119.67 | 67.41 |
February | 0.00 | 0.00 | 121.12 | 60.92 |
March | 0.00 | 0.00 | 115.67 | 64.40 |
April | 0.00 | 0.00 | 103.82 | 57.40 |
May | 0.00 | 0.00 | 88.74 | 52.87 |
June | 0.00 | 0.00 | 77.78 | 45.91 |
July | 0.00 | 0.00 | 69.33 | 44.61 |
August | 0.00 | 0.00 | 70.37 | 44.61 |
September | 0.00 | 0.00 | 75.49 | 46.20 |
October | 0.00 | 0.00 | 86.03 | 52.97 |
November | 0.00 | 0.00 | 104.19 | 57.42 |
December | 0.00 | 0.00 | 117.01 | 64.84 |
Annual Sum or Average | 0.00 | 0.00 | 95.62 | 659.57 |
Minimum of Months | 0.00 | 0.00 | 69.33 | 44.61 |
Maximum of Months | 0.00 | 0.00 | 121.12 | 67.41 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 119.90 | 67.44 |
February | 0.00 | 0.00 | 121.75 | 61.14 |
March | 0.00 | 0.00 | 115.78 | 64.40 |
April | 0.00 | 0.00 | 103.12 | 57.04 |
May | 0.00 | 0.00 | 89.06 | 52.99 |
June | 0.00 | 0.00 | 78.06 | 45.90 |
July | 0.00 | 0.00 | 70.03 | 44.69 |
August | 0.00 | 0.00 | 70.67 | 44.53 |
September | 0.00 | 0.00 | 75.87 | 46.18 |
October | 0.00 | 0.00 | 86.60 | 53.23 |
November | 0.00 | 0.00 | 103.95 | 57.15 |
December | 0.00 | 0.00 | 116.92 | 64.74 |
Annual Sum or Average | 0.00 | 0.00 | 95.83 | 659.42 |
Minimum of Months | 0.00 | 0.00 | 70.03 | 44.53 |
Maximum of Months | 0.00 | 0.00 | 121.75 | 67.44 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 120.33 | 67.46 |
February | 0.00 | 0.00 | 121.80 | 60.97 |
March | 0.00 | 0.00 | 116.64 | 64.43 |
April | 0.00 | 0.00 | 104.35 | 57.25 |
May | 0.00 | 0.00 | 89.23 | 52.83 |
June | 0.00 | 0.00 | 77.94 | 45.86 |
July | 0.00 | 0.00 | 69.58 | 44.67 |
August | 0.00 | 0.00 | 70.43 | 44.55 |
September | 0.00 | 0.00 | 75.80 | 46.22 |
October | 0.00 | 0.00 | 86.84 | 53.21 |
November | 0.00 | 0.00 | 103.88 | 57.08 |
December | 0.00 | 0.00 | 117.19 | 64.65 |
Annual Sum or Average | 0.00 | 0.00 | 96.02 | 659.18 |
Minimum of Months | 0.00 | 0.00 | 69.58 | 44.55 |
Maximum of Months | 0.00 | 0.00 | 121.80 | 67.46 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 120.02 | 67.33 |
February | 0.00 | 0.00 | 121.85 | 61.07 |
March | 0.00 | 0.00 | 116.17 | 64.36 |
April | 0.00 | 0.00 | 103.89 | 57.09 |
May | 0.00 | 0.00 | 89.39 | 53.00 |
June | 0.00 | 0.00 | 77.85 | 45.86 |
July | 0.00 | 0.00 | 69.26 | 44.61 |
August | 0.00 | 0.00 | 70.36 | 44.60 |
September | 0.00 | 0.00 | 75.65 | 46.20 |
October | 0.00 | 0.00 | 86.22 | 52.96 |
November | 0.00 | 0.00 | 104.11 | 57.28 |
December | 0.00 | 0.00 | 117.17 | 64.68 |
Annual Sum or Average | 0.00 | 0.00 | 95.84 | 659.05 |
Minimum of Months | 0.00 | 0.00 | 69.26 | 44.60 |
Maximum of Months | 0.00 | 0.00 | 121.85 | 67.33 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 120.54 | 67.49 |
February | 0.00 | 0.00 | 121.78 | 60.94 |
March | 0.00 | 0.00 | 116.16 | 64.34 |
April | 0.00 | 0.00 | 103.81 | 57.09 |
May | 0.00 | 0.00 | 89.42 | 53.01 |
