Table of Contents

Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 18:12

Tabular Output Report in Format: HTML

Building: US+MF+CZ7+oilfurnace+slab+IECC_2018

Environment: ANNUAL ** International Falls Intl Ap MN USA TMY3 WMO#=727470

Simulation Timestamp: 2024-06-27 18:12:31


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 1281300.35 41.05 59.29
Net Site Energy 1281300.35 41.05 59.29
Total Source Energy 2268787.87 72.69 104.99
Net Source Energy 2268787.87 72.69 104.99


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 31210.83
Net Conditioned Building Area 21609.96
Unconditioned Building Area 9600.87


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 542483.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 30663.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 41293.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 301503.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 33417.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 311335.02 0.00 0.00 0.00 0.00 0.00 312247.30
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 427481.37 542483.96 0.00 0.00 0.00 0.00 311335.02 0.00 0.00 0.00 0.00 0.00 312247.30
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 542483.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 30663.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 41293.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 17305.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 16112.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
  Water Heater 0.00 0.00 0.00 0.00 0.00 0.00 311335.02 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Unassigned 0.00 542483.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 30663.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 41293.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 301503.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 33417.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 311335.02 0.00 0.00 0.00 0.00 0.00 312247.30
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 2.97 25.10 0.00 0.00 0.00 0.00 14.41 0.00 0.00 0.00 0.00 0.00 14.45
Other 13.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 19.78 25.10 0.00 0.00 0.00 0.00 14.41 0.00 0.00 0.00 0.00 0.00 14.45


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 2.05 17.38 0.00 0.00 0.00 0.00 9.98 0.00 0.00 0.00 0.00 0.00 10.00
Other 9.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 13.70 17.38 0.00 0.00 0.00 0.00 9.98 0.00 0.00 0.00 0.00 0.00 10.00


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 427481.366 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 427481.366 100.00
     
Total On-Site and Utility Electric Sources 427481.366 100.00
Total Electricity End Uses 427481.366 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 312247.30 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 312247.30 100.00
Total Water End Uses 312247.30 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 668.83
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 2541.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Annual Thermal Resilience Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

HEATING AND COOLING LOADS

| BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

General

Value
Program Version and Build EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 18:12
RunPeriod ANNUAL
Weather File International Falls Intl Ap MN USA TMY3 WMO#=727470
Latitude [deg] 48.57
Longitude [deg] -93.4
Elevation [ft] 1177.88
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Above Ground Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94
Above Ground Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
BREEZEWAY 1798.16 No Yes 30553.25 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
ATTIC 7802.71 No Yes 52795.56 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6220 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6220 600.28 2.9092
Total 31210.83     267088.19   16177.97 0.00 2126.74 2126.74 0.4307 866.97 2.0143
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.6220 600.28 2.9092
Unconditioned Total 9600.87     83348.81   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2] Tags
BREEZEWAY 1798.16 No Yes 1.00 BREEZEWAY GENERAL BREEZEWAY 0.0000 0.00 0.0000  
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.6220 600.28 2.9092  
ATTIC 7802.71 No Yes 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL LIVING_UNIT3_BACKROW_TOPFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT3_FRONTROW_TOPFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT1_FRONTROW_TOPFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL LIVING_UNIT2_BACKROW_TOPFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT2_FRONTROW_TOPFLOOR 0.6220 600.28 2.9092  
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL LIVING_UNIT1_BACKROW_TOPFLOOR 0.6220 600.28 2.9092  
Total 31210.83             0.4307 866.97 2.0143  
Conditioned Total 21609.96             0.6220 600.28 2.9092  
Unconditioned Total 9600.87             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [ft2] Conditioned Area [ft2] Unconditioned Area [ft2] Not Part of Total Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
GENERAL 31210.83 21609.96 9600.87 0.00 0.4307 866.97 2.0143
Total 31210.83 21609.96 9600.87 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 29-JUN-18:20 06-JAN-04:10 - - - - 04-FEB-08:19 - - - - - 25-FEB-08:30
Heating 0.00 320.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 42.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 4.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 51.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 227.48 0.00 0.00 0.00 0.00 0.00 1.13
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 118.67 320.67 0.00 0.00 0.00 0.00 227.48 0.00 0.00 0.00 0.00 0.00 1.13


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 320.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 42.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 12.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 4.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 5.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 9.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 25.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 1.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 6.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13
  Water Heater 0.00 0.00 0.00 0.00 0.00 0.00 227.48 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 588052.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 97110.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 130776.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65251.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 954861.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 105833.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 326901.78 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1353833.49 588052.61 0.00 0.00 0.00 0.00 326901.78 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 27.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 6.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 3.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 44.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 4.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 15.13 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 62.65 27.21 0.00 0.00 0.00 0.00 15.13 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 18.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 30.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 3.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 0.00 0.00 0.00 0.00 0.00 10.47 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 43.38 18.84 0.00 0.00 0.00 0.00 10.47 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 354.16
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 237.71
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 292.36
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 332.93
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 237.72
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 292.33
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 431.23
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 216.72
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 332.00
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 405.66
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 195.18
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 297.12
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 331.39
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 331.47
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 453.38
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 271.88
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 271.93
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 442.35
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 354.16 354.16 354.16 354.16 354.16 354.16 1.00 1.00 354.16
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 237.71 237.71 237.71 237.71 237.71 237.71 1.00 1.00 237.71
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 292.36 292.36 292.36 292.36 292.36 292.36 1.00 1.00 292.36
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 332.93 332.93 332.93 332.93 332.93 332.93 1.00 1.00 332.93
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 237.72 237.72 237.72 237.72 237.72 237.72 1.00 1.00 237.72
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 292.33 292.33 292.33 292.33 292.33 292.33 1.00 1.00 292.33
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 431.23 431.23 431.23 431.23 431.23 431.23 1.00 1.00 431.23
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 216.72 216.72 216.72 216.72 216.72 216.72 1.00 1.00 216.72
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 332.00 332.00 332.00 332.00 332.00 332.00 1.00 1.00 332.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 405.66 405.66 405.66 405.66 405.66 405.66 1.00 1.00 405.66
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 195.18 195.18 195.18 195.18 195.18 195.18 1.00 1.00 195.18
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 297.12 297.12 297.12 297.12 297.12 297.12 1.00 1.00 297.12
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 453.38 453.38 453.38 453.38 453.38 453.38 1.00 1.00 453.38
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 271.93 271.93 271.93 271.93 271.93 271.93 1.00 1.00 271.93
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 331.47 331.47 331.47 331.47 331.47 331.47 1.00 1.00 331.47
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 442.35 442.35 442.35 442.35 442.35 442.35 1.00 1.00 442.35
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 271.88 271.88 271.88 271.88 271.88 271.88 1.00 1.00 271.88
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 331.39 331.39 331.39 331.39 331.39 331.39 1.00 1.00 331.39
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 354.16 1.17 0.704407
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 237.71 0.792196 0.701083
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 292.36 0.974345 0.701083
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 332.93 1.10 0.703650
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 237.72 0.792235 0.701083
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 292.33 0.974230 0.701083
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 431.23 1.35 0.720226
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 216.72 0.722239 0.701083
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 332.00 1.08 0.709558
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 405.66 1.27 0.720508
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 195.18 0.650463 0.701083
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 297.12 0.961309 0.710450
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 453.38 1.42 0.720658
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 271.93 0.906243 0.701083
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 331.47 1.09 0.705272
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 442.35 1.38 0.721515
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 271.88 0.906094 0.701083
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 331.39 1.09 0.705021
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 354.16 354.16 354.16 1.17 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 237.71 237.71 237.71 0.792196 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 292.36 292.36 292.36 0.974345 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 332.93 332.93 332.93 1.10 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 237.72 237.72 237.72 0.792235 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 292.33 292.33 292.33 0.974230 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 431.23 431.23 431.23 1.35 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 216.72 216.72 216.72 0.722239 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 332.00 332.00 332.00 1.08 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 405.66 405.66 405.66 1.27 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 195.18 195.18 195.18 0.650463 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 297.12 297.12 297.12 0.961309 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 453.38 453.38 453.38 1.42 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 271.93 271.93 271.93 0.906243 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 331.47 331.47 331.47 1.09 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 442.35 442.35 442.35 1.38 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 271.88 271.88 271.88 0.906094 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 331.39 331.39 331.39 1.09 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Water

Design Size Rated Capacity [Btu/h] Design Size Maximum Water Flow Rate [gal/min] Design Size U-Factor Times Area Value [Btu/h-F]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 26439.12 2.71 383.65
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 19490.28 2.00 275.53
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 22751.87 2.34 326.35
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 25172.70 2.58 363.98
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 19490.99 2.00 275.54
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 22749.81 2.34 326.31
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 31036.80 3.19 454.89
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 18237.01 1.87 255.88
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 25115.54 2.58 363.03
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 29510.85 3.03 431.25
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 16951.95 1.74 235.72
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 23034.80 2.36 330.69
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 32359.96 3.32 475.38
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 21532.27 2.21 307.36
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 25085.29 2.57 362.56
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 31701.74 3.25 465.19
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 21529.60 2.21 307.32
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 25080.54 2.57 362.49
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 354.16
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 237.71
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 292.36
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 332.93
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 237.72
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 292.33
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 431.23
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 216.72
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 332.00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 405.66
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 195.18
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 297.12
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 453.38
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 271.93
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 331.47
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 442.35
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 271.88
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 331.39
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
BOILER LOOP 6.00 12.00
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 2.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
BOILER CIRC PUMP 6.00
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [Btu/h] Design Size Design Water Flow Rate [gal/min]
CENTRAL BOILER 437271.13 44.88
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Version

Version ID
1 23.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No Yes Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40


Site:GroundTemperature:FCfactorMethod

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 10.90 8.24 12.97 20.35 39.67 54.57 64.62 67.68 62.46 50.90 35.44 21.07


Site:GroundTemperature:Shallow

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40


Site:GroundTemperature:Deep

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {ft} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Sensor Height Above Ground {ft} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 32.810 0.140 885.870 4.921 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {ft} Standard Pressure at Elevation {psi} Standard RhoAir at Elevation
1 International Falls Intl Ap MN USA TMY3 WMO#=727470 48.57 -93.40 -6.00 1177.88 14. 1.1539


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{F} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} Fixed Default Water Mains Temperature{F}
1 Correlation NA 37.92 65.88 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 US+MF+CZ7+oilfurnace+slab+IECC_2018 0.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Algorithm {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
Space Heat Balance Sizing

Space Heat Balance Simulation

1 ThirdOrderBackwardDifference No No


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Gradient Coefficient {F/ft}
1 0.220 1213.970 0.003566


Material Details

Material Name ThermalResistance {m2-K/w} Roughness Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} Absorptance:Thermal Absorptance:Solar Absorptance:Visible
1 SHEATHING_CONSOL_LAYER 0.8807 Rough 0.1021 3.533E-002 1.255 0.350 0.9000 0.7000 0.7000
2 CEIL_CONSOL_LAYER 7.7625 Rough 1.5719 6.172E-002 2.618 0.185 0.9000 0.7000 0.7000
3 FLOOR_CONSOL_LAYER 1.9554E-005 Rough 0.0008 12.990 3.438 0.219 0.9000 0.7000 0.7000
4 BSMTWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
5 CRAWLWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
6 WALL_CONSOL_LAYER 2.4438 Rough 0.4584 5.717E-002 7.541 0.248 0.9000 0.7000 0.7000
7 VERY HIGH REFLECTIVITY SURFACE 2.1097E-006 Smooth 0.0016 237.000 168.680 0.216 0.9000 5.0000E-002 5.0000E-002
8 GYPSUMBOARD-5/16IN 5.0054E-002 Rough 0.0260 0.159 39.954 0.270 0.9000 0.4000 0.1000
9 COPPERPIPE 4.7506E-005 MediumRough 0.0625 401.000 140.026 0.200 0.9000 0.6500 0.6500
10 F08 METAL SURFACE 1.7668E-005 Smooth 0.0026 45.280 488.437 0.119 0.9000 0.7000 0.7000
11 CONCRETE_4IN 7.7356E-002 Rough 0.3330 1.312 140.014 0.111 0.9000 0.7000 0.7000
12 ASPHALT_SHINGLE 7.7448E-002 MediumRough 0.0208 8.186E-002 70.000 0.300 0.9000 0.7500 0.7000
13 WOOD_SHINGLE 0.1115 MediumSmooth 0.0417 0.114 26.600 0.390 0.9000 0.7000 0.7000
14 SLATE_SHINGLE 8.8061E-003 MediumSmooth 0.0417 1.442 100.000 0.300 0.9000 0.7000 0.7000
15 CEMENT_STUCCO 2.6422E-002 MediumSmooth 0.0625 0.721 116.464 0.210 0.9000 0.7000 0.7000
16 SYN_STUCCO 3.5237E-002 MediumSmooth 0.0100 8.650E-002 24.971 0.210 0.7000 0.7000 0.7000
17 DRYWALL_1/2IN 7.9331E-002 MediumSmooth 0.0417 0.160 50.000 0.260 0.9000 0.7000 0.7000
18 OSB_5/8IN 0.1365 MediumSmooth 0.0521 0.116 34.000 0.290 0.9000 0.7000 0.7000
19 OSB_7/16IN 9.5550E-002 MediumSmooth 0.0365 0.116 34.000 0.290 0.9000 0.7000 0.7000
20 BLOWN_R30 5.1614 MediumRough 0.6975 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
21 BLOWN_R30_TOP 2.8489 MediumRough 0.3849 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
22 PLYWOOD_3/4IN 0.1650 Rough 0.0625 0.115 34.003 0.161 0.9000 0.7000 0.7000
23 BATT_R19 7.3089 MediumRough 0.0833 3.475E-003 0.600 0.200 0.9000 0.7000 0.7000
24 LUMBER_2X4 0.7709 Rough 0.2920 0.115 32.003 0.183 0.9000 0.7000 0.7000
25 CARPET_N_PAD 0.4224 MediumSmooth 0.0833 6.013E-002 2.000 0.200 0.9000 0.7000 0.7000
26 BATT_R13 2.2936 MediumRough 0.2917 3.876E-002 0.600 0.200 0.9000 0.7000 0.7000
27 OSB_1/2IN 0.1092 MediumSmooth 0.0417 0.116 34.000 0.290 0.9000 0.7000 0.7000
28 SOIL_12IN 0.1761 Rough 1.0000 1.731 115.011 0.056 0.9000 0.7000 0.7000
29 DOOR_CONST 0.5870 Smooth 0.1387 7.201E-002 32.003 0.183 0.9000 0.7000 0.7000
30 GYP_BOARD_1/2IN 8.0130E-002 Rough 0.0417 0.159 39.954 0.270 0.9000 0.4000 0.1000
31 STD WOOD 6INCH 1.2500 MediumSmooth 0.4921 0.120 33.711 0.289 0.9000 0.7000 0.7000
32 PIPE INSULATION 0.3830 VeryRough 0.0417 3.317E-002 5.681 0.200 0.9000 0.5000 0.5000
33 MANF_WALL_AIRGAP 0.1200 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
34 BLDG_PAPER_FELT 1.0567E-002 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
35 R_HIGH 177.0000 MediumRough 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
36 CLEAR ACRYLIC PLASTIC 3.3333E-003 VerySmooth 0.0098 0.900 0.000 0.000 0.9000 0.0000 0.0000
37 DIFFUSING ACRYLIC PLASTIC 2.4444E-003 VerySmooth 0.0072 0.900 0.000 0.000 0.9000 0.0000 0.0000
38 INT_BLIND 0.0000 Rough 0.0000 0.000 0.000 0.000 0.0000 0.0000 0.0000
39 GLASS 0.4127 VerySmooth 0.1373 0.101 0.000 0.000 0.8400 0.0000 0.0000


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Other Side Coefficients

Name Combined convective/radiative film coefficient {Btu/h-ft2-F} User selected Constant Temperature {F} Coefficient modifying the constant temperature term Coefficient modifying the external dry bulb temperature term Coefficient modifying the ground temperature term Coefficient modifying the wind speed term {s/m} Coefficient modifying the zone air temperature term Constant Temperature Schedule Name Sinusoidal Variation Period of Sinusoidal Variation Previous Other Side Temperature Coefficient Minimum Other Side Temperature {F} Maximum Other Side Temperature {F}
1 SURFPROPOTHSDCOEFSLABAVERAGE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABAVERAGESURFACETEMP NO 24.000 0.000 N/A N/A
2 SURFPROPOTHSDCOEFSLABPERIMETER N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABPERIMETERTEMP NO 24.000 0.000 N/A N/A
3 SURFPROPOTHSDCOEFSLABCORE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABCORETEMP NO 24.000 0.000 N/A N/A


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{F}


Surface Convection Coefficient Lower Limit {Btu/h-ft2-F}


Surface Convection Coefficient Upper Limit {Btu/h-ft2-F}


1 CTF - ConductionTransferFunction 392. 0.02 176.1


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 60


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 20 171 48


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {ft} Origin Y-Coordinate {ft} Origin Z-Coordinate {ft} Centroid X-Coordinate {ft} Centroid Y-Coordinate {ft} Centroid Z-Coordinate {ft} Type Zone Multiplier Zone List Multiplier Minimum X {ft} Maximum X {ft} Minimum Y {ft} Maximum Y {ft} Minimum Z {ft} Maximum Z {ft} Ceiling Height {ft} Volume {ft3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {ft2} Exterior Gross Wall Area {ft2} Exterior Net Wall Area {ft2} Exterior Window Area {ft2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BREEZEWAY 0.0 0.00 0.00 0.00 59.94 32.55 13.26 1 1 1 0.00 119.89 30.05 35.04 0.49 25.99 17.00 30553.07 TARP DOE-2 1798.18 0.00 0.00 0.00 4 0 0 Yes
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 4.76 1 1 1 0.00 39.96 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 4.76 1 1 1 39.96 79.93 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 4.76 1 1 1 79.93 119.89 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 4.76 1 1 1 0.00 39.96 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 4.76 1 1 1 39.96 79.93 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 4.76 1 1 1 79.93 119.89 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 13.26 1 1 1 0.00 39.96 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 13.26 1 1 1 39.96 79.93 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 13.26 1 1 1 79.93 119.89 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 13.26 1 1 1 0.00 39.96 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 13.26 1 1 1 39.96 79.93 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 13.26 1 1 1 79.93 119.89 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
14 ATTIC 0.0 -134.9 51.61 0.00 59.94 32.55 29.56 1 1 1 0.00 119.89 0.00 65.10 25.99 39.54 6.76 52795.39 TARP DOE-2 7802.66 881.33 881.33 0.00 11 0 0 Yes
15 LIVING_UNIT3_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 21.75 1 1 1 79.93 119.89 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
16 LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 21.75 1 1 1 79.93 119.89 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
17 LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 21.75 1 1 1 0.00 39.96 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
18 LIVING_UNIT2_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 21.75 1 1 1 39.96 79.93 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
19 LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 21.75 1 1 1 39.96 79.93 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
20 LIVING_UNIT1_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 21.75 1 1 1 0.00 39.96 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {ft2} # Occupants Area per Occupant {ft2/person} Occupant per Area {person/ft2} Interior Lighting {Btu/h-ft2} Electric Load {Btu/h-ft2} Gas Load {Btu/h-ft2} Other Load {Btu/h-ft2} Hot Water Eq {Btu/h-ft2} Steam Equipment {Btu/h-ft2} Sum Loads per Area {Btu/h-ft2} Outdoor Controlled Baseboard Heat
1 BREEZEWAY 1798.18 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
14 ATTIC 7802.66 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
15 LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
16 LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
17 LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
18 LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
19 LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No
20 LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.622 2.909 0.000 0.000 0.000 0.000 3.531 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Number of People {} People/Floor Area {person/ft2} Floor Area per person {ft2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
2 PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
3 PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
4 PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
5 PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
6 PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
7 PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
8 PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
9 PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
10 PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
11 PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
12 PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
13 PEOPLE_UNIT1_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
14 PEOPLE_UNIT2_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
15 PEOPLE_UNIT3_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
16 PEOPLE_UNIT1_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
17 PEOPLE_UNIT2_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
18 PEOPLE_UNIT3_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Lighting Level {Btu/h} Lights/Floor Area {Btu/h-ft2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {Btu/h} Nominal Maximum Lighting Level {Btu/h}
1 LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
2 LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
3 LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
4 LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
5 LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
6 LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
7 LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
8 LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
9 LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
10 LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
11 LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
12 LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
13 LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
14 LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
15 LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
16 LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
17 LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
18 LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
19 LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
20 LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
21 LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
22 LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
23 LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
24 LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
25 LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
26 LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
27 LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
28 LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
29 LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
30 LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
31 LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
32 LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
33 LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
34 LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
35 LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 527.915 0.440 77.362 0.000 0.600 0.200 0.200 0.000 General 36.293 527.915
36 LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 DISHWASHER1_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
2 REFRIGERATOR1_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
3 CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
4 ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
5 ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
6 TELEVISION1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
7 ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
8 IECC_ADJ1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
9 DISHWASHER2_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
10 REFRIGERATOR2_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
11 CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
12 ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
13 ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
14 TELEVISION2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
15 ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
16 IECC_ADJ2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
17 DISHWASHER3_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
18 REFRIGERATOR3_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
19 CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
20 ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
21 ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
22 TELEVISION3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
23 ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
24 IECC_ADJ3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
25 DISHWASHER1_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
26 REFRIGERATOR1_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
27 CLOTHESWASHER1_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
28 ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
29 ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
30 TELEVISION1_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
31 ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
32 IECC_ADJ1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
33 DISHWASHER2_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
34 REFRIGERATOR2_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
35 CLOTHESWASHER2_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
36 ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
37 ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
38 TELEVISION2_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
39 ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
40 IECC_ADJ2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
41 DISHWASHER3_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
42 REFRIGERATOR3_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
43 CLOTHESWASHER3_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
44 ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
45 ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
46 TELEVISION3_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
47 ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
48 IECC_ADJ3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
49 DISHWASHER1_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
50 REFRIGERATOR1_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
51 CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
52 ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
53 ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
54 TELEVISION1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
55 ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
56 IECC_ADJ1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
57 DISHWASHER2_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
58 REFRIGERATOR2_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
59 CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
60 ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
61 ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
62 TELEVISION2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
63 ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
64 IECC_ADJ2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
65 DISHWASHER3_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
66 REFRIGERATOR3_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
67 CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
68 ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
69 ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
70 TELEVISION3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
71 ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
72 IECC_ADJ3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
73 DISHWASHER1_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
74 REFRIGERATOR1_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
75 CLOTHESWASHER1_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
76 ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
77 ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
78 TELEVISION1_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
79 ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
80 IECC_ADJ1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
81 DISHWASHER2_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
82 REFRIGERATOR2_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
83 CLOTHESWASHER2_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
84 ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
85 ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
86 TELEVISION2_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
87 ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
88 IECC_ADJ2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
89 DISHWASHER3_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
90 REFRIGERATOR3_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
91 CLOTHESWASHER3_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
92 ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
93 ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
94 TELEVISION3_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
95 ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
96 IECC_ADJ3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
97 DISHWASHER1_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
98 REFRIGERATOR1_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
99 CLOTHESWASHER1_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
100 ELECTRIC_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
101 ELECTRIC_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
102 TELEVISION1_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
103 ELECTRIC_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
104 IECC_ADJ1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
105 DISHWASHER2_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
106 REFRIGERATOR2_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
107 CLOTHESWASHER2_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
108 ELECTRIC_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
109 ELECTRIC_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
110 TELEVISION2_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
111 ELECTRIC_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
112 IECC_ADJ2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
113 DISHWASHER3_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
114 REFRIGERATOR3_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
115 CLOTHESWASHER3_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
116 ELECTRIC_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
117 ELECTRIC_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
118 TELEVISION3_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
119 ELECTRIC_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
120 IECC_ADJ3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
121 DISHWASHER1_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
122 REFRIGERATOR1_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
123 CLOTHESWASHER1_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
124 ELECTRIC_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
125 ELECTRIC_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
126 TELEVISION1_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
127 ELECTRIC_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
128 IECC_ADJ1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
129 DISHWASHER2_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
130 REFRIGERATOR2_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
131 CLOTHESWASHER2_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
132 ELECTRIC_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
133 ELECTRIC_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
134 TELEVISION2_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
135 ELECTRIC_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
136 IECC_ADJ2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
137 DISHWASHER3_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
138 REFRIGERATOR3_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
139 CLOTHESWASHER3_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
140 ELECTRIC_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
141 ELECTRIC_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
142 TELEVISION3_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
143 ELECTRIC_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
144 IECC_ADJ3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736


Construction CTF

Construction Name Index #Layers #CTFs Time Step {Hours} ThermalConductance {Btu/h-ft2-F} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 EXTERIOR WALL 1 5 10 0.167 0.0498 0.700 0.900 0.700 0.700 MediumSmooth
2 CEILING-FLOOR-LAYER 3 1 5 0.167 0.228 0.900 0.900 0.700 0.700 Rough
3 EXTERIOR FLOOR 4 3 4 0.167 0.300 0.900 0.900 0.700 0.700 Rough
4 INTERIOR CEILING 6 2 12 0.167 0.0225 0.900 0.900 0.700 0.700 Rough
5 ATTIC FLOOR 7 2 12 0.167 0.0225 0.900 0.900 0.700 0.700 MediumSmooth
6 INTERIORWALL 9 3 5 0.167 0.597 0.900 0.900 0.700 0.700 MediumSmooth
7 EXTERIOR ROOF 11 2 4 0.167 0.943 0.900 0.900 0.750 0.700 MediumRough
8 EXTERIOR DOOR 14 1 5 0.167 0.300 0.900 0.900 0.700 0.700 Smooth
9 GABLE_END 16 5 6 0.167 0.428 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} ThermalResistance {m2-K/w}
1 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
2 SHEATHING_CONSOL_LAYER 0.1020 0.035 1.255 0.350 0.8807
3 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
4 WALL_CONSOL_LAYER 0.4584 0.057 7.541 0.248 2.444
5 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
6 LUMBER_2X4 0.2920 0.115 32.003 0.183 0.7709
7 FLOOR_CONSOL_LAYER 0.0010 12.990 3.438 0.219 0.1955E-04
8 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
9 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
10 CEIL_CONSOL_LAYER 1.5719 0.062 2.618 0.185 7.762
11 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
12 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
13 CEIL_CONSOL_LAYER 1.5719 0.062 2.618 0.185 7.762
14 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
15 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
16 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
17 ASPHALT_SHINGLE 0.0207 0.082 70.000 0.300 0.7745E-01
18 OSB_1/2IN 0.0417 0.116 34.000 0.290 0.1092
19 DOOR_CONST 0.1388 0.072 32.003 0.183 0.5870
20 CEMENT_STUCCO 0.0627 0.721 116.464 0.210 0.2642E-01
21 BLDG_PAPER_FELT 0.0000 0.000 0.000 0.000 0.1057E-01
22 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
23 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


CTF

Time Outside Cross Inside Flux (except final one)
1 10 0.51360630E-08 -0.22035233E-13 0.91774209E-08 -0.50676220E-13
2 9 -0.14060012E-04 0.39159197E-12 -0.22958088E-04 0.29728831E-08
3 8 0.28980689E-02 0.65531654E-09 0.46215968E-02 -0.71708779E-05
4 7 -0.65978682E-01 0.13350779E-06 -0.16306378 0.13238707E-02
5 6 0.64596177 0.50193482E-05 2.1320981 -0.28125917E-01
6 5 -3.4215999 0.48298777E-04 -13.652056 0.25148823
7 4 10.645660 0.13839053E-03 47.881148 -1.1749737
8 3 -19.924231 0.11919231E-03 -96.040791 3.0621859
9 2 21.976583 0.26462555E-04 109.48934 -4.4404618
10 1 -13.118296 0.91387708E-06 -65.855375 3.3273744
11 0 3.2593552 0.33613880E-09 16.204438  
12 5 -0.10726087E-01 0.44268190E-05 -0.10726087E-01 0.97389233E-03
13 4 0.31857203 0.80150166E-03 0.31857203 -0.30727185E-01
14 3 -2.8372473 0.12516450E-01 -2.8372473 0.30041224
15 2 9.6667056 0.33176537E-01 9.6667056 -1.1584571
16 1 -13.322214 0.15207483E-01 -13.322214 1.8397512
17 0 6.2472388 0.62260140E-03 6.2472388  
18 4 0.29631924E-13 -0.40788276E-14 0.60443234E-14 -0.77798347E-16
19 3 -0.11254351E-04 0.79669069E-06 -0.23145793E-05 0.39394231E-13
20 2 0.49771861 0.29587917E-01 0.78801895E-01 -0.76025120E-05
21 1 -8.3915550 0.80192706 -1.1535996 0.21114735
22 0 9.2367617 0.51139848 2.4177143  
23 12 0.94888791E-16 -0.11237443E-15 0.21480527E-09 -0.52606005E-16
24 11 -0.44509090E-09 -0.12338758E-15 -0.11566016E-03 0.28501063E-09
25 10 0.60393314E-04 0.62564840E-13 0.62960490E-02 -0.38672578E-04
26 9 -0.20055671E-02 0.85912012E-10 -0.12885789 0.13084700E-02
27 8 0.28697042E-01 0.10381403E-07 1.3966036 -0.19129448E-01
28 7 -0.23229993 0.28493476E-06 -9.1473517 0.15872626
29 6 1.1750436 0.24973161E-05 38.552224 -0.82592201
30 5 -3.8729952 0.80040830E-05 -107.65441 2.8111251
31 4 8.4143451 0.96510929E-05 200.56463 -6.3313915
32 3 -11.897084 0.41099356E-05 -245.77565 9.3152582
33 2 10.487404 0.50788650E-06 189.69676 -8.5734564
34 1 -5.2147174 0.10902359E-07 -83.415737 4.4633233
35 0 1.1135774 0.38882120E-11 15.905642  
36 12 0.21480527E-09 -0.11237443E-15 0.94888791E-16 -0.52606005E-16
37 11 -0.11566016E-03 -0.12338758E-15 -0.44509090E-09 0.28501063E-09
38 10 0.62960490E-02 0.62564840E-13 0.60393314E-04 -0.38672578E-04
39 9 -0.12885789 0.85912012E-10 -0.20055671E-02 0.13084700E-02
40 8 1.3966036 0.10381403E-07 0.28697042E-01 -0.19129448E-01
41 7 -9.1473517 0.28493476E-06 -0.23229993 0.15872626
42 6 38.552224 0.24973161E-05 1.1750436 -0.82592201
43 5 -107.65441 0.80040830E-05 -3.8729952 2.8111251
44 4 200.56463 0.96510929E-05 8.4143451 -6.3313915
45 3 -245.77565 0.41099356E-05 -11.897084 9.3152582
46 2 189.69676 0.50788650E-06 10.487404 -8.5734564
47 1 -83.415737 0.10902359E-07 -5.2147174 4.4633233
48 0 15.905642 0.38882120E-11 1.1135774  
49 5 -0.27590492E-07 0.65241430E-08 -0.27590492E-07 0.17331255E-13
50 4 0.68608714E-03 0.11323974E-03 0.68608714E-03 -0.15705033E-07
51 3 -0.21538511 0.37821720E-01 -0.21538511 0.25667047E-03
52 2 5.0173519 0.62258424 5.0173519 -0.50236511E-01
53 1 -19.904252 0.86481321 -19.904252 0.58144210
54 0 16.688993 0.62060609E-01 16.688993  
55 4 0.75441920E-10 0.23883683E-10 0.47514224E-10 -0.69373194E-20
56 3 -0.33730907E-03 0.89366797E-04 -0.22574866E-03 0.77828620E-10
57 2 0.58624422 0.18542418 0.49024360 -0.17301269E-03
58 1 -11.299243 2.8799011 -8.6239668 0.15905732
59 0 15.219762 1.4410112 12.640375  
60 5 -0.32935335E-06 0.42931990E-07 -0.32935335E-06 0.47097488E-08
61 4 0.68052310E-03 0.12823787E-03 0.68052310E-03 -0.14200104E-04
62 3 -0.11535993 0.17375615E-01 -0.11535993 0.40770076E-02
63 2 2.1922172 0.21284128 2.1922172 -0.13171357
64 1 -7.8704965 0.30308566 -7.8704965 0.79499401
65 0 6.3596665 0.33276539E-01 6.3596665  
66 6 0.97988530E-11 0.43917118E-12 0.24496810E-11 -0.34892153E-15
67 5 -0.75005310E-05 0.16499726E-06 -0.28271466E-05 0.19166609E-11
68 4 0.32354224E-01 0.66949565E-03 0.10283773E-01 -0.11111676E-05
69 3 -1.8201547 0.67148336E-01 -0.62076152 0.38788549E-02
70 2 21.173821 0.53241617 7.5279938 -0.97325542E-01
71 1 -64.420211 0.46601667 -21.697519 0.64629334
72 0 46.121323 0.20873329E-01 15.867130  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {Btu/h-ft2-F} Conductance (Before Adjusted) {Btu/h-ft2-F} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 EXTERIOR WINDOW 12 1 VerySmooth 0.300 0.300 1.000 0.335    
2 INTERIOR WINDOW 13 1 VerySmooth 0.300 0.300 1.000 0.335    
3 WINDOW_W_BLINDS 18 2 VerySmooth 0.300 0.300 1.000 0.309    
4 TDD DOME 22 1 VerySmooth 1.071 1.071 1.000 0.929    
5 TDD DIFFUSER 23 1 VerySmooth 1.077 1.077 1.000 0.906    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {ft} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLASS SpectralAverage   0.13728 0.24698 0.55113 0.55113 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10138 1.00000 No
2 GLASS SpectralAverage   0.13728 0.24698 0.55113 0.55113 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10138 1.00000 No
3 GLASS SpectralAverage   0.13728 0.24698 0.55113 0.55113 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10138 1.00000 No
4 CLEAR ACRYLIC PLASTIC SpectralAverage   0.00984 0.92000 5.00000E-002 5.00000E-002 0.92000 5.00000E-002 5.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No
5 DIFFUSING ACRYLIC PLASTIC SpectralAverage   0.00722 0.90000 8.00000E-002 8.00000E-002 0.90000 8.00000E-002 8.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No


WindowMaterial:Blind

Material Name Slat Width {ft} Slat Separation {ft} Slat Thickness {ft} Slat Angle {deg} Slat Beam Solar Transmittance Slat Beam Solar Front Reflectance Blind To Glass Distance {ft}
1 INT_BLIND 0.0820 0.0615 0.0033 45.000 0.000 0.500 0.164


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000. SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {ft3} Maximum Capacity {Btu/h} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 6.9509 36002.1 0.822 0.6044
2 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 6.9509 36002.1 0.822 0.6044
3 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 6.9509 36002.1 0.822 0.6044
4 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 6.9509 36002.1 0.822 0.6044
5 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 6.9509 36002.1 0.822 0.6044
6 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 6.9509 36002.1 0.822 0.6044
7 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 6.9509 36002.1 0.822 0.6044
8 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 6.9509 36002.1 0.822 0.6044
9 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 6.9509 36002.1 0.822 0.6044
10 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 6.9509 36002.1 0.822 0.6044
11 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 6.9509 36002.1 0.822 0.6044
12 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 6.9509 36002.1 0.822 0.6044
13 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 6.9509 36002.1 0.822 0.6044
14 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 6.9509 36002.1 0.822 0.6044
15 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 6.9509 36002.1 0.822 0.6044
16 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR 6.9509 36002.1 0.822 0.6044
17 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR 6.9509 36002.1 0.822 0.6044
18 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR 6.9509 36002.1 0.822 0.6044


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
2 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
3 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
4 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
5 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
6 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
7 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
8 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
9 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
11 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
12 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
13 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
14 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
15 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
16 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
17 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
18 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
19 ATTICVENT ALWAYS_AVAIL ATTIC 7802.66 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/person Area {ft3/min-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {psi} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{F}/Schedule Maximum Indoor Temperature{F}/Schedule Delta Temperature{F}/Schedule Minimum Outdoor Temperature{F}/Schedule Maximum Outdoor Temperature{F}/Schedule Maximum WindSpeed{ft/min}
1 VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
2 VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
3 VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
4 VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
5 VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
6 VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
7 VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
8 VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
9 VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
10 VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
11 VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
12 VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
13 VENTILATION_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
14 VENTILATION_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
15 VENTILATION_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
16 VENTILATION_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
17 VENTILATION_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
18 VENTILATION_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BREEZEWAY Mixing/Well-Stirred
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
14 ATTIC Mixing/Well-Stirred
15 LIVING_UNIT3_BACKROW_TOPFLOOR Mixing/Well-Stirred
16 LIVING_UNIT3_FRONTROW_TOPFLOOR Mixing/Well-Stirred
17 LIVING_UNIT1_FRONTROW_TOPFLOOR Mixing/Well-Stirred
18 LIVING_UNIT2_BACKROW_TOPFLOOR Mixing/Well-Stirred
19 LIVING_UNIT2_FRONTROW_TOPFLOOR Mixing/Well-Stirred
20 LIVING_UNIT1_BACKROW_TOPFLOOR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {Btu/h} User Des Load {Btu/h} Calc Des Air Flow Rate {ft3/min} User Des Air Flow Rate {ft3/min} Design Day Name Date/Time of Peak Temperature at Peak {F} Humidity Ratio at Peak {lbWater/lbDryAir} Floor Area {ft2} # Occupants Calc Outdoor Air Flow Rate {ft3/min} Calc DOAS Heat Addition Rate {Btu/h}
1 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Cooling 7970.59182 7970.59182 354.15250 354.15250 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 81.56719 0.01272 1200.55323 2.00000 44.99491 0.00000
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Heating 15387.30675 15387.30675 292.22454 292.22454 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Cooling 3831.11036 3831.11036 170.23536 170.23536 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 86.18000 0.01273 1200.55323 2.00000 44.99491 0.00000
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Heating 12516.35933 12516.35933 237.71183 237.71183 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Cooling 5927.59247 5927.59247 263.36861 263.36861 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 80.48840 0.01272 1200.55323 2.00000 44.99491 0.00000
6 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Heating 15394.48212 15394.48212 292.37284 292.37284 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
7 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Cooling 7492.90704 7492.90704 332.92369 332.92369 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 80.26520 0.01272 1200.55323 2.00000 44.99491 0.00000
8 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Heating 15390.43866 15390.43866 292.28810 292.28810 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
9 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Cooling 3077.31354 3077.31354 136.73325 136.73325 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 77.47520 0.01272 1200.55323 2.00000 44.99491 0.00000
10 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Heating 12516.97905 12516.97905 237.71183 237.71183 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
11 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Cooling 5248.01921 5248.01921 233.17794 233.17794 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 77.06601 0.01272 1200.55323 2.00000 44.99491 0.00000
12 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Heating 15392.66608 15392.66608 292.33047 292.33047 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
13 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Cooling 9705.34348 9705.34348 431.22876 431.22876 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 80.82320 0.01272 1200.55323 2.00000 44.99491 0.00000
14 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Heating 13386.39537 13386.39537 254.23726 254.23726 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
15 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Cooling 4877.20557 4877.20557 216.71607 216.71607 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 86.18000 0.01273 1200.55323 2.00000 44.99491 0.00000
16 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Heating 10277.12784 10277.12784 195.19489 195.19489 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
17 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Cooling 7472.00619 7472.00619 331.99148 331.99148 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 81.04640 0.01272 1200.55323 2.00000 44.99491 0.00000
18 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Heating 13387.33309 13387.33309 254.25844 254.25844 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
19 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Cooling 9129.72373 9129.72373 405.65673 405.65673 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 79.14920 0.01272 1200.55323 2.00000 44.99491 0.00000
20 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Heating 13388.10956 13388.10956 254.27963 254.27963 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
21 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Cooling 4127.16888 4127.16888 183.38049 183.38049 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 76.65679 0.01272 1200.55323 2.00000 44.99491 0.00000
22 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Heating 10276.32472 10276.32472 195.17964 195.17964 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
23 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Cooling 6687.29242 6687.29242 297.11861 297.11861 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 78.25640 0.01272 1200.55323 2.00000 44.99491 0.00000
24 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Heating 13384.01568 13384.01568 254.19488 254.19488 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
25 LIVING_UNIT3_BACKROW_TOPFLOOR Cooling 6659.86543 6659.86543 295.91098 295.91098 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 78.81440 0.01272 1200.55323 2.00000 44.99491 0.00000
26 LIVING_UNIT3_BACKROW_TOPFLOOR Heating 17449.34230 17449.34230 331.39826 331.39826 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
27 LIVING_UNIT3_FRONTROW_TOPFLOOR Cooling 7425.05007 7425.05007 329.91521 329.91521 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 81.04640 0.01272 1200.55323 2.00000 44.99491 0.00000
28 LIVING_UNIT3_FRONTROW_TOPFLOOR Heating 17453.53486 17453.53486 331.46182 331.46182 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
29 LIVING_UNIT1_FRONTROW_TOPFLOOR Cooling 10203.63892 10203.63892 453.38977 453.38977 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 80.26520 0.01272 1200.55323 2.00000 44.99491 0.00000
30 LIVING_UNIT1_FRONTROW_TOPFLOOR Heating 17457.38383 17457.38383 331.54657 331.54657 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
31 LIVING_UNIT2_BACKROW_TOPFLOOR Cooling 4983.63571 4983.63571 221.44065 221.44065 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 76.65679 0.01272 1200.55323 2.00000 44.99491 0.00000
32 LIVING_UNIT2_BACKROW_TOPFLOOR Heating 14315.88371 14315.88371 271.88556 271.88556 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
33 LIVING_UNIT2_FRONTROW_TOPFLOOR Cooling 5201.24639 5201.24639 231.12285 231.12285 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 86.18000 0.01273 1200.55323 2.00000 44.99491 0.00000
34 LIVING_UNIT2_FRONTROW_TOPFLOOR Heating 14318.24731 14318.24731 271.92793 271.92793 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
35 LIVING_UNIT1_BACKROW_TOPFLOOR Cooling 9955.35242 9955.35242 442.35164 442.35164 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 79.14920 0.01272 1200.55323 2.00000 44.99491 0.00000
36 LIVING_UNIT1_BACKROW_TOPFLOOR Heating 17456.83798 17456.83798 331.52538 331.52538 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [ft3/min] User Des Air Flow Rate [ft3/min] Design Day Name Date/Time of Peak
1 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Cooling Sensible 2394.00 354.15250 354.15250 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Heating Sensible 5796.36 292.22454 292.22454 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
3 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Cooling Sensible 1260.49 170.23536 170.23536 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Heating Sensible 4967.20 237.71183 237.71183 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
5 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Cooling Sensible 1788.65 263.36861 263.36861 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Heating Sensible 5798.43 292.37284 292.37284 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
7 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Cooling Sensible 2238.10 332.92369 332.92369 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Heating Sensible 5797.26 292.28810 292.28810 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
9 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Cooling Sensible 923.48 136.73325 136.73325 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Heating Sensible 4967.38 237.71183 237.71183 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
11 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Cooling Sensible 1545.38 233.17794 233.17794 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Heating Sensible 5797.90 292.33047 292.33047 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
13 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Cooling Sensible 2885.30 431.22876 431.22876 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Heating Sensible 5218.51 254.23726 254.23726 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
15 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Cooling Sensible 1562.89 216.71607 216.71607 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Heating Sensible 4320.52 195.19489 195.19489 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
17 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Cooling Sensible 2242.74 331.99148 331.99148 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
18 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Heating Sensible 5218.78 254.25844 254.25844 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
19 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Cooling Sensible 2696.00 405.65673 405.65673 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
20 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Heating Sensible 5219.01 254.27963 254.27963 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
21 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Cooling Sensible 1215.77 183.38049 183.38049 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
22 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Heating Sensible 4320.29 195.17964 195.17964 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
23 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Cooling Sensible 1977.72 297.11861 297.11861 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
24 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Heating Sensible 5217.82 254.19488 254.19488 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
25 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Cooling Sensible 3021.72 453.38977 453.38977 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
26 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Heating Sensible 6394.22 331.54657 331.54657 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
27 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Cooling Sensible 1656.57 231.12285 231.12285 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
28 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Heating Sensible 5487.61 271.92793 271.92793 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
29 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Cooling Sensible 2229.17 329.91521 329.91521 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
30 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Heating Sensible 6393.11 331.46182 331.46182 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
31 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Cooling Sensible 2934.68 442.35164 442.35164 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
32 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Heating Sensible 6394.07 331.52538 331.52538 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
33 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Cooling Sensible 1463.36 221.44065 221.44065 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
34 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Heating Sensible 5486.92 271.88556 271.88556 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
35 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Cooling Sensible 1977.43 295.91098 295.91098 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
36 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Heating Sensible 6391.90 331.39826 331.39826 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 354.15250
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 237.71183
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 292.37284
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 332.92369
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 237.71183
6 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 292.33047
7 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 431.22876
8 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 216.71607
9 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 331.99148
10 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 405.65673
11 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 195.17964
12 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 297.11861
13 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 331.39826
14 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 331.46182
15 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 453.38977
16 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 271.88556
17 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 271.92793
18 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 442.35164
19 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 354.15250
20 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 354.15250
21 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 354.15250
22 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 354.15250
23 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 354.15250
24 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 354.15250
25 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
26 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
27 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 237.71183
28 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 237.71183
29 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 237.71183
30 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 237.71183
31 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 237.71183
32 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 237.71183
33 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
34 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
35 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 292.37284
36 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 292.37284
37 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 292.37284
38 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 292.37284
39 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 292.37284
40 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 292.37284
41 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
42 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
43 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 332.92369
44 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 332.92369
45 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 332.92369
46 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 332.92369
47 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 332.92369
48 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 332.92369
49 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
50 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
51 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 237.71183
52 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 237.71183
53 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 237.71183
54 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 237.71183
55 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 237.71183
56 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 237.71183
57 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
58 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
59 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 292.33047
60 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 292.33047
61 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 292.33047
62 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 292.33047
63 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 292.33047
64 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 292.33047
65 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
66 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
67 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 431.22876
68 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 431.22876
69 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 431.22876
70 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 431.22876
71 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 431.22876
72 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 431.22876
73 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
74 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
75 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 216.71607
76 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 216.71607
77 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 216.71607
78 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 216.71607
79 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 216.71607
80 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 216.71607
81 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
82 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
83 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 331.99148
84 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 331.99148
85 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 331.99148
86 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 331.99148
87 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 331.99148
88 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 331.99148
89 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
90 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
91 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 405.65673
92 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 405.65673
93 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 405.65673
94 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 405.65673
95 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 405.65673
96 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 405.65673
97 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
98 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
99 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 195.17964
100 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 195.17964
101 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 195.17964
102 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 195.17964
103 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 195.17964
104 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 195.17964
105 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
106 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
107 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 297.11861
108 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 297.11861
109 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 297.11861
110 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 297.11861
111 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 297.11861
112 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 297.11861
113 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
114 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
115 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 453.38977
116 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 453.38977
117 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 453.38977
118 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 453.38977
119 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 453.38977
120 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 453.38977
121 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
122 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
123 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 271.92793
124 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 271.92793
125 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 271.92793
126 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 271.92793
127 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 271.92793
128 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 271.92793
129 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
130 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
131 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 331.46182
132 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 331.46182
133 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 331.46182
134 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 331.46182
135 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 331.46182
136 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 331.46182
137 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
138 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
139 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 442.35164
140 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 442.35164
141 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 442.35164
142 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 442.35164
143 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 442.35164
144 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 442.35164
145 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
146 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
147 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 271.88556
148 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 271.88556
149 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 271.88556
150 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 271.88556
151 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 271.88556
152 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 271.88556
153 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
154 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
155 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 331.39826
156 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 331.39826
157 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 331.39826
158 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 331.39826
159 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 331.39826
160 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 331.39826
161 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
162 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
163 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 354.15250
164 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 237.71183
165 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 292.37284
166 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 332.92369
167 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 237.71183
168 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 292.33047
169 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 431.22876
170 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 216.71607
171 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 331.99148
172 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 405.65673
173 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 195.17964
174 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 297.11861
175 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 453.38977
176 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 271.92793
177 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 331.46182
178 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 442.35164
179 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 271.88556
180 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 331.39826
181 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 354.15250
182 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.16919
183 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70441
184 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 354.15250
185 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 354.15250
186 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 354.15250
187 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.16919
188 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 26439.11731
189 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.71389
190 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 383.64798
191 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
192 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 354.15250
193 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 237.71183
194 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.79220
195 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
196 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 237.71183
197 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 237.71183
198 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 237.71183
199 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.79220
200 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 19490.28411
201 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.00062
202 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 275.52645
203 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
204 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 237.71183
205 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 292.37284
206 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.97434
207 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
208 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 292.37284
209 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 292.37284
210 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 292.37284
211 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.97434
212 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 22751.86953
213 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.33541
214 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 326.34514
215 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
216 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 292.37284
217 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 332.92369
218 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.10250
219 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70365
220 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 332.92369
221 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 332.92369
222 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 332.92369
223 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.10250
224 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 25172.69879
225 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.58389
226 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 363.98358
227 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
228 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 332.92369
229 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 237.71183
230 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.79224
231 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
232 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 237.71183
233 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 237.71183
234 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 237.71183
235 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.79224
236 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 19490.98640
237 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.00068
238 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 275.53741
239 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
240 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 237.71183
241 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 292.33047
242 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.97423
243 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
244 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 292.33047
245 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 292.33047
246 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 292.33047
247 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.97423
248 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 22749.81152
249 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.33519
250 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 326.31316
251 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
252 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 292.33047
253 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 431.22876
254 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.35352
255 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72023
256 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 431.22876
257 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 431.22876
258 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 431.22876
259 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.35352
260 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 31036.79963
261 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 3.18582
262 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 454.89267
263 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
264 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 431.22876
265 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 216.71607
266 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.72224
267 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
268 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 216.71607
269 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 216.71607
270 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 216.71607
271 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.72224
272 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 18237.01113
273 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.87196
274 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 255.87943
275 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
276 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 216.71607
277 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 331.99148
278 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.07794
279 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70956
280 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 331.99148
281 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 331.99148
282 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 331.99148
283 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.07794
284 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 25115.53956
285 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.57803
286 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 363.03258
287 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
288 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 331.99148
289 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 405.65673
290 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.27187
291 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72051
292 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 405.65673
293 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 405.65673
294 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 405.65673
295 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.27187
296 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 29510.85497
297 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 3.02919
298 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 431.25384
299 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
300 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 405.65673
301 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 195.17964
302 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.65046
303 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
304 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 195.17964
305 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 195.17964
306 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 195.17964
307 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.65046
308 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 16951.95206
309 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.74006
310 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 235.72254
311 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
312 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 195.17964
313 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 297.11861
314 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.96131
315 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.71045
316 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 297.11861
317 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 297.11861
318 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 297.11861
319 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.96131
320 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 23034.80435
321 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.36445
322 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 330.69010
323 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
324 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 297.11861
325 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 453.38977
326 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.42067
327 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72066
328 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 453.38977
329 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 453.38977
330 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 453.38977
331 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.42067
332 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 32359.96054
333 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 3.32164
334 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 475.38115
335 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
336 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 453.38977
337 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 271.92793
338 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.90624
339 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
340 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 271.92793
341 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 271.92793
342 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 271.92793
343 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.90624
344 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 21532.27368
345 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.21021
346 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 307.36262
347 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
348 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 271.92793
349 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 331.46182
350 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.09048
351 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70527
352 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 331.46182
353 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 331.46182
354 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 331.46182
355 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.09048
356 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 25085.29065
357 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.57492
358 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 362.56379
359 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
360 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 331.46182
361 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 442.35164
362 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.38156
363 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72152
364 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 442.35164
365 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 442.35164
366 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 442.35164
367 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.38156
368 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 31701.73981
369 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 3.25408
370 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 465.19037
371 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
372 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 442.35164
373 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 271.88556
374 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.90609
375 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
376 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 271.88556
377 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 271.88556
378 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 271.88556
379 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.90609
380 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 21529.59512
381 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.20994
382 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 307.32094
383 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
384 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 271.88556
385 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 331.39826
386 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.09132
387 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70502
388 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 331.39826
389 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 331.39826
390 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 331.39826
391 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.09132
392 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 25080.53947
393 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.57443
394 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 362.49010
395 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
396 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 331.39826
397 PlantLoop BOILER LOOP Maximum Loop Flow Rate [ft3/min] 5.99888
398 PlantLoop BOILER LOOP Plant Loop Volume [ft3] 12.00097
399 Pump:VariableSpeed BOILER CIRC PUMP Design Flow Rate [ft3/min] 5.99888
400 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [Btu/h] 0.437271E+06
401 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [gal/min] 44.88446
402 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
403 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
404 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
405 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
406 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
407 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
408 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
409 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
410 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
411 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
412 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
413 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
414 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
415 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
416 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
417 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
418 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
419 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
420 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
421 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
422 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
423 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
424 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
425 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
426 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
427 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
428 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
429 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
430 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
431 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
432 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
433 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
434 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
435 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
436 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
437 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
438 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
439 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
440 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
441 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
442 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
443 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
444 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
445 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
446 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
447 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
448 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
449 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
450 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
451 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
452 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
453 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
454 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
455 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
456 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
457 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
458 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
459 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
460 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
461 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
462 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
463 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
464 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
465 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
466 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
467 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
468 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
469 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
470 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
471 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
472 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
473 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
474 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
475 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
476 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
477 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
478 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
479 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
480 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
481 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
482 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
483 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
484 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
485 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
486 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
487 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
488 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
489 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
490 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
491 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {ton} Standard Rated Net COP {Btuh/Btuh} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.1 3.51 11.98 12.72 12.23 12.64
2 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.1 3.41 11.63 12.33 12.19 -99999.
3 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.8 3.52 12.00 12.74 12.25 12.67
4 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.8 3.41 11.65 12.35 12.21 -99999.
5 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 0.9 3.52 12.00 12.74 12.25 12.67
6 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 0.9 3.41 11.65 12.35 12.21 -99999.
7 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.1 3.51 11.99 12.73 12.23 12.65
8 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.1 3.41 11.63 12.33 12.19 -99999.
9 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.8 3.52 12.00 12.74 12.25 12.67
10 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.8 3.41 11.65 12.35 12.21 -99999.
11 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 0.9 3.52 12.00 12.74 12.25 12.67
12 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 0.9 3.41 11.65 12.35 12.21 -99999.
13 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.3 3.49 11.89 12.62 12.13 12.49
14 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.3 3.38 11.52 12.21 12.07 -99999.
15 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.7 3.52 12.00 12.74 12.25 12.67
16 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.7 3.41 11.65 12.35 12.21 -99999.
17 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 1.0 3.50 11.95 12.69 12.20 12.59
18 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 1.0 3.40 11.59 12.29 12.15 -99999.
19 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.2 3.48 11.89 12.62 12.13 12.49
20 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.2 3.38 11.52 12.21 12.07 -99999.
21 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.6 3.52 12.00 12.74 12.25 12.67
22 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.6 3.41 11.65 12.35 12.21 -99999.
23 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 0.9 3.50 11.95 12.68 12.19 12.58
24 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 0.9 3.40 11.59 12.28 12.14 -99999.
25 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.4 3.48 11.89 12.62 12.13 12.48
26 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.4 3.38 11.52 12.21 12.07 -99999.
27 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 0.9 3.52 12.00 12.74 12.25 12.67
28 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 0.9 3.41 11.65 12.35 12.21 -99999.
29 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 1.1 3.51 11.98 12.71 12.22 12.63
30 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 1.0 3.41 11.62 12.32 12.18 -99999.
31 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.3 3.48 11.88 12.61 12.12 12.47
32 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.3 3.37 11.51 12.20 12.06 -99999.
33 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 0.9 3.52 12.00 12.74 12.25 12.67
34 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 0.9 3.41 11.65 12.35 12.21 -99999.
35 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 1.1 3.51 11.98 12.72 12.22 12.64
36 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 1.0 3.41 11.62 12.32 12.18 -99999.