June | 0.00 | 0.00 | 78.11 | 45.86 |
July | 0.00 | 0.00 | 69.92 | 44.67 |
August | 0.00 | 0.00 | 70.68 | 44.54 |
September | 0.00 | 0.00 | 76.04 | 46.21 |
October | 0.00 | 0.00 | 86.81 | 53.21 |
November | 0.00 | 0.00 | 104.10 | 57.14 |
December | 0.00 | 0.00 | 117.45 | 64.62 |
Annual Sum or Average | 0.00 | 0.00 | 96.09 | 659.11 |
Minimum of Months | 0.00 | 0.00 | 69.92 | 44.54 |
Maximum of Months | 0.00 | 0.00 | 121.78 | 67.49 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 121.11 | 67.52 |
February | 0.00 | 0.00 | 122.81 | 61.16 |
March | 0.00 | 0.00 | 116.68 | 64.37 |
April | 0.00 | 0.00 | 104.64 | 57.36 |
May | 0.00 | 0.00 | 89.23 | 52.83 |
June | 0.00 | 0.00 | 77.94 | 45.85 |
July | 0.00 | 0.00 | 69.58 | 44.67 |
August | 0.00 | 0.00 | 70.39 | 44.55 |
September | 0.00 | 0.00 | 75.72 | 46.23 |
October | 0.00 | 0.00 | 86.50 | 53.01 |
November | 0.00 | 0.00 | 105.24 | 57.44 |
December | 0.00 | 0.00 | 118.59 | 65.00 |
Annual Sum or Average | 0.00 | 0.00 | 96.38 | 659.97 |
Minimum of Months | 0.00 | 0.00 | 69.58 | 44.55 |
Maximum of Months | 0.00 | 0.00 | 122.81 | 67.52 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 120.61 | 67.45 |
February | 0.00 | 0.00 | 122.54 | 61.18 |
March | 0.00 | 0.00 | 116.36 | 64.28 |
April | 0.00 | 0.00 | 104.30 | 57.24 |
May | 0.00 | 0.00 | 89.41 | 53.00 |
June | 0.00 | 0.00 | 77.86 | 45.86 |
July | 0.00 | 0.00 | 69.28 | 44.61 |
August | 0.00 | 0.00 | 70.34 | 44.60 |
September | 0.00 | 0.00 | 75.55 | 46.21 |
October | 0.00 | 0.00 | 86.32 | 53.00 |
November | 0.00 | 0.00 | 104.72 | 57.38 |
December | 0.00 | 0.00 | 117.75 | 64.78 |
Annual Sum or Average | 0.00 | 0.00 | 96.10 | 659.60 |
Minimum of Months | 0.00 | 0.00 | 69.28 | 44.60 |
Maximum of Months | 0.00 | 0.00 | 122.54 | 67.45 |
Report: WATER HEATER: LOADS
For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | COOLING COIL WATER HEATING ELECTRICITY RATE [W] | COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs] | |
January | 0.00 | 0.00 | 121.13 | 67.65 |
February | 0.00 | 0.00 | 122.40 | 61.02 |
March | 0.00 | 0.00 | 116.25 | 64.19 |
April | 0.00 | 0.00 | 104.18 | 57.25 |
May | 0.00 | 0.00 | 89.44 | 53.02 |
June | 0.00 | 0.00 | 78.09 | 45.84 |
July | 0.00 | 0.00 | 69.94 | 44.69 |
August | 0.00 | 0.00 | 70.62 | 44.54 |
September | 0.00 | 0.00 | 75.89 | 46.20 |
October | 0.00 | 0.00 | 86.39 | 52.99 |
November | 0.00 | 0.00 | 104.91 | 57.43 |
December | 0.00 | 0.00 | 117.71 | 64.74 |
Annual Sum or Average | 0.00 | 0.00 | 96.26 | 659.57 |
Minimum of Months | 0.00 | 0.00 | 69.94 | 44.54 |
Maximum of Months | 0.00 | 0.00 | 122.40 | 67.65 |
Report: HEATING AND COOLING LOADS
For: UNHEATEDBSMT
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: BREEZEWAY
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 32.51 | 800.42 |
February | 43.57 | 555.66 |