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {Btu/h}
1 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 26026.80
2 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 18257.92
3 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 21915.28
4 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 24616.86
5 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 18258.70
6 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 21912.96
7 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 31131.05
8 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 16842.59
9 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 24551.35
10 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 29438.84
11 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 15385.60
12 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 22229.86
13 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 32596.41
14 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 20550.68
15 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 24517.16
16 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 31867.26
17 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 20547.68
18 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 24511.88


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB SizingPeriod:DesignDay 01/21 01/21 WinterDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
2 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB SizingPeriod:DesignDay 07/21 07/21 SummerDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
3 ANNUAL WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No SizingPeriod:DesignDay    
2 No SizingPeriod:DesignDay    
3 No      


Environment:WarmupDays

NumberofWarmupDays
1 6
2 6
3 6


Environment:Design Day Data

Max Dry-Bulb Temp {F} Temp Range {dC} Temp Range Ind Type Hum Ind Type Hum Ind Value at Max Temp Hum Ind Units Pressure {psi} Wind Direction {deg CW from N} Wind Speed {ft/min} Clearness Rain Snow
1 -26.9 0.00 DefaultMultipliers Wetbulb -32.70 {C} 14. 210 472.5 0.00 No No
2 86.18 12.40 DefaultMultipliers Wetbulb 21.10 {C} 14. 200 925.2 0.00 No No


Environment:Design Day Misc

DayOfYear ASHRAE A Coeff ASHRAE B Coeff ASHRAE C Coeff Solar Constant-Annual Variation Eq of Time {minutes} Solar Declination Angle {deg} Solar Model
1 21 1229.0 0.1415 5.7310E-002 1.0 -11.15 -20. ASHRAEClearSky
2 202 1084.4 0.2082 0.1365 1.0 -6.23 20.6 ASHRAETau


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaF} Std Dev Warmup Temperature Difference {deltaF} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {Btu/h} Std Dev Warmup Load Difference {Btu/h} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BREEZEWAY SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000913 0.000000453 Pass Pass 0.000000000 0.000000000 Pass Pass
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000026131 0.000147294 Pass Pass 0.005999804 0.010404914 Pass Pass
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000004067 0.000007656 Pass Pass 0.007301411 0.012577782 Pass Pass
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000010399 0.000017069 Pass Pass 0.005993219 0.010357163 Pass Pass
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000010094 0.000016502 Pass Pass 0.005994733 0.010359865 Pass Pass
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000004067 0.000007656 Pass Pass 0.007301060 0.012576875 Pass Pass
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000010410 0.000017087 Pass Pass 0.005993843 0.010358212 Pass Pass
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000001645 0.000002213 Pass Pass 0.007075150 0.011551270 Pass Pass
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000005437 0.000009160 Pass Pass 0.009155202 0.014911657 Pass Pass
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000005889 0.000009455 Pass Pass 0.007073932 0.011547295 Pass Pass
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000004005 0.000006407 Pass Pass 0.007074110 0.011548321 Pass Pass
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000004389 0.000007549 Pass Pass 0.009155229 0.014911245 Pass Pass
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000003654 0.000005531 Pass Pass 0.007076069 0.011551536 Pass Pass
14 ATTIC SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000067631 0.000058862 Pass Pass 0.000000000 0.000000000 Pass Pass
15 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000010731 0.000015787 Pass Pass 0.005467881 0.008472922 Pass Pass
16 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000010725 0.000015778 Pass Pass 0.005466491 0.008470714 Pass Pass
17 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000005253 0.000007883 Pass Pass 0.005467371 0.008473850 Pass Pass
18 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000003870 0.000006527 Pass Pass 0.006653017 0.010263773 Pass Pass
19 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000003869 0.000006525 Pass Pass 0.006651845 0.010261921 Pass Pass
20 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000006044 0.000008890 Pass Pass 0.005467004 0.008473048 Pass Pass
21 BREEZEWAY SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.363231887 0.207181930 Pass Pass 0.000000000 0.000000000 Pass Pass
22 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000038774 0.000223499 Pass Pass 0.179341832 0.110716025 Pass Pass
23 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000002398 0.000006313 Pass Pass 0.128335436 0.091328822 Pass Pass
24 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000026069 0.000142102 Pass Pass 0.158286546 0.165688263 Pass Pass
25 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000036295 0.000214211 Pass Pass 0.175914719 0.112277079 Pass Pass
26 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000001342 0.000002921 Pass Pass 0.115028671 0.095148795 Pass Pass
27 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000005265 0.000018124 Pass Pass 0.156198827 0.173550970 Pass Pass
28 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000045206 0.000265392 Pass Pass 0.113177564 0.050317361 Pass Pass
29 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000025982 0.000115554 Pass Pass 0.078200919 0.051007488 Pass Pass
30 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000040848 0.000197409 Pass Pass 0.098836017 0.092139147 Pass Pass
31 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000029407 0.000186214 Pass Pass 0.110371016 0.049960105 Pass Pass
32 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000014039 0.000093049 Pass Pass 0.068051227 0.050542960 Pass Pass
33 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000024568 0.000121978 Pass Pass 0.096369935 0.096994178 Pass Pass
34 ATTIC SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.511543962 0.349562361 Pass Pass 0.000000000 0.000000000 Pass Pass
35 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000005149 0.000016275 Pass Pass 0.095058459 0.098409179 Pass Pass
36 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000040852 0.000201230 Pass Pass 0.098327359 0.093828167 Pass Pass
37 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000047330 0.000274542 Pass Pass 0.115952883 0.050582383 Pass Pass
38 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000001601 0.000003450 Pass Pass 0.075392047 0.047789809 Pass Pass
39 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000002455 0.000006289 Pass Pass 0.081143669 0.053716763 Pass Pass
40 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000031245 0.000197975 Pass Pass 0.113290808 0.048095310 Pass Pass
41 BREEZEWAY RunPeriod: ANNUAL 0.168717176 0.112073176 Pass Pass 0.000000000 0.000000000 Pass Pass
42 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000026053 0.000093145 Pass Pass 0.039905117 0.039205990 Pass Pass
43 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000138655 0.000377252 Pass Pass 0.034893964 0.032608489 Pass Pass
44 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000042034 0.000144955 Pass Pass 0.034535675 0.041030280 Pass Pass
45 LIVING_UNIT1_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000025482 0.000050503 Pass Pass 0.025869991 0.027023413 Pass Pass
46 LIVING_UNIT2_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000127824 0.000326394 Pass Pass 0.020079866 0.021167623 Pass Pass
47 LIVING_UNIT3_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000037890 0.000121385 Pass Pass 0.021609892 0.026519227 Pass Pass
48 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000029463 0.000173941 Pass Pass 0.053986960 0.050779978 Pass Pass
49 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000080697 0.000271282 Pass Pass 0.050139925 0.042382086 Pass Pass
50 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000031782 0.000109368 Pass Pass 0.042785038 0.044452283 Pass Pass
51 LIVING_UNIT1_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000009268 0.000014938 Pass Pass 0.026673631 0.027822626 Pass Pass
52 LIVING_UNIT2_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000050469 0.000177671 Pass Pass 0.019701558 0.023621558 Pass Pass
53 LIVING_UNIT3_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000013250 0.000046087 Pass Pass 0.021572758 0.027493470 Pass Pass
54 ATTIC RunPeriod: ANNUAL 0.322463322 0.273695862 Pass Pass 0.000000000 0.000000000 Pass Pass
55 LIVING_UNIT3_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.000040111 0.000148850 Pass Pass 0.019546027 0.021813948 Pass Pass
56 LIVING_UNIT3_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.000044728 0.000165243 Pass Pass 0.031763355 0.033910268 Pass Pass
57 LIVING_UNIT1_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.000021959 0.000043752 Pass Pass 0.037804865 0.034083907 Pass Pass
58 LIVING_UNIT2_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.000022730 0.000064513 Pass Pass 0.018257960 0.019118427 Pass Pass
59 LIVING_UNIT2_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.000069660 0.000232419 Pass Pass 0.033012250 0.029324989 Pass Pass
60 LIVING_UNIT1_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.000034449 0.000131011 Pass Pass 0.022923690 0.023022102 Pass Pass



Table of Contents

Report: Annual Heat Emissions Report

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Annual Heat Emissions Summary

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kBtu] 2158644.82 545740.11 291415.33 0.00 278669.88 3274476.00



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Heat Index Hours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
BREEZEWAY 8539.67 219.67 0.67 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 8188.33 379.17 166.83 25.67 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 8188.33 0.00 0.00 0.00 0.00
Max 8760.00 379.17 166.83 25.67 0.00
Average 8720.40 29.94 8.37 1.28 0.00
Sum 174408.00 598.83 167.50 25.67 0.00


Heat Index OccupantHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12062.38 0.00 0.00 0.00 0.00
Average 10856.14 0.00 0.00 0.00 0.00
Sum 217122.86 0.00 0.00 0.00 0.00


Heat Index OccupiedHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 7884.00 0.00 0.00 0.00 0.00
Sum 157680.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BREEZEWAY 8739.50 20.50 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8621.67 138.33 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8632.67 127.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8636.50 123.50 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8616.33 143.67 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8612.00 148.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8630.50 129.50 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8756.50 3.50 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8756.67 3.33 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8756.50 3.50 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8756.67 3.33 0.00 0.00 0.00
ATTIC 8085.67 574.50 84.50 15.33 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8752.50 7.50 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8752.50 7.50 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8751.83 8.17 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8755.83 4.17 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8755.83 4.17 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8751.83 8.17 0.00 0.00 0.00
Min 8085.67 0.00 0.00 0.00 0.00
Max 8760.00 574.50 84.50 15.33 0.00
Average 8682.08 72.93 4.23 0.77 0.00
Sum 173641.50 1458.67 84.50 15.33 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 11847.85 214.53 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 11883.76 178.62 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 11861.44 200.94 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 11841.12 221.26 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 11869.51 192.87 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 11850.95 211.44 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12060.69 1.69 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12060.77 1.61 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12060.69 1.69 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12060.77 1.61 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12055.12 7.27 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 12055.33 7.05 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12053.70 8.68 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12060.37 2.02 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12060.37 2.02 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12053.74 8.64 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12062.38 221.26 0.00 0.00 0.00
Average 10793.05 63.10 0.00 0.00 0.00
Sum 215860.93 1261.93 0.00 0.00 0.00


Humidex OccupiedHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8621.67 138.33 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8632.67 127.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8636.50 123.50 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8616.33 143.67 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8612.00 148.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8630.50 129.50 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8756.50 3.50 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8756.67 3.33 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8756.50 3.50 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8756.67 3.33 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8752.50 7.50 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8752.50 7.50 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8751.83 8.17 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8755.83 4.17 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8755.83 4.17 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8751.83 8.17 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 148.00 0.00 0.00 0.00
Average 7840.82 43.18 0.00 0.00 0.00
Sum 156816.33 863.67 0.00 0.00 0.00


Hours of Safety for Cold Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7884.00 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Hours of Safety for Heat Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7884.00 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Unmet Degree-Hours

Cooling Setpoint Unmet Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] Heating Setpoint Unmet Degree-Hours [°F·hr] Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Heating Setpoint Unmet Occupied Degree-Hours [°C·hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.10 0.10 0.10 132.57 172.62 132.57
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.04 0.07 0.04 30.64 30.15 30.64
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.08 0.09 0.08 21.97 41.54 21.97
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.08 0.09 0.08 382.26 252.30 382.26
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.04 0.07 0.04 64.38 62.00 64.38
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.05 0.07 0.05 14.66 28.27 14.66
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.13 0.14 0.13 29.36 29.57 29.36
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.16 0.15 0.16 17.11 17.48 17.11
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.13 0.12 0.13 81.92 158.27 81.92
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.10 0.12 0.10 468.45 302.06 468.45
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.10 0.14 0.10 42.25 44.02 42.25
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.09 0.10 0.09 50.97 100.20 50.97
ATTIC 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.07 0.08 0.07 31.80 62.91 31.80
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.14 0.11 0.14 50.03 97.90 50.03
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.12 0.13 0.12 145.25 143.87 145.25
LIVING_UNIT2_BACKROW_TOPFLOOR 0.05 0.07 0.05 47.50 51.89 47.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.09 0.09 0.09 18.11 19.38 18.11
LIVING_UNIT1_BACKROW_TOPFLOOR 0.09 0.10 0.09 367.65 227.27 367.65
Min 0.00 0.00 0.00 0.00 0.00 0.00
Max 0.16 0.15 0.16 468.45 302.06 468.45
Average 0.08 0.09 0.08 99.84 92.09 99.84
Sum 1.66 1.86 1.66 1996.88 1841.72 1996.88


Discomfort-weighted Exceedance OccupantHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00


Discomfort-weighted Exceedance OccupiedHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB -26.9 0.00 -26.9 Wetbulb [F] 472.46 210.00
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 86.18 22.32 69.98 Wetbulb [F] 925.24 200.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [in] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [in] Monthly Total Roof Irrigation Depth [in] Monthly Total Rain Collection Volume [ft3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.47 13      
Apr 0.63 23      
May 0.00 0      
Jun 7.48 53      
Jul 5.35 41      
Aug 3.43 42      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BREEZEWAYROOF INTERIOR CEILING 0.30 0.022 0.022 599.39 599.39 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
iz-BREEZEWAYROOF ATTIC FLOOR 0.30 0.022 0.022 599.39 599.39 0.00 180.00  
iz-CEILING_UNIT3_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  


Exterior Fenestration

Construction Frame and Divider Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average             2126.74 0.300 0.335 0.883                      
North Total or Average             531.68 0.300 0.335 0.883                      
Non-North Total or Average             1595.05 0.300 0.335 0.883                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [Btu/h-ft2] Space Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.4397 1200.55 527.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 475.00
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total       0.3110 43219.92 13441.11               12093.82


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
Exterior Lighting Total 1377.69           6034.31



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Central Plant

Type Reference Capacity [Btu/h] Reference Efficiency [Btuh/Btuh] Rated Capacity [Btu/h] Rated Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 437271.13 0.80        


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   14030.27 9883.03 4147.25 0.70 4.09    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9506.36 6664.75 2841.61 0.70 4.09    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   11692.14 8197.16 3494.98 0.70 4.09    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   13230.02 9309.30 3920.72 0.70 4.09    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9506.83 6665.08 2841.75 0.70 4.09    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   11690.76 8196.19 3494.56 0.70 4.09    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   16242.21 11698.05 4544.15 0.72 4.09    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8666.87 6076.20 2590.67 0.70 4.09    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   12935.33 9178.36 3756.97 0.71 4.09    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   15262.42 10996.69 4265.73 0.72 4.09    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   7805.56 5472.34 2333.21 0.70 4.09    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   11535.71 8195.54 3340.17 0.71 4.09    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   17048.08 12285.83 4762.24 0.72 4.09    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10874.92 7624.22 3250.70 0.70 4.09    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13085.76 9229.01 3856.75 0.71 4.09    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   16578.76 11961.84 4616.93 0.72 4.09    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10873.13 7622.97 3250.16 0.70 4.09    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13095.84 9232.84 3863.00 0.71 4.09    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.1 3.51 11.98 12.72 12.23 12.64
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.8 3.52 12.00 12.74 12.25 12.67
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.9 3.52 12.00 12.74 12.25 12.67
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.1 3.51 11.99 12.73 12.23 12.65
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.8 3.52 12.00 12.74 12.25 12.67
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.9 3.52 12.00 12.74 12.25 12.67
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.3 3.49 11.89 12.62 12.13 12.49
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.7 3.52 12.00 12.74 12.25 12.67
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   1.0 3.50 11.95 12.69 12.20 12.59
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.2 3.48 11.89 12.62 12.13 12.49
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.6 3.52 12.00 12.74 12.25 12.67
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.9 3.50 11.95 12.68 12.19 12.58
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.4 3.48 11.89 12.62 12.13 12.48
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.9 3.52 12.00 12.74 12.25 12.67
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.1 3.51 11.98 12.71 12.22 12.63
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.3 3.48 11.88 12.61 12.12 12.47
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.9 3.52 12.00 12.74 12.25 12.67
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.1 3.51 11.98 12.72 12.22 12.64
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coils [ SEER2 ]

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP2 [Btuh/Btuh] EER2 [Btu/W-h] SEER2 User [Btu/W-h] SEER2 Standard [Btu/W-h] IEER2 [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.41 11.63 12.33 12.19  
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.8 3.41 11.65 12.35 12.21  
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.41 11.65 12.35 12.21  
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.41 11.63 12.33 12.19  
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.8 3.41 11.65 12.35 12.21  
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.41 11.65 12.35 12.21  
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.3 3.38 11.52 12.21 12.07  
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.7 3.41 11.65 12.35 12.21  
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.0 3.40 11.59 12.29 12.15  
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.2 3.38 11.52 12.21 12.07  
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.6 3.41 11.65 12.35 12.21  
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.40 11.59 12.28 12.14  
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.4 3.38 11.52 12.21 12.07  
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.41 11.65 12.35 12.21  
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.0 3.41 11.62 12.32 12.18  
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.3 3.37 11.51 12.20 12.06  
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.41 11.65 12.35 12.21  
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.0 3.41 11.62 12.32 12.18  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER2 User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER2 Standard is calculated using AHRI Std 210/240-2023 default PLF curve and cooling coefficient of degradation. IEER Calculation was removed from the 2023 Version of the Standard.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


Water-to-Air Heat Pumps at Rated Temperatures Report

Coil Type Rated Total Capacity [Btu/h] Rated Sensible Capacity [Btu/h] Rated Power[Btu/h] Rated COP [Btuh/Btuh] Rated Air Dry-bulb Temperature [F] Rated Air Wet-bulb Temperature [F] Rated Water Temperature [F] Design Day used for Sizing
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


DX Heating Coils [ HSPF2 ]

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF2 [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 26439.12 26026.82 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 19490.28 18257.92 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 22751.87 21915.26 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water 25172.70 24616.86 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water 19490.99 18258.71 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water 22749.81 21912.96 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 31036.80 31131.04 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 18237.01 16842.58 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 25115.54 24551.36 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water 29510.85 29438.84 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water 16951.95 15385.58 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water 23034.80 22229.88 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water 32359.96 32596.41 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water 21532.27 20550.68 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water 25085.29 24517.17 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water 31701.74 31867.26 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water 21529.60 20547.68 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water 25080.54 24511.88 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 354.16 133.59 0.38 1.00 2.53 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 237.71 89.66 0.38 1.00 3.16 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 292.36 110.28 0.38 1.00 2.80 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 332.93 125.58 0.38 1.00 2.61 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 237.72 89.67 0.38 1.00 3.16 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 292.33 110.26 0.38 1.00 2.80 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 431.23 162.66 0.38 1.00 2.29 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 216.72 81.74 0.38 1.00 3.35 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 332.00 125.23 0.38 1.00 2.61 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 405.66 153.01 0.38 1.00 2.36 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 195.18 73.62 0.38 1.00 3.58 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 297.12 112.07 0.38 1.00 2.78 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 453.38 171.01 0.38 1.00 2.24 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 271.93 102.57 0.38 1.00 2.92 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 331.47 125.03 0.38 1.00 2.62 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 442.35 166.85 0.38 1.00 2.26 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 271.88 102.55 0.38 1.00 2.92 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 331.39 125.00 0.38 1.00 2.62 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
BOILER CIRC PUMP Pump:VariableSpeed Intermittent 0.00 44.884442 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.82 0.60



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 7970.59 7970.59 6.64 354.157 354.157 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 75.00 0.00849 81.57 0.01272 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3831.11 3831.11 3.19 170.235 170.235 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 75.00 75.00 0.00909 86.18 0.01273 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5927.59 5927.59 4.94 263.376 263.376 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 75.00 75.00 0.00864 80.49 0.01272 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7492.91 7492.91 6.24 332.934 332.934 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 75.00 75.00 0.00857 80.27 0.01272 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3077.31 3077.31 2.56 136.733 136.733 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00970 77.48 0.01272 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5248.02 5248.02 4.37 233.177 233.177 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 75.00 75.00 0.00880 77.07 0.01272 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9705.34 9705.34 8.08 431.233 431.233 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 75.00 75.00 0.00826 80.82 0.01272 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4877.21 4877.21 4.06 216.717 216.717 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 75.00 75.00 0.00865 86.18 0.01273 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7472.01 7472.01 6.22 331.995 331.995 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 75.00 75.00 0.00833 81.05 0.01272 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9129.72 9129.72 7.60 405.659 405.659 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.00 75.00 0.00833 79.15 0.01272 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4127.17 4127.17 3.44 183.380 183.380 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 75.00 75.00 0.00912 76.66 0.01272 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6687.29 6687.29 5.57 297.123 297.123 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 75.00 75.00 0.00843 78.26 0.01272 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 6659.87 6659.87 5.55 295.909 295.909 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 75.00 75.00 0.00854 78.81 0.01272 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7425.05 7425.05 6.18 329.913 329.913 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 75.00 75.00 0.00844 81.05 0.01272 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 10203.64 10203.64 8.50 453.381 453.381 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 75.00 75.00 0.00832 80.27 0.01272 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 4983.64 4983.64 4.15 221.438 221.438 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 75.00 75.00 0.00902 76.66 0.01272 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 5201.25 5201.25 4.33 231.120 231.120 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 75.00 75.00 0.00873 86.18 0.01273 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9955.35 9955.35 8.29 442.350 442.350 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.00 75.00 0.00835 79.15 0.01272 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 15387.31 15387.31 12.82 292.228 292.228 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00626 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12516.36 12516.36 10.43 237.708 237.708 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00605 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 15394.48 15394.48 12.82 292.364 292.364 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00626 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 15390.44 15390.44 12.82 292.288 292.288 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00626 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12516.98 12516.98 10.43 237.720 237.720 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00605 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 15392.67 15392.67 12.82 292.330 292.330 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00626 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 13386.40 13386.40 11.15 254.245 254.245 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00644 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 10277.13 10277.13 8.56 195.195 195.195 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00619 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 13387.33 13387.33 11.15 254.263 254.263 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00644 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 13388.11 13388.11 11.15 254.278 254.278 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00644 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 10276.32 10276.32 8.56 195.180 195.180 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00619 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 13384.02 13384.02 11.15 254.200 254.200 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00644 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 17449.34 17449.34 14.53 331.389 331.389 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00642 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 17453.53 17453.53 14.54 331.469 331.469 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00642 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 17457.38 17457.38 14.54 331.542 331.542 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00642 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 14315.88 14315.88 11.92 271.885 271.885 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00623 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 14318.25 14318.25 11.93 271.930 271.930 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00623 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 17456.84 17456.84 14.54 331.532 331.532 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00642 -26.9 0.00018 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 354.16 354.16 292.23 292.23 354.1569 354.1569 354.1569 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 170.24 170.24 237.71 237.71 237.7084 237.7084 237.7084 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 263.38 263.38 292.36 292.36 292.3643 292.3643 292.3643 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 332.93 332.93 292.29 292.29 332.9337 332.9337 332.9337 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 136.73 136.73 237.72 237.72 237.7202 237.7202 237.7202 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 233.18 233.18 292.33 292.33 292.3299 292.3299 292.3299 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 431.23 431.23 254.25 254.25 431.2333 431.2333 431.2333 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 216.72 216.72 195.19 195.19 216.7170 216.7170 216.7170 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 332.00 332.00 254.26 254.26 331.9954 331.9954 331.9954 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 405.66 405.66 254.28 254.28 405.6591 405.6591 405.6591 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 183.38 183.38 195.18 195.18 195.1796 195.1796 195.1796 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 297.12 297.12 254.20 254.20 297.1231 297.1231 297.1231 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 453.38 453.38 331.54 331.54 453.3812 453.3812 453.3812 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 231.12 231.12 271.93 271.93 271.9297 271.9297 271.9297 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.91 329.91 331.47 331.47 331.4690 331.4690 331.4690 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 442.35 442.35 331.53 331.53 442.3505 442.3505 442.3505 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 221.44 221.44 271.88 271.88 271.8848 271.8848 271.8848 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 295.91 295.91 331.39 331.39 331.3894 331.3894 331.3894 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 14030.274 9883.028 354.156908 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 14116.62 11388.09 354.156908 77.05 62.15 0.00902524 53.60 50.67 0.00750000 81.57 0.01272136 68.68 12.7048 75.00 0.00847473 44.0156 7959.22 0.00 14036.13 9707.73
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 26439.117 26439.117 354.156908 0.36271529 383.648 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 26439.12 23330.36 354.156908 59.43 49.36 0.00548726 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 12.7048 71.98 0.00625918 36.1006 15387.31 0.00 26015.96 26015.96
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 9506.356 6664.746 237.708447 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 9605.87 6991.96 237.708447 79.17 64.34 0.01005360 53.60 50.67 0.00750000 86.18 0.01272586 70.04 18.9286 75.00 0.00909354 47.1850 3831.11 0.00 9510.32 6547.16
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 19490.284 19490.284 237.708447 0.26738502 275.526 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 19490.28 17198.59 237.708447 53.28 45.48 0.00493829 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 18.9286 71.99 0.00604847 34.8960 12516.36 0.00 18242.61 18242.61
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 11692.136 8197.160 292.364341 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 11909.00 9246.72 292.364341 77.16 62.65 0.00933937 53.60 50.67 0.00750000 80.49 0.01272031 68.36 15.3900 75.00 0.00863851 44.8540 5906.71 0.00 11697.01 8052.54
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 22751.870 22751.870 292.364341 0.31213035 326.345 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 22751.87 20076.67 292.364341 56.77 47.87 0.00532463 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 15.3900 71.98 0.00625979 36.1041 15394.48 0.00 21903.38 21903.38
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 13230.021 9309.297 332.933692 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 13424.45 10677.57 332.933692 76.93 62.26 0.00913073 53.60 50.67 0.00750000 80.27 0.01272010 68.29 13.5147 75.00 0.00856337 44.4698 7486.20 0.00 13235.54 9143.60
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 25172.699 25172.699 332.933692 0.34534143 363.984 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 25172.70 22212.85 332.933692 58.63 48.92 0.00543828 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 13.5147 71.98 0.00625945 36.1021 15390.44 0.00 24605.68 24605.68
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 9506.826 6665.076 237.720215 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 10114.50 6732.08 237.720215 77.03 64.56 0.01069593 53.60 50.67 0.00750000 77.48 0.01271739 67.44 18.9277 75.00 0.00970445 50.3040 3077.31 0.00 9510.79 6547.49
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 19490.986 19490.986 237.720215 0.26739466 275.537 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 19490.99 17199.21 237.720215 53.28 45.48 0.00493840 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 18.9277 71.99 0.00604854 34.8964 12516.98 0.00 18243.40 18243.40
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 11690.756 8196.193 292.329851 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 12150.02 9147.56 292.329851 76.62 62.79 0.00955803 53.60 50.67 0.00750000 77.07 0.01271700 67.32 15.3919 75.00 0.00878389 45.5978 5214.87 0.00 11695.63 8051.59
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 22749.812 22749.812 292.329851 0.31210211 326.313 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 22749.81 20074.85 292.329851 56.77 47.87 0.00532439 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 15.3919 71.98 0.00625964 36.1032 15392.67 0.00 21901.08 21901.08
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 16242.205 11698.055 431.233270 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 16302.87 13648.55 431.233270 76.83 61.63 0.00872837 53.60 50.67 0.00750000 80.82 0.01272064 68.46 10.4340 75.00 0.00825783 42.9036 9691.05 0.00 16248.98 11479.31
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 31036.800 31036.800 431.233270 0.42579037 454.893 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 31036.80 27387.44 431.233270 61.67 50.90 0.00578578 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 10.4340 71.99 0.00643843 37.1195 13386.40 0.00 31124.44 31124.44
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 8666.875 6076.200 216.717042 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 8634.70 6648.21 216.717042 78.54 63.34 0.00949955 53.60 50.67 0.00750000 86.18 0.01272586 70.04 20.7621 75.00 0.00865418 44.9358 4877.21 0.00 8670.49 5969.00
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 18237.011 18237.011 216.717042 0.25019151 255.879 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 18237.01 16092.67 216.717042 51.47 44.63 0.00494330 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 20.7621 71.99 0.00619050 35.7032 10277.13 0.00 16828.26 16828.26
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 12935.326 9178.360 331.995354 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 13025.87 10645.37 331.995354 77.04 61.99 0.00892284 53.60 50.67 0.00750000 81.05 0.01272086 68.52 13.5529 75.00 0.00832572 43.2510 7458.04 0.00 12940.72 9012.22
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 25115.540 25115.540 331.995354 0.34455727 363.033 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 25115.54 22162.41 331.995354 58.59 49.20 0.00559076 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 13.5529 71.99 0.00643852 37.1200 13387.33 0.00 24542.74 24542.74
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 15262.420 10996.693 405.659055 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 15471.78 12789.62 405.659055 76.68 61.71 0.00881781 53.60 50.67 0.00750000 79.15 0.01271901 67.95 11.0918 75.00 0.00832301 43.2378 9125.31 0.00 15268.79 10791.34
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 29510.855 29510.855 405.659055 0.40485611 431.254 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 29510.85 26040.92 405.659055 61.02 50.55 0.00574477 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 11.0918 71.99 0.00643859 37.1204 13388.11 0.00 29431.76 29431.76
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 7805.556 5472.344 195.179594 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 8203.83 5862.90 195.179594 76.62 63.44 0.01000411 53.60 50.67 0.00750000 76.66 0.01271660 67.19 23.0531 75.00 0.00913866 47.4135 4109.83 0.00 7808.81 5375.80
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 16951.952 16951.952 195.179594 0.23256193 235.723 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 16951.95 14958.71 195.179594 49.20 43.25 0.00480559 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 23.0531 71.99 0.00619040 35.7026 10276.32 0.00 15370.64 15370.64
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 11535.709 8195.543 297.123078 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 11808.90 9436.59 297.123078 76.71 62.12 0.00908156 53.60 50.67 0.00750000 78.26 0.01271815 67.68 15.1436 75.00 0.00842007 43.7346 6666.86 0.00 11540.52 8043.88
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 23034.804 23034.804 297.123078 0.31601190 330.690 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 23034.80 20326.34 297.123078 57.02 48.31 0.00549101 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 15.1436 71.99 0.00643821 37.1183 13384.02 0.00 22220.41 22220.41
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 17048.075 12285.834 453.381249 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 17165.39 14309.61 453.381249 76.74 61.64 0.00875680 53.60 50.67 0.00750000 80.27 0.01272010 68.29 9.9243 75.00 0.00831464 43.1953 10203.05 0.00 17055.19 12050.23
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 32359.961 32359.961 453.381249 0.44394267 475.381 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 32359.96 28555.03 453.381249 62.17 51.14 0.00580159 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 9.9243 71.98 0.00642059 37.0220 17457.38 0.00 32589.87 32589.87
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 10874.921 7624.225 271.929722 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 10829.67 8319.08 271.929722 78.39 63.31 0.00950993 53.60 50.67 0.00750000 86.18 0.01272586 70.04 16.5465 75.00 0.00873249 45.3375 5201.25 0.00 10879.46 7489.71
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 21532.274 21532.274 271.929722 0.29539885 307.363 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 21532.27 19000.48 271.929722 55.63 47.17 0.00523286 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 16.5465 71.99 0.00623404 35.9560 14318.25 0.00 20538.08 20538.08
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 13085.760 9229.014 331.468994 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 13201.97 10653.80 331.468994 77.04 62.14 0.00902210 53.60 50.67 0.00750000 81.05 0.01272086 68.52 13.5744 75.00 0.00843585 43.8159 7421.97 0.00 13091.22 9061.70
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 25085.291 25085.291 331.468994 0.34414229 362.564 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 25085.29 22135.72 331.468994 58.57 49.15 0.00557369 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 13.5744 71.98 0.00642032 37.0204 17453.53 0.00 24508.27 24508.27
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 16578.765 11961.835 442.350485 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 16797.43 13918.18 442.350485 76.64 61.67 0.00879819 53.60 50.67 0.00750000 79.15 0.01271901 67.95 10.1718 75.00 0.00834697 43.3611 9951.40 0.00 16585.68 11733.32
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 31701.740 31701.740 442.350485 0.43491261 465.190 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 31701.74 27974.20 442.350485 61.93 51.01 0.00578612 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 10.1718 71.98 0.00642055 37.0218 17456.84 0.00 31860.54 31860.54
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 10873.126 7622.966 271.884834 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 11369.36 8343.93 271.884834 76.55 63.07 0.00976847 53.60 50.67 0.00750000 76.66 0.01271660 67.19 16.5493 75.00 0.00903298 46.8735 4968.54 0.00 10877.66 7488.48
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 21529.595 21529.595 271.884834 0.29536210 307.321 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 21529.60 18998.11 271.884834 55.63 47.17 0.00523251 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 16.5493 71.99 0.00623382 35.9547 14315.88 0.00 20535.08 20535.08
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 13095.838 9232.840 331.389374 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 13395.76 10583.09 331.389374 76.80 62.29 0.00917705 53.60 50.67 0.00750000 78.81 0.01271869 67.85 13.5777 75.00 0.00853136 44.3052 6631.28 0.00 13101.30 9065.28
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 25080.539 25080.539 331.389374 0.34407711 362.490 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 25080.54 22131.53 331.389374 58.56 49.15 0.00557323 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 13.5777 71.98 0.00642002 37.0187 17449.34 0.00 24502.98 24502.98



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [Btu/lbm-R] Dry Air Heat Capacity [Btu/lbm-R] Standard Air Density Adjusted for Elevation [lb/ft3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [ft3/min] Supply Fan Maximum Air Mass Flow Rate [lb/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [Btu/lbm-R] Plant Fluid Density [lb/ft3] Plant Maximum Fluid Mass Flow Rate [lb/s] Plant Design Fluid Return Temperature [F] Plant Design Fluid Supply Temperature [F] Plant Design Fluid Temperature Difference [deltaF] Plant Design Capacity [Btu/h] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [F] System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h] Coil Air Mass Flow Rate at Rating Conditions [lb/s] Coil Entering Air Drybulb at Rating Conditions [F] Coil Entering Air Wetbulb at Rating Conditions [F] Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] Coil Leaving Air Drybulb at Rating Conditions [F] Coil Leaving Air Wetbulb at Rating Conditions [F] Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 14030.274 9883.028 354.156908 -999. -999.00 -999.0000 1.00000 1.00000 0.2440 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 354.156908 0.42525076   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 14116.62 11388.09 1.0062 0.42525076 354.156908 77.05 62.15 0.00902524 11.5 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 455.793 13660.82 81.57 0.01272136 68.68 44.99498340 12.7048 75.00 0.00848731 75.00 0.00847473 44.0156 7959.22 0.00 14036.13 9707.73 0.40845657 80.00 67.00 0.01118466 13.2 52.92 52.90 0.00850009 7.9
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 26439.117 26439.117 354.156908 0.36271529 383.648 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 354.156908 0.42525076   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 5.9271 6.046390 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 26439.12 23330.36 1.0000 0.42525076 354.156908 59.43 49.36 0.00548726 7.0 122.00 74.22 0.00800000 17.0 0.37739263 140.00 120.20 19.80 0.000 26439.12 -26.9 0.00018338 -26.9 44.99498340 12.7048 71.98 0.00625918 71.98 0.00625918 36.1006 15387.31 0.00 26015.96 26015.96 0.42525076 61.88 51.09 0.00548726 7.3 131.98 74.87 0.00548726 16.7
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 9506.356 6664.746 237.708447 -999. -999.00 -999.0000 1.00000 0.82905 0.2445 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 237.708447 0.28542631   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 Sensible 9605.87 6991.96 1.0105 0.28542631 237.708447 79.17 64.34 0.01005360 12.4 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 305.926 9299.94 86.18 0.01272586 70.04 44.99498340 18.9286 75.00 0.00909354 75.00 0.00909354 47.1850 3831.11 0.00 9510.32 6547.16 0.27415413 80.00 67.00 0.01118466 13.2 52.78 52.74 0.00844654 7.9
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 19490.284 19490.284 237.708447 0.26738502 275.526 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 237.708447 0.28542631   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 4.3693 4.457254 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 19490.28 17198.59 1.0000 0.28542631 237.708447 53.28 45.48 0.00493829 5.8 122.00 74.22 0.00800000 17.0 0.27820481 140.00 120.20 19.80 0.000 19490.28 -26.9 0.00018338 -26.9 44.99498340 18.9286 71.99 0.00604847 71.99 0.00604847 34.8960 12516.36 0.00 18242.61 18242.61 0.28542631 61.88 50.02 0.00493829 7.0 135.19 75.08 0.00493829 16.8
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11692.136 8197.160 292.364341 -999. -999.00 -999.0000 1.00000 0.97321 0.2441 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 292.364341 0.35105389   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 Sensible 11909.00 9246.72 1.0185 0.35105389 292.364341 77.16 62.65 0.00933937 11.7 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 376.267 11532.73 80.49 0.01272031 68.36 44.99498340 15.3900 75.00 0.00864276 75.00 0.00863851 44.8540 5906.71 0.00 11697.01 8052.54 0.33718991 80.00 67.00 0.01118466 13.2 52.78 52.74 0.00844654 7.9
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 22751.870 22751.870 292.364341 0.31213035 326.345 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 292.364341 0.35105389   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 5.1005 5.203149 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 22751.87 20076.67 1.0000 0.35105389 292.364341 56.77 47.87 0.00532463 6.5 122.00 74.22 0.00800000 17.0 0.32476076 140.00 120.20 19.80 0.000 22751.87 -26.9 0.00018338 -26.9 44.99498340 15.3900 71.98 0.00625979 71.98 0.00625979 36.1041 15394.48 0.00 21903.38 21903.38 0.35105389 61.88 50.77 0.00532463 7.2 133.39 75.06 0.00532463 16.8
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13230.021 9309.297 332.933692 -999. -999.00 -999.0000 1.00000 1.00000 0.2441 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 332.933692 0.39976718   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 Sensible 13424.45 10677.57 1.0147 0.39976718 332.933692 76.93 62.26 0.00913073 11.5 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 428.479 12995.97 80.27 0.01272010 68.29 44.99498340 13.5147 75.00 0.00856983 75.00 0.00856337 44.4698 7486.20 0.00 13235.54 9143.60 0.38397939 80.00 67.00 0.01118466 13.2 52.86 52.85 0.00848497 7.9
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 25172.699 25172.699 332.933692 0.34534143 363.984 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 332.933692 0.39976718   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 5.6432 5.756771 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 25172.70 22212.85 1.0000 0.39976718 332.933692 58.63 48.92 0.00543828 6.8 122.00 74.22 0.00800000 17.0 0.35931574 140.00 120.20 19.80 0.000 25172.70 -26.9 0.00018338 -26.9 44.99498340 13.5147 71.98 0.00625945 71.98 0.00625945 36.1021 15390.44 0.00 24605.68 24605.68 0.39976718 61.88 50.99 0.00543828 7.3 132.41 74.93 0.00543828 16.8
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 9506.826 6665.076 237.720215 -999. -999.00 -999.0000 1.00000 0.85582 0.2448 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 237.720215 0.28544044   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 10114.50 6732.08 1.0639 0.28544044 237.720215 77.03 64.56 0.01069593 12.5 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 305.942 9808.56 77.48 0.01271739 67.44 44.99498340 18.9277 75.00 0.00970445 75.00 0.00970445 50.3040 3077.31 0.00 9510.79 6547.49 0.27416770 80.00 67.00 0.01118466 13.2 52.78 52.74 0.00844654 7.9
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 19490.986 19490.986 237.720215 0.26739466 275.537 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 237.720215 0.28544044   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 4.3695 4.457414 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 19490.99 17199.21 1.0000 0.28544044 237.720215 53.28 45.48 0.00493840 5.8 122.00 74.22 0.00800000 17.0 0.27821483 140.00 120.20 19.80 0.000 19490.99 -26.9 0.00018338 -26.9 44.99498340 18.9277 71.99 0.00604854 71.99 0.00604854 34.8964 12516.98 0.00 18243.40 18243.40 0.28544044 61.88 50.02 0.00493840 7.0 135.19 75.08 0.00493840 16.8
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11690.756 8196.193 292.329851 -999. -999.00 -999.0000 1.00000 0.97939 0.2442 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 292.329851 0.35101247   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 Sensible 12150.02 9147.56 1.0393 0.35101247 292.329851 76.62 62.79 0.00955803 11.8 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 376.223 11773.80 77.07 0.01271700 67.32 44.99498340 15.3919 75.00 0.00880271 75.00 0.00878389 45.5978 5214.87 0.00 11695.63 8051.59 0.33715014 80.00 67.00 0.01118466 13.2 52.78 52.74 0.00844654 7.9
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 22749.812 22749.812 292.329851 0.31210211 326.313 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 292.329851 0.35101247   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 5.1000 5.202679 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 22749.81 20074.85 1.0000 0.35101247 292.329851 56.77 47.87 0.00532439 6.5 122.00 74.22 0.00800000 17.0 0.32473139 140.00 120.20 19.80 0.000 22749.81 -26.9 0.00018338 -26.9 44.99498340 15.3919 71.98 0.00625964 71.98 0.00625964 36.1032 15392.67 0.00 21901.08 21901.08 0.35101247 61.88 50.77 0.00532439 7.2 133.39 75.06 0.00532439 16.8
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 16242.205 11698.055 431.233270 -999. -999.00 -999.0000 1.00000 1.00000 0.2439 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 431.233270 0.51779952   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 Sensible 16302.87 13648.55 1.0037 0.51779952 431.233270 76.83 61.63 0.00872837 11.3 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 554.989 15747.88 80.82 0.01272064 68.46 44.99498340 10.4340 75.00 0.00826329 75.00 0.00825783 42.9036 9691.05 0.00 16248.98 11479.31 0.49735035 80.00 67.00 0.01118466 13.2 53.71 53.69 0.00875515 8.2
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 31036.800 31036.800 431.233270 0.42579037 454.893 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 431.233270 0.51779952   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 6.9578 7.097839 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 31036.80 27387.44 1.0000 0.51779952 431.233270 61.67 50.90 0.00578578 7.5 122.00 74.22 0.00800000 17.0 0.44302006 140.00 120.20 19.80 0.000 31036.80 -26.9 0.00018338 -26.9 44.99498340 10.4340 71.99 0.00643843 71.99 0.00643843 37.1195 13386.40 0.00 31124.44 31124.44 0.51779952 61.88 51.65 0.00578578 7.5 130.72 74.89 0.00578578 16.8
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 8666.875 6076.200 216.717042 -999. -999.00 -999.0000 1.00000 0.89281 0.2442 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 216.717042 0.26022107   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 Sensible 8634.70 6648.21 0.9963 0.26022107 216.717042 78.54 63.34 0.00949955 12.0 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 278.911 8355.78 86.18 0.01272586 70.04 44.99498340 20.7621 75.00 0.00865418 75.00 0.00865418 44.9358 4877.21 0.00 8670.49 5969.00 0.24994430 80.00 67.00 0.01118466 13.2 52.78 52.74 0.00844654 7.9
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 18237.011 18237.011 216.717042 0.25019151 255.879 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 216.717042 0.26022107   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 4.0884 4.170641 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 18237.01 16092.67 1.0000 0.26022107 216.717042 51.47 44.63 0.00494330 5.6 122.00 74.22 0.00800000 17.0 0.26031556 140.00 120.20 19.80 0.000 18237.01 -26.9 0.00018338 -26.9 44.99498340 20.7621 71.99 0.00619050 71.99 0.00619050 35.7032 10277.13 0.00 16828.26 16828.26 0.26022107 61.88 50.03 0.00494330 7.0 136.05 75.31 0.00494330 17.0
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 12935.326 9178.360 331.995354 -999. -999.00 -999.0000 1.00000 1.00000 0.2440 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 331.995354 0.39864047   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 Sensible 13025.87 10645.37 1.0070 0.39864047 331.995354 77.04 61.99 0.00892284 11.4 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 427.272 12598.60 81.05 0.01272086 68.52 44.99498340 13.5529 75.00 0.00832740 75.00 0.00832572 43.2510 7458.04 0.00 12940.72 9012.22 0.38289719 80.00 67.00 0.01118466 13.2 53.18 53.16 0.00858547 8.0
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 25115.540 25115.540 331.995354 0.34455727 363.033 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 331.995354 0.39864047   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 5.6304 5.743699 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 25115.54 22162.41 1.0000 0.39864047 331.995354 58.59 49.20 0.00559076 6.9 122.00 74.22 0.00800000 17.0 0.35849985 140.00 120.20 19.80 0.000 25115.54 -26.9 0.00018338 -26.9 44.99498340 13.5529 71.99 0.00643852 71.99 0.00643852 37.1200 13387.33 0.00 24542.74 24542.74 0.39864047 61.88 51.28 0.00559076 7.4 132.41 75.11 0.00559076 16.9
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 15262.420 10996.693 405.659055 -999. -999.00 -999.0000 1.00000 1.00000 0.2439 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 405.659055 0.48709151   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 15471.78 12789.62 1.0137 0.48709151 405.659055 76.68 61.71 0.00881781 11.3 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 522.076 14949.70 79.15 0.01271901 67.95 44.99498340 11.0918 75.00 0.00833111 75.00 0.00832301 43.2378 9125.31 0.00 15268.79 10791.34 0.46785508 80.00 67.00 0.01118466 13.2 53.73 53.71 0.00876022 8.2
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 29510.855 29510.855 405.659055 0.40485611 431.254 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 405.659055 0.48709151   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 6.6157 6.748869 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 29510.85 26040.92 1.0000 0.48709151 405.659055 61.02 50.55 0.00574477 7.3 122.00 74.22 0.00800000 17.0 0.42123869 140.00 120.20 19.80 0.000 29510.85 -26.9 0.00018338 -26.9 44.99498340 11.0918 71.99 0.00643859 71.99 0.00643859 37.1204 13388.11 0.00 29431.76 29431.76 0.48709151 61.88 51.58 0.00574477 7.5 131.08 74.94 0.00574477 16.8
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 7805.556 5472.344 195.179594 -999. -999.00 -999.0000 1.00000 0.93229 0.2444 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 195.179594 0.23436017   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 Sensible 8203.83 5862.90 1.0510 0.23436017 195.179594 76.62 63.44 0.01000411 12.0 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 251.193 7952.63 76.66 0.01271660 67.19 44.99498340 23.0531 75.00 0.00912216 75.00 0.00913866 47.4135 4109.83 0.00 7808.81 5375.80 0.22510471 80.00 67.00 0.01118466 13.2 52.78 52.74 0.00844654 7.9
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 16951.952 16951.952 195.179594 0.23256193 235.723 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 195.179594 0.23436017   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 3.8003 3.876760 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 16951.95 14958.71 1.0000 0.23436017 195.179594 49.20 43.25 0.00480559 5.2 122.00 74.22 0.00800000 17.0 0.24197259 140.00 120.20 19.80 0.000 16951.95 -26.9 0.00018338 -26.9 44.99498340 23.0531 71.99 0.00619040 71.99 0.00619040 35.7026 10276.32 0.00 15370.64 15370.64 0.23436017 61.88 49.76 0.00480559 6.9 137.12 75.43 0.00480559 17.0
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11535.709 8195.543 297.123078 -999. -999.00 -999.0000 1.00000 1.00000 0.2440 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 297.123078 0.35676790   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 Sensible 11808.90 9436.59 1.0237 0.35676790 297.123078 76.71 62.12 0.00908156 11.5 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 382.392 11426.51 78.26 0.01271815 67.68 44.99498340 15.1436 75.00 0.00843258 75.00 0.00842007 43.7346 6666.86 0.00 11540.52 8043.88 0.34267826 80.00 67.00 0.01118466 13.2 53.26 53.22 0.00859968 8.0
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 23034.804 23034.804 297.123078 0.31601190 330.690 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 297.123078 0.35676790   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 5.1639 5.267854 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 23034.80 20326.34 1.0000 0.35676790 297.123078 57.02 48.31 0.00549101 6.6 122.00 74.22 0.00800000 17.0 0.32879938 140.00 120.20 19.80 0.000 23034.80 -26.9 0.00018338 -26.9 44.99498340 15.1436 71.99 0.00643821 71.99 0.00643821 37.1183 13384.02 0.00 22220.41 22220.41 0.35676790 61.88 51.09 0.00549101 7.3 133.24 75.21 0.00549101 16.9
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 17048.075 12285.834 453.381249 -999. -999.00 -999.0000 1.00000 1.00000 0.2439 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 453.381249 0.54439351   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 Sensible 17165.39 14309.61 1.0069 0.54439351 453.381249 76.74 61.64 0.00875680 11.3 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 583.493 16581.90 80.27 0.01272010 68.29 44.99498340 9.9243 75.00 0.00832013 75.00 0.00831464 43.1953 10203.05 0.00 17055.19 12050.23 0.52289408 80.00 67.00 0.01118466 13.2 53.75 53.72 0.00875984 8.2
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 32359.961 32359.961 453.381249 0.44394267 475.381 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 453.381249 0.54439351   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 7.2544 7.400434 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 32359.96 28555.03 1.0000 0.54439351 453.381249 62.17 51.14 0.00580159 7.5 122.00 74.22 0.00800000 17.0 0.46190690 140.00 120.20 19.80 0.000 32359.96 -26.9 0.00018338 -26.9 44.99498340 9.9243 71.98 0.00642059 71.98 0.00642059 37.0220 17457.38 0.00 32589.87 32589.87 0.54439351 61.88 51.68 0.00580159 7.5 130.43 74.83 0.00580159 16.7
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10874.921 7624.225 271.929722 -999. -999.00 -999.0000 1.00000 0.89502 0.2442 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 271.929722 0.32651720   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 Sensible 10829.67 8319.08 0.9958 0.32651720 271.929722 78.39 63.31 0.00950993 12.0 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 349.969 10479.70 86.18 0.01272586 70.04 44.99498340 16.5465 75.00 0.00873249 75.00 0.00873249 45.3375 5201.25 0.00 10879.46 7489.71 0.31362224 80.00 67.00 0.01118466 13.2 52.78 52.74 0.00844654 7.9
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 21532.274 21532.274 271.929722 0.29539885 307.363 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 271.929722 0.32651720   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 4.8271 4.924239 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 21532.27 19000.48 1.0000 0.32651720 271.929722 55.63 47.17 0.00523286 6.3 122.00 74.22 0.00800000 17.0 0.30735222 140.00 120.20 19.80 0.000 21532.27 -26.9 0.00018338 -26.9 44.99498340 16.5465 71.99 0.00623404 71.99 0.00623404 35.9560 14318.25 0.00 20538.08 20538.08 0.32651720 61.88 50.60 0.00523286 7.1 133.99 75.11 0.00523286 16.9
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13085.760 9229.014 331.468994 -999. -999.00 -999.0000 1.00000 1.00000 0.2440 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 331.468994 0.39800845   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 Sensible 13201.97 10653.80 1.0089 0.39800845 331.468994 77.04 62.14 0.00902210 11.5 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 426.594 12775.38 81.05 0.01272086 68.52 44.99498340 13.5744 75.00 0.00843798 75.00 0.00843585 43.8159 7421.97 0.00 13091.22 9061.70 0.38229013 80.00 67.00 0.01118466 13.2 52.99 52.95 0.00851441 7.9
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 25085.291 25085.291 331.468994 0.34414229 362.564 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 331.468994 0.39800845   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 5.6236 5.736782 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 25085.29 22135.72 1.0000 0.39800845 331.468994 58.57 49.15 0.00557369 6.9 122.00 74.22 0.00800000 17.0 0.35806807 140.00 120.20 19.80 0.000 25085.29 -26.9 0.00018338 -26.9 44.99498340 13.5744 71.98 0.00642032 71.98 0.00642032 37.0204 17453.53 0.00 24508.27 24508.27 0.39800845 61.88 51.25 0.00557369 7.4 132.42 75.09 0.00557369 16.9
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 16578.765 11961.835 442.350485 -999. -999.00 -999.0000 1.00000 1.00000 0.2439 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 442.350485 0.53114842   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 16797.43 13918.18 1.0132 0.53114842 442.350485 76.64 61.67 0.00879819 11.3 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 569.297 16228.13 79.15 0.01271901 67.95 44.99498340 10.1718 75.00 0.00835421 75.00 0.00834697 43.3611 9951.40 0.00 16585.68 11733.32 0.51017207 80.00 67.00 0.01118466 13.2 53.81 53.77 0.00877515 8.2
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 31701.740 31701.740 442.350485 0.43491261 465.190 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 442.350485 0.53114842   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 7.1069 7.249905 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 31701.74 27974.20 1.0000 0.53114842 442.350485 61.93 51.01 0.00578612 7.5 122.00 74.22 0.00800000 17.0 0.45251144 140.00 120.20 19.80 0.000 31701.74 -26.9 0.00018338 -26.9 44.99498340 10.1718 71.98 0.00642055 71.98 0.00642055 37.0218 17456.84 0.00 31860.54 31860.54 0.53114842 61.88 51.65 0.00578612 7.5 130.57 74.85 0.00578612 16.7
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10873.126 7622.966 271.884834 -999. -999.00 -999.0000 1.00000 0.95913 0.2443 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 271.884834 0.32646330   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 Sensible 11369.36 8343.93 1.0456 0.32646330 271.884834 76.55 63.07 0.00976847 11.9 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 349.911 11019.45 76.66 0.01271660 67.19 44.99498340 16.5493 75.00 0.00901666 75.00 0.00903298 46.8735 4968.54 0.00 10877.66 7488.48 0.31357047 80.00 67.00 0.01118466 13.2 52.78 52.74 0.00844654 7.9
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 21529.595 21529.595 271.884834 0.29536210 307.321 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 271.884834 0.32646330   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 4.8265 4.923626 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 21529.60 18998.11 1.0000 0.32646330 271.884834 55.63 47.17 0.00523251 6.3 122.00 74.22 0.00800000 17.0 0.30731399 140.00 120.20 19.80 0.000 21529.60 -26.9 0.00018338 -26.9 44.99498340 16.5493 71.99 0.00623382 71.99 0.00623382 35.9547 14315.88 0.00 20535.08 20535.08 0.32646330 61.88 50.60 0.00523251 7.1 133.99 75.11 0.00523251 16.9
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13095.838 9232.840 331.389374 -999. -999.00 -999.0000 1.00000 1.00000 0.2441 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 331.389374 0.39791285   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 Sensible 13395.76 10583.09 1.0229 0.39791285 331.389374 76.80 62.29 0.00917705 11.6 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 426.492 12969.27 78.81 0.01271869 67.85 44.99498340 13.5777 75.00 0.00854194 75.00 0.00853136 44.3052 6631.28 0.00 13101.30 9065.28 0.38219830 80.00 67.00 0.01118466 13.2 52.97 52.94 0.00850945 7.9
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 25080.539 25080.539 331.389374 0.34407711 362.490 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 331.389374 0.39791285   1.0027 62.4216 6.24161916 159.80 179.60 19.80 446071.38 5.6225 5.735695 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 25080.54 22131.53 1.0000 0.39791285 331.389374 58.56 49.15 0.00557323 6.9 122.00 74.22 0.00800000 17.0 0.35800026 140.00 120.20 19.80 0.000 25080.54 -26.9 0.00018338 -26.9 44.99498340 13.5777 71.98 0.00642002 71.98 0.00642002 37.0187 17449.34 0.00 24502.98 24502.98 0.39791285 61.88 51.25 0.00557323 7.4 132.43 75.09 0.00557323 16.9