March | 63.54 | 393.59 |
April | 123.97 | 79.89 |
May | 179.21 | 2.68 |
June | 228.52 | 0.00 |
July | 227.19 | 0.00 |
August | 212.41 | 0.00 |
September | 184.10 | 2.00 |
October | 125.63 | 31.62 |
November | 59.48 | 463.83 |
December | 27.68 | 978.27 |
Annual Sum or Average | 1507.81 | 3307.96 |
Minimum of Months | 27.68 | 0.00 |
Maximum of Months | 228.52 | 978.27 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 27.18 | 494.68 |
February | 35.74 | 334.87 |
March | 45.53 | 231.73 |
April | 91.18 | 38.90 |
May | 131.68 | 0.88 |
June | 170.92 | 0.00 |
July | 173.08 | 0.00 |
August | 164.49 | 0.00 |
September | 143.42 | 1.31 |
October | 100.10 | 14.53 |
November | 48.71 | 278.19 |
December | 24.22 | 625.19 |
Annual Sum or Average | 1156.24 | 2020.27 |
Minimum of Months | 24.22 | 0.00 |
Maximum of Months | 173.08 | 625.19 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 28.33 | 757.47 |
February | 42.19 | 491.95 |
March | 59.39 | 339.42 |
April | 122.91 | 51.69 |
May | 179.19 | 0.71 |
June | 231.82 | 0.00 |
July | 230.79 | 0.00 |
August | 214.84 | 0.00 |
September | 183.52 | 1.08 |
October | 119.21 | 26.22 |
November | 55.44 | 440.25 |
December | 24.29 | 930.16 |
Annual Sum or Average | 1491.91 | 3038.93 |
Minimum of Months | 24.29 | 0.00 |
Maximum of Months | 231.82 | 930.16 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 15.06 | 1102.20 |
February | 22.08 | 740.06 |
March | 40.90 | 483.04 |
April | 105.97 | 86.16 |
May | 174.60 | 3.18 |
June | 229.69 | 0.00 |
July | 225.55 | 0.00 |
August | 199.77 | 0.00 |
September | 152.55 | 4.05 |
October | 83.32 | 52.60 |
November | 24.58 | 634.30 |
December | 12.98 | 1354.56 |
Annual Sum or Average | 1287.05 | 4460.15 |
Minimum of Months | 12.98 | 0.00 |
Maximum of Months | 229.69 | 1354.56 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 8.29 | 843.91 |
February | 15.26 | 566.82 |
March | 25.05 | 344.72 |
April | 74.15 | 48.35 |
May | 127.51 | 0.66 |
June | 172.38 | 0.00 |
July | 171.65 | 0.00 |
August | 151.82 | 0.00 |
September | 111.65 | 1.65 |
October | 58.20 | 30.67 |
November | 15.20 | 457.06 |
December | 6.75 | 1030.50 |
Annual Sum or Average | 937.88 | 3324.34 |
Minimum of Months | 6.75 | 0.00 |
Maximum of Months | 172.38 | 1030.50 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 6.90 | 1077.30 |
February | 17.65 | 675.40 |
March | 35.32 | 423.51 |
April | 103.73 | 56.16 |
May | 174.43 | 0.64 |
June | 232.83 | 0.00 |
July | 228.83 | 0.00 |
August | 201.87 | 0.00 |
September | 151.24 | 1.60 |
October | 75.94 | 37.49 |
November | 19.78 | 591.12 |
December | 4.30 | 1302.16 |
Annual Sum or Average | 1252.81 | 4165.38 |
Minimum of Months | 4.30 | 0.00 |
Maximum of Months | 232.83 | 1302.16 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 36.90 | 561.55 |
February | 48.95 | 372.56 |