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2460.17 6912.17 1581.83
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1372.17 6996.00 774.17
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2364.50 6844.67 1513.67
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2747.50 7117.50 1991.33
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1712.33 7274.50 1208.50
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2616.67 7045.83 1884.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2448.33 6043.33 1046.83
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1218.50 6022.17 231.83
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2388.17 5979.00 1006.83
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2743.17 6272.67 1504.33
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1381.50 6276.33 488.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2591.33 6230.17 1385.50
LIVING_UNIT3_BACKROW_TOPFLOOR 3238.17 6328.83 1969.67
LIVING_UNIT3_FRONTROW_TOPFLOOR 3058.83 6136.50 1656.50
LIVING_UNIT1_FRONTROW_TOPFLOOR 3134.83 6208.00 1724.00
LIVING_UNIT2_BACKROW_TOPFLOOR 2416.50 6394.33 1395.83
LIVING_UNIT2_FRONTROW_TOPFLOOR 2030.17 6179.50 941.50
LIVING_UNIT1_BACKROW_TOPFLOOR 3353.50 6385.83 2059.83
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 3927.00 7470.00 2541.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 100.00 0.00 100.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 26.67 0.00 26.67 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 20.33 0.00 20.33 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 156.67 0.00 156.67 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 49.17 0.00 49.17 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 10.33 0.00 10.33 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 25.33 0.00 25.33 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 17.67 0.00 17.67 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 96.33 0.00 96.33 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 206.50 0.00 206.50 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 34.33 0.00 34.33 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 60.00 0.00 60.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 40.17 0.00 40.17 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 60.17 0.00 60.17 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 84.67 0.00 84.67 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 45.50 0.00 45.50 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 14.33 0.00 14.33 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 155.67 0.00 155.67 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 668.83 0.00 668.83 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.140 0.000 0.284
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.123 0.000 0.284
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.140 0.000 0.284
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.139 0.000 0.284
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.123 0.000 0.284
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.140 0.000 0.284
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.061 0.000 0.284
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.045 0.000 0.284
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.061 0.000 0.284
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.061 0.000 0.284
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.045 0.000 0.284
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.061 0.000 0.284
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.140 0.000 0.284
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.140 0.000 0.284
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.140 0.000 0.284
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.123 0.000 0.284
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.123 0.000 0.284
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.140 0.000 0.284
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Zone Area [ft2] Design Zone Outdoor Airflow - Voz [ft3/min] Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
Total Facility   24.79 36.00 183739.38 21609.96 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Infiltration [ft3] Total Ventilation and Infiltration [ft3] Dynamic Target Ventilation - Voz-dyn [ft3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 12377625.13 37524452.11 23785081.69 1454.17 1131.50 6222.33 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 10904159.40 36050986.38 23785081.69 1454.17 1131.50 6222.33 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 12382760.87 37529587.85 23785081.69 1454.17 1131.50 6222.33 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 12367044.08 37513871.06 23785081.69 1454.17 1131.50 6222.33 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 10895093.15 36041920.13 23785081.69 1454.17 1131.50 6222.33 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 12375788.55 37522615.53 23785081.69 1454.17 1131.50 6222.33 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 5434770.41 30583137.73 23785081.69 1449.83 1132.00 6226.17 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 3954879.34 29103246.66 23785081.69 1449.83 1132.00 6226.17 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 5435711.13 30584078.45 23785081.69 1449.83 1132.00 6226.17 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 5428021.55 30576388.87 23785081.69 1449.83 1132.00 6226.17 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 3950338.42 29098705.74 23785081.69 1449.83 1132.00 6226.17 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 5431694.46 30580061.78 23785081.69 1449.83 1132.00 6226.17 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 25149909.29 25149909.29 12399696.87 37549606.15 23785081.69 1446.33 1131.00 6230.67 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 25149909.29 25149909.29 12405862.22 37555771.51 23785081.69 1446.33 1131.00 6230.67 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 25149909.29 25149909.29 12401587.05 37551496.34 23785081.69 1446.33 1131.00 6230.67 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 25149909.29 25149909.29 10917410.46 36067319.75 23785081.69 1446.33 1131.00 6230.67 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 25149909.29 25149909.29 10926217.55 36076126.84 23785081.69 1446.33 1131.00 6230.67 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 25149909.29 25149909.29 12391589.54 37541498.83 23785081.69 1446.33 1131.00 6230.67 0.00
Total Facility 0.00 0.452671E+09 0.452671E+09 0.172380E+09 0.625051E+09 0.428131E+09 1454.17 1139.33 6230.67 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Infiltration [ft3/min] Total Ventilation and Infiltration [ft3/min] Dynamic Target Ventilation - Voz-dyn [ft3/min] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 23.4151 70.9862 44.9950 1454.17 1131.50 6222.33
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 20.6277 68.1988 44.9950 1454.17 1131.50 6222.33
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 23.4249 70.9959 44.9950 1454.17 1131.50 6222.33
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 23.3951 70.9662 44.9950 1454.17 1131.50 6222.33
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 20.6106 68.1816 44.9950 1454.17 1131.50 6222.33
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 23.4117 70.9827 44.9950 1454.17 1131.50 6222.33
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 10.2811 57.8551 44.9950 1449.83 1132.00 6226.17
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 7.4816 55.0555 44.9950 1449.83 1132.00 6226.17
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 10.2829 57.8569 44.9950 1449.83 1132.00 6226.17
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 10.2684 57.8423 44.9950 1449.83 1132.00 6226.17
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 7.4730 55.0469 44.9950 1449.83 1132.00 6226.17
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 10.2753 57.8493 44.9950 1449.83 1132.00 6226.17
LIVING_UNIT3_BACKROW_TOPFLOOR 0.0000 47.5769 47.5769 23.4569 71.0338 44.9950 1446.33 1131.00 6230.67
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0000 47.5769 47.5769 23.4686 71.0454 44.9950 1446.33 1131.00 6230.67
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0000 47.5769 47.5769 23.4605 71.0373 44.9950 1446.33 1131.00 6230.67
LIVING_UNIT2_BACKROW_TOPFLOOR 0.0000 47.5769 47.5769 20.6528 68.2297 44.9950 1446.33 1131.00 6230.67
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0000 47.5769 47.5769 20.6695 68.2463 44.9950 1446.33 1131.00 6230.67
LIVING_UNIT1_BACKROW_TOPFLOOR 0.0000 47.5769 47.5769 23.4416 71.0184 44.9950 1446.33 1131.00 6230.67
Total Facility 0.0000 856.3312 856.3312 326.0971 1182.4283 809.9097 1454.17 1139.33 6230.67


Total Outdoor Air by AirLoop

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 23785081.69 1454.17 1131.50 6222.33 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 23785081.69 1454.17 1131.50 6222.33 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 23785081.69 1454.17 1131.50 6222.33 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 23785081.69 1454.17 1131.50 6222.33 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 23785081.69 1454.17 1131.50 6222.33 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 23785081.69 1454.17 1131.50 6222.33 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 23785081.69 1449.83 1132.00 6226.17 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 23785081.69 1449.83 1132.00 6226.17 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 23785081.69 1449.83 1132.00 6226.17 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 23785081.69 1449.83 1132.00 6226.17 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 23785081.69 1449.83 1132.00 6226.17 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 23785081.69 1449.83 1132.00 6226.17 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 25149909.29 25149909.29 23785081.69 1446.33 1131.00 6230.67 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 25149909.29 25149909.29 23785081.69 1446.33 1131.00 6230.67 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 25149909.29 25149909.29 23785081.69 1446.33 1131.00 6230.67 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 25149909.29 25149909.29 23785081.69 1446.33 1131.00 6230.67 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 25149909.29 25149909.29 23785081.69 1446.33 1131.00 6230.67 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 25149909.29 25149909.29 23785081.69 1446.33 1131.00 6230.67 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 44.9950 1454.17 1131.50 6222.33
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 44.9950 1454.17 1131.50 6222.33
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 44.9950 1454.17 1131.50 6222.33
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 44.9950 1454.17 1131.50 6222.33
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 44.9950 1454.17 1131.50 6222.33
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 44.9950 1454.17 1131.50 6222.33
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 44.9950 1449.83 1132.00 6226.17
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 44.9950 1449.83 1132.00 6226.17
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 44.9950 1449.83 1132.00 6226.17
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 44.9950 1449.83 1132.00 6226.17
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 44.9950 1449.83 1132.00 6226.17
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 44.9950 1449.83 1132.00 6226.17
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 47.5769 47.5769 44.9950 1446.33 1131.00 6230.67
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 47.5769 47.5769 44.9950 1446.33 1131.00 6230.67
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 47.5769 47.5769 44.9950 1446.33 1131.00 6230.67
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 47.5769 47.5769 44.9950 1446.33 1131.00 6230.67
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 47.5769 47.5769 44.9950 1446.33 1131.00 6230.67
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 47.5769 47.5769 44.9950 1446.33 1131.00 6230.67


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [ft3/min] Limits and Scheduled Limits [ft3/min] Economizer [ft3/min] Exhaust Flow [ft3/min] Mixed Air Flow [ft3/min] High Humidity [ft3/min] Demand Controlled Ventilation [ft3/min] Night Ventilation [ft3/min] Demand Limiting [ft3/min] Energy Management System [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Surfaces by Class

Total Outdoors
Wall 74 50
Floor 28 3
Roof 21 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 60 60
Overhang 30 30
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1953
Defaulted Fields 1695
Fields with Defaults 6332
Autosized Fields 382
Autosizable Fields 546
Autocalculated Fields 150
Autocalculatable Fields 329