March | 71.68 | 245.53 |
April | 139.80 | 40.21 |
May | 200.56 | 1.14 |
June | 250.64 | 0.00 |
July | 251.06 | 0.00 |
August | 236.43 | 0.00 |
September | 206.79 | 0.81 |
October | 142.08 | 15.55 |
November | 67.75 | 307.09 |
December | 31.43 | 715.52 |
Annual Sum or Average | 1684.07 | 2259.95 |
Minimum of Months | 31.43 | 0.00 |
Maximum of Months | 251.06 | 715.52 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 33.78 | 288.88 |
February | 43.46 | 191.82 |
March | 55.24 | 123.38 |
April | 107.95 | 14.66 |
May | 153.16 | 0.02 |
June | 191.68 | 0.00 |
July | 195.70 | 0.00 |
August | 187.43 | 0.00 |
September | 166.46 | 0.08 |
October | 119.83 | 6.74 |
November | 58.66 | 149.41 |
December | 29.72 | 401.77 |
Annual Sum or Average | 1343.08 | 1176.75 |
Minimum of Months | 29.72 | 0.00 |
Maximum of Months | 195.70 | 401.77 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 34.32 | 528.80 |
February | 49.22 | 325.12 |
March | 69.45 | 207.12 |
April | 141.42 | 22.39 |
May | 202.54 | 0.00 |
June | 254.70 | 0.00 |
July | 255.15 | 0.00 |
August | 239.76 | 0.00 |
September | 206.98 | 0.00 |
October | 136.83 | 7.91 |
November | 64.90 | 288.45 |
December | 30.50 | 677.17 |
Annual Sum or Average | 1685.76 | 2056.95 |
Minimum of Months | 30.50 | 0.00 |
Maximum of Months | 255.15 | 677.17 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 16.82 | 831.32 |
February | 26.40 | 537.35 |
March | 47.48 | 330.97 |
April | 120.49 | 42.26 |
May | 196.20 | 0.94 |
June | 251.93 | 0.00 |
July | 249.62 | 0.00 |
August | 223.99 | 0.00 |
September | 175.39 | 0.21 |
October | 98.10 | 21.44 |
November | 28.52 | 444.31 |
December | 15.45 | 1051.55 |
Annual Sum or Average | 1450.40 | 3260.35 |
Minimum of Months | 15.45 | 0.00 |
Maximum of Months | 251.93 | 1051.55 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 10.80 | 575.77 |
February | 18.29 | 361.37 |
March | 32.53 | 196.51 |
April | 90.19 | 17.32 |
May | 149.21 | 0.01 |
June | 193.28 | 0.00 |
July | 194.45 | 0.00 |
August | 174.93 | 0.00 |
September | 134.30 | 0.29 |
October | 74.18 | 11.66 |
November | 20.78 | 286.48 |
December | 8.98 | 727.72 |
Annual Sum or Average | 1101.93 | 2177.11 |
Minimum of Months | 8.98 | 0.00 |
Maximum of Months | 194.45 | 727.72 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 10.63 | 813.41 |
February | 22.56 | 477.28 |
March | 43.19 | 270.10 |
April | 121.64 | 26.52 |
May | 198.16 | 0.00 |
June | 255.83 | 0.00 |
July | 253.39 | 0.00 |
August | 226.97 | 0.00 |
September | 175.04 | 0.12 |
October | 91.46 | 21.72 |
November | 25.24 | 416.42 |
December | 7.42 | 1013.91 |
Annual Sum or Average | 1431.54 | 3039.48 |
Minimum of Months | 7.42 | 0.00 |
Maximum of Months | 255.83 | 1013.91 |
Report: HEATING AND COOLING LOADS
For: ATTIC
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 8.10 | 1160.02 |