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 125198.92 8248.63 06-JUN-03:10 34756.07 29-JUN-18:10
Electricity:Building 100396.90 6292.37 02-JAN-03:10 19051.98 01-JAN-18:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
Electricity:SpaceType:GENERAL 100396.90 6292.37 02-JAN-03:10 19051.98 01-JAN-18:10
InteriorLights:Electricity 12093.82 270.83 01-JAN-00:10 3939.36 01-JAN-19:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
InteriorLights:Electricity:SpaceType:GENERAL 12093.82 270.83 01-JAN-00:10 3939.36 01-JAN-19:10
General:InteriorLights:Electricity 12093.82 270.83 01-JAN-00:10 3939.36 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:SpaceType:GENERAL 12093.82 270.83 01-JAN-00:10 3939.36 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5577.61 349.58 02-JAN-03:10 1058.44 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 671.88 15.05 01-JAN-00:10 218.85 01-JAN-19:10
InteriorEquipment:Electricity 88303.07 5995.41 02-JAN-04:10 15497.32 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
InteriorEquipment:Electricity:SpaceType:GENERAL 88303.07 5995.41 02-JAN-04:10 15497.32 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
electric_range:InteriorEquipment:Electricity:SpaceType:GENERAL 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:SpaceType:GENERAL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
electric_mels:InteriorEquipment:Electricity:SpaceType:GENERAL 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
Fans:Electricity 9787.17 578.57 12-MAY-15:00 2353.56 29-JUN-18:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 125198.92 8248.63 06-JUN-03:10 34756.07 29-JUN-18:10
ElectricityPurchased:Plant 125198.92 8248.63 06-JUN-03:10 34756.07 29-JUN-18:10
Cogeneration:ElectricityPurchased 125198.92 8248.63 06-JUN-03:10 34756.07 29-JUN-18:10
General:Cogeneration:ElectricityPurchased 125198.92 8248.63 06-JUN-03:10 34756.07 29-JUN-18:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 125198.92 8248.63 06-JUN-03:10 34756.07 29-JUN-18:10
ElectricityNet:Plant 125198.92 8248.63 06-JUN-03:10 34756.07 29-JUN-18:10
Cogeneration:ElectricityNet 125198.92 8248.63 06-JUN-03:10 34756.07 29-JUN-18:10
General:Cogeneration:ElectricityNet 125198.92 8248.63 06-JUN-03:10 34756.07 29-JUN-18:10
Electricity:HVAC 18767.72 578.57 12-MAY-15:00 14945.36 29-JUN-16:20
Ventilation:Fans:Electricity 5068.29 578.57 01-JAN-00:10 578.57 01-JAN-00:10
General:Fans:Electricity 4718.89 0.00 12-MAY-15:00 1774.99 29-JUN-18:10
ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Exterior-Lights:ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Garage-Lights:ExteriorLights:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 8980.54 0.00 01-JAN-00:10 12615.48 29-JUN-16:20
General:Cooling:Electricity 8980.54 0.00 01-JAN-00:10 12615.48 29-JUN-16:20
Electricity:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 5424.84 0.00 11-APR-13:20 320445.61 06-JAN-05:00
NaturalGas:Plant 5424.84 0.00 11-APR-13:20 320445.61 06-JAN-05:00
Heating:NaturalGas 5424.84 0.00 11-APR-13:20 320445.61 06-JAN-05:00
Boiler:Heating:NaturalGas 5424.84 0.00 11-APR-13:20 320445.61 06-JAN-05:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
Water:Plant 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
WaterSystems:Water 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
Domestic Hot Water:WaterSystems:Water 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
MainsWater:Facility 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
MainsWater:Plant 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
WaterSystems:MainsWater 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
Domestic Hot Water:WaterSystems:MainsWater 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 1688185.04 926.19 18-AUG-03:00 797494.17 06-JAN-08:10
EnergyTransfer:Building 550703.61 0.00 12-MAY-15:00 262703.50 06-JAN-05:00
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer 445025.50 0.00 11-APR-14:50 262703.50 06-JAN-05:00
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 445025.50 0.00 11-APR-14:50 262703.50 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 105678.10 0.00 01-JAN-00:10 125562.84 29-JUN-18:10
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer 105678.10 0.00 01-JAN-00:10 125562.84 29-JUN-18:10
General:Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 32233.20 0.00 04-FEB-13:50 15747.49 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 26935.95 0.00 04-FEB-13:50 15747.49 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 26935.95 0.00 04-FEB-13:50 15747.49 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5297.24 0.00 01-JAN-00:10 8744.72 29-JUN-17:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5297.24 0.00 01-JAN-00:10 8744.72 29-JUN-17:10
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 24580.55 0.00 04-FEB-14:10 12767.51 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 21326.33 0.00 04-FEB-14:10 12767.51 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 21326.33 0.00 04-FEB-14:10 12767.51 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3254.23 0.00 01-JAN-00:10 4317.10 23-JUL-13:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3254.23 0.00 01-JAN-00:10 4317.10 23-JUL-13:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 31761.14 0.00 08-FEB-13:20 15764.50 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 26772.46 0.00 08-FEB-13:20 15764.50 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 26772.46 0.00 08-FEB-13:20 15764.50 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4988.68 0.00 01-JAN-00:10 6544.19 29-JUL-10:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4988.68 0.00 01-JAN-00:10 6544.19 29-JUL-10:10
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 33310.07 0.00 19-MAR-16:10 15829.13 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 29174.91 0.00 19-MAR-16:10 15829.13 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 29174.91 0.00 19-MAR-16:10 15829.13 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4135.16 0.00 01-JAN-00:10 8441.45 29-JUN-17:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4135.16 0.00 01-JAN-00:10 8441.45 29-JUN-17:20
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 26036.34 0.00 26-MAR-17:30 12855.46 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 23744.70 0.00 26-MAR-17:30 12855.46 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 23744.70 0.00 26-MAR-17:30 12855.46 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2291.65 0.00 01-JAN-00:10 4112.18 29-JUN-18:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2291.65 0.00 01-JAN-00:10 4112.18 29-JUN-18:20
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 32948.08 0.00 10-APR-08:30 15840.80 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 29120.28 0.00 10-APR-08:30 15840.80 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 29120.28 0.00 10-APR-08:30 15840.80 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3827.81 0.00 01-JAN-00:10 5913.03 29-JUL-09:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3827.81 0.00 01-JAN-00:10 5913.03 29-JUL-09:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 29057.72 0.00 04-FEB-13:10 13402.98 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 20525.66 0.00 04-FEB-13:10 13402.98 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 20525.66 0.00 04-FEB-13:10 13402.98 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8532.06 0.00 01-JAN-00:10 10565.36 30-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8532.06 0.00 01-JAN-00:10 10565.36 30-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 20665.68 0.00 04-FEB-12:40 10217.63 06-JAN-08:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 14587.41 0.00 04-FEB-12:40 10217.63 06-JAN-08:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 14587.41 0.00 04-FEB-12:40 10217.63 06-JAN-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6078.27 0.00 01-JAN-00:10 5452.27 01-SEP-14:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6078.27 0.00 01-JAN-00:10 5452.27 01-SEP-14:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 28649.57 0.00 04-FEB-12:50 13419.40 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 20294.98 0.00 04-FEB-12:50 13419.40 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 20294.98 0.00 04-FEB-12:50 13419.40 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8354.59 0.00 01-JAN-00:10 8117.34 29-JUL-10:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8354.59 0.00 01-JAN-00:10 8117.34 29-JUL-10:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 29695.79 0.00 04-FEB-19:10 13510.40 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 22858.14 0.00 04-FEB-19:10 13510.40 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 22858.14 0.00 04-FEB-19:10 13510.40 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 6837.65 0.00 01-JAN-00:10 10308.82 30-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 6837.65 0.00 01-JAN-00:10 10308.82 30-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 21673.69 0.00 20-FEB-17:40 10343.30 06-JAN-09:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 17134.86 0.00 20-FEB-17:40 10343.30 06-JAN-09:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 17134.86 0.00 20-FEB-17:40 10343.30 06-JAN-09:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4538.84 0.00 01-JAN-00:10 5197.25 29-JUN-18:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4538.84 0.00 01-JAN-00:10 5197.25 29-JUN-18:30
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 29490.23 0.00 26-MAR-10:10 13521.74 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 22828.93 0.00 26-MAR-10:10 13521.74 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 22828.93 0.00 26-MAR-10:10 13521.74 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6661.30 0.00 01-JAN-00:10 7244.18 29-JUL-09:40
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6661.30 0.00 01-JAN-00:10 7244.18 29-JUL-09:40
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 38282.11 0.00 10-APR-08:50 17717.98 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 31482.22 0.00 10-APR-08:50 17717.98 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 31482.22 0.00 10-APR-08:50 17717.98 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 6799.90 0.00 01-JAN-00:10 7268.14 29-JUL-09:50
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 6799.90 0.00 01-JAN-00:10 7268.14 29-JUL-09:50
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 36952.18 0.00 08-FEB-13:10 17632.46 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 28921.33 0.00 08-FEB-13:10 17632.46 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 28921.33 0.00 08-FEB-13:10 17632.46 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 8030.85 0.00 01-JAN-00:10 8084.08 29-JUL-10:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 8030.85 0.00 01-JAN-00:10 8084.08 29-JUL-10:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 37399.21 0.00 04-FEB-14:20 17619.23 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 29125.23 0.00 04-FEB-14:20 17619.23 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 29125.23 0.00 04-FEB-14:20 17619.23 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 8273.98 0.00 01-JAN-00:10 11299.10 30-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 8273.98 0.00 01-JAN-00:10 11299.10 30-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 30440.19 0.00 10-APR-17:10 14508.71 06-JAN-09:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 25628.69 0.00 10-APR-17:10 14508.71 06-JAN-09:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 25628.69 0.00 10-APR-17:10 14508.71 06-JAN-09:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4811.49 0.00 01-JAN-00:10 6160.53 29-JUN-18:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4811.49 0.00 01-JAN-00:10 6160.53 29-JUN-18:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 28868.11 0.00 04-FEB-14:50 14381.30 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 22956.82 0.00 04-FEB-14:50 14381.30 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 22956.82 0.00 04-FEB-14:50 14381.30 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5911.29 0.00 01-JAN-00:10 6122.55 29-JUN-18:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5911.29 0.00 01-JAN-00:10 6122.55 29-JUN-18:20
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 38659.72 0.00 19-MAR-15:50 17711.32 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 31606.62 0.00 19-MAR-15:50 17711.32 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 31606.62 0.00 19-MAR-15:50 17711.32 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 7053.11 0.00 01-JAN-00:10 11256.06 30-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 7053.11 0.00 01-JAN-00:10 11256.06 30-JUN-18:10
PlantLoopHeatingDemand:Facility 563984.50 926.19 18-AUG-03:00 284513.23 06-JAN-08:10
PlantLoopHeatingDemand:Plant 130113.54 926.19 18-AUG-03:00 34295.86 26-FEB-09:00
WaterSystems:PlantLoopHeatingDemand 130113.54 926.19 18-AUG-03:00 34295.86 26-FEB-09:00
General:WaterSystems:PlantLoopHeatingDemand 130113.54 926.19 18-AUG-03:00 34295.86 26-FEB-09:00
EnergyTransfer:HVAC 573380.73 0.00 12-MAY-12:50 257012.67 06-JAN-05:00
HeatingCoils:EnergyTransfer 433870.96 0.00 11-APR-13:20 257012.67 06-JAN-05:00
PlantLoopHeatingDemand:HVAC 433870.96 0.00 11-APR-13:20 257012.67 06-JAN-05:00
HeatingCoils:PlantLoopHeatingDemand 433870.96 0.00 11-APR-13:20 257012.67 06-JAN-05:00
CoolingCoils:EnergyTransfer 139509.77 0.00 01-JAN-00:10 170509.26 29-JUN-18:10
EnergyTransfer:Plant 564100.71 926.19 18-AUG-03:00 283605.98 06-JAN-08:10
WaterSystems:EnergyTransfer 130113.54 926.19 18-AUG-03:00 34295.86 26-FEB-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 130113.54 926.19 18-AUG-03:00 34295.86 26-FEB-09:00
Boilers:EnergyTransfer 433987.16 0.00 11-APR-13:20 256356.49 06-JAN-05:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
FuelOilNo2:Facility 311335.02 0.00 01-JAN-00:10 227318.29 04-FEB-08:10
FuelOilNo2:Plant 311335.02 0.00 01-JAN-00:10 227318.29 04-FEB-08:10
WaterSystems:FuelOilNo2 311335.02 0.00 01-JAN-00:10 227318.29 04-FEB-08:10
Water Heater:WaterSystems:FuelOilNo2 311335.02 0.00 01-JAN-00:10 227318.29 04-FEB-08:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 26935.855 -441.13 0.000 0.000 3085.035 2294.076 10464.601 8973.297 0.000 130.391 0.000 0.000 -8474.33 0.000 -24866.92 -13244.86
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 21326.252 -271.00 0.000 0.000 3078.700 2294.076 10464.601 4482.328 0.000 125.986 0.000 0.000 -3370.65 0.000 -23822.03 -11325.06
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 26772.364 -415.44 0.000 0.000 3083.480 2294.076 10464.601 8852.979 0.000 130.394 0.000 0.000 -8332.01 0.000 -24891.11 -13386.11
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 29174.813 -344.36 0.000 0.000 3089.476 2294.076 10464.601 5779.447 0.000 130.393 0.000 0.000 -9124.88 0.000 -24802.47 -12870.39
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 23744.622 -190.84 0.000 0.000 3084.185 2294.076 10464.601 1069.585 0.000 126.016 0.000 0.000 -3877.56 0.000 -23768.74 -10845.15
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 29120.189 -318.77 0.000 0.000 3087.301 2294.076 10464.601 5603.299 0.000 130.396 0.000 0.000 -8934.18 0.000 -24851.88 -13085.99
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 20525.578 -710.52 0.000 0.000 3057.878 2294.076 10464.601 8834.915 0.000 108.948 0.000 0.000 -8712.32 0.000 -19989.30 -8052.39
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 14587.349 -506.18 0.000 0.000 3050.020 2294.076 10464.601 4419.769 0.000 104.563 0.000 0.000 -3470.61 0.000 -18943.86 -6427.65
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 20294.908 -695.75 0.000 0.000 3059.830 2294.076 10464.601 8708.089 0.000 108.948 0.000 0.000 -8553.58 0.000 -19997.58 -8024.71
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 22858.065 -569.42 0.000 0.000 3066.174 2294.076 10464.601 5677.933 0.000 108.949 0.000 0.000 -9354.16 0.000 -19911.15 -8366.92
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 17134.801 -377.98 0.000 0.000 3059.483 2294.076 10464.601 1034.150 0.000 104.567 0.000 0.000 -3977.87 0.000 -18879.76 -6695.22
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 22828.859 -554.74 0.000 0.000 3065.702 2294.076 10464.601 5490.828 0.000 108.950 0.000 0.000 -9149.98 0.000 -19951.90 -8489.83
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 31482.135 -566.28 0.000 0.000 3071.257 2294.076 10464.601 5498.408 0.000 128.780 0.000 0.000 -9115.87 0.000 -24977.41 -12046.08
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 28921.247 -668.79 0.000 0.000 3067.493 2294.076 10464.601 8727.496 0.000 128.776 0.000 0.000 -8511.43 0.000 -25015.41 -12046.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 29125.137 -689.03 0.000 0.000 3067.428 2294.076 10464.601 8852.183 0.000 128.778 0.000 0.000 -8667.62 0.000 -24992.29 -11998.39
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 25628.623 -400.69 0.000 0.000 3066.591 2294.076 10464.601 1036.243 0.000 124.426 0.000 0.000 -3959.34 0.000 -23899.67 -9944.07
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 22956.748 -492.28 0.000 0.000 3060.523 2294.076 10464.601 4425.970 0.000 124.424 0.000 0.000 -3449.75 0.000 -23953.47 -10011.85
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 31606.525 -587.36 0.000 0.000 3072.138 2294.076 10464.601 5680.934 0.000 128.779 0.000 0.000 -9319.69 0.000 -24931.38 -11942.95
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18693.381 113370.439 0.000 0.000 0.000 -132063.82 -1.00
Total Facility 0.000 0.000 445024.069 -8800.57 0.000 0.000 55272.694 41293.362 188362.826 103147.853 0.000 20875.845 113370.439 0.000 -128355.83 0.000 -544510.17 -188804.62


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 29-JUN-17:10 0.00 0.00 0.00 -0.7 0.00 0.00 263.16 500.54 1664.02 7629.72 0.00 1176.61 0.00 0.00 0.00 0.00 0.00 -2490.2
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 23-JUL-13:30 0.00 0.00 0.00 -0.4 0.00 0.00 115.09 96.26 1109.73 3181.88 0.00 679.49 0.00 0.00 0.00 0.00 0.00 -865.8
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 29-JUL-10:15 0.00 0.00 0.00 -0.5 0.00 0.00 115.09 96.26 1121.12 7268.06 0.00 332.89 0.00 0.00 0.00 0.00 0.00 -2387.6
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 29-JUN-17:19 0.00 0.00 0.00 -0.7 0.00 0.00 263.16 500.54 1664.02 7565.21 0.00 1157.77 0.00 0.00 0.00 0.00 0.00 -2708.7
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 29-JUN-18:23 0.00 0.00 0.00 -0.3 0.00 0.00 426.77 673.81 1724.99 1076.98 0.00 976.61 0.00 0.00 0.00 0.00 0.00 -766.1
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 29-JUL-08:06 0.00 0.00 0.00 -0.5 0.00 0.00 194.41 141.18 1179.68 7092.25 0.00 177.16 0.00 0.00 0.00 0.00 0.00 -2862.1
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 30-JUN-18:15 0.00 0.00 0.00 -0.9 0.00 0.00 426.75 673.81 1724.99 6738.05 0.00 561.10 442.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 01-SEP-13:00 0.00 0.00 0.00 -0.5 0.00 0.00 115.09 96.26 1084.63 3601.83 0.00 154.63 399.42 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 29-JUL-10:35 0.00 0.00 0.00 -0.7 0.00 0.00 115.09 96.26 1121.12 6888.49 0.00 311.10 0.00 0.00 0.00 0.00 0.00 -413.3
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 30-JUN-18:15 0.00 0.00 0.00 -0.9 0.00 0.00 426.75 673.81 1724.99 7303.50 0.00 561.12 0.00 0.00 0.00 0.00 0.00 -379.9
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29-JUN-18:34 0.00 0.00 0.00 -0.4 0.00 0.00 426.76 673.81 1724.99 1072.84 0.00 755.74 543.77 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 29-JUL-09:45 0.00 0.00 0.00 -0.6 0.00 0.00 115.09 96.26 1126.15 6276.34 0.00 228.49 0.00 0.00 0.00 0.00 0.00 -596.6
LIVING_UNIT3_BACKROW_TOPFLOOR 29-JUL-09:55 0.00 0.00 0.00 -0.6 0.00 0.00 115.09 96.26 1126.15 6041.51 0.00 289.04 0.00 0.00 0.00 0.00 0.00 -398.5
LIVING_UNIT3_FRONTROW_TOPFLOOR 29-JUL-10:35 0.00 0.00 0.00 -0.7 0.00 0.00 115.09 96.26 1121.12 6880.95 0.00 358.09 0.00 0.00 0.00 0.00 0.00 -485.9
LIVING_UNIT1_FRONTROW_TOPFLOOR 30-JUN-18:15 0.00 0.00 0.00 -0.9 0.00 0.00 426.75 673.81 1724.99 6717.72 0.00 682.26 1074.24 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 29-JUN-18:34 0.00 0.00 0.00 -0.5 0.00 0.00 426.76 673.81 1724.99 1065.88 0.00 942.65 1327.36 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 29-JUN-18:26 0.00 0.00 0.00 -0.5 0.00 0.00 426.76 673.81 1724.99 534.37 0.00 972.60 1790.34 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 30-JUN-18:15 0.00 0.00 0.00 -0.9 0.00 0.00 426.75 673.81 1724.99 7277.35 0.00 682.27 472.54 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-JUN-18:10 0.00 0.00 0.00 -10.5 0.00 0.00 7681.66 12128.50 31049.73 48787.85 0.00 17391.96 50904.03 0.00 0.00 0.00 -42371.2 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 06-JAN-04:00 0.00 0.00 15747.35 0.00 0.00 0.00 526.23 154.01 831.88 0.00 0.00 0.00 0.00 0.00 -3968.6 0.00 -10229.8 -3061.0
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17-MAR-17:04 0.00 0.00 13612.01 0.00 0.00 0.00 307.66 500.54 1664.02 0.00 0.00 0.00 0.00 0.00 -592.9 0.00 -3265.8 -12225.5
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 06-JAN-04:00 0.00 0.00 15764.36 0.00 0.00 0.00 526.26 154.01 831.88 0.00 0.00 0.00 0.00 0.00 -3964.3 0.00 -10229.6 -3082.6
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 20-MAR-13:57 0.00 0.00 16349.67 0.00 0.00 0.00 147.20 96.26 1084.63 1373.83 0.00 0.00 0.00 0.00 0.00 0.00 -2418.1 -16633.5
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 06-JAN-04:00 0.00 0.00 12855.35 0.00 0.00 0.00 526.22 154.01 831.88 0.00 0.00 0.00 0.00 0.00 -1598.9 0.00 -9729.6 -3038.9
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 06-JAN-04:00 0.00 0.00 15840.66 0.00 0.00 0.00 526.26 154.01 831.88 0.00 0.00 0.00 0.00 0.00 -3960.2 0.00 -10229.6 -3163.0
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 06-JAN-04:00 0.00 0.00 13402.85 0.00 0.00 0.00 526.22 154.01 831.88 0.00 0.00 0.00 0.00 0.00 -4023.9 0.00 -7878.7 -3012.3
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 06-MAR-17:52 0.00 0.00 14655.49 0.00 0.00 0.00 309.51 500.54 1664.02 0.00 0.00 0.00 0.00 0.00 -807.3 0.00 -3787.1 -12535.1
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 06-JAN-04:00 0.00 0.00 13419.27 0.00 0.00 0.00 526.27 154.01 831.88 0.00 0.00 0.00 0.00 0.00 -4008.4 0.00 -7878.5 -3044.5
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 05-APR-14:55 0.00 0.00 18903.77 0.00 0.00 0.00 144.22 96.26 1091.85 987.64 0.00 0.00 0.00 0.00 0.00 0.00 -2339.7 -18884.1
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 10-MAR-18:32 0.00 0.00 11517.69 0.00 0.00 0.00 486.59 673.81 1724.99 0.00 0.00 0.00 0.00 0.00 -728.0 0.00 -2591.9 -11083.2
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 06-JAN-04:00 0.00 0.00 13521.62 0.00 0.00 0.00 526.24 154.01 831.88 0.00 0.00 0.00 0.00 0.00 -3996.5 0.00 -7878.7 -3158.5
LIVING_UNIT3_BACKROW_TOPFLOOR 06-JAN-04:00 0.00 0.00 17717.82 0.00 0.00 0.00 526.26 154.01 831.88 0.00 0.00 0.00 0.00 0.00 -3985.0 0.00 -10238.2 -5006.8
LIVING_UNIT3_FRONTROW_TOPFLOOR 06-JAN-04:00 0.00 0.00 17632.30 0.00 0.00 0.00 526.26 154.01 831.88 0.00 0.00 0.00 0.00 0.00 -4000.6 0.00 -10238.2 -4905.6
LIVING_UNIT1_FRONTROW_TOPFLOOR 06-JAN-04:00 0.00 0.00 17619.07 0.00 0.00 0.00 526.27 154.01 831.88 0.00 0.00 0.00 0.00 0.00 -4021.4 0.00 -10238.1 -4871.8
LIVING_UNIT2_BACKROW_TOPFLOOR 23-MAR-18:33 0.00 0.00 14754.22 0.00 0.00 0.00 507.98 673.81 1724.99 0.00 0.00 0.00 0.00 0.00 -683.9 0.00 -2945.9 -14031.2
LIVING_UNIT2_FRONTROW_TOPFLOOR 04-APR-16:02 0.00 0.00 15778.52 0.00 0.00 0.00 166.34 359.36 1350.56 0.00 0.00 0.00 0.00 0.00 -79.6 0.00 -4088.0 -13487.2
LIVING_UNIT1_BACKROW_TOPFLOOR 20-MAR-14:46 0.00 0.00 19352.35 0.00 0.00 0.00 148.80 96.26 1091.85 0.00 0.00 0.00 0.00 0.00 -710.1 0.00 -2437.1 -17542.0
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 06-JAN-04:00 0.00 0.00 262701.15 0.00 0.00 0.00 9472.34 2772.23 14973.78 0.00 0.00 10607.21 0.00 0.00 -57590.3 0.00 -167076.9 -75859.5



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 354.1569 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 354.1569 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 237.7084 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 237.7084 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 292.3643 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 292.3643 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 332.9337 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 332.9337 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 237.7202 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 237.7202 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 292.3299 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 292.3299 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 431.2333 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 431.2333 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 216.7170 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 216.7170 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 331.9954 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 331.9954 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 405.6591 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 405.6591 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 195.1796 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 195.1796 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 297.1231 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 297.1231 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 453.3812 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 453.3812 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 271.9297 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 271.9297 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 331.4690 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 331.4690 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 442.3505 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 442.3505 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 271.8848 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 271.8848 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 331.3894 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 331.3894 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 354.1569 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 354.1569 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 237.7084 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 237.7084 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 292.3643 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 292.3643 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 332.9337 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 332.9337 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 237.7202 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 237.7202 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 292.3299 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 292.3299 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 431.2333 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 431.2333 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 216.7170 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 216.7170 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 331.9954 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 331.9954 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 405.6591 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 405.6591 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 195.1796 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 195.1796 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 297.1231 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 297.1231 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 453.3812 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 453.3812 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 271.9297 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 271.9297 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 331.4690 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 331.4690 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 442.3505 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 442.3505 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 271.8848 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 271.8848 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 331.3894 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 331.3894 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 354.1569 354.1569 354.1569 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 237.7084 237.7084 237.7084 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 292.3643 292.3643 292.3643 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 332.9337 332.9337 332.9337 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 237.7202 237.7202 237.7202 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 292.3299 292.3299 292.3299 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 431.2333 431.2333 431.2333 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 216.7170 216.7170 216.7170 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 331.9954 331.9954 331.9954 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 405.6591 405.6591 405.6591 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 195.1796 195.1796 195.1796 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 297.1231 297.1231 297.1231 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 331.3894 331.3894 331.3894 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 331.4690 331.4690 331.4690 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 453.3812 453.3812 453.3812 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 271.8848 271.8848 271.8848 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 271.9297 271.9297 271.9297 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 442.3505 442.3505 442.3505 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 354.1569 354.1569 354.1569 354.1569 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 237.7084 237.7084 237.7084 237.7084 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 292.3643 292.3643 292.3643 292.3643 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 332.9337 332.9337 332.9337 332.9337 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 237.7202 237.7202 237.7202 237.7202 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 292.3299 292.3299 292.3299 292.3299 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 431.2333 431.2333 431.2333 431.2333 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 216.7170 216.7170 216.7170 216.7170 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 331.9954 331.9954 331.9954 331.9954 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 405.6591 405.6591 405.6591 405.6591 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 195.1796 195.1796 195.1796 195.1796 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 297.1231 297.1231 297.1231 297.1231 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 453.3812 453.3812 453.3812 453.3812 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 271.9297 271.9297 271.9297 271.9297 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 331.4690 331.4690 331.4690 331.4690 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 442.3505 442.3505 442.3505 442.3505 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 271.8848 271.8848 271.8848 271.8848 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 331.3894 331.3894 331.3894 331.3894 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 354.1569 354.1569 354.1569 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 237.7084 237.7084 237.7084 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 292.3643 292.3643 292.3643 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 332.9337 332.9337 332.9337 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 237.7202 237.7202 237.7202 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 292.3299 292.3299 292.3299 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 431.2333 431.2333 431.2333 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 216.7170 216.7170 216.7170 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 331.9954 331.9954 331.9954 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 405.6591 405.6591 405.6591 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 195.1796 195.1796 195.1796 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 297.1231 297.1231 297.1231 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 331.3894 331.3894 331.3894 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 331.4690 331.4690 331.4690 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 453.3812 453.3812 453.3812 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 271.8848 271.8848 271.8848 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 271.9297 271.9297 271.9297 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 442.3505 442.3505 442.3505 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 354.1569 354.1569 354.1569 354.1569 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 237.7084 237.7084 237.7084 237.7084 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 292.3643 292.3643 292.3643 292.3643 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 332.9337 332.9337 332.9337 332.9337 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 237.7202 237.7202 237.7202 237.7202 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 292.3299 292.3299 292.3299 292.3299 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 431.2333 431.2333 431.2333 431.2333 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 216.7170 216.7170 216.7170 216.7170 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 331.9954 331.9954 331.9954 331.9954 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 405.6591 405.6591 405.6591 405.6591 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 195.1796 195.1796 195.1796 195.1796 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 297.1231 297.1231 297.1231 297.1231 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 453.3812 453.3812 453.3812 453.3812 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 271.9297 271.9297 271.9297 271.9297 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 331.4690 331.4690 331.4690 331.4690 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 442.3505 442.3505 442.3505 442.3505 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 271.8848 271.8848 271.8848 271.8848 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 331.3894 331.3894 331.3894 331.3894 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Sec1.1A-General Information

Data
Weather File ANNUAL ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Total gross floor area [ft2] 31210.83
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
BREEZEWAY 1798.16 0.00 1798.16 0.00
ATTIC 7802.71 0.00 7802.71 0.00
Totals 31210.83 21609.96 9600.87  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 668.83
Number of hours cooling loads not met 0.00
Number of hours not met 668.83


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 5424.84 320445.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 8980.54 12615.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 12093.82 3939.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Exterior-Lights 6034.31 1377.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- dishwasher 3088.82 985.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- refrigerator 12036.11 1639.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- clotheswasher 1577.30 427.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_dryer 12502.11 3196.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_range 9058.39 3721.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_mels 46926.68 7929.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- IECC_adj 3113.66 526.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation 5068.29 578.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 4718.89 1774.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 311335.02 227318.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 301503.54 427481.37
Natural Gas 0.00 542483.96
Additional 0.00 311335.02
Total 301503.54 1281300.35


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.39
Space Heating 0.00
Space Cooling 0.29
Fans (All) 0.31
Service Water Heating 0.00
Receptacle Equipment 2.83
Miscellaneous (All) 4.01
Subtotal 4.01


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 5.09
Service Water Heating 0.00
Miscellaneous (All) 5.09
Subtotal 5.09


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 9.96
Miscellaneous 9.96


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 3.22
Space Heating 42.34
Space Cooling 2.39
Fans (All) 2.61
Service Water Heating 24.30
Receptacle Equipment 23.53
Miscellaneous 1.61


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OCCUPANCY 6031. 8760.
INTERIORLIGHTING 2852. 8760.
INTERIORLIGHTINGHE 3070. 8760.
INTERIORLIGHTINGHE_OS 2910. 8760.
INTERIORLIGHTINGHE_VS 2149. 8760.
EXTERIORLIGHTING 4380. 4380.
REFRIGERATOR 7343. 8760.
MISCPLUGLOAD 5918. 8760.
COOKINGRANGE 2434. 8760.
DISHWASHER_FLOW_SCH 2642. 8760.
CLOTHESWASHER_FLOW_SCH 3113. 8760.
DISHWASHER_EQUIP_SCH 3134. 8760.
CLOTHESWASHER_EQUIP_SCH 3692. 8760.
CLOTHESDRYER 3911. 8760.
SHADING_2012IECC 0. 0.
SHADING_2012IECC_HERS 7007. 8760.
SINKSENSSCHEDULE 6025. 8760.
SINKLATSCHEDULE 2735. 8760.
SHOWERSENSSCHEDULE 4492. 8760.
SHOWERLATSCHEDULE 4268. 8760.
BATHSENSSCHEDULE 8760. 8760.
BATHLATSCHEDULE 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
HEATING_SCH THERMOSTAT_LIVING DUAL SP CONTROL January 72.00 365 72.00 365
COOLING_SCH THERMOSTAT_LIVING DUAL SP CONTROL July 75.00 365 75.00 365



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupiedHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 18:12:31

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupiedHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 39.361 39.361
February 0.833 0.003 652.056 28.339 28.339
March 13.111 0.168 696.939 24.161 24.161
April 75.722 1.892 491.450 13.917 21.873
May 262.375 7.474 149.344 9.856 21.588
June 454.014 15.549 13.208 15.691 19.382
July 587.528 22.264 0.000 22.264 22.940
August 514.153 16.993 7.000 17.049 17.493
September 249.792 6.690 182.117 8.218 10.235
October 60.861 1.449 585.500 11.953 13.580
November 0.000 0.000 694.417 20.252 20.436
December 0.000 0.000 744.000 36.948 36.948
           
Annual Sum or Average 2218.389 72.482 4960.031 248.009 276.337
Minimum of Months 0.000 0.000 0.000 8.218 10.235
Maximum of Months 587.528 22.264 744.000 39.361 39.361



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 23.409 23.409
February 0.000 0.000 650.972 16.700 17.425
March 0.000 0.000 696.678 14.105 16.293
April 48.500 0.454 546.969 7.581 9.311
May 236.672 3.467 230.589 5.022 6.023
June 475.528 10.216 21.250 10.290 10.313
July 613.525 15.599 0.333 15.600 15.600
August 549.322 12.268 4.583 12.285 12.285
September 265.778 4.467 148.750 5.001 5.012
October 58.444 0.828 583.500 6.317 6.515
November 0.000 0.000 691.583 11.112 11.349
December 0.000 0.000 744.000 21.518 21.518
           
Annual Sum or Average 2247.769 47.300 5063.208 148.939 155.051
Minimum of Months 0.000 0.000 0.333 5.001 5.012
Maximum of Months 613.525 15.599 744.000 23.409 23.409



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 42.446 42.446
February 0.000 0.000 659.750 30.537 31.024
March 0.000 0.000 712.909 25.616 26.187
April 84.409 1.118 512.650 13.744 15.108
May 279.903 6.049 201.333 8.842 11.172
June 497.708 15.659 16.500 15.843 17.788
July 604.211 22.023 0.167 22.024 22.731
August 533.758 16.287 3.917 16.336 16.777
September 265.689 6.228 139.167 7.673 12.422
October 62.424 1.148 575.833 12.398 14.857
November 0.000 0.000 692.694 21.810 22.175
December 0.000 0.000 744.000 39.816 39.816
           
Annual Sum or Average 2328.102 68.512 5002.921 257.085 272.502
Minimum of Months 0.000 0.000 0.167 7.673 11.172
Maximum of Months 604.211 22.023 744.000 42.446 42.446



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 43.736 43.736
February 0.000 0.000 665.028 32.552 33.386
March 0.472 0.001 710.305 27.550 29.845
April 41.833 0.811 541.405 14.636 22.143
May 237.944 5.805 235.533 8.829 13.331
June 453.044 14.014 35.764 14.256 14.929
July 590.606 19.911 5.417 19.926 19.983
August 502.347 13.818 10.333 13.885 14.107
September 198.778 3.792 205.172 5.568 7.871
October 18.083 0.213 610.215 12.087 16.875
November 0.000 0.000 696.489 22.923 24.402
December 0.000 0.000 744.000 40.527 40.527
           
Annual Sum or Average 2043.108 58.365 5203.661 256.474 281.135
Minimum of Months 0.000 0.000 5.417 5.568 7.871
Maximum of Months 590.606 19.911 744.000 43.736 43.736



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 26.111 26.111
February 0.000 0.000 671.583 19.609 19.639
March 0.000 0.000 728.523 16.899 18.214
April 8.083 0.102 606.844 8.851 11.525
May 188.131 2.285 261.617 4.088 5.557
June 474.325 8.802 18.433 8.866 8.866
July 617.122 13.360 0.000 13.360 13.360
August 538.639 9.110 4.667 9.128 9.128
September 183.972 1.708 174.108 2.392 2.538
October 0.417 0.000 641.250 6.619 8.308
November 0.000 0.000 707.767 13.015 13.036
December 0.000 0.000 744.000 23.710 23.710
           
Annual Sum or Average 2010.689 35.368 5302.792 152.648 159.992
Minimum of Months 0.000 0.000 0.000 2.392 2.538
Maximum of Months 617.122 13.360 744.000 26.111 26.111



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 45.503 45.503
February 0.000 0.000 671.917 34.015 34.025
March 0.000 0.000 743.111 28.894 28.983
April 24.319 0.213 586.894 14.480 15.258
May 252.889 4.334 223.000 7.304 9.434
June 498.147 14.257 15.583 14.430 16.411
July 605.333 19.876 0.000 19.876 20.571
August 524.044 13.219 3.917 13.267 13.782
September 229.417 3.066 155.833 4.722 9.344
October 7.167 0.021 642.111 12.661 13.846
November 0.000 0.000 707.750 23.994 24.097
December 0.000 0.000 744.000 42.130 42.130
           
Annual Sum or Average 2141.317 54.987 5238.117 261.276 273.384
Minimum of Months 0.000 0.000 0.000 4.722 9.344
Maximum of Months 605.333 19.876 744.000 45.503 45.503



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 39.995 39.995
February 13.250 0.179 620.583 27.443 27.443
March 35.167 0.752 637.525 22.567 22.567
April 132.333 4.443 422.253 13.719 16.756
May 420.069 15.289 105.167 16.434 19.643
June 566.014 24.538 7.222 24.600 24.997
July 670.194 32.361 0.000 32.361 32.361
August 636.281 25.430 3.625 25.463 25.607
September 346.944 10.768 123.833 11.810 13.115
October 99.678 2.937 513.639 11.861 12.301
November 6.583 0.041 663.528 19.652 19.652
December 0.000 0.000 744.000 38.238 38.238
           
Annual Sum or Average 2926.514 116.740 4585.375 284.145 292.677
Minimum of Months 0.000 0.000 0.000 11.810 12.301
Maximum of Months 670.194 32.361 744.000 39.995 39.995



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 16.256 16.256
February 3.250 0.007 612.611 10.751 11.141
March 14.667 0.072 627.722 8.315 9.714
April 121.889 1.997 407.500 5.049 6.286
May 437.125 9.338 79.806 9.600 9.616
June 612.153 17.241 3.417 17.249 17.249
July 695.956 22.999 0.000 22.999 22.999
August 686.842 19.019 1.167 19.019 19.019
September 402.222 8.110 64.306 8.249 8.249
October 107.431 2.155 452.694 4.741 4.976
November 9.083 0.044 642.500 6.729 6.923
December 0.000 0.000 744.000 15.201 15.201
           
Annual Sum or Average 3090.617 80.982 4379.722 144.157 147.629
Minimum of Months 0.000 0.000 0.000 4.741 4.976
Maximum of Months 695.956 22.999 744.000 22.999 22.999



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 40.224 40.224
February 1.208 0.003 614.861 27.189 29.012
March 15.671 0.143 622.868 21.549 23.669
April 159.538 3.800 378.950 12.352 16.194
May 452.161 13.866 58.278 14.678 19.610
June 599.856 24.679 2.583 24.713 25.210
July 675.681 31.373 0.000 31.373 31.373
August 642.253 24.099 0.917 24.111 24.397
September 358.192 10.162 60.167 10.868 17.727
October 101.106 2.629 450.167 11.239 19.062
November 4.194 0.020 642.222 19.561 22.602
December 0.000 0.000 744.000 38.414 38.414
           
Annual Sum or Average 3009.860 110.775 4319.012 276.271 307.495
Minimum of Months 0.000 0.000 0.000 10.868 16.194
Maximum of Months 675.681 31.373 744.000 40.224 40.224



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 38.497 38.497
February 0.000 0.000 630.778 27.094 32.908
March 6.250 0.061 642.944 21.533 30.820
April 82.667 2.141 445.045 11.252 20.664
May 393.042 12.696 112.883 13.797 17.234
June 570.042 22.828 6.167 22.876 23.074
July 674.506 29.752 0.000 29.752 29.752
August 629.728 21.623 3.333 21.652 21.832
September 296.639 6.690 135.131 7.741 10.602
October 47.750 0.616 542.245 9.488 15.349
November 0.000 0.000 674.489 19.317 23.553
December 0.000 0.000 744.000 36.116 36.116
           
Annual Sum or Average 2700.622 96.407 4681.014 259.117 300.399
Minimum of Months 0.000 0.000 0.000 7.741 10.602
Maximum of Months 674.506 29.752 744.000 38.497 38.497



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 18.961 18.961
February 0.000 0.000 669.097 13.342 13.544
March 0.000 0.000 708.222 10.463 12.548
April 45.083 0.430 491.832 4.410 6.541
May 386.750 7.004 93.153 7.314 7.585
June 616.133 15.590 2.917 15.595 15.595
July 701.203 20.478 0.000 20.478 20.478
August 681.975 15.339 1.167 15.339 15.339
September 322.083 4.094 89.578 4.284 4.366
October 29.250 0.126 541.708 3.386 4.920
November 2.083 0.005 699.231 8.188 8.228
December 0.000 0.000 744.000 17.262 17.262
           
Annual Sum or Average 2784.561 63.066 4784.904 139.021 145.365
Minimum of Months 0.000 0.000 0.000 3.386 4.366
Maximum of Months 701.203 20.478 744.000 20.478 20.478



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 43.701 43.701
February 0.000 0.000 671.750 31.358 31.377
March 0.000 0.000 735.681 25.036 25.457
April 98.542 1.329 448.528 11.203 13.943
May 423.322 11.200 65.972 12.112 16.421
June 601.989 22.990 2.417 23.022 23.453
July 678.764 28.794 0.000 28.794 28.794
August 637.669 20.437 1.083 20.453 20.710
September 321.611 6.051 83.278 6.953 13.687
October 49.139 0.362 546.250 10.496 15.738
November 0.000 0.000 699.528 22.211 22.572
December 0.000 0.000 744.000 40.954 40.954
           
Annual Sum or Average 2811.036 91.164 4742.486 276.294 296.809
Minimum of Months 0.000 0.000 0.000 6.953 13.687
Maximum of Months 678.764 28.794 744.000 43.701 43.701



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 56.752 56.752
February 2.917 0.011 647.444 39.721 39.721
March 20.167 0.384 675.139 32.530 32.971
April 109.833 3.654 448.167 17.828 25.417
May 391.292 15.317 115.694 17.308 23.389
June 533.139 25.116 10.628 25.243 26.227
July 650.489 33.334 0.000 33.334 33.334
August 586.611 25.133 4.542 25.200 25.829
September 287.389 9.315 157.931 11.676 17.313
October 78.944 2.245 550.903 16.828 19.579
November 0.000 0.000 690.583 29.465 29.715
December 0.000 0.000 744.000 54.044 54.044
           
Annual Sum or Average 2660.781 114.508 4789.031 359.927 384.290
Minimum of Months 0.000 0.000 0.000 11.676 17.313
Maximum of Months 650.489 33.334 744.000 56.752 56.752



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 25.860 25.860
February 0.000 0.000 647.194 17.656 18.412
March 1.833 0.001 676.361 13.958 16.409
April 98.361 1.572 472.467 7.617 8.741
May 404.278 9.652 128.511 10.405 10.682
June 568.458 17.962 8.667 17.994 18.003
July 674.350 24.239 0.000 24.239 24.239
August 644.958 18.872 4.250 18.887 18.887
September 328.611 6.683 158.472 7.418 7.474
October 80.292 1.574 538.347 7.180 7.477
November 2.000 0.004 686.208 11.987 12.235
December 0.000 0.000 744.000 24.125 24.125
           
Annual Sum or Average 2803.142 80.560 4808.478 187.328 192.545
Minimum of Months 0.000 0.000 0.000 7.180 7.474
Maximum of Months 674.350 24.239 744.000 25.860 25.860



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 47.319 47.319
February 0.000 0.000 655.722 33.105 33.779
March 3.583 0.017 685.494 26.474 27.485
April 123.514 2.761 437.633 14.153 16.994
May 426.603 13.440 100.889 14.877 18.644
June 577.544 24.614 4.917 24.681 25.401
July 659.189 31.804 0.000 31.804 31.804
August 602.378 23.417 3.083 23.460 23.810
September 302.514 8.544 146.917 10.443 15.284
October 83.146 1.912 533.222 14.036 19.085
November 0.000 0.000 688.333 24.588 25.318
December 0.000 0.000 744.000 45.036 45.036
           
Annual Sum or Average 2778.471 106.509 4744.211 309.976 329.959
Minimum of Months 0.000 0.000 0.000 10.443 15.284
Maximum of Months 659.189 31.804 744.000 47.319 47.319



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 55.220 55.220
February 0.000 0.000 661.694 40.115 41.807
March 2.917 0.021 687.161 32.355 37.054
April 74.139 2.065 478.051 16.525 26.126
May 372.847 13.546 146.675 15.612 19.979
June 536.958 24.000 11.028 24.115 24.745
July 656.183 31.550 0.000 31.550 31.550
August 581.278 22.210 9.083 22.289 22.618
September 239.000 6.070 206.569 8.687 12.086
October 36.583 0.473 587.674 15.204 21.558
November 0.000 0.000 694.597 29.421 31.452
December 0.000 0.000 744.000 51.912 51.912
           
Annual Sum or Average 2499.906 99.937 4970.533 343.006 376.109
Minimum of Months 0.000 0.000 0.000 8.687 12.086
Maximum of Months 656.183 31.550 744.000 55.220 55.220



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 28.627 28.627
February 0.000 0.000 671.833 20.528 20.545
March 0.000 0.000 717.800 16.415 18.918
April 43.167 0.507 529.496 7.812 10.536
May 369.736 8.085 146.239 8.953 9.422
June 573.681 16.897 5.333 16.922 16.922
July 680.853 22.530 0.000 22.530 22.530
August 639.164 16.025 4.528 16.041 16.041
September 254.250 3.610 190.264 4.543 4.705
October 17.639 0.084 606.250 6.814 8.780
November 0.000 0.000 705.667 13.812 13.829
December 0.000 0.000 744.000 26.257 26.257
           
Annual Sum or Average 2578.489 67.739 5065.410 189.253 197.111
Minimum of Months 0.000 0.000 0.000 4.543 4.705
Maximum of Months 680.853 22.530 744.000 28.627 28.627



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 50.670 50.670
February 0.000 0.000 672.000 37.002 37.002
March 0.000 0.000 743.217 29.971 30.069
April 81.319 1.183 502.575 14.007 16.209
May 404.081 11.636 108.500 13.173 16.847
June 582.103 23.576 3.917 23.632 24.450
July 661.167 30.143 0.000 30.143 30.143
August 599.961 20.680 3.083 20.724 21.088
September 269.736 5.187 166.900 7.374 11.677
October 36.111 0.228 606.889 14.046 16.984
November 0.000 0.000 705.750 27.154 27.359
December 0.000 0.000 744.000 47.599 47.599
           
Annual Sum or Average 2634.478 92.633 5000.831 315.495 330.098
Minimum of Months 0.000 0.000 0.000 7.374 11.677
Maximum of Months 661.167 30.143 744.000 50.670 50.670



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8410.28 0.00 0.00
February 6596.66 0.00 0.00
March 4790.33 0.00 0.00
April 2169.30 0.00 0.00
May 373.82 0.00 0.00
June 22.94 0.00 0.00
July 0.00 0.00 0.00
August 8.52 0.00 0.00
September 234.28 0.00 0.00
October 1718.62 0.00 0.00
November 3928.35 0.00 0.00
December 7831.06 0.00 0.00
       
Annual Sum or Average 2993.05 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 8410.28 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 6782.62 0.00 0.00
February 5349.38 0.00 0.00
March 3914.08 0.00 0.00
April 1782.44 0.00 0.00
May 334.12 0.00 0.00
June 16.50 0.00 0.00
July 0.06 0.00 0.00
August 3.60 0.00 0.00
September 115.03 0.00 0.00
October 1254.22 0.00 0.00
November 3018.58 0.00 0.00
December 6255.27 0.00 0.00
       
Annual Sum or Average 2390.74 0.00 0.00
Minimum of Months 0.06 0.00 0.00
Maximum of Months 6782.62 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8389.86 0.00 0.00
February 6568.69 0.00 0.00
March 4726.45 0.00 0.00
April 2102.38 0.00 0.00
May 399.41 0.00 0.00
June 26.72 0.00 0.00
July 0.14 0.00 0.00
August 7.04 0.00 0.00
September 206.64 0.00 0.00
October 1704.82 0.00 0.00
November 3917.78 0.00 0.00
December 7808.96 0.00 0.00
       
Annual Sum or Average 2974.43 0.00 0.00
Minimum of Months 0.14 0.00 0.00
Maximum of Months 8389.86 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 9006.89 0.00 0.00
February 7258.63 0.00 0.00
March 5278.74 0.00 0.00
April 2380.24 0.00 0.00
May 447.09 0.00 0.00
June 36.04 0.00 0.00
July 2.18 0.00 0.00
August 9.73 0.00 0.00
September 261.08 0.00 0.00
October 1861.39 0.00 0.00
November 4266.18 0.00 0.00
December 8281.54 0.00 0.00
       
Annual Sum or Average 3241.27 0.00 0.00
Minimum of Months 2.18 0.00 0.00
Maximum of Months 9006.89 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 7390.10 0.00 0.00
February 6057.11 0.00 0.00
March 4496.00 0.00 0.00
April 2078.32 0.00 0.00
May 370.76 0.00 0.00
June 13.83 0.00 0.00
July 0.00 0.00 0.00
August 3.63 0.00 0.00
September 141.35 0.00 0.00
October 1443.20 0.00 0.00
November 3381.66 0.00 0.00
December 6711.18 0.00 0.00
       
Annual Sum or Average 2660.04 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 7390.10 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8996.61 0.00 0.00
February 7261.76 0.00 0.00
March 5286.66 0.00 0.00
April 2351.76 0.00 0.00
May 422.70 0.00 0.00
June 25.18 0.00 0.00
July 0.00 0.00 0.00
August 6.78 0.00 0.00
September 235.59 0.00 0.00
October 1897.81 0.00 0.00
November 4282.22 0.00 0.00
December 8267.51 0.00 0.00
       
Annual Sum or Average 3236.69 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 8996.61 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 6722.97 0.00 0.00
February 5020.44 0.00 0.00
March 3458.35 0.00 0.00
April 1338.56 0.00 0.00
May 145.90 0.00 0.00
June 8.15 0.00 0.00
July 0.00 0.00 0.00
August 3.99 0.00 0.00
September 127.23 0.00 0.00
October 1169.29 0.00 0.00
November 3022.12 0.00 0.00
December 6375.77 0.00 0.00
       
Annual Sum or Average 2272.93 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 6722.97 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5007.53 0.00 0.00
February 3715.53 0.00 0.00
March 2540.63 0.00 0.00
April 900.78 0.00 0.00
May 71.22 0.00 0.00
June 2.21 0.00 0.00
July 0.00 0.00 0.00
August 0.18 0.00 0.00
September 36.04 0.00 0.00
October 706.34 0.00 0.00
November 2059.81 0.00 0.00
December 4702.88 0.00 0.00
       
Annual Sum or Average 1638.06 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 5007.53 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 6714.46 0.00 0.00
February 4972.54 0.00 0.00
March 3373.89 0.00 0.00
April 1231.37 0.00 0.00
May 105.05 0.00 0.00
June 4.58 0.00 0.00
July 0.00 0.00 0.00
August 1.37 0.00 0.00
September 86.51 0.00 0.00
October 1124.06 0.00 0.00
November 2996.59 0.00 0.00
December 6362.68 0.00 0.00
       
Annual Sum or Average 2238.16 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 6714.46 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 7431.87 0.00 0.00
February 5703.37 0.00 0.00
March 3896.78 0.00 0.00
April 1494.98 0.00 0.00
May 159.52 0.00 0.00
June 7.31 0.00 0.00
July 0.00 0.00 0.00
August 3.97 0.00 0.00
September 146.33 0.00 0.00
October 1321.91 0.00 0.00
November 3394.21 0.00 0.00
December 6918.61 0.00 0.00
       
Annual Sum or Average 2527.92 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 7431.87 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5692.51 0.00 0.00
February 4483.52 0.00 0.00
March 3149.58 0.00 0.00
April 1155.15 0.00 0.00
May 84.61 0.00 0.00
June 1.50 0.00 0.00
July 0.00 0.00 0.00
August 0.20 0.00 0.00
September 50.58 0.00 0.00
October 881.12 0.00 0.00
November 2467.62 0.00 0.00
December 5222.43 0.00 0.00
       
Annual Sum or Average 1922.54 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 5692.51 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 7403.26 0.00 0.00
February 5756.91 0.00 0.00
March 3964.08 0.00 0.00
April 1436.10 0.00 0.00
May 119.60 0.00 0.00
June 4.22 0.00 0.00
July 0.00 0.00 0.00
August 1.93 0.00 0.00
September 112.19 0.00 0.00
October 1327.47 0.00 0.00
November 3421.83 0.00 0.00
December 6886.89 0.00 0.00
       
Annual Sum or Average 2523.90 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 7403.26 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 9268.50 0.00 0.00
February 7080.75 0.00 0.00
March 4932.56 0.00 0.00
April 1976.84 0.00 0.00
May 242.68 0.00 0.00
June 15.86 0.00 0.00
July 0.00 0.00 0.00
August 7.86 0.00 0.00
September 276.84 0.00 0.00
October 1838.77 0.00 0.00
November 4384.15 0.00 0.00
December 8755.87 0.00 0.00
       
Annual Sum or Average 3217.27 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 9268.50 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 7529.23 0.00 0.00
February 5757.68 0.00 0.00
March 4016.38 0.00 0.00
April 1596.98 0.00 0.00
May 173.94 0.00 0.00
June 7.76 0.00 0.00
July 0.00 0.00 0.00
August 3.34 0.00 0.00
September 162.28 0.00 0.00
October 1342.94 0.00 0.00
November 3389.85 0.00 0.00
December 7063.27 0.00 0.00
       
Annual Sum or Average 2575.13 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 7529.23 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 9302.59 0.00 0.00
February 7096.90 0.00 0.00
March 4884.38 0.00 0.00
April 1914.82 0.00 0.00
May 213.42 0.00 0.00
June 10.37 0.00 0.00
July 0.00 0.00 0.00
August 6.20 0.00 0.00
September 267.71 0.00 0.00
October 1835.91 0.00 0.00
November 4400.09 0.00 0.00
December 8784.08 0.00 0.00
       
Annual Sum or Average 3211.86 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 9302.59 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 9947.21 0.00 0.00
February 7835.10 0.00 0.00
March 5447.80 0.00 0.00
April 2205.99 0.00 0.00
May 275.29 0.00 0.00
June 15.95 0.00 0.00
July 0.00 0.00 0.00
August 10.01 0.00 0.00
September 335.35 0.00 0.00
October 2030.68 0.00 0.00
November 4797.47 0.00 0.00
December 9278.66 0.00 0.00
       