February | 20.30 | 698.92 |
March | 41.09 | 411.41 |
April | 128.71 | 49.55 |
May | 211.82 | 0.01 |
June | 282.15 | 0.00 |
July | 280.35 | 0.00 |
August | 252.53 | 0.00 |
September | 196.70 | 0.57 |
October | 98.42 | 35.10 |
November | 22.23 | 622.28 |
December | 4.21 | 1419.53 |
Annual Sum or Average | 1546.63 | 4397.40 |
Minimum of Months | 4.21 | 0.00 |
Maximum of Months | 282.15 | 1419.53 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 23.77 | 837.36 |
February | 39.30 | 524.29 |
March | 58.27 | 344.79 |
April | 140.01 | 47.64 |
May | 213.76 | 0.02 |
June | 280.45 | 0.00 |
July | 280.13 | 0.00 |
August | 259.02 | 0.00 |
September | 216.00 | 0.47 |
October | 132.40 | 29.69 |
November | 53.22 | 467.29 |
December | 20.79 | 1039.46 |
Annual Sum or Average | 1717.12 | 3291.02 |
Minimum of Months | 20.79 | 0.00 |
Maximum of Months | 280.45 | 1039.46 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 28.36 | 891.45 |
February | 41.48 | 596.97 |
March | 63.86 | 391.71 |
April | 140.89 | 69.44 |
May | 212.64 | 1.20 |
June | 276.90 | 0.00 |
July | 276.55 | 0.00 |
August | 256.23 | 0.00 |
September | 216.35 | 0.79 |
October | 139.15 | 32.52 |
November | 57.65 | 507.22 |
December | 21.91 | 1094.12 |
Annual Sum or Average | 1731.96 | 3585.42 |
Minimum of Months | 21.91 | 0.00 |
Maximum of Months | 276.90 | 1094.12 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 8.77 | 914.36 |
February | 17.69 | 585.98 |
March | 30.84 | 325.36 |
April | 98.42 | 39.12 |
May | 164.33 | 0.34 |
June | 220.75 | 0.00 |
July | 222.41 | 0.00 |
August | 201.64 | 0.00 |
September | 157.32 | 0.69 |
October | 82.18 | 20.65 |
November | 18.86 | 479.27 |
December | 6.32 | 1125.16 |
Annual Sum or Average | 1229.54 | 3490.93 |
Minimum of Months | 6.32 | 0.00 |
Maximum of Months | 222.41 | 1125.16 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 23.69 | 564.60 |
February | 35.23 | 374.46 |
March | 45.95 | 238.69 |
April | 109.27 | 38.91 |
May | 166.00 | 0.41 |
June | 218.78 | 0.00 |
July | 221.93 | 0.00 |
August | 208.06 | 0.00 |
September | 176.55 | 0.42 |
October | 115.78 | 12.67 |
November | 47.87 | 303.14 |
December | 19.09 | 719.87 |
Annual Sum or Average | 1388.20 | 2253.15 |
Minimum of Months | 19.09 | 0.00 |
Maximum of Months | 221.93 | 719.87 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 16:47:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
January | 14.21 | 1196.95 |
February | 24.50 | 780.89 |
March | 47.27 | 479.40 |
April | 130.00 | 78.50 |
May | 210.78 | 1.11 |
June | 278.71 | 0.00 |
July | 276.94 | 0.00 |
August | 249.89 | 0.00 |
September | 197.56 | 1.59 |
October | 106.44 | 43.42 |
November | 29.43 | 649.15 |
December | 10.81 | 1475.99 |
Annual Sum or Average | 1576.54 | 4707.00 |
Minimum of Months | 10.81 | 0.00 |
Maximum of Months | 278.71 | 1475.99 |