Annual Sum or Average 3497.82 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 9947.21 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8205.59 0.00 0.00
February 6553.06 0.00 0.00
March 4629.01 0.00 0.00
April 1879.76 0.00 0.00
May 196.28 0.00 0.00
June 5.88 0.00 0.00
July 0.00 0.00 0.00
August 3.45 0.00 0.00
September 202.20 0.00 0.00
October 1573.00 0.00 0.00
November 3826.39 0.00 0.00
December 7578.89 0.00 0.00
       
Annual Sum or Average 2873.11 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 8205.59 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 9963.07 0.00 0.00
February 7865.66 0.00 0.00
March 5482.70 0.00 0.00
April 2141.94 0.00 0.00
May 227.93 0.00 0.00
June 8.78 0.00 0.00
July 0.00 0.00 0.00
August 6.23 0.00 0.00
September 307.49 0.00 0.00
October 2073.32 0.00 0.00
November 4824.21 0.00 0.00
December 9288.17 0.00 0.00
       
Annual Sum or Average 3498.62 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 9963.07 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.08
June 0.00 0.00 0.17
July 0.00 0.00 0.24
August 0.00 0.00 0.19
September 0.00 0.00 0.07
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.24



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.04
June 0.00 0.00 0.12
July 0.00 0.00 0.17
August 0.00 0.00 0.14
September 0.00 0.00 0.05
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.17



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.06
June 0.00 0.00 0.18
July 0.00 0.00 0.24
August 0.00 0.00 0.18
September 0.00 0.00 0.07
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.24



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.06
June 0.00 0.00 0.16
July 0.00 0.00 0.22
August 0.00 0.00 0.15
September 0.00 0.00 0.04
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.02
June 0.00 0.00 0.10
July 0.00 0.00 0.15
August 0.00 0.00 0.10
September 0.00 0.00 0.02
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.15



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.04
June 0.00 0.00 0.16
July 0.00 0.00 0.22
August 0.00 0.00 0.15
September 0.00 0.00 0.03
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.05
May 0.00 0.00 0.15
June 0.00 0.00 0.26
July 0.00 0.00 0.33
August 0.00 0.00 0.26
September 0.00 0.00 0.11
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.10
June 0.00 0.00 0.20
July 0.00 0.00 0.26
August 0.00 0.00 0.22
September 0.00 0.00 0.09
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.26



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.14
June 0.00 0.00 0.27
July 0.00 0.00 0.34
August 0.00 0.00 0.26
September 0.00 0.00 0.11
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.13
June 0.00 0.00 0.24
July 0.00 0.00 0.31
August 0.00 0.00 0.22
September 0.00 0.00 0.07
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.31



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.08
June 0.00 0.00 0.18
July 0.00 0.00 0.23
August 0.00 0.00 0.17
September 0.00 0.00 0.05
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.23



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.12
June 0.00 0.00 0.25
July 0.00 0.00 0.31
August 0.00 0.00 0.22
September 0.00 0.00 0.07
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.31



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.15
June 0.00 0.00 0.27
July 0.00 0.00 0.34
August 0.00 0.00 0.26
September 0.00 0.00 0.10
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.10
June 0.00 0.00 0.20
July 0.00 0.00 0.27
August 0.00 0.00 0.21
September 0.00 0.00 0.08
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.27



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.14
June 0.00 0.00 0.28
July 0.00 0.00 0.35
August 0.00 0.00 0.26
September 0.00 0.00 0.09
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.35



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.13
June 0.00 0.00 0.25
July 0.00 0.00 0.33
August 0.00 0.00 0.23
September 0.00 0.00 0.06
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.09
June 0.00 0.00 0.19
July 0.00 0.00 0.25
August 0.00 0.00 0.18
September 0.00 0.00 0.04
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.25



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.12
June 0.00 0.00 0.26
July 0.00 0.00 0.33
August 0.00 0.00 0.23
September 0.00 0.00 0.06
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.03 1286.57
February 0.00 0.00 1767.12 1188.34
March 0.00 0.00 1758.53 1309.27
April 0.00 0.00 1707.07 1229.97
May 0.00 0.00 1608.83 1197.82
June 0.00 0.00 1507.77 1086.36
July 0.00 0.00 1428.59 1063.63
August 0.00 0.00 1385.23 1031.34
September 0.00 0.00 1402.77 1010.71
October 0.00 0.00 1465.58 1091.16
November 0.00 0.00 1555.27 1120.59
December 0.00 0.00 1650.86 1229.11
         
Annual Sum or Average 0.00 0.00 1579.34 13844.87
Minimum of Months 0.00 0.00 1385.23 1010.71
Maximum of Months 0.00 0.00 1767.12 1309.27



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.03 1286.56
February 0.00 0.00 1767.16 1188.37
March 0.00 0.00 1758.57 1309.30
April 0.00 0.00 1707.24 1230.08
May 0.00 0.00 1610.95 1199.39
June 0.00 0.00 1505.56 1084.77
July 0.00 0.00 1428.97 1063.91
August 0.00 0.00 1383.05 1029.72
September 0.00 0.00 1400.59 1009.14
October 0.00 0.00 1465.53 1091.13
November 0.00 0.00 1555.30 1120.61
December 0.00 0.00 1650.80 1229.07
         
Annual Sum or Average 0.00 0.00 1579.02 13842.06
Minimum of Months 0.00 0.00 1383.05 1009.14
Maximum of Months 0.00 0.00 1767.16 1309.30



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.03 1286.57
February 0.00 0.00 1767.06 1188.31
March 0.00 0.00 1758.48 1309.24
April 0.00 0.00 1706.86 1229.81
May 0.00 0.00 1608.76 1197.77
June 0.00 0.00 1505.48 1084.71
July 0.00 0.00 1428.81 1063.79
August 0.00 0.00 1385.09 1031.24
September 0.00 0.00 1400.68 1009.21
October 0.00 0.00 1467.19 1092.37
November 0.00 0.00 1552.65 1118.70
December 0.00 0.00 1652.77 1230.53
         
Annual Sum or Average 0.00 0.00 1579.04 13842.24
Minimum of Months 0.00 0.00 1385.09 1009.21
Maximum of Months 0.00 0.00 1767.06 1309.24



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.03 1286.57
February 0.00 0.00 1767.01 1188.27
March 0.00 0.00 1760.68 1310.88
April 0.00 0.00 1709.81 1231.93
May 0.00 0.00 1611.18 1199.57
June 0.00 0.00 1505.68 1084.86
July 0.00 0.00 1428.70 1063.71
August 0.00 0.00 1385.18 1031.30
September 0.00 0.00 1405.27 1012.51
October 0.00 0.00 1467.56 1092.64
November 0.00 0.00 1555.35 1120.65
December 0.00 0.00 1650.79 1229.06
         
Annual Sum or Average 0.00 0.00 1580.15 13851.94
Minimum of Months 0.00 0.00 1385.18 1012.51
Maximum of Months 0.00 0.00 1767.01 1310.88



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.03 1286.56
February 0.00 0.00 1767.06 1188.31
March 0.00 0.00 1758.59 1309.32
April 0.00 0.00 1711.83 1233.39
May 0.00 0.00 1611.13 1199.53
June 0.00 0.00 1505.45 1084.69
July 0.00 0.00 1428.73 1063.73
August 0.00 0.00 1383.06 1029.72
September 0.00 0.00 1402.95 1010.84
October 0.00 0.00 1467.62 1092.69
November 0.00 0.00 1555.19 1120.53
December 0.00 0.00 1650.82 1229.08
         
Annual Sum or Average 0.00 0.00 1579.75 13848.40
Minimum of Months 0.00 0.00 1383.06 1010.84
Maximum of Months 0.00 0.00 1767.06 1309.32



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.03 1286.57
February 0.00 0.00 1767.06 1188.30
March 0.00 0.00 1758.58 1309.32
April 0.00 0.00 1709.10 1231.43
May 0.00 0.00 1609.14 1198.05
June 0.00 0.00 1505.56 1084.78
July 0.00 0.00 1428.49 1063.55
August 0.00 0.00 1385.19 1031.31
September 0.00 0.00 1402.92 1010.82
October 0.00 0.00 1467.37 1092.49
November 0.00 0.00 1555.27 1120.59
December 0.00 0.00 1650.97 1229.19
         
Annual Sum or Average 0.00 0.00 1579.52 13846.40
Minimum of Months 0.00 0.00 1385.19 1010.82
Maximum of Months 0.00 0.00 1767.06 1309.32



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.03 1286.57
February 0.00 0.00 1764.70 1186.72
March 0.00 0.00 1758.45 1309.22
April 0.00 0.00 1702.66 1226.79
May 0.00 0.00 1604.51 1194.60
June 0.00 0.00 1505.30 1084.59
July 0.00 0.00 1426.36 1061.96
August 0.00 0.00 1382.90 1029.61
September 0.00 0.00 1398.57 1007.68
October 0.00 0.00 1465.28 1090.94
November 0.00 0.00 1553.04 1118.98
December 0.00 0.00 1650.75 1229.03
         
Annual Sum or Average 0.00 0.00 1577.27 13826.68
Minimum of Months 0.00 0.00 1382.90 1007.68
Maximum of Months 0.00 0.00 1764.70 1309.22



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.02 1286.56
February 0.00 0.00 1764.78 1186.77
March 0.00 0.00 1758.62 1309.34
April 0.00 0.00 1704.41 1228.04
May 0.00 0.00 1602.11 1192.81
June 0.00 0.00 1503.22 1083.09
July 0.00 0.00 1426.58 1062.13
August 0.00 0.00 1382.71 1029.47
September 0.00 0.00 1396.12 1005.92
October 0.00 0.00 1463.12 1089.33
November 0.00 0.00 1552.72 1118.75
December 0.00 0.00 1652.92 1230.65
         
Annual Sum or Average 0.00 0.00 1576.83 13822.87
Minimum of Months 0.00 0.00 1382.71 1005.92
Maximum of Months 0.00 0.00 1764.78 1309.34



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.03 1286.57
February 0.00 0.00 1767.17 1188.38
March 0.00 0.00 1756.36 1307.66
April 0.00 0.00 1702.19 1226.45
May 0.00 0.00 1603.98 1194.21
June 0.00 0.00 1503.16 1083.04
July 0.00 0.00 1426.56 1062.11
August 0.00 0.00 1383.00 1029.68
September 0.00 0.00 1400.43 1009.02
October 0.00 0.00 1462.99 1089.24
November 0.00 0.00 1552.86 1118.85
December 0.00 0.00 1652.96 1230.67
         
Annual Sum or Average 0.00 0.00 1577.18 13825.89
Minimum of Months 0.00 0.00 1383.00 1009.02
Maximum of Months 0.00 0.00 1767.17 1307.66



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.03 1286.57
February 0.00 0.00 1767.22 1188.41
March 0.00 0.00 1760.95 1311.07
April 0.00 0.00 1707.08 1229.97
May 0.00 0.00 1604.80 1194.81
June 0.00 0.00 1505.08 1084.42
July 0.00 0.00 1426.38 1061.98
August 0.00 0.00 1382.89 1029.60
September 0.00 0.00 1400.65 1009.19
October 0.00 0.00 1467.48 1092.58
November 0.00 0.00 1552.92 1118.89
December 0.00 0.00 1652.95 1230.67
         
Annual Sum or Average 0.00 0.00 1578.58 13838.17
Minimum of Months 0.00 0.00 1382.89 1009.19
Maximum of Months 0.00 0.00 1767.22 1311.07



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.02 1286.56
February 0.00 0.00 1767.07 1188.31
March 0.00 0.00 1758.63 1309.35
April 0.00 0.00 1707.17 1230.04
May 0.00 0.00 1604.64 1194.70
June 0.00 0.00 1503.26 1083.12
July 0.00 0.00 1426.52 1062.09
August 0.00 0.00 1382.64 1029.42
September 0.00 0.00 1398.48 1007.62
October 0.00 0.00 1467.74 1092.77
November 0.00 0.00 1553.02 1118.96
December 0.00 0.00 1650.77 1229.04
         
Annual Sum or Average 0.00 0.00 1577.87 13831.97
Minimum of Months 0.00 0.00 1382.64 1007.62
Maximum of Months 0.00 0.00 1767.07 1309.35



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.03 1286.56
February 0.00 0.00 1767.06 1188.31
March 0.00 0.00 1758.58 1309.31
April 0.00 0.00 1705.24 1228.64
May 0.00 0.00 1603.75 1194.04
June 0.00 0.00 1503.16 1083.04
July 0.00 0.00 1427.34 1062.70
August 0.00 0.00 1382.56 1029.35
September 0.00 0.00 1400.39 1009.00
October 0.00 0.00 1467.70 1092.74
November 0.00 0.00 1553.04 1118.98
December 0.00 0.00 1650.83 1229.09
         
Annual Sum or Average 0.00 0.00 1577.85 13831.77
Minimum of Months 0.00 0.00 1382.56 1009.00
Maximum of Months 0.00 0.00 1767.06 1309.31



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.03 1286.57
February 0.00 0.00 1767.12 1188.35
March 0.00 0.00 1756.46 1307.73
April 0.00 0.00 1706.90 1229.84
May 0.00 0.00 1604.69 1194.74
June 0.00 0.00 1505.34 1084.61
July 0.00 0.00 1428.88 1063.84
August 0.00 0.00 1383.08 1029.74
September 0.00 0.00 1400.74 1009.25
October 0.00 0.00 1467.24 1092.40
November 0.00 0.00 1552.97 1118.93
December 0.00 0.00 1650.77 1229.05
         
Annual Sum or Average 0.00 0.00 1578.22 13835.05
Minimum of Months 0.00 0.00 1383.08 1009.25
Maximum of Months 0.00 0.00 1767.12 1307.73



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.02 1286.56
February 0.00 0.00 1767.18 1188.39
March 0.00 0.00 1758.45 1309.22
April 0.00 0.00 1704.68 1228.24
May 0.00 0.00 1604.61 1194.68
June 0.00 0.00 1505.18 1084.50
July 0.00 0.00 1426.35 1061.96
August 0.00 0.00 1382.94 1029.64
September 0.00 0.00 1398.72 1007.79
October 0.00 0.00 1465.24 1090.91
November 0.00 0.00 1554.06 1119.72
December 0.00 0.00 1651.85 1229.85
         
Annual Sum or Average 0.00 0.00 1577.81 13831.45
Minimum of Months 0.00 0.00 1382.94 1007.79
Maximum of Months 0.00 0.00 1767.18 1309.22



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.03 1286.57
February 0.00 0.00 1767.12 1188.34
March 0.00 0.00 1758.49 1309.24
April 0.00 0.00 1704.55 1228.15
May 0.00 0.00 1603.91 1194.16
June 0.00 0.00 1503.29 1083.14
July 0.00 0.00 1428.94 1063.89
August 0.00 0.00 1382.97 1029.66
September 0.00 0.00 1400.53 1009.10
October 0.00 0.00 1465.34 1090.99
November 0.00 0.00 1552.88 1118.86
December 0.00 0.00 1652.94 1230.66
         
Annual Sum or Average 0.00 0.00 1577.96 13832.75
Minimum of Months 0.00 0.00 1382.97 1009.10
Maximum of Months 0.00 0.00 1767.12 1309.24



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.03 1286.57
February 0.00 0.00 1767.01 1188.27
March 0.00 0.00 1760.59 1310.81
April 0.00 0.00 1707.26 1230.10
May 0.00 0.00 1606.34 1195.96
June 0.00 0.00 1505.36 1084.63
July 0.00 0.00 1426.59 1062.14
August 0.00 0.00 1385.12 1031.26
September 0.00 0.00 1402.97 1010.85
October 0.00 0.00 1467.80 1092.82
November 0.00 0.00 1552.98 1118.94
December 0.00 0.00 1650.53 1228.86
         
Annual Sum or Average 0.00 0.00 1578.93 13841.21
Minimum of Months 0.00 0.00 1385.12 1010.85
Maximum of Months 0.00 0.00 1767.01 1310.81



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.02 1286.56
February 0.00 0.00 1767.07 1188.32
March 0.00 0.00 1758.58 1309.31
April 0.00 0.00 1709.32 1231.58
May 0.00 0.00 1604.40 1194.52
June 0.00 0.00 1505.36 1084.63
July 0.00 0.00 1426.76 1062.26
August 0.00 0.00 1380.84 1028.08
September 0.00 0.00 1402.98 1010.86
October 0.00 0.00 1467.71 1092.75
November 0.00 0.00 1552.57 1118.64
December 0.00 0.00 1652.91 1230.64
         
Annual Sum or Average 0.00 0.00 1578.58 13838.15
Minimum of Months 0.00 0.00 1380.84 1010.86
Maximum of Months 0.00 0.00 1767.07 1309.31



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1728.03 1286.57
February 0.00 0.00 1767.06 1188.30
March 0.00 0.00 1758.58 1309.31
April 0.00 0.00 1706.93 1229.86
May 0.00 0.00 1604.16 1194.34
June 0.00 0.00 1505.21 1084.52
July 0.00 0.00 1426.44 1062.02
August 0.00 0.00 1383.11 1029.76
September 0.00 0.00 1402.94 1010.83
October 0.00 0.00 1467.75 1092.78
November 0.00 0.00 1553.04 1118.98
December 0.00 0.00 1650.54 1228.87
         
Annual Sum or Average 0.00 0.00 1578.35 13836.15
Minimum of Months 0.00 0.00 1383.11 1010.83
Maximum of Months 0.00 0.00 1767.06 1309.31



Table of Contents

Report: HEATING AND COOLING LOADS

For: BREEZEWAY

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 6396.09
February 0.02 4532.85
March 1.28 3648.45
April 13.53 1631.69
May 49.43 327.70
June 92.67 29.78
July 129.14 2.33
August 101.02 8.08
September 44.05 181.01
October 10.00 1321.14
November 0.00 2900.24
December 0.00 5956.59
     
Annual Sum or Average 441.14 26935.95
Minimum of Months 0.00 2.33
Maximum of Months 129.14 6396.09



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 5129.77
February 0.00 3656.91
March 0.00 2970.03
April 2.98 1314.66
May 21.22 257.61
June 57.31 12.22
July 85.82 0.04
August 69.76 2.73
September 28.33 84.74
October 5.57 953.22
November 0.00 2213.70
December 0.00 4730.69
     
Annual Sum or Average 271.00 21326.33
Minimum of Months 0.00 0.04
Maximum of Months 85.82 5129.77



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 6391.42
February 0.00 4523.29
March 0.00 3608.51
April 7.77 1562.71
May 38.93 315.10
June 94.08 26.65
July 128.86 2.54
August 97.01 6.94
September 40.97 170.47
October 7.82 1316.35
November 0.00 2898.55
December 0.00 5949.93
     
Annual Sum or Average 415.45 26772.46
Minimum of Months 0.00 2.54
Maximum of Months 128.86 6391.42



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 6855.22
February 0.00 4995.30
March 0.01 4031.99
April 5.55 1787.82
May 37.67 358.64
June 82.53 29.11
July 113.62 1.87
August 79.84 8.24
September 23.80 202.26
October 1.36 1443.15
November 0.00 3157.11
December 0.00 6304.21
     
Annual Sum or Average 344.37 29174.91
Minimum of Months 0.00 1.87
Maximum of Months 113.62 6855.22



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 5591.29
February 0.00 4140.34
March 0.00 3409.76
April 0.58 1536.78
May 13.30 287.27
June 47.71 10.18
July 70.72 0.00
August 48.88 2.76
September 9.65 104.68
October 0.00 1102.98
November 0.00 2481.04
December 0.00 5077.61
     
Annual Sum or Average 190.84 23744.70
Minimum of Months 0.00 0.00
Maximum of Months 70.72 5591.29



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 6853.60
February 0.00 4999.54
March 0.00 4035.07
April 1.32 1745.93
May 26.64 332.32
June 83.69 25.61
July 113.16 2.39
August 75.24 7.00
September 18.60 191.60
October 0.13 1460.31
November 0.00 3167.67
December 0.00 6299.24
     
Annual Sum or Average 318.77 29120.28
Minimum of Months 0.00 2.39
Maximum of Months 113.16 6853.60



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 5142.00
February 1.31 3469.21
March 5.59 2649.32
April 31.41 1006.45
May 99.93 123.48
June 146.10 7.45
July 187.74 0.00
August 149.60 3.58
September 68.68 99.70
October 19.90 902.54
November 0.28 2244.43
December 0.00 4877.50
     
Annual Sum or Average 710.53 20525.66
Minimum of Months 0.00 0.00
Maximum of Months 187.74 5142.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 3783.75
February 0.05 2536.66
March 0.54 1924.65
April 14.51 663.70
May 62.37 53.97
June 105.73 1.62
July 137.94 0.00
August 116.06 0.14
September 53.38 26.44
October 15.31 535.54
November 0.29 1507.63
December 0.00 3553.32
     
Annual Sum or Average 506.18 14587.41
Minimum of Months 0.00 0.00
Maximum of Months 137.94 3783.75



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 5136.44
February 0.02 3443.23
March 1.06 2592.62
April 27.36 930.10
May 92.66 98.24
June 153.30 5.15
July 189.60 0.00
August 146.61 2.08
September 66.77 88.60
October 18.22 893.65
November 0.15 2236.52
December 0.00 4868.35
     
Annual Sum or Average 695.75 20294.98
Minimum of Months 0.00 0.00
Maximum of Months 189.60 5136.44



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 5664.68
February 0.00 3947.91
March 0.43 3006.04
April 14.63 1140.76
May 81.54 134.40
June 134.48 6.10
July 170.00 0.00
August 123.83 3.68
September 40.64 118.95
October 3.86 1034.97
November 0.00 2526.24
December 0.00 5274.41
     
Annual Sum or Average 569.42 22858.14
Minimum of Months 0.00 0.00
Maximum of Months 170.00 5664.68



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 4302.97
February 0.00 3061.39
March 0.00 2387.97
April 2.84 853.28
May 45.32 64.98
June 94.21 1.10
July 120.23 0.00
August 89.87 0.15
September 24.70 37.37
October 0.79 672.41
November 0.03 1806.04
December 0.00 3947.18
     
Annual Sum or Average 377.98 17134.86
Minimum of Months 0.00 0.00
Maximum of Months 120.23 4302.97



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 5661.15
February 0.00 3978.53
March 0.00 3038.34
April 9.00 1078.09
May 72.99 107.24
June 141.39 4.66
July 171.46 0.00
August 120.39 2.41
September 37.26 107.38
October 2.25 1041.24
November 0.00 2542.57
December 0.00 5267.31
     
Annual Sum or Average 554.74 22828.93
Minimum of Months 0.00 0.00
Maximum of Months 171.46 5661.15



Table of Contents

Report: HEATING AND COOLING LOADS

For: ATTIC

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 7590.79
February 0.00 5415.81
March 0.00 4184.74
April 8.04 1594.84
May 76.57 188.04
June 145.46 9.36
July 180.28 0.00
August 122.48 6.07
September 32.03 244.24
October 1.42 1601.16
November 0.00 3569.34
December 0.00 7077.82
     
Annual Sum or Average 566.28 31482.22
Minimum of Months 0.00 0.00
Maximum of Months 180.28 7590.79



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 7087.61
February 0.00 4887.90
March 0.12 3730.55
April 19.71 1428.70
May 90.24 177.23
June 153.62 10.25
July 193.13 0.00
August 142.79 5.99
September 56.04 216.49
October 13.14 1426.01
November 0.00 3256.85
December 0.00 6693.76
     
Annual Sum or Average 668.79 28921.33
Minimum of Months 0.00 0.00
Maximum of Months 193.13 7087.61



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 7094.43
February 0.08 4897.22
March 2.81 3783.79
April 25.42 1498.46
May 99.53 208.63
June 148.69 15.29
July 192.01 0.00
August 146.59 8.26
September 58.92 227.02
October 14.99 1428.31
November 0.00 3260.31
December 0.00 6703.51
     
Annual Sum or Average 689.04 29125.23
Minimum of Months 0.00 0.00
Maximum of Months 192.01 7094.43



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 6207.04
February 0.00 4476.94
March 0.00 3511.30
April 3.35 1388.88
May 52.20 150.71
June 100.50 4.32
July 130.07 0.00
August 92.49 2.62
September 21.56 149.43
October 0.52 1200.94
November 0.00 2804.18
December 0.00 5732.34
     
Annual Sum or Average 400.69 25628.69
Minimum of Months 0.00 0.00
Maximum of Months 130.07 6207.04



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 5694.02
February 0.00 3934.81
March 0.01 3046.45
April 11.11 1175.23
May 63.69 133.03
June 108.37 5.73
July 142.64 0.00
August 112.61 2.54
September 42.97 119.62
October 10.85 1020.01
November 0.02 2484.20
December 0.00 5341.17
     
Annual Sum or Average 492.28 22956.82
Minimum of Months 0.00 0.00
Maximum of Months 142.64 5694.02



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:12:31

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 7594.52
February 0.00 5411.73
March 0.15 4182.60
April 13.96 1671.55
May 86.82 227.06
June 140.72 14.05
July 179.35 0.00
August 126.65 8.85
September 36.76 262.46
October 2.95 1584.31
November 0.00 3564.01
December 0.00 7085.46
     
Annual Sum or Average 587.37 31606.62
Minimum of Months 0.00 0.00